Burnham SCG User Manual

DNAGNITAREPO,NOITALLATSNI
GCS
RELIOBDERIF-SAG
As an ENERGY STAR
STAR® guidelines for energy effi ciency established by the United States Environmental Protection Agency (EPA).
sserddA
8140705R3-1/07
®
Partner, Burnham Hydronics has determined that the SCG meets the ENERGY
rebmuNledoMrelioB
___-____GCS
rotcartnoCgnitaeH rebmuNenohP
rebmuNlaireSrelioB
________
.lebaLgnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp,reliob
etaDnoitallatsnI
Price - $5.00
nonoitamrofnignikeesnehW.rotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
IMPORTANT INFORMATION - READ CAREFULLY
NOTE: The equipment shall be installed in accordance with those installation regulations enforced in the area where the
installation is to be made. These regulations shall be carefully followed in all cases. Authorities having jurisdiction shall be consulted before installations are made.
All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or local regulations. All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or local regulations.
The New York City Department of Buildings has approved the SCG™ Series boiler: Approval No. MEA 5-06-E. The City of New York requires either a Licensed Master Plumber or a Fire Suppression Piping Contractor supervise the
installation of this product. The Massachusetts Board of Plumbers and Gas Fitters has approved the SCG™ Series boiler. See the Massachusetts Board of
Plumbers and Gas Fitters website, http://license.reg.state.ma.us/pubLic/pb_pre_form.asp for the latest Approval Code or ask your local Sales Representative.
The Commonwealth of Massachusetts requires this product to be installed by a Licensed Plumber or Gas Fitter.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
REGNAD
noitautissuodrazahyltnenimminasetacidnI
,htaednitluserlliw,dediovatonfi,hcihw
nisuoires
.egamad
ytreporplaitnatsbusroyruj
.
egamad
GNINRAW
noitautissuodrazahyllaitnetopasetacidnI
,htaednitluserdluoc,dediovatonfi,hcihw
jnisuoires
.egamad
ytreporplaitnatsbusroyru
razahyrujnilanosrep
NOITUAC
noitautissuodrazahyllaitnetopasetacidnI
nitluseryam,dediovatonfi,hcihw
ytreporproyrujnironimroetaredom
ECITON
nosnoitcurtsnilaicepssetacidnI
ecnanetniamro,noitarepo,noitallatsni
otdetalertontubtnatropmierahcihw
.sd
REGNAD
ynarosihtfoytinicivehtnisdiuqilrosropavelbammalfrehtoroenilosagesuroerotsTONOD
.ecnailpparehto
lacirtceleynahcuotTONOD-ecnailppaynaetarepootyrtTONOD,sropavsagllemsuoyfI
aidemmI.gnidliubehtnienohpynaesurohctiws
.tnemtrapederifeht
yletomeramorfreilppussagehtllac,ylet
tcatnoc,elbaliavanusireilppusehtfirosnoitcurtsnis'reilppussagehtwolloF.enohpdetacol
2
GNINRAW
ehtwolloF.ylefasetarepootecivresdnaecnanetniamralugerseriuqerreliobsihT
.launamsihtnideniatnocsnoitcurtsni
ytreporpesuacnacecnanetniamroecivres,noitaretla,tnemtsujda,noitallatsnireporpmI
ehtdnatsrednudnadaeR.efilfossolroyrujnilanosrep,egamad
.detnevylreporpebtsumreliobsihT
.rianoitalitnevdnanoitsubmocetauqedarof
.ycneiciffes'reliobehtgniniatniam
.sliated
erofeblaunameritne
ebtsumecivresdnanoitallatsnI.ecivresro,noitarepopu-trats,noitallatsnignitpmetta
.ycnegaecivresrorellatsnielbaegdelwonkdna,delliks,decneirepxenaybylnodemrofrep
snoisivorperaerehtosdellatsniebtsumdnanoitarepoefasrofriahserfsdeenreliobsihT
ehtfotratsehterofebdenaelcdnadetcepsniebtsummetsysgnitnevehtforoiretniehT
ynarofnosaesgnitaehehttuohguorhtyllacidoirepdetcepsniebdluohsdnanosaesgnitaeh
suoixonwollaotyrassecensimetsysgnitnevdetcurtsbonudnanaelcA.snoitcurtsbo
drawotetubirtnoclliwdnaylefastnevotefilfossolroyrujniesuacdluoctahtsemuf
gnippatehtotnidellatsnisievlavfeilererusserpasselnuetelpmoctonsinoitallatsnI
roflaunamsihtfonoitceSmirTdnagnipiPretaWehteeS-.ecnailppafopotnodetacol
tondnanwodtuhsotreliobehtesuacyamhcihwsecivedytefashtiwdeilppussireliobsihT
metsysgnitaeheht,ytilibissopasisepipnezorfoteudegamadfI.ecivrestuohtiwtrats-er
dluohssmraladnasdraugefasetairporpparo;rehtaewdlocnidednettanutfelebtondluohs
.evitareponisireliobehtfiegamadtneverpotmetsysgnitaehehtnodellatsnieb
sgnittifepipynawercsnutonoD.erusserphgihrednuretawtohyrevsniatnocreliobsihT
ehtgnirussaylevitisoptuohtiwreliobsihtfostnenopmocynatcennocsidottpmettaron
nehwtnempiuqednagnihtolcevitcetorpraewsyawlA.erusserponsahdnaloocsiretaw ehtnoylertonoD.seirujnidlacstneverpotreliobsihtgnicivresropugnitrats,gnillatsni
.reliobehtfoerusserpdnaerutarepmetehtenimretedotseguagerutarepmetdnaerusserp
oD.gnitareposireliobehtnehwtohyrevemocebhcihwstnenopmocsniatnocreliobsihT
cynahcuotton
.gnicivres
liobpeeK
.sdiuqilrosropav
.loocerayehtsselnustnenopmo
,acilis,animulaniatnocleufehtdnanoitsubmocfostcudorp,noitcurtsnocfoslairetamrelioB
rocixotrehtoro/dnasedyhedla,sedixonegortin,edixonomnobrac,slatemyvaeh
yrujnilanosrepesuacnacredroreporpehtnisnoitcurtsnillawollofoteruliaF
niatnocesohtllagnidulcni,snoitcurtsnilladaeR
.semitllataecalpniebtsumsdraugdnaserusolcne,setalprevocllA
lufmrah
foetatsehtotnwonkerahcihwdnayrujnisuoiresrohtaedesuacnachcihwsecnatsbus
reporpesusyawlA.mrahevitcudorperrehtodnastcefedhtrib,recnacesuacotainrofilaC
.ecnailppaehtybraengnikrowrognicivresnehwtnempiuqednasrotaripser,gnihtolcytefas
.htaedro
slaunamsrerutcafunamtnenopmocnide
rogniniatniam,gnitarepo,pugnitrats,gnillatsnierofebreliobehthtiwdedivorperahcihw
elbammalfrehtodnaenilosag,slairetamelbitsubmocmorfeerfdnaraelcaerare
ECITON
.launamsihtfokcabehtnodetnirpsihcihwfoypoca,ytnarrawdetimilasahreliobsihT
dellatsniyltcerroceraslortnocllatahteesotrotcartnocgnillatsniehtfoytilibisnopserehtsitI
.etelpmocsinoitallatsniehtnehwylreporpgnitarepoeradna
3
Table of Contents
I. Pre-Installation ............................... 6
II. Unpack Boiler ................................7
III. Venting/Air Intake Piping .............. 8
IV. Water Piping and Trim .................45
V. Gas Piping .................................... 50
VI. Electrical ....................................... 53
VII. Modular Installation .................... 62
VIII. System Start-up ............................64
IX. Service .......................................... 68
X. Repair Parts .................................. 74
Figure 1: Minimum Clearances to Combustibles
4
Figure 2: Dimensions
5
I. Pre-Installation
.yru
jni
F. Provide combustion and ventilation air in accordance
GNINRAW
snoitcurtsniesehtwolloftonoduoyfI
tluseryamnoisolpxeroerifa,yltcaxe
lanosreproegamadytreporpgnisuac
with applicable provisions of local building codes, or: USA - National Fuel Gas Code, NFPA 54/ANSI Z223.1, Air for Combustion and Ventilation;
Canada - Natural Gas Installation Code, CAN/
CGA-B149.1, or Propane Installation Code, CAN/ CGA-B149.2, Venting Systems and Air Supply for Appliances.
REGNAD
rehtoroenilosagerehwreliobllatsnitonoD
fosecruosro,sdiuqilrosropavelbammalf
racordyh
,srenaelc,sehcaelb.e.i(snob
cirbaf,srevomertniap,syarps,slacimehc
.derotsrodesuera).cte,srenetfos
ECITON
,reliobehtfotnetnocretawwolehtoteuD
ehtotdragerhtiwreliobehtfognizis-sim
evissecxenitluserlliwdaolmetsysgnitaeh
tnenopmocdetareleccadnagnilcycreliob
tnarrawTONSEODmahnruB.eruliaf
iaf
.gnizisrevo
A. Installation must conform to the requirements of the
authority having jurisdiction. In the absence of such requirements, installation must conform to the National Fuel Gas Code, NFPA 54/ANSI Z223.1, and/or CAN/ CGA B149 Installation Codes.
B. Appliance is design certi ed for installation on
combustible fl ooring. Do not install boiler on carpeting.
C. Provide clearance between boiler jacket and
combustible material in accordance with local fi re ordinance. Refer to Figure 1 for minimum listed clearance from combustible material. Recommended service clearance is 24 inches from left side, right side and front. Service clearances may be reduced to minimum clearances to combustible materials.
D. Install on level oor. For basement installation provide
solid base such as concrete, if fl oor is not level or if water may be encountered on fl oor around boiler. Floor must be able to support weight of boiler, water and all additional system components.
reliobdezis-simybdesuacserul
otreliobehtezisrevoTONOD.snoitacilppa
snoitallatsnireliobraludoM.metsyseht
reliobfodoohilekilehtecuderyltaerg
GNINRAW
rianoitalitnevdnanoitsubmocetauqedA
reporperussaotdedivorpebtsum
.noitsubmoc
The following guideline is based on the National Fuel Gas Code, NFPA 54/ANSI Z223.1.
1. Determine volume of space (boiler room). Rooms communicating directly with space (through openings not furnished with doors) are considered part of space.
Volume [ft³] = Length [ft] x Width [ft] x Height [ft]
2. Determine Total Input of all appliances in space. Round result to nearest 1,000 Btu per hour (Btuh).
3. Determine type of space. Divide Volume by Total Input.
a. If result is greater than or equal to 50 ft³ per
1,000 Btuh, space is considered an uncon ned space.
b. If result is less than 50 ft³ per 1,000 Btuh, space
is considered a con ned space.
4. Determine building type. A building of unusually tight construction has the following characteristics:
a. Walls and ceiling exposed to outside atmosphere
have a continuous water vapor retarder with a rating of 1 perm or less with openings gasketed and sealed, and;
b. Weather-stripping has been added on openable
windows and doors, and;
c. Caulking or sealants applied in joints around
window and door frames, between sill plates and oors, between wall-ceiling joints, between wall panels, at plumbing and electrical penetrations, and at other openings.
5. For boiler located in an uncon ned space in a building of other than unusually tight construction, adequate combustion and ventilation air is normally provided by fresh air infi ltration through cracks around windows and doors.
E. Protect gas ignition system components from water
(dripping, spraying, rain, etc.) during boiler operation and service (circulator replacement, condensate trap, control replacement, etc.).
6
ECITON
delaes(tnevtceridhtiwdetareposrelioB
gnideenmorftpmexeera)noitsubmoc
ehtmorfrianoitsubmocrofsnoisivorp
d
ellatsnisignipipekatniriadedivorp,moor
sihtnisnoitcurtsniehtdnaedocrep
.launam
6. For boiler located within unconfi ned space in building of unusually tight construction or within confi ned space, provide outdoor air through two permanent
openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within twelve (12) inches of top of space. Locate remaining opening within twelve (12) inches of bottom of space. Minimum dimension of air opening is three (3) inches. Size each opening per following:
a. Direct communication with outdoors. Minimum
free area of one (1) square inch per 4,000 Btu per hour input of all equipment in space.
b. Vertical ducts. Minimum free area of one (1)
square inch per 4,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
c. Horizontal ducts. Minimum free area of one (1)
square inch per 2,000 Btu per hour input of all equipment in space. Duct cross-sectional area shall be same as opening free area.
Alternate method for boiler located within
confi ned space. Use indoor air if two permanent openings communicate directly with additional space(s) of suffi cient volume such that combined volume of all spaces meet criteria for unconfi ned space. Size each opening for minimum free area of one (1) square inch per 1,000 Btu per hour input of all equipment in spaces, but not less than 100 square inches.
7. Combustion Air/Ventilation Duct Louvers and Grilles. Equip outside openings with louvers to prevent entrance of rain and snow, and screens to prevent entrance of insects and rodents. Louvers and grilles must be fi xed in open position or interlocked with equipment to open automatically before burner operation. Screens must not be smaller than ¼ inch mesh.
Consider the blocking effect of louvers, grilles and
screens when calculating the opening size to provide the required free area. If free area of louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
.noitareporeporperusniot
II. Unpack Boiler
NOITUAC
reliobpmubtonoD.reliobpordtonoD
.roolftsniagatekcaj
A. Move boiler to approximate installed position. B. Remove all crate fasteners. C. Lift and remove outside container. Save two of the
wooden slats from the container sleeve for use in Steps E and F.
D. Remove all boiler hold-down fasteners.
NOITUAC
nanireliobsihtgnitarepodiova,)riAroodnI-noitceSgnitneVees(noitsubmocrofriaroodnignisufI
sireliobfI.tneserpera.cte,tsudllawyrd,srebifnoitalusniesool,tsudwaserehwtnemnorivne
yliaddetcepsnidnadenaelcebtsumstropdnaroiretnirenrubeht,snoitidnocesehtrednudetarepo
GNINRAW
ebdluohsreliobsihtfonoitallatsnI
delliksdnadeniartybylnonekatrednu
p
E. Tilt the boiler to its front side or back side and slide a
wooden slat under the three raised feet.
F. Tilt the boiler in the opposite direction and slide
another wooden slat under the three raised feet.
G. Slide the boiler left or right off the skid using the two
wooden slats as runners.
.ycnegaecivresdeifilauqamorflennosre
H. Move boiler to its permanent location.
7
III. Venting / Air Intake Piping
GNINRAW
®
C4-92LAnonrehtoyna
onoD
perdoogniebdluohssecafrus
.yenmihc
umixamdeecxetonoD
Table 1: Air Intake / Vent System Options
rocillatemnon,leetssselniats613epyTro403epyT,dezinavlaghtiwreliobsihtesutonoD
.smetsystnevdesab
.ecnailppasihthtiwdoohtfardrorepmadcirtemorabaesutonoD
.reliobsihthtiwsrepmadtnevesut
,noitaroiretedtneverpoT.noitanimretdnuorasecafrusnomrofyamecidnaerutsioM
.).cte,detniap,delaes(ria
eraerehtosdellatsniebtsumdnanoitarepoefasrofriahserfsdeenecnailppasihT
italitnevdnanoitsubmocetauqedarofsnoisivorp
.riano
.epipekatniriafoezisecudertonoD
sernoitcurtsnirianoitsubmocwollofdnadnatsrednu,daeR
-erPehtnideniatnocsnoitcirt
.launamsihtfosnoitcurtsninoitallatsnI
diuqilrosropavelbammalfrehtoroenilosagerehwecnailppaetarepotonoD
,slacimehc,srenaelc,sehcaelb.e.i(snobracordyh
fosecruosro,s
,srenetfoscirbaf,srevomertniap,syarps
.riaehtnitneserpro/dnaderots,desuera).cte
nacecnailpparehtoon,yenmihchguorhtepiptnevgnillatsninehW
ehtotnidetneveb
.4elbaTotrefeR.shtgnelekatniria/tnevm
noitpOnoitpircseD
etarapeS.1
latnoziroH
etarapeS.2
lacitreV
lacitreV
riAroodnI.5
lanoitpO.6
etarapeS
latnoziroH
pip
itanibmoC.3
no
latnoziroH
noitanibmoC.4
tniriadna
atniriadnaepip
lanoitiddA tiKtneV deriuqeR
tnevehthtobhtiw)noitsubmocdelaes(tneVtceriD
yllatnozirohgnitanimretepipekatniriadnaepip
rofsnoitarteneplaudividnihtiw)llawedisahguorht(
.slanimretdnagnipipekatniriadnatneveht
tnevehthtobhtiw)noitsubmocdelaes(tneVtceriD
yllacitrevgnitanimretepipekatniriadnae
rofsnoitarteneplaudividnihtiw)foorehthguorht(
.slanimretdnagnipipekatniriadnatneveht
epiptnevehthtiw)noitsubmocdelaes(tneVtceriD
lanimretnommocatagniniojepipekatniriadna
pullawedisahguorht(yllatnozirohgnitanimretdna
.noitartenepenoylnohtiw)kciht"51ot
epiptnevehthtiw)noitsubmocdelaes(tneVtceriD
lanimretnommocatagniniojepipeka
htiw)foorehthguorht(yllacitrevgnitanimretdna
.noitartenepenoylno
dedivorpsinoitsubmocrofdesuriA-tneVrewoP
.gnidliubehtnihtiwmorf
tnevehthtobhtiw)noitsubmocdelaes(tneVtceriD
yllatnozirohgnitanimretepipek
rofsnoitarteneplaudividnihtiw)llawedisahguorht(
.slanimretdnagnipipekatniriadnatneveht
oN
oN
seY
seY
oN2elbaTeeS.
oN2
traP
rebmuN
eeS
2elbaT
eeS
2elbaT
116(
eS6-5
elbaTeeS.I
noitceS6-3
)21060
noitceS4-3 )10-222001( noitc )10-322001(
noitallatsnI
dnagniwarD
noitacificepS
)noitceSeeS(
.D
.E
.F
.G
H
8
Table 2: Vent System Components Included with Boiler
stnenopmoCmetsyStneVrebmuNtraP
"3lanimreTtneVdeteksaG
)7-GCSurht3-GCS(latnoziroH
"4lanimreTtneVdeteksaG
)9GCS&8-GCS(latnoziroH
"3-ekatnIriAcsiD
)4-GCS&3-GCS(
"4-ekatnIriAcsiD
)6-GCS&5-GCS(
"5-ekatnIriA
)9-GCSurht7-GCS(
1070118
70118
20
5406116
9406116
3606116
Table 3: Burnham Vent System and Air Intake System Components
metsyStneV
tnenopmoC
tF1xepiP.aiD"3U6926118
tF1xepiP.aiD"410-671001
tF3xepiP.aiD"3U8926118
tF3xepiP.aiD"410-771001
3U0036118
"410-181001
elbuoD"35116118
tF5xepiP.aiD"
tF5xepiP.aiD"410-871001
elbatsujdAxepiP.aiD"3U9136118
elbats
ujdAxepiP.aiD"410-971001
woblE°09.aiD"3U4926118
woblE°09.aiD"410-081001
woblE°54.aiD"3U2926118
woblE°54.aiD
eeTniarDlatnoziroH.aiD"3U2036618
eeTniarDlatnoziroH.aiD"410-281001
eeTniarDlacitreV.aiD"3U4036
eeTniarDlacitreV.aiD"410-381001
elbmihTllaWelgniS"36116118
elbmihTllaWelgniS"410-481001
elbmihTllaW
elbmihTllaWelbuoD"410-581001
traP
rebmuN
118
tnelaviuqE
epiPfoteeF
1
3
5
otlauqE**
htgneLdellatsnI
)46.1ot60.1(
5
5
½7
½7
---
---
metsySekatnI stnenopmoC
)srehtOybstraP(
tnelaviuqE
*epiPfoteeF
tF1xepiPDI"5ro,"4,"31
tF2xepiPDI"5ro,"4,"32
tF4xepiPDI"5ro,"4,"34
tF5xepiPDI"5ro,"4,"35
woblE°09"4ro,"35
54"4ro,"35
woblE°
woblE°09"56
woblE°54"56
nodesaBepiPfoteeFtnelaviuqE*
ngiseDepiPekomS"4dradnatS
Table 4: Vent/Air Intake Length
ledoM
.niM.xaM.niM.xaM.niM.xaM.niM.xaM.niM.xaM
4-GCS&3-GCS805----------------805--------
6-GCS&5-GCS--------805--------805--------
7-GCS----------------805805--------
9-GCS&8-GCS-----
epiPekatnIriA"3
).tF.viuqE(
-----------804--------804
epiPekatnIriA"4
).tF.viuqE(
epiPekatnIriA"5
).tF.viuqE(
qE(
epiPtneV"3
).tF.viu
epiPtneV"4
).tF.viuqE(
9
A. Vent Guidelines Due to Removal of an Existing
Boiler
For installations not involving the replacement of an
existing boiler, proceed to Step B.
When an existing boiler is removed from a common
venting system, the common venting system is likely to be too large for proper venting of the remaining appliances. At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system placed in operation, while the other appliances remaining connected to the common venting system are not in operation:
1. Seal any unused openings in the common venting system.
2. Visually inspect the venting system for proper size and horizontal pitch and determine there is no blockage or restriction, leakage, corrosion, and other defi ciencies which could cause an unsafe condition.
3. Insofar as is practical, close all building doors and windows and all doors between the space in which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any appliance not connected to the common venting system. Turn on any exhaust fans, such as range-hoods and bathroom exhausts, so they will operate at maxi mum speed. Do not operate a summer exhaust fan. Close replace dampers.
4. Place in operation the appliance being inspected. Follow the Lighting (or Operating) Instructions. Adjust thermo stat so appliance will operate continuously.
5. Test for spillage at the draft hood relief opening after fi ve (5) minutes of main burner operation. Use the fl ame of a match or candle, or smoke from a cigarette, cigar or pipe.
6. After it has been determined that each appliance remain ing connected to the common venting system properly vents when tested as outlined above, return doors, win dows, exhaust fans, fi replace dampers and any other gas burning appliance to their previous conditions of use.
7. Any improper operation of the common venting system should be corrected so the installation conforms with the National Fuel Gas Code, NFPA 54/ANSI Z223.1. When resizing any portion of the common venting system, the common venting system should be resized to approach the minimum size as determined using the appropriate tables in Part II in the National Fuel Gas Code, NFPA 54/ ANSI Z223.1.
B. General Guidelines
1. Vent system installation must be in accordance with National Fuel Gas Code, NFPA 54/ANSI Z221.3 or applicable provisions of local building codes. Contact local building or fi re offi cials about restrictions and installation inspection in your area.
2. The SCG is designed to be installed as either a Direct Vent boiler or Power Vent boiler. In the Direct Vent confi guration all of the air for combustion is supplied directly to the burner enclosure from outdoors and fl ue gases are vented directly outdoors (through wall or roof). In the Power Vent confi guration, room air provides air for combustion and ventilation. Flue gases are still vented directly outdoors (through wall or roof).
Note: Venting requirements change if indoor air is
used.
3. Refer to the appropriate drawings in this section of this manual to determine the proper confi guration of venting system. See Table 1.
4. This appliance requires a Special Gas Vent. The product is designed to use Burnham supplied AL 29-4C® Stainless Steel vent system components. The following manufacturers offer similar AL 29-4C® components and are approved for use with this product. Heat-Fab Inc. - Saf-T-Vent, Flex-L International Inc. - Star-34, Z-Flex U. S., Inc. - Z-Vent, and Protech Systems , Inc.- FasNSeal™ or equivalent. The use of these alternate manufacturer’s venting systems will require adapters to connect to the Burnham supplied vent connector and vent terminal. These adapters are not supplied with this unit and should be obtained from the supplier of the alternate manufacturer’s venting system. See Table 3 for complete list of Burnham Vent System Components.
5. Horizontal vent pipe must maintain a minimum ¼ inch per foot slope down towards boiler.
6. Use noncombustible ¾ inch pipe strap to support horizontal runs and maintain vent location and slope while preventing sags in pipe. Do not restrict thermal expansion or movement of vent system. Maximum support spacing is fi ve (5) feet. Do not penetrate any part of the vent system with fasteners.
7. Vent length restrictions are based on equivalent length of vent/air pipe (total length of straight pipe plus equivalent length of fi ttings). Maximum vent/air lengths are listed in Table 4. Do not exceed maximum vent/air intake lengths. Table 3 lists equivalent lengths for fi ttings. Do not include vent/ air terminals in equivalent feet calculations.
8. Provide and maintain vent pipe minimum clearances to combustible materials. Vent pipe minimum clearance to combustible material is four (4) inches when vent is installed in a fully enclosed (chase) application or three (3) inches when vent is installed
10
with at least one side open, similar to a joist bay application. Use double wall thimble [Burnham Part No. 8116115 (3”), 100185-01 (4”)] when penetrating a combustible wall.
9. Do not install venting system components on the exterior of the building except as specifi cally required by these instructions. The vent termination location is restricted as follows:
a. Minimum twelve (12) inches above grade plus
normally expected snow accumulation level, or seven (7) feet above grade if located adjacent to public walkway. Do not install over public walkway where local experience indicates appliance fl ue gas vapor or condensate creates a nuisance or hazard.
b. Minimum three (3) feet above any forced air
inlet located within ten (10) feet.
c. Direct Vent - Minimum one (1) foot below, one
(1) foot horizontally from, or one (1) foot above any door, window, or gravity air inlet.
Power Vent - Minimum four (4) feet below, four
(4) feet horizontally from, or four (4) feet above any door, window, or gravity air inlet.
d. Minimum four (4) feet horizontally from electric
meters, gas meters, regulators, and relief valves. This distance may be reduced if equipment is protected from damage due to condensation or vapor by enclosure, overhangs, etc.
e. Minimum twelve (12) inches from overhang or
corner of building.
10. Enclose vent passing through occupied or unoccupied spaces above the boiler with material having a fi re resistance rating of at least equal to the rating of the adjoining fl oor or ceiling. Maintain minimum clearances to combustible materials. See Figure 1.
Note: For one or two family dwellings, fi re
resistance rating requirement may not need to be met, but is recommended.
11. Plan venting system to avoid possible contact with plumbing or electrical wires. Start at vent connector on top of boiler and work towards vent terminal.
12. Once a vent pipe manufacturer and system is chosen never mix and match vent systems.
13. If a non-standard length pipe is required:
Gasketed Vent System: The use of the adjustable
length pipe (P/N 8116319U) is recommended to complete a non-standard pipe length. This pipe requires a minimum installed length of 12¾ inch and can adjust across a 7 inch gap up to a maximum of 19¾ inch long. (Note for the adjustable pipe the installed length should be measured from the centerline of the bead on the male end of the fi rst pipe to the end of the female pipe excluding the locking band of the second pipe with a single gasket.) Only in the event the adjustable length pipe is not suffi cient a standard length pipe may be cut using the procedure outlined below for the Gasket­Less Vent System.
GNINRAW
fohtgneldellatsnimumixamdeecxereveN
.epiphtgnelelbatsujdarofsehcni¾91
.elbissopsiegakaelsageulffoksiR
ECITON
rodelifdnaepiphtiwerauqsebtsumtuC
ylluferaC.gniniojerofebhtoomsdednas
e
.launamsihtnideificeps
C. Install Vent Pipe, Burnham Gasketed Vent System.
1. Procedure for Joining Burnham Gasketed Vent Pipe and Fittings. See Figure 3.
htiwdnahybepiptucfossendnuorerusn
VTRhtiwtniojlaeS.gnillatsnierofebsevolg
Figure 3: Burnham Gasketed Vent Joint Detail
11
a. Wipe the male end of each joint using an alcohol
pad to remove any dirt and grease.
b. Align weld seams in pipes and use a slight
twisting motion to FULLY insert male end into female end of joint. Ensure bead in male end of pipe is below locking band and rest against the end of the female pipe. Verify the factory­installed gasket is not dislodged or cut.
c. Tighten locking band by HAND with a 5/16”
nut driver until snug plus ¼ turn. DO NOT SECURE JOINTS WITH SHEET METAL SCREWS OR POP RIVETS. DO NOT PUNCTURE THE VENT SYSTEM!
d. Once the installation is complete, operate
appliance and inspect all joints to ensure that fl ue gases and/or liquid condensate will not escape.
D. Separate Horizontal Venting System. See Figures 4,
5A and 5B.
Vent Piping
1. This boiler is supplied with components as standard equipment for installation of the separate horizontal venting system.
2. Do not exceed maximum vent/air intake lengths. Refer to Table 4.
3. Recommended horizontal installation consists of vent being sloped down ¼ inch per foot away from boiler. See Figure 4.
4. Use appropriate designed thimbles when passing through combustible walls (thimble use optional for noncombustible walls). Insert thimble through wall from outside. Secure outside fl ange to wall with nails or screws, and seal ID, OD and vent holes with sealant material. Install inside fl ange to inside wall, secure with nails or screws, and seal with sealant material.
5. For noncombustible wall application when thimble is not used, size opening such that bell with locking band attached cannot pass through.
6. Join vent terminal to vent pipe. See Figures 5A and 5B.
7. Insert vent pipe through thimble/opening from outside and join to vent system. Apply sealant between vent pipe and opening/thimble to provide weathertight seal.
Air Intake piping - See Figures 4, 5A and 5B.
8. Locate air intake termination on the same wall as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with vertical venting and sidewall combustion air inlet or visa versa, if installation conditions do not allow alternate arrangement.
9. Do not exceed air intake length. See Table 4.
10. Use single wall metal or PVC pipe. a. Air intake pipe diameter is based on boiler size.
SCG-3 & SCG-4 uses 3 inch diameter piping. SCG-5 & SCG-6 uses 4 inch diameter piping. SCG-7 thru SCG-9 uses 5 inch diameter piping.
11. Air intake termination must be located:
Horizontal - At least twelve (12) inches above
grade plus the expected snow accumulation.
12. Start at collar on burner enclosure (inside boiler jacket) and work towards the air intake terminal.
13. Maintain minimum of ¼ inch per foot slope on horizontal runs. Slope towards air inlet terminal when possible. If not, slope towards boiler.
14. The air intake pipe must be adequately supported with straps or supports no less than fi ve (5) feet apart on horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts without collapse.
15. Inlet air pipe penetration:
Horizontal - Size wall penetration to allow easy
insertion of air inlet piping. Seal around pipe with sealant to form weathertight exterior joint.
16. Seal all joints airtight, using silicone caulk or self­adhesive aluminum tape.
17. Install Air Intake T erminal :
Horizontal - Remove four (4) screws from cover
plate and remove cover plate from terminal. Insert intake piping into intake terminal collar. Secure terminal to intake piping and seal joint with silicone caulk or self-adhesive aluminum tape. Apply continuous bead of silicone caulk around the back of the intake terminal, approximately ¼ inch from its edge. Push inlet terminal inward until terminal’s back fl ange is against the wall surface. Secure the terminal with noncorrosive fasteners (stainless steel, brass or aluminum) to the wall. Reinstall the cover plate with four (4) screws. Apply a bead of silicone caulk to perimeter of intake terminal’s back fl ange to provide a weathertight seal.
12
Figure 4: Recommended Separate Horizontal – Vent/Air Intake Installation
13
14
Figure 4B: Alternate Separate Horizontal – Vent/Air Intake Installation
Figure 5A: Separate Horizontal – Vent/Air Intake Terminal Confi guration (SCG-3 thru 7)
15
16
Figure 5B: Separate Horizontal – Vent/Air Intake Terminal Confi guration (SCG-8 and 9)
E. Separate Vertical Venting System - See Figures 6, 7, 8A, 8B and 9.
ECITON
.reliob
foorfoesuehteriuqersnoitartenepfooR
htiwdeilppuston-rallocmrotsdnagnihsalf
Vertical Venting
1. Do not exceed maximum vent lengths. Refer to Table 4.
2. Installation of a vertical vent tee 8116304U is required on all vertical vent applications. See Figures 6 and 7. Attach vertical vent drain tee directly to elbow or horizontal pipe from an elbow immediately after vent connector.
3. Slope horizontal runs minimum ¼ inch per foot. Slope towards vertical vent drain tee. Position weld seams in vent pipes, in all horizontal runs, at the top to avoid condensate from lying on the seams.
4. Install fi re stops where vent passes through fl oors, ceilings or framed walls. The fi re stop must close the opening between the vent pipe and the structure.
5. Whenever possible, install vent straight through the roof. Refer to Figure 7 if offset is necessary. Maintain minimum clearance to combustible materials.
6. Install V ent Terminal. a. Size roof opening to maintain minimum
clearance from combustible materials.
b. Extend vent pipe to maintain minimum vertical
and horizontal distance of twelve (12) inches from roof surface. Allow additional vertical distance for expected snow accumulation. Provide brace as required. Refer to Figures 8A and 8B.
ECITON
foorfoesuehtseriuqergnitnevlacitreV
tneverpotrallocmrotsadnagnihsalf
.erutcurtsehtgniretnemorferutsiom
c. Install storm collar on vent pipe immediately
above fl ashing. Apply Dow Corning Silastic 732 RTV Sealant between vent pipe and storm collar to provide weathertight seal.
d. Attach vent terminal.
Vertical Air Intake Piping
7. Do not exceed maximum air intake length. Refer to Table 4.
8. Locate air intake termination on the same roof location as the vent termination if possible, to prevent nuisance boiler shutdowns. However, boiler may be installed with vertical venting and sidewall combustion air inlet or visa versa, if installation conditions do not allow alternate arrangement.
9. Use single wall metal pipe or PVC and fi ttings available at most heating distributors.
a. Air intake pipe diameter is based on boiler size.
SCG-3 & SCG-4 uses 3 inch diameter piping. SCG-5 & SCG-6 uses 4 inch diameter piping. SCG-7 thru SCG-9 uses 5 inch diameter piping.
10. Air intake termination must be located: Vertical - At least twelve (12) inches above the roof
surface plus the expected snow accumulation.
11. Start at collar on burner enclosure (inside boiler
jacket) and work towards the air intake terminal.
12. Maintain minimum of ¼ inch per foot slope on
horizontal runs. Slope down towards boiler.
13. The air intake pipe must be adequately supported
with straps or supports no less than fi ve (5) feet apart on horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts without collapse.
14. Inlet air pipe penetration:
Vertical - Size roof opening to allow easy insertion
of inlet piping and allow proper installation of ashing and storm collar.
a. Use appropriately designed vent fl ashing
when passing through roofs. Follow fl ashing manufacturers’ instructions for installation procedures. Flashing manufacturers are Air­Jet, American Metal Products, Metal Fab, and Simpson Dura-Vent.
b. Extend air intake pipe to maintain minimum
vertical and horizontal distance of twelve (12) inches from roof surface. Allow additional vertical distance for expected snow accumulation. Provide brace as required. Refer to Figures 8A and 8B.
c. Vertical air intake requires fl ashing and a storm
collar to prevent moisture from entering the structure.
17
d. Install storm collar on air intake pipe
immediately above fl ashing. Apply Dow Corning Silastic 732 RTV Sealant between air intake pipe and storm collar to provide weathertight seal.
e. All exposed air intake piping must be
constructed of corrosion resistant material such as aluminum, stainless steel or PVC.
15. Seal all joints airtight, using silicone caulk or self­adhesive aluminum tape.
16. Install Air Intake Terminal:
Vertical - Insert intake piping into intake terminal
collar. Secure terminal to intake piping and seal joint with silicone caulk.
18
Figure 7: Attic OffsetFigure 6: Vertical Vent Installation
19
20
Figure 8A: Vertical Vent/Air Termination (3” Vent Terminal)
Extend Vent/Air Intake Piping to maintain minimum vertical (“X”) and minimum horizontal (“Y”) distance of twelve (12) inches from
roof surface. Allow additional vertical (“X”) distance for expected snow accumulation.
Figure 8B: Vertical Vent/Air Termination (4” Vent Terminal)
Extend Vent/Air Intake Piping to maintain minimum vertical (“X”) and minimum horizontal (“Y”) distance of twelve (12) inches from roof surface. Allow ad-
21
ditional vertical (“X”) distance for expected snow accumulation.
22
Figure 9: Vertical Air Intake Piping
F. Combination Horizontal Venting System –SCG-3 Through SCG-6 ONLY – See Figures 10 and 11.
ECITON
tonstnenopmocseriuqermetsystnevsihT
.reliobehthtiwdeilppus
2.
Install Combination Vent/Air Terminal. See Figure 11.
a. After determining the location with reference to Section B - General Venting Guidelines, cut a 6-1/8 inch square
opening in the wall for the air box sub-assembly which is 6 inch square.
b. Remove and save shipping screw from end panel with collar and vent pipe assembly. This will be reinstalled in a later
step.
1. Do not exceed maximum vent/air intake lengths. Refer to Table 4.
21060116rebmuNtraPnotraCtneV)wolebsmetisedulcni(
noitpircseDrebmuNtraPtnenopmoC
A)gnol'2xerauqs"6(ylbmessA-buSxoBriA 11060116
B)erauqs"01(revoCllaWroiretxE 61060117
CrecudeRepiPtneV"3x"4 93
D)2(revoCroiretxElaeS-etalP 71060117
E)91(wercSlateMteehSleetSsselniatS"½x8# 74006808
F)8(wercSenihcaMleetSsselniatS"¼x23-01# 24806808
26118
G)4(recapSmunimulA"½x23-01# 71616808
BMOC
STNENOPMOCMETSYSTNEVLATNOZIROHNOITANI
23
c. From exterior of building, insert air box sub-
assembly into square opening. Push air box inward until wall fl ange is against wall, check for level and mark the location of the four (4) securing holes on the exterior wall. Remove air box from wall.
d. Drill four (4) pilot holes, properly sized for the
non-corrosive fasteners (stainless steel, brass, or aluminum) to be used to secure the wall fl ange to the exterior wall. (Securing screws not supplied with kit.)
e. Attach four (4) 1/2 inch long threaded aluminum
spacers to the outer fl anges of the exterior wall fl ange with four (4) number 10 - 32 x 1/4 inch stainless steel machine screws provided. (See Figure 11.)
f. Apply a 1/4 inch thick continuous bead of
silicone caulk to perimeter of exterior wall ange’s back surface to provide a weathertight seal.
g. Reinstall air box sub-assembly into opening in
exterior wall and secure to wall.
GNINRAW
.desuebtsumsrenetsafevisorroc-noN
h. Apply a bead of silicone caulk to perimeter of
wall fl ange, where the wall and fl ange join. Use a tool or your fi nger and apply pressure while smoothing caulking to provide a weathertight seal.
i. From interior of building, insert end panel with
collar and vent pipe assembly into open end of air box sub-assembly. (See Figure 11.)
j. Secure end panel to air box sub-assembly with
shipping screw and thirteen (13) number 8 sheet metal screws provided.
k. From exterior of building, position 10 inch
square exterior wall cover over exterior wall ange. Insert 3 inch diameter vent pipe into center opening in terminal cover. Align four (4) holes on cover with 1/2 inch long threaded spacers on wall fl ange. Secure terminal cover with four (4) number 10 - 32 x 1/4 inch stainless steel machine screws provided.
l. Apply a bead of silicone caulk to perimeter of
plate-seal and around pipe. Secure plate-seal to exterior cover with six (6) #8 stainless steel sheet metal screws provided. Smooth caulk around plate-seal and pipe to provide weathertight seal.
m. Install Vent Terminal supplied with boiler to vent
pipe penetrating through terminal cover. Join terminal and pipe with locking band and seal with RTV (see Figure 3).
3. Install Vent Piping. See Figure 10 and 11.
a. Start at vent connector on boiler and work
towards combination vent/air terminal.
b. Installation of a vertical vent tee 8116304U is
required on all vertical vent applications. See Figures 12 and 13. Attach vertical vent drain tee directly to elbow or horizontal pipe from an elbow immediately after vent connector.
c. Slope horizontal runs minimum ¼ inch per foot.
Slope towards vertical vent drain tee. Position weld seams in vent pipes, in all horizontal runs, at the top to avoid condensate from lying on the seams.
d. Use 3/4 inch pipe strap to support horizontal runs
and maintain vent location and slope. Maximum support spacing is fi ve (5) feet.
e. Install vent piping to connect vent connector
on boiler and combination vent/air terminal. Reference Section B - General Venting Guidelines for proper procedure for joining pipe and fi ttings.
f. Connect vent piping to combination vent/air
terminal. See Figure 10.
4. Install Air Intake Piping. See Figures 10 and 11.
a. Do not exceed air intake length. See Table 4. b. Use single wall metal pipe or PVC and fi ttings
available at most heating distributors.
c. Air intake pipe diameter is based on boiler size.
SCG-3 & SCG-4 uses 3 inch diameter piping. SCG-5 & SCG-6 uses 4 inch diameter piping. SCG-7 thru SCG-9 uses 5 inch diameter piping.
d. Start at collar on burner enclosure (inside boiler
jacket) and work towards the combination vent/ air terminal.
e. Maintain minimum of 1/4 inch per foot slope on
horizontal runs. Slope down towards boiler.
f. The air intake pipe must be adequately supported
with straps or supports no less than fi ve (5) feet apart on horizontal runs. The complete air intake piping system must be rigid and able to withstand minor impacts without collapse.
g. Connect Air Intake Piping to Combination Vent/
Air Terminal. See Figure 10.
NOTE: When installing 3 inch diameter air intake piping for a SCG-3 or SCG-4 application, the use of a 4 inch x 3 inch reducer will be required to connect air intake piping to combination vent/air terminal. (Reducer included with combination horizontal venting kit).
h. Seal all joints airtight, using silicone caulk or
self-adhesive aluminum tape.
24
Figure 10: Combination Horizontal – Vent/Air Installation (SCG-3 thru 6)
25
26
Figure 11: Combination Horizontal – Vent/Air Terminal Installation (SCG-3 thru 6)
G. Combination Vertical Venting System – SCG-3 Through SCG-6 ONLY – See Figures 12, 13 and 14.
ECITON
tonstnenopmocseriuqermetsystnevsihT
.reliobehthtiwdeilppus
rebmuNtraP
noitpircseD
rebmuNtraPnotraCtneV 10-22200110-322001
eeTretratS 10-42200110-522001
rotpadAriA/tneV 10-622001
4-GCS&3-GCS6-GCS&5-GCS
STNENOPMOCMETSYSTNEVLACITREVNOITANIBMOC
27
1. Saf-T Vent SC is an advanced concentric vent system designed for zero clearance installation in residential applications. The inner wall is constructed from superferritic AL29-4C® stainless steel. The outer wall is also constructed from stainless steel, providing durability and a lasting nish.
2. As a Special Gas Vent system: Saf-T Vent is approved for use on ANSI Category I, II, III, and IV Gas-Burning Appliances and certain Direct Vent Appliances. Saf-T Vent SC is appropriate for use on appliances that specify an AL29-4C venting system.
3. As a Sealed Combustion system: The unique concentric design of Saf-T Vent SC also allows it to function as a pipe-in-a-pipe vent. Products of combustion are exhausted out through the inner wall while combustion air is drawn in through the outer wall. An appliance can be direct-vented with only a single penetration through the building structure.
This application must be approved by the Appliance Manufacturer.
Note: Saf-T Vent SC includes an integral seal and
does not require RTV sealant. However, sealant may be necessary when connecting Saf-T Vent SC components directly to certain appliance fl ue collars and to the gasket-less Saf-T Vent GC and Saf-T Vent CI vent systems.
For applications up to 550°F/288°C, approved
sealants include GE RTV 106 and Dow Corning
736.
For applications up to 300°F/149°C, approved
sealants include GE RTV 106 and Dow Corning
732.
4. Pre-Installation Considerations:
• Proper planning prior to installation is essential
as to avoid possible contact with concealed plumbing or electrical wiring inside walls, oors or ceilings as well as maintaining proper clearances. Be sure to plan a suffi cient number of supports for the entire system that will maintain the required straight-line pitch and hold
the system in place. A continuous straight-line pitch of at least ¼” (2°) to the foot on horizontal runs must be maintained in order to properly rid the system of the corrosive condensate.
5. General Installation Requirements:
• Saf-T Vent SC vent sections, or other Saf-T Vent products, must be used throughout the entire length of the system. Alternatives such as galvanized pipe, PVC, nonmetallic pipe, prefabricated chimney, fi eld-fabricated vents or Type B vent sections must not be used. Do not mix pipes, fi ttings, or joining methods from different manufacturers.
• More than one appliance may not be interconnected to any part of the venting system.
• Any penetrations of ceilings, fl oors or walls must be properly fi re-stopped.
• Whenever gas-burning equipment is installed in the same space where halogenated substances may exist (refrigerants, solvents, bleaches, salts, etc.), clean outside air must be utilized for combustion.
• The vent system shall not be routed into, through or within any other actively used vent or chimney.
• Seal weather exposed joints of the outer jacket with foil tape or an exterior grade silicone sealant.
• Combustible Material is any material made of or surfaced with wood, compressed paper, plant bers, or other materials that are capable of being ignited or burned. Such material shall be considered combustible even though it is fl ame- proofed, fi re-retardant, or plastered. (Source: NPFPA54/ANSI Z223.1-1999.)
• Non-Combustible Material is any material that is not capable of being ignited and burned, such material consisting entirely of, or a combination of, steel, iron, brick, tile, concrete, slate, asbestos, glass and plaster. (Source: NPFPA54/ ANSI Z223.1-1999.)
28
Clearances to Combustibles:
otecnaraelC
retemaiD
elbitsubmoC
lairetaM
"0
"4-"3
"1004
"0
"1055
"0055ynAlairetamelbitsu
eulFmumixaM
)F°(.pmeTsaG
055
033
004,nepoedis1tsaelta,desolcnenU
noitatneirOerusolcnE
,lacitreV
stesffOoN
,latnoziroH
htiwlacitreV
sffO
ste
elbitsubmocybdesolcneylluF
sedisllanolairetam
anolairetamelbitsubmoc
sedis3fomumixam
bmocnoN
Loading...
+ 64 hidden pages