FI-SCHUKOMAT, SCHUKO socket outlet (RCD) with earth leakage circuit breaker
®
Functions at a glance
Shuttered.
Without PE monitoring.
With connecting conductor and protection of downstream socket outlets.
Rated actuating current: 30 mA. Release time: ≤ 30 ms. Short-circuit strength:
3000 A (with 25 A GL fuse). Current surge strength: 250 A (8/20) µs.
With fixing claws.
Rated frequency: 45-60 Hz.
Rated voltage: 230 V~
Rated current: 16 A
Protection class (device): IP 20
Temperature range (device): -25 °C - 40 °C
Connecting terminals approved in accordance with VDE 0620-1 as connectors.
Protective measure according to VDE 0100; can be proven or checked using the
Profitest 0100S testing device, for example.
Increased shock protection .
RAL colour number: 9010