Burkert SE 56 User Manual

OPERATING AND INSTALLATION MANUAL
SE 56
210_EN_BU_4_3_5X.d
INDEX
SE 56
q Introduction ________________________________________________________________________________pag.3
§ Symbol Used on the manual________________________________________________________________pag.3
q Technical characteristics _____________________________________________________________________ pag.4
§ Electrical characteristics ___________________________________________________________________pag.4
§ Environmental conditions of use ____________________________________________________________ pag.4
§ Operative temperature ____________________________________________________________________pag.4
§ Overall dimensions _______________________________________________________________________pag.5
Electrical connections ________________________________________________________________________pag.6
§ Grounding instructions ____________________________________________________________________pag.6
§ Power supply converter ___________________________________________________________________pag.6
§ Terminal block M1 for compact, separate and panel version ______________________________________pag.7
§ Electrical connections sensor-converter _______________________________________________________pag.8
q Inputs/outputs______________________________________________________________________________pag.9
§ Expansion modules (no rele module)________________________________________________________ pag.10
§ Expansion modules (rele module) __________________________________________________________ pag.11
§ Digital Input ___________________________________________________________________________ pag.12
§ On/Off output wiring (up to 1250 Hz) - low frequency __________________________________________ pag.15
§ On/Off output wiring (up to 12500 Hz) - high frequency ________________________________________ pag.15
§ Analogical output - 0\4÷20 mA____________________________________________________________ pag.15
q Start up and maintenance of the instruments _________________________________________________ pag.16
q How to access at the instrument functions ____________________________________________________ pag.17
§ Converter visualization pages _____________________________________________________________ pag.17
§ Converter visualization pages with currency enable ____________________________________________ pag.17
§ Flags interpretation and led _______________________________________________________________ pag.18
§ Converter key board _____________________________________________________________________ pag.19
§ Converters menues _____________________________________________________________________ pag.20
§ Functions description ____________________________________________________________________ pag.21
§ Access codes ___________________________________________________________________________ pag.24
§ Block levels ____________________________________________________________________________ pag.26
§ Access the configuration menu_____________________________________________________________ pag.26
q Programming functions _____________________________________________________________________ pag.27
q Batch ______________________________________________________________________________________ pag.35
§ Enable batch ___________________________________________________________________________ pag.35
§ Programming batch______________________________________________________________________ pag.35
§ Start / stop batch _______________________________________________________________________ pag.36
§ Important notes ________________________________________________________________________ pag.36
q Alarm messages ___________________________________________________________________________ pag.37
§ Causes and actions to be taken ____________________________________________________________ pag.37
§ Anomalies codes _______________________________________________________________________ pag.37
q Display rotation ______________________________________________________________________________ pag.38
APPENDIX 1
2
210_EN_BU_4_3_5X.d
This manual is integral part of the product. Read carefully the instructions contained
Techn
ical information and relative products in this manual could undergo modifications
The flow meter must be used for what it has been built for. The improper use, possible
ns of any not original
The manufacturer is considered responsible only if the instrument it’s used in his original
ATTENTION
WARNING
PRECAUTIONS
DANGER ELECTRIC SHOCK
INTRODUCTION
SE 56
since they give important indications for the safe use and maintenance.
without any previous notice.
tampering of the instrument or parts of it and substitutio components, make the warranty to decay automatically.
configuration.
Reproduction of the present manual and of any possible software supplied with the instrument is strictly forbidden.
Symbols Used in the manual
3
210_EN_BU_4_3_5X.d
q
The output 4÷20 mA and the output 24 Vdc are electrical
ly connected
* For discontinuous use, the installation of a heating resistance is necessary
SE 56
TECHNICAL CHARACTERISTICS
ELECTRIC CHARACTERISTICS
Classification of the instrument: class I, IP 67, category of installation II
Power supply
versions
HV 90÷265 Vac 44÷66 Hz 20W/25VA 0,25 A
LV 18÷45 Vac/dc 0-44÷66 Hz 20W/25VA 1,6 A
LLV 10÷35 Vdc 20 W 1,5 A
Power supply
voltage
Power supply
frequency
Pmax
current
Input/output are insulated up to 500V
INPUT/OUTPUT ISOLATION
ENVIRONMENTAL CONDITIONS OF USE
The instrument can be installed inside or outside buildings Altitude: from –200 a 6000 m (from -656 to 19685 feet) Humidity range: 0÷100% (IP 67)
q Line voltage range: (see table on technical characteristics)
OPERATING TEMPERATURE
CONVERTER
Ambient Temp.
Min. Max
°C °F °C °F
-20* -4* 60 140
4
max
210_EN_BU_4_3_5X.d
COMPACT V
ERSION
SE 56
OVERALL DIEMENSIONS
146
170
146
138
138
SEPARATE VERSION
146
170
146
138
230
138
25
PANEL VERSION
137.0
145.0
160.0
67.0
80.0
72.0
144.0
IP65 (OPTIONAL)
5
210_EN_BU_4_3_5X.d
an external protection for current overload (fuse
Panel version
For the correct operation of the meter it’s NECESSARY that sensor and liquid are
SE 56
GROUNDING INSTRUCTIONS
equipotential, so ALWAYS connect sensor and converter to the ground
Wall version
q Before connecting the power supply, verify that
(+)
L
M3
N
(-)
q ATTENTION: the converters on dc power
q For the wiring use only approved conductors,
q The power supply line must be equipped with
CONVERTER POWER SUPPLY
the mains voltage falls between the limits indicated on the tag plate
supply line are not protected against the inversions of polarity.
with fireproof properties.
L
(+)N(-)
M3
NOTE: characteristics of meter’s power supply, see page 4
or automatic line breaker with limiting capacity not greater than 10 A).
q In the proximity of the instrument Provide a
circuit breaker that must be easily accessible from the operator and clearly identified.
6
210_EN_BU_4_3_5X.d
TERMINAL BLOCK M
1 FOR COMPACT/SEPARATE VERSIONS
Dip switch for block levels enabling
TERMINAL BLOCK M1 FOR PANEL VERSIONS
Dip switch for block levels enabling
ELECTRICAL CONNECTIONS
SE 56
Power supply
IF2 socket
Signalling LED with light: interpretation at page 18
LOCK
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20
M1
262524232221
323130292827
M2
Dangerous voltage on block 12-13:
- 60 Vdc Max
- 250 V Max on commutation coils
Power supply
M1M2
Dangerous voltage on blocks 12-13:
- 60 Vdc Max
- 250 V Max on commutation coils
IF2 socket
26 25 24 23 22 21
32 31 30 29 28 27
M3
20 19 18 17 16 15 14 13 12 11
10 9 8 7 6 5 4 3 2 1
7
M3
210_EN_BU_4_3_5X.d
SEPARATE VERSION
Max length of the cable C014 : 500 m
PREAMPLIFER VERSION
SE 56
ELECTRICAL CONNECTIONS SENSOR TO CONVERTER
TERMINAL BLOCK M1
1
C015
C016
2 3
4
11 12
13
E1 E2
C SH
SH B1
B2
ELECTRODES INPUT RS485 4-20mA
E1 E2 C SH + - B A + -
1 2 3 4 5 6 7 8 9
11 12 13 14 15 16 17 18 19 20
Sudden movements of the electrodes cable, can cause noises on measure
Max length of cable: m 20
From pin 1 to pin 5 cables connected to the sensor
123456789
Cavo 1 Cavo 2
Cavo 3 Cavo 12 Cavo 13
Cavo 6
Cavo 7
Cavo 8
Cavo 9
Cavo 10
C014
10
From pin 6 to pin 10 cables connected to the converter
10 (preamp.) 9 (preamp.) 8 (preamp.)
7 (preamp.) 6 (preamp.)
11 12
13
8
OUT2OUT124VCOILS 24V
1 2 3
4
10
-ECEC+SHB2B1SH
1 (E1) 2 (E2) 3 (C)
4 (SH) 11 (SH)
12 (B1) 13 (B2)
210_EN_BU_4_3_5X.d
ME200:
2 programmable on/off outputs
1 programmable on/off output + 1
1 0/4…20mA output + 2
1 RS232 port + 2 programmable
rt + 2 programmable
SC:
Cable shield, electrically connected to
Input terminal of the signal “CLEAR TO
E
Output terminal of the signal “TRASMIT
Terminal “SIGNAL GROUND” common to
Terminal connected with the COLLECTOR of
INPUT/OUTPUT
OPT
IONAL MODULE (NO RELE MODULE)
SE 56
q
q ME201:
high frequency output
q ME202:
programmable on/off output
q ME203:
on/off outputs
q ME204: 1 RS232 po
on/off outputs + 1 0/4…20mA out
q ME220: see the manual
LEGENDA
ground and to the casing
CTS:
SEND” of the RS232 port
RD: Input terminal of the signal “RECEIV DATA” RS232 port
TD:
DATA” of the RS 232 port
SG:
all signals of the RS232 port
C:
the transistor of the on/off output
OUT 3 E C
RS 232
CTS RD
TD
SG
21 22 23 24 25 26
20
(M1)
27 28 29 30 31 32
- + INP2
E C
OUT 4
SC
- +
4..20mA
9
210_EN_BU_4_3_5X.d
ME205:
2 relay outputs with 1 NO contact + 1
INPUT/OUTPUT
OPTIONAL RELE’ MODULE
SE 56
LEGENDA
NC contact each, 2A 60Vac, 60W/125Va
ME207: 2 relay outputs with 1 NO contact + 1 NC contact each, 2A 250Vac, 60W/125Va
q SC: Cable shield, electrically connected to
ground and to the casing
q C: relay – common
q NC: Normally closed contact
q NO: Normally open contact
OUT 4
C NC
NO
OUT 3
C NC
NO
OUT 3
NO NC
C
OUT 4
NO NC
C
26 25 24 23 22 21
14
(M1)
21 22 23 24 25 26
32 31 30 29 28 27
SC
10
210_EN_BU_4_3_5X.d
DIGITAL INPUT
The functions
Functions that act directly on the inputs independently from the select input
only assignable functions to the input 1 and only to the input 2 which they
The list of such functions is suitable in the tab at page 36.
SE 56
External power supply
10 K
3/40 Vdc (ON) 0/1,5 Vdc (OFF)
5 (+)
6 (-)
Internal power supply
+24
10 K
15
5
6
0
20
1) only assignable functions to the input 1 (page 12)
2)
3)
Remember that the activation of any functions of batch automatically disable the other.
referring to the inputs could be divided in three groups:
(page 13)
interact between them (some examples to page 14)
11
210_EN_BU_4_3_5X.d
OPERATION ON INPUT ON/OFF
Auto-calibration
Reset totalizes
Block totalizes
Totalizers active
Necessary conditions for enabling the function
Tmin<T<1sec. = autocalibration
T > 1 sec. = Auto zero
1 e/o 2 DISABLED
Range change
N.B.: THE FUNCTIONS ABOVE INDICAT
ED ARE ENABLED ONLY ON INPUT 1
SE 56
INPUT OPERATION STAGE (GENERIC FUNCTIONS)
0-1,5 V
0-1,5 V
AUTOCALIB. OFF
3-40 V
3-40 V
T
BLOCK
T
RESET
Tmin = 100ms
POS. 5.7 ENABLED
POS. 5.9 (batch on input 1) DISABLED
POS. 5.10 batch functions assign to input 2 (optional) DISABLED
Necessary conditions for enabling the function
POS. 5.1 ÷ 5.4 ENABLED at least one
N.B.: This function is even assignable to the input 2
Block totalizes
3-40 V
0-1,5 V
Necessary conditions for enabling the function
POS. 5.6 ENABLED
POS. 12.5 (auto-batch) DISABLED
POS. 12.7 (batch consent) DISABLED
Scale 2
3-40 V
0-1,5 V
Scale 1
Necessary conditions for enabling the function
POS. 5.8 ENABLE
POS. 5.9 (batch on input 1) DISABLED
POS. 5.10 batch functions assign to input 2 (optional) DISABLED
POS. 6.1-6.4 end-batch functions assign to output 2
Speed rate
Tmin
10 Hz 20 Hz 50 Hz 80 Hz
150 Hz
220 ms 110 ms
45 ms 30 ms 15 ms
ATTENTION: time T must be to Tmin
12
210_EN_BU_4_3_5X.d
Start batch from remote input
Start batch from consent (remote)
Start batch from remote input with
auto
-
Start batch from remote input with
automatic selection of formula 00/03
T= 100ms ±50ms for select the formula 00
T= 200ms ±50ms for select the formula 01
T= 300ms ±50ms for select the formula 02
T= 400ms ±50ms for select the formula 03
Start batch from remote input 1 reset p+
T BEETWEEN 1 E 4 = RESET TOTALIZER
T<1 = START E RESET TOTALIZER
0-1,5 V 3-40 V
INPUT
BATCH
INPUT
0-1,5 V
3-40 V
BATCH
3-40 V 0-1,5 V
5 Sec. <5 Sec.
INPUT
AUTO-BATCH BATCH
3-40 V
0-1,5 V
Formula selection
Start
OUTPUT
BATCH
INPUT
OUTPUT
3-40 V 0-1,5 V Start
BATCH Start
SE 56
OPERATION STAGE ON INPUT 1 OR 2 (BATCH FUNCTION)
Opening valve
Closing valve
Necessary conditions for enabling the function
q POS. 5.9 ENABLE or POS. 5.10 on batch q POS. 6.1 ÷ 6.4 on end batch
OUTPUT
Necessary conditions for enabling the function
OUTPUT
Opening valve
Closing valve
Opening valve
POS. 5.9 ENABLED or POS. 5.10 on batch POS. 6.1 ÷ 6.4 on batch POS. 12.7 (CONSENT MODE) ENABLED
Opening valve
batch enabled
Closing valve quantity to batch memorized
Closing valve
Necessary conditions for enabling the function
q POS. 5.9 ENABLED or q POS. 5.10 on batch q POS. 6.1 ÷ 6.4 on end batch q POS. 12.5 (auto-batch) ENABLED q POS. 12.7 (consent mode) q DISABLED
T
Opening valve
Closing valve
In case of stop batch from remote input the time of input
Necessary conditions for enable the function
INPUT
POS. 5.9 ENABLE or POS. 5.10 on batch POS. 6.1 ÷ 6.4 on end batch POS. 12.6 (automatic selection of formula) ENABLED POS. 12.7 (consent mode) DISABLED POS. 5.10 selection function for the formula 00/01 assigned to input 2 (optional) DISABLED
enabled on remote input 1
T
Necessary conditions for enabling the function
Opening valve
Closing valve
POS. 5.9 (batch on input 1) ENABLED POS. 6.1 ÷ 6.4 on AND BATCH POS. 5.2 (reset P+) ENABLED
N.B.: THE ACTIVATION OF BATCH FUNCTIONS ON INPUT 2
PREVENTS THE ACTIVATION OF BATCH FUNCTIONS ON INPUT 1
13
210_EN_BU_4_3_5X.d
OPERATION STAGE ON INPUT 1 AND 2 (BATCH FUNCTION)
Start batch on remote in
put 1 stop from output
B
lock and reset totalize from remote input 1
The block of the totalizer always
Necessary conditions for enabling the
The block of the totalizer always determines
Therefore both the presence of the consent or
The start of a new batch
. 5.10 function of batch assigned to
3-40 V
0-1,5 V
Start
BATCH FORMULA 00
BATCH FORMULA 01
BATCH
FORMULA 00
BATCH FORMULA 01
3-
40 V
INPUT 1
3-40 V 0-1,5 V
Start Start
NEW BATCH
INPUT 2
INPUT 2
INPUT 1
T<1 Sec.
3-40 V
0-1,5 V Start
RESET
T<1 Sec.
Start
INTERRUPTED BATCH
0-1,5 V
3-40 V BLOCK 0-1,5 V 3-40 V
Start
0-1,5 V 3-40 V BLOCK RESET T2
INPUT 1
INTERRUPTED BATCH
NEW BATCH
INTERRUPTED BATCH
SE 56
selection formula 00 o 01 from remote input 2
Necessary conditions for enabling the function
Opening valve
Closing valve
Opening valve
Closing valve
POS. 5.9 ENABLED POS. 6.1 or 6.4 on AND BATCH POS. 5.10 function of formula selection 00/01 assigned to input 2 (optional) ENABLED
OUTPUT
Block totalizer from remote input 1 start batch from
remote input 2
T
Opening valve
Closing valve
T T
Opening valve
RESTART INTERRUPTED
BATCH
Opening valve
Closing valve
Opening valve
Closing valve
Closing valve
determines the interruption of the batch. Exciting again the input 2 is possible to get 2 results:
1) T< 1Sec = restart interrupted batch
2) T between 1 e 4 Sec = reset interrupted batch. N.B.: will be necessary to give a new start
OUTPUT
impulse to the input 2 (T< 1Sec)
to begin a new batch
function
q POS. 5.6 (Block totalize) ENABLE
q POS. 6.1 OR 6.4 on END BATCH
q POS. 5.10 funzione di dosaggio
attribuita ad ingresso 2
T comprise tar 1 e 4 Sec.
(optional) ENABLE
q POS. 5.2 (P+) ENABLE
start batch from remote input 2 consent mode
to batch enable
Opening
Opening valve
Closing valve
valve
Closing valve
the stop of batching. With the T2 reset function enabled on the input 1 descent front, the batch totalizer in use goes to zero.
a new pulse on the input 2 will determine
Necessary conditions for enabling the function
OUTPUT
q POS. 5.6 (Block totalizer) ABILITATO q POS
input 2 (optional) ENABLE
q POS. 12.7 (consent mode) ENABLE q POS. 5.2 (P+) ENABLE
14
210_EN_BU_4_3_5X.d
Opto-insulated output
with collector and
Refresh frequency equal to the sample frequency
insualted output with collector and emitter terminals
ctable. In order to get the maximum
speed performances it is necessary to connect the emitter to
the common terminal of the outputs (0V), while the load has
to be on the collector. This output is internally connected to
able on the terminal
Maximum saturation voltage between collector and emitter
and emitter
Maximum switching frequency, load on the collector and
Insulation from the other secondary circuits (except 24V and
OUT 1/OUT 2 standard
-
OUT 3/OUT 4 with modules (page 9)
SE 56
16 (out1) 18 (out2)
17 (out1) 19 (out2)
emitter terminals floating and freely connectable Maximum switching voltage: 40 Vdc Maximum switching current: 100mA Maximum saturation voltage between collector and emitter @100mA: 1,2V Maximum switching frequency (load on the collector or emitter, RL=470, VOUT=24Vdc): 1250Hz
OUTPUTS WIRING
Output on/off 1250 Hz
43V
Output on/off 12500 Hz
43V
Only with ME 201 module
q Opto-
floating and freely conne
30
the power supply source 24 Vdc avail block.
q Maximum switching voltage: 40Vdc q Maximum switching current: 100mA q
100mA, load on the collector and internal power supply: 0,3V
q Maximum saturation voltage between collector
100mA, load on the emitter and internal power supply: 3V
q
29
internal power supply: (RL=470, VOUT=24Vdc): 12500Hz
q Maximum switching frequency, load on the emitter or
external power supply: (RL=470, VOUT=24Vdc): 2500Hz
q
4…20mA outputs): 500 Vdc
Output 0-4÷20mA
+24V INTERNAL
q Opto-insulated output
mA
I
24V COMMON
9 (+)
0/4..20mA OUT
10 (-)
q Maximum load 1000 ohm q Maximum voltage without load 27 Vdc q
of the connected sensor
q protected against persistent over voltages till 30
Vdc
The converter detect a loss of load on the 4÷20mA output; to disable this function set the value "mA Val. Fault" to 0 ( pag 28 Pos. 4.7)
15
210_EN_BU_4_3_5X.d
START UP AND MAINTENANCE OF THE INSTRUMENTS
The integrity of the power supply cables, wiring and other electrical parts
The integrity of the front panel (display and keyboard), damages may
SE 56
Before starting up the instrument please verify the following:
Power supply voltage must correspond to that specified in the name plate Electric connections must be done as described at page 8 Ground connections must be done
Verify periodically:
q
connected
q The integrity of the instrument’s housing (this must not have bruises or other
damages that may compromises the hermetical sealing)
q The tightening of the sealing elements (cable glands, covers, etc.) q
compromise the sealing
q The mechanical fixing of the instrument on the pipe or on the wall stand
16
210_EN_BU_4_3_5X.d
The direct exposure of the converter to the solar rays, could damage
* The maximum digit shown from the totalizer is 999999999 inde
pendently from the number of
Flow rate value
% full scale
Direct / reverse totalizer
Sampling rate
Analogical bar of flow rate variations
interpretation of flags
Flow speed
Flow rate value
% full scale
Measure units
Flow direction
Time scale (vedi Pos. 3.1)
% full scale
Active scale
Flow rate value
Currency value
Total direct totalizer
VISUAL
IZATION PAGES
Push to change visualisation
CONVERTER VIS
UALIZATION PAGE WITH CURRENCY FUNCTION ENABLE
The visualization of the pages can be change respect to some functions enabled o disabled
NOTE
SE 56
the liquid crystals display. N.B. Contrast set see page 32 pos. 8.3
*
Flow direction +/-
See: anomalies codes and
C=Calibration S=Simulation
Scale (1=low); (2=high)
selected decimal. Beyond this value the totalise are reset.
Partial reverse totalizer
(Pos. 8.4 - 8.8 – 8.10 and batch functions)
17
210_EN_BU_4_3_5X.d
Flags interpretation and LED
FLAGS
LED
SE 56
INTERPRETATION FLAGS
FLAG DESCRIPTION
M Alarm max activated m Alarm min activated
C Calibration running S Simulation
- Interruption coils circuit
!
- Segnal error
- Empty pipe
Pulse output saturation ( reduce TIME PULSE )
LOCK
1 2 3 4 5 6 7 8 9 10
11 12 13 14 15 16 17 18 19 20
M3
M1
PERMANENT LIGHT: initialisation FLASHING LIGHT ( 1 sec.): normal function FLASHING LIGHT (<1 SEC.): alarm on
The LED signals the real alarm status only if the display visualizes one of the visualization pages suitable to page 17
ATTENTION: in the panel version the LED is not visible
LED INTERPRETATION
18
210_EN_BU_4_3_5X.d
It decreases the numeric figure or the parameter selected by the cursor
KEYBOARD
For converter without keyboard (
blind version), the
SE 56
SHORT PRESSING (< 1 SECOND):
It increases the numeric figure or the parameter selected by the cursor It goes to the previous subject on the menu batch start/stop (when enabled)
LONG PRESSING (> 1 SECOND):
It goes to the next subject on the menu
SHORT PRESSING (< 1 SECOND):
It moves the cursor rightward on the input field It goes to the following subject of the menu It changes the display of the process data
LONG PRESSING (> 1 SECOND):
It moves the cursor leftward on the input field It goes to the previous subject on the menu
SHORT PRESSING (< 1 SECOND):
It enters /leaves the selected function It enables the main menu for the instrument configuration It cancels the selected function under progress
LONG PRESSING (> 1 SECOND):
It leaves the current menu It enables the totalise reset request (when enabled) It confirms the selected function
BLIND VERSION
programming of functions is made up by the IF2 serial device:
19
210_EN_BU_4_3_5X.d
QUICK START MENU FUNCTIONS
MENU DEL CONVERTITORE ML210
u”
by the function 8.6 in the display
The functions “batching setup, regulation setup, flow measure setup” they
instantaneously shape the instrument for the set up operation modifying in optimal way
chosen operation. For enable one of three types of
Description function from page 20
SE 56
Some of more use functions are available in immediate way in the “Quick start men pressing the key . This menu can be disabling menu; in this case, pressing the key the access will be directly to the main menu.
Automatic optimization of the parameters (see below)
Access to all functions
all the parameters refer to the operation press on the function the key and then the key to confirm.
20
210_EN_BU_4_3_5X.d
1.5
Factory parameter
1.6
length of the cable connecting the sensor to the converter
1.7
Enables the empty pipe detection feature
1.8* Enables the automat
ic zero calibration system
3.8*
Energy saving
are visualized on display only with other active
SE 56
ML210 Functions
(for detail functions with symbol “*”see the manual from page 27)
Attention: The function in grey colour
functions or with optional modules
1.1 Insert ND of sensor ( 0-3000 )
1.2 Calibration data of sensor visualized on sensor’s label
1.3 Sensors model: Enter the first two characters of the serial number of the sensor
1.4 Position for insertion sensors: 0=1/8DN, 1=1/2DN, 2=7/8DN
1.9* Enables the automatic calibration procedure of the empty pipe detection
2.1*Full scale value set for range N.1
2.2*Full scale value set for range N.2
2.3* Unit of measure and number of decimal totalizes
2.4* Pulse value on channel 1
2.5* Pulse value on channel 2
2.6* Duration of the pulse generated on channel 1
2.7* Duration of the pulse generated on channel 2
2.8 Full scale freq. for channel 1 (0.1Hz-1000.0Hz) (0.1Hz-10000Hz con modulo opt.)
2.9 Full scale freq. for channel 2 (0.1Hz-1000.0Hz) (0.1Hz-10000Hz con modulo opt.)
2.10Enable/disable the selection of mass units on full scale set
2.11Specific gravity set in kg/dm³
3.1* Time constant
3.2 Filter on the power supply: 0.1s=“ready” measure; 0.5s=filter of noise on the liquid
3.3* Acceleration threshold
3.4* Anomalous signal pick cut off threshold
3.5 Low flow zero threshold: 0-25% of full scale value
3.6 Enable every hour a internal cycle of calibration. The measure it's stopped for 8-15 sec.
3.7* Automatic change of scale
4.1 Maximum value alarm set for direct flow rate
4.2 Maximum value alarm set for reverse flow rate
4.3 Minimum value alarm set for direct flow rate
4.4 Minimum value alarm set for reverse flow rate
4.5 Hysteresis threshold set for the minimum and maximum flow rate alarms
4.6 Empty pipe detection threshold. It’s automatically set by the function 1.9
4.7*Current output value in case of failure
4.8*Frequency output value in case of failure
4.9*Batch safety timer
21
210_EN_BU_4_3_5X.d
6.3*
Output 3 functions
5.1*
Total direct (positive) flow totalise reset enable
8.1 Choice of the language
: E=
English
, I=italian, F=
French
, S=
Spanish
8.4
Partial totalizer visualization (with batch enable the function is always on)
SE 56
5.2* Partial direct (positive) flow totalise reset enable
5.3* Total reverse (negative) flow totalise reset enable
5.4* Partial reverse (negative) flow totalise reset enable
5.5 Reset totalise of pulse from digital input (see page 12)
5.6 Totalise counting lock command (see page 12)
5.7* Autozero calibration external command
5.8 Range change external command (see function 3.7)
5.9 Batch start/stop external command (see batch functions)
5.10* Functions assigned to input 2
6.1* Output 1 functions
6.2* Output 2 functions
6.4* Output 4 functions
6.5* Duty cycle value for pulses/frequency output
6.6* Choice of the function and the range of current output n.1
6.7* Choice of the function and the range of current output n.2
7.1 Choice of the communication protocol for the IF2 device
7.2 Choice of the communication protocol for the RS232 port
7.3 Address value of converter (range 0 – 255)
7.4 Speed of the RS485 output (possible choices: 2400, 9600, 19200, 38400 bps)
7.5 Speed of the RS232 output (possible choices: 2400, 9600, 19200, 38400 bps)
7.6 Print function enables (optional; see manual MI200)
7.7 Print of the performed batch
7.8 Stampa dei dati ad intervalli regolari ed impostabili
7.9 Print of the data process on regular intervals
7.10 Address of a further converter connected like a terminal
7.11 Start remote connection to the terminal. Connection interrupted after 10sec. of inactivity
8.2 Updating frequency on the display: 1-2-5-10 Hz
8.3* Display contrast
8.5 Date and time visualization with data logger enable
8.6 Quick start menu visualization
8.7 Enable the change value of the totalizers (see function 5.1-5.4)
8.8* Enable the page of net totalizer (difference between direct and reverse. see page 17)
8.9 Reset the processor of the display (useful in case of particular badly operations of the display)
8.10 Visualizes the values of the partial totalirer in the unit of selected currency
8.11 Choice of the numbers of decimals for the visualization currency value: From 0 to 3
8.12*Value of conversion/currency for direct totalizer
8.13*Value of conversion/currency for reverse totalizer
22
210_EN_BU_4_3_5X.d
9.1*
Date and time set
9.4 Displaying of the data stored in the data logger
9.3 Interval time for the data logging function
: 1, 2, 3, 6, 8, 12, 24, 48 hours
11.1
Level 2 access code enter
11.4
Load
user data saved
11.3
Load
factory data pre
-
set
12.2*
% limit of compensation
threshold
SE 56
9.2 Automatic data logger enable
9.5 Displaying of the last 64 alarms stored in the data logger
9.6 Visualization function of minimum and maximum peak of flow rate
9.7 Logged data cancel function
9.8 Reset all alarm events
9.9 Reset all minimum and maximum peak of flow rate stored
10.1* Enable the calibration of the converter
10.2* Converter autotest
10.3* Flow rate simulation enabling
11.2 Block level function can be set from 0 to 3
11.5 Save user data
11.6 Visualisation of the total operation hours of the converter (function not editable)
11.7 Ignore the calibration error during the switch on test
11.8 Ks Coefficient
Menu 12: Menu visualized only with batch active
(see from pag. 35)
12.1 of batch cycles to be done to define the value of compensation. Value 0=OFF
12.3* Compensation value
12.4* Prebatch value
12.5* Auto-batch
12.6* Automatic selection of batch formula
12.7* Static consent of batch
23
210_EN_BU_4_3_5X.d
ACCESS TO THE CONFIGURATION MENUES
The access to the configuration menu can take place in two different modes:
where it is possible to access to all function with
Enter in the “Quick start menu”
Access to the function “Fs1”
Change the value
Confirm the new value
Long push
Main page
SE 56
q Through the “Quick start menu” where it is possible to access directly to
some of the principal functions
q Through the “Main menu”
access code 2
We show below some examples relating to the change of the value in the “Fs1” function
EXAMPLE: modifying the full scale value from 4dm³/s to 5dm³/s.
from “Quick start menu”
Push repeatedly
24
210_EN_BU_4_3_5X.d
Enter in the “Quick start menu”
Access to the “Main Menu”
Access to the “Scale” menu
Access to the function “Fs1”
Chan
ge the value
Confirm the new value
Long push
Long push
X 5 TIMES
Main
page
SE 56
EXAMPLE: modifying the full scale value from 4dm³/s to 5dm³/s.
from “Main Menu” (quick start menu enable)
Push
25
210_EN_BU_4_3_5X.d
FACTORY PRE
-
SETTINGS
The converter is delivered with access code L2:
and with the "Quick start menu" enable. Press
the key to access to the "Quick start menu"
The “Qui
ck start menu” it’s enable by 8.6 function
(display menu); from the “Quick start menu” the
functions may be set without entering any access
The last function allows to access the main menu.
the block level enables or disables the access to
The available levels of block are the following:
: it completely disables the access to
erform the following
: it enables the access to the
the
: it enables the access to all the
ACCESS CODES
Some functions in the converter are enabled by the
The information’s of this manual are
related to all the functions available with L2 level.
you disable the
NOTE: the availability of the functions is
(freely chosen by the
user) you can proceed programming all the
functions up to L2 security level, entering the
the Main
take note very carefully of the
there is
BLOCK LEVELS
FACTORY PRE
-
SETTINGS
The converter is delivered with the following
If for several reasons you need to change the
” of menu
To enable the selected block level place the DIP
switches are on “OFF”, all
LOCK
SE 56
access codes.
All the functions available through higher level are protected and reserved to the service.
Description of the L2 access code
(Menu “11 Internal data” pos. 11.1)
q with code L2 = 00000
request of code
related to the selected block
q * with L2 customised
code itself whenever you need enter menu
*ATTENTION:
customised code you have chosen, since no way for the user to retrieve it if it forgotten
from one of the visualization pages
ACCESS CODES
11111
code (see example 1 on page 24).
the functions of the converter.
(Menu “11 Internal data” pos. 11.2)
q Level 0
the functions. You can p functions through the keyboard:
§ Changing the display mode
§ Dosing Start/stop
§ Data printing
q Level 1
following functions:
Totalise re-setting
Dosing functions modifications
q Level 2: it enables the access to
following functions:
§ Quick start menu
§ Scale (full enabling)
§ Display (partial enabling)
§ Diagnostics (partial enabling)
q Level 3
functions of level 2
block level:
block level, follow the steps:
q Set the dip switch on OFF position q Access to the function “Block level
11 (main menu)
q Choose the desired level of block
switch on the ON position
When the Dip­functions are available.
BLOCK LEVELS
3
(OFF)
(ON)
Dip switch
26
210_EN_BU_4_3_5X.d
MENU 1.SENSOR
Menu visualized on the converter ( from 1 to 11)
Synthetic description of the function
Identification of the funct
ion (not visualized on display)
Converter request
SE 56
FUNCTIONS DESCRIPTION
(description of the functions with access code< 3)
(POS. 1) Nominal diameter of sensor [ND= XXXX]
N.B.: follow are detailed description only some functions of the converter
(see note to page 20)
MENU 1.SENSOR
(POS. 1.8) “Autozero” calibration [AUTOZERO CAL.]
Enables the automatic zero calibration system. To perform the sensor it is absolutely necessary the sensor is full of liquid and that the liquid is perfectly staying still. Even very small movement of the liquid may affect the result of this function. When the percentage flow rate value is stable press the key . Check the percentage flow rate value goes to zero, otherwise repeat the operation again. When the value is stable at zero, then press . (POS. 1.7) “Empty pipe” calibration [E.P. CALIBR.] This function enables the automatic calibration procedure of the empty pipe detection function. Before performing this function, the sensor has to be completely filled with the liquid. The sensor has then to be emptied again and then you should press the key : the operation will have to be confirmed by pressing the key or any other key annul the operation. By this function the system sets the value of a parameter, which could also be manually changed (see function “E.P.thr” menu 4­ALARMS).
MENU 2.SCALES
(POS. 2.1-2.2) Full scale n° 1-2 [FS1-2=dm³/S X.XXXX]
Full scale value set for range N.1-2. There are four fields to fill in order to set this parameter, from left to right: 1) volume unit of measure, 2) type of unit, 3) time unit of measure and 4) numeric value. The selection is made by positioning the cursor on the field to modify. To change the type of unit of measure (metric, British or American, mass or volume) the cursor has to be positioned on the symbol “/” (field N. 2). When the nominal diameter is set to zero it is possible to modify only the numeric field, since the unit of measure stays at m/sec. The following tables show the units of measure available and the conversion factor by comparison with 1 dm3 and 1 kg. The converter accepts any kind of combination of units of measure satisfying both the following conditions: Numeric field value 99999 1/25 fs Where fs
numeric field value fs
max
is the maximum full scale value corresponding to the sensor, equal to a 10 m/sec liquid
max
max
.
speed. The units of measure are shown as appear on the display. The British and American units are diversified by using capital and small characters. Available units of mass and volume:
27
210_EN_BU_4_3_5X.d
SE 56
cm3 Cubic centimetre
ml Millilitre
l Liter
dm3 Cubic decimeter
dal Decalitre
hl Hectolitre
m3 Cubic metre
in3 Cubic inch Gal American gallon GAL British gallon ft3 Cubic foot Bbl Standard barrel BBL Oil barrel yd3 Cubic yard kgl KAmerican gallon KGL
KBritish gallon
G Gram Kg T Ton
Kilogram
Oz Ounce Lb Pound Ton short tons
When a mass unit of measure is set, the specific gravity function is automatically enabled by the system. The units of measure of time may be chosen among the values:
s=second,m=minute,h=hour,d= day. (POS. 2.3) Unit of measure and number of decimal totalizes [UM.tot:dm³X.XXX]
Setting the unit of measure and number of decimals for visualized the totalizes or the volumes to batch. For set the unit of measure, position the cursor on field of the actual unit of measure; For set the type of unit, position the cursor on the blank space between the unit of measure and the numeric value; For set the number of decimal totalizes position the cursor on numeric field and choose one of the possible combinations: 1000-01.00-001.0-00001. *(POS.2.4-2.5) Pulse value channel 1 and unit of measure of tot. [IMP1-2=dm³X.XXXXX] Setting of the pulse volume corresponding to channel 1-2 and of the totalizers measure units. There are three fields to fill in to set this parameter, from left to right: 1) measure unit, 2) unit type and 3) numeric value. The selection is performed by positioning the cursor on the field to be modified. To change the unit type (metric, British or American, mass or volume) just position the cursor on the blank space between the measure unit and the numeric value. When the nominal diameter is set to zero it is possible to modify only the numeric field since the measure unit stays at meter (m) or feet (ft). The possible measure units are those above described
(POS.2.6-2-7) Pulse duration channel 1-2 [TPUL1-2=msXXXX.XX]
Setting of the duration of the pulse generated on channel 1-2. Its value is expressed in milliseconds and has to be between 0.4 and 9999.99. When the high frequency output is present, then the minimum value can go down to 0.04 milliseconds. ATTENTION: since the instrument cannot detect which type of device it is connected to, it is up to the user to verify the set pulse duration is compatible with the external device processing such pulses. If, for example, an electro-mechanical pulse counter is connected, then two kind of problems may occur: if the pulse is too long than the coil may burn or, if it is too short, the counter may not be able to count and eventually even cause the damaging of the output itself.
MENU 3.MEASURE
(POS. 3.1) Time constant [TCONST=s XXXX.X]
This parameter affects the integrating filter making the instrument response quicker or slower, according to the set value. A higher value corresponds to a more stable but slower measure, a smaller value the opposite. The most common values are from 1 to 5 seconds. The valid range of value it’s from 0 (integral filter disabled) to 6000.0 seconds. The following diagram shows the response of the instrument for a flow rate variation from 0 to 100% within the T time constant period (POS. 3.3) Acceleration threshold Acceleration threshold set. The acceleration threshold stands for the limit beyond which a flow rate variation determines an immediate response at the output, without being filtered by the time constant. This system allows the instrument to have an immediate response in case of big variations of the flow rate, filtering (and delaying) the response to small variations. The result of that is a very stable measure, ready to follow the process. The value is set as percentage of the full scale value from 0 to 125%. If such a value is set to zero any flow rate variation bigger than 0.5% of the full scale value will immediately affect the outputs. The following diagram shows the instrument response in two cases: a flow rate variation from 0 to 10% completely absorbed by the time constant effect and a variation form 10% to 100% exceeding the acceleration threshold and then immediately sent
28
210_EN_BU_4_3_5X.d
SE 56
to the output. In actual fact there is always a minimum time between the measure acquisition and the outputs update.
(POS. 3.4) Peak cut off threshold [PEAK THR=% XXX]
Anomalous signal pick cut off threshold set. This parameter allows setting the maximum value of deviation of the actual measure sample by comparison with the average one. If the new value is higher than the set limit, than such a value is “cut” to the limit value. This function is used to make the meter less sensitive to big perturbations on the flow rate measure, as it may happen when there are solids in suspension in the liquid hitting against the electrodes determining a high electrical noise. The permitted values of this function range from 0 to 125 % and are referred to the full scale value. If this parameter is set to zero the peak detection function is disabled and any new measure ample will be accepted and processed as it is by the converter. (POS. 3.7) Automatic scale change enable [AUTORANGE=ON/OFF] Enables the automatic change of scale. The meter may have two different working ranges in order to suit to the variable process conditions. In order to get the best results out of this function it is important range N.2 is bigger than N.1. When the flow rate increases and reaches the 100% of the full scale 1, then the meter automatically switches to scale 2. When the flow rate decreases again reaching a value on scale 2 equal to the 90% of full scale N.1, then the active scale is 1 again. Allowed values for this parameter: ON / OFF. N.B.: the autorange doesn’t allow using the manual change of range (see pos. 5.8) (POS. 3.8) Energy saving enable [E.SAVING=ON/OFF] This function is used when the instrument is powered by a battery or solar cells, allowing an energy saving up the 60-80. The energy consumption is controlled by the ratio between the measuring cycles powering the coils and the cycles without powering the coils. When the flow rate is stable the number of “off” cycles is higher than the “on” ones, so that the average consumption is strongly reduced. If the flow rate suddenly changes, then the meter switches on a higher number of measuring cycles, in order to get a higher response time, switching off the cycles as soon as the flow rate gets back to be stable. If the flow rate varies below of the “acceleration threshold” (POS.18) percentage value, then the meter goes on with “off” cycles, but as soon as the flow rate value exceeds such a threshold, the meter switches on many measuring cycles again. Allowed values for this parameter: ON/OFF N.B.: to optimise this function it is recommended choose a value for the acceleration threshold within 10÷15 (POS. 3.3)
MENU 4.ALARMS
(POS. 4.7) Current output value in case of failure [mA VAL.FAULT =% XXX]
Setting of the value the 0/4...20 mA current output has to be in one of the following cases: empty pipe; coils interrupted; ADC error The allowed range is from 0 to 120% of the 0..20 mA scale, 120% corresponds to 24 mA and does not depend on the selected range (0…20 / 4…20 mA). The NAMUR NE43 recommendation asks for a alarms signalling value for the current output lower than 3.6 mA (<18%) or bigger than 21 mA (>105%). It would then be preferable to set the value of this function at the 10%, so that the current value in case of the a.m. cases would be 2 mA, allowing the following diagnostics: current < 2 mA - 5%: line interrupted, power supply failure or faulty converter; 2 mA -5% current 2 mA + 5%: hardware alarm;
29
210_EN_BU_4_3_5X.d
SE 56
4 mA current 20 mA: normal working range; 20 mA < current 22 mA: out of range, measure above 100% f.s.
N.B.: To set this parameter to zero corresponds to disable the alarm (POS. 4.8) Frequency output value in case of failure [Hz VAL.FAULT=%XXX]
Setting of the frequency value to assign to the on/off output in one or more of the following cases: Empty pipe ; Coils interrupted ; ADC error The allowed range is from 0 to 125% of the frequency full scale value. Although there are not specific rules regulating cases like this one, it would be convenient to use the failure information as follows:
q 0% Hz frequency 100% f.s.: normal working range; q 100% f.s. < frequency 110% f.s.: overflow, measure above the 100% of the f.s.; q 115% f.s. frequency 125% f.s.: hardware alarm condition.
(POS. 4.9) Batch safety timer
This function is useful when you need control one or both of the followings condition:
q batch valve open and flow rate is zero q batch valve closed and flow rate different to zero
When this alarm is activates, they are aborted the batch operation and the power supply of the valve. The values of function are from 0 to 25.5 seconds and is active only if one or more of the batch functions are enable.
MENU 5.INPUTS
(POS. 5.1-5.2-5.3-5.4) Totalise + reset enable [T/P+/-RESET=ON/OFF]
To make the reset of the totalise from the key board it is necessary enable the function 8.7 (modify tot.) and one of function from 5.1 to 5.4. From visualisation pages, proceed in the following mode:
1) Push the key , Set the L2 CODE if required and then push the key
2) Positioning the cursor on value field to modify the numerical value (it’s possible only modify the totalizer enabled) push the key to confirm the modified value
3) Positioning the cursor on “RESET TOTALIZ.?” Push the key and then the key to confirm or any other key to cancel this operation.
With function 8.7 disabled it’s possible reset the totalizer pushing the key from visualization page, at the required “RESET TOTALIZ.?” Push the key and then the key to confirm or any other key to cancel this operation (POS.5.7)“Autozero” calibration external command enable [CALIBRATION=ON/OFF] When this function is active, applying a voltage on the on/off input terminals the meter performs a autozero calibration cycle. ATTENTION: if the voltage pulse is less 1 sec., the meter performs a calibration cycle for compensate possible thermal drifts. If the voltage pulse is more 1 sec, the meter performs a zero calibration of measure. This function enables/disables the automatic zero calibration system. To perform the sensor it is absolutely necessary the sensor is full of liquid and that the liquid is perfectly staying still. Even very small movement of the liquid may affect the result of this function, and, consequently, the accuracy of the system. (POS. 5.8) Range change external command enable [RANGE CHANGE=ON/OFF] Range change external command enables. When this function is enabled, applying a voltage on the on/off input terminals the meter switches to the second measuring range (Fs2).
N.B.: the autorange doesn’t allow using the manual change range (see pos. 3.7) (POS.5.10)Functions assigned to input 2 [ING.2=XXXXXX]
Choice of the function to associate the input 2 The functions are listed in the table below.
OFF: DISABLE T+ RESET: RESET TOTAL DIRECT TOTALIZER FOR DIRECT FLOW RATE (+) P+ RESET: RESET PARTIAL DIRECT TOTALIZER FOR DIRECT FLOW RATE (+) T- RESET: RESET TOTAL REVERSE TOTALIZER FOR REVERSE FLOW RATE (-) P- RESET: RESET PARTIAL REVERSE TOTALIZER FOR REVERSE FLOW RATE (-) BATCH: START/STOP BATCH MD SELECTION: STATIC SELECTION OF FORMULA
FUNCTION FOR INPUT 2
30
210_EN_BU_4_3_5X.d
SE 56
MENU 6.OUTPUT
(POS. 6.1-6.2-6.3-6.4) Function corresponding to on/off output 1-2-3-4 [OUT1=XXXXXX]
Choice of the function corresponding to digital Output 1. The functions are listed in the table to the next page
The output 3-4 are optional and the output 4 it’ the only output, which can reach a 12.5 KHz frequency.
OFF: DISABLED #1 IMP+: PULSE ON CHANNEL 1 FOR POSITIVE FLOW RATE #1 IMP-: PULSE ON CHANNEL 1 FOR NEGATIVE FLOW RATE #1 IMP±: PULSE ON CHANNEL 1 FOR POSITIVE AND NEGATIVE FLOW RATE #2 IMP+: PULSE ON CHANNEL 2 FOR POSITIVE FLOW RATE #2 IMP-: PULSE ON CHANNEL 2 FOR NEGATIVE FLOW RATE #2 IMP±: PULSE ON CHANNEL 2 FOR POSITIVE AND NEGATIVE FLOW RATE #1 FREQ+: FREQUENCY CHANNEL 1 FOR POSITIVE FLOW RATE #1 FREQ-: FREQUENCY CHANNEL 1 FOR NEGATIVE FLOW RATE #1 FREQ±: FREQUENCY CHANNEL 1 FOR POSITIVE AND NEGATIVE FLOW RATE #2 FREQ+: FREQUENCY CHANNEL 2 FOR POSITIVE FLOW RATE #2 FREQ-: FREQUENCY CHANNEL 2 FOR NEGATIVE FLOW RATE #2 FREQ±: FREQUENCY CHANNEL 2 FOR POSITIVE AND NEGATIVE FLOW RATE SIGN: FLOW DIRECTION OUTPUT (ENERGISED = -) RANGE: RANGE INDICATION OUTPUT (ENERGISED = SCALE 2) MAX AL+: MAX DIRECT FLOW RATE OUTPUT(ENERGISED = AL. OFF) MAX AL-: MAX REVERSE FLOW RATE OUTPUT(ENERGISED = AL. OFF) MAX AL±: MAX DIRECT/REVERSE FLOW RATE OUTPUT(ENERGISED = AL. OFF) MIN AL+: MIN DIRECT FLOW RATE OUTPUT(ENERGISED = AL. OFF) MIN AL-: MIN REVERSE FLOW RATE OUTPUT(ENERGISED = AL. OFF) MIN AL±: MIN DIRECT/REVERSE FLOW RATE OUTPUT(ENERGISED = AL. OFF) MAX+MIN±: MAX AND MIN FLOW RATE ALARM OUTPUT (ENERGISED = AL. OFF) EMPTY PIPE: EMPTY PIPE ALARM OUTPUT (ENERGISED = FULL PIPE) OVERFLOW.: OUT OF RANGE ALARM OUTPUT (ENERGISED = FLOW RATE OK) HW ALARM: CUMULATIVE ALARM OUTPUT interrupt coils, empty pipe, measure error (ENERGISED = NO ALARMS BATCH AL: BATCH ALARM EXT. COMM.: ONLY AVAILABLE WITH DATA LOGGER MODULE BATCH SIN.: AT THE AND OF BATCH THE OUTPUT CHANGE STATUS END BATCH.: END BATCH OUTPUT (ENERGISED =BATCH IN PROGRESS) PREBATCH.: PREBATCH OUTPUT (ENERGISED = PREBATCH IN PROGRESS)
FUNCTION FOR OUTPUT 1, 2,3,4
(POS. 6.5)duty cycle value for pulses/frequency output [OUT.1=XXXXXX]
The duty cycle function define the time ratio between ON and OFF state when frequency output are used: 50% it mean that the ON phase will be the same of OFF phase, 60% it mean that the phase ON will be 60 % and phase OFF will be 40% of the total cycle time. When pulses outputs are used , the duty cycle define the OFF phase because the ON phase it’s already set with the function "PULSE DURATION"( see menu “SCALE” ) . In this case if is setting for example the duty cycle at 50% and the pulse duration to 50ms, the OFF phase will be the same of ON phase. The formula for calculate the minimum time of the OFF phase and the time of total cycle is the following: T. total cycle= 100 x (pulse duration in ms)/ (duty cycle) T. OFF phase = T. total cycle - pulse duration N.B.: If the value of the function is set to 0 the issue of the pulses happens in synchronous mode with the flow rate therefore when is uses the function in frequency DOESN'T set the duty cycle to 0.
31
210_EN_BU_4_3_5X.d
CURRENT VALUES IN mA ASSOCIATE TO THE % VALUE OF FULL SCALE
≤ -
110%
+110%
* Example 1: out 4÷22 +
** Example 2: out 4÷20
–0+
SE 56
(POS. 6.6-6.7) Function and the range of current output n.1-2 [OUT.mA1-2=X÷XX±] Choice of the function and the range of current output N.1-2. The current output N.1 is optional and it is mounted on the main board. There are three fields to modify for this function:
q Scale zero: 4 or 0 mA ; Full scale: 20 or 22 mA q Field: + = positive, - = negative, ± = both, -0+ = central zero scale
The values corresponding to the scale points are shown in the following chart:
POSSIBLE FIELD
OutmA = 0 ÷ 20 + 0 0 0 20 20 OutmA = 0 ÷ 22 + 0 0 0 20 22 OutmA = 4 ÷ 20 + 4 4 4 20 20
* OutmA = 4 ÷ 22 + 4 4 4 20 22
OutmA = 0 ÷ 20 - 20 20 0 0 0 OutmA = 0 ÷ 22 - 22 20 0 0 0 OutmA = 4 ÷ 20 - 20 20 4 4 4
OutmA = 4 ÷ 22 - 22 20 4 4 4 OutmA = 0 ÷ 20 ± 20 20 0 20 20 OutmA = 0 ÷ 22 ± 22 20 0 20 22 OutmA = 4 ÷ 20 ± 20 20 4 20 20 OutmA = 4 ÷ 22 ± 22 20 4 20 22
OutmA = 0 ÷ 20 –0+ 0 0 10 20 20 OutmA = 0 ÷ 22 –0+ 0 1 11 21 22
** OutmA = 4 ÷ 20 –0+ 4 4 12 20 20
OutmA = 4 ÷ 22 –0+ 4 4.8 12.8 20.8 22
REVERSE FLOW VALUE ZERO DIRECT FLOW VALUE
-100% 0% +100%
In hardware alarm conditions “HW ALARM” (interrupted coils, empty pipe, measure error) the current value is programmed by the function “mA VALL. FAULT” (pos. 4.7) and it is expressed as percentage of a fixed current range, where: 0% = 0 mA e 110% = 22 mA.
I (mA) 22 mA
20 mA
4 mA
-110% F.S. -100% F.S. +100% F.S. +110% F.S. zero
I (mA) 20 mA
12 mA
4 mA
-110% F.S. -100% F.S. +100% F.S. +110% F.S. zero
32
210_EN_BU_4_3_5X.d
SE 56
MENU 8.DISPLAY
(POS. 8.3) Display contrast set [CONTRAST=X]
Display visual contrast set. The contrast can change according to the room temperature. The set values are from 0 to 15. The entered value has effect only when leaving the function itself.
Contrast also can be set from visualization pages (pag. 17) pushing the key for 8 second or more. In this way the contrast set that will be visualized at release of the key. (POS. 8.12-8.13) Conversion factor for flow rate totaliser [EUR/dm³+ =X]
Set the value of conversion/currency for direct totalise( positive ). There are three set fields for this parameter, from left to right: 1) monetary token, 2 ) default/personalized monetary token, 3 ) conversion coefficient. For the selection setting the cursor over the field to modify. The mode set of monetary token could be two:
1. Choice of one of the 7 predetermined monetary tokens (standard ISO 4217-REV81): EUR = Eur ; USD = USA ; dollar CAD = Canadian dollar ; AUD = Australian dollar ; GPB = English pound ; CHF = Swissfranc ; JPY = Japanese yen.
2. Choice three free characters (number or letter ) . To change the characters , the cursor has to
be positioned on the symbol “/” (field N. 2)
MENU 9.DATA LOGGER
(POS. 9.1) Date and time set [· = dd/mm/yy hh:mm]
Date and time set. If the real time clock optional module is present, then the time setting is kept also when the power supply is off, otherwise it is frozen till the power supply is back. For example, if the power supply has been off for one hour, when switched on the instrument will be one hour late. The calendar is valid till year 2091. N.B.: date and time are visualized on display only if the data logger is enable (Pos 9.2).
MENU 10. DIAGNOSTIC
(POS. 10.1) Meter “calibration” [CALIBRATION]
Enable the calibration of the meter. The activation of this function happens pressing the key during the visualization of the function. Will be visualized the following question: " EXECUTE?" press for more of two second the key to proceed . Press any other key to delete the operation (POS. 10.2) “Autotest” function enable [SELF TEST] Meter autotest function. This function stops the normal functions of the meter and performs a complete test cycle on the measure input circuits and on the excitation generator. To activate this function, after select it, push key , at the question: “EXECUTE?” push the key For start autotest, or any other key for delete operation. The result of the test is shown on the display. At the end of operation will have visualized one of visualization page. This function is automatically performed when switching on the device. (POS. 10.3) Flow rate simulation [SIMULATION] Flow rate simulation enabling. With this function it is possible to generate an internal signal that simulates the flow rate, allowing the outputs and all the connected instruments test. After enabling it, the flow rate simulation can be:
- set: by pushing the key from one of four visualization pages
- started: by pushing the key after set it
- finished: by pushing the key from visualization pages and then by pushing the key . N.B.: the enable of flow rate simulation disable the contrast regulation with the key (Pos. 8.3)
33
210_EN_BU_4_3_5X.d
SE 56
MENU 12.BATCH
Menu visualized only with batch active (output on batch and/or pos. 5.9 enable or 5.10
on batch)
(POS. 12.1) Number of batch samples [N.SAMPLES=XXX]
Number of batch cycles to be done to define the value of compensation. This function allows to automatically determine the average value for automatic compensation of system delay (POS. 9.3) . Set to ZERO this function for manually introduction of the compensation value.
(POS. 12.2) % limit of compensation [DIFF.THR=%XXX]
This value defines the percentage of maximum difference between the compensation value set (see pos. 12.3) and the average compensation value defined with the function 12.1. Over this threshold the new compensation value will be automatically set (if Number of batch samples is different from zero) (POS. 12.3) Compensation value [V.COM.=XX.XXX] This value, expressed in the same selected volume unit of measure, is the result of the difference between the batch value set and the quantity of product really supplied due to the system delays: closing valves, stop pumps, stop motors, etc. Attention: if you need to set manually the value of compensation, preset to ZERO the Number of batch samples (POS. 12.1) (POS. 12.4) Prebatch value [V.PRE.=XX.XXX] set the volume of liquid at which you want to enable the pre-batch. When the pre-batch volume “V Pre” is reached the output (if enabled) is de-activated. This value is constant for all quantities to be batched and must be set in current volume unit of measure. The pre-batch function is useful when you need fast and accurate fillings.
(POS. 12.5) Enable/disable auto-batch function [AUTO BATCH=ON/OFF]
Applying a voltage on the on/off input terminals for more than 5 second the valve controlled by the meter stands open while the voltage is applied on the input. When the product has reached the desired volume/level, removing the voltage from the input, the meter closes the valve and memorizes the supplied product volume in the current memory batch (see "BATCH FUNTIONS"); the value obtained with this procedure will be the volume supplied in every following batch. In order to modify this value, repeat the operations above. This procedure set the safety timer at a value 1.25 times greater than the time used to reach the batched quantity; after that the counter will be reset.
(POS. 12.6) Automatic selection of batch formula [BM AUTO SEL=ON/OFF]
The function allows the automatic selection of the first 4 formulas depending on the duration of the pulse of the batch start (see page 11 "Input operation stage"). This function is active only if the function cons. mode (POS. 12.7) has not enabled. Besides, activating this function, the automatic compensation of the batch volume is also excluded (the value of the parameter "N.medie" (POS.
12.1) will be automatically set to zero). However the manual compensation is possible introducing the opportune value on the parameter "V.com" (POS. 12.3)
(POS. 12.7) Static consent of batch [Cons. mode=ON/OFF]
The function enable the start and the stop of the dosing using a static signal, instead of an impulsive, applied to the input (see pag. 11 "Digital input), this signal will have to stand applied all through the batch. This function automatically disables the functions "BM AUTO SEL" (POS. 12.6) and " AUTO BATCH" (POS. 12.5).
34
210_EN_BU_4_3_5X.d
BATCH FUNCTION.
For each formula you can
for
batch (safety time for
After activating the batch
function from visualization
page at pages 47, proceed
VISUALIZATION PAGE WITH BATCH FUNCTION ENABLE
PROGRAMMING
BATCH
Programming formula n°
prod
uct Name
Batch in progress
Programming batch quantity
Visualization batched product
Input key code
Input quantity product for each batch
Input product name for batch (max 8 charac
ters.)
will have activated also the alarm output
From the visualization pages
ENABLE BATCH
SE 56
Enable one of the following functions to enable and program the batch on the converter:
q POS. 5.9-5.10: START/STOP batch from input q POS. 6.1-6.2: assign one of the functions to one of two output
Some examples of operation of such functions are visualized from page 11
Visualizations:
1) batch off: n° batch effected
2) batch on: decrease safety timer
3) programming: programming safety timer indefinite if timer=0 timer disabled
Choose the formula number for associate quantity batch (between 00 and 15)
associate:
q Product quantity q Product name q Maximum time
each formula)
as in the aside example.
Input maximum time for batch If timer = 0, safety timer disabled max time set = 6000 sec. N.B. if to one output is assigned the function of batch alarm, to the attainment of the maximum time, beyond to the interruption of the batch,
35
210_EN_BU_4_3_5X.d
S
TART STOP BATCH
assigning the functions of start/stop batch to the input 1 (POS.
the start of batch from keyboard is always on the descent front (release of the
in this case the stop of batch will have activated from a output signal to
een set and this is exceeded,
during the batch the symbol of the active batch and the name of the formula are
outputs
will remain energized till the key is released. On the display, in place of the CT and ST
AGISCE SU
SE 56
START: it is possible activate the start of batch in two different way:
1. from remote input:
5.9) or input 2 (POS. 5.10) and using the input/s like visualized from page 12.
2. from keyboard: short pressing of the key
N.B.:
key) and is not available with the function of batch consent (POS. 12.7)
STOP: the stop of batch can be due to three events:
1. keyboard or remote input (manual stop): short pressing of the key
2. end of batch: the attainment of the batch quantity
3. maximum time of batch: if a maximum batch time has b the batch in progress is stopped independently from the batched quantity
Notes:
q
visualized on video.
q When the batch outputs are enable, pushing for more of 5 sec. the key , the
totalisers the following messages will appear:
!! VALVE !! !! OPENED !!
The start of the batch disables any function listed below:
* SE UTILIZZATO INGRESSO 1 ** VALORE A ZERO
IMPORTANT NOTES
POS 12.5 POS 12.6 POS 5.6 POS 12.1 POS 5.9 POS 3.7-5.8 POS 3.8 POS 5.7
AUTO BATCH
BM AUTO SEL
BLOCK TOTALIZER
POS 12.5 AUTO BATCH *DISABLE POS 12.6 BM AUTO SEL ** DISABLE POS 12.7 CONS. MODE DISABLE DISABLE * DISABLE
POS 5.9
POS 5.10 POS 5.10 BM SELECT DISABLE ** DISABLE
POS 6.1÷6.4 OUTPUT ON END BATCH DISABLE
INPUT 1 ON START/STOP BATCH INPUT 2 ON START/STOP BATCH
DISABLE DISABLE DISABLE
DISABLE DISABLE DISABLE DISABLE
N. SAMPLES
BATCH
INPUT 1 ON START/STOP
AUTO RANGE CHANGE OR
FROM INPUT
To optimize the performances of the meter used as a batch instrument, it is recommended to set it as prompt as possible according to the plant requirements, choosing the opportune values of time constant (pos. 3.1) and acceleration threshold (pos. 3.2).
36
CALIBRATION
ENERGY SAVING
210_EN_BU_4_3_5X.d
Alarm messages, causes and actions to be taken
Anomalies codes
SE 56
Messages ANOMALIES ACTION TO TAKE
NO ALARMS All works regularly -----
MAX ALARM The flow rate is higher than the maximum threshold set
MIN ALARM The flow rate is lower than the minimum threshold set
FLOW RATE >FS
PULSE/FREQ>FS
EMPTY PIPE
The flow rate is higher than the full scale value set on the instrument
The pulse generation output of the device is saturated and cannot generate the sufficient number of impulses
The measuring pipe is empty or the detection system has not been properly calibrated
Batch interrupted for the followings condition:
q Timer batch expired before the end of the batch
BATCH ALARM
INPUT NOISY
EXCITATION FAIL The coils or the cable connecting the sensor are interrupted Check the connecting cables to the sensor
CURR. LOOP
OPEN
P.SUPPLY FAIL Power supply different from that indicated on the label.
q Batch valve open and flow rate to zero for a time longer
to the safety timer set
q Batch valve closed and flow rate different from zero for
a time longer to the safety timer set
The measure is strongly effected by external noise or the cable connected the converter to the sensor is broken
The 0/4...20mA output on board or the optional one are not correctly closed on a valid load
Check the maximum flow rate threshold set and the process conditions
Check the minimum flow rate threshold set and the process conditions
Check the full scale value set on the instrument and the process conditions
Set a bigger unit of volume or, if the connected counting device allows it, reduce the pulse duration value
Check whether the pipe is empty or perform again the empty pipe calibration procedure
Verify:
q Presetting q System condition
Check the status of the cables connecting the sensor, the grounding connections of the devices or the possible presence of noise sources
Verify the load is applied to the output (max 1000 ohm).
To disable the alarm,set the “mA VAL.FAULT” value ( menu alarm ) to 0.
Verify that the power supply is that indicated on the label
CODES ANOMALIE DESCRIPTIONS ACTION TO TAKE
0001 problem with watch-dog circuit 0002 wrong configuration work data in eeprom 0004 wrong configuration safety data in eeprom 0008 defective eeprom 0010 defective keyboard (one or more key are pushed during the test) 0020 Power supply voltage (+3.3) is out of range 0040 Power supply voltage (+13) is too low (<10V) 0080 Power supply voltage (+13) it’s too high (>14V) 0200 timeout calibration input (input circuit is broken)
0400 Gain input stage is out of range
0800 Interruption on the coils circuit
Check the status of the cables connecting the sensor to the converter, the grounding connections of the devices or the possible presence of strong and anomalous noise sources
Check the status of the cables connecting the sensor to the converter
ADDRESSING TO SERVICE
0C00 Cumulative alarm 0800 + 0400
see single code
37
210_EN_BU_4_3_5X.d
Unscrew the screws suitable in pic. 1
Lift the board, take off the flat cable
Pic.2
4 allen spanner
Display
Unscrew the fixing screw of display to
Take off the
1
2
3 4
Display
Rotate the display in the desired location,
Pic.6
Pic.4
Pic.7
Display rotation
Pic.1
Pic.3
Restore the connection of the flat c
able to
Pic.5
SE 56
Fixing screw of board
q
flat cable
q
verify the correct set of the seal, the cleaning of the contact surfaces of and set the display in the lodging.
q Shift the angular in the suitable direction
(pic. 5) and screw down the scew, till to the support perception of the angular on the display
q Shut definitely the screw in the order
1-2-3-4 suitable in represents pic. 4
from the display pic. 2 and extract definitely the board from the box
the display
allow the shift of the angular and the extraction of the display
N.B.: don't unscrew entirely the screw
Verify the correct set of the board in the
fixing clip ( Pic.7 )
Finish the assemblage fixing to the box
the board
38
210_EN_BU_4_3_5X.d
SE 56
DECLARATION OF CONFORMITY
According to ISO / IEC Guide 22 and EN 45014
Product’s name: Electromagnetic flow meter series’
Converter model: SE 56
Option: all applicable
Sensors model: SO 501 – SO 600 – SO 1000 – SO 2410 – SO 2500 – SO
3700 – SO 3770 – SO 5000
BURKERT declares that the above mentioned products satisfy the following requirements:
EN61010, dielectric strength = 4 kV, installation category II, IP65
EMC reference : Immunity: EN 61326-1
Test :
q EN55011 (150 kHz – 30 MHz): Group 1, class B q EN55011 (30 MHz – 1GHz): Group 1, class B q IEC 1000-4-2: 4 kV CD, 8 kV AD q IEC 1000-4-3 (f = 80 MHz – 1 GHz, antenna at 3 m, AM modulation 1kHz
80%): 10 V/m
q IEC 1000-4-4: 4 kV on all ports q IEC 1000-4-5 (2kV diff/2kV common mode) q IEC 1000-4-6 (f = 150 kHz – 80 MHz, AM modulation 1 kHz 80%): 10 V q IEC 1000-4-11
Safety
EMC
Emission: EN 61326-1
39
FFIILLEE NNAAMMEE::
221100__EENN__BBUU__44__33__55XX..ddoocc
The last three character of file name , identify the sw version which the manual is
refer . the sw version is visualized during switch on of converter