Cameron 351, 352, 353 Installation Manual

Page 1
BARTON® NUCLEAR
MODELS 351/352/353
LIQUID LEVEL SYSTEMS
Installation Manual
Part No. 9A-C10521, Rev. 03
Safety ............................................................................................................... 2
Section 1— Introduction ................................................................................ 3
General ......................................................................................................... 3
Product Description....................................................................................... 4
Model 351 Liquid Level System ................................................................ 4
Model 352 Liquid Level System ................................................................ 4
Model 351/352 System Sensors ............................................................... 4
Model 353 Liquid Level System ................................................................ 5
Sensor Housings and Capillary Tubing ......................................................... 5
Specications ................................................................................................ 6
Section 2—Theory of Operation .................................................................... 7
General ......................................................................................................... 7
Model 353 Sensor ..................................................................................... 7
Section 3—Installation ................................................................................... 9
Unpacking ..................................................................................................... 9
Model 353 Sensor Assembly ..................................................................... 9
Mounting ....................................................................................................... 9
Piping and Installation ................................................................................... 9
Section 4—Operation, Maintenance, and Calibration ............................... 13
Startup ........................................................................................................ 13
General Field and Periodic Maintenance .................................................... 13
Model 351 Sensor Inspection and Cleaning............................................ 13
Model 353 Sensor Inspection and Cleaning ........................................... 13
Model 353 Sensor Bellows Removal/Replacement .................................... 14
Calibration ................................................................................................... 16
Troubleshooting .......................................................................................... 16
Section 5—Parts List.................................................................................... 17
General ....................................................................................................... 17
Section 6—Dimensional Drawings ............................................................. 27
General ....................................................................................................... 27
Product Warranty ........................................................................................ 33
Product Brand ............................................................................................. 33
November 2015
Page 2

Safety

Before installing this product, become familiar with the installation instruc­tions presented in Section 3. In addition, adhere to the following safety precautions:
Pressure – The instrument shall not be subjected to pressure higher than the safe working pressure stamped on the pressure housings.
Corrosion – The bellows and O-rings of the sensors shall not be subjected to media incompatible with ethylene propylene and 316 stainless steel.
Vibration and Shock – The instrument shall not be subjected to severe me­chanical vibration or hydraulic shock.
 WARNING:Thissymbolidentiesinformationaboutpracticesorcircum-
!
stances that can lead to personal injury or death, property damage, or economic loss.
CAUTION: Indicates actions or procedures which if not performed correctly
IMPORTANT: Indicates actions or procedures which may affect instrument operation or
may lead to personal injury or incorrect function of the instrument or connected equipment.
may lead to an instrument response that is not planned.
2
Page 3
Model 351/352/353 Liquid Level Systems Section 1

Section 1— Introduction

General

The Barton Liquid Level System provides accurate hydraulic transmission of a process medium for measuring the level of liquids contained in a process vessel. The self-contained system is typically mounted outside the vessel. Floats, levers, pins, and other mechanical devices susceptible to contamina­tion or wear are not required. Because the basic system is actuated by the process media, local indication is possible without external power.
Barton Liquid Level Sensors can be purchased as a component of a factory-
built system, or as a part for a eld-installed system. Sealed sensor systems can be designed in the following congurations:
• a single sensor system (Model 351)
• a dual-sensor system (Model 352)
For applications involving corrosive uids or tank temperatures above 200°F (95°C), a dual-sensor conguration is recommended.
For applications involving unusual ll requirements due to liquid volumes or
high ambient temperatures, a Model 353 system is recommended. The Model 353 system can be designed with one or two sensors. See Model 353 Liquid
Level System on page 5 for details.
Process vessel
Single sensor
DPU (shown with indicator)
Single-Sensor System
Figure 1.1—Single-sensor and dual-sensor system congurations
IMPORTANT: In this manual, the term “sensor,” refers to a mechanical bellows as-
sembly and its pressure housing used to detect and transmit a hydraulic or pneumatic signal to an electronic transmitter, mechanical indicator or switch.
Sensor
Sensor
Dual-Sensor System
3
Page 4
Section 1 Model 351/352/353 Liquid Level Systems

Product Description

Model 351 Liquid Level System

The Model 351 consists of a single reference sensor connected by capillary
tubing to a Barton Differential Pressure Unit (DPU). Hydraulic uid is sealed
inside the sensor and the capillary tubing, eliminating the need for additional piping.
The Model 351 system, as shipped from the factory, needs only to be mount­ed on the vessel to provide continuous level measurement when used with a Barton readout instrument. The sensor can be installed on vented or sealed process vessels. The readout instrument (DPU, for example) can be installed at various elevations (i.e., below the vessel, at the vessel upper connection or above the vessel ) as long as the instrument calibration considers the elevation difference between the instrument and the sensor.
Model 352 Liquid Level System
The Model 352 consists of two reference sensors connected by capillary tub­ing to a Barton DPU.
Unlike the Model 351 system, the process media does not come into contact with the DPU, making the model ideal for applications involving corrosive
liquids or tank temperatures above 200°F (95°C).
The DPU can be mounted up to 50 ft (15 meters) away from the vented or sealed process vessel and at ele vations up to 30 ft (9 meters) above the lowest
sensor. Elevation of the readout instrument (DPU) with respect to the sensors is essentially unlimited as long as the instrument calibration considers the elevation difference between the two sensors.
Model 351/352 System Sensors
A Model 351 or Model 352 system can include any of three sensor types, depending on the pressure rating required:
• 500-psi SWP sensor (referred to as Model 351 sensor throughout this document)
• 3,000-psi SWP sensor (referred to as Model 351 sensor throughout this document)
• No-pressure-rating sensor (referred to as Model S048 sensor throughout this document)
All three sensor types contain a 3.75” (95 mm) bellows that functions as a seal. As pressure on the bellows varies due to changes in liquid level and/or process system pressure variations, these pressure variations are transmitted
through the liquid lled sensor and capillary tubing to the readout instrument.
4
Page 5
Model 351/352/353 Liquid Level Systems Section 1
The S048 sensor is constructed with the same housing as the 500-psi SWP sen­sor for mounting purposes, but has no pressure rating and is designed to mount inside open ves sels or sumps. The large bottom opening of the sensor prevents fouling of the sensor ports due to dirt, loose debris, or other contamination.
Model 353 Liquid Level System
The Model 353 system is designed specically for unusual ll liquid require­ments due to liquid volumes or high ambient temperatures.
A Model 353 system can be designed with one or two sensors. Systems are
typically assembled in the eld.
The Model 353 high-volume sealed sensor is rated for a 3,000-psi SWP and contains a single removable bellows with an initial volume of 10 in.³ (164
cc). The bellows is 2.25 in. (57 mm) long and has a diameter of 3.75 in. (95
mm). It can extend an additional 1 in. (25 mm), adding an additional 7.5 in.³ (123 cc) to its volumetric capacity (see Figure 1.2). When the bellows is fully compressed, an internal valve closes to prevent the escape of process uids.
The bellows may be removed for replacing a dam aged bellows or for pressure testing the capillary tubing.
Travel to close valve
0.84 in. (21 mm)
Normal length
2.25 in. (57 mm)
1 in. (25 mm)
Expanded bellows
Figure 1.2—Model 353 bellows travel (approximate dimensions)

Sensor Housings and Capillary Tubing

All sensors have stainless steel housings. Capillary tubing connecting the sen­sor to the DPU is either 1/4-in. or 3/16-in. OD. Tubing length is deter mined by the installation. Capillary tubing may be bent or looped as required. A 1/4-in. NPT plug or a high-pressure tting (3/8-in. OD tubing) in the housing
facilitates venting.
5
Page 6
Section 1 Model 351/352/353 Liquid Level Systems
Specications
Specications for Barton sealed sensor systems are presented in Tables 1.1
and 1.2.
CAUTION: Never operate the system at pressures exceeding the safe working
pressureofthesensorangeorattachedinstrument,whicheveris
lower. Periodic testing at pressures up to 150% of the safe working pressure is permitted, provided the pressure is applied equally and simultaneously to the entire system.
Table1.1—SensorSpecications
Specication Model S048 Model 351 Model 353
Housing Material 316 SST 316 SST 316 SST
Safe Working Pressure N/A 500 or 3000 psi
(3.5 or 20.7 MPa)
Bellows Material
Housing Seals
Bellows Volume
Nominal 3.5 in.³
Thermal Expansion
Bellows Seals O-rings O-rings O-rings
316L SST 316L SST
N/A O-ring & Backup
(57.4 cc)
N/A N/A
O-ring
3.5 in.³
(57.4 cc)
3000 psi
(20.7 MPa)
316L SST
O-ring, Backup O-ring, and Flat Nickel Gasket
10 in.³
(165 cc)
17.5 in.³
(288 cc)
Table1.2—CapillarySpecications
Specication 1/4-in. OD 3/16-in. OD
Material 316 SST 304L SST
Outside Diameter ¼ in. (6.4 mm) 3/16 in. (4.8 mm)
Wall Thickness 0.060 in. (1.5 mm) 0.049 in. (1.2 mm)
Capillary Armor Material 302 SST 316 SST
Capillary Fill Material Silicone Oil, Water, Ethylene
Glycol & Water or Mineral Oil
Weight (with armor) 0.25 lb/ft (350 g/m) 0.25 lb/ft (350 g/m)
Bend Radius (minimum) 2 in. (50 mm) 2 in. (50 mm)
Silicone Oil, Water, Ethylene Glycol & Water or Mineral Oil
6
Page 7
Model 351/352/353 Liquid Level Systems Section 2

Section 2—Theory of Operation

General

A uid column exerts a pressure proportional to its height and density, inde­pendent of the shape or volume of the containing vessel. A differential pres-
sure unit (DPU) can be calibrated to indicate the height of a uid when the uid density is known. In tanks of given dimensions, the weight and volume
of contents can be measured by a DPU.
One or two sealed sensors are connected to the DPU by capillary tubing. These sensors contain bellows which function as “isolation seals.” As pres­sure on the sensor bellows varies due to changes in liquid level, the variations are transmitted hydraulically through the tubing to the bellows of the DPU.
Model 351/Model S048 Sensors
The pressure deection characteristics of the Model 351 (500-psi or 3,000­psi) and Model S048 sensor bellows are shown in Figure 2.1.
Figure 2.1—Pressure deection characteristics of the Model 351/352 sensor bellows

Model 353 Sensor

In the event of thermal expansion of the ll-liquid in the capillary tubing
and in the other instruments, the Model 353 sensor bellows can extend 1 in.
(25 mm) for 7.5 in.³ (123 cc) displacement. If leakage occurs in the capillary tubing, the bel lows becomes compressed approximately 0.56 in. (14 mm) and
7
Page 8
Section 2 Model 351/352/353 Liquid Level Systems
then closes an internal valve to prevent further loss of bel lows liquid. This action prevents escape of process liquid.
The sensor bellows may be removed with a special wrench (see Table 4.1 and Figure 4.1, page 14). This permits pressure testing and leak testing of the hous-
ing and capillary tubing and allows damaged parts to be replaced before the
system is lled.
The pressure deection characteristics of the Model 353 sensor bellows are
shown in Figure 2.2.
1 in. (25 mm)
Normal length
2.25 in. (57 mm)
Travel to fully close valve
0.84 in. (21 mm)
Figure 2.2—Pressure deection characteristics of the Model 353 sensor bellows
The bellows can extend over 1 in. (25 mm) to accommodate ll uid expan­sion under hot operating conditions. As seen in Figure 2.2, the expansion creates an internal pressure of 25.7 in. H2O (6.4 kPa) at 1 in. (25 mm). When
compressed, the bellows travels approximately 0.5 in. (13 mm) before the internal valve begins to close. Compression of the bellows to 0.5 in. (13 mm) requires approximately 10 in. H2O (2.6 kPa) of external pressure.
8
Page 9
Model 351/352/353 Liquid Level Systems Section 3

Section 3—Installation

Unpacking

All instruments are inspected during manufacture and prior to shipping. How­ever, an inspection should be performed at the time of unpacking to detect any damage that may have occurred during shipping.
When unpacking, carefully remove the instrument from the container. If the instrument is a liquid-lled sys tem, remove the strap-fasteners and gently
unroll the capillary tubing.
The transmitter output may indicate “Near Full Scale” if the system is tested prior to installation. This is nor mal, and the transmitter output will be correct when the reference leg is elevated.

Model 353 Sensor Assembly

The Model 353 sensor bellows and bottom plate bolts are not torqued to installation requirements as shipped. See Section 4 on page 13 for instruc­tions on removal and replacement of Model 353 sensor bellows.

Mounting

Mount the sensors as close to vertical orientation as possible to ensure proper operation. The sensor may be oriented with the vent pointed up or down, depending on the service or installation design.
When mounted with the L-bracket, mount the sensors with three 3/8-16 SAE
bolts, Grade 5 or better, torqued to 24 to 26 ft-lb (33-35 N-m). The mount­ing bracket may be rotated axially or reversed, as required for installation (as shown in dimensional drawings in Section 6).
Interfacing process tubing should be supported to minimize relative motion between the sensor and connections. The capillary tubing should be supported
with at least one support located within 1 ft (0.3 meters) of the sensor. The minimum bend radius of the capillary tubing is 2 in. (50 mm).

Piping and Installation

IMPORTANT: Sealed systems are normally lled at the factory, but can be installed and
lled in the eld.
Sensors should be connected in accordance with user specications. Flanges and tube ttings (3/8”, 1/2” or 3/4”) are available for this purpose.
9
Page 10
Section 3 Model 351/352/353 Liquid Level Systems
Capillary Tubing Welding
Figures 3.1 through 3.3 present the information and procedures necessary to weld the capillary tubing and tubing coupling.
Figure 3.1—1/4-in. OD capillary tubing welds
IMPORTANT: All parts are solution annealed 316 or 304 stainless steel. Please adhere
10
to the following welding practices:
(1) Weld type: GTAW llet, 45 amps, 10 volts, 20 CFH (9.5 l/m) Argon gas ow. (2) Use 1/16” dia. Type 308 ller rod
Page 11
Model 351/352/353 Liquid Level Systems Section 3
Figure 3.2—3/16-in. OD capillary tubing welds
IMPORTANT: All parts are solution annealed 304L stainless steel. Please adhere to the
following welding practices:
(1) Weld type: GTAW llet, 45 amps, 10 volts, 20 CFH (9.5 l/m) Argon gas ow. (2) Use 1/16” dia. Type 308 ller rod
11
Page 12
Section 3 Model 351/352/353 Liquid Level Systems
NOTE—Weldment should join both ends (male/female) using the capillary tubing as a “backup ring.”
Penetration through the tubing wall is not required.
Figure 3.3—3/16-in. OD capillary tubing coupling welds
IMPORTANT: All parts are solution annealed 304L stainless steel. Please adhere to the
12
following welding practices: (1) Weld type: GTAW V-groove, 45 amps, 10 volts, 20 CFH (9.5 l/m)
Argon gas ow. (2) Use 1/16” dia. Type 308 ller rod
Page 13
Model 351/352/353 Liquid Level Systems Section 3

Section 4—Operation, Maintenance, and Calibration

Startup

Startup and operating instructions for an instrument actuated by the Liquid Level System are presented in the installation and operation manual for that instrument.

General Field and Periodic Maintenance

The sensor is basically maintenance-free. If installed in an application where sediment can accumulate in the bel lows convolutions, periodic inspection and cleaning may be required.
CAUTION: The sensor bellows can be damaged by contact with the housing.

Model 351 Sensor Inspection and Cleaning

When removing the sensor assembly, avoid unnecessary contact with the housing.
1. Remove the sensor from the housing. The 500 psi (3.5 MPa) sensor is connected by a retainer ring; the 3000 psi (20.7 MPa) sensor is connected by 6 bolts. Carefully separate the sensor from the housing assembly.
2. Remove any accumulated material from between the bellows convolu­tions, using a soft brush and solvent as required.
3. Inspect the O-rings and seals before reassembly. Replace as necessary (see note on page 17).
4. Replace the housing over the sensor bellows. For 3000 psi (20.7 MPa) sensors, lubricate the bolt threads and seat the bolts at 34 to 35 ft-lb (46 to 48 N-m). For 500 psi (3.5 MPa) sensors, install the retaining ring.

Model 353 Sensor Inspection and Cleaning

1. Remove the 12 bolts connecting the sensor to the housing, and carefully separate the sensor from the housing assembly.
2. Remove any accumulated material from between the bellows convolu­tions, using a soft brush and solvent as required.
3. Inspect the bellows for damage. Free-length should be 2-1/4 in. (57 mm) (see Figure 1.2). Length may vary by 1/8 in. (3 mm) due to system tem­perature-effects. Press lightly (by hand) on the free end of the bellows; the bellows should be “incom pressible” if the system is liquid lled.
4. Inspect the O-ring, backup ring, and nickel gasket before reassembly. Replace as necessary (see note on page 17).
5. Carefully replace the sensor in the housing assembly. Lubricate the bolts
lightly and torque uniformly to approximately 34 to 35 ft-lb (46 to 48
N-m).
13
Page 14
Section 3 Model 351/352/353 Liquid Level Systems

Model 353 Sensor Bellows Removal/Replacement

The sensor bellows must be removed under the following circumstances:
• when the capillary system is to be pressurized
• for argon ow during weld ing
• for static pressure tests of the capillary system
• for replacement of a damaged sensor
To remove the sensor bellows, perform the following steps:
1. Remove the 12 housing bolts. Carefully remove the bellows bottom plate assembly from the housing.
CAUTION: The sensor bellows can be damaged by contact with the housing.
When removing the sensor assembly, avoid unnecessary contact with the housing.
2. Remove the bellows from the bottom plate by turning the valve seat with the sensor bellows wrench and lift ing the bellows until the guide stem is withdrawn from the capillary tubing. Observe the two O-rings on the bot­tom of the valve seat; they may fall free when the bellows is lifted.
3. (Pressure Tests Only) Install a test tting with an O-ring (refer to Figure
4.1, item 4, and Figure 4.2, page 15). Tighten with the sensor bellows wrench to 39 to 40 ft-lb (53 to 55 N-m). Remove the test tting when
pressure tests are complete.
Table 4.1—Model 353 Tools and Test Fittings
Item Description Part No. Purpose Qty
1 Sensor Bellows
Spacer Assembly
2 Sensor Bellows
Wrench
3 Fill Valve Test Fitting 9A-0353-1109B Connection for applying
4 Seal Plug Adapter 9A-S039-0087Z Replace sensor bellows
9A-0353-1069B Hold bellows in “open”
position during ll
9A-0353-1053C Removal/installation of
sensor bellows
pressure thru ll valve
assembly during pressure tests
2 per sensor
2
3
1 per sensor
14
Figure 4.1—Model 353 tools and test ttings identication
Page 15
Model 351/352/353 Liquid Level Systems Section 4
Figure 4.2—Model 353 sensor bellows and bottom plate assembly
To install the sensor bellows, perform the following steps:
4. Inspect the sensor bellows to verify that the bellows is undamaged and the guide stem is in place.
IMPORTANT: This inspection should be performed whether the old bellows or a
replacement bellows is to be installed.
5. Inspect the two O-rings in the valve seat, the O-ring and the backup ring in the bottom plate, and the nickel gasket to verify there is no dam­age (see note on page 17). Install the nickel gasket on the bottom plate. Lubricate the O-rings and backup ring lightly with lubricant (part number
9A-C0002-1003U) and insert in the appropriate grooves.
6. Engage the valve seat to the bottom plate. The guide stem must enter the capillary tubing without restric tion.
IMPORTANT: To prevent loss of the O-rings in the valve seat, invert the bellows and
bottom plate during this step.
7. Tighten the valve seat with the sensor bellows wrench to approximately
39 to 40 ft-lb (53 to 55 N-m). Verify that a metal-to-metal t is obtained
between the valve seat and the bottom plate (zero clearance).
8. After the sensor bellows and capillary tubing are lled with liquid, care­fully insert the plate and bellows assembly into the housing. Uniformly
tighten the 12 housing bolts to 34 to 35 ft-lb (46 to 48 N-m).
15
Page 16
Section 4 Model 351/352/353 Liquid Level Systems
CAUTION: The sensor bellows can be damaged by contact with the housing.
When installing the sensor assembly, avoid unnecessary contact with the housing.

Calibration

The actuated instrument is calibrated according to the procedure presented in the installation and operation manual for that instrument.
IMPORTANT: During calibration, the sensor should be elevated to the exact position it
will occupy in the installa tion. Otherwise, calibration pressures must be
modied to compensate for the differences in hydro static pressures.

Troubleshooting

Troubleshooting procedures for the actuated instrument are presented in the technical manual for that instru ment.
Troubleshooting procedures for the sensor are presented in Table 4.2.
Table 4.2—Sensor Troubleshooting Chart
Problem Probable Cause Corrective Action
Transmitter reading off zero (±1%) with empty tank.
Transmitter reading off zero (exceeds ±1%).
Transmitter remains at full­scale.
Transmitter does not respond to level changes.
Transmitter is slow or erratic. Sensors contaminated.
Transmitter drifts. Leak in sealed system. Repair.
Minor elevation errors. Re-zero transmitter according
Elevations of sensors (or transmitter) are incorrect.
Sensors are reversed. Reinstall sensors, HP sensor
Sensors contaminated. Capillary tubing closed. Transmitter inoperative.
Capillary tubing closed.
to actuated instrument technical manual.
Raise/lower upper sensor. Raise/lower transmitter (single sensor system).
to top of tank.
Clean sensors carefully. Replace tube.
Replace parts, see actuated instrument technical manual.
Clean sensors carefully.
Open or replace.
16
Page 17
Model 351/352/353 Liquid Level Systems Section 4

Section 5—Parts List

General

The component parts of the actuated instrument are listed and identied in the technical manual for that instru ment. Component parts are called out in gures and listed by sensor type in the corresponding tables.
Sensor Type Table Reference
Model 351 Sensor, 500 psi (3.5 MPa) 5.1 page 18
Model 351 Sensor, 3000 psi (20.7 MPa) 5.2 page 20
Model S048 Sensor 5.3 page 22
Model 353 Sensor 5.4 page 24
Fill -Valve Assembly 5.5 page 26
IMPORTANT: O-rings should be examined anytime the seal is opened. They should be
replaced whenever:surfaces are damaged or deteriorated, “squeeze” is
less than 0.010 in. (0.25 mm), or sealing areas have at surfaces.
17
Page 18
Section 4 Model 351/352/353 Liquid Level Systems
18
NOTE: Mounting bracket No. 9 may be reversed or rotated to obtain the desired configuration.
Table 5.1—Model 351 Sensor Assembly
500 psi (3.5 MPa)
Item Description Part No. Qty per System**
351 352
1* O-ring 1 2
EPT 9A-C0001-1074R
Viton 9A-C0001-0131R
2 Plate, Bottom, SST 9A-C0351-0012C 1 2
3 Protective Spring, for 1/4” O.D.
Tubing, SST
4 Tubing, 1/4” O.D. Capillary, SST 9A-C0700-1014P As Required As Required
5 Bellows Assembly 1 2
SST 9A-C0351-0001B
Inconel 9A-C0351-1031B
6 Sensor Housing 1 2
1” NPT 9A-C0351-0014C
3/4” NPT 9A-CS696-0231Z
7 Vent Fitting 1 2
1/4 NPT Plug 9A-C0199-0214C
1/4 NPT Plug (drilled for Lock­wire)
3/8” Tube Fitting 9A-C0505-1029M
3/8” Tube Fitting Plug 9A-C0600-1012L
8* Retainer Ring, SST 9A-C0087-1007T 1 2
9 Bracket, Mounting 9A-CS778-0078Z 1 2
10 Process Connection Tube Fitting 1 2
9A-C0305-1001C As Required As Required
9A-C0224-0272C
18
3/8” Tube 9A-C0505-1028M
Page 19
Model 351/352/353 Liquid Level Systems Section 5
Table 5.1—Model 351 Sensor Assembly
500 psi (3.5 MPa)
Item Description Part No. Qty per System**
351 352
1/2” Tube 9A-C0505-1070M
3/4” Tube 9A-C0505-1026M
11 Nut, SST 9A-C0353-1005C 1 2
12 Washer, SST 9A-C0353-1006C 1 2
13 Process Connection Adapter 1 2
3/8” Tube 9A-C0353-1010C
1/2” Tube 9A-C0353-1009C
3/4” Tube 9A-C0353-1008C
14* Lubricant, O-ring (not shown) 9A-C0002-1003U As Required As Required
15 Coupling, 1/4” O.D. Tubing (not
shown)
16 Nipples – Alternate Process
Connection to be used with a
ange (not shown)
1” Sched 40, 2” long, 316 SST 9A-CS696-0365C
1” Sched 40, 4” long, 316 SST 9A-CS696-0366C
1” Sched 40, 6” long, 316 SST 9A-CS696-0367C
1” Sched 40, 8” long, 316 SST 9A-CS696-0368C
1” Sched 80, 2” long, 316 SST 9A-CS696-0374Z
1” Sched 80, 4” long, 316 SST 9A-CS696-0373Z
1” Sched 80, 6” long, 316 SST 9A-CS696-0070Z
1” Sched 80, 8” long, 316 SST 9A-CS696-0351Z
¾” Sched 40, 8” long, 316 SST 9A-CS696-0371C
17 Flanges – Alternate Process Con-
nection to be used with a nipple (not shown)
1” Class 150, RF/SO, 316 SST 9A-C0059-1633T
1” Class 300, RF/SO, 316 SST 9A-C0059-1632T
1” Class 600, RF/SO, 316 SST 9A-C0059-1657T
1” Class 1500, RF/SO, 316 SST 9A-C0059-1693T
2:1 Class 150, RF/SO, 316 SST 9A-CS696-0137Z
2:1 Class 600, RF/SO, 316 SST 9A-CS696-0133Z
2:1 Class 1500, RF/SO, 316 SST 9A-CS696-0115Z
3/4” Class 150, RF/SO, 316 SST 9A-C0059-1632T
3/4” Class 600, RF/SO, 316 SST 9A-C0059-1656T
3/4” Class 1500, RF/SO, 316 SST 9A-C0059-1692T
1” Class 150, FF/SO, 316 SST 9A-CS696-0375C
2:1 Class 150, FF/SO, 316 SST 9A-CS696-0363T
18 Nut, Lock, SST 9A-C0353-1013C 1 2
*Recommended Spare Parts (EPT = Ethylene Propylene Terpolymer)
** Model 351 systems have a single sensor; Model 352 systems require two sensors.
9A-C0353-1022C As Required As Required
1 2
1 2
19
Page 20
Section 5 Model 351/352/353 Liquid Level Systems
21
NOTE: Mounting bracket No. 9 may be reversed or rotated to obtain the desired configuration.
Table 5.2—Model 351 Sensor Assembly
3000 psi (20.7 MPa)
Item Description Part No. Qty/System**
351 352
1* O-ring 1 2
EPT 9A-C0001-1074R
Viton 9A-C0001-0131R
2* Ring, Backup 1 2
EPT 9A-C0001-1116R
Viton 9A-C0001-1046R
3 Plate, Bottom, SST 9A-C0351-0018C 1 2
4 Protective Spring, for 1/4” O.D.
Tubing, SST
5 Tubing, 1/4” O.D. Capillary, SST 9A-C0700-1014P As Required As Required
6 Screw, Socket Head Cap, 3/8”-24
x 1-1/8” long, SST
7 Bellows Assembly 1 2
SST 9A-C0351-0001B
Inconel 9A-C0351-1031B
8 Sensor Housing, 1” NPT 9A-C0351-0016C 1 2
9 Bracket, Mounting 9A-CS778-0078Z 1 2
10 Washer, Split-lock, SST 9A-C0003-1171K 6 12
11 Process Connection Tube Fitting 1 2
3/8” Tube 9A-C0505-1028M
1/2” Tube 9A-C0505-1070M
3/4” Tube 9A-C0505-1026M
9A-C0305-1001C As Required As Required
9A-C0220-1039J 6 12
20
Page 21
Model 351/352/353 Liquid Level Systems Section 5
Table 5.2—Model 351 Sensor Assembly
3000 psi (20.7 MPa)
Item Description Part No. Qty/System**
351 352
12 Nut, SST 9A-C0353-1005C 1 2
13 Washer, SST 9A-C0353-1006C 1 2
14 Process Connection Adapter 1 2
3/8” Tube 9A-C0353-1010C
1/2” Tube 9A-C0353-1009C
3/4” Tube 9A-C0353-1008C
15 Vent Fitting 1 2
1/4 NPT Plug 9A-C0199-0214C
1/4 NPT Plug (drilled for Lockwire) 9A-C0224-0272C
3/8” Tube Fitting 9A-C0505-1029M
16 Vent Fitting Plug – 3/8 Tube
Fitting Plug
17* Lubricant, O-ring (not shown) 9A-C0002-1003U As Required As Required
18 Coupling, 1/4” O.D. Tubing (not
shown)
19 Nipples – Alternate Process Con-
nection to be used with a ange
(not shown)
1” Sched 40, 2” long, 316 SST 9A-CS696-0365C
1” Sched 40, 4” long, 316 SST 9A-CS696-0366C
1” Sched 40, 6” long, 316 SST 9A-CS696-0367C
1” Sched 40, 8” long, 316 SST 9A-CS696-0368C
1” Sched 80, 2” long, 316 SST 9A-CS696-0374Z
1” Sched 80, 4” long, 316 SST 9A-CS696-0373Z
1” Sched 80, 6” long, 316 SST 9A-CS696-0070Z
1” Sched 80, 8” long, 316 SST 9A-CS696-0351Z
20 Flanges – Alternate Process Con-
nection to be used with a nipple (not shown)
1” Class 150, RF/SO, 316 SST 9A-C0059-1633T
1” Class 300, RF/SO, 316 SST 9A-C0059-1632T
1” Class 600, RF/SO, 316 SST 9A-C0059-1657T
1” Class 1500, RF/SO, 316 SST 9A-C0059-1693T
2:1 Class 150, RF/SO, 316 SST 9A-CS696-0137Z
2:1 Class 600, RF/SO, 316 SST 9A-CS696-0133Z
2:1 Class 1500, RF/SO, 316 SST 9A-CS696-0115Z
21 Nut, Lock, SST 9A-C0353-1013C 1 2
*Recommended Spare Parts (EPT = Ethylene Propylene Terpolymer)
** Model 351 systems have a single sensor; Model 352 systems require two sensors.
9A-C0600-1012L 1 2
9A-C0353-1022C As Required As Required
1 2
1 2
21
Page 22
Section 5 Model 351/352/353 Liquid Level Systems
NOTE: Mounting bracket No. 7 may be reversed or rotated to obtain the desired configuration.
Table 5.3—Model S048 Sensor Assembly
Item Description Part No. Qty/System**
351 352
1 Sensor Housing, SST 1 2
1” NPT (L-bracket mounting) 9A-CS048-0007Z
1” S/O (ange mounting) 9A-CS048-0002Z
2 Sensor Bellows Assembly 1 2
SST 9A-C0351-0001B
Inconel 9A-C0351-1031B
3* Test Assembly 9A-CS048-0018B 1 2
4 Sensor Adapter, SST 9A-C0353-1010C 1 2
5 Washer, SST 9A-C0353-1006C 1 2
6 Nut, SST 9A-C0353-1005C 1 2
7 Bracket, Mounting 9A-CS778-0078Z 1 2
8 O-ring, 014, EPT 9A-C0001-1050R 2 4
9 Nut, SST 9A-CS048-0041C 1 2
10 Protective Spring, for 1/4” O.D.
Tubing, SST
11 Tubing, Capillary, 1/4” O.D., SST 9A-C0700-1014P As Required As Required
12 Washer, SST 9A-C0003-0089K 1 2
13 Spacer, SST 9A-CS048-0004Z 1 2
14* Lubricant, O-ring (not shown) 9A-C0002-1003U As Required As Required
15 Coupling, 1/4” O.D. Tubing (not
shown)
9A-C0305-1001C As Required As Required
9A-C0353-1022C As Required As Required
22
Page 23
Model 351/352/353 Liquid Level Systems Section 5
Table 5.3—Model S048 Sensor Assembly
Item Description Part No. Qty/System**
351 352
16 Nipples – Alternate mounting
to be used with a ange (not
shown)
1” Solid, 2” long, 316 SST 9A-CS696-0065Z
1” Solid, 6” long, 316 SST 9A-CS696-0151Z
17 Flanges – Alternate mounting
to be used with a nipple (not shown)
1” Class 150, FF/SO, 316 SST 9A-CS696-0375C
2:1 Class 150, FF/SO, 316 SST 9A-CS696-0363T
* Recommended Spare Parts (EPT = Ethylene Propylene Terpolymer)
** Model 351 systems have a single sensor; Model 352 systems require two sensors.
1 2
1 2
23
Page 24
Section 5 Model 351/352/353 Liquid Level Systems
0.192/0.197 in. (4.9/5.0 mm) ID
NOTE: Mounting bracket No. 7 may be reversed or rotated to obtain the desired configuration.
Table 5.4—Model 353 Sensor Assembly
Item Description Part No. Qty
1 Sensor Housing, SST 9A-C0353-1133B 1
2* Gasket, Housing, Nickel 9A-C0353-1058C 1
3 Screw, Socket Head Cap, 3/8”-24 x 1-1/2”
long, SST
4* O-ring, EPT 9A-C0001-1074R 1
5* Ring, Backup, EPT 9A-C0001-1116R 1
6 Bellows Assembly, SST 9A-C0353-1036B 1
7 Bracket 9A-CS778-0078Z 1
8 Washer, SST 9A-C0353-1006C 1
9 Nut, SST 9A-C0353-1005C 1
10 Process Connection Tube Fitting 1
3/8” Tube 9A-C0505-1028M
1/2” Tube 9A-C0505-1070M
3/4” Tube 9A-C0505-1026M
11 Washer, Split Lock, 3/8”, SST 9A-C0003-1171K 12
12 Plate and Pigtail Assembly 9A-C0353-1050B 1
13 Plug, SST 9A-C0353-1060C 1
14* O-ring, EPT 9A-C0001-1052R 1
15* O-ring, EPT 9A-C0001-1053R 1
9A-C0220-1028J 12
24
Page 25
Model 351/352/353 Liquid Level Systems Section 5
Table 5.4—Model 353 Sensor Assembly
Item Description Part No. Qty
16 Fill Valve & Tee Assembly (See Figure 5-5) 9A-C0351-1044B 1
17* Lubricant, O-ring (not shown) 9A-C0002-1003U As Required
18 Process Connection Adapter 1
3/8” Tube 9A-C0353-1010C
1/2” Tube 9A-C0353-1009C
3/4” Tube 9A-C0353-1008C
19 Adapter, 1/4” NPT x 3/8” Tube, SST 9A-C0505-1029M 1
20 Plug, 3/8” Tube, SST 9A-C0600-1012L 1
21 Adapter, Capillary Tubing, 1/4” O.D. x 3/16”
O.D., SST
22 Capillary, Armored, 3/16” O.D., 0.049” Wall,
200 ft (61 m) in length
23 Sleeve, Female 3/16” O.D. Tubing Coupling
(not shown)
24 Sleeve, Male, 3/16” O.D. Tubing Coupling
(not shown)
25 1” Sched. 160, 316L SST, 9” long alternate
process connection (not shown)
*Recommended Spare Parts (EPT = Ethylene Propylene Terpolymer)
9A-C0353-1080C 1
9A-C0353-1090B As Required
9A-C0353-1092C As Required
9A-C0353-1094C As Required
9A-C0353-1059C 1
25
Page 26
Section 5 Model 351/352/353 Liquid Level Systems
(Part of Fill Valve & Tee Assembly, Part No. 9A-C0351-1044B)
Table 5.5—Fill Valve Assembly
Item Description Part No. Qty/Unit
1 Valve Body Assembly 9A-C0353-1014B 1
2 Valve 9A-C0353-1011C 2
3* O-ring, Backup, EPT, #8-006 9A-C0001-1062R 2
4* O-ring, EPT, #2-006 9A-C0001-1063R 2
5* Fill Valve Cover 9A-C0353-1012C 2
6* Lubricant, O-ring (not shown) 9A-C0002-1003U As Required
*Recommended Spare Parts (EPT = Ethylene Propylene Terpolymer)
26
Page 27
Model 351/352/353 Liquid Level Systems Section 5

Section 6—Dimensional Drawings

General

The drawings in this section show the outline dimensions for each sensor as-
sembly. These images are based on production drawing 9A-C0351-10782.
Liquid Level System Type Figure Reference
Model 351, 500 psi (3.5 MPa) 6.1 page 28
Model 351, 3000 psi (20.7 MPa) 6.2 page 29
Model S048 6.3 page 30
Model 353, 3000 psi (20.7 MPa) 6.4 page 31
27
Page 28
Section 5 Model 351/352/353 Liquid Level Systems
*DIMENSION VARIES WITH TUBE FITTING SIZE.
** AVAILABLE IN 3/8, 1/2, & 3/4 IN. TUBE SIZES. ALSO AVAILABLE WITH 3/4" & 1" PIPE WITH FLANGE CONNECTION.
4. MOUNTING BRACKET CAN BE ROTATED OR REVERSED AS NECESSARY TO SATISFY INSTALLATION REQUIREMENTS.
3. TORQUE BOTTOM PLATE CAP SCREWS TO 35 FT-LB [47 N-m].
2. TORQUE MOUNTING BRACKET NUT TO 147.5 FT-LB [200 N-m].
1. ALL DIMENSIONS ARE ± 0.13 IN. [3.2 MM] UNLESS OTHERWISE NOTED.
28
Figure 6.1—Model 351 sensor, 500 psi (3.5 Mpa)
Page 29
Model 351/352/353 Liquid Level Systems Section 6
*DIMENSION VARIES WITH TUBE FITTING SIZE.
** AVAILABLE IN 3/8, 1/2, & 3/4 IN. TUBE SIZES. ALSO AVAILABLE WITH 3/4" & 1" PIPE WITH FLANGE CONNECTION.
4. MOUNTING BRACKET CAN BE ROTATED OR REVERSED AS NECESSARY TO SATISFY INSTALLATION REQUIREMENTS.
3. TORQUE BOTTOM PLATE CAP SCREWS TO 35 FT-LB [47 N-m].
2. TORQUE MOUNTING BRACKET NUT TO 147.5 FT-LB [200 N-m].
1. ALL DIMENSIONS ARE ± 0.13 IN. [3.2 MM] UNLESS OTHERWISE NOTED.
Figure 6.2—Model 351 sensor, 3000 psi (20.7 MPa)
29
Page 30
Section 6 Model 351/352/353 Liquid Level Systems
30
Figure 6.3—Model S048 sensor
Page 31
Model 351/352/353 Liquid Level Systems Section 6
*DIMENSION VARIES WITH TUBE FITTING SIZE.
*** AVAILABLE IN 3/8, 1/2 & 3/4 TUBE SIZES. ALSO
AVAILABLE WITH 9" LONG 1" SCHEDULE 160 PIPE.
4. MOUNTING BRACKET CAN BE ROTATED OR
REVERSED AS NECESSARY TO SATISFY
INSTALLATION REQUIREMENTS.
3. TORQUE BOTTOM PLATE CAP SCREWS TO
35 FT-LB [47 N-m].
2. TORQUE MOUNTING BRACKET NUT TO
147.5 FT-LB [200 N-m].
1. ALL DIMENSIONS ARE ± 0.13 IN. [3.2 MM] UNLESS
OTHERWISE NOTED.
Figure 6.4—Model 353 sensor, 3000 psi (20.7 MPa)
31
Page 32
Section 6 Model 351/352/353 Liquid Level Systems
32
Page 33
Model 351/352/353 Liquid Level Systems Section 6
Product Warranty
A. Warranty
Cameron International Corporation (“Cameron”) warrants that at the time of shipment, the products manufactured by Cameron and sold hereunder will be free from defects in mate­rial and workmanship, and will conform to the specications furnished by or approved by Cameron.
B. Warranty Adjustment
1. If any defect within this warranty appears, Buyer shall notify Cameron immediately
2. Cameron agrees to repair or furnish a replacement for, but not install, any product
which within one (1) year from the date of shipment by Cameron shall, upon test and examination by Cameron, prove defective within the above warranty.
3. No product will be accepted for return or replacement without the written authoriza-
tion of Cameron. Upon such authorization, and in accordance with instructions by Cameron, the product will be returned shipping charges prepaid by Buyer. Replace-
ments made under this warranty will be shipped prepaid.
C. Exclusions from Warranty
1. THE FOREGOING WARRANTY IS IN LIEU OF AND EXCLUDES ALL OTHER
EXPRESSED OR IMPLIED WARRANTIES OF MERCHANTABILITY, OR FIT­NESS FOR A PARTICULAR PURPOSE, OR OTHERWISE.
2. Components manufactured by any supplier other than Cameron shall bear only the
warranty made by the manufacturer of that product, and Cameron assumes no respon-
sibility for the performance or reliability of the unit as a whole.
3. “In no event shall Cameron be liable for indirect, incidental, or consequential dam-
ages nor shall the liability of Cameron arising in connection with any products sold
hereunder (whether such liability arises from a claim based on contract, warranty, tort,
or otherwise) exceed the actual amount paid by Buyer to Cameron for the products
delivered hereunder.”
4. The warranty does not extend to any product manufactured by Cameron which has
been subjected to misuse, neglect, accident, improper installation or to use in violation
of instructions furnished by Cameron.
5. The warranty does not extend to or apply to any unit which has been repaired or
altered at any place other than at Cameron’s factory or service locations by persons not expressly approved by Cameron.
Product Brand
Barton® is a registered trademark of Cameron International Corporation (“Cameron”).
33
Page 34
Section 6 Model 351/352/353 Liquid Level Systems
34
Page 35
35
Page 36
www.c-a-m.com/measurement
HEADQUARTERS (HOUSTON, TX)
1.281.582.9500
UNITED STATES
1.800.654-3760
CANADA
1.403.291.4814
ASIA PACIFIC
+603.7954.0145
MIDDLE EAST & NORTH AFRICA
971.4802.7700
INDIA
91.982.2431686
EUROPE, CASPIAN, RUSSIA & S. AFRICA
+44.1892.518000
LATIN AMERICA
+55.21.2172.9714
Loading...