Burnham SCG-3, SCG-4, SCG-5, SCG-6, SCG-7 Installation & Service Instructions Manual

...
DNAGNITAREPO,NOITALLATSNI
GCS
RELIOBDERIF-SAG
As an ENERGY STAR
STAR® guidelines for energy effi ciency established by the United States Environmental Protection Agency (EPA).
sserddA
8140705R3-1/07
®
Partner, Burnham Hydronics has determined that the SCG meets the ENERGY
rebmuNledoMrelioB
___-____GCS
rotcartnoCgnitaeH rebmuNenohP
rebmuNlaireSrelioB
________
.lebaLgnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp,reliob
etaDnoitallatsnI
Price - $5.00
nonoitamrofnignikeesnehW.rotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
IMPORTANT INFORMATION - READ CAREFULLY
NOTE: The equipment shall be installed in accordance with those installation regulations enforced in the area where the
installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or local regulations. All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or local regulations.
The New York City Department of Buildings has approved the SCG™ Series boiler: Approval No. MEA 5-06-E. The City of New York requires either a Licensed Master Plumber or a Fire Suppression Piping Contractor supervise the
installation of this product. The Massachusetts Board of Plumbers and Gas Fitters has approved the SCG™ Series boiler. See the Massachusetts Board of
Plumbers and Gas Fitters website, http://license.reg.state.ma.us/pubLic/pb_pre_form.asp for the latest Approval Code or ask your local Sales Representative.
The Commonwealth of Massachusetts requires this product to be installed by a Licensed Plumber or Gas Fitter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
REGNAD
noitautissuodrazahyltnenimminasetacidnI
,htaednitluserlliw,dediovatonfi,hcihw
nisuoires
.egamad
ytreporplaitnatsbusroyruj
.
egamad
GNINRAW
noitautissuodrazahyllaitnetopasetacidnI
,htaednitluserdluoc,dediovatonfi,hcihw
jnisuoires
.egamad
ytreporplaitnatsbusroyru
razahyrujnilanosrep
NOITUAC
noitautissuodrazahyllaitnetopasetacidnI
nitluseryam,dediovatonfi,hcihw
ytreporproyrujnironimroetaredom
ECITON
nosnoitcurtsnilaicepssetacidnI
ecnanetniamro,noitarepo,noitallatsni
otdetalertontubtnatropmierahcihw
.sd
REGNAD
ynarosihtfoytinicivehtnisdiuqilrosropavelbammalfrehtoroenilosagesuroerotsTONOD
.ecnailpparehto
lacirtceleynahcuotTONOD-ecnailppaynaetarepootyrtTONOD,sropavsagllemsuoyfI
aidemmI.gnidliubehtnienohpynaesurohctiws
.tnemtrapederifeht
yletomeramorfreilppussagehtllac,ylet
tcatnoc,elbaliavanusireilppusehtfirosnoitcurtsnis'reilppussagehtwolloF.enohpdetacol
2
GNINRAW
ehtwolloF.ylefasetarepootecivresdnaecnanetniamralugerseriuqerreliobsihT
.launamsihtnideniatnocsnoitcurtsni
ytreporpesuacnacecnanetniamroecivres,noitaretla,tnemtsujda,noitallatsnireporpmI
ehtdnatsrednudnadaeR.efilfossolroyrujnilanosrep,egamad
.detnevylreporpebtsumreliobsihT
.rianoitalitnevdnanoitsubmocetauqedarof
.ycneiciffes'reliobehtgniniatniam
.sliated
erofeblaunameritne
ebtsumecivresdnanoitallatsnI.ecivresro,noitarepopu-trats,noitallatsnignitpmetta
.ycnegaecivresrorellatsnielbaegdelwonkdna,delliks,decneirepxenaybylnodemrofrep
snoisivorperaerehtosdellatsniebtsumdnanoitarepoefasrofriahserfsdeenreliobsihT
ehtfotratsehterofebdenaelcdnadetcepsniebtsummetsysgnitnevehtforoiretniehT
ynarofnosaesgnitaehehttuohguorhtyllacidoirepdetcepsniebdluohsdnanosaesgnitaeh
suoixonwollaotyrassecensimetsysgnitnevdetcurtsbonudnanaelcA.snoitcurtsbo
drawotetubirtnoclliwdnaylefastnevotefilfossolroyrujniesuacdluoctahtsemuf
gnippatehtotnidellatsnisievlavfeilererusserpasselnuetelpmoctonsinoitallatsnI
roflaunamsihtfonoitceSmirTdnagnipiPretaWehteeS-.ecnailppafopotnodetacol
tondnanwodtuhsotreliobehtesuacyamhcihwsecivedytefashtiwdeilppussireliobsihT
metsysgnitaeheht,ytilibissopasisepipnezorfoteudegamadfI.ecivrestuohtiwtrats-er
dluohssmraladnasdraugefasetairporpparo;rehtaewdlocnidednettanutfelebtondluohs
.evitareponisireliobehtfiegamadtneverpotmetsysgnitaehehtnodellatsnieb
sgnittifepipynawercsnutonoD.erusserphgihrednuretawtohyrevsniatnocreliobsihT
ehtgnirussaylevitisoptuohtiwreliobsihtfostnenopmocynatcennocsidottpmettaron
nehwtnempiuqednagnihtolcevitcetorpraewsyawlA.erusserponsahdnaloocsiretaw ehtnoylertonoD.seirujnidlacstneverpotreliobsihtgnicivresropugnitrats,gnillatsni
.reliobehtfoerusserpdnaerutarepmetehtenimretedotseguagerutarepmetdnaerusserp
oD.gnitareposireliobehtnehwtohyrevemocebhcihwstnenopmocsniatnocreliobsihT
cynahcuotton
.gnicivres
liobpeeK
.sdiuqilrosropav
.loocerayehtsselnustnenopmo
,acilis,animulaniatnocleufehtdnanoitsubmocfostcudorp,noitcurtsnocfoslairetamrelioB
rocixotrehtoro/dnasedyhedla,sedixonegortin,edixonomnobrac,slatemyvaeh
yrujnilanosrepesuacnacredroreporpehtnisnoitcurtsnillawollofoteruliaF
niatnocesohtllagnidulcni,snoitcurtsnilladaeR
.semitllataecalpniebtsumsdraugdnaserusolcne,setalprevocllA
lufmrah
foetatsehtotnwonkerahcihwdnayrujnisuoiresrohtaedesuacnachcihwsecnatsbus
reporpesusyawlA.mrahevitcudorperrehtodnastcefedhtrib,recnacesuacotainrofilaC
.ecnailppaehtybraengnikrowrognicivresnehwtnempiuqednasrotaripser,gnihtolcytefas
.htaedro
slaunamsrerutcafunamtnenopmocnide
rogniniatniam,gnitarepo,pugnitrats,gnillatsnierofebreliobehthtiwdedivorperahcihw
elbammalfrehtodnaenilosag,slairetamelbitsubmocmorfeerfdnaraelcaerare
ECITON
.launamsihtfokcabehtnodetnirpsihcihwfoypoca,ytnarrawdetimilasahreliobsihT
dellatsniyltcerroceraslortnocllatahteesotrotcartnocgnillatsniehtfoytilibisnopserehtsitI
.etelpmocsinoitallatsniehtnehwylreporpgnitarepoeradna
3
Table of Contents
I. Pre-Installation ............................... 6
II. Unpack Boiler ................................7
III. Venting/Air Intake Piping .............. 8
IV. Water Piping and Trim .................45
V. Gas Piping .................................... 50
VI. Electrical ....................................... 53
VII. Modular Installation .................... 62
VIII. System Start-up ............................64
IX. Service .......................................... 68
X. Repair Parts .................................. 74
Figure 1: Minimum Clearances to Combustibles
4
Figure 2: Dimensions
5
I. Pre-Installation
.yru
jni
F. Provide combustion and ventilation air in accordance
GNINRAW
snoitcurtsniesehtwolloftonoduoyfI
tluseryamnoisolpxeroerifa,yltcaxe
lanosreproegamadytreporpgnisuac
with applicable provisions of local building codes, or: USA - National Fuel Gas Code, NFPA 54/ANSI Z223.1, Air for Combustion and Ventilation;
Canada - Natural Gas Installation Code, CAN/
CGA-B149.1, or Propane Installation Code, CAN/ CGA-B149.2, Venting Systems and Air Supply for Appliances.
REGNAD
rehtoroenilosagerehwreliobllatsnitonoD
fosecruosro,sdiuqilrosropavelbammalf
racordyh
,srenaelc,sehcaelb.e.i(snob
cirbaf,srevomertniap,syarps,slacimehc
.derotsrodesuera).cte,srenetfos
ECITON
,reliobehtfotnetnocretawwolehtoteuD
ehtotdragerhtiwreliobehtfognizis-sim
evissecxenitluserlliwdaolmetsysgnitaeh
tnenopmocdetareleccadnagnilcycreliob
tnarrawTONSEODmahnruB.eruliaf
iaf
.gnizisrevo
A. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such requirements, installation must conform to the National Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/ CGA B149 Installation Codes.
B. Appliance is design certi ed for installation on
combustible fl ooring. Do not install boiler on carpeting.
C. Provide clearance between boiler jacket and
combustible material in accordance with local fi re ordinance. Refer to Figure 1 for minimum listed clearance from combustible material. Recommended service clearance is 24 inches from left side, right side and front. Service clearances may be reduced to minimum clearances to combustible materials.
D. Install on level oor. For basement installation provide
solid base such as concrete, if fl oor is not level or if water may be encountered on fl oor around boiler. Floor must be able to support weight of boiler, water and all additional system components.
reliobdezis-simybdesuacserul
otreliobehtezisrevoTONOD.snoitacilppa
snoitallatsnireliobraludoM.metsyseht
reliobfodoohilekilehtecuderyltaerg
GNINRAW
rianoitalitnevdnanoitsubmocetauqedA
reporperussaotdedivorpebtsum
.noitsubmoc
The following guideline is based on the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
1. Determine volume of space (boiler room). Rooms communicating directly with space (through openings not furnished with doors) are considered part of space.
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space. Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total Input.
a. If result is greater than or equal to 50 ft³ per
1,000 Btuh, space is considered an uncon ned space.
b. If result is less than 50 ft³ per 1,000 Btuh, space
is considered a con ned space.
4. Determine building type. A building of unusually tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed, and;
b. Weather-stripping has been added on openable
windows and doors, and;
c. Caulking or sealants applied in joints around
window and door frames, between sill plates and oors, between wall-ceiling joints, between wall panels, at plumbing and electrical penetrations, and at other openings.
5. For boiler located in an uncon ned space in a building of other than unusually tight construction, adequate combustion and ventilation air is normally provided by fresh air infi ltration through cracks around windows and doors.
E. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, condensate trap, control replacement, etc.).
6
ECITON
delaes(tnevtceridhtiwdetareposrelioB
gnideenmorftpmexeera)noitsubmoc
ehtmorfrianoitsubmocrofsnoisivorp
d
ellatsnisignipipekatniriadedivorp,moor
sihtnisnoitcurtsniehtdnaedocrep
.launam
6. For boiler located within unconfi ned space in building of unusually tight construction or within confi ned space, provide outdoor air through two permanent
openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within twelve (12) inches of top of space. Locate remaining opening within twelve (12) inches of bottom of space. Minimum dimension of air opening is three (3) inches. Size each opening per following:
a. Direct communication with outdoors. Minimum
free area of one (1) square inch per 4,000 Btu per hour input of all equipment in space.
b. Vertical ducts. Minimum free area of one (1)
square inch per 4,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
c. Horizontal ducts. Minimum free area of one (1)
square inch per 2,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
Alternate method for boiler located within
confi ned space. Use indoor air if two permanent openings communicate directly with additional space(s) of suffi cient volume such that combined volume of all spaces meet criteria for unconfi ned space. Size each opening for minimum free area of one (1) square inch per 1,000 Btu per hour input of all equipment in spaces, but not less than 100 square inches.
7. Combustion Air/Ventilation Duct Louvers and Grilles. Equip outside openings with louvers to prevent entrance of rain and snow, and screens to prevent entrance of insects and rodents. Louvers and grilles must be fi xed in open position or interlocked with equipment to open automatically before burner operation. Screens must not be smaller than ¼ inch mesh.
Consider the blocking effect of louvers, grilles and
screens when calculating the opening size to provide the required free area. If free area of louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
.noitareporeporperusniot
II. Unpack Boiler
NOITUAC
reliobpmubtonoD.reliobpordtonoD
.roolftsniagatekcaj
A. Move boiler to approximate installed position. B. Remove all crate fasteners. C. Lift and remove outside container. Save two of the
wooden slats from the container sleeve for use in Steps E and F.
D. Remove all boiler hold-down fasteners.
NOITUAC
nanireliobsihtgnitarepodiova,)riAroodnI-noitceSgnitneVees(noitsubmocrofriaroodnignisufI
sireliobfI.tneserpera.cte,tsudllawyrd,srebifnoitalusniesool,tsudwaserehwtnemnorivne
yliaddetcepsnidnadenaelcebtsumstropdnaroiretnirenrubeht,snoitidnocesehtrednudetarepo
GNINRAW
ebdluohsreliobsihtfonoitallatsnI
delliksdnadeniartybylnonekatrednu
p
E. Tilt the boiler to its front side or back side and slide a
wooden slat under the three raised feet.
F. Tilt the boiler in the opposite direction and slide
another wooden slat under the three raised feet.
G. Slide the boiler left or right off the skid using the two
wooden slats as runners.
.ycnegaecivresdeifilauqamorflennosre
H. Move boiler to its permanent location.
7
III. Venting / Air Intake Piping
GNINRAW
®
C4-92LAnonrehtoyna
onoD
perdoogniebdluohssecafrus
.yenmihc
umixamdeecxetonoD
Table 1: Air Intake / Vent System Options
rocillatemnon,leetssselniats613epyTro403epyT,dezinavlaghtiwreliobsihtesutonoD
.smetsystnevdesab
.ecnailppasihthtiwdoohtfardrorepmadcirtemorabaesutonoD
.reliobsihthtiwsrepmadtnevesut
,noitaroiretedtneverpoT.noitanimretdnuorasecafrusnomrofyamecidnaerutsioM
.).cte,detniap,delaes(ria
eraerehtosdellatsniebtsumdnanoitarepoefasrofriahserfsdeenecnailppasihT
italitnevdnanoitsubmocetauqedarofsnoisivorp
.riano
.epipekatniriafoezisecudertonoD
sernoitcurtsnirianoitsubmocwollofdnadnatsrednu,daeR
-erPehtnideniatnocsnoitcirt
.launamsihtfosnoitcurtsninoitallatsnI
diuqilrosropavelbammalfrehtoroenilosagerehwecnailppaetarepotonoD
,slacimehc,srenaelc,sehcaelb.e.i(snobracordyh
fosecruosro,s
,srenetfoscirbaf,srevomertniap,syarps
.riaehtnitneserpro/dnaderots,desuera).cte
nacecnailpparehtoon,yenmihchguorhtepiptnevgnillatsninehW
ehtotnidetneveb
.4elbaTotrefeR.shtgnelekatniria/tnevm
noitpOnoitpircseD
etarapeS.1
latnoziroH
etarapeS.2
lacitreV
lacitreV
riAroodnI.5
lanoitpO.6
etarapeS
latnoziroH
pip
itanibmoC.3
no
latnoziroH
noitanibmoC.4
tniriadna
atniriadnaepip
lanoitiddA tiKtneV deriuqeR
tnevehthtobhtiw)noitsubmocdelaes(tneVtceriD
yllatnozirohgnitanimretepipekatniriadnaepip
rofsnoitarteneplaudividnihtiw)llawedisahguorht(
.slanimretdnagnipipekatniriadnatneveht
tnevehthtobhtiw)noitsubmocdelaes(tneVtceriD
yllacitrevgnitanimretepipekatniriadnae
rofsnoitarteneplaudividnihtiw)foorehthguorht(
.slanimretdnagnipipekatniriadnatneveht
epiptnevehthtiw)noitsubmocdelaes(tneVtceriD
lanimretnommocatagniniojepipekatniriadna
pullawedisahguorht(yllatnozirohgnitanimretdna
.noitartenepenoylnohtiw)kciht"51ot
epiptnevehthtiw)noitsubmocdelaes(tneVtceriD
lanimretnommocatagniniojepipeka
htiw)foorehthguorht(yllacitrevgnitanimretdna
.noitartenepenoylno
dedivorpsinoitsubmocrofdesuriA-tneVrewoP
.gnidliubehtnihtiwmorf
tnevehthtobhtiw)noitsubmocdelaes(tneVtceriD
yllatnozirohgnitanimretepipek
rofsnoitarteneplaudividnihtiw)llawedisahguorht(
.slanimretdnagnipipekatniriadnatneveht
oN
oN
seY
seY
oN2elbaTeeS.
oN2
traP
rebmuN
eeS
2elbaT
eeS
2elbaT
116(
eS6-5
elbaTeeS.I
noitceS6-3
)21060
noitceS4-3 )10-222001( noitc )10-322001(
noitallatsnI
dnagniwarD
noitacificepS
)noitceSeeS(
.D
.E
.F
.G
H
8
Table 2: Vent System Components Included with Boiler
stnenopmoCmetsyStneVrebmuNtraP
"3lanimreTtneVdeteksaG
)7-GCSurht3-GCS(latnoziroH
"4lanimreTtneVdeteksaG
)9GCS&8-GCS(latnoziroH
"3-ekatnIriAcsiD
)4-GCS&3-GCS(
"4-ekatnIriAcsiD
)6-GCS&5-GCS(
"5-ekatnIriA
)9-GCSurht7-GCS(
1070118
70118
20
5406116
9406116
3606116
Table 3: Burnham Vent System and Air Intake System Components
metsyStneV
tnenopmoC
tF1xepiP.aiD"3U6926118
tF1xepiP.aiD"410-671001
tF3xepiP.aiD"3U8926118
tF3xepiP.aiD"410-771001
3U0036118
"410-181001
elbuoD"35116118
tF5xepiP.aiD"
tF5xepiP.aiD"410-871001
elbatsujdAxepiP.aiD"3U9136118
elbats
ujdAxepiP.aiD"410-971001
woblE°09.aiD"3U4926118
woblE°09.aiD"410-081001
woblE°54.aiD"3U2926118
woblE°54.aiD
eeTniarDlatnoziroH.aiD"3U2036618
eeTniarDlatnoziroH.aiD"410-281001
eeTniarDlacitreV.aiD"3U4036
eeTniarDlacitreV.aiD"410-381001
elbmihTllaWelgniS"36116118
elbmihTllaWelgniS"410-481001
elbmihTllaW
elbmihTllaWelbuoD"410-581001
traP
rebmuN
118
tnelaviuqE
epiPfoteeF
1
3
5
otlauqE**
htgneLdellatsnI
)46.1ot60.1(
5
5
½7
½7
---
---
metsySekatnI stnenopmoC
)srehtOybstraP(
tnelaviuqE
*epiPfoteeF
tF1xepiPDI"5ro,"4,"31
tF2xepiPDI"5ro,"4,"32
tF4xepiPDI"5ro,"4,"34
tF5xepiPDI"5ro,"4,"35
woblE°09"4ro,"35
54"4ro,"35
woblE°
woblE°09"56
woblE°54"56
nodesaBepiPfoteeFtnelaviuqE*
ngiseDepiPekomS"4dradnatS
Table 4: Vent/Air Intake Length
ledoM
.niM.xaM.niM.xaM.niM.xaM.niM.xaM.niM.xaM
4-GCS&3-GCS805----------------805--------
6-GCS&5-GCS--------805--------805--------
7-GCS----------------805805--------
9-GCS&8-GCS-----
epiPekatnIriA"3
).tF.viuqE(
-----------804--------804
epiPekatnIriA"4
).tF.viuqE(
epiPekatnIriA"5
).tF.viuqE(
qE(
epiPtneV"3
).tF.viu
epiPtneV"4
).tF.viuqE(
9
A. Vent Guidelines Due to Removal of an Existing
Boiler
For installations not involving the replacement of an
existing boiler, proceed to Step B.
When an existing boiler is removed from a common
venting system, the common venting system is likely to be too large for proper venting of the remaining appliances. At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, and other defi ciencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range-hoods and bathroom exhausts, so they will operate at maxi mum speed. Do not operate a summer exhaust fan. Close replace dampers.
4. Place in operation the appliance being inspected. Follow the Lighting (or Operating) Instructions. Adjust thermo stat so appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after fi ve (5) minutes of main burner operation. Use the fl ame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remain ing connected to the common venting system properly vents when tested as outlined above, return doors, win dows, exhaust fans, fi replace dampers and any other gas burning appliance to their previous conditions of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, NFPA 54/ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part II in the National Fuel Gas Code, NFPA 54/ ANSI Z223.1.
B. General Guidelines
1. Vent system installation must be in accordance with National Fuel Gas Code, NFPA 54/ANSI Z221.3 or applicable provisions of local building codes. Contact local building or fi re offi cials about restrictions and installation inspection in your area.
2. The SCG is designed to be installed as either a Direct Vent boiler or Power Vent boiler. In the Direct Vent confi guration all of the air for combustion is supplied directly to the burner enclosure from outdoors and fl ue gases are vented directly outdoors (through wall or roof). In the Power Vent confi guration, room air provides air for combustion and ventilation. Flue gases are still vented directly outdoors (through wall or roof).
Note: Venting requirements change if indoor air is
used.
3. Refer to the appropriate drawings in this section of this manual to determine the proper confi guration of venting system. See Table 1.
4. This appliance requires a Special Gas Vent. The product is designed to use Burnham supplied AL 29-4C® Stainless Steel vent system components. The following manufacturers offer similar AL 29-4C® components and are approved for use with this product. Heat-Fab Inc. - Saf-T-Vent, Flex-L International Inc. - Star-34, Z-Flex U. S., Inc. - Z-Vent, and Protech Systems , Inc.- FasNSeal™ or equivalent. The use of these alternate manufacturer’s venting systems will require adapters to connect to the Burnham supplied vent connector and vent terminal. These adapters are not supplied with this unit and should be obtained from the supplier of the alternate manufacturer’s venting system. See Table 3 for complete list of Burnham Vent System Components.
5. Horizontal vent pipe must maintain a minimum ¼ inch per foot slope down towards boiler.
6. Use noncombustible ¾ inch pipe strap to support horizontal runs and maintain vent location and slope while preventing sags in pipe. Do not restrict thermal expansion or movement of vent system. Maximum support spacing is fi ve (5) feet. Do not penetrate any part of the vent system with fasteners.
7. Vent length restrictions are based on equivalent length of vent/air pipe (total length of straight pipe plus equivalent length of fi ttings). Maximum vent/air lengths are listed in Table 4. Do not exceed maximum vent/air intake lengths. Table 3 lists equivalent lengths for fi ttings. Do not include vent/ air terminals in equivalent feet calculations.
8. Provide and maintain vent pipe minimum clearances to combustible materials. Vent pipe minimum clearance to combustible material is four (4) inches when vent is installed in a fully enclosed (chase) application or three (3) inches when vent is installed
10
with at least one side open, similar to a joist bay application. Use double wall thimble [Burnham Part No. 8116115 (3”), 100185-01 (4”)] when penetrating a combustible wall.
9. Do not install venting system components on the exterior of the building except as specifi cally required by these instructions. The vent termination location is restricted as follows:
a. Minimum twelve (12) inches above grade plus
normally expected snow accumulation level, or seven (7) feet above grade if located adjacent to public walkway. Do not install over public walkway where local experience indicates appliance fl ue gas vapor or condensate creates a nuisance or hazard.
b. Minimum three (3) feet above any forced air
inlet located within ten (10) feet.
c. Direct Vent - Minimum one (1) foot below, one
(1) foot horizontally from, or one (1) foot above any door, window, or gravity air inlet.
Power Vent - Minimum four (4) feet below, four
(4) feet horizontally from, or four (4) feet above any door, window, or gravity air inlet.
d. Minimum four (4) feet horizontally from electric
meters, gas meters, regulators, and relief valves. This distance may be reduced if equipment is protected from damage due to condensation or vapor by enclosure, overhangs, etc.
e. Minimum twelve (12) inches from overhang or
corner of building.
10. Enclose vent passing through occupied or unoccupied spaces above the boiler with material having a fi re resistance rating of at least equal to the rating of the adjoining fl oor or ceiling. Maintain minimum clearances to combustible materials. See Figure 1.
Note: For one or two family dwellings, fi re
resistance rating requirement may not need to be met, but is recommended.
11. Plan venting system to avoid possible contact with plumbing or electrical wires. Start at vent connector on top of boiler and work towards vent terminal.
12. Once a vent pipe manufacturer and system is chosen never mix and match vent systems.
13. If a non-standard length pipe is required:
Gasketed Vent System: The use of the adjustable
length pipe (P/N 8116319U) is recommended to complete a non-standard pipe length. This pipe requires a minimum installed length of 12¾ inch and can adjust across a 7 inch gap up to a maximum of 19¾ inch long. (Note for the adjustable pipe the installed length should be measured from the centerline of the bead on the male end of the fi rst pipe to the end of the female pipe excluding the locking band of the second pipe with a single gasket.) Only in the event the adjustable length pipe is not suffi cient a standard length pipe may be cut using the procedure outlined below for the Gasket­Less Vent System.
GNINRAW
fohtgneldellatsnimumixamdeecxereveN
.epiphtgnelelbatsujdarofsehcni¾91
.elbissopsiegakaelsageulffoksiR
ECITON
rodelifdnaepiphtiwerauqsebtsumtuC
ylluferaC.gniniojerofebhtoomsdednas
e
.launamsihtnideificeps
C. Install Vent Pipe, Burnham Gasketed Vent System.
1. Procedure for Joining Burnham Gasketed Vent Pipe and Fittings. See Figure 3.
htiwdnahybepiptucfossendnuorerusn
VTRhtiwtniojlaeS.gnillatsnierofebsevolg
Figure 3: Burnham Gasketed Vent Joint Detail
11
a. Wipe the male end of each joint using an alcohol
pad to remove any dirt and grease.
b. Align weld seams in pipes and use a slight
twisting motion to FULLY insert male end into female end of joint. Ensure bead in male end of pipe is below locking band and rest against the end of the female pipe. Verify the factory­installed gasket is not dislodged or cut.
c. Tighten locking band by HAND with a 5/16”
nut driver until snug plus ¼ turn. DO NOT SECURE JOINTS WITH SHEET METAL SCREWS OR POP RIVETS. DO NOT PUNCTURE THE VENT SYSTEM!
d. Once the installation is complete, operate
appliance and inspect all joints to ensure that fl ue gases and/or liquid condensate will not escape.
D. Separate Horizontal Venting System. See Figures 4,
5A and 5B.
Vent Piping
1. This boiler is supplied with components as standard equipment for installation of the separate horizontal venting system.
2. Do not exceed maximum vent/air intake lengths. Refer to Table 4.
3. Recommended horizontal installation consists of vent being sloped down ¼ inch per foot away from boiler. See Figure 4.
4. Use appropriate designed thimbles when passing through combustible walls (thimble use optional for noncombustible walls). Insert thimble through wall from outside. Secure outside fl ange to wall with nails or screws, and seal ID, OD and vent holes with sealant material. Install inside fl ange to inside wall, secure with nails or screws, and seal with sealant material.
5. For noncombustible wall application when thimble is not used, size opening such that bell with locking band attached cannot pass through.
6. Join vent terminal to vent pipe. See Figures 5A and 5B.
7. Insert vent pipe through thimble/opening from outside and join to vent system. Apply sealant between vent pipe and opening/thimble to provide weathertight seal.
Air Intake piping - See Figures 4, 5A and 5B.
8. Locate air intake termination on the same wall as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with vertical venting and sidewall combustion air inlet or visa versa, if installation conditions do not allow alternate arrangement.
9. Do not exceed air intake length. See Table 4.
10. Use single wall metal or PVC pipe. a. Air intake pipe diameter is based on boiler size.
SCG-3 & SCG-4 uses 3 inch diameter piping. SCG-5 & SCG-6 uses 4 inch diameter piping. SCG-7 thru SCG-9 uses 5 inch diameter piping.
11. Air intake termination must be located:
Horizontal - At least twelve (12) inches above
grade plus the expected snow accumulation.
12. Start at collar on burner enclosure (inside boiler jacket) and work towards the air intake terminal.
13. Maintain minimum of ¼ inch per foot slope on horizontal runs. Slope towards air inlet terminal when possible. If not, slope towards boiler.
14. The air intake pipe must be adequately supported with straps or supports no less than fi ve (5) feet apart on horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts without collapse.
15. Inlet air pipe penetration:
Horizontal - Size wall penetration to allow easy
insertion of air inlet piping. Seal around pipe with sealant to form weathertight exterior joint.
16. Seal all joints airtight, using silicone caulk or self­adhesive aluminum tape.
17. Install Air Intake T erminal :
Horizontal - Remove four (4) screws from cover
plate and remove cover plate from terminal. Insert intake piping into intake terminal collar. Secure terminal to intake piping and seal joint with silicone caulk or self-adhesive aluminum tape. Apply continuous bead of silicone caulk around the back of the intake terminal, approximately ¼ inch from its edge. Push inlet terminal inward until terminal’s back fl ange is against the wall surface. Secure the terminal with noncorrosive fasteners (stainless steel, brass or aluminum) to the wall. Reinstall the cover plate with four (4) screws. Apply a bead of silicone caulk to perimeter of intake terminal’s back fl ange to provide a weathertight seal.
12
Figure 4: Recommended Separate Horizontal – Vent/Air Intake Installation
13
14
Figure 4B: Alternate Separate Horizontal – Vent/Air Intake Installation
Figure 5A: Separate Horizontal – Vent/Air Intake Terminal Confi guration (SCG-3 thru 7)
15
16
Figure 5B: Separate Horizontal – Vent/Air Intake Terminal Confi guration (SCG-8 and 9)
E. Separate Vertical Venting System - See Figures 6, 7, 8A, 8B and 9.
ECITON
.reliob
foorfoesuehteriuqersnoitartenepfooR
htiwdeilppuston-rallocmrotsdnagnihsalf
Vertical Venting
1. Do not exceed maximum vent lengths. Refer to Table 4.
2. Installation of a vertical vent tee 8116304U is required on all vertical vent applications. See Figures 6 and 7. Attach vertical vent drain tee directly to elbow or horizontal pipe from an elbow immediately after vent connector.
3. Slope horizontal runs minimum ¼ inch per foot. Slope towards vertical vent drain tee. Position weld seams in vent pipes, in all horizontal runs, at the top to avoid condensate from lying on the seams.
4. Install fi re stops where vent passes through fl oors, ceilings or framed walls. The fi re stop must close the opening between the vent pipe and the structure.
5. Whenever possible, install vent straight through the roof. Refer to Figure 7 if offset is necessary. Maintain minimum clearance to combustible materials.
6. Install V ent Terminal. a. Size roof opening to maintain minimum
clearance from combustible materials.
b. Extend vent pipe to maintain minimum vertical
and horizontal distance of twelve (12) inches from roof surface. Allow additional vertical distance for expected snow accumulation. Provide brace as required. Refer to Figures 8A and 8B.
ECITON
foorfoesuehtseriuqergnitnevlacitreV
tneverpotrallocmrotsadnagnihsalf
.erutcurtsehtgniretnemorferutsiom
c. Install storm collar on vent pipe immediately
above fl ashing. Apply Dow Corning Silastic 732 RTV Sealant between vent pipe and storm collar to provide weathertight seal.
d. Attach vent terminal.
Vertical Air Intake Piping
7. Do not exceed maximum air intake length. Refer to Table 4.
8. Locate air intake termination on the same roof location as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with vertical venting and sidewall combustion air inlet or visa versa, if installation conditions do not allow alternate arrangement.
9. Use single wall metal pipe or PVC and fi ttings available at most heating distributors.
a. Air intake pipe diameter is based on boiler size.
SCG-3 & SCG-4 uses 3 inch diameter piping. SCG-5 & SCG-6 uses 4 inch diameter piping. SCG-7 thru SCG-9 uses 5 inch diameter piping.
10. Air intake termination must be located: Vertical - At least twelve (12) inches above the roof
surface plus the expected snow accumulation.
11. Start at collar on burner enclosure (inside boiler
jacket) and work towards the air intake terminal.
12. Maintain minimum of ¼ inch per foot slope on
horizontal runs. Slope down towards boiler.
13. The air intake pipe must be adequately supported
with straps or supports no less than fi ve (5) feet apart on horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts without collapse.
14. Inlet air pipe penetration:
Vertical - Size roof opening to allow easy insertion
of inlet piping and allow proper installation of ashing and storm collar.
a. Use appropriately designed vent fl ashing
when passing through roofs. Follow fl ashing manufacturers’ instructions for installation procedures. Flashing manufacturers are Air­Jet, American Metal Products, Metal Fab, and Simpson Dura-Vent.
b. Extend air intake pipe to maintain minimum
vertical and horizontal distance of twelve (12) inches from roof surface. Allow additional vertical distance for expected snow accumulation. Provide brace as required. Refer to Figures 8A and 8B.
c. Vertical air intake requires fl ashing and a storm
collar to prevent moisture from entering the structure.
17
d. Install storm collar on air intake pipe
immediately above fl ashing. Apply Dow Corning Silastic 732 RTV Sealant between air intake pipe and storm collar to provide weathertight seal.
e. All exposed air intake piping must be
constructed of corrosion resistant material such as aluminum, stainless steel or PVC.
15. Seal all joints airtight, using silicone caulk or self­adhesive aluminum tape.
16. Install Air Intake Terminal:
Vertical - Insert intake piping into intake terminal
collar. Secure terminal to intake piping and seal joint with silicone caulk.
18
Figure 7: Attic OffsetFigure 6: Vertical Vent Installation
19
20
Figure 8A: Vertical Vent/Air Termination (3” Vent Terminal)
Extend Vent/Air Intake Piping to maintain minimum vertical (“X”) and minimum horizontal (“Y”) distance of twelve (12) inches from
roof surface. Allow additional vertical (“X”) distance for expected snow accumulation.
Figure 8B: Vertical Vent/Air Termination (4” Vent Terminal)
Extend Vent/Air Intake Piping to maintain minimum vertical (“X”) and minimum horizontal (“Y”) distance of twelve (12) inches from roof surface. Allow ad-
21
ditional vertical (“X”) distance for expected snow accumulation.
22
Figure 9: Vertical Air Intake Piping
F. Combination Horizontal Venting System –SCG-3 Through SCG-6 ONLY – See Figures 10 and 11.
ECITON
tonstnenopmocseriuqermetsystnevsihT
.reliobehthtiwdeilppus
2.
Install Combination Vent/Air Terminal. See Figure 11.
a. After determining the location with reference to Section B - General Venting Guidelines, cut a 6-1/8 inch square
opening in the wall for the air box sub-assembly which is 6 inch square.
b. Remove and save shipping screw from end panel with collar and vent pipe assembly. This will be reinstalled in a later
step.
1. Do not exceed maximum vent/air intake lengths. Refer to Table 4.
21060116rebmuNtraPnotraCtneV)wolebsmetisedulcni(
noitpircseDrebmuNtraPtnenopmoC
A)gnol'2xerauqs"6(ylbmessA-buSxoBriA 11060116
B)erauqs"01(revoCllaWroiretxE 61060117
CrecudeRepiPtneV"3x"4 93
D)2(revoCroiretxElaeS-etalP 71060117
E)91(wercSlateMteehSleetSsselniatS"½x8# 74006808
F)8(wercSenihcaMleetSsselniatS"¼x23-01# 24806808
26118
G)4(recapSmunimulA"½x23-01# 71616808
BMOC
STNENOPMOCMETSYSTNEVLATNOZIROHNOITANI
23
c. From exterior of building, insert air box sub-
assembly into square opening. Push air box inward until wall fl ange is against wall, check for level and mark the location of the four (4) securing holes on the exterior wall. Remove air box from wall.
d. Drill four (4) pilot holes, properly sized for the
non-corrosive fasteners (stainless steel, brass, or aluminum) to be used to secure the wall fl ange to the exterior wall. (Securing screws not supplied with kit.)
e. Attach four (4) 1/2 inch long threaded aluminum
spacers to the outer fl anges of the exterior wall fl ange with four (4) number 10 - 32 x 1/4 inch stainless steel machine screws provided. (See Figure 11.)
f. Apply a 1/4 inch thick continuous bead of
silicone caulk to perimeter of exterior wall ange’s back surface to provide a weathertight seal.
g. Reinstall air box sub-assembly into opening in
exterior wall and secure to wall.
GNINRAW
.desuebtsumsrenetsafevisorroc-noN
h. Apply a bead of silicone caulk to perimeter of
wall fl ange, where the wall and fl ange join. Use a tool or your fi nger and apply pressure while smoothing caulking to provide a weathertight seal.
i. From interior of building, insert end panel with
collar and vent pipe assembly into open end of air box sub-assembly. (See Figure 11.)
j. Secure end panel to air box sub-assembly with
shipping screw and thirteen (13) number 8 sheet metal screws provided.
k. From exterior of building, position 10 inch
square exterior wall cover over exterior wall ange. Insert 3 inch diameter vent pipe into center opening in terminal cover. Align four (4) holes on cover with 1/2 inch long threaded spacers on wall fl ange. Secure terminal cover with four (4) number 10 - 32 x 1/4 inch stainless steel machine screws provided.
l. Apply a bead of silicone caulk to perimeter of
plate-seal and around pipe. Secure plate-seal to exterior cover with six (6) #8 stainless steel sheet metal screws provided. Smooth caulk around plate-seal and pipe to provide weathertight seal.
m. Install Vent Terminal supplied with boiler to vent
pipe penetrating through terminal cover. Join terminal and pipe with locking band and seal with RTV (see Figure 3).
3. Install Vent Piping. See Figure 10 and 11.
a. Start at vent connector on boiler and work
towards combination vent/air terminal.
b. Installation of a vertical vent tee 8116304U is
required on all vertical vent applications. See Figures 12 and 13. Attach vertical vent drain tee directly to elbow or horizontal pipe from an elbow immediately after vent connector.
c. Slope horizontal runs minimum ¼ inch per foot.
Slope towards vertical vent drain tee. Position weld seams in vent pipes, in all horizontal runs, at the top to avoid condensate from lying on the seams.
d. Use 3/4 inch pipe strap to support horizontal runs
and maintain vent location and slope. Maximum support spacing is fi ve (5) feet.
e. Install vent piping to connect vent connector
on boiler and combination vent/air terminal. Reference Section B - General Venting Guidelines for proper procedure for joining pipe and fi ttings.
f. Connect vent piping to combination vent/air
terminal. See Figure 10.
4. Install Air Intake Piping. See Figures 10 and 11.
a. Do not exceed air intake length. See Table 4. b. Use single wall metal pipe or PVC and fi ttings
available at most heating distributors.
c. Air intake pipe diameter is based on boiler size.
SCG-3 & SCG-4 uses 3 inch diameter piping. SCG-5 & SCG-6 uses 4 inch diameter piping. SCG-7 thru SCG-9 uses 5 inch diameter piping.
d. Start at collar on burner enclosure (inside boiler
jacket) and work towards the combination vent/ air terminal.
e. Maintain minimum of 1/4 inch per foot slope on
horizontal runs. Slope down towards boiler.
f. The air intake pipe must be adequately supported
with straps or supports no less than fi ve (5) feet apart on horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts without collapse.
g. Connect Air Intake Piping to Combination Vent/
Air Terminal. See Figure 10.
NOTE: When installing 3 inch diameter air intake piping for a SCG-3 or SCG-4 application, the use of a 4 inch x 3 inch reducer will be required to connect air intake piping to combination vent/air terminal. (Reducer included with combination horizontal venting kit).
h. Seal all joints airtight, using silicone caulk or
self-adhesive aluminum tape.
24
Figure 10: Combination Horizontal – Vent/Air Installation (SCG-3 thru 6)
25
26
Figure 11: Combination Horizontal – Vent/Air Terminal Installation (SCG-3 thru 6)
G. Combination Vertical Venting System – SCG-3 Through SCG-6 ONLY – See Figures 12, 13 and 14.
ECITON
tonstnenopmocseriuqermetsystnevsihT
.reliobehthtiwdeilppus
rebmuNtraP
noitpircseD
rebmuNtraPnotraCtneV 10-22200110-322001
eeTretratS 10-42200110-522001
rotpadAriA/tneV 10-622001
4-GCS&3-GCS6-GCS&5-GCS
STNENOPMOCMETSYSTNEVLACITREVNOITANIBMOC
27
1. Saf-T Vent SC is an advanced concentric vent system designed for zero clearance installation in residential applications. The inner wall is constructed from superferritic AL29-4C® stainless steel. The outer wall is also constructed from stainless steel, providing durability and a lasting nish.
2. As a Special Gas Vent system: Saf-T Vent is approved for use on ANSI Category I, II, III, and IV Gas-Burning Appliances and certain Direct Vent Appliances. Saf-T Vent SC is appropriate for use on appliances that specify an AL29-4C venting system.
3. As a Sealed Combustion system: The unique concentric design of Saf-T Vent SC also allows it to function as a pipe-in-a-pipe vent. Products of combustion are exhausted out through the inner wall while combustion air is drawn in through the outer wall. An appliance can be direct-vented with only a single penetration through the building structure.
This application must be approved by the Appliance Manufacturer.
Note: Saf-T Vent SC includes an integral seal and
does not require RTV sealant. However, sealant may be necessary when connecting Saf-T Vent SC components directly to certain appliance fl ue collars and to the gasket-less Saf-T Vent GC and Saf-T Vent CI vent systems.
For applications up to 550°F/288°C, approved
sealants include GE RTV 106 and Dow Corning
736.
For applications up to 300°F/149°C, approved
sealants include GE RTV 106 and Dow Corning
732.
4. Pre-Installation Considerations:
• Proper planning prior to installation is essential
as to avoid possible contact with concealed plumbing or electrical wiring inside walls, oors or ceilings as well as maintaining proper clearances. Be sure to plan a suffi cient number of supports for the entire system that will maintain the required straight-line pitch and hold
the system in place. A continuous straight-line pitch of at least ¼” (2°) to the foot on horizontal runs must be maintained in order to properly rid the system of the corrosive condensate.
5. General Installation Requirements:
• Saf-T Vent SC vent sections, or other Saf-T Vent products, must be used throughout the entire length of the system. Alternatives such as galvanized pipe, PVC, nonmetallic pipe, prefabricated chimney, fi eld-fabricated vents or Type B vent sections must not be used. Do not mix pipes, fi ttings, or joining methods from different manufacturers.
• More than one appliance may not be interconnected to any part of the venting system.
• Any penetrations of ceilings, fl oors or walls must be properly fi re-stopped.
• Whenever gas-burning equipment is installed in the same space where halogenated substances may exist (refrigerants, solvents, bleaches, salts, etc.), clean outside air must be utilized for combustion.
• The vent system shall not be routed into, through or within any other actively used vent or chimney.
• Seal weather exposed joints of the outer jacket with foil tape or an exterior grade silicone sealant.
• Combustible Material is any material made of or surfaced with wood, compressed paper, plant bers, or other materials that are capable of being ignited or burned. Such material shall be considered combustible even though it is fl ame- proofed, fi re-retardant, or plastered. (Source: NPFPA54/ANSI Z223.1-1999.)
• Non-Combustible Material is any material that is not capable of being ignited and burned, such material consisting entirely of, or a combination of, steel, iron, brick, tile, concrete, slate, asbestos, glass and plaster. (Source: NPFPA54/ ANSI Z223.1-1999.)
Clearances to Combustibles:
otecnaraelC
retemaiD
elbitsubmoC
lairetaM
"0
"4-"3
"1004
"0
"1055
"0055ynAlairetamelbitsu
28
eulFmumixaM
)F°(.pmeTsaG
055
033
004,nepoedis1tsaelta,desolcnenU
noitatneirOerusolcnE
,lacitreV
stesffOoN
,latnoziroH
htiwlacitreV
sffO
ste
elbitsubmocybdesolcneylluF
sedisllanolairetam
anolairetamelbitsubmoc
sedis3fomumixam
bmocnoN
• For a venting system that extends through any zone above that on which the connected appliance is located (except for one and two family dwellings), the vent system shall be enclosed with an enclosure having a fi re resistance rating equal to or greater than that of the fl oor or roof assemblies through which it passes.
• Design any enclosure to permit inspection of the system.
• Do not place any type of insulation in any required clearance spaces surrounding the vent system.
6. Vertical Installation Requirements: a. Seal weather exposed joints of the outer jacket
with foil tape or an exterior grade silicone sealant.
b. The vent system must terminate at least 3 feet
above the roof line and at least 2 feet higher than any portion of the building within 10 feet.
c. When terminated at a height of more than 6 feet
the stack must be supported by a support bracing. The vent should be supported every 10 feet.
d. The total continuous distance of the vent system
from the appliance fl ue collar to the termination shall not exceed that specifi ed in the appliance manufacturer’s installation instructions.
e. In cold climates do not install a condensate drain
on the exterior of the building. Doing so may result in dangerous icy conditions on surfaces near the drain and may cause damage to the vent system and/or the building exterior.
f. Install supports every 10 feet vertically along the
vent pipe route. Vertical supports are required after every transition to vertical and are required after every offset elbow. When the vent is free standing and penetrates a roof/ceiling another means of support must be used at a second location. Refer to the Vertical Supports section in this manual.
29
7. Joint Assembly Instructions:
a. Before joining the sections or fi ttings together, use an alcohol pad to wipe the joint area of both ends of the inner
pipe. This will remove any foreign matter which may affect the integrity of the seal. Install the system with the female ends (ends with the red seal) pointing away from the appliance. (Unless specifi ed differently by the appliance manufacturer.)
b. Insert the male end of the inner pipe into the female end of the previous section. In extremely dry conditions it may be
helpful to moisten the seal with clean water prior to assembly. Push fi rmly until the outer jacket has made contact with the snap ring located inside the female end of the previous section. When fully assembled the outer female end will overlap the male end 1”.
30
c. Use the three (3) self-tapping screws provided to connect the outer vents. No pre-drilling is required.
NOITUAC
,llirdeuqrotelbairavagnisufI.nethgitrevotonoD
.desuebnactevirtoptrohsro).xamgnol"½(wercs
swercsllatsniotgnitteseuqrotwolaesu
sa,
retemaidregrala,gninethgitrevooteuddeppirtssemocebelohafI.selohehttuopirtsotton
8. Straight Sections Cut To Length: If a custom length of SC is necessary, a standard vent
section can be cut. a. Measure the distance of the length needed, taking the
measurement from the end of one of the outer jackets to the beginning of the other outer jacket on the section to connect to, (A to B on diagram).
b. Select a section that is longer than the required
length.
c. It will be necessary to disassemble the vent prior to
cutting.
Stand the section on end with the holes up. Find the
end of snap ring and pry it out of its groove, being careful not to damage the ends of the vent pipes. Pull up on end of the snap ring and pull it out from the end of the pipe. It may want to spiral out as it is removed. After the snap ring is removed, the inner vent pipe can be separated from the outer jacket.
d. Add 2” to the distance measured previously for the
cut length of the outer jacket. Mark a cut line on the outer jacket on the male end (the end without holes in it).
An effective way of marking is to run a length of tape
around the section, assuring a square cut.
e. Add 3” to the distance measured previously for the
cut length of the inner vent pipe. Mark a cut line on the inner vent on the male end (the end without the red seal).
The inner pipe is always cut 1” longer than the
outer pipe.
f. WEAR GLOVES, as cut ends are very sharp. Cut
the pipes with an abrasive cutoff saw, plasma cutter, or compound snips. If using snips, start the cut at the male end and follow a spiral path around the pipe until the cutoff mark is reached. File off any burrs or rough edges that develop in the cutting process and clean off any dust or grit. If the cutting process distorts the roundness of the pipes, carefully use your thumbs to re-round the ends.
g. Reassemble the inner vent into the outer jacket and
reinstall the snap ring into the groove. Push the inner vent into the outer jacket until the triangle on the inner vent is seated fi rmly against the bead on outer jacket. Start one end of the snap ring into the groove of the outer pipe. Slowly turn and feet the snap ring into the groove in a spiral motion, and continue around the pipe until the snap ring is fully inserted. Ensure that the triangle on the inner vent is all the way down against the bead of the outer jacket by pushing in fi rmly. Also ensure that the snap ring is completely in the groove all the way around outer jacket.
31
9. Air Intake Connections for Direct Vent and Sealed Combustion Appliances*:
The Air Intake Tee may be used on approved direct vent
and sealed combustion appliances that have separate (non­concentric) air intake and fl ue exhaust collars. The male end of the tee connects to EZ Seal appliance adapters and the tee takeoff/snout connects to the appliance air intake.
• Insert the male end of the Air Intake Tee into the female
end of the EZ Seal vent section or appliance adapter and complete the ring and tab connection.
• Insert the male end of the next SC section into the female
end of the Air Intake Tee and secure as described elsewhere in this manual.
• Connect the tee takeoff to the appliance combustion air inlet
using appropriate hose or pipe.
* Direct Vent Appliances are constructed and installed so that
all air for combustion is supplied directly from the outside atmosphere. The passage for the combustion air is allowed a small amount of leakage in the building environment. No special installation considerations are required to use Saf-T Vent SC on Direct Vent appliances unless specifi ed by the appliance manufacturer. Sealed Combustion appliances are similar to Direct Vent except the combustion air passage must be sealed to prevent leakage within the building envelope. When Saf-T Vent SC is used on approved Sealed Combustion appliances the joints of the outer jacket must be sealed with a foil tape (example: 3M 425), or approved silicone sealant (example: Dow Corning 732).
10. Condensate Drains: When An Internal Condensate Drain is NOT Part of the
Appliance:
• A Saf-T Vent SC In-Line Drain Section is strongly recommended. Install this drain fi tting as close to the appliance fl ue collar as possible.
• A condensate drain is required for every 30 feet of horizontal vent and at/near the bottom of a vertical stack.
• Use the In-Line Drain Section for a straight horizontal or vertical run. When used horizontally, rotate the fi tting so that
the drain tube is as vertical as possible.
• A Condensate Drain Tube Kit is available to direct the condensate to an appropriate location, i.e. fl oor drain or vented sanitary sewer connection. A trap loop must be formed into the drain hose and must be a diameter that is at least four (4) times the appliance’s rated stack pressure in inches of water column or 3 inches, whichever is greater. Secure the loop with a cable tie. Prior to fi nal assembly the trap loop must be ‘primed’ by pouring a small quantity of water into the drain hose. Inspect at least annually to verify the trap is ‘primed’.
• Follow all local and national codes and regulations for the draining of acidic condensate.
• In cold climates do not install a condensate drain on the exterior of the building. Doing so may result in dangerous icy conditions on surfaces near the drain and may cause damage to the vent system and/or the building exterior.
32
11. Horizontal Supports: Saf-T Vent SC must have supports for every six (6) feet of horizontal run and after every transition from vertical to
horizontal. Support hangers by themselves do not maintain the necessary clearances to combustible materials; be sure to consider clearances when planning the system.
The supports must be secured to solid material using at least #10 fasteners. Do not fasten supports to drywall sheathing
without using hollow wall anchors. The conduit supports must maintain the ¼” per foot pitch to avoid collection of condensate in the vent. Position the vent so that the welded seam is on the top.
0” Clearance Support Clamp, (SC_ _SUP): Attach the bracket to the structure but do not tighten in place. Open the
hose clamp and slip it under the support bracket. Position the clamp between the mounting screws and rotate the clamp so that the screw housing will be accessible after the vent is installed. Restart the threads on the hose clamp and securely tighten the mounting screws to the structure. This can also be installed vertically.
1” Clearance Support Clamp, (SC_ _SUP1): Supports the vent at 1” clearance to the structure. Line up the support
mounting brackets so that the mounting screws will follow the center line of the vent section. This can also be installed vertically.
33
Support Clamp, (4_ _27SS): Support clamps are sold in pairs and can be clamped around the vent and suspended from a
rod or cable. They can be used singularly as a saddle clamp to rest the vent in and suspended from two (2) rods or cables.
Support Legs Rotated Horizontally: Support legs can be used on horizontal runs by rotating the clamp at the rivet
connection. The legs can be cut to shorter lengths if necessary.
Vertical Supports, (SC_ _VSL): Vertical support legs can be used above or below a structure for support. To install,
slide the support clamp over the end of the vent section, leaving the clamp loose. Position the support legs and install two (2) screws through each leg into the structure. Tighten the clamp around vent pipe. The legs can be cut to shorter lengths if necessary and can rotate around the support clamp at the rivet connection. By rotating the clamp to a horizontal position the support legs can be used on horizontal runs.
34
Fire Stop/Wall Thimble/Support, (SC_ _FS):
• The Saf-T Vent SC Fire Stop can be used as a fi restop, a wall thimble, or as a support plate.
• To use as a Wall Thimble prepare an opening according to the chart below. Remove any insulation from the opening,
using additional framing if necessary. Attach the plate over the center of the opening using appropriate fasteners.
• Install the vent section through the thimble plate and secure the section to the thimble by screwing the self-tapping
screws through the holes in the tabs on the plate and into the outer wall of the vent. Apply silicone sealant around the vent section where it passes through the plate and around the plate where it is attached to the structure.
• To use as a Firestop before passing through ceilings or enclosed chases, prepare a round or square opening ¼” larger than
the outer jacket (5¼” for 3” vent or 7¼” for 4” vent). Remove any insulation from the opening. Secure the fi restop to the structure at the four (4) corners. Install the vent section through the fi restop and secure to the thimble by screwing the self-tapping screws through the holes in the tabs on plate and into outer wall of the vent. This method can also be used to support the vent section either vertically or horizontally.
Tall Cone Flashing:
Directly On Roof or Curb: Tall Cones are available for at (SC_ _TCF), 2/12 pitch (SC_ _TCFA), and 6/12 - 12/12 pitch roofs (SC_ _TCFB).
Prepare a square or round opening at least 1/4” larger than the outer jacket (5¼” for 3” vent or 7¼” for 4” vent). Remove any insulation from the opening. Apply weather-stripping or outdoor caulk to the bottom of the cone plate and attach the plate to the roof using common construction methods. Flash over the cone plate and seal the fastener heads using normal roofi ng requirements. When the vent pipe is in place through the Tall Cone, attach a storm collar (sold separately) around the pipe. Apply high temperature silicone sealant around the pipe where it passes through the top of the storm collar. Continue to install vent sections as needed to meet the height requirements by code. Seal weather exposed joints of the
outer jacket with foil tape or an exterior grade silicone sealant.
35
Vertical Terminations, (SC_ _VT): Install the vertical termination adapter into the last vent section and secure with the
three (3) self-tapping screws provided. If the exhaust termination needs to be extended, a section of EZ Seal vent can be connected directly to the vertical termination adapter. Seal weather exposed joints of the outer jacket with foil tape or an exterior grade silicone sealant. To allow for inspection of the system, do not seal the exhaust termination.
36
H. Indoor Air Installation – See Figures 12, 13, 14, 15 and 16.
1. Do not exceed maximum vent length. Refer to Table 4.
Horizontal
2. Maintain minimum ¼ inch per foot slope in horizontal runs.
3 Recommended horizontal installation consists of
vent being sloped down away from boiler. See Figure 12.
4. Slope horizontal runs minimum ¼ inch per foot. Slope towards vertical vent drain tee. Position weld seams in vent pipes, in all horizontal runs, at the top to avoid condensate from lying on the seams.
5. Use appropriately designed thimbles when passing through combustible walls (thimble use optional for noncombustible walls). Insert thimble through wall from outside. Secure outside fl ange to wall with nails or screws, and seal with sealant material. Install inside fl ange to inside wall, secure with nails or screws, and seal with sealant material.
6. For noncombustible wall application when thimble is not used, size opening such that female (bell) end with locking band attached cannot pass through.
7. Join vent terminal to vent pipe. Locate vent terminal between seventeen (17) inches and twenty­nine (29) inches from wall when joined to inside vent piping. See Figure 14.
8. Insert vent pipe through thimble/opening from outside and join to vent system. Apply sealant between vent pipe and opening/thimble to provide weathertight seal.
9. Join vent terminal to 45° elbow included in kit. Join 45° elbow/terminal assembly to vent pipe. Refer to Section C for proper procedures for joining vent pipe and fi ttings. See Figure 3 .
Vertical
10. Installation of a vertical vent tee 8116304U is
11. Install fi re stops where vent passes through fl oors,
12. Whenever possible install vent straight through roof.
13.
14. Install supplied air intake terminal onto collar of the
required on all vertical vent applications. See Figure 6. Attach vertical vent drain tee directly to elbow or horizontal pipe from an elbow immediately after vent connector.
ceilings or framed walls. The fi re stop must close the opening between the vent pipe and the structure. Fire stop manufacturers are Air-Jet, American Metal Products, Metal-Fab, and Simpson Dura-Vent.
Refer to Figure 13 if offset is necessary. Maintain minimum clearance to combustible materials.
Install Vent Terminal.
a. Size roof opening to maintain minimum
clearance from combustible materials.
b. Use appropriately designed vent fl ashing
when passing through roofs. Follow fl ashing manufacturers’ instructions for installation procedures. Flashing manufacturers are Air­Jet, American Metal Products, Metal Fab, and Simpson Dura-Vent.
c. Extend vent pipe to maintain minimum vertical
and horizontal distance of twelve (12) inches from roof surface. Allow additional vertical distance for expected snow accumulation. Provide brace as required. Refer to Figure 15.
d. Vertical venting requires fl ashing and a storm
collar to prevent moisture from entering the structure.
e. Install storm collar on vent pipe immediately
above fl ashing. Apply Dow Corning Silastic 732 RTV Sealant between vent pipe and storm collar to provide weathertight seal.
f. Attach vent terminal.
jacket enclosure. See Figure 16.
37
38
Figure 12: Recommended Separate Horizontal - Vent Installation
Figure 13: Alternate Separate Horizontal - Vent Installation
39
Figure 14: Optional Indoor Air - 3” or 4” Vent Terminal Installation
Figure 15: Indoor Air - Horizontal / Vertical Vent Terminal Installation
Extend Vent/Air Intake Piping to maintain minimum vertical (“X”) and minimum horizontal (“Y”) distance of twelve (12) inches from roof surface. Allow additional vertical (“X”) distance for expected snow accumulation.
Figure 16: Indoor Air - Air Intake Terminal Installation
40
I. Optional Exterior Separate Horizontal Vent/Air Intake Terminal Mounting – See Figures 17, 18, 19, 20, 21 and 22.
1. Do not exceed maximum vent/air intake lengths. Refer to Table 4.
2. This installation will allow a maximum of fi ve (5) feet vertical exterior run of the vent/air intake piping to be installed on separate horizontal venting and indoor air horizontal venting.
ECITON
tnelaviuqenidedulcniebotnurroiretxE
.shtgnelekatniria/tnev
3. Install vent piping.
a. Install vent piping for desired venting system.
Refer to specifi c section for details for vent pipe installation.
b. After penetrating wall/thimble, install an
AL 29-4C® 90° elbow so that elbow leg is in the up direction.
c. Install maximum of fi ve (5) feet of AL 29-4C®
vent pipe. Refer to Sections C through E for proper procedures for joining vent pipe and ttings.
d. At top of vent pipe length install an AL 29-4C
90° elbow so that elbow leg is opposite the building’s exterior surface.
e. If installation requires indoor air, install
AL 29-4C
®
45° elbow (provided in indoor air kit) to upper AL 29-4C® 90° elbow so that leg of 45° is in down direction (see Figure 21 or 22). If not using indoor air, proceed to Step f.
f. Install horizontal vent terminal (provided with
boiler).
g. Brace piping if required.
4. Air Intake Piping (not required for indoor air).
a. Install air intake piping for desired venting
system. Refer to specifi c section for details for air intake installation.
b. After penetrating wall, install a corrosion
resistant 90o elbow so that elbow leg is in the up direction.
c. Install maximum of fi ve (5) feet of corrosion
resistant air intake pipe.
d. At top of air intake pipe install air intake
terminal (provided with boiler).
e. Brace piping if required.
®
Figure17: Optional Separate Horizontal Air 3” or 4” Intake Terminal Installation
41
Figure 18: Optional Separate Horizontal Air 5” Intake Terminal Installation
Figure 19: Optional Separate Horizontal 3” Vent Terminal Installation
42
Figure 20: Optional Separate Horizontal 4” Vent Terminal Installation
Figure 21: Optional Separate Horizontal 3” Vent Terminal Installation (Indoor Air)
43
Figure 22: Optional Separate Horizontal 4” Vent Terminal Installation (Indoor Air)
44
IV. Water Piping and Trim
.erutcurts
GNINRAW
roreliobotegamaddnanoitareporeporpminitluseryamreliobepipylreporpoteruliaF
reliobleetsdnanorifonoisorrocesuaclliwretawreliobfonoitanimatnocnegyxO
revoctonseodytnarraWdradnatSs'mahnruB.eruliafreliobotdaelnacdna,stnenopmoc
desuacpu-dliub)emil(elacsroretawreliobfonoitanimatnocnegyxoybdesuacsmelborp
.retawfonoitiddatneuqerfyb
A. Design and install boiler and system piping to
prevent oxygen contamination of boiler water and frequent water additions.
1. There are many possible causes of oxygen contamination such as:
a. Addition of excessive make-up water as a result
of system leaks. b. Absorption through open tanks and fi ttings. c. Oxygen permeable materials in the distribution
system.
2. In order to insure long product life, oxygen sources must be eliminated. This can be accomplished by taking the following measures:
a. Repairing system leaks to eliminate the need for
addition of make-up water. b. Eliminating open tanks from the system. c. Eliminating and/or repairing fi ttings which allow
oxygen absorption. d. Use of non-permeable materials in the
distribution system. e. Isolating the boiler from the system water by
installing a heat exchanger. f. Use properly designed and operating air
elimination devices in water piping.
B. Low Water Cut Off (LWCO) on Hot Water Boilers
(Optional)
addition, some jurisdictions require the use of a LWCO with a hot water boiler.
Where
The universal location for a LWCO on both gas and oil
hot water boilers is above the boiler, in either the supply or return piping. The minimum safe water level of a water boiler is at the uppermost top of the boiler; that is, it must be full of water to operate safely.
What Kind
The SCG boiler is designed to accept the wiring of the
Safgard Model 1100-H4 (P/N 45-1104) LWCO. This is a probe type LWCO. The factory wiring is designed to allow simple “Plug-in” installation of the wiring.
How to Pipe
A “tee” is commonly used to connect the probe LWCO
to the supply or return piping, as shown below.
GNINRAW
.ffO
When
A low water cutoff is required to protect a hot water
boiler when any connected heat distributor (radiation) is installed below the top of the hot water boiler (i.e. baseboard on the same fl oor level as the boiler). In
otseriwyrotcaftucotTPMETTATONOD
ffOtuCretaWwoLtekramretfanallatsni
snoitcennocesuylnO.)OCWL(
tuCretaWwoLrofdeifitnediyllacificeps
ffOtuCretaWwoLehtwollof,sesacllanI
.snoitcurtsnis'rerutcafunam)OCWL(
Select the appropriate size tee using the LWCO
manufacturer’s instructions. Often, the branch connection must have a minimum diameter to prevent bridging between the probe and the tee. Also, the run of the tee must have a minimum diameter to prevent the end of the probe from touching or being located too close to the inside wall of the run of the tee.
Ideally, manual shutoff valves should be located
above the LWCO and the boiler to allow for servicing. This will allow probe removal for inspection without
LWCO Location
45
draining the heating system. Many probe LWCO manufacturers recommend an annual inspection of the probe.
How to Wire
Ensure power is turned off to boiler. Locate the LWCO jumper wire in the factory wiring
harness. Remove the jumper wire and install the LWCO wiring from LWCO Model 1100-H4 (P/N 45-1100) into the plug of the SCG factory wiring.
How to Test
Shut off fuel supply. Lower water level until water
level is BELOW the LWCO. Generate a boiler demand by turning up thermostat. Boiler should not attempt to operate. Increase the water level by fi lling the system. The boiler should attempt to operate once the water level is above the LWCO.
ECITON
ehtniOCWLehtfonoitacolehterusnE
ehtfonoitcennocrofwollalliwgnipip
gniriwyrotcafehtotssenrahgniriwOCWL
.G
CSehtfo
C. Connect system supply and return piping to boiler.
See Figures 25 and 26. Maintain minimum ½ inch clearance from hot water piping to combustible materials.
GNINRAW
tsumgnipipegrahcsidevlavfeilererusserP
erevesfolaitnetopehttahthcusdepipeb
ynaniepipTONOD.detanimilesisnrub
TONOD.ruccodluocgnizeerferehwaera
.spacrosgulp,sevlavffo-tuhsynallatsni
egrahcsidreporprofsedoClacoLtlusnoC
.tnemegnarragnipip
F. Space heating and domestic water heating with
Alliance™ water heater. Install Alliance water heater as a separate heating zone. Refer to Alliance Installation, Operating and Service Instructions for additional information.
G. If boiler is used in connection with refrigeration
systems, boiler must be installed with chilled medium
piped in parallel with the heating boiler using appropriate valves to prevent chilled medium from entering boiler, see Figure 23.
H. If boiler is connected to heating coils located in
air handling units where they may be exposed to refrigerated air, boiler piping must be equipped with ow control valves to prevent gravity circulation of boiler water during operation of cooling system.
ECITON
metsysehtgnizissdnemmocermahnruB
ot)MPG(wolftneiciffusylppusotrotalucric
02awolla
itcennoclladnagnibuttnaidar
.deredisnoc
D. Install circulator with anges, gaskets and bolts
provided. Circulator harness allows circulator to be mounted on supply or return. Connect harness to circulator and secure any excess conduit.
E. Install supply manifold, pressure/temperature gauge
and pressure relief valve.
See Figure 24. Pressure Relief Valve must be installed
with spindle in vertical position. Installation of the relief valve must comply with the ASME Boiler and Pressure Vessel Code, Section IV.
ehtnilaitnereffiderutarepmet
eht,rotalucricmetsysehtgnizisnehW.metsys
dnadraobesab,srotaidarllafoporderusserp
ebtsumgnipipgn
Figure 23: Recommended Piping for Combination
Heating & Cooling (Refrigeration) System
I. Use a boiler bypass if the boiler is to be operated
in a system which has a large volume or excessive radiation where low boiler water temperatures may be encountered (i.e. converted gravity circulation system, etc.).
46
Figure 24: Supply Water Manifold Piping
Install pipe tee between circulator and boiler return
along with second tee in supply piping as shown in Figure 25 or 26. Bypass should be same size as the supply and return lines with valves located in bypass and supply outlet as illustrated in Figure 25 or 26 in order to regulate water fl ow to maintain higher boiler water temperatures.
After the boiler is operational (reference Section VIII.
System Start-Up) set by-pass and boiler supply valves to half throttle position to start. Operate boiler until system water temperature reaches normal operating range.
Adjust valves to provide 180° to 200°F supply water
temperature. Opening the boiler supply valve will raise system temperature, while opening the by-pass valve will lower system supply temperature.
J. A hot water boiler installed above radiation level
must be provided with a low water cutoff device as part of installation.
K. If a low water cutoff is required, it must be mounted
in the system piping above the boiler. The minimum safe water level of a hot water boiler is just above the highest water containing cavity of the boiler; that is, a hot water boiler must be full of water to operate safely.
L. Oil, grease, and other foreign materials which
accumulate in new hot water boilers and a new or reworked system should be boiled out, and then thoroughly fl ushed. A local qualifi ed water treatment chemical specialist is a suggested source for recommendations regarding appropriate chemical compounds and concentrations which are compatible with local environmental regulations.
M. After the boiler and system have been cleaned and
ushed, and before refi lling the entire system add appropriate water treatment chemicals, if necessary, to bring the pH between 7 and 11.
N. If it is required to perform a long term pressure
test of the hydronic system, the boiler should rst be
isolated to avoid a pressure loss due to the escape of air trapped in the boiler.
To perform a long term pressure test including the
boiler, ALL trapped air must fi rst be removed from the boiler.
A loss of pressure during such a test, with no visible
water leakage, is an indication that the boiler contained trapped air.
47
48
Figure 25: Recommended Water Piping for Circulator Zoned Heating Systems
Figure 26: Recommended Water Piping for Zone Valve Zoned Heating Systems
49
V. Gas Piping
GNINRAW
otylppussagepipylreporpoteruliaF
dnanoitareporeporpminitluseryamreliob
syawlA.erutcurtsroreliobehtotegamad
eerfkaelyletulosbasignipipsagerussa
ehtrofepytdnaezisreporpehtfodna
.daoldetcennoc
rpsaglanoitiddanA
.reilppussagtlusnoC.dedeeneb
A. Size gas piping. Design system to provide adequate gas
supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to boiler. Maximum allowable system pressure is ½ psig. Actual point of delivery pressure may be less; contact gas supplier for additional information. Minimum gas valve inlet pressure is stamped on the rating label located in the boiler’s vestibule compartment.
2. Maximum gas demand. Refer to the boiler’s input as printed on it’s rating label. Also consider existing and expected future gas utilization equipment (i.e. water heater, cooking equipment).
3. Length of piping and number of fi ttings. Refer to Table 7 for maximum capacity of Schedule 40 pipe. Table 8 lists equivalent pipe length for standard ttings.
yamrotalugererusse
4. Specifi c gravity of gas. Gas piping systems for gas with a specifi c gravity of 0.70 or less can be sized directly from Table 7, unless authority having jurisdiction specifi es a gravity factor be applied. For specifi c gravity greater than 0.70, apply gravity factor from Table 6. If exact specifi c gravity is not shown choose next higher value.
Table 6: Specifi c Gravity Correction Factors
cificepS
ytivarG
--------58.018.0
--------09.028.0
06.000.100.187.0
56.069.001.147.0
07.039.002.117.0
57.009.003.186.0
08.078.004.166.0
noitcerroC
rotcaF
cificepS
ytivarG
For materials or conditions other than those listed
above, refer to National Fuel Gas Code, NFPA54/ANSI Z223.1, or size system using standard engineering methods acceptable to authority having jurisdiction.
noitcerroC
rotcaF
Table 5: Gas Ratings
relioB
ledoM
rebmuN
3-GCS
4-GCS
5-GCS
6-GCS
7-GCS
8-GCS
9-GCS
PL/larutaN
mumixaM
erusserPsaG
nI
).c.w.ni(
415.45.115.35.01
larutaNmuminiM
erusserPsaG
).c.w.ni(
evlaVsaGottel
PLmuminiM
erusserPsaG
).c.w.ni(
evlaVsaGottelnI
larutaN
dlofinaM
erusserP
).c.w.ni(
ECITON
.teef0001repnoitcuder%2nodesabsietareD.slevelaesevobateef
.levelaesevobateef000,01-000,5ledoM"H"ehtdna,level
.re
rutcafunamehttlusnoc,teef000,01evobasnoitacilpparoF
PL
dlofinaM
erusserP
).c.w.ni(
yllaicepsebotdeenlevelaesevobateef999,4nahtretaergsedutitlaroftliubsreliobGCS
neebsahledoM"H"reliobGCSehT.snoiitidnoccirehpsomtanisegnahcroftsujdaotdecifiro
situpnI.levelaesevobateef000,01ot000,5morfsnoitidnoccirehpsomtanietarepootdeifitrec
000,01tasnoitacilpparof%02dna,levelaesevobateef000,5tasnoitacilpparof%01ybdetared
aesevobateef999,4-0ledoM"S"ehT:sledoMedutitla)2(owtnielbaliavasireliobGCSehT
50
Table 7: Maximum Capacity of Schedule 40 Pipe in CFH* For Gas Pressures of 0.5 psig or Less
htgneL ]teeF[
01231872025050,1571063086004,1
0229091053037021052564059
033725158209579002573077
043603154200528071023066
056551151204437151582085
0605501591004668310620
07646908107316521042094
08340907105375811022064
09044806102335011502034
001839705150305301591004
½¾ 1 ¼1½¾1¼1
porDerusserP.c.whcni3.0 porDerusserP.c.whcni5.0
35
* 1 CFH of Natural Gas is approximately equal to 1 MBH; 1 CFH of LP is approximately equal to 2.5 MBH; con­tact your gas supplier for the actual heating value of your gas.
B. Connect boiler gas valve to gas supply system.
GNINRAW
nosdnuopmocdaerhtreporpesuoteruliaF
foskaelnitluseryamsrotcennocsaglla
.sagelbammalf
GNINRAW
ebtsummetsysdnareliobotylppussaG
rognillatsniotroirpffotuhsyletulosba
.gnipipsagreliobgnicivres
1. Use methods and materials in accordance with local plumbing codes and requirements of gas supplier. In absence of such requirements, follow National Fuel Gas Code, NFPA 54/ANSI Z223.1.
2. Use thread (joint) compounds (pipe dope) resistant to action of liquefi ed petroleum gas.
3. Install sediment trap, ground-joint union and manual shut-off valve upstream of boiler gas control valve and outside jacket. See Figure 27.
Table 8: Equivalent Lengths of Standard Pipe Fittings & Valves
epiP
eziS
.D.I
sehcnIetaGebolGelgnA
gniwS
kcehC
°09
woblE
Figure 27: Recommended Gas Piping
NEPOYLLUFSEVLAV
°54
woblE
wolF,eeT°09
nuRhguorhT
wolF,eeT°09
hcnarBhguorhT
"½226.053.06.813.93.46.187.00.11.3
"¾428.044.01.325.113.51.279.04.11.4
"1940.165.04.927.418.66.232.18.13.5
"¼1083.147.06.833.919.85.306.13.29.6
51
4. All above ground gas piping upstream from manual shut-off valve must be electrically continuous and bonded to a grounding electrode. Do not use gas piping as grounding electrode. Refer to National Electrical Code, NFPA 70.
C. Pressure test. The boiler and its gas connection must
be leak tested before placing boiler in operation.
1. Protect boiler gas control valve. For all testing over ½ psig, boiler and its individual shutoff valve must be disconnected from gas supply piping. For testing at ½ psig or less, isolate boiler from gas supply
piping by closing boiler’s individual manual shutoff valve.
2. Locate leaks using approved combustible gas detector, soap and water, or similar nonfl ammable solution.
REGNAD
semalfnepo,seldnac,sehctamesutonoD
.skaelrofkcehcotecruosnoitingirehtoro
52
VI. Electrical
.mrah
REGNAD
ecivresronoitallatsnignitpmettaerofebderewopnuerasnoitcennoclacirtcelellaerussaylevitisoP
htiwsexoblacirtcelellatuokcoL.gnidliubroreliobehtfosnoitcennocrostnenopmoclacirtcelefo
.ffodenrutsirewopecnokcoldap
GNINRAW
lacisyhpsuoiresnitluseryamreliobehtotsnoitcennoclacirtceleeriwylreporpoteruliaF
.krowlacirtceleynagnitpmetta
.slortnocehthtiwdeilppussnoitcurtsni
A. General. Install wiring and electrically ground boiler
in accordance with authority having jurisdiction or, in the absence of such requirements, follow the National Electrical Code, NFPA 70, and/or CSA C22.1 Electrical
Code.
B. A separate electrical circuit must be run from
the main electrical service with an over-current device/disconnect in the circuit. A service switch is recommended and may be required by some local jurisdictions. Install the service switch in the line voltage “Hot” leg of the power supply. Locate the
laerusekaM.ecruosenonahterommorfebyamrewoplacirtcelE
.ecivedtnerruc-revodezisylreporpahtiwdetcetorpebtsumreliobhcaE
.slortnocgnitareporoytefasynaevitareponiekamrotuopmujreveN
service switch such that the boiler can be shut-off without exposing personnel to danger in the event of an emergency. Connect the main power supply and ground to the three (3) boiler wires (black, white and green) located in the junction box at the inside top of the boiler jacket. If a low water cutoff is to be used, connect the low water cutoff so that all 120V power to boiler is interrupted if the low water cutoff’s switch opens.
erofebffosirewopl
reliobhcaE.ylnosesoprupecnereferroferalaunamsihtnideniatnocsmargaidgniriwehT
ehtdnamargaidsihtotrefeR.roodtnorfehtotdehcattamargaidgniriwahtiwdeppihssi
gniriwllawollofdnadnatsrednu,daeR.reliobehthtiwdesuslortnocynafomargaidgniriw
C. Refer to Figures 28 and 29 for details on the internal
boiler wiring.
nipipmetsyseht
ECITON
fogniriwlanretniehtedisnidetacoltimilerutarepmetretawhgihahtiwdeppiuqesireliobsihT
sdeecxeerutarepmetretawreliobehttneveehtninwodtuhsreliobsedivorptimilsihT.reliobeht
erutarepmetretawlanoitiddanaeriuqersedoClacoLniatreC.lortnoctimilehtfotniopteseht
tesmuminimehtwolebserutarepmettaetarepoyamsmetsysfosepytniatrec,noitiddanI.timil
.reliobehtnideniatnoctimilehtfotniop
nidetacol)tatsauqA6004LllewyenoH(timilerutarepmetretawlanoitiddanallatsni,sruccosihtfI
saeriW.launamsihtfonoitceSmirTdnagnipiPretaWehtninwohssag
.launamsihtfonoitceSlacirtcelEehtnidetacidni
ECITON
.detonesiwrehtosselnudeilppusrellatsniera.cteslortnoc,stuneriw,eriwllA
53
54
Figure 28: Internal Boiler Wiring Schematic Diagram
ECITON
ehtninwohsrepmujtimilyrailixuaehthtiwseiresnillatsni,desusitimilmetsyslanoitiddanafI
.wolebgniward
Figure 29: Internal Boiler Wiring Ladder Diagram
55
D. System Controls and Wiring
1. Refer to National Electric Code or Local Electric Codes for proper size and type of wire required. Follow Code.
2. Use anti-short bushings on all wiring passing through boiler jacket, junction boxes and/or control boxes.
3. Use armored cable (BX) over all exposed line voltage wiring.
4. If an Alliance™ indirect water heater is used, use priority zoning except for Hydro-Air Systems.
5. Single Zone Heating System – Refer to Figure 30 of this manual for the electrical diagram for this type of system. Set the thermostat heat anticipator to 0.60 amps.
6. Single Zone Heating System with Alliance™ Water Heater - Refer to Figure 31 of this manual for the electrical diagram for this type of system.
Set the thermostat heat anticipator to 0.60 amps.
7. Conventional Circulator Zoned System – Refer to Figure 32 of this manual for the electrical diagram for this type of system.
Read, understand and follow all of the instructions provided with the Honeywell R8888 control. Connect the thermostat of each zone and the circulator for that zone to R8888 panel. If an Alliance™ indirect water
heater is used, connect the Alliance™ thermostat and circulator to the Zone 1 terminals of the R8888.
Set the thermostat heat anticipator to 0.12 amps.
ECITON
"noisnapxe"othctiwsepytlenapeht
.8888Rhtruofrodriht,dnocesehtno
enoz)4(ruofadna)A8888R(ledoMenoz)3(eerhtanielbaliavasilortnoC8888RllewyenoHehT
evlewtotpuroflortnocedivorpotrehtegotdesuebyams'8888R)4(ruofotpU.)B8888R(ledoM
ytiroirpedivorplliw,lortnocniamehtfoenoztsrifeht,enoz)1(enoylnO.senozlaudividni)21(
,Aehtgniriwybs'8888Rlanoitiddatcennoc,deriuqererasenoz)4(ruofnahteromfI.noitalucric
fI.ylppusrewoptlov021aseriuqer8888RhcaE.rehtegotlortnochcaefoslanimretCdna,B
tesdna8888Rtsrifehtno"niam"othctiwsepytlenapehttes,desusi8888R)1(enonahterom
8. Conventional Zone Valve Zoned System – Refer to Figure 33. Wiring to the most popular models of zone valves is given in Figure 34.
Connect the thermostat of each zone and the zone valve for that zone to the R8889 control. If an Alliance™ indirect water
heater is used, connect the Alliance™ thermostat and zone valve to the “zone 1” terminals of the R8889.
Set the thermostat heat anticipator to 0.12 amps.
ECITON
enoz)4(ruofowtdnasledomenoz)3(eerhtowtnielbaliavasilortnoC9888RllewyenoHehT
trofA9888RledoMgnisusdnemmocermahnruB.sledom
.9888Rhtruofrodriht,dnoces
ledoMdnasmetsysenoz)3(eerh
yamdnayticapacdaolsselevahD9888RdnaC9888RsledoM.smetsysenoz)4(ruofrofB9888R
otrehtegotdesuebyams'9888R)4(ruofotpU.sevlavenozfosepytniatrechtiwetarepoton
lortnocniamehtfoenoztsrifeht,enoz)1(enoylnO.senozlaudividni)61(neetxisotpuedivorp
erasenoz)4(ruofnahteromfI.retaehretawtceridniecnaillAehtrofgninozytiroirpedivorplliw
.rehtegotlortnochcaefoslanimretCdnaB,Aehtgniriwybs'9888Rlanoitiddatcennoc,deriuqer
lenapehttes,desusi9888R)1(enonahteromfI.ylppusrewoptlov021aseriuqer9888RhcaE
ehtno"noisnapxe"othctiwsepytlenapehttesdna9888Rtsrifehtno"niam"othctiwsepyt
56
Figure 30: System Wiring Schematic for Single Zone Space Heating Only
57
ECITON
ehtninwohsrepmujtimilyrailixuaehthtiwseiresnillatsni,desusitimilmetsyslanoitiddanafI
.wolebgniward
58
Figure 31: Single Zone System with Packaged Alliance™ Water Heater Wiring Schematic
Figure 32: Circulator Zoned System Wiring Schematic
59
60
Figure 33: Zone Valve Zoned System Wiring Schematic
Figure 34: Different Manufacturer’s Zone Valve Connections to Honeywell R8889
61
VII. Modular Installation
A. General Guidelines
1. Read and follow all venting, combustion air, water piping, gas piping and electrical instructions contained in this manual unless otherwise instructed in this section.
2. Consult Local Building Codes or National Fuel Gas Code, NFPA 54/ANSI Z222.3 for restrictions and instructions on modular boiler installations.
B. Module Sizing
Burnham recommends sizing each boiler in a modular
system to provide 20 % of the combined heating load where ever possible.
C. Venting
1. Each boiler must have an individual vent pipe. Refer to Venting Section of this manual for venting guidelines and options.
GNINRAW
.rehtegotsepiptnevdlofinamtonoD
2. The maximum vent length for each boiler is fi fty (50) equivalent feet.
3. The minimum horizontal distance between vent terminations is one (1) foot. Additional horizontal distance is desirable to avoid frost damage to the building. Vent terminations must be at least twelve (12) inches above the ground plus the expected snow accumulation.
NOITUAC
esolcsnoitanimrettnevelpitlumgnillatsnI
nopudliubtsorfsetomorprehtegot
liub
4. Multiple vertical vent pipes may be piped through a common conduit or chase so that one roof penetration may be made. Each vent termination must be one (1) foot from other terminations.
D. Air Intake Piping
1. Each boiler must have an individual air intake pipe, refer to Venting Section of this manual for Air Intake Guidelines and Options.
2. The maximum air intake length for each boiler is fty (50) equivalent feet.
3. Locate air intake termination on the same wall as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed
62
,ytilibissopsihteziminimoT.sgnid
ehtotgnidliubehtmorfecnatsidehtdnetxe
.snoitanimretneewtebecnatsidlatnoziroh
with vertical venting and sidewall combustion air inlet (or visa versa) if installation conditions do not allow alternate arrangement.
Table 9: Modular Boiler Water Manifold Sizing
tuptuOdenibmoC
)HBM(
< 661"¼1
< 062"½1
< 055"2
< 009"½2
< 0002"3
muminiMdednemmoceR
dlofinaMretaWnommoC
)TPN(eziS
E. Water Piping (See T able 9)
Installing a low water cutoff in the system piping of
modular systems is strongly recommended and may be required by Local Codes.
F. Gas Piping
1. Refer to National Fuel Gas Code, Local Codes and Tables 7 and 8 for gas pipe sizing.
2. Each boiler must be piped as shown in Figure 27.
GNINRAW
evobasignidliubehtnierusserpsagfI
rotalugererusserpsaglanoitiddana,gisp½
rotalugerlanoitiddaenognisU.deriuqersi
efasnunitluseryamsreliobelpitlumrof
rotalugerlanoitiddaehT.noitareporeliob
telbaebtsum
ehtesaercnidnanoitanimrettnevehtfodne
.sgnitar
G. Electrical
1. Each boiler must be provided with a fused disconnect and service switch.
2. Install wiring in accordance with requirements of authority having jurisdiction. In the absence of such requirements, follow the National Electric Code, NFPA 70 and/or CSA C22.1 Electric Code.
H. Modular Boiler Control Systems
Contact a controls manufacturer such as Honeywell or
Tekmar to properly apply a modular control system.
Common systems may use outdoor temperature, return
water temperature or both to stage the boilers.
sagetalugerylreporpo
.reliobtsellamsehtfotupniehttaerusserp
eromroowt,sihtodtonnacrotalugerehtfI
tlusnoC.deriuqererasrotalugerlanoitidda
saglacolro/dnarerutcafunamrotaluger
tnempiuqednasnoitcurtsnirofreilppus
Figure 35: Modular Boiler Gas Piping
63
VIII. System Start-up
A. Safe operation and other performance criteria were
met with gas manifold and control assembly provided on boiler when boiler underwent tests specifi ed in
American National Standard for Gas-Fired Low­Pressure Steam and Hot Water Boilers, ANSI Z21.13.
B. Verify that the venting, water piping, gas piping and
electrical system are installed properly. Refer to installation instructions contained in this manual.
C. Con rm all electrical, water and gas supplies are
turned off at the source and that vent is clear of obstructions.
D. Con rm that all manual shut-off gas valves between
the boiler and gas source are closed.
GNINRAW
erofeblaunamsihtnisnoitcurtsni
.putratsgnitpmetta
E. Fill entire heating system with water and vent air
from system. Use the following procedure on a Series Loop or multi-zoned system installed as per Figure 25 or 26 to remove air from system when fi lling.
4. Starting with one circuit at a time, open zone valve or shut-off valve in system supply and return piping.
5. Open hose bib.
6. Open fi ll valve (Make-up water line should be located directly after full port ball valve in system supply piping between air scoop and expansion tank).
7. Allow water to overfl ow from bucket until discharge from hose is bubble free for 30 seconds.
8. Close the opened zone valve or shut-off valve for the zone being purged of air, then open the zone valve or shut-off valve for the next zone to be purged. Repeat this step until all zones have been purged. At completion, open all zone valves or shut-off valves.
9. Close hose bib, continue fi lling the system until the
llawollofdnadnatsrednu,daeryletelpmoC
pressure gauge reads 12 psi. Close fi ll valve.
(Note - If make-up water line is equipped with
pressure reducing valve, system will automatically ll to 12 psi. Follow fi ll valve manufacturer’s instructions).
10. Open isolation valve in boiler supply piping.
11. Remove hose from hose bib.
GNINRAW
sihtfoerusserpgnitarepomumixamehT
sihtdeecxereveN.gisp03sireliob
erusserpegnahcrogulptonoD.erusserp
.evl
avfeiler
ECITON
mretgnolamrofrepotderiuqersitifI
eht,metsyscinordyhehtfotseterusserp
adiovaotdetalosiebtsrifdluohsreliob
riafoepacseehtoteudssolerusserp
.reliobehtnideppart
tseterusserpmretgnolamrofrepoT
liobehtgnidulcni
.reliobehtmorfdevomerebtsrif
1. Close full port ball valve in boiler supply piping.
2. Isolate all zones by closing zone valves or shut-off valves in supply and return of each zone(s).
3. Attach a hose to the vertical hose bib located prior to the full port ball valve in the system supply piping. (Note - Terminate hose in fi ve gallon bucket at a suitable fl oor drain or outdoor area).
tsumriadeppartLLA,re
htiw,tsetahcusgniruderusserpfossolA
noitacidninasi,egakaelretawelbisivon
.riadeppartdeniatnocreliobehttaht
F. Confi rm that the boiler and system have no water
leaks.
G. Prepare to check operation.
1. Obtain gas heating value (in Btu per cubic foot) from gas supplier.
2. Connect manometer to pressure tap on gas valve. Use 1/8 NPT tapping provided.
3. Temporarily turn off all other gas-fi red appliances.
4. Turn on gas supply to the boiler gas piping.
5. Confi rm that the supply pressure to the gas valve is 14 in. w.c. or less. Refer to Table 5 for minimum supply pressure.
6. Open the fi eld installed manual gas shut-off valve located upstream of the gas valve on the boiler.
7. Using soap solution, or similar non-combustible solution, electronic leak detector or other approved method. Check that boiler gas piping valves, and all other components are leak free. Eliminate any leaks.
REGNAD
semalfnepo,seldnac,sehctamesutonoD
.skaelrofkcehcotecruosnoitingirehtoro
8. Purge gas line of air.
64
Figure 36: Operating Instructions
65
Figure 38: 1 Inch Main Burner fl ame
Figure 39: Pilot Burner Flame
K. Check main burner ame. See Figures 38. Flame
should have clearly defi ned inner cone with no yellow tipping. Orange-yellow streaks should not be confused with true yellow tipping.
Figure 37: Sequence of Operation
H. Follow Operating Instructions to place boiler in
operation. See Figure 36.
I. Sequence of Operation. See Figure 37. If boiler fails
to operate properly, see Troubleshooting Tree in Section IX: Service.
J. Check pilot burner ame. See Figure 39. Flame
should be steady, medium hard blue enveloping 3/8 to ½ inch of sensing probe.
66
L. Check thermostat operation. Raise and lower
temperature setting to start and stop boiler operation.
M. Check ignition control module shut-off. Disconnect
pilot lead wires from gas valve. If burners do not shutdown, determine cause of malfunction. Replace necessary items and check operation.
N. Check low water cutoff (if so equipped).
1. Adjust thermostat to highest setting.
2. With boiler operating, open drain valve and slowly drain boiler.
3. Main burners and pilot burner will extinguish and blower will stop when water level drops below low water cutoff probe. Verify limit, thermostat or other controls have not shut off boiler.
4. Adjust thermostat to lowest setting. Refi ll boiler.
O. Check limit.
1. Adjust thermostat to highest setting.
2. Observe temperature gauge. When temperature is indicated, adjust limit to setting below observed temperature. Main burners and pilot burner should extinguish, and blower should stop.
3. Adjust limit to setting above observed temperature. Ignition sequence should begin.
4. Adjust thermostat to lowest setting. Adjust limit to desired setting.
P. Adjust gas input rate to boiler.
1. Adjust thermostat to highest setting.
2. Check manifold gas pressure. See Table 5 or rating label located in the boiler’s vestibule compartment. Adjust gas valve pressure regulator as necessary (turn adjustment screw counterclockwise to decrease manifold pressure, or clockwise to increase manifold pressure). If pressure cannot be attained, check gas valve inlet pressure. If less than minimum indicated in Table 5 or boiler’s rating label, contact gas supplier for assistance.
3. Clock gas meter for at least 30 seconds. Use Table 10 to determine gas fl ow rate in Cubic Feet per Hour.
GNINRAW
more than 0.3 inch w.c. If measured input rate is still less than 98% of rated input:
i. Remove Main Burners per procedure in
Section IX: Service.
ii. Remove gas orifi ces. Drill one (1) drill size
larger (drill size is stamped on orifi ce, or see Section X: Repair Parts).
iii. Reinstall gas orifi ces and main burners.
Measure input rate.
6. Recheck Main Burner Flame.
7. Return other gas-fi red appliances to previous conditions of use.
Q. Review User’s Information Manual and system
operation with owner or operator.
Table 10: Gas Flow Rate in Cubic Feet Per Hour
sdnoceS
enOrof
noituloveR
0306021042
2365311522
4335601212
6305001002
flaH-enO
.tF.uC
enO
.tF.uC
laiDreteMsaGfoeziS
owT
.tF.uC
lliwetartupnisagtsujdaylreporpoteruliaF
ehtfognirifrednurognirifrevonitluser
reliobefasnudnareporpmI.ecnailppa
.tluseryamnoitarepo
4. Determine Input Rate. Multiply gas fl ow rate by gas heating value.
5. Compare measured input rate to input rate stated on rating plate.
a. Boiler must not be over fi red. Reduce input rate
by decreasing manifold pressure. Do not reduce more than 0.3 inch w.c. If boiler is still overfi red, contact your Burnham distributor or Regional Offi ce for replacement Gas Orifi ce.
b. Increase input rate if less than 98% of rating
plate input. Increase manifold gas pressure no
837459981
045409081
243468271
441428461
649387751
847357051
056327441
255396831
453376331
652346921
851326421
060306021
67
IX. Service
REGNAD
retawtohyrevdna,strapgnivom,yticirtceleegatlovhgih,sagelbammalfsesureliobsihT
ehttahtdnaffoeraseilppusrewopcirtcelednasagllatahterussA.erusserphgihrednu
.ecivresroylbmessasidynagnitpmettaerofebloocsierutarepmetretaw
ynagnitpmettaerofebffoerasehctiwstcennocsidlacirtcelednasevlavsagllatahterussA
.ecivresroylbmessasid
.reliobehtfoytinicivehtniriaehtnitneserpsisagfikrowecivresynatpmettatonoD
iwrepmatroevomer,yfidomreveN
.ecivedlortnocynaht
GNINRAW
ecivresdecneirepxednadelliksybderiaperdnadecivresebylnotsumreliobsihT
.snaicinhcet
.sledomlacitnedihtiwdecalperebtsumyeht,decalpereraslortnocynafI
snoitcesehtllanideniatnocsgninrawdnasnoitcurtsniehtllawollofdnadnatsrednu,daeR
.launamsihtfo
erussadnaseriwehtlebalylraelc,ecivresgniruddetcennocsideraseriwlacirtceleynafI
.ylreporpdetcennocereraseriwehttaht
.slaunamnoitcurtsnitnenopmoc
.ecivresnikcabreliobehtgnicalp
A. General. Inspection and service should be conducted
annually. Turn off electrical power and gas supply while conducting service or maintenance. Follow instructions TO TURN OFF GAS TO APPLIANCE. See Figure 37.
B. Low water cutoff (if so equipped).
Probe Type (Annual Service). Probe type LWCO
should be removed once a year, examined and cleaned of any dirt accumulations to assure proper operations. Do not attempt to repair mechanisms in the eld. Complete replacement mechanisms, including necessary gaskets and installation instructions, are available from the manufacturer.
C. Vent/Air Intake System. Inspect for obstructions, soot
accumulation, proper support, and deterioration of pipe, ttings, and joints.
1. Clean terminal screens. Terminals must be free of obstruction, undamaged, with screens securely in place.
2. Terminal and wall thimbles (if used) must be weathertight.
3. Pipe must be full round shape, and show no damage from impact or excessive temperature.
68
.reliobsihtfotnenopmocrolortnocgnitareporoytefasynassapybrotuopmujreveN
ehtfoLLAnideniatnocsgninrawdnasnoitcurtsniehtllawollofdnadnatsrednu,daeR
erofebylreporpgnitarepoerastnenopmocdnaslortnocgnitarepodnaytefasllatahterussA
4. Pipe must be supported at minimum fi ve (5) foot intervals and must not sag.
5. All vent joints must be secure and watertight.
6. All air intake joints must be secure and airtight. Horizontal vent tee drain or vertical vent tee drain (if used) must have minimum 6 inch trap and allow condensate to fl ow freely. To Clean:
a. Disconnect drain tube from drain fi tting. b. Flush drain tube with water. Fill trap with water. c. Securely fasten drain tube to drain fi tting,
providing gas-tight and watertight seal.
7. If pipe must be disassembled for removal of obstructions or resealing of joint, see Section III, Paragraph C.
D. Boiler Flue Passages. Inspect for blockage or soot
accumulation.
1. Remove Main Burners. See Figure 42. a. Remove front door. b. Remove air intake box front door.
i. Remove sheet metal screws.
c. Disconnect pilot tubing and pilot lead wires at
the gas valve.
d. Remove wires to Flame Roll-out Switch. e. Remove air diffuser screen. f. Remove Burner Access Panel. g. Mark location of Main Burner with Pilot Bracket
on gas manifold.
h. Hold Main Burner on throat. Lift front of
burners to clear orifi ce. Burner which holds pilot can be removed by lifting the burner adjacent to its right fi rst.
2. Disconnect Vent Connector and Vent Pipe from Blower Outlet
3. Remove Jacket Top Panel.
4. Disconnect the Black and Gary Silicone Tubing from the Canopy.
5. Disconnect Wiring Harness from Blower Motor.
6. Remove Canopy/Blower Assembly. a. Loosen the (4) screws from Canopy.
7. Remove Flue Gas Baffl es. Inspect Flue Gas Baffl es for deterioration.
8. Inspect fl ue passages. Clean with fl ue brush. See Figure 42.
9. Inspect heating surface in combustion chamber. Clean with straight handle wire brush.
10. Install Flue Gas Baffl es.
11. Replace Canopy/Blower Assembly.
12. Connect Silicone Tubing between Pressure Fittings on Canopy Assembly and Pressure Switch. Route through bushings in Vestibule Panel . See Figure
40.
Figure 41: Blower Vent Connector Assembly
13. Install Jacket Top Rear Panel.
14. Connect Vent System. See Figure 41.
15. Connect Blower Motor Wiring Harness.
E. Main Burners and Firebox.
1. Vacuum fi rebox. Exercise care - do not damage base insulation.
2. Clean main burners. Brush top of burners with soft bristle brush. See Figure 42. Vacuum to remove any dirt and lint.
3. Vacuum tip of pilot burner.
4. Check gas orifi ces for lint and dirt. Clean as necessary.
5. Install main burners by reversing procedure to remove burners.
a. Pilot burner must be installed in original
location. See Table 11.
b. Main burners must be properly secured in burner
tray slot at rear of fi rebox and over gas orifi ce. See Figure 42.
c. Pilot gas supply and pilot lead wires must be
reconnected. d. Burner access panel must be securely in place. e. Reinstall air diffuser screen. f. Reconnect Flame Roll-out wires. g. Air Intake Box Front Door must be installed.
F. Check operation. Follow steps G through P from
Section VIII: System Start-up.
Figure 40: Silicone Tubing Assembly
69
70
Figure 42: Flue and Burner Cleanout, 1” Burner
Table 11: Pilot Burner Location
ledoMrelioBtekcarBtoliPhtiwrenruBniaM *srenruBniaMneewteBdetacoLrenruBtoliP
3-GCS2 3&2
4-GCS3 4&3
5-GCS4 5&4
6-GCS5 6&5
7-GCS6 7&6
8-GCS7 8&7
9-GCS8 9&8
niaM*
G. Procedure for Measuring Differential Pressure (See
Figure 43).
1. With boiler off, remove Gray and Black Hoses at differential pressure switch.
2. With tees and ¼ inch aluminum stubs, connect water manometer as shown with additional tubing.
3. Start boiler and read Pressure on Manometer when boiler water temperature reaches operating temperature. Refer to Table 12 for minimum readings.
NOTE: If switch drops-out before boiler reaches
temperature or if pressure differential readings are below minimums shown in Table 12, check for cracks in hose or contact your nearest Burnham representative.
4. Stop boiler, remove manometer and reconnect hoses to differential pressure switch. See Figures 40 and
43.
.reliobfotnorfmorfdeweivsathgirottfelderebmunsrenrub
Figure 43: Differential Pressure Measurement
Table 12: Differential Pressure Switch Settings
ledoMrelioB
3-GCS.c.w"23.1.c.w"08.
4-GCS.c.w"71.1.c.w"56.
5-GCS.c.w"71.1.c.w"56.
6-GCS.c.w"88..c.w"53.
7-GCS.c.w"08..c.w"03.
CS.c.w"88..c.w"53.
8-G
9-GCS.c.w"88..c.w"53.
erusserPlaitnereffiDmuminiM
.tF999,4otleveLaeSnoitavelE.tF000,01-000,5
71
72
73
XI. Repair Parts
All SCG Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require assistance in locating a Burnham distributor in your area, or have questions regarding the availability of Burnham products or repair parts, please contact Burnham Customer Service at (717) 481-8400 or Fax (717) 481-8408.
74
yeK
.oN
noitpircseD
rebmuNtraP]ytitnauQ[
3-GCS4-GCS5-GCS6-GCS7-GCS8-GCS9-GCS
YLBMESSAGNITSAC.1
1ylbmessAnoitceS13070716140707161507071616070715170707161807071619070716
A1noitceSdnEtfeL 10070717
B1noitceSretneC
C1noitceSdnEthgiR 20070717
D13#,elppiNpilS
E1elffaBsaGeulF
F102-"¼,do
G102-"¼,tuNxeH 70406808)4(
ReiT
)1(
30070717
)4(
900006608
)2(
20070117
)2(
10-901001
)2(
30070717
)6(
900006608
)3(
20070117
)2(
50-801001
)3(
30070717
)8(
900006608
)4(
20070117
)2(
70-801001
)4(
30070717
)01(
900006608
)5(
20070117
)2(
31-801001
)5(
30070717
)21(
900006608
)6(
20070117
)2(
41-801001
)6(
30070717
)41(
900006608
)7(
20070117
)2(
51-801001
)7(
30070717
)61(
900006608
)8(
20070117
)2(
61-801001
75
76
yeK
.oN
noitpircseD
3-GCS4-GCS5-GCS6-GCS7-GCS8-GCS9-GCS
rebmuNtraP]ytitnauQ[
YLBMESSAESAB.2
A2repparWesaB13070817140708171507081716070817170708171807081719070817
B2yarTesaB230708172407081725070817260708172707
C2ylbmessAyarTrenruB13070816140708161507081616070816170708161807081619070816
D2lenaPtnorFesaB5
E2lenaPsseccArenruB630708176407081765070817660708176707081
F2"2x"2/1teksaGtlefareC 2006026
G2"2x"2/1teksaGtlefareC 2006026
H2noitalusnIediSesaB 10070027)
J2noitalusnIraeResaB13070027140700271507002716070027170700271807002719070027
K2noitalusnItnorFesaB2307002724070
L2ylbmessAgeLesaB 1006816)4(
M2"2/1x02-"4/1,wercSgnippaTfleS 0070680
N2hctiwStuo-lloRemalF 44006108
P2"4/3x8#,wercSlateMteehS 03006808
Q2"8/3x23-01,wercSgnippaTfleS50706808)
R2
"4/3x81-61/5
,paCxeHwercSgnippaTtfeS
3070817540708175507081756070817570708175807081759070817
2(
0272507002726070027270700272807002729070027
8)81(
5(0706808)6(0706808)7(
08172807081729070817
76807081769070817
71706808)4(
77
78
yeK
.oN
noitpircseD
3-GCS4-GCS5-GCS6-GCS7-GCS8-GCS9-GCS
rebmuNtraP]ytitnauQ[
YLBMESSAERUSOLCNEESAB.3
A3ylbmessAxoBriA23070816240708162507081626070816270708162807081629070816
B3rooDxoBriA430708174407081745070817460708
C3resuffiDriAnoitsubmoCA/N940708179507081796070817970708179807081799070817
D3etalPrevoCt
E3teksaGebuTtoliP 8306028
F3teksaGtroPnoitavresbO 9306028)2(
G3sneLtroPnoitavresbO 28062
H3reniateRsneLtroPnoitavresbO 9106817
J3"2/1x8#swercSlateMteehS 00006808)01(
K3"8/3x23-01,wercSgnippaTfleS5
eksaGebuTtoliP 2006907
0706808)81(50706808)22(
17470708174807081749070817
08
79
80
yeK
.oN
noitpircseD
3-GCS4-GCS5-GCSCS6-GCS7-GCS-G8 CS-G9
rebmuNtraP]ytitnauQ[
YLBMESSAYPONAC/NAF.4
A4
B4tlefareC 5006029
C4pilC-U 21516808)4(
D4"4/3x01#,wercSlat
E4teksaGnaF 5806028
F4naF 21516118
G401#,rehsaWkcoL 63606808)4(
H4"2/1-2x42-01#,wercSenihcaM 2
eMteehS 31006808)4(
leveLaeS-ylbmessAyponaC13070116140701161507011616070116170701161807011619070116
edutitlAhgiH-ylbmessAyponaC2
3070116240701162507011626070116270701162807011629070116
89806808)4(
81
82
yeK
.oN
noitpircseD
3-GCS4-GCS5-GCS
SEILBMESSARENRUB.5
,)saGlarutaN(evlaVsaG
1711P4028RVllewyenoH
,)saGlarutaN(evlaVsaG
A5
B5
C5
D5
B
E5
F5
G5renruBtoliP 10-741001
H5renruBniaM
J5gnibuTtoliP 2216328
K5"2/1x02-4/1,wercSgnippaTfleS 00706808)6(
TPN,noinU 320406605A/N
TPN,noinUA/N100406608
d
lofinaMsaG13070228140702281507022816070228170702281807022819070228
dlofinaMsaG
bmessAtoliP 4616328
6944P4038RVllewyenoH
,)saGPL(evlaVsaG
5103C4028RVllewyenoH
,)saGPL(evlaVsaG
0824P4038RVllewyenoH
CxTPN,elppiN 040006608A/N
esol
esolCxTPN,elppiNA/N220006608
74#saGlarutaN-secifirOrenru
mm02.1saGPL-secifirOrenruB
saGlarutaN-ylbmessAtoliP 3616328
saGPL-yl
)4(
017228
)4(
28
2972
)3(
10-641001
)6(
)6(
)5(
28206618A/N
A/N38206
64106618A/N
A/N18106618
017228
297228
10-641001
)8(
017228
)8(
297228
)7(
10-641001
rebmuNtraP]ytitnauQ[
6-GCS7-GCS-GCS8 -GCS9
618
)01(
017228
)01(
297228
)9(
10-641001
)21(
017228
)21(
297228
)11
(
10-641001
)41(
017228
)41(
297228
)31(
10-641001
)61(
)61(
)51(
017228
297228
10-641001
83
84
yeK
.oN
noitpircseD
3-GCS4-GCS5-GCS6-GCS7-GCS8-GCS9-GCS
YLBMESSALENAPLORTNOC.6
A6D0804LllewyenoH,timiL 65106108
B6D5828RllewyenoH,yaleR/remrofsnarT U55106108
C6
D66001U2228RllewyenoH,yaleRrewolB U69006108
E6
F6xoB
70
01E0768S
noitcnuJ 9526318
llewyenoH,eludoMnoitingI
hctiwSerusserPlaitnereffiD
'9994-'0leveLaeS
'000,01-'0005-edutitlAhgiH9570610836706108467061085670610846706108
2670610816706108067061089570610806706108
rebmuNtraP]ytitnauQ[
80106108
85
86
yeK
.oN
noitpircseD
3-GCS4-GCS5-GCS6-GCS7-GCS8-GCS9-GCS
STRAPTEKCAJ.7
A7lenaPediStfeLtekcaJ 20070406
B7lenaPediSthgiRtekcaJ 10070406
rebmuNtraP]ytitnauQ[
C7lenaPraeR330704063407040635070406360704063707040
D7lenaPelubitseV43070406440704064507040646070406470704064807040649070406
E7lenaPpoT230704062407040
F7rooDtnorF13070407140704071507040716070407170704071807040719070407
G7ylbmes
H7eldnaH 4816508
J7pilCrooD 1291407)2(
K7gnihsuB 8406318
L7ogoLmahnruB 990
sAralloCekatnIriA300704064007040650070406
6257040626070406270704062807040629070406
06418
63807040639070406
87
yeK
.oN
noitpircseD
3-GCS4-GCS5-GCS6-GCS7-GCS8-GCS9-GCS
8. NOTRACSTRAPSUOENALLECSIM
A8dlofinaMretaW 10070608
B8eguaGerusserP/erutarepmeT 9616508
C8ssenraHgniriWrotalucriC 1070316
rebmuNtraP]ytitnauQ[
D8evlaVfeileRyte
E8evlaVniarDrelioB 160306608
F8lanimreTtneV 10701182070118
G8lanimreTekatnIriA540611644061163606116
H8r
faS 36306618
otcennoCtneV 30701184070118
88
noitamrofnIytefaStcudorPtnatropmI
tcudorPrebiFcimareCyrotcarfeR
Warning: This product contains refractory ceramic fi bers (RCF). RCF has been classifi ed as a
possible human carcinogen. After this product is fi red, RCF may, when exposed to extremely high temperature (>1800F), change into a known human carcinogen. When disturbed as a result of servicing or repair, RCF becomes airborne and, if inhaled, may be hazardous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures: Do not remove or replace previously fi red RCF (combustion chamber insulation, target
walls, canopy gasket, fl ue cover gasket, etc.) or attempt any service or repair work involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH) approved respirator
2. Long sleeved, loose fi tting clothing
3. Gloves
4. Eye Protection
Take steps to assure adequate ventilation.
Wash all exposed body areas gently with soap and water after contact.
Wash work clothes separately from other laundry and rinse washing machine
after use to avoid contaminating other clothes.
Discard used RCF components by sealing in an air tight plastic bag.
First Aid Procedures:
If contact with eyes: Flush with water for at least 15 minutes. Seek immediate medical attention if irritation persists.
If contact with skin: Wash affected area gently with soap and water. Seek immediate medical attention if irritation persists.
If breathing diffi culty develops: Leave the area and move to a location with clean fresh air. Seek immediate medical attention if breathing diffi culties persist.
Ingestion: Do not induce vomiting. Drink plenty of water. Seek immediate medical attention.
89
SERVICE RECORD
DATE SERVICE PERFORMED
90
SERVICE RECORD
DATE SERVICE PERFORMED
91
Limited Warranty
FOR RESIDENTIAL CAST IRON WATER BOILERS
Subject to the terms and conditions set forth below, U.S. Boiler™ Co., Inc. Lancaster, Pennsylvania hereby extends the following limited warranties to the original owner of a residential grade water boiler manufactured and shipped on or after July 1,1991:
ONE YEAR LIMITED WARRANTY
ON RESIDENTIAL GRADE WATER BOILERS
U.S. Boiler Co., Inc. warrants to the original owner that its residential grade water boilers comply at the time of manufacture with recognized hydronic industry standards and requirements then in effect and will be free of defects in material and workmanship under normal usage for a period of one year from the date of original installation. If any part of a water boiler is found to be defective in material or workmanship during this one year period, U.S. Boiler Co., Inc. will, at its option, repair or replace the defective part.
LIFETIME LIMITED WARRANTY ON HEAT EXCHANGER
U.S. Boiler Co., Inc. warrants to the original owner that the heat exchanger of its residential grade water boilers will remain free from defects in material and workmanship under normal usage for the lifetime of the original owner at the original place of installation. If a claim is made under this warranty during the first ten years from the date of original installation, U.S. Boiler Co., Inc. will, at its option, repair or replace the heat exchanger. If a claim is made under this warranty after the expiration of ten years from the date of original installation, U.S. Boiler Co., Inc. will, at its option and upon payment of the pro-rated service charge set forth below, repair or replace the heat exchanger. The service charge applicable to a heat exchanger warranty claim is
based upon the number of years the heat exchanger has been in service and will be determined as a percentage of the retail price of the heat exchanger model involved at the time the warranty claim is made as follows:
sraeY
ecivreSnI
egrahCecivreS
fo%sa
ecirPliateR
sraeY
ecivreSnI
egrahCecivreS
fo%sa
ecirPliateR
NOTE: If the heat exchanger model involved is no longer available due to product obsolescence or redesign, the value used to establish the retail price will be the published price as shown in the Burnham Hydronics Repair Parts Price Sheet where the heat exchanger last appeared or the current retail price of the then nearest equivalent heat exchanger.
ADDITIONAL TERMS AND CONDITIONS
1. Applicability: The limited warranties set forth above are extended
only to the original owner at the original place of installation within the
United States and Canada. These warranties are applicable only to
water boilers designated as residential grade by U.S. Boiler Co., Inc.
and installed in a single or two-family residence and do not apply to
s
team boilers of any kind or to commercial grade boilers.
2. Components Manufactured by Others: Upon expiration of the one
year limited warranty on residential grade water boilers, all boiler
components manufactured by others but furnished by U.S. Boiler
Co., Inc. (such as oil burner, circulator and controls) will be subject
only to the manufacturer’s warranty, if any.
3. Proper Installation: The warranties extended by U.S. Boiler Co., Inc.
are conditioned upon the installation of the residential grade water
boiler in strict compliance with U.S. Boiler Co., Inc. installation
instructions. U. S. Boiler Co., Inc. specifically disclaims liability of any
kind caused by or relating to improper installation.
4. Proper Use and Maintenance: The warranties extended by U.S.
Boiler Co., Inc. conditioned upon the use of the residential grade
01-11121 3141516171
oN
50151025203 53
egrahC
81 91021222 3242
0454055506560757
water boiler for its intended purposes and its maintenance accordance with U. S. Boiler Co., Inc. recommendations and hydronics industry standards. These warranties will be inapplicable if the residential grade water boiler is used or operated over its rated capacity, is subjected to unauthorized modification, or is damaged as
a result of being otherwise improperly operated or serviced including, but not limited to, damage from any of the following: operation with
insufficient water, allowing the boiler to freeze, subjecting the boiler to flood conditions, and operation with unapproved water or fuel additives which cause deposits or corrosion.
5. Removal and Installation: These warranties do not cover expenses of removal or reinstallation. The owner is responsible for the cost of removing and reinstalling any defective part and its replacements and all labor and material connected therewith.
6. Exclusive Remedy: U.S. Boiler Co., Inc. obligation for any breach of these warranties is limited to the repair or replacement of its parts in accordance with the terms and conditions of these warranties.
7. Limitation of Damages: Under no circumstances shall U.S. Boiler Co., Inc. be liable for incidental, indirect, special or consequential damages of any kind whatsoever under these warranties, including, but not limited to, injury or damage to persons or property and damages for loss of use, inconvenience or loss of time. U.S. Boiler Co., Inc. liability under these warranties shall under no circumstances exceed the purchase price paid by the owner for the residential grade water boiler involved. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
8. Limitation of Warranties: These warranties set forth the entire obligation of U.S. Boiler Co., Inc. with respect to any defect in a residential grade water boiler and U.S. Boiler Co., Inc. shall have no express obligations, responsibilities or liabilities of any kind whatsoever other than those set forth herein. These warranties are given in lieu of all other express warranties.
ALL APPLICABLE IMPLIED WARRANTIES, IF ANY, INCLUDING
ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY LIMITED IN DURATION TO A PERIOD OF ONE YEAR EXCEPT THAT IMPLIED
dna52
evoba
WARRANTIES, IF ANY, APPLICABLE TO THE HEAT EXCHANGER IN A RESIDENTIAL GRADE WATER BOILER SHALL EXTEND TO THE ORIGINAL OWNER FOR THE LIFETIME OF THE ORIGINAL OWNER AT THE ORIGINAL PLACE OF INSTALLATION. SOME STATES DO NO ALLOW LIMITATION ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU.
PROCEDURE FOR OBTAINING WARRANTY SERVICE
In order to assure prompt warranty service, the owner is requested to
complete and mail the attached Warranty Card within ten days after the installation of the boiler, although failure to comply with this request will not void the owner’s rights under these warranties.
Upon discovery of a condition believed to be related to a defect in
material or workmanship covered by these warranties, the owner should notify the installer, who will in turn notify the distributor. If this action is not possible or does not produce a prompt response, the owner should write to U.S. Boiler Co., Inc., Burnham Hydronics, at P.O. Box 3079, Lancaster, PA 17604, giving full particulars in support of the claim.
The owner is required to make available for inspection by U.S. Boiler
Co., Inc. or its repres requested by U.S. Boiler Co., Inc. to ship these parts prepaid to U.S. Boiler Co., Inc. at the above address for inspection or repair. In addition, the owner agrees to make all reasonable efforts to settle any disagreement arising in connection with a claim before resorting to legal remedies in the courts.
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND
YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
entative the parts claimed to be defective and, if
03/03
Loading...