Camden Door Controls CV-634W Installation Instructions

Model CV-634W
Piezo Keypad W/ Wiegand Output
Installation Instruction
Protocol: Wiegand 26
Power Supply: 12 to 28 VDC
Power Standby Consumption: less than 30 mA
(40mA when illuminated)
Mounting: Single Gang Switch Box, or directly to the wall.
Temperature: - 40° to + 70°C
CLICK-N-LOCK mounting screw protection.
When the LED control input is pulled low, the GREEN LED will be ON and the RED LED will be OFF. When the input goes high the RED LED is ON and the GREEN LED is OFF.
The RED LED will ash with each key press. The LED control
input is pulled to the internal +5v with a 2.2K resistor.
The data is sent at 1 msec per bit with a pulse duration of 50
usec. A Buzzer beeps with each key press.
26 BIT WIEGAND SPECIFICATIONS:
WIRING COLOR FUNCTION ELECTRICAL FUNCTION
RED Input Voltage (+) 8-25 VDC
BLACK Input Voltage (-)
GREEN Data 0 Open drain, 2.2K pull-up to internal +5V
WHITE Data 1 Open drain, 2.2K pull-up to internal +5V
BROWN LED Input ‘LOW’: LED=green, ‘OPEN’: LED=red
BLUE CCTV output
VIOLET Housing Ground
ORANGE Buffered Input ‘LOW’: Hold
GREY Tamper Output Open drain, max 0.25A, ‘LOW’ when light sensed
Open drain, max 0.25 A activated with
each key for 30 Sec.
NOTES:
Model CM-634W Piezo Keypad W/ Wiegand Output Manual
1. Wiegand keypads are programmed with default Site Code “000”.
To change this Site Code perform the following functions:
Disconnect the power for a minimum of 10 Sec.
• Connect Power.
Perform the following functions within 3 Sec. Of applying power:
Enter * on Keypad. / Keypad enters program mode (Red Led ashing)
• Enter new Site Code followed by the # sign. /
The new Site Code is assigned
2. Blue Wire PRESSING any key on the keypad will generate a 30 second 0.25 amp intermittent duty grounding output.
3. Orange Wire When the Hold Line, Orange wire, is pulled
“low”, any codes entered on the keypad are stored in the
buffer. When the Hold Line is released to a logic “high” - the buffered code data is sent.
4. Grey Wire When the photodiode senses ambient light, the grey wire is pulled “LOW”
This Photodiode is mounted on the back of the Keypad. When installing this unit be careful not to damage the Photodiode.
5. An error code is generated by any of the following: a) Pressing the # key with no preceding digits; b) Pressing any number of only zero’s prior to pressing the # key, or; c) Pressing 65,535 or any number above 65,535. An Error Code will send all binary l’s to your pane1.
DO NOT Program your panel to accept code number 65,535.
Questions?
Call Camden tech support @ 1-877-226-3369
Push Buttons Keypads Strikes Magnetic Locks Key Switches Relays & Timers Access Control
5502 Timberlea Blvd., Mississauga, ON Canada L4W 2T7
www.camdencontrols.com Toll Free: 1.877.226.3369
File: CV-634W Instructions..indd- Rev1 Revised: July 4th, 2014