Burnham SCG, SCG Series, PVG Series User's Information Manual

LAUNAMNOITAMROFNIS'RESU
GCS
RELIOBDERIF-SAG
WARNING: If the information in this
manual is not followed exactly, a re or
explosion may result causing property damage, personal injury or loss of life.
-
Do not store or use gasoline or other
ammable vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
Do not try to light any appliance.
Do not touch any electrical switch; do
not use any phone in your building.
Immediately call your gas supplier
from a neighbor's phone. Follow the gas supplier's instructions.
If you cannot reach your gas supplier,
call the re department.
-
Installation and service must be performed by a qualied installer, service agency or the gas supplier.
AVERTISSEMENT. Assurez-vous de bien suivre les instructions données dans cette notice pour réduire au minimum le risque d'incendie ou d'explosion ou pour éviter tout dommage matériel, toute blessure ou
la mort.
Ne pas entreposer ni utiliser d'essence ni
-
d'autres vapeurs ou liquides inam-mables dans le voisinage de cet appareil ou de tout
autre appareil. QUE FAIRE SI VOUS SENTEZ UNE ODEUR
DE GAZ:
Ne pas tenter d'allumer d'appareils.
Ne touchez à aucun interrupteur. Ne pas
vous servir des téléphones dans le bâtiment où vous vous trouvez.
Appelez immédiatement votre
fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
Si vous ne pouvez rejoindre le
fournisseur de gaz, appelez le service
des incendies.
L'installation et I'entretien doivent être
-
assuréx par un installateur ou un service d'entretien qualié ou par le fournisseur de
gaz.
8140704R3-12/08
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels.
WARNING
Indicates a potentially hazardous situation which,
if not avoided, could result in death, serious injury or substantial property damage.
Indicates a potentially hazardous situation which,
if not avoided, may result in moderate or minor
injury or property damage.
CAUTION
Basic Operation
CAUTION
Should overheating occur or the gas supply fail to shut off, do not turn off or disconnect the electrical
supply to the pump. Instead, shut off the gas supply at a location external to the appliance.
En cas de surchauffe ou si I'admission de gaz ne peut étre coupée, ne pas couper ni débrancher l'alimentation électrique de la pompe. Fermer plutôt le robinet d'admission de gaz à l'extérieur de I'appareil.
Do not use this boiler if any part has been under water. Immediately call a qualied service technician to inspect the boiler and to replace any part of the control system and any gas control which has been under
water.
A. General. This water boiler utilizes fan-assisted
combustion and is equipped with controls for proper operation. All controls must be in proper working order.
Contact a qualied service agency to provide annual maintenance as specied in Installation, Operating and Service Instructions.
Service on this boiler should be undertaken only by trained and skilled personnel from a qualied service agency.
WARNING
1. Limit. See Figure 1. A device which automatically
interrupts boiler operation when the water temperature exceeds the set point. Maximum allowable temperature is 240°F.
Original equipment with this boiler is a Honeywell
L4080D1036. Boiler operation is interrupted when
system temperature reaches cut-out temperature. Boiler operation resumes automatically when system
temperature falls 30°F to cut-out temperature.
2. Flame Rollout Switch. See Figure 1. A device
which automatically interrupts boiler operation when ames or excessive heat are present in the
combustion area enclosure. The control is a single use device. The control is located in the combustion
area enclosure. If the control was activated to interrupt boiler operation, do not attempt to place boiler in operation. Contact a qualied service agency.
3. Pressure Switch. See Figure 1. A device which
automatically prevents or interrupts boiler
operation when the induced draft blower fails to
move sufcient combustion air for proper burner operation. Boiler operation resumes automatically when sufcient combustion air ow is reestablished.
Electronic Ignition System. The Electronic Ignition
4.
(EI) System consists of:
a. a solid state ignition control module to initiate,
monitor and stop burner operation. See Figure 1.
b. a combination gas valve to regulate gas ow to
the burners. See Figure 1.
c. a pilot burner to provide the ignition source for
the main burners. See Figure 4.
2
Figure 1: Control Locations
A Blower Relay B Limit
C/D J-Box & Transformer/Relay
E Flame Roll-out Switch F Blower G Pressure Switch
H Ignition Control Module
J Gas Valve
B. Instructions to place the boiler in operation and to turn
off the boiler are shown on the Operating Instruction
Label posted on the left jacket panel of the boiler. The
Operating Instruction Label is shown in Figure 2.
C. The Sequence of Operation is shown in Figure 3.
3
NOTE: YOUR BOILER IS EQUIPPED WITH A HONEYWELL VR8204 OR VR8304 GAS
VALVE. PLEASE FOLLOW THESE OPERATING INSTRUCTIONS:
4
Figure 2: Operating Instructions
Figure 3: Sequence of Operation
5