Documentazione
Tecnica
OOP DETECTOR
L
SMA - SMA 2 - SMA 230
T20
ev. 3.0
r
1/2010
0
©
CAME
CANCELLI
AUTOMATICI
119RT20-EN
Operating instructions for Installing and Start-up (Translation)
Safety instructions
1
These devices and their accessories may only be operated in compliance with the operating instructions (intended use)!
These devices and their accessories may only be commissioned by trained and qualified personnel.
These devices may only be operated with the intended operating voltages and parameters.
If malfunctions occur that cannot be rectified, shut down the device and send it in for repair.
These devices are only allowed to be repaired by the manufacturer. Tampering and alterations are not permitted. This will invalidate all guarantee and
warranty claims.
Mounting and electrical connection
2
SMA is mounted directly onto a standardized 35-mm mounting rail.
The terminals for all connections are coded pluggable terminals.
The loop connection wiring to the loop detector must be twisted at least 20 times per meter.
Please wire the device in accordance with the terminal assignment. Make sure the terminals are assigned correctly.
ENGLISH
Supply voltage
Value and parameter setting options
3
Loop connection
1-channel device
Loop connection
2-channel device
Alerting Output 2nd output
General
The settings of the devices in this chapter are shown and explained for the 1-loop device. The settings for loop 2 of a 2-loop device should be made using
the corresponding method.
LCD display and controls
3.1
Standard display
1-loop device
3.2
Basic functions 0 (see Table 4.1a for settings)
Standard display
2-loop device
Control button Control button
Explanation of the LCD display
Function
Example:
Time
function set
Loop 1, output 1
Loop 2,
output 2
Example:
Parameter «h»
set
Explanation of the LED
Red: Start-up phase
Green: Operation
Red & green: Configuration
Flashing green: Loop activated
Flashing red: Error
Flashing red + green: Simulation
Parameters
1: Door and gate The assigned output relay picks up when the loop is activated and drops out when the loop returns to a non-activated condition.
2: Barrier The assigned output relay picks up when the loop is activated and drops out when the loop returns to a non-activated condition.
3: Quiescent current The assigned output relay drops out when the loop is activated and picks up again when the loop returns to a non-activated condition.
4: Direction logic Output 1 switches if an object moves from loop 1 to 2. Output 2 switches if an object moves from loop 1 to 2. Both loops must be
activated for a short time. The outputs are reset again when loop 2 returns to a non-activated condition. Both loops must have returned to a non-activated condition for another direction detection.
0: Loop 2 Loop 2 / output 2 can be deactivated in a 2-loop device.
Relay response to malfunctions (see chapter 6 Troubleshooting):
1.Door/gate
systems
A malfunctioncauses
the output relay to be
released. The alarm
relay drops out.
2. Barrier
A malfunctioncauses
the output relay to pick
up. The alarm relay
drops out.
3. Quiescent
current
A malfunctioncauses the
output relay to be
released. The alarmrelay
drops out.
4. Directionlogic
(2-loop device
only)
A malfunctioncauses
the output relays to be
released. The alarm
relay drops out.
1
Time functions 1, time unit 2 and time factor 3 (see Table 4.1a for settings)
3.3
The relaypicks up when the
loopis activated and drops
out when the loop is exited.
On delay:
The relaypicks up afterthe
timet when the loop is activated and drops out when
the loop is exited.
Off delay:
The relaypicks up when the
loopis activated and drops
out afterthe time t when the
loopis exited.
Activation pulse:
The relaypicks up when the
loopis activated and drops
out againafter the time t.
Sensitivity 4 (see Table 4.1a for settings)
3.4
he sensitivity 5 (=Sensitivity) of the loop detector can be adapted in 9 stages: 51 = Lowest sensitivity, 59 = Highest sensitivity,
T
Impulse by leaving the loop:
By leaving the loop,
the relaypicks up after
the time t, relaydrops out.
56 = Factory setting. The sensitivity setting depends on the frequencies (see chapter 3.6 Frequency).
.5
3
Automatic Sensitivity Boost ASB 5 (see Table 4.1a for settings)
ASB (=Automatic Sensitivity Boost). ASB is required in order to be able to recognise trailer drawbars after activation.
3.6
Frequency 6 (see Table 4.1a for settings)
Four different frequencies F1, F2, F3, F4* can be set in order to avoid interference when using several loop detectors. These settings influence the
sensitivity (the sensitivity can be set in the range 1–7 for frequencies F1 to F3). F2 to F4 can be set for inductance < 150 µH and only F4 can be set for
inductance < 75 µH.
3.7
Direction logic7 (see Table 4.1a for settings)
The direction logic function can only be used with a 2-loop device. Direction logic must have been set in the basic function (see chapter 3.2). Detection
can be performed from: ➝ Loop 1 to loop 2 ➝ From loop 2 to loop 1 ➝ from both directions
3.8
Output 2 8 (see Table 4.1b for settings)
In a device with 2 outputs, output 2 can be either activated or deactivated. In ProLoop 11, output 2 can also be set as an alarm output.
3.9
Protection against power failure 9 (see Table 4.1a for settings)
Basic function 2 «Barrier systems» or 3 «quiescent current» must be set for this function.
P 1 = Protection against power tailure activated: The sensitivity is restricted to 1–5 and the time function to h.
3.9.1
Signal characteristics with protection against power failure active (Function 9 = 1)
For Activation (e.g. Barriers)
Basic function 0 = 2 Barrier systems
Without power Initialisation Free Occupied Free
For Safeguarding (e.g. Barriers, bollards)
Basic function 0 = 3 Quiescent current
Without power Initialisation Free Occupied Free
2
Changeover from operation to configuration mode
4
1- loop device
Display after start-up:
Touch the «Mode» button once
to change to configuration
mode
2- loop device
Display after start-up:
Touch the «Mode» button once
to change to configuration
mode
Loop 1 is
selected
Loop 2 is
selected