Burnham SCG 1100-H4 User Manual

Page 1
As an ENERGY STAR
ROFSNOITCURTSNIECIVRES
GCS
RELIOBDERIF-SAG
nonoitamrofnignikeesnehW.rotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
.lebaLgnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp,reliob
rebmuNledoMrelioB
GCS
rebmuNlaireSrelioB etaDnoitallatsnI
rotcartnoCgnitaeH rebmuNenohP
sserddA
STAR® guidelines for energy efciency established by the United States Environmental Protection Agency (EPA).
®
Partner, Burnham Hydronics has determined that the SCG meets the ENERGY
8140705R9-10/08
Price - $5.00
Page 2
IMPORTANT INFORMATION - READ CAREFULLY
NOTE: The equipment shall be installed in accordance with those installation regulations enforced in the area where the
installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or local regulations. All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or local regulations.
The New York City Department of Buildings has approved the SCG™ Series boiler: Approval No. MEA 5-06-E. The City of New York requires a Licensed Master Plumber supervise the installation of this product. The Massachusetts Board of Plumbers and Gas Fitters has approved the SCG™ Series boiler. See the Massachusetts Board of
Plumbers and Gas Fitters website, http://license.reg.state.ma.us/pubLic/pb_pre_form.asp for the latest Approval Code or ask your local Sales Representative.
The Commonwealth of Massachusetts requires this product to be installed by a Licensed Plumber or Gas Fitter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to
important information concerning product life.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
Indicates a potentially hazardous situation which, if not avoided, may result in moderate or minor injury or property damage.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
CAUTION
NOTICE
DANGER
DO NOT store or use gasoline or other ammable vapors or liquids in the vicinity of this or any other
appliance. If you smell gas vapors, NO NOT try to operate any appliance - DO NOT touch any electrical switch or use
any phone in the building. Immediately, call the gas supplier from a remotely located phone. Follow the gas
supplier’s instructions or if the supplier is unavailable, contact the re department.
2
Page 3
WARNING
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained
in this manual. Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal
injury or loss of life. Read and understand the entire manual before attempting installation, start-up operation, or service. Installation and service must be performed only by an experienced, skilled, and knowledgeable installer or service agency.
This boiler must be properly vented.
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air. The interior of the venting system must be inspected and cleaned before the start of the heating season
and should be inspected periodically throughout the heating season for any obstructions. A clean and unobstructed venting system is necessary to allow noxious fumes that could cause injury or loss of life
to vent safely and will contribute toward maintaining the boiler’s efciency.
Installation is not complete unless a pressure relief valve is installed into the tapping located on top of appliance. - See the Water Piping and Trim Section of this manual for details.
This boiler is supplied with safety devices which may cause the boiler to shut down and not re-start without service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
This boiler contains very hot water under high pressure. Do not unscrew any pipe ttings nor attempt
to disconnect any components of this boiler without positively assuring the water is cool and has no
pressure. Always wear protective clothing and equipment when installing, starting up or servicing this
boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the boiler. This boiler contains components which become very hot when the boiler is operating. Do not touch any components unless they are cool.
Boiler materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause death or serious injury and which are known to the state of California to cause cancer, birth defects and
other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing
or working nearby the appliance. Failure to follow all instructions in the proper order can cause personal injury or death. Read all instruc-
tions, including all those contained in component manufacturers manuals which are provided with the boiler before installing, starting up, operating, maintaining or servicing.
Keep boiler area clear and free from combustible materials, gasoline and other ammable vapors or liquids.
All cover plates, enclosures and guards must be in place at all times.
NOTICE
This boiler has a limited warranty, a copy of which is printed on the back of this manual. It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating properly when the installation is complete.
3
Page 4
Table of Contents
I. Pre-Installation ...............................6
II. Unpack Boiler ................................
III. Venting/Air Intake Piping ..............
IV. Water Piping and Trim .................
V. Gas Piping ....................................
45
50
VI. Electrical .......................................53
7
8
VII. Modular Installation ....................
VIII. System Start-up ............................
IX. Service .......................................... 71
X. Repair Parts ..................................
62
64
78
Figure 1: Minimum Clearances to Combustibles
4
Page 5
Figure 2: Dimensions
5
Page 6
I. Pre-Installation
WARNING
If you do not follow these instructions exactly,
a re or explosion may result causing property
damage or personal injury.
F. Provide combustion and ventilation air in accordance
with applicable provisions of local building codes, or: USA - National Fuel Gas Code, NFPA 54/ANSI Z223.1, Air for Combustion and Ventilation;
Canada - Natural Gas or Propane Installation Code,
CAN/CSA-B149.1.
DANGER
Do not install boiler where gasoline or other
ammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used or stored.
NOTICE
Due to the low water content of the boiler, mis­sizing of the boiler with regard to the heating system load will result in excessive boiler cycling and accelerated component failure. Burnham DOES NOT warrant failures caused by mis-sized boiler applications. DO NOT oversize the boiler to the system. Modular boiler installations greatly reduce the likelihood of boiler oversizing.
A. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such requirements, installation must conform to the National Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/ CSA B149.1 Installation Codes.
B. Appliance is design certied for installation on
combustible ooring. Do not install boiler on
carpeting.
C. Provide clearance between boiler jacket and
combustible material in accordance with local re
ordinance. Refer to Figure 1 for minimum listed clearance from combustible material. Recommended service clearance is 24 inches from left side, right side and front. Service clearances may be reduced to minimum clearances to combustible materials.
D. Install on level oor. For basement installation provide
solid base such as concrete, if oor is not level or if water may be encountered on oor around boiler. Floor
must be able to support weight of boiler, water and all additional system components.
E. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, condensate trap, control replacement, etc.).
WARNING
Adequate combustion and ventilation air must
be provided to assure proper combustion.
The following guideline is based on the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
1. Determine volume of space (boiler room). Rooms communicating directly with space (through openings not furnished with doors) are considered part of space.
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space. Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total Input.
a. If result is greater than or equal to 50 ft³ per
1,000 Btuh, space is considered an unconned space.
b. If result is less than 50 ft³ per 1,000 Btuh, space
is considered a conned space.
4. Determine building type. A building of unusually tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed, and;
b. Weather-stripping has been added on openable
windows and doors, and;
c. Caulking or sealants applied in joints around
window and door frames, between sill plates and
oors, between wall-ceiling joints, between wall
panels, at plumbing and electrical penetrations, and at other openings.
5. For boiler located in an unconned space in a building of other than unusually tight construction, adequate combustion and ventilation air is normally
provided by fresh air inltration through cracks
around windows and doors.
6
Page 7
NOTICE
Boilers operated with direct vent (sealed combustion) are exempt from needing provisions for combustion air from the room, provided air intake piping is installed per Code and the instructions in the manual.
6. For boiler located within
of unusually tight construction or within conned space, provide outdoor air through two permanent
openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within twelve (12) inches of top of space. Locate remaining opening within twelve (12) inches of bottom of space. Minimum dimension of air opening is three (3) inches. Size each opening per following:
a. Direct communication with outdoors. Minimum
free area of one (1) square inch per 4,000 Btu per hour input of all equipment in space.
b. Vertical ducts. Minimum free area of one (1)
square inch per 4,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
unconned space in building
c. Horizontal ducts. Minimum free area of one (1)
square inch per 2,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
Alternate method for boiler located within
conned space. Use indoor air if two permanent
openings communicate directly with additional
space(s) of sufcient volume such that combined volume of all spaces meet criteria for unconned
space. Size each opening for minimum free area of one (1) square inch per 1,000 Btu per hour input of all equipment in spaces, but not less than 100 square inches.
7. Combustion Air/Ventilation Duct Louvers and Grilles. Equip outside openings with louvers to prevent entrance of rain and snow, and screens to prevent entrance of insects and rodents. Louvers and
grilles must be xed in open position or interlocked
with equipment to open automatically before burner operation. Screens must not be smaller than ¼ inch mesh.
Consider the blocking effect of louvers, grilles and
screens when calculating the opening size to provide the required free area. If free area of louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
CAUTION
If using indoor air for combustion (see Venting Section - Indoor Air), avoid operating this boiler in an
environment where saw dust, loose insulation bers, dry wall dust, etc. are present. If boiler is operated
under these conditions, the burner interior and ports must be cleaned and inspected daily to insure proper operation.
II. Unpack Boiler
CAUTION
Do not drop boiler. Do not bump boiler jacket
against oor.
A. Move boiler to approximate installed position. B. Remove all crate fasteners. C. Lift and remove outside container. Save two of the
wooden slats from the container sleeve for use in Steps E and F.
D. Remove all boiler hold-down fasteners.
Installation of this boiler should be undertaken only by trained and skilled personnel from a
qualied service agency.
E. Tilt the boiler to its front side or back side and slide a
wooden slat under the three raised feet.
F. Tilt the boiler in the opposite direction and slide
another wooden slat under the three raised feet.
G. Slide the boiler left or right off the skid using the two
wooden slats as runners.
WARNING
H. Move boiler to its permanent location.
7
Page 8
III. Venting / Air Intake Piping
WARNING
Do not use this boiler with galvanized, Type 304 or Type 316 stainless steel, non metallic or any other non AL29-4C® based vent systems.
Do not use a barometric damper or drafthood with this appliance. Do not use vent dampers with this boiler. Moisture and ice may form on surfaces around termination. To prevent deterioration, surfaces should
be in good repair (sealed, painted, etc.). This appliance needs fresh air for safe operation and must be installed so there are provisions for
adequate combustion and ventilation air.
Do not reduce size of air intake pipe. Read, understand and follow combustion air instruction restrictions contained in the Pre-Installation
instructions of this manual. Do not operate appliance where gasoline or other ammable vapors or liquids, or sources of hydro-
carbons (i.e. bleaches, cleaners, chemicals, sprays, paint removers, fabric softeners, etc.) are used, stored and/or present in the air.
When installing vent pipe through chimney, no other appliance can be vented into the chimney. Do not exceed maximum vent/air intake lengths. Refer to Table 4.
TABLE 1: AIR INTAKE / VENT SYSTEM OPTIONS
Option Description
Direct Vent (sealed combustion) with both the vent pipe and
1. Separate
Horizontal
2. Separate
Vertical
3. Combination
Horizontal
4. Combination
Vertical
5. Indoor Air
6. Optional
Separate Horizontal
air intake pipe terminating horizontally (through a sidewall) with individual penetrations for the vent and air intake piping and terminals.
Direct Vent (sealed combustion) with both the vent pipe and air intake pipe terminating vertically (through the roof) with individual penetrations for the vent and air intake piping and terminals.
Direct Vent (sealed combustion) with the vent pipe and air
intake pipe joining at a common terminal and terminating
horizontally (through a sidewall up to 15” thick) with only one penetration.
Direct Vent (sealed combustion) with the vent pipe and air
intake pipe joining at a common terminal and terminating
vertically (through the roof) with only one penetration.
Power Vent - Air used for combustion is provided from within the building.
Direct Vent (sealed combustion) with both the vent pipe and air intake pipe terminating horizontally (through a sidewall) with individual penetrations for the vent and air intake piping and terminals.
Additional
Vent Kit
Part Number
Required
No See Table 2 D.
No See Table 2 E.
Yes
Yes
No ----- H.
No See Table 2 I.
3 - 6 Section
(61106012)
3 - 4 Section
(100222-01)
5 - 6 Section
(100223-01)
Installation
Drawing and
Specication
(See Section)
F.
G.
8
Page 9
TABLE 2: VENT SYSTEM COMPONENTS INCLUDED WITH BOILER
Vent System Components Part Number
Gasketed Vent Terminal 3” Horizontal (SCG-3 thru SCG-7)
Gasketed Vent Terminal 4” Horizontal (SCG-8 & SCG 9)
Disc Air Intake - 3” (SCG-3 & SCG-4)
Disc Air Intake - 4” (SCG-5 & SCG-6)
Air Intake - 5” (SCG-7 thru SCG-9)
8110701
8110702
6116045
6116044
6116063
TABLE 3: BURNHAM VENT SYSTEM AND AIR INTAKE SYSTEM COMPONENTS
Vent System Component Part Number
3” Dia. Pipe x 1 Ft 8116296U 4” Dia. Pipe x 1 Ft 100176-01 3” Dia. Pipe x 3 Ft 8116298U 4” Dia. Pipe x 3 Ft 100177-01 3” Dia. Pipe x 5 Ft 8116300U 4” Dia. Pipe x 5 Ft 100178-01 3” Dia. Pipe x Adjustable 8116319U
4” Dia. Pipe x Adjustable 100179-01 3” Dia. 90° Elbow 8116294U
4” Dia. 90° Elbow 100180-01 3” Dia. 45° Elbow 8116292U 4” Dia. 45° Elbow 100181-01 3” Dia. Horizontal Drain Tee 8116302U 4” Dia. Horizontal Drain Tee 100182-01 3” Dia. Vertical Drain Tee 8116304U 4” Dia. Vertical Drain Tee 100183-01 3” Single Wall Thimble 8116116 4” Single Wall Thimble 100184-01 3” Double Wall Thimble 8116115 4” Double Wall Thimble 100185-01
Equivalent
Feet of Pipe
1
3
5
Equal to
Installed Length
(1.06 TO 1.64)
5
5
2
---
---
Intake System Components
(Parts by Others)
3”, 4”, or 5” ID Pipe x 1 Ft 1 3”, 4”, or 5” ID Pipe x 2 Ft 2 3”, 4”, or 5” ID Pipe x 4 Ft 4 3”, 4”, or 5” ID Pipe x 5 Ft 5
3”, or 4” 90° Elbow 5 3”, or 4” 45° Elbow 5
5” 90° Elbow 6 5” 45° Elbow 6
* Equivalent Feet of Pipe Based on Standard 4” Smoke Pipe Design
Equivalent
Feet of Pipe *
TABLE 4: VENT/AIR INTAKE LENGTH
Model
3” Air Intake Pipe
(Equiv. Ft.)
4” Air Intake Pipe
(Equiv. Ft.)
5” Air Intake Pipe
(Equiv. Ft.)
3” Vent Pipe
(Equiv. Ft.)
4” Vent Pipe
(Equiv. Ft.)
Min. Max. Min. Max. Min. Max. Min. Max. Min. Max.
SCG-3 & SCG-4 8 50 --- --- --- --- 8 50 --- --­SCG-5 & SCG-6 --- --- 8 50 --- --- 8 50 --- ---
SCG-7 --- --- --- --- 8 50 8 50 --- ---
SCG-8 & SCG-9 --- --- --- --- 8 40 --- --- 8 40
9
Page 10
A. Vent Guidelines Due to Removal of an Existing
Boiler
For installations not involving the replacement of an
existing boiler, proceed to Step B.
When an existing boiler is removed from a common
venting system, the common venting system is likely to be too large for proper venting of the remaining appliances. At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, and other
deciencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range-hoods and bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close
replace dampers.
4. Place in operation the appliance being inspected. Follow the Lighting (or Operating) Instructions. Adjust thermostat so appliance will operate continuously.
5. Test for spillage at the draft hood relief opening
after ve (5) minutes of main burner operation. Use the ame of a match or candle, or smoke from a
cigarette, cigar or pipe.
6. After it has been determined that each appliance remaining connected to the common venting system properly vents when tested as outlined above, return
doors, windows, exhaust fans, replace dampers and
any other gas burning appliance to their previous conditions of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, NFPA 54/ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part II in the National Fuel Gas Code, NFPA 54/ ANSI Z223.1.
10
B. General Guidelines
1. Vent system installation must be in accordance
with National Fuel Gas Code, NFPA 54/ANSI Z221.3 or applicable provisions of local building
codes. Contact local building or re ofcials about
restrictions and installation inspection in your area.
2. The SCG is designed to be installed as either a Direct Vent boiler or Power Vent boiler. In
the Direct Vent conguration all of the air for
combustion is supplied directly to the burner
enclosure from outdoors and ue gases are vented
directly outdoors (through wall or roof). In the
Power Vent conguration, room air provides air
for combustion and ventilation. Flue gases are still vented directly outdoors (through wall or roof).
Note: Venting requirements change if indoor air is
used.
3. Refer to the appropriate drawings in this section of
this manual to determine the proper conguration of
venting system. See Table 1.
4. This appliance requires a Special Gas Vent. The product is designed to use Burnham supplied AL 29-4C® Stainless Steel vent system components. The following manufacturers offer similar AL 29-4C® components and are approved for use with this product. Heat-Fab Inc. - Saf-T-Vent (800­772-0739); Flex-L International Inc. - Star-34 (800­561-1980); Z-Flex U. S., Inc. - Z-Vent (800-654-
5600); and Protech Systems, Inc.- FasNSeal™ (800­766-3473) or equivalent. The use of these alternate manufacturer’s venting systems will require adapters to connect to the Burnham supplied vent connector and vent terminal. These adapters are not supplied with this unit and should be obtained from the supplier of the alternate manufacturer’s venting system. See Table 3 for complete list of Burnham Vent System Components.
5. Horizontal vent pipe must maintain a minimum ¼ inch per foot slope down towards boiler.
6. Use noncombustible ¾ inch pipe strap to support horizontal runs and maintain vent location and slope while preventing sags in pipe. Do not restrict thermal expansion or movement of vent system.
Maximum support spacing is ve (5) feet. Do not
penetrate any part of the vent system with fasteners.
7. Vent length restrictions are based on equivalent length of vent/air pipe (total length of straight
pipe plus equivalent length of ttings). Maximum
vent/air lengths are listed in Table 4. Do not exceed maximum vent/air intake lengths. Table 3 lists
equivalent lengths for ttings. Do not include vent/
air terminals in equivalent feet calculations.
8. Provide and maintain vent pipe minimum clearances to combustible materials. Vent pipe minimum clearance to combustible material is four (4) inches when vent is installed in a fully enclosed (chase) application or three (3) inches when vent is installed
Page 11
with at least one side open, similar to a joist bay application. Use double wall thimble [Burnham Part No. 8116115 (3”), 100185-01 (4”)] when penetrating a combustible wall.
9. Do not install venting system components on
the exterior of the building except as specically
required by these instructions. The vent termination location is restricted as follows:
a. Minimum twelve (12) inches above grade plus
normally expected snow accumulation level, or seven (7) feet above grade if located adjacent to public walkway. Do not install over public walkway where local experience indicates
appliance ue gas vapor or condensate creates a
nuisance or hazard.
b. Minimum three (3) feet above any forced air
inlet located within ten (10) feet.
c. Direct Vent - Minimum one (1) foot below, one
(1) foot horizontally from, or one (1) foot above any door, window, or gravity air inlet.
Power Vent - Minimum four (4) feet below, four
(4) feet horizontally from, or four (4) feet above any door, window, or gravity air inlet.
d. Minimum four (4) feet horizontally from electric
meters, gas meters, regulators, and relief valves. This distance may be reduced if equipment is protected from damage due to condensation or vapor by enclosure, overhangs, etc.
e. Minimum twelve (12) inches from overhang or
corner of building.
10. Enclose vent passing through occupied or unoccupied spaces above the boiler with material
having a re resistance rating of at least equal to the rating of the adjoining oor or ceiling. Maintain
minimum clearances to combustible materials. See Figure 1.
Note: For one or two family dwellings, re
resistance rating requirement may not need to be met, but is recommended.
11. Plan venting system to avoid possible contact with plumbing or electrical wires. Start at vent connector on top of boiler and work towards vent terminal.
12. Once a vent pipe manufacturer and system is chosen never mix and match vent systems.
13. If a non-standard length pipe is required:
Gasketed Vent System: The use of the adjustable
length pipe (P/N 8116319U) is recommended to complete a non-standard pipe length. This pipe requires a minimum installed length of 12¾ inch and can adjust across a 7 inch gap up to a maximum of 19¾ inch long. (Note for the adjustable pipe the installed length should be measured from the
centerline of the bead on the male end of the rst
pipe to the end of the female pipe excluding the locking band of the second pipe with a single gasket.) Only in the event the adjustable length pipe
is not sufcient a standard length pipe may be cut
using the procedure outlined below for the Gasket­Less Vent System.
WARNING
Never exceed maximum installed length of 19¾ inches for adjustable length pipe.
Risk of ue gas leakage is possible.
NOTICE
Cut must be square with pipe and led or
sanded smooth before joining. Carefully ensure roundness of cut pipe by hand with gloves before
installing. Seal joint with RTV specied in this
manual.
C. Install Vent Pipe, Burnham Gasketed Vent System.
1. Procedure for Joining Burnham Gasketed Vent Pipe and Fittings. See Figure 3.
Figure 3: Burnham Gasketed Vent Joint Detail
11
Page 12
a. Wipe the male end of each joint using an alcohol
pad to remove any dirt and grease.
b. Align weld seams in pipes and use a slight
twisting motion to FULLY insert male end into female end of joint. Ensure bead in male end of pipe is below locking band and rest against the end of the female pipe. Verify the factory­installed gasket is not dislodged or cut.
c. Tighten locking band by HAND with a 5/16”
nut driver until snug plus ¼ turn. DO NOT SECURE JOINTS WITH SHEET METAL SCREWS OR POP RIVETS. DO NOT PUNCTURE THE VENT SYSTEM!
d. Once the installation is complete, operate
appliance and inspect all joints to ensure that ue
gases and/or liquid condensate will not escape.
D. Separate Horizontal Venting System. See Figures
4A, 4B, 5A and 5B. See Figure 43 on Page 72 for Blower Vent Connector Assembly.
Vent Piping
1. This boiler is supplied with components as standard equipment for installation of the separate horizontal venting system.
2. Do not exceed maximum vent/air intake lengths. Refer to Table 4.
3. Recommended horizontal installation consists of vent being sloped down ¼ inch per foot away from boiler. See Figure 4A. See Figure 48 for an alternate horizontal installation.
4. Use appropriate designed thimbles when passing through combustible walls (thimble use optional for noncombustible walls). Insert thimble through wall
from outside. Secure outside ange to wall with
nails or screws, and seal ID, OD and vent holes with
sealant material. Install inside ange to inside wall,
secure with nails or screws, and seal with sealant material.
5. For noncombustible wall application when thimble is not used, size opening such that bell with locking band attached cannot pass through.
6. Join vent terminal to vent pipe. See Figures 5A and 5B.
7. Insert vent pipe through thimble/opening from outside and join to vent system. Apply sealant between vent pipe and opening/thimble to provide weathertight seal.
Air Intake piping - See Figures 4A, 4B, 5A and 5B.
8. Locate air intake termination on the same wall as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with vertical venting and sidewall combustion air inlet or visa versa, if installation conditions do not allow alternate arrangement.
9. Do not exceed air intake length. See Table 4.
10. Use single wall metal or PVC pipe. a. Air intake pipe diameter is based on boiler size.
SCG-3 & SCG-4 uses 3 inch diameter piping. SCG-5 & SCG-6 uses 4 inch diameter piping. SCG-7 thru SCG-9 uses 5 inch diameter piping.
11. Air intake termination must be located:
Horizontal - At least twelve (12) inches above
grade plus the expected snow accumulation.
12. Start at collar on boiler jacket and work towards the air intake terminal.
13. Maintain minimum of ¼ inch per foot slope on horizontal runs. Slope towards air inlet terminal when possible. If not, slope towards boiler.
14. The air intake pipe must be adequately supported
with straps or supports no less than ve (5) feet
apart on horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts without collapse.
Inlet air pipe penetration:
15.
Horizontal - Size wall penetration to allow easy
insertion of air inlet piping. Seal around pipe with sealant to form weathertight exterior joint.
16. Seal all joints airtight, using silicone caulk or self­adhesive aluminum tape.
Install Air Intake Terminal:
17.
Horizontal - Remove four (4) screws from cover
plate and remove cover plate from terminal. Insert intake piping into intake terminal collar. Secure terminal to intake piping and seal joint with silicone caulk or self-adhesive aluminum tape. Apply continuous bead of silicone caulk around the back of the intake terminal, approximately ¼ inch from its edge. Push inlet terminal inward until terminal’s
back ange is against the wall surface. Secure the
terminal with noncorrosive fasteners (stainless steel, brass or aluminum) to the wall. Reinstall the cover plate with four (4) screws. Apply a bead of silicone
caulk to perimeter of intake terminal’s back ange
to provide a weathertight seal.
12
Page 13
Figure 4A: Recommended Separate Horizontal – Vent/Air Intake Installation
13
Page 14
14
Figure 4B: Alternate Separate Horizontal – Vent/Air Intake Installation
Page 15
Figure 5A: Separate Horizontal – Vent/Air Intake Terminal Conguration (SCG-3 thru 7)
15
Page 16
16
Figure 5B: Separate Horizontal – Vent/Air Intake Terminal Conguration (SCG-8 and 9)
Page 17
E. Separate Vertical Venting System - See Figures 6, 7, 8A, 8B and 9.
NOTICE
Roof penetrations require the use of roof ashing
and storm collar - not supplied with boiler.
Vertical Venting
1. See Figure 43 on Page 72 for Blower Vent Connector Assembly. Do not exceed maximum vent lengths. Refer to Table 4.
2. Installation of a vertical vent drain tee 8116304U is required on all vertical vent applications. See Figures 6 and 7. Attach vertical vent drain tee directly to elbow or horizontal pipe from an elbow immediately after vent connector.
3. Slope horizontal runs minimum ¼ inch per foot. Slope towards vertical vent drain tee. Position weld seams in vent pipes, in all horizontal runs, at the top to avoid condensate from lying on the seams.
4. Install re stops where vent passes through oors, ceilings or framed walls. The re stop must close
the opening between the vent pipe and the structure.
5. Whenever possible, install vent straight through the roof. Refer to Figure 7 if offset is necessary. Maintain minimum clearance to combustible materials.
6. Install Vent Terminal. a. Size roof opening to maintain minimum
clearance from combustible materials.
b. Extend vent pipe to maintain minimum vertical
and horizontal distance of twelve (12) inches from roof surface. Allow additional vertical distance for expected snow accumulation. Provide brace as required. Refer to Figures 8A and 8B.
NOTICE
Vertical venting requires the use of roof ashing
and a storm collar to prevent moisture from entering the structure.
c. Install storm collar on vent pipe immediately
above ashing. Apply Dow Corning Silastic 732
RTV Sealant between vent pipe and storm collar to provide weathertight seal.
d. Attach vent terminal.
Vertical Air Intake Piping
7. Do not exceed maximum air intake length. Refer to Table 4.
8. Locate air intake termination on the same roof location as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with vertical venting and sidewall combustion air inlet or visa versa, if installation conditions do not allow alternate arrangement.
9. Use single wall metal pipe or PVC and ttings
available at most heating distributors. a. Air intake pipe diameter is based on boiler size.
SCG-3 & SCG-4 uses 3 inch diameter piping. SCG-5 & SCG-6 uses 4 inch diameter piping. SCG-7 thru SCG-9 uses 5 inch diameter piping.
10. Air intake termination must be located: Vertical - At least twelve (12) inches above the roof
surface plus the expected snow accumulation.
11. Start at collar on burner enclosure (inside boiler
jacket) and work towards the air intake terminal.
12. Maintain minimum of ¼ inch per foot slope on
horizontal runs. Slope down towards boiler.
13. The air intake pipe must be adequately supported
with straps or supports no less than ve (5) feet
apart on horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts without collapse.
14. Inlet air pipe penetration:
Vertical - Size roof opening to allow easy insertion
of inlet piping and allow proper installation of
ashing and storm collar. a. Use appropriately designed vent ashing
when passing through roofs. Follow ashing
manufacturers’ instructions for installation procedures. Flashing manufacturers are Air­Jet, American Metal Products, Metal Fab, and Simpson Dura-Vent.
b. Extend air intake pipe to maintain minimum
vertical and horizontal distance of twelve (12) inches from roof surface. Allow additional vertical distance for expected snow accumulation. Provide brace as required. Refer to Figures 8A and 8B.
c. Vertical air intake requires ashing and a storm
collar to prevent moisture from entering the structure.
17
Page 18
d. Install storm collar on air intake pipe
immediately above ashing. Apply Dow
Corning Silastic 732 RTV Sealant between air intake pipe and storm collar to provide weathertight seal.
e. All exposed air intake piping must be
constructed of corrosion resistant material such as aluminum, stainless steel or PVC.
15. Seal all joints airtight, using silicone caulk or self­adhesive aluminum tape.
16. Install Air Intake Terminal:
Vertical - Insert intake piping into intake terminal
collar. Secure terminal to intake piping and seal joint with silicone caulk.
18
Page 19
Figure 7: Attic OffsetFigure 6: Vertical Vent Installation
19
Page 20
20
Figure 8A: Vertical Vent/Air Termination (3” Vent Terminal)
Extend Vent/Air Intake Piping to maintain minimum vertical (“X”) and minimum horizontal (“Y”) distance of twelve (12) inches from
roof surface. Allow additional vertical (“X”) distance for expected snow accumulation.
Page 21
Figure 8B: Vertical Vent/Air Termination (4” Vent Terminal)
Extend Vent/Air Intake Piping to maintain minimum vertical (“X”) and minimum horizontal (“Y”) distance of twelve (12) inches from roof surface. Allow ad-
21
ditional vertical (“X”) distance for expected snow accumulation.
Page 22
22
Figure 9: Vertical Air Intake Piping
Page 23
F. Combination Horizontal Venting System –SCG-3 Through SCG-6 ONLY – See Figures 10 and 11.
NOTICE
This vent system requires components not
supplied with the boiler.
2.
Install Combination Vent/Air Terminal. See Figure 11.
a. After determining the location with reference to Section B - General Venting Guidelines, cut a 6-1/8 inch square
opening in the wall for the air box sub-assembly which is 6 inch square.
b. Remove and save shipping screw from end panel with collar and vent pipe assembly. This will be reinstalled in a later
step.
1. Do not exceed maximum vent/air intake lengths. Refer to Table 4.
Vent Carton Part Number 61106012 (Includes Items Below)
Description Component Part Number
A Air Box Sub-Assembly (6” square x 2’ long) 61106011 B Exterior Wall Cover (10” square) 71106016 C 4” x 3” Vent Pipe Reducer 8116239 D Plate-Seal Exterior Cover (2) 71106017 E #8 x ½” Stainless Steel Sheet Metal Screw (19) 80860047 F #10 - 32 x ¼” Stainless Steel Machine Screw (8) 80860842 G #10 - 32 x ½” Aluminum Spacer (4) 80861617
COMBINATION HORIZONTAL VENT SYSTEM COMPONENTS
23
Page 24
c. From exterior of building, insert air box sub-
assembly into square opening. Push air box
inward until wall ange is against wall, check
for level and mark the location of the four (4) securing holes on the exterior wall. Remove air box from wall.
d. Drill four (4) pilot holes, properly sized for the
non-corrosive fasteners (stainless steel, brass, or
aluminum) to be used to secure the wall ange to
the exterior wall. (Securing screws not supplied with kit.)
e. Attach four (4) 1/2 inch long threaded aluminum
spacers to the outer anges of the exterior wall ange with four (4) number 10 - 32 x 1/4
inch stainless steel machine screws provided. (See Figure 11.)
f. Apply a 1/4 inch thick continuous bead of
silicone caulk to perimeter of exterior wall
ange’s back surface to provide a weathertight
seal.
g. Reinstall air box sub-assembly into opening in
exterior wall and secure to wall.
WARNING
Non-corrosive fasteners must be used.
h. Apply a bead of silicone caulk to perimeter of
wall ange, where the wall and ange join. Use a tool or your nger and apply pressure while
smoothing caulking to provide a weathertight seal.
i. From interior of building, insert end panel with
collar and vent pipe assembly into open end of air box sub-assembly. (See Figure 11.)
j. Secure end panel to air box sub-assembly with
shipping screw and thirteen (13) number 8 sheet metal screws provided.
k. From exterior of building, position 10 inch
square exterior wall cover over exterior wall
ange. Insert 3 inch diameter vent pipe into
center opening in terminal cover. Align four (4) holes on cover with 1/2 inch long threaded
spacers on wall ange. Secure terminal cover
with four (4) number 10 - 32 x 1/4 inch stainless steel machine screws provided.
l. Apply a bead of silicone caulk to perimeter of
plate-seal and around pipe. Secure plate-seal to exterior cover with six (6) #8 stainless steel sheet metal screws provided. Smooth caulk around plate-seal and pipe to provide weathertight seal.
m. Install Vent Terminal supplied with boiler to vent
pipe penetrating through terminal cover. Join terminal and pipe with locking band and seal with RTV (see Figure 3).
Install Vent Piping. See Figures 10 and 11.
3. a. Start at vent connector on boiler, see Figure 43
on Page 72, and work towards combination vent/ air terminal.
b. Installation of a vertical vent tee 8116304U is
required on all vertical vent applications. See Figures 12 and 13. Attach vertical vent drain tee directly to elbow or horizontal pipe from an elbow immediately after vent connector.
c. Slope horizontal runs minimum ¼ inch per foot.
Slope towards vertical vent drain tee. Position weld seams in vent pipes, in all horizontal runs, at the top to avoid condensate from lying on the seams.
d. Use 3/4 inch pipe strap to support horizontal runs
and maintain vent location and slope. Maximum
support spacing is ve (5) feet.
e. Install vent piping to connect vent connector
on boiler and combination vent/air terminal. Reference Section B - General Venting Guidelines for proper procedure for joining pipe
and ttings.
f. Connect vent piping to combination vent/air
terminal. See Figure 10.
4.
Install Air Intake Piping. See Figures 10 and 11.
a. Do not exceed air intake length. See Table 4.
b. Use single wall metal pipe or PVC and ttings
available at most heating distributors.
c. Air intake pipe diameter is based on boiler size.
SCG-3 & SCG-4 uses 3 inch diameter piping. SCG-5 & SCG-6 uses 4 inch diameter piping. SCG-7 thru SCG-9 uses 5 inch diameter piping.
d. Start at collar on burner enclosure (inside boiler
jacket) and work towards the combination vent/ air terminal.
e. Maintain minimum of 1/4 inch per foot slope on
horizontal runs. Slope down towards boiler.
f. The air intake pipe must be adequately supported
with straps or supports no less than ve (5)
feet apart on horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts without collapse.
g. Connect Air Intake Piping to Combination Vent/
Air Terminal. See Figure 10.
NOTE: When installing 3 inch diameter air intake piping for a SCG-3 or SCG-4 application, the use of a 4 inch x 3 inch reducer will be required to connect air intake piping to combination vent/air terminal. (Reducer included with combination horizontal venting kit).
h. Seal all joints airtight, using silicone caulk or
self-adhesive aluminum tape.
24
Page 25
Figure 10: Combination Horizontal – Vent/Air Installation (SCG-3 thru 6)
25
Page 26
26
Figure 11: Combination Horizontal – Vent/Air Terminal Installation (SCG-3 thru 6)
Page 27
G. Combination Vertical Venting System – SCG-3 Through SCG-6 ONLY – See Figures 12, 13 and 14.
NOTICE
This vent system requires components not
supplied with the boiler.
Description
Part Number
SCG-3 & SCG-4 SCG-5 & SCG-6
Vent Carton Part Number 100222-01 100223-01
Air Intake Tee 100224-01 100225-01 Termination Adapter 100226-01
COMBINATION VERTICAL VENT SYSTEM COMPONENTS
27
Page 28
1. Saf-T Vent SC is an advanced concentric vent system designed for zero clearance installation in residential applications. The inner wall is constructed from superferritic AL29-4C® stainless steel. The outer wall is also constructed from stainless steel, providing durability and a lasting
nish.
2. As a Special Gas Vent system: Saf-T Vent is approved for use on ANSI Category I, II, III, and IV Gas-Burning Appliances and certain Direct Vent Appliances. Saf-T Vent SC is appropriate for use on appliances that specify an AL29-4C venting system.
As a Sealed Combustion system: The unique
3. concentric design of Saf-T Vent SC also allows it to function as a pipe-in-a-pipe vent. Products of combustion are exhausted out through the inner wall while combustion air is drawn in through the outer wall. An appliance can be direct-vented with only a single penetration through the building structure.
This application must be approved by the Appliance Manufacturer.
Note: Saf-T Vent SC includes an integral seal and
does not require RTV sealant. However, sealant may be necessary when connecting Saf-T Vent SC
components directly to certain appliance ue collars
and to the gasket-less Saf-T Vent GC and Saf-T Vent CI vent systems.
For applications up to 550°F/288°C, approved
sealants include GE RTV 106 and Dow Corning
736.
For applications up to 300°F/149°C, approved
sealants include GE RTV 106 and Dow Corning
732.
4. Pre-Installation Considerations:
• Proper planning prior to installation is essential
as to avoid possible contact with concealed plumbing or electrical wiring inside walls,
oors or ceilings as well as maintaining proper clearances. Be sure to plan a sufcient number
of supports for the entire system that will maintain the required straight-line pitch and hold
the system in place. A continuous straight-line pitch of at least ¼” (2°) to the foot on horizontal runs must be maintained in order to properly rid the system of the corrosive condensate.
5. General Installation Requirements:
• Saf-T Vent SC vent sections, or other Saf-T
Vent products, must be used throughout the entire length of the system. Alternatives such as galvanized pipe, PVC, nonmetallic pipe,
prefabricated chimney, eld-fabricated vents
or Type B vent sections must not be used. Do
not mix pipes, ttings, or joining methods from
different manufacturers.
• More than one appliance may not be interconnected to any part of the venting system.
• Any penetrations of ceilings, oors or walls must be properly re-stopped.
• Whenever gas-burning equipment is installed in the same space where halogenated substances may exist (refrigerants, solvents, bleaches, salts, etc.), clean outside air must be utilized for combustion.
• The vent system shall not be routed into, through or within any other actively used vent or chimney.
• Seal weather exposed joints of the outer jacket with foil tape or an exterior grade silicone sealant.
• Combustible Material is any material made of or surfaced with wood, compressed paper, plant
bers, or other materials that are capable of
being ignited or burned. Such material shall be
considered combustible even though it is ame­proofed, re-retardant, or plastered. (Source:
NFPA54/ANSI Z223.1-1999.)
• Non-Combustible Material is any material that is not capable of being ignited and burned, such material consisting entirely of, or a combination of, steel, iron, brick, tile, concrete, slate, asbestos, glass and plaster. (Source: NFPA54/ ANSI Z223.1-1999.)
CLEARANCES TO COMBUSTIBLES:
Clearance to
Diameter
Combustible
Material
0”
3” - 4”
1” 400 0” 400 1” 550 0” 550 Any Noncombustible material
28
Maximum Flue
Gas Temp. (°F)
550
Orientation Enclosure
Vertical, No
Offsets
Horizontal,
Vertical with
Offsets
Fully enclosed by combustible material on all sides330
Unenclosed, at least 1 side open, combustible material on a maximum of 3 sides
Page 29
• For a venting system that extends through any zone above that on which the connected appliance is located (except for one and two family dwellings), the vent system shall be
enclosed with an enclosure having a re
resistance rating equal to or greater than that of
the oor or roof assemblies through which it
passes.
• Design any enclosure to permit inspection of the system.
• Do not place any type of insulation in any required clearance spaces surrounding the vent system.
6.
Vertical Installation Requirements: a. Seal weather exposed joints of the outer jacket
with foil tape or an exterior grade silicone sealant.
b. The vent system must terminate at least 3 feet
above the roof line and at least 2 feet higher than any portion of the building within 10 feet.
c. When terminated at a height of more than 6 feet
the stack must be supported by a support bracing. The vent should be supported every 10 feet.
d. The total continuous distance of the vent system
from the appliance ue collar to the termination shall not exceed that specied in the appliance
manufacturer’s installation instructions.
e. In cold climates do not install a condensate drain
on the exterior of the building. Doing so may result in dangerous icy conditions on surfaces near the drain and may cause damage to the vent system and/or the building exterior.
f. Install supports every 10 feet vertically along the
vent pipe route. Vertical supports are required after every transition to vertical and are required after every offset elbow. When the vent is free standing and penetrates a roof/ceiling another means of support must be used at a second location. Refer to the Vertical Supports section in this manual.
29
Page 30
7. Joint Assembly Instructions:
a. Before joining the sections or ttings together, use an alcohol pad to wipe the joint area of both ends of the inner
pipe. This will remove any foreign matter which may affect the integrity of the seal. Install the system with the
female ends (ends with the red seal) pointing away from the appliance. (Unless specied differently by the appliance
manufacturer.)
b. Insert the male end of the inner pipe into the female end of the previous section. In extremely dry conditions it may be
helpful to moisten the seal with clean water prior to assembly. Push rmly until the outer jacket has made contact with
the snap ring located inside the female end of the previous section. When fully assembled the outer female end will overlap the male end 1”.
c. Use the three (3) self-tapping screws provided to connect the outer vents. No pre-drilling is required.
NOTICE
Do not overtighten. If using a variable torque drill, use a low torque setting to install screws, as not to strip out the holes. If a hole becomes stripped due to overtightening, a larger diameter screw (½” long max.) or short pot rivet can be used.
30
Page 31
8. Straight Sections Cut To Length: If a custom length of SC is necessary, a standard vent
section can be cut. a. Measure the distance of the length needed, taking the
measurement from the end of one of the outer jackets to the beginning of the other outer jacket on the section to connect to, (A to B on diagram).
b. Select a section that is longer than the required
length.
c. It will be necessary to disassemble the vent prior to
cutting.
Stand the section on end with the holes up. Find the
end of snap ring and pry it out of its groove, being careful not to damage the ends of the vent pipes. Pull up on end of the snap ring and pull it out from the end of the pipe. It may want to spiral out as it is removed. After the snap ring is removed, the inner vent pipe can be separated from the outer jacket.
d. Add
An effective way of marking is to run a length of tape
2” to the distance measured previously for the
cut length of the outer jacket. Mark a cut line on the outer jacket on the male end (the end without holes in it).
around the section, assuring a square cut.
e. Add
The inner pipe is always cut 1” longer than the
f.
g. Reassemble the inner vent into the outer jacket and
3” to the distance measured previously for the
cut length of the inner vent pipe. Mark a cut line on the inner vent on the male end (the end without the red seal).
outer pipe.
WEAR GLOVES, as cut ends are very sharp. Cut the pipes with an abrasive cutoff saw, plasma cutter, or compound snips. If using snips, start the cut at the male end and follow a spiral path around the pipe until the cutoff mark is reached. File off any burrs or rough edges that develop in the cutting process and clean off any dust or grit. If the cutting process distorts the roundness of the pipes, carefully use your thumbs to re-round the ends.
reinstall the snap ring into the groove. Push the inner vent into the outer jacket until the triangle on
the inner vent is seated rmly against the bead on
outer jacket. Start one end of the snap ring into the groove of the outer pipe. Slowly turn and feet the snap ring into the groove in a spiral motion, and continue around the pipe until the snap ring is fully inserted. Ensure that the triangle on the inner vent is all the way down against the bead of the outer jacket
by pushing in rmly. Also ensure that the snap ring
is completely in the groove all the way around outer jacket.
31
Page 32
9. Air Intake Connections for Direct Vent and Sealed Combustion Appliances*:
The Air Intake Tee may be used on approved direct vent
and sealed combustion appliances that have separate (non-
concentric) air intake and ue exhaust collars. The male end
of the tee connects to EZ Seal appliance adapters and the tee takeoff/snout connects to the appliance air intake.
• Insert the male end of the Air Intake Tee into the female
end of the EZ Seal vent section or appliance adapter and complete the ring and tab connection.
• Insert the male end of the next SC section into the
female end of the Air Intake Tee and secure as described elsewhere in this manual.
• Connect the tee takeoff to the appliance combustion air
inlet using appropriate hose or pipe.
* Direct Vent Appliances are constructed and installed so that
all air for combustion is supplied directly from the outside atmosphere. The passage for the combustion air is allowed a small amount of leakage in the building environment. No special installation considerations are required to use Saf-T
Vent SC on Direct Vent appliances unless specied by the
appliance manufacturer. Sealed Combustion appliances are similar to Direct Vent except the combustion air passage must be sealed to prevent leakage within the building envelope. When Saf-T Vent SC is used on approved Sealed Combustion appliances the joints of the outer jacket must be sealed with a foil tape (example: 3M 425), or approved silicone sealant (example: Dow Corning 732).
Condensate Drains:
10.
When An Internal Condensate Drain is NOT Part of the
Appliance:
• A Saf-T Vent SC In-Line Drain Section is strongly
recommended. Install this drain tting as close to the appliance ue collar as possible.
• A condensate drain is required for every 30 feet of
horizontal vent and at/near the bottom of a vertical stack.
• Use the In-Line Drain Section for a straight horizontal or
vertical run. When used horizontally, rotate the tting so that
the drain tube is as vertical as possible.
• A Condensate Drain Tube Kit is available to direct the condensate
to an appropriate location, i.e. oor drain or vented sanitary
sewer connection. A trap loop must be formed into the drain hose and must be a diameter that is at least four (4) times the appliance’s rated stack pressure in inches of water column or 3 inches, whichever is greater. Secure the loop with a cable tie.
Prior to nal assembly the trap loop must be ‘primed’ by pouring
a small quantity of water into the drain hose. Inspect at least
annually to verify the trap is ‘primed’.
• Follow all local and national codes and regulations for the
draining of acidic condensate.
• In cold climates do not install a condensate drain on the exterior
of the building. Doing so may result in dangerous icy conditions on surfaces near the drain and may cause damage to the vent system and/or the building exterior.
32
Page 33
11. Horizontal Supports: Saf-T Vent SC must have supports for every six (6) feet of horizontal run and after every transition from vertical to
horizontal. Support hangers by themselves do not maintain the necessary clearances to combustible materials; be sure to consider clearances when planning the system.
The supports must be secured to solid material using at least #10 fasteners. Do not fasten supports to drywall sheathing
without using hollow wall anchors. The conduit supports must maintain the ¼” per foot pitch to avoid collection of condensate in the vent. Position the vent so that the welded seam is on the top.
0” Clearance Support Clamp, (SC_ _SUP): Attach the bracket to the structure but do not tighten in place. Open the
hose clamp and slip it under the support bracket. Position the clamp between the mounting screws and rotate the clamp so that the screw housing will be accessible after the vent is installed. Restart the threads on the hose clamp and securely tighten the mounting screws to the structure. This can also be installed vertically.
1” Clearance Support Clamp, (SC_ _SUP1): Supports the vent at 1” clearance to the structure. Line up the support
mounting brackets so that the mounting screws will follow the center line of the vent section. This can also be installed vertically.
33
Page 34
Support Clamp, (4_ _27SS): Support clamps are sold in pairs and can be clamped around the vent and suspended from a
rod or cable. They can be used singularly as a saddle clamp to rest the vent in and suspended from two (2) rods or cables.
Support Legs Rotated Horizontally: Support legs can be used on horizontal runs by rotating the clamp at the rivet
connection. The legs can be cut to shorter lengths if necessary.
Vertical Supports, (SC_ _VSL): Vertical support legs can be used above or below a structure for support. To install,
slide the support clamp over the end of the vent section, leaving the clamp loose. Position the support legs and install two (2) screws through each leg into the structure. Tighten the clamp around vent pipe. The legs can be cut to shorter lengths if necessary and can rotate around the support clamp at the rivet connection. By rotating the clamp to a horizontal position the support legs can be used on horizontal runs.
34
Page 35
Fire Stop/Wall Thimble/Support, (SC_ _FS):
• The Saf-T Vent SC Fire Stop can be used as a restop, a wall thimble, or as a support plate.
• To use as a Wall Thimble prepare an opening according to the chart below. Remove any insulation from the opening, using additional framing if necessary. Attach the plate over the center of the opening using appropriate fasteners.
• Install the vent section through the thimble plate and secure the section to the thimble by screwing the self-tapping screws through the holes in the tabs on the plate and into the outer wall of the vent. Apply silicone sealant around the vent section where it passes through the plate and around the plate where it is attached to the structure.
• To use as a Firestop before passing through ceilings or enclosed chases, prepare a round or square opening ¼” larger than
the outer jacket (5¼” for 3” vent or 7¼” for 4” vent). Remove any insulation from the opening. Secure the restop to the structure at the four (4) corners. Install the vent section through the restop and secure to the thimble by screwing the
self-tapping screws through the holes in the tabs on plate and into outer wall of the vent. This method can also be used to support the vent section either vertically or horizontally.
Tall Cone Flashing:
Directly On Roof or Curb: Tall Cones are available for at (SC_ _TCF), 2/12 pitch (SC_ _TCFA), and 6/12 - 12/12 pitch roofs (SC_ _TCFB).
Prepare a square or round opening at least 1/4” larger than the outer jacket (5¼” for 3” vent or 7¼” for 4” vent). Remove any insulation from the opening. Apply weather-stripping or outdoor caulk to the bottom of the cone plate and attach the plate to the roof using common construction methods. Flash over the cone plate and seal the fastener heads using normal
roong requirements. When the vent pipe is in place through the Tall Cone, attach a storm collar (sold separately) around
the pipe. Apply high temperature silicone sealant around the pipe where it passes through the top of the storm collar. Continue to install vent sections as needed to meet the height requirements by code. Seal weather exposed joints of the
outer jacket with foil tape or an exterior grade silicone sealant.
35
Page 36
Vertical Terminations, (SC_ _VT): Install the vertical termination adapter into the last vent section and secure with the
three (3) self-tapping screws provided. If the exhaust termination needs to be extended, a section of EZ Seal vent can be connected directly to the vertical termination adapter. Seal weather exposed joints of the outer jacket with foil tape or an exterior grade silicone sealant. To allow for inspection of the system, do not seal the exhaust termination.
36
Page 37
H. Indoor Air Installation – See Figures 12, 13, 14, 15 and 16.
1. Do not exceed maximum vent length. Refer to Table 4.
Horizontal
2. Maintain minimum ¼ inch per foot slope in horizontal runs. Position weld seams in vent pipes, in all horizontal runs, at the top to avoid condensate from lying on the seams.
3 Recommended horizontal installation consists of
vent being sloped down away from boiler. See Figure 12.
4. Alternate horizontal installation consists of vent being sloped down toward the boiler. A horizontal vent tee is required. See Figure 13.
5. Use appropriately designed thimbles when passing through combustible walls (thimble use optional for noncombustible walls). Insert thimble through
wall from outside. Secure outside ange to wall
with nails or screws, and seal with sealant material.
Install inside ange to inside wall, secure with nails
or screws, and seal with sealant material.
6. For noncombustible wall application when thimble is not used, size opening such that female (bell) end with locking band attached cannot pass through.
7. Join vent terminal to vent pipe. Locate vent terminal between seventeen (17) inches and twenty­nine (29) inches from wall when joined to inside vent piping. See Figure 14.
8. Insert vent pipe through thimble/opening from outside and join to vent system. Apply sealant between vent pipe and opening/thimble to provide weathertight seal.
Vertical
10. Installation of a vertical vent drain tee is required on all vertical vent applications. See Figure 6. Attach vertical vent drain tee directly to elbow or horizontal pipe from an elbow immediately after vent connector.
11. Install re stops where vent passes through oors, ceilings or framed walls. The re stop must close
the opening between the vent pipe and the structure. Fire stop manufacturers are Air-Jet, American Metal Products, Metal-Fab, and Simpson Dura-Vent.
12. Whenever possible install vent straight through roof. Refer to Figure 6. Maintain minimum clearance to combustible materials. For attic offset see Figure 7.
13. Install Vent Terminal. a. Size roof opening to maintain minimum
clearance from combustible materials.
b. Use appropriately designed vent ashing
when passing through roofs. Follow ashing
manufacturers’ instructions for installation procedures. Flashing manufacturers are Air­Jet, American Metal Products, Metal Fab, and Simpson Dura-Vent.
c. Extend vent pipe to maintain minimum vertical
and horizontal distance of twelve (12) inches from roof surface. Allow additional vertical distance for expected snow accumulation. Provide brace as required. Refer to Figure 15.
d. Vertical venting requires ashing and a storm
collar to prevent moisture from entering the structure.
e. Install storm collar on vent pipe immediately
above ashing. Apply Dow Corning Silastic 732
RTV Sealant between vent pipe and storm collar to provide weathertight seal.
f. Attach vent terminal.
Vent Terminal and Air Intake Terminal
14. Join vent terminal to 45° elbow (supplied by installer). Join 45° elbow/terminal assembly to vent pipe. Refer to Section C for proper procedures for
joining vent pipe and ttings. See Figure 3.
15. Install supplied air intake terminal. See Figure 16.
37
Page 38
38
Figure 12: Recommended Separate Horizontal - Vent Installation
Page 39
Figure 13: Alternate Separate Horizontal - Vent Installation
39
Page 40
Figure 14: Optional Indoor Air - Vent Terminal Installation
Figure 15: Indoor Air - Vertical Vent Terminal Installation
Extend Vent/Air Intake Piping to maintain minimum vertical (“X”) and minimum horizontal (“Y”) distance of twelve (12) inches from roof surface. Allow additional vertical (“X”) distance for expected snow accumulation.
40
Figure 16: Indoor Air - Air Intake Terminal Installation
Page 41
I. Optional Exterior Separate Horizontal Vent/Air Intake Terminal Mounting – See Figures 17, 18, 19, 20, 21 and 22.
1. Do not exceed maximum vent/air intake lengths. Refer to Table 4.
2. This installation will allow a maximum of seven (7) feet vertical exterior run of the vent/air intake piping to be installed on separate horizontal venting and indoor air horizontal venting.
NOTICE
Exterior run to be included in equivalent vent/air
intake lengths.
3. Install vent piping.
a. Install vent piping for desired venting system.
Refer to specic section for details for vent pipe
installation.
b. After penetrating wall/thimble, install an
AL 29-4C® 90° elbow so that elbow leg is in the up direction.
c. Install maximum of seven (7) feet of AL 29-4C
vent pipe. Refer to Sections C through E for proper
procedures for joining vent pipe and ttings.
d. At top of vent pipe length install an AL 29-4C
90° elbow so that elbow leg is opposite the building’s exterior surface.
e. If installation requires indoor air, install
AL 29-4C® 45° elbow to upper AL 29-4C® 90° elbow so that leg of 45° is in down direction (see Figure 21 or 22). If not using indoor air, proceed to Step f.
f. Install horizontal vent terminal (provided with
boiler).
g. Brace piping if required.
®
4. Air Intake Piping (not required for indoor air).
a. Install air intake piping for desired venting
system. Refer to specic section for details for
air intake installation.
b. After penetrating wall, install a corrosion
resistant 90o elbow so that elbow leg is in the up
®
direction.
c. Install maximum of seven (7) feet of corrosion
resistant air intake pipe.
d. At top of air intake pipe install air intake
terminal (provided with boiler).
e. Brace piping if required.
Figure 17: Optional Separate Horizontal Air 3” or 4” Intake Terminal Installation
41
Page 42
Figure 18: Optional Separate Horizontal Air 5” Intake Terminal Installation
42
Figure 19: Optional Separate Horizontal 3” Vent Terminal Installation
Page 43
Figure 20: Optional Separate Horizontal 4” Vent Terminal Installation
Figure 21: Optional Separate Horizontal 3” Vent Terminal Installation (Indoor Air)
43
Page 44
Figure 22: Optional Separate Horizontal 4” Vent Terminal Installation (Indoor Air)
44
Page 45
IV. Water Piping and Trim
WARNING
Failure to properly pipe boiler may result in improper operation and damage to boiler or structure.
Oxygen contamination of boiler water will cause corrosion of iron and steel boiler components, and can lead to boiler failure. Burnham’s Standard Warranty does not cover problems caused by oxygen
contamination of boiler water or scale (lime) build-up caused by frequent addition of water.
A. Design and install boiler and system piping to
prevent oxygen contamination of boiler water and frequent water additions.
1. There are many possible causes of oxygen contamination such as:
a. Addition of excessive make-up water as a result
of system leaks.
b. Absorption through open tanks and ttings.
c. Oxygen permeable materials in the distribution
system.
2. In order to insure long product life, oxygen sources must be eliminated. This can be accomplished by taking the following measures:
a. Repairing system leaks to eliminate the need for
addition of make-up water.
b. Eliminating open tanks from the system.
c. Eliminating and/or repairing ttings which allow
oxygen absorption.
d. Use of non-permeable materials in the
distribution system.
e. Isolating the boiler from the system water by
installing a heat exchanger.
f. Use properly designed and operating air
elimination devices in water piping.
B. Low Water Cut Off (LWCO) on Hot Water Boilers
(Optional)
Where
The universal location for a LWCO on both gas and oil
hot water boilers is above the boiler, in either the supply or return piping. The minimum safe water level of a water boiler is at the uppermost top of the boiler; that is, it must be full of water to operate safely.
What Kind
The SCG boiler is designed to accept the wiring of the
Safgard Model 1100-H4 (P/N 100592-01) LWCO. This is a probe type LWCO. The factory wiring is designed to allow simple “Plug-in” installation of the wiring.
How to Pipe
A “tee” is commonly used to connect the probe LWCO
to the supply or return piping, as shown below.
WARNING
DO NOT ATTEMPT to cut factory wires to install an aftermarket Low Water Cut Off
(LWCO). Only use connections specically identied for Low Water Cut Off.
In all cases, follow the Low Water Cut Off (LWCO) manufacturer’s instructions.
When
A low water cutoff is required to protect a hot water
boiler when any connected heat distributor (radiation) is installed below the top of the hot water boiler (i.e.
baseboard on the same oor level as the boiler). In
addition, some jurisdictions require the use of a LWCO with a hot water boiler.
LWCO Location
Select the appropriate size tee using the LWCO
manufacturer’s instructions. Often, the branch connection must have a minimum diameter to prevent bridging between the probe and the tee. Also, the run of the tee must have a minimum diameter to prevent the end of the probe from touching or being located too close to the inside wall of the run of the tee.
Ideally, manual shutoff valves should be located
above the LWCO and the boiler to allow for servicing. This will allow probe removal for inspection without draining the heating system. Many probe LWCO manufacturers recommend an annual inspection of the probe.
45
Page 46
How to Wire
Ensure power is turned off to boiler. Locate the LWCO jumper wire in the factory wiring
harness. Remove the jumper wire and install the LWCO wiring from LWCO Model 1100-H4 (P/N 100592-01) into the plug of the SCG factory wiring.
How to Test
Shut off fuel supply. Lower water level until water
level is BELOW the LWCO. Generate a boiler demand by turning up thermostat. Boiler should not attempt to
operate. Increase the water level by lling the system.
The boiler should attempt to operate once the water level is above the LWCO.
NOTICE
Ensure the location of the LWCO in the piping will allow for connection of the LWCO wiring harness to the factory wiring of the SCG.
C. Connect system supply and return piping to boiler.
See Figures 25 and 26. Maintain minimum ½ inch clearance from hot water piping to combustible materials.
WARNING
Pressure relief valve discharge piping must be piped such that the potential of severe burns is eliminated. DO NOT pipe in any area where freezing could occur. DO NOT install any shut-off valves, plugs or caps. Consult Local Codes for proper discharge piping arrangement.
F. Space heating and domestic water heating with
Alliance™ water heater. Install Alliance water heater as a separate heating zone. Refer to Alliance Installation, Operating and Service Instructions for additional information.
G. If boiler is used in connection with refrigeration
systems, boiler must be installed with chilled medium
piped in parallel with the heating boiler using appropriate valves to prevent chilled medium from entering boiler, see Figure 23.
NOTICE
Burnham recommends sizing the system
circulator to supply sufcient ow (GPM) to allow a
20°F temperature differential in the system. When sizing the system circulator, the pressure drop of all radiators, baseboard and radiant tubing and all connecting piping must be considered.
D. Install circulator with anges, gaskets and bolts
provided. Circulator harness allows circulator to be mounted on supply or return. Connect harness to circulator and secure any excess conduit.
E. Install supply manifold, pressure/temperature gauge
and pressure relief valve.
See Figure 24. Pressure Relief Valve must be installed
with spindle in vertical position. Installation of the relief valve must comply with the ASME Boiler and Pressure Vessel Code, Section IV.
Figure 23: Recommended Piping for Combination
Heating & Cooling (Refrigeration) System
H. If boiler is connected to heating coils located in
air handling units where they may be exposed to refrigerated air, boiler piping must be equipped with
ow control valves to prevent gravity circulation of
boiler water during operation of cooling system.
I. Use a boiler bypass if the boiler is to be operated
in a system which has a large volume or excessive radiation where low boiler water temperatures may be encountered (i.e. converted gravity circulation system, etc.).
46
Page 47
Figure 24: Supply Water Manifold Piping
Install pipe tee between circulator and boiler return
along with second tee in supply piping as shown in Figure 25 or 26. Bypass should be same size as the supply and return lines with valves located in bypass and supply outlet as illustrated in Figure 25 or 26 in
order to regulate water ow to maintain higher boiler
water temperatures.
After the boiler is operational (reference Section VIII.
System Start-Up) set by-pass and boiler supply valves to half throttle position to start. Operate boiler until system water temperature reaches normal operating range.
Adjust valves to provide 180° to 200°F supply water
temperature. Opening the boiler supply valve will raise system temperature, while opening the by-pass valve will lower system supply temperature.
J. A hot water boiler installed above radiation level
must be provided with a low water cutoff device as part of installation.
K. If a low water cutoff is required, it must be mounted
in the system piping above the boiler. The minimum safe water level of a hot water boiler is just above the highest water containing cavity of the boiler; that is, a hot water boiler must be full of water to operate safely.
L. Oil, grease, and other foreign materials which
accumulate in new hot water boilers and a new or reworked system should be boiled out, and
then thoroughly ushed. A local qualied water
treatment chemical specialist is a suggested source for recommendations regarding appropriate chemical compounds and concentrations which are compatible with local environmental regulations.
M. After the boiler and system have been cleaned and
ushed, and before relling the entire system add
appropriate water treatment chemicals, if necessary, to bring the pH between 7 and 11.
N. If it is required to perform a long term pressure
test of the hydronic system, the boiler should rst be
isolated to avoid a pressure loss due to the escape of air trapped in the boiler.
To perform a long term pressure test including the
boiler, ALL trapped air must rst be removed from the
boiler.
A loss of pressure during such a test, with no visible
water leakage, is an indication that the boiler contained trapped air.
47
Page 48
48
Figure 25: Recommended Water Piping for Circulator Zoned Heating Systems
Page 49
Figure 26: Recommended Water Piping for Zone Valve Zoned Heating Systems
49
Page 50
V. Gas Piping
WARNING
Failure to properly pipe gas supply to boiler may result in improper operation and damage to the boiler or structure. Always assure gas piping is absolutely leak free and of the proper size and type for the connected load.
An additional gas pressure regulator may be needed. Consult gas supplier.
A. Size gas piping. Design system to provide adequate gas
supply to boiler. Consider these factors:
1. Allowable pressure drop from point of delivery to boiler. Maximum allowable system pressure is ½ psig. Actual point of delivery pressure may be less; contact gas supplier for additional information. Minimum gas valve inlet pressure is stamped on the rating label located in the boiler’s vestibule compartment.
2. Maximum gas demand. Refer to the boiler’s input as printed on it’s rating label. Also consider existing and expected future gas utilization equipment (i.e. water heater, cooking equipment).
3. Length of piping and number of ttings. Refer to
Table 7 for maximum capacity of Schedule 40 pipe. Table 8 lists equivalent pipe length for standard
ttings.
4. Corrections for the specic gravity of natural gas
can be found in Table 6.
For materials or conditions other than those listed
above, refer to National Fuel Gas Code, NFPA54/ANSI Z223.1, or size system using standard engineering methods acceptable to authority having jurisdiction.
TABLE 6: SPECIFIC GRAVITY CORRECTION FACTORS FOR NATURAL GAS
Specic
Gravity
--- --- 0.85 0.81
--- --- 0.90 0.82
0.60 1.00 1.00 0.78
0.65 0.96 1.10 0.74
0.70 0.93 1.20 0.71
0.75 0.90 1.30 0.68
0.80 0.87 1.40 0.66
Correction
Factor
Specic
Gravity
Correction
Factor
TABLE 5: GAS RATINGS
Boiler Model
Number
SCG-3 SCG-4
SCG-5
SCG-6
SCG-7
SCG-8
SCG-9
Natural/LP
Maximum
Gas Pressure
(in. w.c.)
14 4.5 11.5 3.5 10.5
Minimum Natural
Gas Pressure
(in. w.c.)
Inlet to Gas Valve
Minimum LP
Gas Pressure
(in. w.c.)
Inlet to Gas Valve
Natural
Manifold
Pressure
(in. w.c.)
LP
Manifold
Pressure
(in. w.c.)
NOTICE
SCG boilers built for altitudes greater than 4,999 feet above sea level need to be specially oriced to adjust for changes in atmospheric conditions. The SCG boiler “H” Model has been certied to operate in atmospheric
conditions from 5,000 to 10,000 feet above sea level. Input is de-rated by 10% for applications at 5,000 feet above sea level, and 20% for applications at 10,000 feet above sea levels. De-rate is based on 2% reduction per 1000 feet.
The SCG boiler is available in two (2) altitude Models: The “S” Model 0 to 4,999 feet above sea level, and the “H” Model 5,000 to 10,000 feet above sea level.
For applications above 10,000 feet, consult the manufacturer.
50
Page 51
TABLE 7: MAXIMUM CAPACITY OF SCHEDULE 40 PIPE IN CFH* FOR NATURAL GAS PRESSURES OF 0.5 PSIG OR LESS
Length
[Feet]
10 132 278 520 1,050 175 360 680 1,400 20 92 190 350 730 120 250 465 950 30 73 152 285 590 97 200 375 770 40 63 130 245 500 82 170 320 660 50 56 115 215 440 73 151 285 580 60 50 105 195 400 66 138 260 530 70 46 96 180 370 61 125 240 490 80 43 90 170 350 57 118 220 460 90 40 84 160 320 53 110 205 430
100 38 79 150 305 50 103 195 400
0.3 Inch w.c. Pressure Drop 0.5 Inch w.c. Pressure Drop
½ ¾ 1 ½ ¾ 1
* 1 CFH of Natural Gas is approximately equal to 1 MBH; 1 CFH of LP is approximately equal to 2.5 MBH; con­tact your gas supplier for the actual heating value of your gas.
B. Connect boiler gas valve to gas supply system.
WARNING
Failure to use proper thread compounds on all
gas connectors may result in leaks of ammable
gas.
WARNING
Gas supply to boiler and system must be absolutely shut off prior to installing or servicing boiler gas piping.
1. Use methods and materials in accordance with local plumbing codes and requirements of gas supplier. In absence of such requirements, follow National Fuel Gas Code, NFPA 54/ANSI Z223.1.
2. Use thread (joint) compounds (pipe dope) resistant
to action of liqueed petroleum gas.
3. Install sediment trap, ground-joint union and manual shut-off valve upstream of boiler gas control valve and outside jacket. See Figure 27.
Figure 27: Recommended Gas Piping
TABLE 8: EQUIVALENT LENGTHS OF STANDARD PIPE FITTINGS & VALVES
VALVES FULLY OPEN
Pipe Size
½” 06.22 0.35 18.6 9.3 4.3 1.6 0.78 1.0 3.1 ¾” 0.824 0.44 23.1 11.5 5.3 2.1 0.97 1.4 4.1
1” 1.049 0.56 29.4 14.7 6.8 2.6 1.23 1.8 5.3
1¼” 1.380 0.74 38.6 19.3 8.9 3.5 1.60 2.3 6.9
I.D.
Inches
Gate Globe Angle
Swing
Check
90°
Elbow
45°
Elbow
90° Tee, Flow
Through Run
90° Tee, Flow
Through Branch
51
Page 52
4. All above ground gas piping upstream from manual shut-off valve must be electrically continuous and bonded to a grounding electrode. Do not use gas piping as grounding electrode. Refer to National Electrical Code, NFPA 70.
C. Pressure test. The boiler and its gas connection must
be leak tested before placing boiler in operation.
1. Protect boiler gas control valve. For all testing over ½ psig, boiler and its individual shutoff valve must be disconnected from gas supply piping. For testing at ½ psig or less, isolate boiler from gas supply
piping by closing boiler’s individual manual shutoff valve.
2. Locate leaks using approved combustible gas
detector, soap and water, or similar nonammable
solution.
DANGER
Do not use matches, candles, open ames or
other ignition source to check for leaks.
52
Page 53
VI. Electrical
DANGER
Positively assure all electrical connections are unpowered before attempting installation or service of electrical components or connections of the boiler or building. Lock out all electrical boxes with padlock once power is turned off.
WARNING
Failure to properly wire electrical connections to the boiler may result in serious physical harm. Electrical power may be from more than one source. Make sure all power is off before attempting any
electrical work. Each boiler must be protected with a properly sized over-current device.
Never jump out or make inoperative any safety or operating controls. The wiring diagrams contained in this manual are for reference purposes only. Each boiler is shipped with
a wiring diagram attached to the front door. Refer to this diagram and the wiring diagram of any controls used with the boiler. Read, understand and follow all wiring instructions supplied with the controls.
A. General. Install wiring and electrically ground boiler
in accordance with authority having jurisdiction or, in the absence of such requirements, follow the National Electrical Code, NFPA 70, and/or CSA C22.1 Electrical
Code.
B. A separate electrical circuit must be run from
the main electrical service with an over-current device/disconnect in the circuit. A service switch is recommended and may be required by some local jurisdictions. Install the service switch in the line voltage “Hot” leg of the power supply. Locate the
service switch such that the boiler can be shut-off without exposing personnel to danger in the event of an emergency. Connect the main power supply and ground to the three (3) boiler wires (black, white and green) located in the junction box at the inside top of the boiler jacket. If a low water cutoff is to be used, connect the low water cutoff so that all 120V power to boiler is interrupted if the low water cutoff’s switch opens.
C. Refer to Figures 28 and 29 for details on the internal
boiler wiring.
NOTICE
This boiler is equipped with a high water temperature limit located inside the internal wiring of the boiler.
This limit provides boiler shutdown in the event the boiler water temperature exceeds the set point of the
limit control. Certain Local Codes require an additional water temperature limit. In addition, certain types
of systems may operate at temperatures below the minimum set point of the limit contained in the boiler.
If this occurs, install an additional water temperature limit (Honeywell L4006 Aquastat) located in the system
piping as shown in the Water Piping and Trim Section of this manual. Wire as indicated in the Electrical Section of this manual.
NOTICE
All wire, wire nuts, controls etc. are installer supplied unless otherwise noted.
53
Page 54
54
Figure 28: Internal Boiler Wiring Schematic Diagram
Page 55
NOTICE
If an additional system limit is used, install in series with the auxiliary limit jumper shown in the drawing below.
Figure 29: Internal Boiler Wiring Ladder Diagram
55
Page 56
D. System Controls and Wiring
1. Refer to National Electric Code or Local Electric Codes for proper size and type of wire required. Follow Code.
2. Use anti-short bushings on all wiring passing through boiler jacket, junction boxes and/or control boxes.
3. Use armored cable (BX) over all exposed line voltage wiring.
4. If an Alliance™ indirect water heater is used, use priority zoning except for Hydro-Air Systems. Single Zone Heating System – Refer to Figure 30 of this manual for the electrical diagram for this type of system.
5.
Set the thermostat heat anticipator to 0.60 amps.
Single Zone Heating System with Alliance™ Water Heater - Refer to Figure 31 of this manual for the electrical diagram
6.
for this type of system.
Set the thermostat heat anticipator to 0.60 amps.
7. Conventional Circulator Zoned System – Refer to Figure 32 of this manual for the electrical diagram for this type of
system. Read, understand and follow all of the instructions provided with the Honeywell R8888 control. Connect the thermostat of each zone and the circulator for that zone to R8888 panel. If an Alliance™ indirect water
heater is used, connect the Alliance™ thermostat and circulator to the Zone 1 terminals of the R8888. Set the thermostat heat anticipator to 0.12 amps.
NOTICE
The Honeywell R8888 Control is available in a three (3) zone Model (R8888A) and a four (4) zone Model (R8888B). Up to four (4) R8888’s may be used together to provide control for up to twelve (12) individual
zones. Only one (1) zone, the rst zone of the main control, will provide priority circulation. If more than four (4) zones are required, connect additional R8888’s by wiring the A, B, and C terminals of each control together. Each R8888 requires a 120 volt power supply. If more than one (1) R8888 is used, set the panel type switch to “main” on the rst R8888 and set the panel type switch to “expansion” on the second, third
or fourth R8888.
Conventional Zone Valve Zoned System – Refer to Figure 33. Wiring to the most popular models of zone valves is given
8.
in Figure 34. Connect the thermostat of each zone and the zone valve for that zone to the R8889 control. If an Alliance™ indirect water
heater is used, connect the Alliance™ thermostat and zone valve to the “zone 1” terminals of the R8889. Set the thermostat heat anticipator to 0.12 amps.
NOTICE
The Honeywell R8889 Control is available in two three (3) zone models and two four (4) zone models. Burnham recommends using Model R8889A for three (3) zone systems and Model R8889B for four (4) zone systems. Models R8889C and R8889D have less load capacity and may not operate with certain types of zone valves. Up to four (4) R8889’s may be used together to provide up to sixteen (16) individual zones.
Only one (1) zone, the rst zone of the main control will provide priority zoning for the Alliance indirect water heater. If more than four (4) zones are required, connect additional R8889’s by wiring the A, B and C terminals of each control together. Each R8889 requires a 120 volt power supply. If more than one (1) R8889 is used, set the panel type switch to “main” on the rst R8889 and set the panel type switch to
“expansion” on the second, third or fourth R8889.
56
Page 57
Figure 30: System Wiring Schematic for Single Zone Space Heating Only
57
Page 58
NOTICE
If an additional system limit is used, install in series with the auxiliary limit jumper shown in the drawing below.
58
Figure 31: Single Zone System with Packaged Alliance™ Water Heater Wiring Schematic
Page 59
Figure 32: Circulator Zoned System Wiring Schematic
59
Page 60
60
Figure 33: Zone Valve Zoned System Wiring Schematic
Page 61
Figure 34: Different Manufacturer’s Zone Valve Connections to Honeywell R8889
61
Page 62
VII. Modular Installation
A. General Guidelines
1. Read and follow all venting, combustion air, water piping, gas piping and electrical instructions contained in this manual unless otherwise instructed in this section.
2. Consult Local Building Codes or National Fuel Gas Code, NFPA 54/ANSI Z222.3 for restrictions and instructions on modular boiler installations.
B. Module Sizing
Burnham recommends sizing each boiler in a modular
system to provide 20 % of the combined heating load where ever possible.
C. Venting
1. Each boiler must have an individual vent pipe. Refer to Venting Section of this manual for venting guidelines and options.
WARNING
Do not manifold vent pipes together.
2. The maximum vent length for each boiler is fty
(50) equivalent feet.
3. The minimum horizontal distance between vent terminations is one (1) foot. Additional horizontal distance is desirable to avoid frost damage to the building. Vent terminations must be at least twelve (12) inches above the ground plus the expected snow accumulation.
CAUTION
Installing multiple vent terminations close together promotes frost buildup on buildings. To minimize this possibility, extend the distance from the building to the end of the vent termination and increase the horizontal distance between terminations.
4. Multiple vertical vent pipes may be piped through a common conduit or chase so that one roof penetration may be made. Each vent termination must be one (1) foot from other terminations.
D. Air Intake Piping
1. Each boiler must have an individual air intake pipe, refer to Venting Section of this manual for Air Intake Guidelines and Options.
2. The maximum air intake length for each boiler is
fty (50) equivalent feet.
3. Locate air intake termination on the same wall as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with vertical venting and sidewall combustion air
62
inlet (or visa versa) if installation conditions do not allow alternate arrangement.
TABLE 9: MODULAR BOILER WATER MANIFOLD SIZING
Combined Output
(MBH)
< 166 1¼” < 260 1½” < 550 2” < 900 2½”
< 2000 3”
Recommended Minimum
Common Water Manifold
Size (NPT)
E. Water Piping (See Table 9)
Installing a low water cutoff in the system piping of
modular systems is strongly recommended and may be required by Local Codes.
F. Gas Piping
1. Refer to National Fuel Gas Code, Local Codes and Tables 7 and 8 for gas pipe sizing.
2. Each boiler must be piped as shown in Figure 27.
WARNING
If gas pressure in the building is above ½ psig,
an additional gas pressure regulator is required.
Using one additional regulator for multiple boilers may result in unsafe boiler operation. The additional regulator must be able to properly regulate gas pressure at the input of the smallest boiler. If the regulator cannot do this, two or
more additional regulators are required. Consult
regulator manufacturer and/or local gas supplier
for instructions and equipment ratings.
G. Electrical
1. Each boiler must be provided with a fused disconnect and service switch.
2. Install wiring in accordance with requirements of authority having jurisdiction. In the absence of such requirements, follow the National Electric Code, NFPA 70 and/or CSA C22.1 Electric Code.
H. Modular Boiler Control Systems
Contact a controls manufacturer such as Honeywell or
Tekmar to properly apply a modular control system.
Common systems may use outdoor temperature, return
water temperature or both to stage the boilers.
Page 63
Figure 35: Modular Boiler Gas Piping
63
Page 64
VIII. System Start-up
A. Safe operation and other performance criteria were
met with gas manifold and control assembly provided
on boiler when boiler underwent tests specied in
American National Standard for Gas-Fired Low­Pressure Steam and Hot Water Boilers, ANSI Z21.13.
B. Verify that the venting, water piping, gas piping and
electrical system are installed properly. Refer to installation instructions contained in this manual.
C. Conrm all electrical, water and gas supplies are
turned off at the source and that vent is clear of obstructions.
D. Conrm that all manual shut-off gas valves between
the boiler and gas source are closed.
WARNING
Completely read, understand and follow all instructions in this manual before attempting start up.
E. Fill entire heating system with water and vent air
from system. Use the following procedure on a Series Loop or multi-zoned system installed as per Figure 25
or 26 to remove air from system when lling.
WARNING
The maximum operating pressure of this boiler is 30 psig. Never exceed this pressure. Do not plug or change pressure relief valve.
NOTICE
If it is required to perform a long term pressure
test of the hydronic system, the boiler should
rst be isolated to avoid a pressure loss due to
the escape of air trapped in the boiler. To perform a long term pressure test including
the boiler, ALL trapped air must rst be removed
from the boiler. A loss of pressure during such a test, with no
visible water leakage, is an indication that the boiler contained trapped air.
1. Close full port ball valve in boiler supply piping.
2. Isolate all zones by closing zone valves or shut-off valves in supply and return of each zone(s).
3. Attach a hose to the vertical hose bib located prior to the full port ball valve in the system supply piping.
(Note - Terminate hose in ve gallon bucket at a suitable oor drain or outdoor area).
4. Starting with one circuit at a time, open zone valve
or shut-off valve in system supply and return piping.
5. Open hose bib.
6. Open ll valve (Make-up water line should be
located directly after full port ball valve in system supply piping between air scoop and expansion tank).
7. Allow water to overow from bucket until discharge
from hose is bubble free for 30 seconds.
8. Close the opened zone valve or shut-off valve for the zone being purged of air, then open the zone valve or shut-off valve for the next zone to be purged. Repeat this step until all zones have been purged. At completion, open all zone valves or shut-off valves.
9. Close hose bib, continue lling the system until the pressure gauge reads 12 psi. Close ll valve.
(Note - If make-up water line is equipped with
pressure reducing valve, system will automatically
ll to 12 psi. Follow ll valve manufacturer’s
instructions).
10. Open isolation valve in boiler supply piping.
11. Remove hose from hose bib.
F. Conrm that the boiler and system have no water
leaks.
G. Prepare to check operation.
1. Obtain gas heating value (in Btu per cubic foot) from gas supplier.
2. Connect manometer to pressure tap on gas valve. Use 1/8 NPT tapping provided.
3. Temporarily turn off all other gas-red appliances.
4. Turn on gas supply to the boiler gas piping.
5. Conrm that the supply pressure to the gas valve is
14 in. w.c. or less. Refer to Table 5 for minimum supply pressure.
6. Open the eld installed manual gas shut-off valve
located upstream of the gas valve on the boiler.
7. Using soap solution, or similar non-combustible solution, electronic leak detector or other approved method. Check that boiler gas piping valves, and all other components are leak free. Eliminate any leaks.
DANGER
Do not use matches, candles, open ames or
other ignition source to check for leaks.
8. Purge gas line of air.
64
Page 65
Figure 36: Operating Instructions
65
Page 66
H. Operating Instructions.
1. Follow Operating Instructions to place boiler in operation. See Figure 36.
2. Electronic Ignition Modules with LED indicators. Table 10 cross-references the ignition module terminal designations to the ignition terminal
numbers in the wiring ladder diagrams. The yellow
LED indicates the status of the ame, see Table 11.
The green LED indicates the status of the system, see Table 12. See Figure 37 for LED locations. See Figure 38 for Troubleshooting Guide.
TABLE 10: IGNITION MODULE TERMINAL CROSS-REFERENCE
Ignition Module
Terminal Designation
MV 1
MV/PV 2
PV 3
GND 4
24V (GND) 5
24V 6
Figure 37: LED Locations
TABLE 11: YELLOW LED FLAME CODES
Yellow LED
Flash Code
a
Indicates Recommended Service Action
SPARK 9
Heartbeat Normal Flame Signal N/A
Weak Flame Signal ­System will operate reliably but ame signal is
2
less than desired. Note: This indication may ash temporarily
during or shortly after lightoff on some appli-
cations.
System may not operate reliably over time.
1
Service call recommended. Note: This indication may ash temporarily
during or shortly after lightoff on some appli-
cations.
OFF
operation.
a
Flash Code Descriptions
Marginal Flame Signal (less than 1.1 µA) -
No Flame or Flame Signal -
below minimum threshold for system
Perform routine maintenance to
assure optimum ame signal.
Check gas supply, pilot burner, ame sense wiring, contamination of ame rod, burner ground connection.
Wiring Ladder Diagram
Terminal Number
N/A
66
- Heartbeat: Constant ½ second bright, ½ second dim cycles.
- The ash code number signies that the LED ashes X times at 2Hz, remains off for two seconds, and then repeats sequence.
Page 67
TABLE 12: GREEN LED STATUS CODES
Green LED
Flash Code
(X + Y)
Flash Fast
Heartbeat Normal operation N/A None
a
Flash Code Descriptions:
a
OFF No “Call for Heat” N/A None
Startup - Flame sense
calibration
5 minute Retry Delay-
2
3
4
7
8
6 + 2
6 + 3
6 + 4
ON
- Flash Fast: rapid blinking
- Heartbeat: Constant ½ second bright, ½ second dim cycles.
- A single ash code number signies that the LED ashes X times at 2Hz, remains off for two seconds, and then
- X + Y ash codes signify that the LED ashes X times at 2Hz, remains off for two seconds, ashes Y times at 2
Pilot ame not detected
during trial for ignition
Recycle- Flame failed during run
Flame sensed out of sequence
Flame sense leakage to ground
Low secondary voltage supply- (below 15.5 Vac)
5 minute Retry Delay­On every third retry on same “Call for Heat”
On every 6th ame
failure during run on the
same “Call for Heat”
Flame sensed out of sequence- longer than
10 seconds
Soft lockout due to error detected during self check sequences
repeats the sequence.
Hz, remains off for three seconds, and then repeats the sequence.
Indicates Next System Action Recommended Service Action
N/A None
If system fails to light on next trial
for ignition check gas supply, pilot
Initiate new trial for ignition after retry
delay completed.
Initiate new trial for ignition. Flash
code will remain through the ignition
trial until ame is proved.
If situation self corrects within 10
seconds, control returns to normal
sequence. If ame out of sequence re­mains longer than 10 seconds, control goes to Flash code 6+4 (see below)
Control remains in wait mode. When
the fault corrects, control resumes nor-
mal operation after a one minute delay.
Control remains in wait mode. When
the fault corrects, control resumes nor-
mal operation after one minute delay.
Initiate new trial for ignition after retry
delay completed.
5 minute retry delay, then initiate new trial for ignition.
Control waits until ame is no longer sensed and then goes to soft lockout. Flash code continues. Control auto resets from soft lockout after one hour.
Control auto resets from soft lockout
after one hour.
burner, spark and ame sense wir­ing, ame rod contamination or out of position, burner ground connec­tion.
If system fails to light on next trial
for ignition check gas supply, pilot
burner, ame sense wiring, ame rod contamination, burner ground connection.
Check for pilot ame. Replace gas valve if pilot ame present. If no pilot ame, cycle “Call for Heat.” If error repeats, replace control.
Check ame sense lead wire for damage or shorting. Check that ame rod is in proper position. Check ame rod ceramic for cracks, damage or tracking.
Check transformer and AC line for
proper input voltage to the control.
Check with full system load on the
transformer. Check gas supply, pilot burner, spark
and ame sense wiring, ame rod
contamination or out of position,
burner ground connection. Check gas supply, pilot burner, ame
sense wiring, contamination of ame rod, burner ground connection.
Check for pilot ame. Replace gas valve if pilot ame present. If no pilot ame, cycle “Call for Heat.” If error repeats, replace control.
Reset by cycling “Call for Heat.” If
error repeats, replace the control
67
Page 68
Honeywell Electronic Ignition Troubleshooting Guide
68
Figure 38: Troubleshooting Guide
Page 69
Figure 40: 1 Inch Main Burner ame
Figure 41: Pilot Burner Flame
tipping. Orange-yellow streaks should not be confused with true yellow tipping.
Figure 39: Sequence of Operation
I. Sequence of Operation. See Figure 39. If boiler fails
to operate properly, see Troubleshooting Tree in Section IX: Service.
J. Check pilot burner ame. See Figure 41. Flame
should be steady, medium hard blue enveloping 3/8 to ½ inch of sensing probe.
K. Check main burner ame. See Figures 40. Flame
should have clearly dened inner cone with no yellow
L. Check thermostat operation. Raise and lower
temperature setting to start and stop boiler operation.
M. Check ignition control module shut-off. Disconnect
pilot lead wires from gas valve. If burners do not shutdown, determine cause of malfunction. Replace necessary items and check operation.
N. Check low water cutoff (if so equipped).
1. Adjust thermostat to highest setting.
2. With boiler operating, open drain valve and slowly drain boiler.
3. Main burners and pilot burner will extinguish and blower will stop when water level drops below low water cutoff probe. Verify limit, thermostat or other controls have not shut off boiler.
4. Adjust thermostat to lowest setting. Rell boiler.
69
Page 70
O. Check limit.
1. Adjust thermostat to highest setting.
2. Observe temperature gauge. When temperature is indicated, adjust limit to setting below observed temperature. Main burners and pilot burner should extinguish, and blower should stop.
3. Adjust limit to setting above observed temperature. Ignition sequence should begin.
4. Adjust thermostat to lowest setting. Adjust limit to desired setting.
P. Adjust gas input rate to boiler.
1. Adjust thermostat to highest setting.
2. Check manifold gas pressure. See Table 5 or rating label located in the boiler’s vestibule compartment. Adjust gas valve pressure regulator as necessary (turn adjustment screw counterclockwise to decrease manifold pressure, or clockwise to increase manifold pressure). If pressure cannot be attained, check gas valve inlet pressure. If less than minimum indicated in Table 5 or boiler’s rating label, contact gas supplier for assistance.
3. Clock gas meter for at least 30 seconds. Use Table
13 to determine gas ow rate in Cubic Feet per
Hour.
WARNING
Failure to properly adjust gas input rate will result
in over ring or under ring of the appliance.
Improper and unsafe boiler operation may result.
4. Determine Input Rate. Multiply gas ow rate by gas
heating value.
5. Compare measured input rate to input rate stated on rating plate.
a. Boiler must not be over red. Reduce input rate
by decreasing manifold pressure. Do not reduce
more than 0.3 inch w.c. If boiler is still overred,
contact your Burnham distributor or Regional
Ofce for replacement Gas Orice.
b. Increase input rate if less than 98% of rating
plate input. Increase manifold gas pressure no
more than 0.3 inch w.c. If measured input rate is still less than 98% of rated input:
i. Remove Main Burners per procedure in
Section IX: Service.
ii. Remove gas orices. Drill one (1) drill size
larger (drill size is stamped on orice, or see
Section X: Repair Parts).
iii. Reinstall gas orices and main burners.
Measure input rate.
6. Recheck Main Burner Flame.
7. Return other gas-red appliances to previous
conditions of use.
Q. Review User’s Information Manual and system
operation with owner or operator.
TABLE 13: GAS FLOW RATE IN CUBIC FEET PER HOUR
Seconds
for One
Revolution
30 60 120 240 32 56 113 225
34 53 106 212 36 50 100 200 38 47 95 189
40 45 90 180 42 43 86 172
44 41 82 164 46 39 78 157 48 37 75 150
50 36 72 144 52 35 69 138 54 33 67 133 56 32 64 129 58 31 62 124 60 30 60 120
Size of Gas Meter Dial
One-Half
Cu. Ft.
One
Cu. Ft.
Two
Cu. Ft.
70
Page 71
IX. Service
DANGER
This boiler uses ammable gas, high voltage electricity, moving parts, and very hot water under high
pressure. Assure that all gas and electric power supplies are off and that the water temperature is cool before attempting any disassembly or service.
Assure that all gas valves and electrical disconnect switches are off before attempting any disassembly or service.
Do not attempt any service work if gas is present in the air in the vicinity of the boiler. Never modify, remove or tamper with any control device.
WARNING
This boiler must only be serviced and repaired by skilled and experienced service technicians. If any controls are replaced, they must be replaced with identical models.
Read, understand and follow all the instructions and warnings contained in all the sections of this manual.
If any electrical wires are disconnected during service, clearly label the wires and assure that the wires are reconnected properly.
Never jump out or bypass any safety or operating control or component of this boiler. Read, understand and follow all the instructions and warnings contained in ALL of the component
instruction manuals. Assure that all safety and operating controls and components are operating properly before placing
the boiler back in service.
A. General. Inspection and service should be conducted
annually. Turn off electrical power and gas supply while conducting service or maintenance. Follow instructions TO TURN OFF GAS TO APPLIANCE. See Figure 36.
B. Low water cutoff (if so equipped).
Probe Type (Annual Service). Probe type LWCO
should be removed once a year, examined and cleaned of any dirt accumulations to assure proper operations. Do not attempt to repair mechanisms in the
eld. Complete replacement mechanisms, including
necessary gaskets and installation instructions, are available from the manufacturer.
C. Vent/Air Intake System. Inspect for obstructions, soot
accumulation, proper support, and deterioration of pipe,
ttings, and joints.
1. Clean terminal screens. Terminals must be free of obstruction, undamaged, with screens securely in place.
2. Terminal and wall thimbles (if used) must be weathertight.
3. Pipe must be full round shape, and show no damage from impact or excessive temperature.
4. Pipe must be supported at minimum ve (5) foot
intervals and must not sag.
5. All vent joints must be secure and watertight.
6. All air intake joints must be secure and airtight. Horizontal vent tee drain or vertical vent tee drain (if used) must have minimum 6 inch trap and allow
condensate to ow freely. To Clean: a. Disconnect drain tube from drain tting.
b. Flush drain tube with water. Fill trap with water.
c. Securely fasten drain tube to drain tting,
providing gas-tight and watertight seal.
7. If pipe must be disassembled for removal of obstructions or resealing of joint, see Section III, Paragraph C.
D. Boiler Flue Passages. Inspect for blockage or soot
accumulation.
1. Remove Main Burners. See Figure 44. a. Remove front door. b. Remove air intake box front door.
i. Remove sheet metal screws.
c. Disconnect pilot tubing and pilot lead wires at
the gas valve.
71
Page 72
d. Remove wires to Flame Roll-out Switch. e. Remove air diffuser screen. f. Remove Burner Access Panel. g. Mark location of Main Burner with Pilot Bracket
on gas manifold.
h. Hold Main Burner on throat. Lift front of
burners to clear orice. Burner which holds pilot
can be removed by lifting the burner adjacent to
its right rst.
2. Disconnect Vent Connector and Vent Pipe from Blower Outlet
3. Remove Jacket Top Panel.
4. Disconnect the Black and Gary Silicone Tubing from the Canopy.
5. Disconnect Wiring Harness from Blower Motor.
6. Remove Canopy/Blower Assembly. a. Loosen the (4) screws from Canopy.
7. Remove Flue Gas Bafes. Inspect Flue Gas Bafes
for deterioration.
8. Inspect ue passages. Clean with ue brush. See
Figure 44.
9. Inspect heating surface in combustion chamber. Clean with straight handle wire brush.
10. Install Flue Gas Bafes.
11. Replace Canopy/Blower Assembly.
12. Connect Silicone Tubing between Pressure Fittings on Canopy Assembly and Pressure Switch. Route through bushings in Vestibule Panel . See Figure
42.
Figure 42: Silicone Tubing Assembly
13. Install Jacket Top Rear Panel.
14. Connect Vent System. See Figure 43.
15. Connect Blower Motor Wiring Harness.
Figure 43: Blower Vent Connector Assembly
TABLE 14: PILOT BURNER LOCATION
Boiler Model Main Burner with Pilot Bracket Pilot Burner Located Between Main Burners *
SCG-3 2 2 & 3 SCG-4 3 3 & 4 SCG-5 4 4 & 5 SCG-6 5 5 & 6 SCG-7 6 6 & 7 SCG-8 7 7 & 8
SCG-9 8 8 & 9
* Main burners numbered left to right as viewed from front of boiler.
72
Page 73
Figure 44: Flue and Burner Cleanout, 1” Burner
73
Page 74
E. Main Burners and Firebox.
1. Vacuum rebox. Exercise care - do not damage base
insulation.
2. Clean main burners. Brush top of burners with soft bristle brush. See Figure 44. Vacuum to remove any dirt and lint.
3. Vacuum tip of pilot burner.
4. Check gas orices for lint and dirt. Clean as
necessary.
5. Install main burners by reversing procedure to remove burners.
a. Pilot burner must be installed in original
location. See Table 14.
b. Main burners must be properly secured in burner
tray slot at rear of rebox and over gas orice.
See Figure 44.
c. Pilot gas supply and pilot lead wires must be
reconnected. d. Burner access panel must be securely in place. e. Reinstall air diffuser screen. f. Reconnect Flame Roll-out wires. g. Air Intake Box Front Door must be installed.
F. Check operation. Follow steps G through P from
Section VIII: System Start-up.
NOTE: If switch drops-out before boiler reaches
temperature or if pressure differential readings are below minimums shown in Table 15, check for cracks in hose or contact your nearest Burnham representative.
4. Stop boiler, remove manometer and reconnect hoses to differential pressure switch. See Figures 42 and
45.
G. Procedure for Measuring Differential Pressure (See
Figure 45).
1. With boiler off, remove Gray and Black Hoses at differential pressure switch.
2. With tees and ¼ inch aluminum stubs, connect water manometer as shown with additional tubing.
3. Start boiler and read Pressure on Manometer when boiler water temperature reaches operating temperature. Refer to Table 15 for minimum readings.
TABLE 15: DIFFERENTIAL PRESSURE SWITCH SETTINGS
Minimum Differential Pressure
Boiler Model
Sea Level to 4,999 Ft. 5,000 - 10,000 Ft. Elevation
SCG-3 1.32” w.c. .80” w.c. SCG-4 1.17” w.c. .65” w.c.
SCG-5 1.17” w.c. .65” w.c. SCG-6 .88” w.c. .35” w.c.
Figure 45: Differential Pressure Measurement
74
SCG-7 .80” w.c. .30” w.c. SCG-8 .88” w.c. .35” w.c.
SCG-9 .88” w.c. .35” w.c.
Page 75
THIS PAGE LEFT INTENTIONALLY BLANK
75
Page 76
767778
Page 77
Page 78
XI. Repair Parts
All SCG Repair Parts may be obtained through your local Burnham Wholesale distributor. Should you require assistance in locating a Burnham distributor in your area, or have questions regarding the availability of Burnham products or repair parts, please contact Burnham Customer Service at (717) 481-8400 or Fax (717) 481-8408.
Page 79
Key
No.
Description
SCG-3 SCG-4 SCG-5 SCG-6 SCG-7 SCG-8 SCG-9
[Quantity] Part Number
1. CASTING ASSEMBLY
1 Section Assembly 61707031 61707041 61707051 61707061 61707071 61707081 61707091
1A Left End Section 71707001
1B Center Section
1C Right End Section 71707002
1D Slip Nipple, #3
1E Flue Gas Bafe
1F Tie Rod, ¼” -20
1G Hex Nut, ¼” -20 (4) 80860407
(1)
71707003
(4)
806600009
(2)
71107002
(2)
100109-01
(2)
71707003
(6)
806600009
(3)
71107002
(2)
100108-05
(3)
71707003
(8)
806600009
(4)
71107002
(2)
100108-07
(4)
71707003
(10)
806600009
(5)
71107002
(2)
100108-13
(5)
71707003
(12)
806600009
(6)
71107002
(2)
100108-14
(6)
71707003
(14)
806600009
(7)
71107002
(2)
100108-15
(7)
71707003
(16)
806600009
(8)
71107002
(2)
100108-16
79
Page 80
80
Page 81
Key
No.
Description
SCG-3 SCG-4 SCG-5 SCG-6 SCG-7 SCG-8 SCG-9
[Quantity] Part Number
2. BASE ASSEMBLY
2A Base Wrapper 71807031 71807041 71807051 71807061 71807071 71807081 71807091
2B Base Tray 71807032 71807042 71807052 71807062 71807072 71807082 71807092
2C Burner Tray Assembly 61807031 61807041 61807051 61807061 61807071 61807081 61807091
2D Base Front Panel 71807035 71807045 71807055 71807065 71807075 71807085 71807095
2E Burner Access Panel 71807036 71807046 71807056 71807066 71807076 71807086 71807096
2F Cerafelt Gasket 1/2” x 2” 9206003
2G Cerafelt Gasket 1/2” x 2” 9206003
2H Base Side Insulation (2) 72007001
2J Base Rear Insulation 72007031 72007041 72007051 72007061 72007071 72007081 72007091
2K Base Front Insulation 72007032 72007042 72007052 72007062 72007072 72007082 72007092
2L Base Leg Assembly (4) 6186001
2M Self Tapping Screw, 1/4” -20 x 1/2” (18) 80860700
2N Flame Roll-out Switch 80160044
2P Sheet Metal Screw, #8 x 3/4” 80860030
2Q Self Tapping Screw, 10 -32 x 3/8” (5) 80860705 (6) 80860705 (7) 80860705
2R Self Tapping Screw Hex Cap, 5/16 -18 x 1-1/4” (4) 80860717
81
Page 82
82
Page 83
Key
No.
Description
SCG-3 SCG-4 SCG-5 SCG-6 SCG-7 SCG-8 SCG-9
[Quantity] Part Number
2. BASE ENCLOSURE ASSEMBLY
3A Air Box Assembly 61807032 61807042 61807052 61807062 61807072 61807082 61807092
3B Air Box Door 71807034 71807044 71807054 71807064 71807074 71807084 71807094
3C Combustion Air Diffuser N/A 71807049 71807059 71807069 71807079 71807089 71807099
3D Pilot Tube Gasket Cover Plate 7096002
3E Pilot Tube Gasket 8206038
3F Window Plug 102202-01
3J Sheet Metal Screws #8 x 1/2” (6) 80860000
3K Self Tapping Screw, 10-32 x 3/8” (18) 80860705 (22) 80860705
83
Page 84
84
Page 85
Key
No.
Description
SCG-3 SCG-4 SCG-5 SCG-6 SCG-7 SCG-8 SCG-9
[Quantity] Part Number
4. FAN/CANOPY ASSEMBLY
Canopy Assembly - Sea Level 61107031 61107041 61107051 61107061 61107071 61107081 61107091
4A
Canopy Assembly - High Altitude 61107032 61107042 61107052 61107062 61107072 61107082 61107092
4B Cerafelt 9206005
4C U-Clip (4) 80861512
4D Sheet Metal Screw, #10 x 1” (4) 808600141
4E Fan Gasket 8206085
4F Fan 81161512
4G Lock Washer, #10 (4) 80860636
4H Machine Screw, #10-24 x 2½” (4) 808608982
85
Page 86
86
Page 87
Key
No.
Description
5. BURNER ASSEMBLIES
[Quantity] Part Number
SCG-3 SCG-4 SCG-5 SCG-6 SCG-7 SCG-8 SCG-9
Gas Valve (Natural Gas), Honeywell VR8204P1171
Gas Valve (Natural Gas), Honeywell VR8304P4496
5A
Gas Valve (LP Gas), Honeywell VR8204C3015
Gas Valve (LP Gas), Honeywell VR8304P4280
Nipple, ½” NPT x Close 806600040 N/A
5B
Nipple, ¾” NPT x Close N/A 806600022 Union, ½” NPT 806604023 N/A
5C
Union, ¾” NPT N/A 806604001 ½” Gas Manifold 82207031 82207041 82207051 82207061 --- --- ---
5D
¾” Gas Manifold --- --- --- --- 82207071 82207081 82207191
Burner Orices - Natural Gas #47
5E
Burner Orices - LP Gas 1.20 mm
Pilot Assembly - Natural Gas 8236163
5F
Pilot Assembly - LP Gas 8236164
5G Pilot Burner 100147-01
5H Main Burner
5J Pilot Tubing 8236122 5K Self Tapping Screw, ¼ - 20 x ½” (6) 80860700
(4)
822710
(4)
822792
(3)
100146-01
81660282 N/A
N/A 81660283
81660146 N/A
N/A 81660160
(6)
822710
(6)
822792
(5)
100146-01
(8)
822710
(8)
822792
(7)
100146-01
(10)
822710
(10)
822792
(9)
100146-01
(12)
822710
(12)
822792
(11)
100146-01
(14)
822710
(14)
822792
(13)
100146-01
(16)
822710
(16)
822792
(15)
100146-01
87
Page 88
88
Page 89
Key
No.
Description
SCG-3 SCG-4 SCG-5 SCG-6 SCG-7 SCG-8 SCG-9
[Quantity] Part Number
6. CONTROL PANEL ASSEMBLY
6A Limit, Honeywell L4080D 100189-01
6B Transformer/Relay, Honeywell R8285D 80160155U
6C Ignition Module, Honeywell S8670E3003 100959-01
6D Blower Relay, Honeywell R8222U1006 80160096U
Differential Pressure Switch
Sea Level 0’ - 4999’
6E
High Altitude - 5000’ - 10,000’ 80160759 80160763 80160764 80160765 80160764
6F Junction Box 8136259
80160762 80160761 80160760 80160759 80160760
89
Page 90
90
Page 91
Key
No.
Description
SCG-3 SCG-4 SCG-5 SCG-6 SCG-7 SCG-8 SCG-9
[Quantity] Part Number
7. JACKET PARTS
7A Jacket Left Side Panel 60407002 7B Jacket Right Side Panel 60407001 7C Rear Panel 60407033 60407043 60407053 60407063 60407073 60407083 60407093 7D Vestibule Panel 60407034 60407044 60407054 60407064 60407074 60407084 60407094 7E Top Panel 60407032 60407042 60407052 60407062 60407072 60407082 60407092 7F Front Door 101354-03 101354-04 101354-05 101354-06 101354-07 101354-08 101354-09
7G Air Intake Collar Assembly 60407003 60407004 60407005
7H Handle 8056184
7J Door Clip (2) 7041921
7K Bushing 8136048
7L Burnham Logo 81460099
91
Page 92
Key
No.
Description
[Quantity] Part Number
SCG-3 SCG-4 SCG-5 SCG-6 SCG-7 SCG-8 SCG-9
8. MISCELLANEOUS PARTS CARTON
8A Water Manifold 80607001 8B Temperature/Pressure Gauge 8056169 8C Circulator Wiring Harness 6130701 8D Safety Relief Valve 81660363 8E Boiler Drain Valve 806603061 8F Vent Terminal 8110701 8110702 8G Air Intake Terminal 6116045 6116044 6116063 8H Vent Connector 8110703 8110704
92
Page 93
Important Product Safety Information
Refractory Ceramic Fiber Product
Warning:
The Repair Parts list designates parts that contain refractory ceramic fibers (RCF). RCF has been classified as a possible human carcinogen. When exposed to temperatures about 1805°F, such as during direct flame contact, RCF changes into crystalline silica, a known carcinogen. When disturbed as a result of servicing or repair, these substances become airborne and, if inhaled, may be hazardous to your health.
AVOID Breathing Fiber Particulates and Dust
Precautionary Measures:
Do not remove or replace RCF parts or attempt any service or repair work involving RCF without wearing the following protective gear:
1. A National Institute for Occupational Safety and Health (NIOSH) approved respirator
2. Long sleeved, loose fitting clothing
3. Gloves
4. Eye Protection
Take steps to assure adequate ventilation.
Wash all exposed body areas gently with soap and water after contact.
Wash work clothes separately from other laundry and rinse washing machine after use to avoid contaminating other clothes.
Discard used RCF components by sealing in an airtight plastic bag. RCF and crystalline silica are not classified as hazardous wastes in the United States and Canada.
First Aid Procedures
:
If contact with eyes: Flush with water for at least 15 minutes. Seek
immediate medical attention if irritation persists.
If contact with skin: Wash affected area gently with soap and water.
Seek immediate medical attention if irritation persists.
If breathing difficulty develops: Leave the area and move to a location
with clean fresh air. Seek immediate medical attention if breathing difficulties persist.
Ingestion: Do not induce vomiting. Drink plenty of water. Seek
immediate medical attention.
93
Page 94
SERVICE RECORD
DATE SERVICE PERFORMED
94
Page 95
SERVICE RECORD
DATE SERVICE PERFORMED
95
Page 96
79
water boiler for its intended purposes and its maintenance accordance with U. S. Boiler Co., Inc. recommendations and hydronics industry standards. These warranties will be inapplicable if the residential grade water boiler is used or operated over its rated capacity, is subjected to unauthorized modification, or is damaged as a result of being otherwise improperly operated or serviced including, but not limited to, damage from any of the following: operation with insufficient water, allowing the boiler to freeze, subjecting the boiler to flood conditions, and operation with unapproved water or fuel additives which cause deposits or corrosion.
5. Removal and Installation: These warranties do not cover expenses of removal or reinstallation. The owner is responsible for the cost of removing and reinstalling any defective part and its replacements and all labor and material connected therewith.
6. Exclusive Remedy: U.S. Boiler Co., Inc. obligation for any breach of these warranties is limited to the repair or replacement of its parts in accordance with the terms and conditions of these warranties.
7. Limitation of Damages: Under no circumstances shall U.S. Boiler Co., Inc. be liable for incidental, indirect, special or consequential damages of any kind whatsoever under these warranties, including, but not limited to, injury or damage to persons or property and damages for loss of use, inconvenience or loss of time. U.S. Boiler Co., Inc. liability under these warranties shall under no circumstances exceed the purchase price paid by the owner for the residential grade water boiler involved. Some states do not allow the exclusion or limitation of incidental or consequential damages, so the above limitation or exclusion may not apply to you.
8. Limitation of Warranties: These warranties set forth the entire obligation of U.S. Boiler Co., Inc. with respect to any defect in a residential grade water boiler and U.S. Boiler Co., Inc. shall have no express obligations, responsibilities or liabilities of any kind whatsoever other than those set forth herein. These warranties are given in lieu of all other express warranties.
ALL APPLICABLE IMPLIED WARRANTIES, IF ANY, INCLUDING
ANY WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY LIMITED IN DURATION TO A PERIOD OF ONE YEAR EXCEPT THAT IMPLIED WARRANTIES, IF ANY, APPLICABLE TO THE HEAT EXCHANGER IN A RESIDENTIAL GRADE WATER BOILER SHALL EXTEND TO THE ORIGINAL OWNER FOR THE LIFETIME OF THE ORIGINAL OWNER AT THE ORIGINAL PLACE OF INSTALLATION. SOME STATES DO NO ALLOW LIMITATION ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE LIMITATION MAY NOT APPLY TO YOU.
PROCEDURE FOR OBTAINING WARRANTY SERVICE
In order to assure prompt warranty service, the owner is requested to
complete and mail the attached Warranty Card within ten days after the installation of the boiler, although failure to comply with this request will not void the owner’s rights under these warranties.
Upon discovery of a condition believed to be related to a defect in
material or workmanship covered by these warranties, the owner should notify the installer, who will in turn notify the distributor. If this action is not possible or does not produce a prompt response, the owner should write to U.S. Boiler Co., Inc., Burnham Hydronics, at P.O. Box 3079, Lancaster, PA 17604, giving full particulars in support of the claim.
The owner is required to make available for inspection by U.S. Boiler
Co., Inc. or its representative the parts claimed to be defective and, if requested by U.S. Boiler Co., Inc. to ship these parts prepaid to U.S. Boiler Co., Inc. at the above address for inspection or repair. In addition, the owner agrees to make all reasonable efforts to settle any disagreement arising in connection with a claim before resorting to legal remedies in the courts.
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND
YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
Limited Warranty
FOR RESIDENTIAL CAST IRON WATER BOILERS
03/03
Subject to the terms and conditions set forth below, U.S. Boiler™ Co., Inc. Lancaster, Pennsylvania hereby extends the following limited warranties to the original owner of a residential grade water boiler manufactured and shipped on or after July 1,1991:
ONE YEAR LIMITED WARRANTY
ON RESIDENTIAL GRADE WATER BOILERS
U.S. Boiler Co., Inc. warrants to the original owner that its residential grade water boilers comply at the time of manufacture with recognized hydronic industry standards and requirements then in effect and will be free of defects in material and workmanship under normal usage for a period of one year from the date of original installation. If any part of a water boiler is found to be defective in material or workmanship during this one year period, U.S. Boiler Co., Inc. will, at its option, repair or replace the defective part.
LIFETIME LIMITED WARRANTY ON HEAT EXCHANGER
U.S. Boiler Co., Inc. warrants to the original owner that the heat exchanger of its residential grade water boilers will remain free from defects in material and workmanship under normal usage for the lifetime of the original owner at the original place of installation. If a claim is made under this warranty during the first ten years from the date of original installation, U.S. Boiler Co., Inc. will, at its option, repair or replace the heat exchanger. If a claim is made under this warranty after the expiration of ten years from the date of original installation, U.S. Boiler Co., Inc. will, at its option and upon payment of the pro-rated service charge set forth below, repair or replace the heat exchanger. The service charge applicable to a heat exchanger warranty claim is based upon the number of years the heat exchanger has been in service and will be determined as a percentage of the retail price of the heat exchanger model involved at the time the warranty claim is made as follows:
NOTE: If the heat exchanger model involved is no longer available due to product obsolescence or redesign, the value used to establish the retail price will be the published price as shown in the Burnham Hydronics Repair Parts Price Sheet where the heat exchanger last appeared or the current retail price of the then nearest equivalent heat exchanger.
ADDITIONAL TERMS AND CONDITIONS
1. Applicability: The limited warranties set forth above are extended
only to the original owner at the original place of installation within the
United States and Canada. These warranties are applicable only to
water boilers designated as residential grade by U.S. Boiler Co., Inc.
and installed in a single or two-family residence and do not apply to
steam boilers of any kind or to commercial grade boilers.
2. Components Manufactured by Others: Upon expiration of the one
year limited warranty on residential grade water boilers, all boiler
components manufactured by others but furnished by U.S. Boiler
Co., Inc. (such as oil burner, circulator and controls) will be subject
only to the manufacturer’s warranty, if any.
3. Proper Installation: The warranties extended by U.S. Boiler Co., Inc.
are conditioned upon the installation of the residential grade water
boiler in strict compliance with U.S. Boiler Co., Inc. installation
instructions. U. S. Boiler Co., Inc. specifically disclaims liability of any
kind caused by or relating to improper installation.
4. Proper Use and Maintenance: The warranties extended by U.S.
Boiler Co., Inc. conditioned upon the use of the residential grade
sraeY
ecivreSnI
01-1 11 21 31 41 51 61 71
egrahCecivreS
fo%sa
ecirPliateR
oN
egrahC
5 01 51 02 52 03 53
sraeY
ecivreSnI
81 91 02 12 22 32 42
dna52
evoba
egrahCecivreS
fo%sa
ecirPliateR
04 54 05 55 06 56 07 57
96
Loading...