Burkert TAT002 User Manual [en, de, fr]

Operating Instructions
Bedienungsanleitung
Instructions de Service
Type 0911
3 stage controller
3-Punkt-Regler
3 Régulateur Ponctuel
Id. No. 788 267
788 270
We reserve the right to make technical changes without notice. Technische Änderungen vorbehalten. Sous resérve de modification techniques.
© 2004 Bürkert Werke GmbH & Co.
Operating Instructions 0509/03_EU-ml_00804610
3-STAGE CONTROLLER
TYPE 0911
1 GENERAL INFORMATION ........................................................................................................................ 2
1.1 Symbols ......................................................................................................................................................... 2
1.2 Safety notes ................................................................................................................................................ 2
1.3 Scope of delivery ...................................................................................................................................... 3
1.4 Warranty provisions ............................................................................................................................... 3
2 SYSTEM DESCRIPTION ............................................................................................................................ 4
2.1 General description ................................................................................................................................. 4
2.2 Operation ...................................................................................................................................................... 4
2.3 Before the installation ............................................................................................................................. 7
2.4 Control ............................................................................................................................................................ 8
2.5 Parameters ................................................................................................................................................ 10
2.6 Controlling the loads 13
3 TECHNICAL DATA .....................................................................................................................................14
4 ASSEMBLY, INSTALLATION AND COMMISSIONING .......................................................... 15
4.1 General information regarding the installation and operation ......................................... 15
4.2 Assembly .................................................................................................................................................... 15
4.3 Electrical connections .......................................................................................................................... 16
english
5 HOT-KEY FUNCTION ................................................................................................................................. 18
6 FACTORY SETTING .................................................................................................................................. 19
7 MAINTENANCE ............................................................................................................................................21
8 REPAIR WORK .............................................................................................................................................. 21
8.1 Faults.............................................................................................................................................................21
8.2 Ordering table for basic unit/accessories ................................................................................ 22
0911 - 1
1 GENERAL INFORMATION
1.1 Symbols
The following symbols are used in these operating instructions:
marks a work step that must be carried out.
ATTENTION!
english
NOTE indicates important additional information,
1.2 Safety notes
Please observe the notes in these operating instructions together with the conditions of use and permitted data that are specified in the data sheets of the 0911 controller, so that the device will function perfectly and will have a long service life.
• Keep to the standard engineering rules when planning and operating the device!
• Installation and maintenance work may only be carried out by specialist personnel using the correct tools!
• Observe the current regulations on accident prevention and the safety regulations for electrical devices during the operation and maintenance of the device!
• Comply with the intended usage of the device.
• Only operate the device with its housing fitted.
• Before connecting the device, check that the power supply corresponds to the values printed on the device.
• Check that the connections are correct before switching on the device.
• Observe the maximum load of the relay contacts (see technical data).
• Ensure that all sensors are installed with sufficient separation from voltage­conducting lines. This will avoid incorrect temperature readings and will protect the device from voltage interference at the sensor inputs.
• For applications in the industrial sector with critical environments, switch an RC element in parallel (FT1).
• Always switch off the mains supply before carrying out manipulations on the system.
• Take suitable measures to exclude unintended operation and damage by unauthorised operation!
indicates information which, if ignored, could lead to a risk to your health or to the functionality of the device.
tips and recommendations.
2 - 0911
• Please observe the prescribed environmental conditions with regard to dampness and temperature limits. Malfunctions cannot be excluded if these conditions are not complied with.
• Call in your authorised Bürket sales centre in case of doubt or faulty functioning.
In the case of the non-observance of these notes or of unauthorised manipulation of the device, we will accept no liability, and the guarantee on the device and its accessories will become void!
1.3 Scope of delivery
Immediately after receiving the delivery, ensure that the contents agree with the scope of the delivery. This includes:
• 1 Type 0911 controller
• 1 set of operating instructions (where required, on a data carrier)
• 1 front seal
• 2 Mounting clamps
In case of discrepancy, please contact our Customer centre immediately.
Bürkert Steuer- und Regelungstechnik
or your Bürkert Sales Centre.
Service-Abteilung
Chr.-Bürkert-Str. 13-17
D-76453 Ingelfingen
Tel. : 07940-10111
1.4 Warranty provisions
Bürkert provideds a guarantee of one year on the correct functioning of the controller, under the precondition that the device is employed for its intended use and under compliance with the specified conditions for use.
If the functions of the device are not in order, the respective device will be repaired free of charge or will be replaced.
ATTENTION!
The warranty only covers the the controller and its components, but does not cover consequential damage of any kind that could arise from the failure or malfunctioning of the device.
english
0911 - 3
2 SYSTEM DESCRIPTION
2.1 General description
3-point or neutral zone controller, 74 x 32 mm, with predefinable control function (e.g., heating/cooling or moisten/dehumidify)
The following models are available:
TYPE Configurable Input Parameter UDM
english
TU
Temperature controller
AU
Control device with current/voltage input
2.2 Operation
Output LEDs
Alarm LED
PTC, NTC, Pt100 Thermoelements J, K, S
4 ... 20 mA 0 ... 1 V 0 ... 10 V
LED1
LED 2
(Defined by display unit)
UDM = °C UDM = °F
0 = °C; 1 = °F 2 = % RH 3 = bar 4 = PSI 5 = without units
up­wards
down­wards
SET button
BUTTONS
SET1 Display of Set-value 1
SET2 Display of Set-value 2
4 - 0911
Changing and confirming a default during the programming phase
BUTTON COMBINATIONS
+
Locking and unlocking the keypad
SET1+ Selecting the programming level
SET1+ Return to the room temperature display
LED MESSAGES
LED Mode Meaning
on Output 1 active
on Output 2 active
LED1 blinks Programming level (blinks together with LED2) LED2 blinks Programming level (blinks together with LED1)
E.S. on
Alarm LED on
SWITCH DEVICE ON/OFF
Energy-saving mode (second set-value) has been activated by the digital input
- Signals an Alarm state
- If you are in the lower programming level "Pr2", which can only be accessed using a password, the lighting up of the Alarm LED signals that the displayed parameters can also be accessed in the first level "Pr1" (without password).
english
SET-VALUE DISPLAYS
Hold the SET1 button down for at least 4 sec (only
for parameter OnF = yes).
Briefly press the SET button once. The set-value
display appears in the display.
Briefly press the SET button again, or wait 5
seconds in order to display the room temperature.
0911 - 5
english
CHANGING SET-VALUE 1 / SET-VALUE 2
Hold down the SET button for 2 seconds. Change the set-value within 10 s with the or
buttons.
You can save the new set-value by briefly pressing
the SET button or by waiting 10 seconds.
ENTER PROGRAMMING LEVEL
Hold down the SET1 + button for at least 3
seconds.
Select with Pr2 and then confirm with the SET1
button.
Enter the password 321 and then confirm with the
SET1 button.
Enter the „3“ and then 1x SET1 button Enter the „2“, and then 1x the SET1 button Enter the „2“, and then 1x the SET1 button
You are now in the Parameter List.
USER LEVEL PR1
Hold down the SET1 + button for at least 3
seconds. PR1 contains all the parameters that can be accessed by the user. The device shows the first parameter that is available in the user level.
SERVICE LEVEL PR2 (PASSWORD 321)
See:
Accessing the programming level
ADDING/REMOVING PARAMETERS IN THE USER LEVEL PR1
Accessing the programming level The status can be changed with the SET1 +
buttons. If a parameter is not visible in the PR1 level, this will
be indicated by an LED point.
6 - 0911
.
CHANGING THE DEFAULT PARAMETERS
Enter a desired value with SET + or . Then confirm with the SET button. Enter a desired parameter with or .
NOTE All the parameter values can only be seen by repeatedly
pressing the SET1 buttons.
LOCKING AND UNLOCKING THE KEYPAD
Hold down the buttons and for at least 3 seconds. The POF message appears on the display. The keyboard is locked. The POF message also appears if you hold down a button for longer than 3 s.
The keyboard will be unlocked if you hold down the buttons and for 3 s. POn appears in the display for a few seconds.
2.3 Before the installation
PREDEFINE THE SENSOR TYPE
The configurable input type is noted on the controller label. Please enter this input type if it does not corresponds to the connected sensor type.
Hold down the SET + buttons for 3 seconds. Select the parameter Pbc (sensor type) and then
confirm with the SET button to see the current default.
Type TU (temperature controller): J = Thermoelement J; Pt = Pt100;
C = Thermoelement K; Ptc = PTC; S = Thermoelement S; ntc = NTC
Type AU (control devices with voltage/current input):
cur = 4...20 mA; 0-1 = 0...1 V; 10 = 0...10 V Confirm the default with the SET button. Briefly switch off the power to the device.
english
0911 - 7
english
2.4 Control
MEASUREMENT LIMITS FOR THE SENSOR TYPES
Sensor Lower limit Upper limit
NTC -40°C 110°C PTC -50°C 150°C
Pt100 -200°C 600°C
TcK 0°C 1300°C
TcJ 0°C 600°C
TcS 0°C 1400°C
TWO OUTPUTS INDEPENDENT OF ONE ANOTHER (OUC = IND)
Example:
Default for the set-values SET1 = 50°C und SET2 = 20°C. With parameter default OUC = ind, both set-values are completely independent of each other. The control function must also be predefined. For the control circuit No. 1 Par. S1C = in (heating, humidifying, etc.,) or S1C = dir (cooling, dehumidification, etc.). Also predefined for the control relay No. 2 (S2C = in or S2C = dir).
Example: ouC = ind, S1c = dir, S2c = dir
TWO OUTPUTS INDEPENDENT OF ONE ANOTHER (OUC = DIP)
3-STAGE CONTROLLER
Example:
Default for set-value SET1 = 50°C (for control circuit No. 1). Then predefine a number for SET2 = 5 Kelvin (Delta value). The resulting set-value is then SET2 = 55 °C (SET2 = SET1 + Delta-SET2). If SET1 is then increased, for example by 2 Kelvin to 52°C, SET2 increases to the same extent, i.e., also by 2 Kelvin to 57°C. Also define the control direction of the outputs via the parameters S1C and S2C. In the same way, the set-value default limits for SET2 result from LS2 = SET1 -Delta-LS2 and HS2 = +Delta-HS2.
8 - 0911
NEUTRAL ZONE CONTROLLER
Example:
Default for set-value SET1 = 50°C (for control circuit No. 1). In order to configure a neutral zone control behaviour, always predefine: SET2 = 0 Kelvin; LS2 = 0 and US2 = 0.
Configure the function of Relay 1 („uscita1“ in the following diagram): S1C = in (heating) and Hy1= -2 Kelvin).
Configure the function of Relay 2 („uscita2“ in the following diagram): S2C = dir (heating) and Hy2= +2 Kelvin).
Result (see following diagram):
SET1 = Set Point; db = Hy1 = Hy2
If the neutral zone SET1 - Hy1 is undershot, heating will take place (Relay 1 activated) until the set-value SET1 is reached. If the room temperature exceeds the neutral zone SET1 + Hy1, Relay 2 is activated (cooling) and will be switched off again at exactly SET1.
ON
english
OFF
NOTE
db db
Set point
Var iabl e
Different values can also be predefined in Hy1 and Hy2. In this way, the switch-off point can be changed within the neutral zone!
0911 - 9
2.5 Parameters
Control
Hy1
Hy2
english
LS1
LS2
US1
US2
S1C
S2C
AC
ouc
on
ono
Hysteresis 1
Hysteresis 2
Lowest set-value setting
Lowest set-value setting
Highest set-value setting
Highest set-value setting
Control function 1
Control function 2
Minimum switch-off period Dependency of the
set-values Minimum switch-on period Minimum delay
Switch hysteresis of Set-value 1 with positive or negative values. The default range is dependent on the input type. The parameter may not be entered as zero. The control function is predefined with S1C.
Switch hysteresis of Set-value 2 with positive or negative values(as Hy1). The control function is predefined with S2C.
Set-value limits 1 for operator
Set-value limits 2 for operator
Set-value limits 1 for operator
Set-value limits 2 for operator
in = inverted (Heating, humidifying) dir = direct (cooling, dehumidifying)
in = inverted (heating, humidifying) dir = direct (cooling, dehumidifying)
0 ... 250 sec relay switch-off period diP = dependent
ind = independent
0...250 sec relay switch-on period
0...120 min; minimum delay between two activations of the control relay.
Alarms
ALC
ALL
ALU
ALd
10 - 0911
Configuration Temperature alarm
Low temperature alarm
Over-temperature alarm
Alarm delay at temperature Overshoot/Undershoot
rE = relative to the set-value (in Kelvin) Ab = absolute values (in °C)
If SET - ALL is undershot, a low temperature alarm will be triggered after the delay time ALd.
If SET + ALU exceeded, a high temperature alarm will be triggered after delay time ALd.
0...999 min; Minimum time in which the conditions for an alarm situation must be present.
Alarms
ALH
Hysteresis for the Limit value alarms ALL and ALU
dAO
Alarm delay at with Mains ON
So1
Status of Control Relay 1 with sensor fault
So2
Status of Control Relay 2 with sensor fault
tbA
Status of the control relay after acknowledgement by of an alarm situation
AS
Configuration of the alarm relay at an alarm
Measured value display
LCI
Lower analog Display value (-1999...1999)
UCI
Upper analog display value (-1999...1999)
OPb
calibration of the sensor
rES
Resolution
UdM
Units
PbC
Type of sensor Temperature sensor U):
current/voltage input (AU)
P3F
Third terminal of a Pt100 sensor
Automatic alarm acknowledgement: With high alarm undershot by ALU - ALH and with low alarm with under shooting of ALL + ALH
0...23.5 hours; suppression of Alarms after commissioning.
oFF = opened on = closed
oFF = opened on = closed
oFF = Relay deactivated on = Relay activated
cL = Terminal 5-6 closed oP = Terminal 5-6 closed
scaling of the lower display value at Current input 4 mA or at Voltage input 0 V (only for the inputs 0-20 mA, 0-1V, 0-10 V)
Scaling of the upper display value at current input 20 mA or with voltage input 1 V and 10 V (only for the inpits 0-20 mA, 0-1V, 0-10 V)
regardless of the measurement range
in = only whole numbers dE = also tenths ce = hundreths
Display of the units directly in the illuminated display. Regardless of which controller type is being used: see
General description
Type of inout J = Thermoelement „J“; Pt = Pt100; C = Thermoelement „K“; Ptc = PTC; S = Thermoelement „S“; ntc = NTC cur = 4...20 mA; 0-1 = 0...1 V; 10 = 0...10 V
(if present) no = Pt100 2-wire wired yES = Pt100 3-wire wired
english
0911 - 11
english
Digital inputs
HES
Temperature increase/ Reduction
i1F
Function of the digital Input
i1P
Polarity of the digital input
did
Alarm delay time of the digital input (0...120 min)
Miscellaneous
Adr
Serial address RS485 (1...247)
OnF
Set device to STAND-BY
Ptb
Number of the parameter­table
rEL
Version
Pr2
Display of the parameters in Level Pr2
Set-value is increased/lowered by HES during an energy-saving phase Activation via digital input (i1F = Es).
EAL = external alarm; OFF = unused; bAL = serious external alarm; Es = Energy saving mode Start/Stop; onF = switch the device ON/OFF externally; C-H = reverse the control effect
CL: active with closed contact OP: active with opened contact
For i1F = EAL or i1F = bAL. The corresponding alarm then takes place display or message.
Address for XJ500 recording system. Identifies the device if it is linked into a ModBUS-compatible system.
no = not possible via keyboard yes = STAND-BY can be activated by holding down the SET button for at least 4 sec. If you want to change the set-value, hold down the SET button for approx. 2 sec.
only read-out value
only read-out value
display only
NOTE
12 - 0911
You can access hidden parameters by holding down the keys SET + for 3 sec in the programming level HY. The message Pr2 appears.
2.6 Controlling the loads
CONTROLLER OUTPUT
The control is dependent on the measurement temperature (= sensor temperature). Program the control direction (heating or cooling) with the parameters S1C and S2C.
S1C = dir Cooling Set = Set-value S1C = in Heating Hy = Switch hysterisis
COOLING
temperature
SET+HY
SET
t
compessor
ON
t
Parameter S1C = dir; The value HY has been preset to 2K in the factory.
If the temperature exceeds the value SET + HY, the compressor is switched on and will be switched off again when the temperature falls below SET.
HEATING
temperature
SET
SET-HY
t
heat
ON
english
t
Parameter S1C = in; The value HY has been preset to 2 K in the factory.
If the temperature falls below the value SET-HY, the controller output will be switched on and will be switched off again when SET is exceeded.
0911 - 13
3 TECHNICAL DATA
• Housing ABS, self-extinguishing
• Dimensions Front 74 x 32 mm, Depth 60 mm
• Assembly Panel-mounting unit for 29 x 71 mm cutout
• Protection class IP65 from front, only with front seal RG-C
• Connections Screw terminals
• Pipe cross-section ≤2.5 mm
english
• Auxiliary energy depending on model
• Power consumption max. 3 VA
• Display 3½ digits, red LED, height 12 mm
• Inputs configurable NTC / PTC or
• Relay outputs 2 x NO 8(3) A, 250 V AC + 1 x NC
• Data memory EEPROM
• Ambient temperature 0...+60°C / +32...+140°F
• Storage temperature -30...+85°C / -22...+185°F
• Air humidity 20...85% (non-condensing)
• Measurement range according to sensor
• Resolution 0.1°C or 1°F
• Accuracy at +25 °C better than 0.5% of the limit value of the
IP20
2
12...24 V AC/DC; ±10% 230 V AC; ±10%; 50/60 Hz
optional 110 V AC; ±10%; 50/60 Hz
NTC / PTC / Pt100 / Thermoelement J, K, S or 4... 20 mA / 0...1 V / 0...10 V
measurement range
14 - 0911
4 ASSEMBLY, INSTALLATION AND COMMISSIONING
4.1 General information regarding the installation and operation
ATTENTION!
NOTE
• Do not lay cables for inputs next to lines carrying voltage.
• Avoid heavy vibrations, aggressive gases, heavy soiling and damp.
• Before connecting the device, check that the power supply corresponds to the values shown on the rating plate.
• Observe the maximum loading of the relay contacts (see
Technical data
• Ensure that you install all sensors with sufficient separation from lines carrying voltage, in order to avoid incorrect temperature measurements and to protect the device from voltage interference over the sensor inputs.
).
4.2 Assembly
The device is designed for panel mounting in a cutout of 71 x 29 mm, and is secured with mounting brackets.
In order to ensure the IP65 front protection, a rubber seal must be fitted begind the front frame (optional with RG-C).
The ambient temperature for trouble-free operetion is in the range from 0 ... +60°C.
Ensure sufficient ventilation through the cooling slots.
english
Panel
Mounting bracket
0911 - 15
english
4.3 Electrical connections
Use cable with a cross-section of max. 2.5 mm2. The device is provided with the corresponding screw terminals.
Check the auxiliary energy before you connect the power supply (see
Technical data
Do not load the relay contacts higher than permitted. Where necessary, make use of a contactor.
Panel Mounting clamp
Front seal
).
16 - 0911
PIN ASSIGNMENT
12 V AC/DC or 24 V AC/DC
english
Standard signal input: 0...1 V; 0...10 V = 7(+), 9(-)
Thermoelement J, K, S = 7(+) - 9(-) sensor: Pt100 = 7 - 9(8) voltage supply: 24 V AC/DC = 11 - 12
230 V AC
Standard signal input: 0...1 V; 0...10 V = 9(+), 11(-)
Thermoelement J, K, S = 9(+) - 11(-) sensor: Pt100 = 9 - 11(10) voltage supply: 230 V AC = 7 - 8
4...20 mA = 7(+), 9(-)
4...20 mA = 9(+), 11(-)
0911 - 17
5 HOT-KEY function
DOWNLOAD (HOT-KEY CONTROL DEVICE)
Writing the stored parameter set of the HOT-KEY into the control device:
Switch off the POWER SUPPLY to the controller, or set it to STAND-BY. Insert the HOT-KEY up to the stop in the marked position on the controller. Re-activate the controller.
english
The default parameters of the HOT-KEY will be automatically written into the
controller. During this time, the DoL message blinks in the display. The programming prpcedure is finished after 10 sec, and normal operation starts automatically with the new parameter set.
The HOT-KEY can be removed.
The following messages are possible at the end of the data transfer:
end for a correct data transfer err for a failed data transfer
In this case, switch off the power to the device in order to repeat the procedure. If you want to cancel the procedure, simply remove the HOT­KEY.
UPLOAD (CONTROL DEVICE HOT-KEY)
Writing the current default parameters of the control device into the HOT-KEY:
Insert the HOT-KEY into the provided position when the controller is
switched on again. Operate 1x with . The message uPL is displayed. Press the SET1 button in order to start the data transfer. uPL starts to
blink. You can remove the HOT-KEY again after about 10 seconds.
The following messages are possible at the end of the data transfer:
end for a correct data transfer err for a failed data transfer
In this case, press the SET button again to repeat the procedure. If you
want to cancel the procedure, remove the HOT-KEY.
18 - 0911
6 FACTORY SETTING
1
PA
Description Range Default PE
SET1 Set-value 1 LS1 + US1 0 Pr1
SET2 Set-value 2 LS2 + US2 1 Pr1
HY1 Switch hysterisis 1
HY2 Switch hysterisis 2
LS1 Lowest set-value 1
LS2 Lowest set-value 2
US1 Largest set-value 1
US2 Largest set-value 2
dependent on measurement
range
dependent on measurement
range
Lower measurement range +
SET1
Lower measurement range +
SET2
Upper measurement range +
SET1
Upper measurement range +
SET2
-1 Pr1
-1 Pr1
min Pr2
min Pr2
max Pr2
max Pr2
S1C Control effect Output 1 in = inverse; dir = direct in Pr2 S2C Control effect Output 2 in = inverse; dir = direct in Pr2
Dependency of the set-
ouc
values
ind = independent;
diP = dependent
ind
Ac Delay time for the relay 0...250 sec 0 Pr2
Minimum switch-on time
on
for a relay
0...250 sec 0 Pr2
Minimum waiting time
between two consecutive
ono
activations of the same
0...120 min 0 Pr2
load
Alarm limits are absolute
ALC
values or related to the
rE = relative; Ab = absolute rE Pr2
set-value
ALL
ALU
ALH
ALd
dAO
1
Parameter
2
Programming level
Lower Alarm Limit
(ALC = rE; ALC = Ab)
Upper Alarm Limit
(ALC = rE; ALC = Ab)
Switch hysterisis for temperature alarms
Alarm delay time during
Alarm delay time after
the operation
commissioning
dependent on measurement
range
dependent on measurement
range
dependent on measurement
range
0...999 min 15 Pr2
0...23.5 h 1.3 Pr2
10 Pr2
10 Pr2
2Pr2
2
english
0911 - 19
english
1
PA
Description Range Default PE
So1 Output 1 for sensor error oFF = open; on = closed oFF Pr2
So2 Output 2 for sensor error oFF = open; on = closed oFF Pr2
tbA
AS
LCI
UCI
Alarm relay can be
acknowledged
Polarity of the Alarm
relay
Lower analog display
3
3
value
Upper analog display
value
Opb Sensor calibration
depending on measurement
no; yES yES Pr2
CL...oP oP Pr2
depending on sensor var. Pr1
depending on sensor var. Pr1
range
0Pr1
rES Resolution in = NO; dE = 0,1; cE = 0,01 in Pr2
Type TU: °C = °C, °F = °F;
UdM Units
Type AU: 0 = °C, 1 = °F; 2 = RH, 3 = bar, 4 = PS,
var. Pr1
5 = without display
Pt = Pt100; J = tcJ; c = tck;
PbC Type of sensor
S = tcS; Ptc = PTC;
ntc = NTC; 0.1 = 0...1 V;
var. Pr1
10 = 0...10 V; cur = 0...20 mA
P3F PT100; 3-wire no = no; yES =yes no Pr2
Configuration of the
i1F
i1P
did
digital input
Polarity of the digital
input
Alarm delay of the digital
input
c-H / oFF / off / HES /
EAL / bAL
cL = closed;
oP = open
EAL Pr2
cL Pr2
0...120 min 0Pr2
Adr Serial address for XJ500 RS485 adress 1 Pr2
OnF
Activate Standby
function
no = no; oFF = active no Pr2
Ptb Parameter table Read value - Pr2 rEL Software version Read value - Pr2
Pr2 Parameter access to Pr2 Read value 321 Pr1
2
1
Parameter
2
Programming level
3
Only for devices with voltage and current input
20 - 0911
7 MAINTENANCE
When operated in accordance with the instruction in this handbook, the 0911 controller is maintenance-free.
8 REPAIR WORK
8.1 Faults
ERROR MESSAGES
Message Cause Effect
PFo
PFc Sensor short-circuit
HA High temperature alarm
LA Low temperature alarm
EAL Digital input alarm Outputs remain unchanged
BAL Serious digital alarm All control outputs deactivated
STATUS OF THE ALARM RELAY
Sensor defective or not connected
Alarm relay ON; control circuit according to So1
Alarm relay ON; control circuit according to So1
Alarm relay ON; outputs remain unchanged
Alarm relay ON; Outputs remain unchanged
english
Device status AS = CL AS = OP
Device without power 5 - 6 closed 5 - 6 closed
Normal operation 5 - 6 closed 5 - 6 open
Alarm situation during
operation
5 - 6 open 5 - 6 closed
0911 - 21
Loading...
+ 53 hidden pages