SPECIFICATIONS: SWITCHING EL EMENT "B"
1.0 Mounting Position: Diaphragm Vertical (See Diagram Below).
2.0 Set Point (Sealed): Factory Set @ .15" +.00" / -.10" w.c. Pressure Fall Vertical Plan
3.0 Approximate Switc h ing Differential: Progressive; Increasing From .02
± .01" w.c. at Minimum Set Point To Approximately .1" w.c. At Maximum Set Point.
4.0 Measured Media: Air
5.0 Operating Temperature Range: -40° to 176° F (-40.0° C to 80.0° C).
6.0 Life: 100,000 Cycles Minimum At ½ PSI Maximum Pressure Each Cycle And
At Maximum Electrical Load.
7.0 Electrical Rating
7.1 300 Va Pilot Duty At 115 to 277 Vac
7.2 15a Non-inductive to 277 Vac
8.0 Contact Arrangement: SPDT
9.0 Position Of Switch Contacts Before Pressure Is Applied:
SWITCHING ELEMENT "B"
NC
C
NO
DIMENSIONS
INCHES
(METRIC)
3 5/32
(80)
1 9/16
(40)
3/4
(19)
SPECIFICATIONS: SWITCHING EL EMENT "A"
1.0 Mounting Position: Diaphragm Vertical (See Diagram Below).
2.0 Set Point (Sealed): Factory Set @ 0.80" +.10" / -.00" w.c. Pressure Fall Vertical Plane.
3.0 Approximate Switching Differential: Progressive; Increasing From .02
± .01" w.c. at Minimum Set Point To Approximately .1" w.c. At Maximum Set Point.
4.0 Measured Media: Air
5.0 Operating Temperature Range: -40° to 176° F (-40.0° C to 80.0° C).
6.0 Life: 100,000 Cycles Minimum At ½ PSI Maximum Pressure Each Cycle And
At Maximum Electrical Load.
7.0 Electrical Rating
7.1 300 Va Pilot Duty At 115 to 277 Va c
7.2 15a Non-inductive to 277 Vac
8.0 Contact Arrangement: SPDT
9.0 Position Of Switch Contacts Before Pressure Is Applied:
SWITCHING ELEMENT "A"
3 7/16
(87)
NC
C
NO
7 1/4
(184)
HIGH PRESSURE INLET
SEE NOTE No. 2
1 11/32
(34) (46)
1 13/16
.250 (6) SLIP-ON
BLADE
CONNECTIONS
LOW PRESSURE INLET
SEE NOTE No. 2
SEE NOTE No. 1
2 MOUNTING
HOLES 3/16 DIA.
(5)
COMCOM
NO
NC
NO
NC
7
(178)
7 1/2
(190)
SEE NOTE No.
HIGH PRESSURE INLE
SEE NOTE No. 2
7/8
(22)
7/16
(11)
LOW PRESSURE INLET
SEE NOTE No. 2
NOTES:
1. External Adjustm ent Screw - Sealed
2. Sample Line Connectors, (1) High Pressure and (2) Low Pressure,
Complete With Nut and Ferrule Will Accept 1/4" OD Tubing ie Copper, Aluminum o r P l asti c .
3. Approval or Recognition By: U.L. File MH6213; and C.S.A. File LR18754.
REV
DRAWING RELEASE No.
DWN
CHKD
DCN No.
DATE CHKD
MJA 11/21/05
DATE SCALE
11/21/05FL
3589
CHKDDATE BY
FL
NONE
SENSING SWITCH SPECIFICATIONS
CAPTIVE AIR
CLEVELAND CONTROLS MODEL: DDP-106-313
±±
.XXX = .005.XX = .015
ANGLES = 1
USED ON
B20741-313
°
SHEET OF
11
REV