CaptiveAire PXR5 Installation Manual

C1 C2 AL1 AL2 AL3
PV
°C
Micro-contr oller X
PXR
SV
SEL
Model: PXR4/5/9
Operation Manual

Table of Contents

1. Part Names and Functions ........................................................ 6
2. Operations ................................................................................. 7
2-1 Parameter list ..................................................................................... 7
2-2 Basic operations............................................................................... 12
2-3 Parameter functions and method of settings....................................14
Manual mode setting ................................................................................................. 15
Standby setting .......................................................................................................... 16
Local/remote operation setting .................................................................................. 17
Ramp-soak control..................................................................................................... 18
Canceling the alarm latch .......................................................................................... 19
Auto-tuning function................................................................................................... 20
Displaying ON-delay alarm or the remaining time of timers ...................................... 21
Setting alarm 1, 2 and 3 ............................................................................................ 22
Upper limit of alarm 1, 2 and 3 .................................................................................. 22
Lower limit of alarm 1, 2 and 3................................................................................... 22
Key lock ..................................................................................................................... 23
Proportional band ...................................................................................................... 24
Integral time ............................................................................................................... 25
Derivative time ........................................................................................................... 26
Hysteresis range for ON/OFF control ........................................................................ 27
Cooling-side proportional band coefficient ................................................................ 28
Cooling-side proportional band shift (Dead band/Overlap band) .............................. 29
Output offset value..................................................................................................... 30
Anti-reset windup ....................................................................................................... 30
Control algorithm ....................................................................................................... 31
PV (Measured value) stable range ............................................................................ 35
HYS (Hysteresis) mode at ON/OFF control............................................................... 36
Cycle time of control output 1 .................................................................................... 37
Cycle time of control output 2 (Cooling-side)............................................................. 38
Input signal code........................................................................................................ 39
Setting the measuring range (Input range) ................................................................ 40
Selection °C / °F ........................................................................................................ 40
Decimal point position................................................................................................ 42
PV (Measured value) offset ....................................................................................... 43
SV (Setting value) offset ............................................................................................ 44
Time constant of input filter........................................................................................ 45
Alarm types................................................................................................................ 46
Selecting ramp-soak patterns .................................................................................... 49
Ramp-soak status display.......................................................................................... 50
1st to 8th target SV.................................................................................................... 50
1st to 8th ramp segment time .................................................................................... 50
1st to 8th soak segment time..................................................................................... 50
Ramp-soak modes..................................................................................................... 50
2
Specifying control action and output direction at input burn-out ................................ 53
SV (Setting value) lower limiter.................................................................................. 54
SV (Setting value) upper limiter ................................................................................. 54
The time of ON-delay alarm or timer function............................................................ 55
Displaying current detector input ............................................................................... 57
HB (Set value of heater break alarm) ........................................................................ 57
Hysteresis alarm 1, 2 and 3....................................................................................... 59
Options of alarm 1, 2 and 3 ....................................................................................... 60
Upper and lower limits for control output 1 ................................................................ 62
Upper and lower limits for control output 2 ................................................................ 62
Output limit types ....................................................................................................... 63
Output value display .................................................................................................. 64
RCJ (Cold junction compensation) ............................................................................ 65
Adjusting the PV (Measured value) display (0%)....................................................... 66
Adjusting the PV (Measured value) display (100%)................................................... 66
DI1/2 (Digital input 1/2) operation .............................................................................. 67
Station No. for communication ................................................................................... 70
Parity for communication ........................................................................................... 71
Communication protocol setting ................................................................................ 72
Re-transmission output type setting .......................................................................... 73
Re-transmission base and span scale....................................................................... 74
Remote SV input (0%) adjustment ............................................................................ 75
Remote SV input (100%) adjustment ........................................................................ 75
Remote SV input filter constant ................................................................................. 76
Remote SV input value display.................................................................................. 77
Parameter display mask ............................................................................................ 78
3. Troubleshooting ....................................................................... 79
Index ............................................................................................ 81
3
PXR4
45678
PXR
910111213
-
1
Digit
<Front dimensions>
4
48 X 48mm
<Input signal>
5
Thermocouple °C Thermocouple °F Resistance bulb Pt100 3-wire type °C Resistance bulb Pt100 3-wire type °F 1 to 5V DC 4 to 20mA DC
<Control output 1>
6
Relay contact output Voltage pulse output (24V DC) 4 to 20mA DC output
<Control output 2>
7
None Relay contact output Voltage pulse output (24V DC) 4 to 20mA DC output Re-transmission output (4 to 20mA DC)
<Revision code>
8
<Optional specifications 1>
9
None Alarm (1 pc.) Alarm for heater break Alarm (1 pc.) + Alarm for heater break Ramp-soak Alarm (1 pc.) + Ramp-soak Alarm for heater break + Ramp-soak Alarm (1 pc.) + Alarm for heater break + Ramp-soak Alarm (2 pcs.) Alarm (2 pcs.) + Ramp-soak Alarm (2 pcs.) + Alarm for heater break + Ramp-soak Alarm (3 pcs.) Remote SV Remote SV + Alarm (2 pcs.)
<Instruction manual> <Power supply voltage>
10
None 100 to 240V AC English 100 to 240V AC None 24V DC English 24V DC
<Optional specifications 2>
11
None
12
RS485 (Modbus) communication
13
RS485 (ASCII) communication Digital input 1 point Digital input 2 points RS485 (Modbus) communication + Digital input 1 point RS485 (ASCII) communication + Digital input 1 point
Note 1: Cannot be combined with heater break alarm.
( 2, 3, 6, 7, H cannot be specified on 9th digit.)
Note 2: Cannot be combined with alarm (1 pc.) + heater break alarm, alarm (2 pcs.), or alarm (3pcs.).
( 3, 7, F, G, H, M, P cannot be specified on 9th digit.) Note 3: Cannot be combined with RS485 + 1-point digital input. (V and W cannot be specified on 11th digit.) Note 4: In the case of control output 2, either of heater break alarm or remote SV input can be selected.
(A, C, E and R on the 7th digit, and 2,3,6,7,H, D and P on the 9th digit cannot be specified.)
Input signal, measurement range, and set value at the time of deliver are as follows.
When thermocouple is specified: Thermocouple K, Measurement range; 0 to 400°C, Set value; 0°C When resistance bulb is specified: Pt, Measurement range; 0 to 150°C, Set value; 0°C When voltage/current is specified: Scaling; 0 to 100%, Set value; 0%
For the cases other than the above, specify input signal and measurement range. Input signal of the thermocouple and the resistance bulb can be switched by key operation on the front panel.
The actuating method of the control output has been set to reverse for control output 1, and to direct for control output 2 at the time of delivery. Note that reverse and direct actuation can be switched by key operation on the front panel.
Specification
Note
Note 1
Note 2 Note 2 Note 2 Note 2
Note 3 Note 3
Note 3 Note 3
Note 3 Note 3
Note 3
Note 4
4
T R N S A B
A C E
Y A C E R
1
0 1 2 3 4 5 6 7 F G
H M D P
N V C B
0
0
M
0
N
0
S
0
T
0
V
0
W
0
0 0 0 0 0 0 0
4
PXR5/9
45678
PXR
910111213
-
1
Digit
<Front dimensions>
4
48 X 96mm 96 X 96mm
<Input signal>
5
Thermocouple °C Thermocouple °F Resistance bulb Pt100 3-wire type °C Resistance bulb Pt100 3-wire type °F 1 to 5V DC 4 to 20mA DC
<Control output 1>
6
Relay contact output Voltage pulse output (24V DC) 4 to 20mA DC output
<Control output 2>
7
None Relay contact output Voltage pulse output (24V DC) 4 to 20mA DC output Re-transmission output (4 to 20mA DC)
<Revision code>
8
<Optional specifications 1>
9
None Alarm (1 pc.) Alarm for heater break Alarm (1 pc.) + Alarm for heater break Ramp-soak Alarm (1 pc.) + Ramp-soak Alarm for heater break + Ramp-soak Alarm (1 pc.) + Alarm for heater break + Ramp-soak Alarm (2 pcs.) Alarm (2 pcs.) + Ramp-soak Alarm (2 pcs.) + Alarm for heater break + Ramp-soak Alarm (3 pcs.) Remote SV Remote SV + Alarm (2 pcs.)
<Instruction manual> <Power supply voltage>
10
None 100 to 240V AC English 100 to 240V AC None 24V DC English 24V DC
<Optional specifications 2>
11
None
12
RS485 (Modbus) communication
13
RS485 (ASCII) communication Digital input 1 point Digital input 2 points RS485 (Modbus) communication + Digital input 1 point RS485 (ASCII) communication + Digital input 1 point
Note 1: Cannot be combined with heater break alarm.
( 2, 3, 6, 7, H cannot be specified on 9th digit.)
Note 2: Cannot be combined with RS485 + 1-point digital input.
(V and W cannot be specified on 11th digit.)
Note 3: In the case of control output 2, either of heater break alarm or remote SV input can be selected.
(A, C, E and R on the 7th digit, and 2,3,6,7,H, D and P on the 9th digit cannot be specified.)
Input signal, measurement range, and set value at the time of deliver are as follows.
When thermocouple is specified: Thermocouple K, Measurement range; 0 to 400°C, Set value; 0°C When resistance bulb is specified: Pt, Measurement range; 0 to 150°C, Set value; 0°C When voltage/current is specified: Scaling; 0 to 100%, Set value; 0%
For the cases other than the above, specify input signal and measurement range. Input signal of the thermocouple and the resistance bulb can be switched by key operation on the front panel.
The actuating method of the control output has been set to reverse for control output 1, and to direct for control output 2 at the time of delivery. Note that reverse and direct actuation can be switched by key operation on the front panel.
Specification
Note
Note 1
Note 2 Note 2
Note 2 Note 2
Note 2 Note 2
Note 2
Note 3
5 9
T R N S A B
A C E
Y A C E R
1
0 1 2 3 4 5 6 7 F G
H M D P
N V C B
0
0
M
0
N
0
S
0
T
0
V
0
W
0
0 0 0 0 0 0 0
5
1
This chapter explains the part names and functions on the face panel. The face panel has the PV and SV displays, the sta tus indicating lamp, and the setting keys, etc. Those functions are explained below. Please read and understand them before using the PXR. For details about the setting of parameters, see Chapter 2.
w
Lamp for control output 2
q
Lamp for control output 1

Part Names and Functions

e Alarm lamp
°C
C1 C2 AL1 AL2 AL3
PV
SV
i SV lamp
PXR
SEL
y
q Lamp for control output 1
Lights up while control output 1 stays ON.
w Lamp for control output 2
Lights up while control output 2 stays ON.
e Alarm lamp
Lights up on detecting an alarm. The alarm output is turned ON at the same time. If the optional heater break alarm is provided, the AL3 lamp lights up on detecting a heater break.
key
SEL
r PV (Measured value) display
t SV (Setting value) display o Auto-tuning/self-tuning/manual mode
lamp
u
t SV (Setting value) display
Displays the SV. When setting a parameter, its value appears.
SEL
y
u keys
key
Used to select a parameter block and a parameter, and register a set value.
Used to change the SV, call parameters, and change pa­rameter values.
keys
r PV (Measured value) display
Displays the PV. When setting a parameter, its name appears.
6
i SV lamp
Lights up while the SV is displayed in the SV display. When parameters and data are displayed, the SV lamp goes out.
o Auto-tuning/self-tuning/manual mode lamp
Flashes under an auto-tuning or self-tuning operation. The lamp is kept on in manual mode.
2
Parameter
display symbol
User’s
set value
Reference
page
Parameter name
Description
Setting range and
factory default setting (*)
Parameter
mask DSP
Manual mode selection
Switches between Auto and Manual operation modes.
oN: Manual mode oFF: Auto mode*
0: All settings are changeable both from
the face panel and via communication.*
1: All settings are unchangeable from the
face panel, but changeable via communication.
2: Only the SV is changeable from the
face panel, and all settings are changeable via communication.
3: All settings are changeable from the
face panel, but unchangeable via communication.
4:
All settings are unchangeable from the face
panel or
via
communication.
5:
Only the SV is changeable from the face
panel, but all settings are unchangeable
via
communication.
When the alarm type is absolute value: 0 to 100%FS (*:10)
When the alarm type is deviation:
-100 to 100%FS (*:10)
When the alarm type is absolute value: 0 to 100%FS (*:10)
When the alarm type is deviation:
-100 to 100%FS (*:10)
When the alarm type is absolute value: 0 to 100%FS (*:10)
When the alarm type is deviation:
-100 to 100%FS (*:10)
- (Unit: seconds)
- (Unit: seconds)
- (Unit: seconds)
0: OFF (Resets the auto-tuning or does not use it.)* 1: ON (Performs the auto-tuning in the SV standard type.) 2: ON (Performs the auto-tuning in low PV type (SV value-10%FS).)
0: Keeps the alarm latch.* 1: Opens up the alarm latch.
oFF: Stop* rUn: Start HLd: Hold
rEM: Remote LoCL: Local
oN: Control standby (Output: OFF, Alarm: OFF) oFF: Control RUN*
Upper limit value of alarm 3
Ramp-soak control
Sets the upper limit value at which alarm 3 is detected.
Specifies whether or not to allow the change of parameters.
Lower limit value of alarm 3
Sets the lower limit value at which alarm 3 is detected.
Set value of alarm 3
Sets the value at which alarm 3 is detected.
Upper limit value of alarm 2
Sets the upper limit value at which alarm 2 is detected.
Lower limit value of alarm 2
Sets the lower limit value at which alarm 2 is detected.
Set value of alarm 2
Sets the value during which alarm 2 is detected.
Upper limit value of alarm 1
Sets the upper limit value at which alarm 1 is detected.
Lower limit value of alarm 1
Sets the lower limit value at which alarm 1 is detected.
Set value of alarm 1
Sets the value at which alarm 1 is detected.
Timer 3 display Displays the remaining time of timer 3.
Timer 2 display Displays the remaining time of timer 2.
Timer 1 display Displays the remaining time of timer 1.
Auto-tuning Used for setting the constants for , , and
by auto-tuning.
Alarm latch cancel
Cancels the alarm latch.
Remote/local setting
Switches between remote and local operations.
Standby setting Switches between RUN and Standby for
control.
is displayed when alarm type 1 is 0 to 15, or 32 to 34, and or is displayed when alarm type 1 is 16 to 31.
is displayed when alarm type 3 is 0 to 15 or 32 to 34, and or is displayed when alarm type 3 is 16 to 31.
is displayed when alarm type 2 is 0 to 15 or 32 to 34, and or is displayed when alarm type 2 is 16 to 31.
dP13-32
dSP3-1
dSP2-128
dSP2-64
dSP2-32
dSP2-16
dSP2-8
dSP2-4
dSP2-2
dSP2-1
dSP1-128
dSP1-64
dSP1-32
dSP1-16
dSP1-8
dSP1-4
dSP1-2
dp13-8
dSP1-1
15
Parameter
display symbol
Reference
page
Parameter name
Description
Setting range and
factory default setting (*)
Parameter mask DSP
23
22
*
22
*
22
*
22
*
22
*
22
*
22
*
22
*
22
*
21
21
21
20
19
18
17
16
Set temperature (Set value)
Displays the set temperature (Set value).
0 to 100%FS (*: 0%FS)
Mask not allowed.
Measured temperature (Measurement value)
Displays the currently measured temperature (Measurement value).
Setting not allowed.
See page 78 for the method of turning on/off PV.
14
dP13-64
(SV)
(PV)

Operations

This chapter explains how to set the SV (Setting value) and the parameters for the PXR.

2-1 Parameter list

Parameters for the PXR are classified into operation parameters, and the first block, the second block and the third block parameters according to the frequency of use. The second and the third block parameters are used at initialization or when they are absolutely necessary.
Operation parameter
Parameters of the first block
Note: The parameters for which * is marked with the page number in Reference page are related to Remedies of “4” on page 79.
7
Parameters of the second block
Note: The parameters for which * is marked with the page number in
Reference page are related to Remedies of “4” on page 79.
Parameter
display symbol
Parameter name
Proportional band
Integral time Derivative time Hysteresis range for
ON/OFF control
Cooling-side proportional band coefficient
Cooling-side proportional band shift
Output convergence value
Anti-reset windup
Control algorithm
PV (Measured value) stable range
Setting HYS (Hysteresis) mode
Cycle time of control output 1
Cycle time of control output 2 (cooling-side)
Input signal code
Lower limit of measuring range
Upper limit of measuring range
Setting the decimal point position
°C / °F selection PV (Measured
value) offset SV (Setting value) offset Time constant of
input filter Alarm type 1 Alarm type 2 Alarm type 3 Status display of
ramp-soak Selecting ramp-
soak execute type
1st target value /Switching-SV value
First ramp segment time
Set to 0.0 to select the ON/OFF control (Two-position control).
Sets the hysteresis for ON/OFF control.
Selects the control algorithm.
Sets the PV stable range for the self­tuning operation.
Selects the hysteresis operation at ON/OFF control.
Not shown at 4-20mA DC output
Set this parameter when changing the types of temperature sensors.
Sets the types of alarm operations. Sets the types of alarm operations. Sets the types of alarm operations.
Selects ramp-soak patterns.
Sets the 1st target SV of ramp-soak operation. / Selected at switching­SV function for DI1
Sets the first ramp segment time.
Description
Setting range and factory
default setting (*)
0.0 to 999.9% (*: 5.0)
0 to 3200 seconds (*: 240)
0.0 to 999.9 seconds (*: 60.0) 0 to 50%FS (*: equivalent of 1.0°C)
0.0 to 100.0 (*: 1.0)
-50.0 to +50.0 (*: 0.0)
-100 to 100% (*: single 0.0, dual 50.0)
0 to 100%FS (*: 100%FS)
PID: Runs normal PID control.* FUZY: Runs PID control with fuzzy logic. SELF: Runs PID control with self-running.
0 to 100%FS (*: 2%FS)
oFF: Starts the two-position control at the
values of SV+HYS/2 and SV-HYS/2.
on:
Starts the two-position control at the values of SV and SV+HYS, or SV and SV-HYS.
RLY, SSR: 1 to 150 seconds
(*: Contact output = 30, SSR/SSC-driven output = 2)
1 to 150 seconds (*: 30)
1 to 16 (*: specified by customer while ordering)
-1999 to 9999 (*: specified by customer while ordering)
-1999 to 9999 (*: specified by customer while ordering)
0 to 2 (*: specified by customer while ordering)
°C / °F
-10 to 10%FS (*: 0)
-50 to 50%FS (*: 0)
0.0 to 900.0 seconds (*: 5.0)
0 to 34 (*: 0/5) 0 to 34 (*: 0/9) 0 to 34 (*: 0)
- (*: OFF)
1: Performs 1st to 4th segments.* 2: Performs 5th to 8th segments. 3: Performs 1st to 8th segments.
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
Note 1
Note 1
Note 1
Note 1
*
User’s
set value
Parameter mask DSP
dSP3-2
dSP3-4 dSP3-8 dSP3-16
dSP3-32
dSP3-64
dSP3-128
dSP4-1
dSP4-2
dSP4-4
dSP4-8
dSP4-16
dSP4-32
dSP4-64
dSP4-128
dSP5-1
dSP5-2
dSP5-4 dSP5-8
dSP5-16 dSP5-32
dSP5-64 dSP5-128 dSP6-1 dSP6-2
dSP6-4
dSP6-8
dSP6-16
Reference
page
24 25
26
*
27
28
29 30
30
*
31
*
35
36
37
38 39
40 40 42
40 43
*
44
*
45 46
46 46
50
49
*
50
50
8
Note: The parameters for which * is marked with the page number in
Reference page are related to Remedies of “4” on page 79.
Parameter
display symbol
Parameter name
1st soak segment time
2nd target SV
2nd ramp segment time
2nd soak segment time
3rd target SV
3rd ramp segment time
3rd soak segment time
4th target SV
4th ramp segment time
4th soak segment time
5th target SV
5th ramp segment time
5th soak segment time
6th target SV
6th ramp segment time
6th soak segment time
7th target SV
7th ramp segment time
7th soak segment time
8th target SV
8th ramp segment time
8th soak segment time
Ramp-soak mode
Description
Sets the 1st soak segment time.
Sets the 2nd target SV of ramp-soak operation.
Sets the 2nd ramp segment time.
Sets the 2nd soak segment time.
Sets the 3rd target SV of ramp-soak operation.
Sets the 3rd ramp segment time.
Sets the 3rd soak segment time.
Sets the 4th target SV of ramp-soak operation.
Sets the 4th ramp segment time.
Sets the 4th soak segment time.
Sets the 5th target SV of ramp-soak operation.
Sets the 5th ramp segment time.
Sets the 5th soak segment time.
Sets the 6th target SV of ramp-soak operation.
Sets the 6th ramp segment time.
Sets the 6th soak segment time.
Sets the 7th target SV of ramp-soak operation.
Sets the 7th ramp segment time.
Sets the 7th soak segment time.
Sets the 8th target SV of ramp-soak operation.
Sets the 8th ramp segment time.
Sets the 8th soak segment time.
Selects the power-on start, repeat, and standby functions for ramp-soak operations.
Setting range and factory
default setting (*)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
Within the SV limit. (*: 0%FS)
0 to 99h59m (*: 0.00)
0 to 99h59m (*: 0.00)
0 to 15 (*: 0)
User’s
set value
Parameter
mask DSP
dSP6-32
dSP6-64
dSP6-128
dSP7-1
dSP7-2
dSP7-4
dSP7-8
dSP7-16
dSP7-32
dSP7-64
dSP7-128
dSP8-1
dSP8-2
dSP8-4
dSP8-8
dSP8-16
dSP8-32
dSP8-64
dSP8-128
dSP9-1
dSP9-2
dSP9-4
dSP9-8
Reference
page
50
*
50 50 50
*
50 50 50
*
50 50 50
*
50 50 50
*
50 50 50
*
50 50 50
*
50 50 50 50
Note 1:When a customer does not specify the settings while ordering, the following settings are selected as factory defaults.
Thermocouple input: Thermocouple K Measured range: 0 to 400°C Resistance bulb input: Measured range: 0 to 150°C Voltage/Current input: Scaling: 0 to 100%
9
Parameters of the third block
Note: The parameters for which * is marked with the page number in
Reference page are related to Remedies of “4” on page 79
Parameter
display symbol
Parameter name
Control action
SV (Setting value) lower limiter
SV (Setting value) upper limiter
Delay time 1 Delay time 2 Delay time 3 Current transe display HB (Set value of heater
break alarm) setting Alarm 1 hysteresis
Alarm 2 hysteresis
Alarm 3 hysteresis
Alarm 1 options
Alarm 2 options
Alarm 3 options
Description
Specifies control action and output at the input burn-out.
Sets the lower limit of the SV.
Sets the upper limit of the SV.
Delay time or timer value for alarm 1 relay. Delay time or timer value for alarm 2 relay. Delay time or timer value for alarm 3 relay. Displays the current detector input value for HB alarm. Sets the operation value that detects the
heater break. Sets the hysteresis range of ON and
OFF of alarm 1. Sets the hysteresis range of ON and
OFF of alarm 2. Sets the hysteresis range of ON and
OFF of alarm 3. Sets the optional functions of alarms 1, 2 and
3.
Alarm latch (1: use, 0: not use)
Alarm of error status (1: use, 0: not use)
De-energized output (1: use, 0: not use)
0 to 19 (*: specified by customer while ordering)
0 to 100%FS (*: 0%FS)
0 to 100%FS (*: 100%FS)
0 to 9999 seconds (*: 0) 0 to 9999 seconds (*: 0) 0 to 9999 seconds (*: 0)
­0 to 50.0A (Setting to 0.0A turns off the
HB alarm.) (*: 0.0) 0 to 50%FS (*: 1)
0 to 50%FS (*: 1)
0 to 50%FS (*: 1)
000 to 111 (*: 000)
000 to 111 (*: 000)
000 to 111 (*: 000)
Setting range and factory
default setting (*)
Note 2
User’s
set value
Parameter
mask DSP
dSP9-16
dSP9-32
dSP9-64
dSP9-128 dP10-1 dP10-2 dP10-4
dP10-8
dP10-16
dP10-32
dP10-64
dP10-128
dP11-1
dP11-2
Reference
page
53
*
54
*
54 55
55 55 57
57
*
59
*
59
*
59 60
60 60
Lower limit for output 1 Upper limit for output 1 Lower limit for output 2 Upper limit for output 2 Output limit types
Output value (MV) display
Output value (MV) display
RCJ (Cold junction compensation) setting
PV gradient User-definable zero
adjustment User-definable span
adjustment DI1 (Digital input 1)
operation DI2 (Digital input 2)
operation Station No.
Parity setting
Sets the DI2 operations.
Sets the station No. for communication.
Sets the parity for communication. (The baud rate is fixed at 9600bps.
Sets the lower limit for output 1. Sets the upper limit for output 1. Sets the lower limit for output 2. Sets the upper limit for output 2. Sets the limit types of outputs 1 and 2
(breaking the limit, or maintained within the limit).
Displays the value of output 1.
Displays the value of output 2.
Sets the cold junction compensation function to ON/OFF.
Shifts the zero point of input value.
Shifts the span of input value.
Sets the DI1 operations.
-3.0 to 103.0% (*: -3.0)
-3.0 to 103.0% (*: 103.0)
-3.0 to 103.0% (*: -3.0)
-3.0 to 103.0% (*: 103.0) 0 to 15 (*: 0)
-
-
ON: Performs the RCJ (Cold junction
compensation).*
OFF: Does not perform the RCJ (Cold
junction compensation).
0.001 to 2.000 (*: 1.000)
-50 to 50%FS (*: 0)
-50 to 50%FS (*: 0)
0 to 12 (*: 0=OFF)
0 to 12 (*: 0=OFF)
0 to 255 (Setting to does not start the communications function.) (*: 1)
0: Odd parity* 1: Even parity 2: No parity
dP11-4 dP11-8
dP11-16 dP11-32 dP11-64
dP11-128
dP12-1
dP12-2
dP12-4 dP12-8
dP12-16
dP12-32
dP12-64
dP12-128
dP13-1
62 62 62 62
63
64 64
65
66 66 67 67
70 71
*
*
Note 2:The following settings are selected as factory defaults depending on the model you order.
Seventh digit = Y model: 0 Seventh digit = A model: 4
10
Communication protocol setting
Re-transmission output type setting
Re-transmission output scaling base side setting
Re-transmission output scaling span side setting
Remote SV input zero adjustment
Remote SV input span adjustment
Remote SV input filter constant
Remote SV input value display
Parameter mask
Switches communication protocols between Modbus and ASCII
Sets the type of signals to be outputted from
re-transmission
output.
Re-transmission
output scaling setting
on the base side
Re-transmission
output scaling on the
span side
Shifts the zero point of input value.
Shifts the span point of input value.
Sets the filter constant of remote SV input value.
Displays remote SV input value.
Sets whether or not to display each parameter.
0 : Z-ASCII 1 : Modbus (RTU)
Setting range 0 : PV / 1 : SV / 2 : MV/ 3 : DV (
*
: 0)
Setting range
-
100.0 to 100.0%
(*
: 0.0)
Setting range
-
100.0 to 100.0%
(*
: 100.0)
-
50 to 50%FS (*: 0)
-
50 to 50%FS (*: 0)
0.0 to 900.0 seconds (*: 0.0)
-
0 to 255 (*: specified by customer while ordering)
dP13-2
dP13-4
dP13-4
dP13-4
dP13-16
dP13-16
dP13-16
dP13-16
78
72
73
74
74
75 75 76 77
Parameter
display symbol
User’s
set value
Reference
page
Parameter name
Description
Setting range and factory
default setting (*)
Parameter
mask DSP
Note: The parameters for which * is marked with the page number in
Reference page are related to Remedies of “4” on page 79.
11

2-2 Basic operations

Just after power-on:
The display below appears just after power-on.
C1 C2 AL1 AL2 AL3
PV
SV
SEL
PXR
°C
Status at delivery
<In Auto mode> <In Manual mode>
How to switch parameters:
The figure below shows the basic operations for the PXR.
Just after power-on (PV/SV displayed)
°C
SEL
(approx. 5 seconds)
Changes SV.
SEL SEL
(approx. 1 second)
(approx. 3 seconds)
C1 C2 AL1 AL2 AL3
PV
SV
SEL
PXR
C1 C2 AL1 AL2 AL3
PV
SV
SEL
PXR
Not operated for 30 seconds.
°C
Setting parameters
PV
SV
SEL
SEL
PV
SV
PV
SV
Parameters of the first block
Parameters of the second block
Pressing and holding the
Parameters of the third block
keys makes the value increase or decrease fast.
Basic operations for the PXR (In Auto mode)
PV
SV
12
Not operated for 30 seconds.
Just after power-on (PV/MV displayed)
C1 C2 AL1 AL2 AL3
PV
°C
SEL
(PV/SV displayed)
C1 C2 AL1 AL2 AL3
PV
Setting parameters
°C
PV
SV
Changes MV.
PXR
SEL SEL
(approx. 1 second)
Parameters of the first block
Basic operations for the PXR (In Manual mode)
How to set values:
key: One press increases the value by 1.
Press and hold this key to increase the value fast.
key: One press decreases the value by 1.
Press and hold this key to decrease the value fast.
SV
SEL
SEL
(approx. 3 seconds)
SV
SEL
PXR
Changes SV.
SEL
PV
SEL
PV
(approx. 5 seconds)
SV
SV
SEL
PV
SV
Parameters of the second block
Parameters of the third block
Pressing and holding the keys makes the value increase or decrease fast.
How to register the set data:
By pressing the Note that the SV (SV0) will be registered in 3 seconds without any operation.
key, the displayed values are registered.
SEL
13

2-3 Parameter functions and method of settings

Method of setting the SV (Setting value) [Description]
•The SV is a target value for control.
•Any SV that is outside of the range set in the parameters of (lower limit) and (upper limit) of the third block cannot be set. (See page 54.)
[Setting example] Changing the SV from 250°C to 1195°C
Operating procedureDisplay
Press the or keys to display .
SV
1.
Related parameters: (page 54)
(page 54)
SV
2.
will be registered in the SV (SV0) in three seconds. After that, the controller will operate
with the SV being 1195.
14
Manual mode setting (Settings: oFF/on)
[Description]
•This parameter switches the control mode between Auto and Manual.
• During Manual operation, the decimal point is kept on at the far right in the SV display section.
• During Manual operation, auto tuning or self tuning is not done. If the mode is switched to Manual while auto or self tuning is being done, the tuning is forcibly terminated. The PID parameter remains the same in such cases.
• Manual operation output is not limited by MV limit.
•Manual operation can be carried out during standby operation.
•The operation output set value during Auto/Manual operation mode and manual mode is stored in non-volatile memory. It is kept stored even if a power interruption occurs. When the power is turned on again, the state before the power interruption is resumed.
•The following table lists the operation output at the time of switching between Auto and Manual..
Auto Manual Manual Auto
Balanceless bumpless (Switches to manual mode, holding the MV value just before the switching.)
MV output according to PID operation (Sudden change may occur to the MV value.)
Single output
MV1
Dual
output
MV2
Manual
MV PID
calculation
Manual
AUTO
MAnU
=
ON
P-n1
=
Single
[Setting example] Switching to manual mode
1.
Press and hold the
2.
Press the
Press the or the keys to display .
3.
key once, and the current set value (
SEL
key for one second, and is displayed.
SEL
Manual
Auto
Auto
Manual
Limit
Standby
StandbyLimit
Error
output
Error
output
OUT1
OUT2
Operating procedureDisplay
) on the SV display section starts flickering.
4.
Press the
key once, and the manual lamp at the lower right corner comes on, indicating that
SEL
the mode has been switched to Manual.
5.
To display operation status, press and hold the
SEL
key for two seconds.
15
Standby setting (Settings: oFF/on)
[Description]
•This parameter switches the control between RUN and Standby.
• During standby, the control output and the alarm output stay OFF, like the standby for ramp-soak operation.
• While the alarm with a hold is selected, the hold function takes effect after changing the Standby setting from ON to OFF.
is displayed during the standby for ramp-soak operations or the controller changes to the standby state
in case of the occurrence of errors.
• The other operations are the same as those of the ramp­soak standby.
•The setting of ON/OFF for standby is saved after power­off.
[Setting example] Starting the control
•When the standby is set to ON during the auto-tuning, self-tuning, and ramp-soak operations, those operations will stop. (The PID constant will not be renewed.) Even through it is set to OFF later, the auto-tuning, self-tuning, and ramp-soak operations will not be re-started.
• During standby, the ON-delay timer is reset. When returning to RUN from the standby state, the timer will start from the beginning.
Operating procedureDisplay
Press and hold the
1.
will be displayed. Then press the key once.
2.
Press the The current setting (
3.
Press the or keys to display .
4.
Press the outputs: OFF)
5.
If you want to display the operation status, press and hold the on the SV display will flash, indicating the standby status.
SEL
key once.
key once. The standby state for control is selected . (control output and all the alarm
SEL
key for one second.
SEL
) flashes on the SV display.
key for two seconds. The v alue
SEL
16
Local/remote operation setting (Setting range: LoCL/rEM) (Option)
[Description]
•This parameter is used to switch between local and re­mote operations.
Set value Operation
Performs local operation. Performs remote operation.
(“ ” and the set value (SV) are displa yed alternately in the SV display section on the front face while in remote operation.)
Related parameters:
(page 75)
(page 75) (page 76)
(page 77)
[Setting example] Switching to remote operation
Operating procedureDisplay
Press and hold the
1.
will be displayed on the PV display section.
key for one second.
SEL
* Local operation: Control by SV set by the keys on the
front face, ramp-soak operation, SV selection determined by digital input, and SV setting via communication
* Remote operation: Control by SV determined by Remote
SV input
2.
Press the keys to display .
Press the
3.
The current setting (
4.
Press the keys to display .
Press the
5.
To display the operation status, press and hold the
6.
key once.
SEL
key once. Flickering stops and the operation is switched to remote.
SEL
) in the SV display section flickers.
key for two seconds.
SEL
17
Ramp-soak control (Settings: oFF/rUn/hLd) (Option)
[Description]
• This function automatically changes the SV (Setting value) according to the program pattern set in advance as shown in the right line graph. Up to eight pairs of ramp­soak operation can be programmed.
•The first ramp starts at the PV (Measured value) that is the one just before running the program.
•The program can also automatically run at power-on (Power-on starting function). Refer to the parameter of
(page 47).
Related parameters:
(page 50) to (page 50)
to (page 50)
to (page 50) (page 50) (page 49)
Up to SV-8
SV-3 SV-2 SV-1
SV-4
PV
First ramp
TM1r
Ramp: the section in which the SV changes toward the target value. Soak: the section in which the SV is the target value, and remains unchanged.
First soak
TM1S
Second soak
Second ramp
TM2S
TM2r
Third soak
Third ramp
Fourth ramp
TM3S
TM3r TM4r
Fourth soak
TM4S
Up to TM8r
Up to TM8s
[Setting example] Starting the ramp-soak operation
Operating procedureDisplay
Press and hold the
1.
will be displayed on the PV display.
Press the
2.
Press the
3.
key to display
key once.
SEL
The current setting ( ) flashes on the SV display.
Press the or keys to display .
4.
Press the
5.
key once. Then, the program will start according to the ramp-soak pattern that is
SEL
set in advance.
If you want to display the operation status, press and hold the
6.
key for one second.
SEL
key for two seconds.
SEL
18
Canceling the alarm latch (Setting range: 0/1) (Option)
[Description]
•This parameter cancels the alarm latch when it is latching.
[Setting example] Opening up the alarm latch
Operating procedureDisplay
Related parameters:
to (page 60)
Press and hold the
1.
will be displayed on the PV display.
Press the key to display .
2.
Press the
3.
The current setting ( ) flashes on the SV display.
Press the or keys to display .
4.
Press the
5.
will stop flashing and will change to in a few seconds.
If you want to display the operation status, press and hold the
6.
SEL
SEL
SEL
key once.
key once.
key for one second.
key for two seconds.
SEL
19
Auto-tuning function (Settings: 0/1/2)
[Description]
[Note]
If the controller is powered off during auto-tuning, this makes the auto-tuning ineffectiv e with each parameter of , , and unchanged. To start the auto-tuning operation, set to “1” or “2” again.
•To suspend the auto-tuning, set to “0”. This makes the auto-tuning cancel with each parameter of , , and
unchanged.
• Once the parameters of , , and are set automatically by the auto-tuning, those parameters are stored in the controller even after it is power ed of f. Therefore, it is not necessary to execute the auto-tuning again.
• By setting to “1” or “2” , the auto-tuning operation starts, and at the end of the tuning, will be displayed automatically to .
• After the auto-tuning operation, the controller starts to operate at the automatically set values of , , and .
•A decimal point at the right end of the SV display flashes during auto-tuning.
•There are two codes for AT: Setting code [1]: SV standard type
Performs the auto-tuning based on the SV.
Setting code [2]: Low PV type
Performs the auto-tuning based on the SV-10%FS.
[Note]
Since ON/OFF control is performed during auto-tun­ing, overshoot against the SV may occur. To reduce the overshoot, execute the auto-tuning operation with the setting code [2] (Low PV) selected.
•The auto-tuning can be executed both just after power-on and in a control or stable status.
Related parameters:
(page 24) (page 25) (page 26)
(page 30)
(page 28)
[Setting example] Setting the auto-tuning operation to 1
Operating procedureDisplay
Press and hold the
1.
will be displayed on the PV display.
Press the key to display .
2.
Press the
3.
The current setting ( ) flashes on the SV display.
Press the or keys to display .
4.
Press the
5.
a decimal point at the right end of the SV display flashes.
When the auto-tuning finishes properly, a decimal point stops flashing, and the set values of , ,
6.
and parameters change. When the auto-tuning f inishes abnormally, a decimal point stops flash­ing, but the set values of , , and parameters remain unchanged.
key once.
SEL
key once. will stop flashing and the auto-tuning will start. During auto-tuning,
SEL
key for one second.
SEL
20
If you want to display the operation status, press and hold the
7.
key for two seconds.
SEL
,
,

Displaying ON-delay alarm or the remaining time of timers

[Description]
•These parameters display the remaining time of Timers 1, 2 and 3.
• The remaining time of the ON/OFF-delay timer is counted down. When the counter shows , the alarm relay is closed.
• During count-down, if the PV changes to the value of the temperature at which the alarm is set to OFF, or if “DI” for the timer is set to OFF, the counter is reset, and the alarm relay is opened.
display parameter
PV
SV
[Setting example] Displa ying ON-delay alarm or the remaining time of timers
Operating procedureDisplay
(unit: seconds) (Option)
Remaining time (seconds)
Press and hold the
1.
will be displayed.
Press the key to display
2.
The remaining time of timer 1 will be displayed.
Press the or keys to display the remaining time of , and .
3.
If you want to display the operation status, press and hold the
4.
key for one second.
SEL
.
key for two seconds.
SEL
21
[Description]
Setting alarm 1, 2 and 3 Upper limit of alarm 1, 2 and 3 Lower limit of alarm 1,2 and 3
(Setting range: Absolute value alarm: 0 to 100%FS
Deviation value alarm: -100 to 100%FS )
}
(Option)
• These parameters are used to for settings of alarm 1, 2 and 3.
• When the alarm type ( , 0 to 15, alarms 1, 2 and 3 ( , set.
• When the alarm type ( , any value other than 0 to 15, the upper and lower limits of alarm 1, 2 and 3 ( , ,
) can be set.
[Setting example] Setting the operation value of alarm 2 to -10°C
Press and hold the
1.
will be displayed on the PV display.
Press the key to display .
2.
or
and
or
,
key for one second.
SEL
) is set to
) can be
) is set to
,
,
[Note]
Setting codes (12 to 15) cannot be selected in alarm type 1 and 3 (
Related parameters: ,
Operating procedureDisplay
/
).
, , ,
, , , ,
(page 46) (page 59) (page 55) (page 60)
Press the
3.
The current setting ( ) flashes on the SV display.
Press the or keys to display .
4.
Press the
5.
controller will operate with the operation value of alarm 2 being -10°C.
If you want to display the operation status, press and hold the
6.
key once.
SEL
key once. will stop flashing and will be registered for . After that, the
SEL
SEL
key for two seconds.
22
Key lock (Setting range: 0
5)
[Description]
•This parameter makes the set values of parameters unchangeable. However, the parameter name and the set values can be displayed.
•To reset the key lock, change to .
•Even when the key lock is set, control and alarm functions can operate properly.
[Setting example] Setting the key lock to “2”
•There are six levels of the key lock: : Unlocked (reset) : All settings are unchangeable from the controller, but
changeable via communication.
: Only the SV is changeable from the controller, and all
settings are changeable via communication.
: All settings are changeable from the controller, but
unchangeable via communication.
:
All settings are unchangeable from the controller or via communication.
: Only the SV is changeable from the controller, but all
settings are unchangeable via communication.
Operating procedureDisplay
Press and hold the
1.
will be displayed on the PV display.
Press the key to display .
2.
Press the
3.
The current setting ( ) flashes on the SV display.
Press the or keys to display .
4.
Press the
5.
setting other than the SV cannot be changed from the front panel.
If you want to display the operation status, press and hold the
6.
key once.
SEL
SEL
key once. will stop flashing and will be registered for
key for one second.
SEL
key for two seconds.
SEL
. After that, any
23
Proportional band (Setting range: 0.0 to 999.9% of the measured range)
[Description]
•To select the ON/OFF control (two-position control), set to 0.0. It is not necessary to set and .
can be automatically set by the auto-tuning operation.
• When is too small, control will be unstable, and when is too large, the response will be delayed.
• Set the hysteresis of the ON/OFF control (two-position control) in the parameter
• If auto-tuning is run after the ON/OFF control is selected, the ON/OFF control changes to the PID control. To keep the ON/OFF control selected, do not execute the auto­tuning.
[Setting example] Changing the proportional band from 5.0% to 15.0%
Operating procedureDisplay
.
1.
Press and hold the
will be displayed on the PV display.
Press the
2.
The current setting
Press the or keys to display .
3.
Press the
4.
controller will operate with being 15.0%.
If you want to display the operation status, press and hold the
5.
SEL
key once.
key once. will stop flashing and will be registered for . After that, the
SEL
SEL
key for three seconds.
( )
flashes on the SV display.
SEL
key for two seconds.
24
Integral time (Setting range: 0 to 3200 seconds)
[Description]
can be set automatically by the auto-tuning operation.
can also be set manually.
•When is set to 0, the integral operation does not start.
•When is set to 0.0, this makes the setting of ineffec­tive.
[Setting example] Changing the integral time from 240 seconds to 600 seconds
Operating procedureDisplay
1.
Press and hold the
will be displayed on the PV display.
2.
Press the key to display .
key for three seconds.
SEL
Press the
3.
The current setting ( ) flashes on the SV display.
4.
Press the or keys to display .
Press the
5.
controller will operate with being seconds.
If you want to display the operation status, press and hold the
6.
key once.
SEL
SEL
key once. will stop flashing and will be registered for . After that, the
key for two seconds.
SEL
25
Loading...
+ 58 hidden pages