Product Features Boiler Sequence 6
Single Boiler Control Mode 9
Multiple Boiler Control Mode 10
EMS Boiler Control Mode 11
Manual Boiler Control Mode 14
Auiliary Device 15
Front Panel
Features 16
Display Mode 17
Menu Navigation 18
Setpoints Menu 19
Ignored Ignored Ignored Ignored Ignored By Operator
Ignored Ignored Closed Closed Closed Ignored
Remote On/Off
(Enable)
Input (RO)
Remote Control
Input (C+C-)
Communication
Network
Additional
Information
Enable/
Disable
No No
Peer-To-Peer
or
Modbus*
Enable/
Disable
Peer-To-Peer
or
Modbus*
Enable/
Disable
Remote
Setpoint
Peer-To-Peer
or
Modbus*
Enable/
Disable
Remote
Setpoint
Peer-To-Peer
or
Modbus*
On/Off Ignored
Remote
Modulation
Modbus
Only
Ignored
Modbus Only
Page 9 Page 10 Page 11 Page 12 Page 13 Page 14
* If Modbus is selected the Peer-To-Peer Network can not be used. Modulating Lead/Lag features require the Peer-ToPeer Network.
Sage Boiler Control Instruction Manual Page 2 of 56
Introduction
Quick Reference
Abbreviation List
Abbreviation Description
AL Flame Safeguard Alarm
BIT Boiler Inlet Temperature
BOT Boiler Outlet Temperature
BP Boiler Pump
BV Blocked Vent Switch
C Common Termination Point
CA Low Combustion Air Flow
CH Call For Heat (CFH)
CS Fuel Valve Energized
DH Domestic Hot Water Heating Demand
DP Domestic Hot Water Priority (DHWP)
SBC Sage Boiler Control
EMS Energy Management System
GP High and Low Gas Pressure Switches
HL High Limit Aquastat
HP High Pressure Gas Switch
IN Boiler Inlet Water Temperature
LC Low Water Cutoff Switch
LL Lead Lag
LO Lockout Indicator
LR Local / Remote
M Electric Motor
Mix 3 Way Mixing Valve
OA Outside Air Temperature
OL Operating Limit Aquastat
OO Burner On / Off Switch
OUT Boiler Outlet Water Temperature
RO Remote On / Off
RST Remote System Temperature
SH Space Heating Demand
SI Spare Input (Programmable)
SO Spare Output (Programmable)
SP Setpoint (As found in “Ope rational SP” and “Remote SP”
SP System Pump
VI Vent Inducer
WF Low Water Flow
WWSD Warm Weather Shutdown
Termination Number Identification (Typical):
Description
Mixing Valve
Control, (MR, MS)
Termination
Numbers
Sage Boiler Control Instruction Manual Page 3 of 56
Introduction
Overview
Sage Boiler Control Overview
The Sage Boiler Control (SBC) is a complete boiler monitoring and automation system. The SBC provides advanced
boiler modulation, operating control, diagnostics, multiple boiler lead-lag and auxiliary device control. The SBC provid es
advanced control features in an easy to use package.
Flexible, Field Selectable Control
Control modes, water system, boiler auxiliary and
modulating lead/lag control features are menu selectable
without the need for external programmers, laptops or
down loads. Every boiler is shipped with factory defaults
that make field menu selections unnecessary unless you
are applying additional control features.
Boiler Monitoring and Diagnostic Displays
The SBC’s two line by sixteen character LCD display
may be used for monitoring boiler inlet and outlet,
remote system and outside air temperatures, modulation
rate setpoint and modulating percent and mixing valve
demand percent. Additionally, the display automatically
presents boiler sequence messages, alarms, hold and
lockout messages. A diagnostic menu is included that
provides the last 10 alarm messages and boiler inlet
temperature alarm history. Boiler inlet temperature
alarm history includes time and date, the lowest inlet
temperature reached and the amount of time the water
temperature dropped below the alarm setpoint.
Modulation Rate and On/Off Modes
The SBC may simply control boiler modulation and
on/off output based on the boiler water outlet
temperature and an operator adjusted setpoint.
However, using parameter selections, the SBC allows
the boiler modulation and on/off output to respond to
remote system water and outside air temperatures,
Domestic Hot Water Priority (DHWP) input or Energy
Management System (EMS) modulation rate demand,
remote setpoint or remote start/stop commands.
Parameter selections of remote system water
temperature and remote mode determine the choice of
one of six different control modes.
Advanced Availability
The above control modes are menu selectable options.
However, if a selected sensor fails, the SBC
automatically changes to a control mode that will allow
continued automatic operation of the boiler. For
example, in the event of a remote system temperature
sensor failure, the SBC will automatically switch to boiler
outlet temperature sensor based control.
Outdoor Air Reset
When selected the modulation rate setpoint is
automatically adjusted based on outside air temperature.
Outdoor air “reset” setpoint saves fuel by adjusting the
water temperature of a heating boiler lower as the
outside air temperature increases.
Warm Weather Shutdown (WWSD)
Some boilers are used primarily for heating buildings,
and the boilers can be automatically shutdown when the
outdoor air temperature is warm. When outside air
temperature is above the WWSD setpoint, this function
will prevent the boiler, boiler pump and/or the system
pump from starting.
Domestic Hot Water Priority (DHWP)
Some boilers are used primarily for building space
heating, but also provide heat for the domestic hot water
users. When the outdoor temperature is warm, the
outdoor reset setpoint may drop lower than a desirable
domestic hot water temperature. When enabled and a
DHWP contact input is detected, the hot water setpoint
is adjusted to be greater than a field adjustable DHWP
Setpoint.
Water Side Control Outputs
In order to maximize the life and availability of hot water
systems it may be desirable to automate mixing valves,
boiler pumps, system pumps, and standby system
pumps. The SBC makes this type of automation totally
integrated and cost effective. The control of these
devices is field selectable through simple yes/no menu
selections.
Combustion Air Side Control Outputs
Boiler room Combustion air dampers (fresh air dampers)
and Vent Inducer control outputs are field selectable
options.
Peer-To-Peer Network
The SBC includes state-of-the-art modulating lead-lag
sequencer for up to eight (8) boilers capable of auto
rotation, outdoor reset and peer-to-peer communication.
The peer-peer network is truly “plug and play”.
Communication is activated by simply connecting a
RJ11 telephone line between boilers. The SBC provides
precise boiler coordination by sequencing boilers based
on both remote system water temperature and boiler
modulation rate. For example, the lead boiler can be
configured to start a lag boiler after operating above 90%
modulation rate for longer than an adjustable time. The
boilers are modulated in “unison” (parallel) modulation
rate to ensure even heat distribution
Modbus Communication Interface
A factory configured RS485 Modbus interface is
available
for Energy Management System (EMS) or SCADA
system monitoring and control.
Sage Boiler Control Instruction Manual Page 4 of 56
Introduction
Overview
Standby System Pump
Remote System
System Pump
System
Supply Water
Switch
Domestic Hot
Temperature
Feedback
Water Override
System Pump
Supply
Domestic
Hot Water
System
Modbus RS-485, RJ-11
Local / Remote Switch
High Temperature Limit
Connection
Boiler Outlet TemperatureBoiler Inlet Temperature
Primary
Spare Output
Call For Heat Relay
Fuel Valve Energized
Control
Alarm (Lockout)
Low Fire
Remote On / Off (Enable)
Lockout Indicator
Building Automation
Control
M
Mixing Valve
Boiler Pump
Low Water Flow Switch
Low Water Cutoff Switch
Return Water
Outside Air
Temperature
Sage Boiler Control
FAN
Switch
Air Flow
Combustion
Control
Modutrol Motor
Switch
Damper
Combustion Air
M
Supply
Fresh Air
Boiler On/Off
Boiler
Jacket
Fuel
Fuel Switches
Supply
Sage Boiler Control Instruction Manual Page 5 of 56
Product Features
Boiler Sequence
BOI LER STATE
LCD Display
Pa r a me ter / Notes
Boiler Disable or R em ot e On/Off
Outdoor Air T em p >
Warm Weat her Shut down Set point
Domestic Hot Water Priority
RO
O+,O-
DP
Terminal Number
-
44,30,
75
20,74
Start/ Sto p Seq u en ce St atesPre-Seq u en ce States
Parameter/Note
Boiler Disable
Warm Weather
Shutdown
Locko ut
b &caaa
Pump Purge
Standby
Purge / Pilot Ignition
Limit Hold
-3/d---534/d
-
Low Fire / Ignition
Main I gnition
Low Fire Hold
Boiler Running
Pump Cooldown
Fan Post Purge
54/d
Boil e r Enabl e/Disable On
Domestic Hot Water Demand Monitored
Low Fire Hold
Fuel Valv e Energiz ed
Flame Saf eguard Alarm
Sys t em Pum p F eedback
Call For Heat
Recycling Limits
(LC, OO, WF, GP and HL inputs)
Limits
Inputs
Non-Recycling Limits
(Combustion Air Flow (CA Input))
Call For Heat Relay
Lockout Indicator
( M anual R es et R equire d)
Spare Output
Boiler Pump
System Pump
Relay OutputsInter lo ck Inpu ts
Syst em Pum p Bac k up Pump
Combustion Air Damper
System Alarm
Mix ing Valve Out put
Blower High Speed
Purge %
Modulation
Firing Rat e
Modulation Outputs
Low F ire %
Blower 0 Volts
SI
CS
AL
SI
R+,R-
OR
BO,BC
LC , O O ,WF,
GP,HL
CA
CH
LO
VI
BP
SP
SO
SO
SO
MS,MR
V+,V-,
P+,P-
V+,V-,
P+,P-
V+,V-,
P+,P-
V+,V-,
P+,P-
V+,V-,
P+,P-
9
-
-
9
70,71,
72
8,27,
28
-
-
-
-
2,30
25,30
10
10,27/
e
10
6,79,
80
49
52
-
9,51/f
50
System Pump Feedback Monitored
Call For Heat
Recycling Limits Made
Non-Recycling Limits Made
Call For Heat Relay On
Spare Output On
Boiler Pump On
System Pump On
Starts in response to System Pump Feedback In put SI
Combustion Air Damper Open
Alarm Status is Monitored
Modulate
Notes
a. Boiler Pump is “On” when the Boiler Pump is set to “On Always” or the boiler is lead boiler and Boiler Pump is set to “On Lead”
b. Boiler Pump is "On" when the Boiler Pump is set to "On Always" and WWSD is set to "WWSD of System Pump" or “Off”
c. System Pump is "On" when the System Pump is set to “yes” and WWSD is set to either "WWSD of Boiler" or "Off"
d. Boiler pump is "On" during Prepurge and Post Purge when Boiler Pump is set to "Purge" or boiler is lead & Boiler Pump is set to “On Lead”
e. Combustion Air Damper Spare Output is maintained “On” for 2 minutes after the Call For Heat is removed.
f. Modulation rate is held at purge % when low fire input is not provided.
Sage Boiler Control Instruction Manual Page 6 of 56
Product Features
Boiler Sequence (Continued)
Pre-Sequence States
BOILER
STATE
LCD Display
Boiler
Disabled
Warm
Weather
Shutdown
Lockout Any Mode
Standby
Start/Stop Sequence States
BOILER
STATE
LCD Display
Pump Purge
Limit Hold Any Mode
Purge / Pilot
Ignition
Low Fire /
Ignition
Main Ignition Any Mode
Low Fire
Hold
Boiler
Running
Fan Post
Purge
Pump
Cooldown
CONTROL MODE
LCD Display
Any Mode
(Except for
Remote Control)
Any Mode
(Except for
Manual Mode)
Outlet Sensor &
Local SP Mode
Remote Sensor
& Local SP
Mode
Outlet Sensor &
Remote SP
Mode
Remote Sensor
& Remote SP
Mode
Remote Control
Mode
Manual
Operation Mode
CONTROL MODE
LCD Display
Any Mode
(Except
Manual Mode)
Any Mode
Any Mode
Any Mode The modulation output is held at the Low Fire for the Low Fire Hold time.
Any Mode
Any Mode
Any Mode
Description
Boiler is prevented from starting; Remote On/Off (Enable) (Terminal RO) Input is not
energized.
Boiler is prevented from starting, Warm Weather Shutdown (WWSD) is enabled and
outside air temperature is above the WWSD Setpoint
Boiler is prevented from starting, Flame Safeguard lockout is present. A Flame
Safeguard manual reset is required
Control monitors boiler outlet temperature, a Call For Heat is initiated when boiler
outlet temperature is below the Operational Setpoint
Control monitors Remote System Temperature, a Call For Heat is initiated when
Remote System Temperature is below the Operational Setpoint
Control monitors boiler outlet temperature, a Call For Heat is initiated when boiler
outlet temperature is below the Remote Setpoint Input (Terminal C+,C- or Modbus
Interface)
Control monitors Remote System Temperature, a Call For Heat is initiated when
Remote System Temperature is below the Remote Setpoint Input (terminal C+,C- or
Modbus Interface)
Control monitors Remote On/Off (Enable) input (Terminal RO or Modbus Interface), a
Call For Heat is initiated when input is energized
A Call For Heat is initiated when Manual Mode Menu item Boiler On/Off is set to On
Description
Once a Call For Heat is initiated and Boiler Pump Purge is selected, the pump output
is energized until the Pump Prepurge Time is complete. If the Call For Heat condition
still exists at the end of the Prepurge Time (the temperature of the water at the sensor
may rise with boiler water flowing passed it) the pump will continue to operate and the
Call For Heat Relay is energized
Power is applied to the safety limit string. If any limits does not pass power (is not
energized), the alarm LED and LCD display shows the reason the start sequence is
on Hold. Refer to Trouble shooting section for explanation of individual lockout and
alarm messages
After the limit string passes power, the fan is started, the modulation output is set to
Purge Rate. When the purge period is complete, the flame safeguard sequences on
the ignition transformer and pilot
When the Spare Input Low Fire is selected, modulation output is set to the Low Fire
Speed when the Spare Input is energized.
The main gas valve input is energized and the modulation output is held constant for
an ignition stabilization period
When this Low Fire Hold time is complete, the modulation output is released to
modulate
When water temperature is above setpoint, there is a Flame Safeguard or Limit fault,
the Call For Heat is ended and the modulating output is set to Purge Rate for the Post
Purge Time
When Boiler Pump Purge is selected, the boiler pump remains “on” until the boiler
outlet temperature is less than the Post Purge Delta (default is 5 F) above the Boiler
Inlet Temperature.
Sage Boiler Control Instruction Manual Page 7 of 56
Product Features
Boiler Sequence (Continued)
Multiple Boilers
185
Setpoint
High Fire Limit
(Parameter 37)
1
- Lead Boiler Start
2
- Temperature Based Lag Boiler Start
3
- Modulation % Based Lag Boiler Start
4
- Lag Boiler Stop
5
- Lead Boiler Stop
Notes
- The “Boiler Address” parameter assignment determines the boiler sequencing order.
- The Lead Boiler automatically rotates (when “Rotate” parameter is enabled) based on field adjusted time
- Lead Boiler is the first boiler to turn on and the last boiler to turn off, (First On, Last Off, FOLO).
- Lag Boilers are turned on in order and turned off in reverse order, (First On, Last Off, FOLO).
- Tripped boilers are replaced without waiting for the Boiler On Delay timer. If a tripped boiler becomes available
180
SYSTEM
BOILER
PLANT LOAD
175
TEMPERATURE
100
50
FIRING RATE
0
3
2
1
0
(# BOILERS REQURED)
Lead Boiler
Start
1
Start
st
1
Fast
Load
Change
Lag
2
2
Slow
Load
Change
3
2
Start
nd
Lag
Stop
nd
2
Lag
454
Stop
1st Lag
Lead Boiler
Boiler Start and Stop Peer-To-Peer Network Sequence Diagram
(3 boiler system shown, typical for up to 8 boilers)
Water temperature is below the setpoint by more than the “On Point” differential
Water temperature is below the setpoint by more than the “On Point” differential for longer than the adjustable
time delay (“Boiler On Delay” parameter).
The boiler modulation rate has been above the adjustable limit (“LL Start Trigger” parameter) for longer than the
time delay.
The boiler modulation rate has been below the adjustable limit (“LL Stop Trigger” parameter) for long er than the
time delay. Additionally, lag boilers are stopped when water temperature is above the setpoint by more than the
“Off Point” differential for longer than the “Boiler Off Delay” parameter)
The last boiler remains on line until the water temperature is above the “Off Point” setpoint for longer than the
time delay.
(“Rotate After” parameter, default is 168 hours). When rotating, the lead boiler will move to the end of the lag
order and the 1
st
lag boiler will become the lead. The rest of the boilers will then move up in the lag order
accordingly.
it is returned to service.
5
Stop
Sage Boiler Control Instruction Manual Page 8 of 56
Product Features
Single Boiler Control
Display Shows: Outlet Sensor & Local SP Mode
Return
Water
Outside Air
Temperature
(O+, O-)
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
System
Circulator
System
Supply Water
DHW
Override
Switch (DP)
Domestic Hot
Water (DHW)
Supply
Outlet Sensor & Local SP Mode Application Diagram
(Showing Relevant Connections)
Features
Setpoints
The operator selects the setpoint and on and off points
from the LCD display.
Modulation Rate Control
Boiler automatically modulates to maintain the boiler
outlet temperature at setpoint.
Call for Heat
The Call For Heat is determined by the setpoint, on
and off points and boiler outlet temperature.
Options
Outside Air Reset
If enabled, the Outside Air Sensor will automatically
adjusted the setpoint.
Warm Weather Shutdown (WWSD)
If enabled, the WWSD will disable a boiler start when
outside air temperature is above a Warm Weather
Shutdown (WWSD) setpoint.
Domestic Hot Water Priority (DHWP)
If enabled, the DHWP will adjust the setpoint to satisfy
the DHWP setpoint when a DHWP input (DP) is
energized.
Boiler Inlet
Temperature
(BI, BC)
EMS System Hardwired Connections
Lockout Indicator (LO)
Soft Alarm (SO)
Remote On / Off (Enable) (RO)
RJ11, RS-485 Communication
Peer-To-Peer Network
for Modulating Lead/Lag
Or
Modbus Network
for Touch Screen or EMS Monitoring
Selecting This Control Mode
To select Outlet Sensor & Local SP Mode set the following
parameters:
System Configuration Menu:
Remote Control = “No”
Remote System Temperature Sensor = “No”
Remote On / Off (Enable) Input (RO) = Closed
[Jumper (RO) to (C)]
If the Remote On / Off (Enable) (RO) input is opened, the Call
For Heat Relay (CH) is de-energized.
Modbus Network
To establish a Modbus network set the following parameters:
Communication Menu:
Protocol = Modbus
Modbus Address = Give each boiler a unique address.
Baud Rate = Set identical to remote system
Parity = Set identical to remote system
Connect all boilers using a RJ11 ended telephone cable
If the Modbus network is activated the remote system may
monitor and/or control boiler operation. Refer to page 29 for
additional information.
Sage Boiler Control Instruction Manual Page 9 of 56
Product Features
Multiple Boiler Control
Display Shows: Remote Sensor & Local SP Mode
Outside Air
Temperature
(O+, O-)
Remote System
Temperature
(R+,R-)
System
Circulator
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
Boiler
Circulator
Boiler Inlet
Temperature
(BI, BC)
DHW Override
Switch (DP)
Wired to Each
ECM Controller
Boiler
Circulator
RJ11, RS 485
Peer to Peer
Network
Remote System
Temperature
(R+,R-)
Outside Air
Temperature
(O+, O-)
Connects to
Up to Eight
Boilers
Domestic Hot
Water Priority
(DP)
Remote Sensor & Local SP Mode Application Diagram
(Showing relevant connections for 3 boilers, typical for up to 8)
Features
Setpoints
The ope
rator selects the setpoint and on and off points
from the LCD display.
Modulation Rate Control
Boiler automatically modulates to maintain the Remote
System Temperature (RST) at setpoint.
Call for Heat
The Call for Heat is determined by setpoint, on and off
points and RST. If a Peer-To-Peer network is activated, a
Call for Heat is also initiated when the Lead boiler
modulation rate % is above an adjustable High Fire Rate
Limit (parameter 37) for too long a time.
Options
Outside Air Reset
If enabled, the Outside Air Sensor will automatically
adjusted the setpoint.
Warm Weather Shutdown (WWSD)
If enabled, the WWSD will disable a boiler start when
temperature is above a Warm Weather Shutdown (WWSD)
setpoint.
Domestic Hot Water Priority (DHWP)
If enabled, the DHWP will adjust the setpoint to satisfy the
DHWP setpoint when a DHWP contact input (DP) is
closed. When multiple boilers monitor the DHWP input, an
isolated contact is required for each boiler.
Selecting This Control Mode
To select Remote Sensor & Local SP Mode set the
following parameters:
System Configuration Menu:
Remote Control = “No”
Remote System Temperature Sensor = “Control”
Remote On / Off (Enable) Input (RO) = Closed
[Jumper (RO) to (C)]
If the Remote On / Off (Enable) (RO) input is opened, the
Call For Heat Relay (CH) is de-energized.
If the Remote System Temperature Sensor (RST) fails, the
control mode is automatically switched to Outlet Sensor &
Local SP Mode.
Peer-To-Peer Network
To establish a Peer-To-Peer network follow the procedure
provided on page 28.
If the Peer-To-Peer network is activated the Lead boiler
controls modulation rate and Call for Heat for all
networked boilers. Up to 8 networked boilers are fired in
“Unison” (all at the same modulation rate).
Sage Boiler Control Instruction Manual Page 10 of 56
Product Features
Energy Management System (EMS) Boiler Control
Display Shows: Outlet Sensor & Remote SP Mode
The setpoint is determined by the Remote Input (C+,C-)
or Modbus Input and operator sets the on and off points
from the LCD display.
Modulation Rate Control
Boiler automatically modulates to maintain the boiler
outlet temperature at setpoint.
Call for Heat
The Call For Heat is determined by setpoint, on and off
points and boiler outlet temperature.
Options
Warm Weather Shutdown (WWSD)
If enabled, the WWSD will disable a boiler start when
temperature is above a Warm Weather Shutdown
(WWSD) setpoint.
Outside Air Temperature may be displayed only.
Outside Air Reset and Domestic Hot Water Priority input
(DP) are ignored.
Boiler Inlet
Temperature
(BI, BC)
EMS System Hardwired Connections
Lockout Indicator (LO)
Soft Alarm (SO)
Remote On / Off (Enable) (RO)
Remote Setpoint (C+,C-)
RJ11, RS-485 Communication
Peer-To-Peer Network
for Modulating Lead/La g
Or
Modbus Network
for Touch Screen or EMS Monitoring
Selecting This Control Mode
To select Outlet Sensor & Remote SP Mode set the following
parameters:
System Configuration Menu:
Remote Control = “Remote SP”
Remote System Temperature Sensor = “No”
Local / Remote Input (LR) = Closed
Remote On / Off (Enable) Input (RO) = Closed
[Jumper (RO) to (C)]
When the Local / Remote Input (LR) is open, Remote Input
(C+,C-) is ignored and Outlet Sensor & Local SP Mode is
active.
If the Remote On / Off (Enable) (RO) input is opened, the
Call For Heat Relay (CH) is de-energized.
Modbus Network
To establish a Modbus network set the following parameters:
Communication Menu:
Protocol = Modbus
Modbus Address = Give each boiler a unique address.
Baud Rate = Set identical to remote system
Parity = Set identical to remote system
Connect all boilers using a RJ11 ended telephone cable
If the Modbus network is activated the remote system may
monitor and/or control boiler operation. Refer to page 29 for
additional information.
Sage Boiler Control Instruction Manual Page 11 of 56
Product Features
Energy Management System (EMS) Boiler Control (continued)
Display Shows: Remote Sensor & Remote SP Mode
Return
Water
Outside Air
Temperature
(O+, O-)
Remote System
Temperature
(R+,R-)
System
Circulator
System
Supply Water
Features
Setpoints
The setpoint is determined by the Remote Input (C+,C-)
and operator sets the on and off points from the LCD
display.
Modulation Rate Control
Boiler automatically modulates to maintain the Remote
System Temperature (RST) at setpoint.
Call for Heat
The Call For Heat is determined by setpoint, on and off
points and Remote System Temperature. If a Peer-ToPeer network is activated, a Call for Heat is also initiated
when the Lead boiler modulation rate % is above an
adjustable High Fire Rate Limit (Parameter 37) for too
long a time.
Options
Warm Weather Shutdown (WWSD)
If enabled, the WWSD will disable a boiler start when
temperature is above a Warm Weather Shutdown
(WWSD) setpoint.
Outside Air Reset and Domestic Hot Water Priority input
(DP) are ignored
(Showing relevant connections for 3 boilers, typical for up to 8)
Selecting This Control Mode
To select Remote Sensor & Remote SP Mode set the
following parameters:
System Configuration Menu:
Remote Control = “Remote SP”
Remote System Temperature Sensor = “Control”
Local / Remote Input (LR) = Closed [Jumper (LR) to (C)]
Remote On / Off (Enable) Input (RO) = Closed
[Jumper (LR) to (C)]
When the Local / Remote Input (LR) is open, Remote Input
(C+,C-) is ignored and Remote Sensor & Local SP Mode is
active.
If the Remote On / Off (Enable) (RO) input is opened, the
Call For Heat Relay (CH) is de-energized.
Peer-To-Peer Network
To establish a Peer-To-Peer network follow the procedure
provided on page 28.
If the Peer-To-Peer network is activated the Lead boiler
controls modulation rate and Call for Heat for all networked
boilers. Up to 8 networked boilers are fired in “Unison” (all
at the same modulation rate).
Wired to Each
ECM Controller
Boiler
Circulator
EMS System Connections
Lockout Indicator (LO)
Soft Alarm (SO)
Remote On / Off (Enable) (RO)
Remote Setpoint (C+,C-)
Remote System
Temperature
(R+,R-)
Outside Air
Temperature
(O+, O-)
Connects to
Up to Eight
Boilers
RJ11, RS 485
Peer to Peer
Network
Sage Boiler Control Instruction Manual Page 12 of 56
Product Features
Energy Management System (EMS) Boiler Control (continued)
Display Shows: Remote Control Mode
Return
Water
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
System
Circulator
System
Supply Water
Remote Control Mode Application Diagram
(Showing relevant connections)
Features
Modulation Rate Control
The Remote Input (C+,C-) or Modbus input sets
modulation rate. The setpoint is ignored.
Call for Heat
The Call For Heat is determined by Remote On/Off
input (RO) or Modbus input. The on and off points are
ignored. The boiler will turn off if the water
temperature increases past the temperature set on the
Operational Temperature Limit.
Options
Outside Air Reset and Domestic Hot Water Priority
input (DP) and Warm Weather Shutdown are ignored
.
Boiler Inlet
Temperature
(BI, BC)
EMS System Hardwired Connections
Lockout Indicator (LO)
Soft Alarm (SO)
Remote On / Off (Enable) (RO)
Remote Setpoint (C+,C-)
RJ11, RS-485 Communication
Modbus Network
EMS Monitoring and Control
Remote Firing Rate via Modbus
Remote on/off via Modbus
Selecting This Control Mode
To select Remote Control Mode set the following parameters:
System Configuration Menu:
Remote Control = “Remote Mod”
Remote System Temperature Sensor = “Display Only”
Local / Remote Input (LR) = Closed [Jumper (LR) to (C)].
When the Local / Remote Input (LR) is open, Remote Input
(C+,C-) is ignored and Remote Sensor & Local SP Mode is
active.
Modbus Network
To establish a Modbus network set the following parameters:
Communication Menu:
Protocol = Modbus
Modbus Address = Give each boiler a unique address.
Baud Rate = Set identical to remote system
Parity = Set identical to remote system
Connect all boilers using a RJ11 ended telephone cable
If the Modbus network is activated the remote system may
monitor and/or control boiler operation. Refer to page 29 for
additional information.
Sage Boiler Control Instruction Manual Page 13 of 56
Product Features
Manual Boiler Control Mode
Display Shows: Manual Operation Mode and Lost Sensor Blind Mode
Return
Water
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
System
Circulator
System
Supply Water
Boiler Inlet
Temperature
(BI, BC)
EMS System Hardwired Connections
Lockout Indicator (LO)
Soft Alarm (SO)
Remote On / Off (Enable) (RO)
RJ11, RS-485 Communication
Modbus Network
EMS Monitoring
Manual Operation Mode and Lost Sensor Blind Mode Application Diagram
(Showing relevant connections)
MANUAL OPERATION MODE
Features
Modulation Rate Control
The operator sets the modulation rate. The setpoint is
ignored.
Call for Heat
The Call For Heat Relay (CH) is directly controlled by
the operator. The on and off points are ignored. The
boiler will turn off if the water temperature increases
past the temperature set on the High Temperature
LOST SENSOR BLIND MODE
If both Remote System Temperature (RST) and boiler outlet
temperature and the Remote Control input signal (C,-C+) have
failed, the boiler is started and run continuously at the lowest
modulation rate.
If the controller has entered Lost Sensor Blind Mode, the user
may switch the boiler into manual mode or repair, replace or
reconnect required temperature sensors.
Stop parameter.
Options
Outside Air Reset, Warm Weather Shutdown and
Domestic Hot Water Priority are ignored
.
The Spare Output (VI) and Combustion Air Damper
(SO) outputs are energized when the operator starts
the boiler in manual mode.
Selecting This Control Mode
Manual Mode is activated from the Manual Mode
menu when Supervisor password is entered. Simply
set the Boiler Man/Auto parameter to “Man” and adjust
the Modulation Rate and Boiler On/Off menu items as
required. Once activated the green LED flashes. To
leave manual mode set the Boiler Man/Auto parameter
to “Auto”.
Sage Boiler Control Instruction Manual Page 14 of 56
Product Features
Auxiliary Device Control
Return
Water
M
Fresh Air
Supply
Combustion Air
Open/Close (SO)
Damper
Boiler Inlet
Temperature
(BI, BC)
Standby System Pump
Mixing Valve
M
Control (MR, MS)
Boiler Pump
Start/Stop (BP)
Boiler Outlet
Temperature
(BO, BC)
Start/Stop (SO)
System Pump
Start/Stop (SP)
Spare Output (VI)
System Pump
Feedback (SI)
System
Supply Water
Energy Management
System (EMS)
Interface
Modbus RS-485, RJ-11
Connection
Auxiliary Control Application Diagram
(Showing All Options)
Features
Mixing Valve
The primary function of the mixing valve is to protect the
boiler from thermal shock and sustained flue gas
condensation. When configured, the mixing valve output
compares both minimum return water temperature setpoint
to measured return water temperature and boiler
differential temperature setpoint to measured differential
temperature (boiler outlet minus inlet temperature).
If the boiler return water temperature drops below the
minimum inlet water temperature setpoint (“Min In H2O
Temp” parameter) or the differential temperature increases
above the maximum water differential temperature setpoint
(“Max H2O Delta T” parameter) the mixing valve opens to
allow hot boiler outlet water to blend with cold return water.
The valve repositions toward 0% recirculation after return
water increases above setpoint and the differential
temperature reduces below setpoint.
The mixing valve may be controlled manually from the
Manual Mode menu when Supervisor password is entered.
Simply set the Mixing Valve M/A parameter to “Man” and
adjust the Mixing Valve % as required. Once activated the
green LED flashes. To leave manual mode set the Mixing
Valve M/A parameter to “Auto”
Combustion Air Damper and Vent Inducer
When the Relay (CH) is closed, the Combustion Air
Damper (CAD) and Vent Inducer outputs are energized. If
the CAD open position is needed to be proven, a limit
switch may be wired in series with the Low Water Cut-off
Switch input (LC). The alarm Message may be modified to
reflect this change.
Boiler Pump
The Boiler Pump output (BP) may be configured as None,
Always On, Purge or Lead On by setting the Boiler Pump
(parameter 2) (refer to page 31):
Always On Boiler pump runs continuously.
Purge Boiler pump runs during a pump Prepurge
(Pump Prepurge (parameter 3) time before
boiler starts) while the boiler is running and
during a pump cooldown period (pump
cooldown maintains the boiler pump running
until the boiler outlet temperature is within
the Postpurge Delta (parameter 4) degrees
above the boiler inlet temperature).
Lead On: Boiler Pump runs continuously when the
boiler is the lead and during the fan prepurge, while the boiler is running and during
fan post purge when a lag boiler.
The boiler pump sequences are detailed on the boiler
sequence diagram on page 6.
System and Standby System Pump
When configured, the System Pump output (SP) is always
energized except when turned off by the Warm Weather
Shutdown feature. A Standby System Pump output (SO)
may be configured as a backup to the system pump. The
Standby System Pump is started based on the System
Pump Feedback input (SI).
Selecting This Control Mode
These control modes may be selected using the Boiler and
System Configuration menus.
Sage Boiler Control Instruction Manual Page 15 of 56
Front Panel
Features
POWER LED [Steady On Green LED] indicates power is available down
stream of the Sage Boiler Control’s on board fuse.
[Flashing On Green LED] indicates manual mode operation
for boiler modulation
ALARM LED [Steady On Red LED] indicates an alarm is active.
[Flashing On Red LED] indicates a lockout alarm is a c tive
and a manual reset may be required
SCREEN 2 line by 16 character display provides operational, alarm,
sequence status, configuration and diagnostic user in terface
ENTER The ENTER key has no function in display mode. The
ENTER key is used to select menus, menu items and save
edited parameters as follows:
Select Mode (steady text):
Mode or select a menu or menu item
Edit Mode (blinking text):
value. Press MENU to cancel the current editing operation
UP, DOWN Select Mode (steady text):
selected display and move up and down menu items.
Edit Mode (blinking text):
decreases the value of the number being edited, or scrolls
through a list of choices.
MENU Press and hold MENU to change to the Main Menu screen.
When in a sub menu screen, press MENU to move to the
next higher menu. When in Edit Mode (blinking text) Press
MENU to cancel the current editing operation
Press ENTER to change into Edit
Press ENTER to save the current
Press UP, DOWN to change the
Press UP, DOWN to increases or
Sage Boiler Control Instruction Manual Page 16 of 56
Front Panel
Display Mode
All values shown in Display Mode are for display only and can not be adjusted by the operator. The
keys scroll through the Display Mode screens:
Standby
Low Inlet Temp
OUT 189F IN 180F
RST 189F OA 180F
OUT 189F SP 180F
MOD RATE SH 100%
Boiler State
Alarm Message Low Inlet Temp alarm shown, refer to page 41 for
OUT Boiler Outlet Temperature
IN Boiler Inlet Temperature
RST Remote System Temperature
OA Outside Air Temperature
OUT or RST Boiler Outlet or Remote System Temperature
SP Active Setpoint
MOD RATE Modulation Rate
SH Space Heating (active when DH is not)
DH Domestic Hot Water Priority
Standby boiler state shown, refer to the top of page 6 &
7 for explanation of each boiler state
explanation of all possible alarm messages, the
alarm line is left blank when no alarm is active
(visible when ‘Remote Sensor’ = Display Only or
Control)
(visible when ‘Outdoor Sensor’ = Display Only or
Outdoor Reset)
(Remote System when ‘Remote Sensor’ = Control)
(visible when ‘DHWP’ = Yes and DP input is true)
In 180F SP 130F
MIX VALVE 100%
Outlet Sensor &
Local SP Mode
LEAD BOILER 8
Cycles #,###,###
Hours #,###,###
Home Screen
The Boiler State and Alarm Message screen is the ‘Home Screen’ and is reverted to when no key has been selected for
longer than 30 minutes.
Alarm LED
New alarms illuminate the alarm LED and energize an alarm output (SO) (if enabled). If a lockout condition is detected,
the alarm LED will blink and the lockout indication output (LI) is energized. The display Message is cleared and relays
de-energize when the alarm condition is cleared.
In Boiler Inlet Temperature
SP Min In H2O Temp
MIX VALVE Modulation Rate
Control Mode
LEAD BOILER (0 – 8) Lead Boiler, when zero is displayed modulating
CYCLES Number of boiler cycles
HOURS Number of boilers operating hours
Outlet Sensor & Local SP Mode message shown, refer
to page 2 for an overview of each control mode
lead-lag functions are not available
Sage Boiler Control Instruction Manual Page 17 of 56
Front Panel
Display Navigation
Press and hold the key to leave the Display Mode and access the Main Menu:
Main Menu
DISPLAY MODE
BOILER CONFIG
SYSTEM CONFIG
SETUP
SETPOINTS
COMMUNICATION
DIAGNOSTICS
SECURITY
MANUAL MODE
Arrow Keys :
Up / Down
thr oug h Lis t s
MENU
ENTER
MENU
Sub Menus
DISPLAY MODE
BOILER CONFIG
SYSTEM CONFIG
SETUP
SETPOINTS
COMMUNICATION
DIAGNOSTICS
SYSTEM
SECURITY
MANUAL MODE
Display Mode Displays: Boiler operating status, Display
Only, Values Are Not Editable from this display
Configuration and Setup Menus: Sensor, boiler and
system options selections
(refer to page 31)
Setpoints Menu: Operational, On, Off, Min & Max
Setpoints, Editable Values
(refer to page 19)
Communication Menu
Modbus and Peer-To-Peer Network Selections
(refer to page 27)
Diagnostic Menu: Fault and Low Inlet Temp history,
Input & Output Status
(refer to page 41)
System Menu: Software revision, parameter code and
sensor calibration
(refer to page 43)
Security Menu: Supervisor and Factory access
(refer to page 45)
Manual Mode: User set Call For Heat and modulation
rate. Menu is visible when supervisor password is
entered (Refer to page 38)
Sage Boiler Control Instruction Manual Page 18 of 56
Front Panel
Setpoints Menu
Water
Temperature
Operational SP
Call For Heat
Relay (CH)
Deg F
185
180
175
Call For Heat Settings
Factory
No.
Setting
Range / Choices Parameter and Description
Operational Setpoint
70 180 60 F to 230 F
Setpoint used in Local Setpoint Mode when not servicing a Domestic Hot Water
Priority (DHWP) request
On Point
71 -5 0 F to –99 F
The boiler starts when the water temperature drops ‘On Point’ degrees below the
setpoint.
Off Point
72 15 0 F to 99 F
The boiler stops when the water temperature rises ‘Off Point’ degrees above the
setpoint.
High Temp Stop
The boiler stops when the boiler outlet water temperature is above the High
73 210 60 F to 230 F
Temperature Stop setpoint. This setpoint is active in every control mode. If the
lead boiler’s boiler outlet temperature is above the high temperature stop all
boilers are stopped.
*DHWP Setpoint
The Domestic Hot Water Priority (DHWP) Setpoint is active when DHWP Input
74 180 140 F to 230 F
(DP) closes and “DHWP” parameter is set to “yes” and Local SP Mode is
selected. When the contact is closed, the boiler outlet is maintained at, or above,
the DHW Setpoint.
*WWSD Setpoint
75 60 40 to 90 F
The Warm Weather Shutdown (WWSD) Setpoint used to disable boiler and or
system pump operation when enabled by setting the “WWSD” parameter to
“WWSD of Boiler”, “WWSD of Sys Pump” or “Both”
76 230 140 F to 230 F
Max SP
The Maximum Operational Setpoint for all possible Local and Remote modes
Min SP
77 140 60 F to 230 F
The Minimum Operational Setpoint is the lower limit for all Local and Remote
modes
78 120 110 F to 235 F
Min BIT
Low Boiler Inlet Temperature alarm and event setpoint.
*Min In H2O Temp.
79 130 110 F to 180 F
Minimum Inlet Water Temperature setpoint used as the Mixing Valve inlet
temperature setpoint.
*Max H2O Delta T
80 50 20 F to 50 F
Maximum Water Differential (Boiler Outlet minus Boiler Inlet) Temperature
setpoint used as the Mixing Valve differential temperature setpoint.
Max Delta T Hold
81 40 20 F to 50 F
Maximum Water Differential (Boiler Outlet minus Boiler Inlet) Temperature used
to hold modulation rate at low fire.
* Only visible when parameter enabled on the configuration and setup menus
Off Point
On Point
Time
Sage Boiler Control Instruction Manual Page 19 of 56
Installation
Mounting & Wiring Sensors
The Sage Boiler Control (SBC) is mounted in the burner control panel and wired to the burner circuitry at the factory.
These installation instructions will explain how the boiler inlet and outlet water temperature sensors are mounted in the
boilers supply and return connections and wired to the SBC. Keep a copy of the boiler installation manual on hand to
supplement these instructions.
MPC Boiler
1. Mount Boiler Inlet and Outlet Water Temperature Sensors
a. Remove one of the ½” immersion temperature sensors from the Sage Boiler Control Parts Carton and
apply thread sealant to the threads between the probe and hex shoulder.
b. Install the sensor in the ½” tapping faci ng upward on the MPC return manifold. Refer to Figure 1. (If
an RWMT positioning plug has already been installed in this tapping, remove it and replace it with the
sensor.) Make sure that the hole in the top of the return water mixing tube is aligned with the tapping
in the manifold and that the sensor probe slides through this hole without interference. Wrench the
sensor until watertight.
c. Remove the other ½” temperature sensor from the Sage Boiler Control Parts Ca rton and apply thread
sealant to the threads between the probe and hex shoulder.
d. Install the sensor in the ½” supply manif old tapping that faces the rear of the boiler. Refer to Figure 1.
Wrench the sensor until watertight.
2. Install Sensor Junction Box in Boiler Jacket
a. The temperature sensor wiring can be run to the burner control panel under the boiler jacket, using the
internal wiring chaseway, or it can be run externally, in rigid or flexible conduit. If the sensor wiring will
be run externally, proceed immediately to Part 4 of these instructions. If the sensor wiring will be run
within the boiler’s internal chaseway, continue to step b. below.
b. If the jacket front, intermediate, and rear top panels have already been installed, remove them (using
the MPC manual’s installation instructions and working in reverse).
c. If the boiler control wiring has already been installed in the rear top panel, remove the two (2) screws
from the rear flange of the panel, slide the panel back, and tilt it upward in order to gain access to the
primary internal junction box.
d. Remove the senso r J-box and black snap bushing from the Sage Boiler Control Parts Carton and
install the bushing in the 7/8” hole in the J-box. Mount the sensor J-box (with the snap bushing facing
upward) to the inside surface of the right split rear panel using two (2) of the #8 x ½” lg. hex head SMS
provided. See Figure 1.
3. Install and Connect Temperature Sensor Wiring (If Using Internal Wiring Chaseway)
a. Remove the painted sensor J-box cover (with holes) from the carton. If the blank cover plate is
already mounted on the right rear split panel, remove it. Using flexible conduit and the appropriate
conduit connectors (supplied by others), connect the inlet and outlet temperature sensor wiri ng to the
two (2) holes in the sensor J-box cover plate. Refer to Figures 1 and 2. The conduit length should be
sufficient to allow the cover plate to be installed over the sensor J-box opening in the right rear panel.
b. Install one length of shielded electronic wire cable (supplied by others). To prevent electrical
interference from the internal control/safety circuit wiring harness already installed in the chaseway,
use foil-shielded, 3-conductor (22 AWG), UL-listed cable, as a minimum. The cable length should be
sufficient to reach from the sensor J-box to the SBC terminals in the burner control panel, following the
same path as the internal wiring harness.
c. Pull one end of the shielded cable through the snap bushing on top of the sensor J-box. Trim any
excess length from the sensor wires and connect them to the shielded cable leads in the following
manner:
i. Connect one wire from each sensor to the black wire in the shielded cable.
ii. Trim the shielded cable’s silver drain wire, so that it will not come in contact with any metal
surfaces within the J-box. The drain wire is not used at this end of the cable.
Sage Boiler Control Instruction Manual Page 20 of 56
iii. Connect the second wire from the inlet temperature sensor to one of the remaining wires in
the cable. Be sure to note the color of the cable wire to ensure that it is connected to the
correct terminal on the SBC in later steps.
iv. Connect the second wire from the outlet temperature sensor to the remaining wire in the
cable. Be sure to note the color of the cable wire to ensure that it is connected to the correct
terminal on the SBC in later steps.
d. Mount the sensor J-box cover to the right rear panel using two (2) of the #8 x ½” lg. hex head SMS
provided. See Figure 2. Make sure that all of the exposed wires fit inside of the sensor J-box and that
none of them are pinched once the cover plate is installed.
e. Using wire ties, secure the shielded cable to the primary junction box and chaseway channel in the
same manner as the internal wiring harness, as shown in the MPC installation manual.
f. When the cable reaches the end of the chaseway at the front of the boiler, secure it to the vertical
frame rail using the same cable clamps that were installed with the internal wiring harness. Refer to
the MPC installation manual for details. It may be necessary to temporarily loosen the screws holding
the cable clamps in place, in order to fit the shielded cable through each loop along with the internal
wiring harness. If it is necessary to loosen these screws, the jacket front panel will have to be
removed (if already installed).
g. The shielded cable should exit the boiler jacket through the unused hole in the side of the front panel.
Using flexible conduit and the appropriate conduit connectors (supplied by others), connect the
shielded cable to the burner control panel through one of the panel knockouts n ear the SBC.
h. Connect the wire leads to the appropriate SBC terminals, as shown on the “External Connections”
label on the back of the control. (These terminals are also shown on the “Installation: Terminal Layout”
page of this manual). For easier access to the SBC terminals in Power Flame burner control panels,
remove the screws at the left and right edges of the top panel and rotate the top panel upward, around
the hinge at the top rear of the panel box. (See the Power Flame burner manual for details and
illustration.)
i. Connect the black wire and silver drain wire from the cable to the SBC’s “BC” terminal.
j. Reinstall any jacket panels that may have been removed.
4. Install and Connect Temperature Sensor Wiring (If Using Electrical Conduit Outside of the Boiler Jacket)
a. Using flexible conduit and the appropriate conduit connectors (supplied by others), run the inlet and
outlet temperature sensor wiring to a suitable metal junction box. To prevent electrical interference
from other wiring in the burner control panel, connect the sensor wires to foil-shielded, 3-conductor (22
AWG), UL-listed cable, as a minimum. Do not make any other wiring connections inside of this
junction box. Trim any excess length from the sensor wires and connect them to the shielded cable
leads in the following manner:
i. Connect one wire from each sensor to the black wire in the shielded cable.
ii. Trim the shielded cable’s silver drain wire, so that it will not come in contact with any metal
surfaces within the junction box. The drain wire is not used at this end of the cable.
iii. Connect the second wire from the inlet temperature sensor to one of the remaining wires in
the cable. Be sure to note the color of the cable wire to ensure that it is connected to the
correct terminal on the SBC in later steps.
iv. Connect the second wire from the outlet temperature sensor to the remaining wire in the
cable. Be sure to note the color of the cable wire to ensure that it is connected to the correct
terminal on the SBC in later steps.
b. Using properly supported conduit and the appropriate connectors (supplied by others), connect the
shielded cable to the burner control panel through one of the panel knockouts n ear the SBC.
c. Connect the wire leads to the appropriate SBC terminals, as shown on the “External Connections”
label on the back of the control. (These terminals are also shown on the “Installation: Terminal Layout”
page of this manual). For easier access to the SBC terminals in Power Flame burner control panels,
remove the screws at the left and right edges of the top panel and rotate the top panel upward, around
the hinge at the top rear of the panel box. (See the Power Flame burner manual for details and
illustration.)
Connect the black wire and silver drain wire from the cable to the SBC’s “BC” terminal.
Sage Boiler Control Instruction Manual Page 21 of 56
Installation
Mounting & Wiring Sensors (Cont.)
Figure 1: Installation of SBC Components (Part 1)
Sage Boiler Control Instruction Manual Page 22 of 56
Installation
Mounting & Wiring Sensors (Cont.)
Figure 2: Installation of SBC Components (Part 2)
Sage Boiler Control Instruction Manual Page 23 of 56
Installation
Mounting & Wiring Sensors (Cont.)
V9/V11 Boilers
1. Mount Boiler Inlet and Outlet Water Temperature Sensors
a. Remove one of the ½” immersion temperature sensors from the Sage Boiler Control Parts Carton and
apply thread sealant to the threads between the probe and hex shoulder.
b. Install the supply sensor in the 3/4” tapping T or J (V9, V11 respectfully) using a ¾” x ½” bushing.
Refer to Figure 3. Wrench the sensor until watertight.
c. Remove the other ½” temperature sensor from the Sage Boiler Control Parts Ca rton and apply thread
sealant to the threads between the probe and hex shoulder.
d. Install the return sensor at the lower rear return tapping, using a short 3” nipple and a 3” x 3” x 3” tee
with the branch of the tee bushed down to ½” (or, use a 3” x 3” x ½” tee, if available). For V9, use
tapping C and for V11, use tapping B. Refer to Figure 3. Wrench the sensor until watertight.
2. Install and Connect Temperature Sensor Wiring
Follow the instructions above for the MPC sensor wiring, Step 4 “If Using Electrical Conduit Outside of the
Boiler Jacket”.
V9
V11
Figure 3
Sage Boiler Control Instruction Manual Page 24 of 56
Installation
Terminal Layout
Alternate Connection For
Outside Air Temperature and
RJ-45
(8 pin)
Remote System Temperature
(10k ohm Thermister, 5Vdc)
Label 901 a
Boiler Peer-To-Peer
Communication
Network
RJ-11
(6 pin)
LC
Low Water Cutoff Switch Input
CH
Call For Heat Output
O+
O+
Outside Air Temperature
(10k ohm Thermister, 5Vdc)
O-
OR+
R+
Remote System Temperature
(10k ohm Thermister, 5Vdc)
R-
RDP
Domestic Hot Water Priority
LR
Local / Remote
RO
Remote On / Off (Enable)
SI
Spare Input (Programmable)
C
12 Vdc Common
C
24
(10k ohm Thermister, 5Vdc) Common
Vac
CA - Low Combustion Air Flow
HL - Operating or High Limit
GP - Gas Pressure Switch
WF - Low Water Flow Switch
OO - Burner On/Off Switch
V-, V+ - Firing Rate Demand (0-10Vdc)
P-, P+ - Firing Rate Demand (0-10 Vdc, PWM)
12
Vdc
CA
OO
V- V+ P- P+
GP WFHL
Flame Safeguard Alarm
Fuel Valve Energized
24
Vac
Power Common (-24 Vac)
Power Supply (+24 Vac)
(24 Vac)
(24 V ac)
!
12 Vdc,
0.5 A max total
for LO, VI, BP,
SP and SO
Sage Boiler Control Terminal Arrangement (rear view)
Boil er Outlet Temperature
Boiler Inlet Temperature
12Vdc Common
Spare Output (Programmable)
System Pump Start/Stop
Boiler Pump Start/Stop
Vent Inducer Start/Stop
Alarm Indicator
Mixing Valve Output
(4-20 mAdc)
Remote Firing Rate or
Setpoint Input (0-10 Vdc)
CPRALCS
BC
BO
BI
C
C
C
SO
SP
BP
VI
LO
MR
MS
CC+
Sage Boiler Control Instruction Manual Page 25 of 56
Installation
External Connections
System Water Temperature Sensor
Mount the sensor in the common header downstream of all boiler connections. Locate the sensor a minimum distance
of 10 straight pipe diameters from the from flow disturbing fittings.
Outdoor Air Temperature Sensor
Mount the temperature sensor on an outside wall out of direct sunlight, preferably on a north facing wall. Do not mount
sensor near exhaust of any kind, as this may affect readings.
Sage Boiler Control Instruction Manual Page 26 of 56
Installation
External Connections (Continued)
Outside Air and Remote System Temperature Sensor RJ45 Connection
All boilers may be connected to the remote system temperature (RST) and the outdoor air temperature (OAT) sensors.
Only one of each type sensor is needed for connections with up to eight boilers. The lead boiler is automatically
enabled to monitor the sensors. As the boiler lead rotates the sensor monitoring is automatically transferred to the new
lead boiler.
Boiler 2
Boiler 1
BO I L E R RUNNING
Connect s t o
Up to 8 Boil ers
Power
BOILER RUNNING
Power
Boiler 2
Alarm
Alarm
RJ-45
Power
O+
O+
O-
OR+
R+
R-
R-
BO ILER RUNNING
Alarm
Mult i pl e Boil er Connec tion Diag ram
(Us i ng the ex tra O+, O-, R+ & R- term inal s t o dai sy chain
the boi l ers t ogether )
Boiler 1
RJ-45
Power
O+
O+
OO-
R+
R+
RR-
BOILER RUNNING
Alarm
RJ-45
O+
O+
O-
OR+
R+
R-
R-
RJ-45
O+
O+
OO-
R+
R+
RR-
Outsi de Ai r
Temperature
Remote
System
Temperature
Outsi de Ai r
Temperature
Remote
System
Temperature
Two Boiler
RJ45 C onnec tion Di agram
(Refer to Note 2)
Notes
1. Used Only For Peer-To-Peer Network
. When using Modbus Network wire Outside Air and Remote System sensor
to only one boiler.
2. Wiring from the Outside Air and Remote System Temperature sensors should use low impedance, shielded, twisted
pair wire and go directly to the terminals on any one boiler. Signal wiring should not be run in the same conduit with
power wiring. Wire shields may be connected to the common terminal (C) located on the same terminal block with
the outside air and remote system temperature connections.
3. The RJ45 sensor cables need to be a straight through type cable that connects each pin of the connector on one
end to it’s identical pin on the opposite end. Up to a total of three boilers may be connected using a RJ45 splitter.
When connecting more than three boilers, it is recommended, and may be more convenient, to use the extra O+, O, R+ & R- terminals to daisy chain the boilers together (eliminating the need for RJ45 cables and splitters and
reducing the loop impedance).
Sage Boiler Control Instruction Manual Page 27 of 56
Installation
Communication
The Peer-To-Peer or Modbus networks allow boiler information, including modulation rate and on/off commands, to be
sent via a standard phone cable thus avoiding the cost, time and complexity of wiring multiple signals.
RJ11
Sage Control
Boiler 1Boiler 2
RJ11
RJ11 Splitter
(Not Inc l uded)
RJ11
Sage ControlSage Control
Boiler 3
RJ11 S plitt er
(Not Inc luded)
Connect s to
Up to 8 Boilers
Or Building
Aut om at i on S ys t em
(BAS) Modbus
Connection
Mu ltiple Boile r
RJ11 Connection Diagram
Sage Control
RJ11
Sage Control
RJ11
Boiler 1Boiler 2
Two Bo ile r
RJ11 Connection Diagram
When Wiring Modbus Communication to a Building Automation System (BAS)
The Modbus communication connects to the same RJ11 port that is used by the peer-to-pee r communication. Connect
one end of the RJ11 cable to the SBC and cut off the other end of the cable to access the individual conductors. The
SBC is a 2-wire Modbus communication. Connect the "A" and "B " terminals of a four wire or six wire phone cable (as
shown below) to the BAS terminals. The SBC includes two sets of A and B connections, where the A represents the
active transmission state of the RS485 transmitter (as opposed to the line idle stat e). You need only to wire to one of the
"A" terminals and one of the "B" terminals.
Phone cable signals (4 wire) - connect to pin black or yellow and red or green:
Wire
Color
Black 1 A
Red 2 B
Green 3 B
Yellow 4 A
Notes
1.
2. Please note that all connections between boilers must be kept as short as possible. The maximum cable length
3. In all cases, the wires should be routed away from any obvious sources of electrical noise or magnetic fields
4. SBC power supply common must be grounded at each boiler to enable network communication.
Slot
Connection
Number
Use standard phone cables (although ones that have all six wires terminated at each end) and splitters to
connect each boiler.
between boilers must be kept under 25 feet (average distance between all boilers).
(motors, fluorescent lights, contactors, spark generators, etc.). Use a separate conduit and junction box from
the power wiring.
Sage Boiler Control Instruction Manual Page 28 of 56
Installation
Communication (Continued)
The Sage Boiler Control communication selections are found on the Communication Menu. Press and hold the
key to leave the Display Mode and access the Main Menu:
Use the keys scroll down to the Communication Menu and push the key:
Communication Menu
No.
90
91 1 1-247
92 19.2
93 None
94 30
95
96
97 1 1 to 8
98 - - 6 - - - 321
Factory
Setting
Peer to
Peer
Range / Choices Parameter and Description
Peer to Peer
Modbus
Protocol
Selects between Peer-To-Peer (multiple boiler Lead/Lag control network) and
a Modbus slave communication.
Modbus Address
Each boiler must be given a unique address. Only visible when Protocol
equals Modbus.
9.6
19.2
38.4
Odd
Even
None
1-120
Seconds
Baud Rate
Units are 1000 Bits Per Second (KBPS). Only visible when Protocol equals
Modbus.
Parity
Only visible when Protocol equals Modbus.
Timeout
Only visible when Protocol equals Modbus.
Messages Rcvd
Diagnostic tool used to confirm wiring and Modbus master configuration.
Only visible when Protocol equals Modbus.
Messages Sent
Diagnostic tool used to confirm wiring and Modbus master configuration.
Only visible when Protocol equals Modbus.
Boiler Address
Each boiler must be given a unique address. The boiler address assignment
determines the boiler sequencing order. A value of 0 disables the network
communications. Only visible when Protocol equals Peer to Peer.
Online Status
Each space can be either the boiler address or a ‘ - ‘ depending on whether
there is a boiler of that address on-line. Only visible when Protocol equals
Peer to Peer.
Example: - - 6 - - - 321 indicates that boilers 6,3,2 and 1 are online
ENTER
MENU
Sage Boiler Control Instruction Manual Page 29 of 56
Installation
Peer-To-Peer Network
The Sage Boiler Control includes a dependable Peer-To-Peer communication network. This network allows multiple
boiler modulating lead/lag control and status signals to be transferred between boilers. In order to succe ssful use this
network certain requirements must be followed.
Network Relevant & Updated Parameters
When using the Peer-To-Peer network certain “Network Relevant” parameters must be configured the same in all
boilers (refer to Appendix B for parameter identification). To facilitate the configuration of these “Network Relevant”
parameters, a network update feature has been included. Once communications is established between all boilers in a
system, changing to a “Network Relevant” parameter at the keypad of any boiler will update that parameter in all boilers.
In addition to the “Network Relevant” parameters, other common parameters are also “Updated” over the network
(although it is not necessary for them to be set identically among boilers on the network). If you wish to configure them
differently among boilers, you will have to disconnect the boiler from the network while you change them to prevent the
other boiler from being changed as well. “Network Relevant” and additional “Updated” parameters are identified in
Appendix B, Parameter Summary.
Initially Establishing Peer-to-Peer Communication
A Peer-to-Peer network is established as follows:
1. Assign all boilers a unique Boiler Address between 1 and 8 and set the Protocol to Peer-to-Peer
2. Connect all boilers using a RJ11 ended telephone cable
3. Configured all “Network Relevant” parameters identically on all boilers. Unexpected boiler behavior may result if
these parameter values differ among boilers on the network. When “Network Relevant” parameters are iden tical
the ‘Param Code’ parameter will be identical on each boiler (refer to page 43 for parameter location).
4. When two or more boilers are properly configured for communication, the controllers “auto detect” each other and
shares information.
Re-Establishing Peer-to-Peer Communication After an individual boiler Communication Failure
A Peer-to-Peer network is re-established as follows:
1. Ensure Boiler address is between 1 and 8 and is unique
2. Ensure the Protocol parameter is set to Peer-to-Peer
3. Use the ‘Param Code’ parameter to check that “Network Relevant” parameters are configured identically (refer to
page 43 for parameter location).
4. Remove control power from the boiler
5. Connect the boiler to the network using a RJ11 ended telephone cable
6. Apply control power to the boiler
7. The network will “auto detect” the new boiler and assign it a position in the sequence based on the boiler address.
When a boiler is operated as a stand alone boiler, away from the network, it establishes itself as a lead boiler. If this
stand alone boiler is simply re-connecting to a network of operating boilers there is a potential that boiler operation will
be disrupted as the new boiler becomes lead. This potential is avoided by following the above Re-Establishing
procedure.
Sage Boiler Control Instruction Manual Page 30 of 56
Installation
RS485 Modbus Network
The Sage Boiler Control includes a dependable Modbus communication network. This network allows boilers to be
controlled and/or monitored by a remote system via a RS485 Modbus communication network. Each Sage Boiler
Control is a Modbus slave with the following available boiler information:
Outdoor Air Reset Enable/Disable
Domestic Hot Water Priority (DHWP)
Local / Remote
Remote On / Off Modbus Command
Spare Input (Programmable)
Low Water Cutoff Switch
Burner On / Off Switch
Low Water Flow
High and Low Gas Pressure Switches
Operating or High Limit
Low Combustion Air Flow
Fuel Valve Energized
Flame Safeguard Alarm
Call For Heat (CFH)
General Alarm
Vent Inducer
Boiler Pump
System Pump
Spare Output (Programmable)
State Boiler Disabled
State Weather Shutdown
State Lockout
State Pump Purge
State Limit Hold
State Purge/Pilot Ign
State Low Fire/Ignition
State Main Ignition
State Low Fire Hold
State Boiler Running
State Fan Post Purge
State Pump Cool Down
State Standby
Annunciator Low Water Level
Annunciator Off Switch
Annunciator Low Water Flow
Annunciator Fuel Limit
Annunciator High Temp Limit
Annunciator Low Air Flow
Annunciator FSG Lockout
Annunciator Outlet Temp Fail
Annunciator Inlet Temp Fail
Annunciator OA Temp Fail
Disable Enable
Disable Enable
Local Remote
Y
Off On
Off On 2
Off On 2
Off On 2
Off On 2
Off On 2
Off On 2
Off On
Off On
Off On
Off On 4
Off On
Off On
Off On
Off On
Off On 3
Off On 3
Off On 3
Off On 3
Off On 3
Off On 3
Off On 3
Off On 3
Off On 3
Off On 3
Off On 3
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off
Off On 1
Off On 3
On
On
On
On
On
On
On
On
On
On
On
3
4
4
4
4
4
4
4
4
4
4
Sage Boiler Control Instruction Manual Page 31 of 56
40001
40002
40003
40004
40005
40006
40007 PCB Temperature Sensor -50 300 F
40008
40009
40010
40011
Notes
1. After a Modus communication failure, while using the Modbus connection to monitor or control
‘Comm Failure’ alarm is not cleared until a successful write to both the Remote On / Off Modbus Command
(00004) and Remote Firing Rate or Remote Setpoint (40006) points have been completed, power is cycled or
the ‘Protocol’ parameter is changed from Modbus to Peer-to-Peer and back again.
2. The limit string points (00006 - 00011) are only monitored when there is a Call For Heat. Additionally, if one of
these items is ‘open’ items down stream are not monitored.
3. The boiler "state" points (00020 - 00032) are mutually exclusive (i.e. only one is asserted at a time). This will
reflect the state of the message on the front of the boiler. Refer to page 6 for an explanation of each state.
4. The “Annunciated” points (00033 – 00046) reflect the state of the signals used to control the displayed Alarm
Message. Refer to pages 39 and 40 for an explanation of each annunciator point.
5. “General Alarm” point (00015) turns “On” when the boiler is indicating any alarm condition.
To establish a Modbus network set the following parameters:
Communication Menu:
Protocol = Modbus
Modbus Address = Give each boiler a unique address.
Baud Rate = Set identical to remote system
Parity = Set identical to remote system
Connect all boilers using a RJ11 ended telephone cable
Annunciator Remote Temp Fail
Annunciator Remote In Fail
Annunciator Comm Fail
Annunciator Low Inlet Temp
Annunciator Memory Failure
Description
Boiler Outlet Water Temperature
Boiler Inlet Water Temperature
Outside Air Temperature
Boiler Actual Setpoint
Remote System Temperature
Remote Firing Rate or Remote Setpoint
Firing Rate Output to Mod Motor
Minimum Return Temperature Setpoint
Mixing Valve Output
Control Mode
Off
Off
Off
Off
Off
Engineering
Read/
Write
-50 300 F
-50 300 F
-50 300 F
60 230 F
-50 300 F
Y
0 100 %
110 180 F
0 100 %
1 7
Units for
Register
= 0
0 100 or 300 % or F 1
Engineering
Units for
Register
= 100
On
On
On
On
On
Units
4
4
4
4
4
the boilers, the
Not
es
Sage Boiler Control Instruction Manual Page 32 of 56
Configuration & Tuning
Boiler Configuration Menu
Boiler operating behavior is adjusted using the configuration & tuning menus. Press and hold the
key to leave the Display Mode and access the Main Menu:
Use the keys scroll down to the required Menu and push the key:
No.
1 Deg F
Factory
Setting
Range / Choices Parameter and Description
Deg F
Deg C
Display Units
Selects how temperature parameter values are displayed.
Boiler Pump
Activates the boiler pump output according to selected function
None: No Boiler Pump.
On Always: Pump Runs Continuously.
Purge: Pump Runs during pump pre/post purge operations and during
call for heat.
Lead On: Pump runs continuously when the boiler is the lead and runs
2 None
None
On Always
Purge
Lead On
during the fan pre-purge, while the boiler is running and during
fan post purge when a lag boiler.
Pump Prepurge
Sets length of time the boiler pump will be run prior to closing the “Call for
Heat” relay (CH).
3 15
0 to 600
Seconds
Postpurge Delta
4 5
0 to 20
C or F
Sets the temperature above boiler inlet temperature that boiler outlet
temperature must be below before turning off the boiler pump during pump
post purge (Pump Cooldown State).
5 No
6 Yes
7 -
month / day / year
8 No
No
Yes
No
Yes
hour : minute
No
Yes
Mixing Valve
Enables the mixing valve control output and user display.
Inlet Sensor (Return Sensor)
Enables the return temperature display and control logic.
Set Time/Date
Displays and sets the time and date of the boiler’s real time clock.
Fuel Limit
Specifies a Fuel Limit such as high and low fuel gas pressure switches a re
connected to input (GP). Enables Fuel Limit Hold and alarm messages.
Spare Input
Sets the function of the Spare Input Terminal (SI):
Off: Ignore.
Sys Pump Feedback: Input (SI) should be wired to a flow switch inserted in
the flow path of the system pump. Input (SI) indicates
the system pump is operating. If output (SO) is set to
System Backup Pump, system pump output (SO) is
energized and System pump Feedback is de-energized
the System Backup Pump output (SO) is energized.
9 Off
Off
Sys Pump
Feedback
Low Fire
Low Fire: When the Fuel Valve Energized input (CS) is not
energized and Input (SI) is energized the modulation
rate is set to the “Low Fire” setpoint. When input (SI) is
not energized, the modulation rate is set to “Fan Purge”
setpoint. When the fuel valve energized input (CS) is
energized input (SI) is ignored.
Spare Output Sets the function of the Spare Output Terminal (SO):
Off: Never close output (SO).
CAD: Combustion Air Damper (CAD) or fresh air damper
Closes SO relay with a call for heat, Opens SO relay 2
minutes after call for heat has been de-activated.
System Pump Feedback indicates the Primary System
Pump is not operating.
10 Off
System Pump BU
Off
CAD
Soft Alarm
System Pump BU: Closes when System Pump output is activated but the
Soft Alarm: Alarm indication or warning, closes when any alarm is
active, or a condition is preventing a boiler start,
including Off Switch.
ENTER
MENU
Sage Boiler Control Instruction Manual Page 33 of 56
Configuration & Tuning
System Configuration Menu
No.
20 Off
21 No
22 140 60 F to 140 F
23 220 150 F to 220 F
24 No
25 No
27 No
28
Factory
Setting
“Low
Water
Level”
Range / Choices Parameter and Description
Off
Isolated Demand
Shared Demand
No
Remote SP
Modbus SP
Remote Mod
Modbus Mod
No
Display Only
Control
No
Yes
No
Yes
16 Text
Characters
DHWP
Enables Domestic Hot Water Priority (DHWP) control feature. When input
(DP) is energized DHWP becomes active as selected:
Off No DHWP
Isolated Demand Boiler that receives the input (DP) drops off the
Peer-To-Peer network and it’s temperature setpoint
is adjusted above the DHWP Setpoint. The PID
output is based on boiler outlet temperature and
setpoint. If Remote SP or Remote System
temperature sensors were selected, control is
switched to the Boiler Outlet Sensor.
Shared Demand If the lead boiler receives the input (DP) the
temperature setpoint for all boilers on the Peer-ToPeer network is adjusted above the DHWP Setpoint
Remote Control
Sets the remote (Energy Management System) control mode as follows:
No: Local setpoint and modulation rate is us ed.
Modbus and remote input (C+,C-) are ignored
Remote SP: Remote Input (C+, C-) is used as the temperature
setpoint. Parameter 22 & 23 may be used to adjust
the signal range
Modbus SP: RS485 Modbus (40006) is used as the
temperature setpoint
Remote Mod: Remote Input (C+, C-) is used as the modulation
rate.
Modbus Mod: RS485 Modbus (40006) is used as the modulation
rate.
Remote 1.0 Volt=
Sets the temperature corresponding to input (C+,C-) 1Volts. Voltage below
1V is considered invalid, (failed or incorrect wired sensor).
Remote 9.0 Volt=
Sets the temperature corresponding to input (C+,C-) 9 Volts. Voltage above
9V is considered invalid, (failed or incorrect wired sensor).
Remote Sensor
Enables the Remote System Temperature sensor display and control logic:
No Remote Sensor Input (R+,R-) is ignored.
Display Only Remote Sensor Input (R+,R-) is used for display only
Control Remote Sensor Input (R+,R-) is compared with the
temperature setpoint to establish a modulation rate
System Pump
Enables the System Pump output (SO)
LWC or CAD
Specifies a Low Water Cut-off Switch or Combustion Air Damper (Fresh Air
Damper) Open switch is connected to input (LC). Enables Limit Hold and
alarm messages. Limit hold display message is described by parameter 28
Alarm Message
Limit Hold and alarm message displayed corresponding to sensor connected
to input (LC)
The “ENTER” key and “Up” and “Down” arrow keys are used to change the
text Message.
Sage Boiler Control Instruction Manual Page 34 of 56
Configuration & Tuning
Setup Menu
No.
30 Off
31 90
32 10
33 5
34 5
35 20
36 20
37 100
38 1
39 220
Factory
Setting
Range / Choices Parameter and Description
Off
WWSD of Boiler
WWSD of Sys Pump
Both
50 to 100
% Maximum
Modulation Rate
0 to 50
% Modulation Rate
60 to 900
Seconds
0 to 900
Seconds
1 to 30
Minutes
1 to 30
Minutes
40 - 100
% Modulation Rate
1 - 10
Degrees/Minute
100 - 240
C or F
WWSD
Specifies Warm Weather Shut-Down (WWSD) control of boiler and/or
system pump:
Off: Ignores Warm Weather setpoint
WWSD of boiler: When Outside Air Temperature (OAT) is higher than
the WWSD setpoint, inhibits boiler start
WWSD of Sys Pump: When OAT is higher than the WWSD setpoint de-
energize System Pump output (SO)
Both: When OAT is higher than the WWSD setpoint, inhibit
Call for Heat and de-energized system pump output
(SO)
LL Start Trigger
Specifies the percent of maximum modulation rate the running boiler(s)
must reach before calling upon additional boilers for help.
LL Stop Trigger
Specifies the modulation rate that the running boiler(s) must be below
before shutting down a lag boiler
Boiler On Delay
Time Delay after On Point setpoint has been reached before starting the
next boiler. Short time delay to prevent nuisance starts due to momentary
temperature and modulation rate swings
Boiler Off Delay
Time Delay after the Off Point setpoint before stopping the next boiler.
Short time delay to prevent nuisance stops due to momentary temperature
and modulation rate swings.
%FR On Delay
Time Delay after the modulation rate is above the LL Start Trigger before
starting the next boiler. Long time delay to avoid temperature going below
setpoint as a result of a slow process change
%FR Off Delay
Time Delay after the modulation rate is below the LL Stop Trigger before
stopping the next boiler. Long time delay to avoid temperature going above
setpoint as a result of a slow process change
High Fire Limit
To maximize high efficiency condensing operation, the firing rate is limited
to an adjustable value. The Sage Boiler Control will keep the boilers at this
firing rate or lower as long as the boilers will handle the
load. After the last boiler has started the modulation rate is released up to
100%.
Deg/Min Hold Off
Specifies a temperature rate of change that inhibits the next boiler being
started or stopped. If the temperature is increasing faster than this rate of
change the next boiler is not started. Also, if the temperature is decreasing
faster than this rate of change the next boiler is not stopped.
Cutback Setpoint
Boiler Outlet temperature above the Cutback Setpoint causes the
modulation rate to be reduced proportionally to help avoid a high
temperature limit lockout. This parameter is significant while the boiler is
controlled according to the remote system temperature sensor or remote
input (C+,C-) or Modbus (40006) Remote Firing Rate.
Sage Boiler Control Instruction Manual Page 35 of 56
Configuration & Tuning
Setup Menu (Continued)
No.
40 150
41 5
42 Disable
43 168
Factory
Setting
Range / Choices Parameter and Description
16 to 420
Seconds
3 to 120
Seconds
Disable
Enable
8-720
Hours
Net Start Dwell
The Net Start Dwell Time Delay specifies the length of time the peer-topeer network will wait for the Main Fuel Valve Energized input (CS) to be
energized after a boiler Call for Heat. If the Net Start Dwell time is
exceeded before the main fuel valve is open the next boiler Call for Heat is
initiated without further delay. This parameter should be longer than the
sum of the pump purge and boiler purge times.
Limit Fault Time
The Limit Fault Time Delay specifies the length of time the peer-to-peer
network will wait for the boiler limits input (CA) to be energized after a boiler
Call for Heat. If the Limit Fault time is exceeded before the limits are
energized the next boiler Call for Heat is immediately initiated.
Rotation
Enables the lead boiler role to be rotated through the boilers on the
network. When disabled the boiler with the lowest network address is lead.
Rotate after
Specifies number of hours (cumulative) a lead boiler runs before passing
the lead to another boiler.
Lead role will be surrendered earlier if the lead boiler is placed into manual
mode, is run remotely (mode 6), fails to start, is “blind” (all input sensors
failed), or is satisfying a DHWP request.
49 100
50 0
51 0
52 0
53 600
54 0
0 to 100
% Full Scale
0 to 100
% Full Scale
0-100
% Modulation Rate
0 to 100
% Modulation Rate
10 to 1200
Seconds
0 to 600
Seconds
Parameters 44 through 48 are found on the following page
Blower Spd High (Linkage Max. Position)
Percent of (0 - 10 Vdc output [V+,V-]) output that represents a 100%
modulation rate. This scaling factor allows the Sage Boiler Control to
display 100 % when the linkage is at rated boiler output.
Please Note
The Burner input rate adjustment must be completed before
can be set. After maximum boiler firing rate is established, the Sage
Controller Firing Rate Display “FR” percentage should be 100%. If boiler
rate is established at less than 100% FR, that value should be entered in
parameter 49 as blower speed high. This will establish the correct scaling
factor and will prevent overfiring of the boiler.
Blower Spd Low (Linkage Min. Position)
Percent (0 - 10 Vdc output (V+,V-) or pulse) output that represents a 0%
modulation rate. This scaling factor allows the Sage Boiler Control to
display 0 % when the linkage is at minimum boiler output.
Low Fire Spd
Modulation % used for Low Fire Hold and Low Fire Start conditions. Low
fire position is established by the linkage adjustment. This parameter may
be left at 0%.
Fan Purge Speed
[Note – Fan Purge Speed used during Low Fire Hold (parameter 53)].
Burners with linkage control purge and light-off rates using the RM7800 and
linkage adjustments.
Low Fire Hold
Time modulation rate is held at preset value (Low Fire Spd or Fan Purge
Spd depending on the state and configuration of Spare Input) after the Fuel
Valve Energized Input (CS) is energized.
Post Purge Time
Time modulation rate is held at Purge % setpoint after the Fuel Valve
Energized Input (CS) is de-energized.
this parameter
Sage Boiler Control Instruction Manual Page 36 of 56
Configuration & Tuning
Setup Menu (Continued)
230
210
190
170
150
130
110
90
70
Boiler
Setpoint
Ho t Water Setpoint
Outdoor Air Temperature
-20100800 204060
Boiler Design
Boiler Set Up
230
210
190
170
150
130
110
90
70
Temperature
Hot Water Setpoint
Outdoor Air Temperature
-20100800 204060
Outdoor Des ign
Outdoor Set Up
Design
Set Up
Temperature
Max Setpoint
Min Setpoint
Outdoor Reset Graph
Energy used by the hot water heating system can be greatly reduced by adjusting (resetting) the operating temperature
setpoint as the outdoor temperature changes. Using this approach, the heat lost from the building is matched by the
heat input to the building. The control utilizes a reset curve to set the relationship between outdoor temperature and
boiler outlet temperature setpoint. The reset curve is determined from the “Set Up” and the “Design” conditions as
shown in the above graph and described by parameters 45, 46, 47 and 48:
No.
Factory
Setting
Range / Choices Parameter and Description
Outdoor Sensor
Enables the Outside Air Temperature display and control logic:
No Outside Air Input (O+O-) is ignored.
44 No
No
Display Only
Outdoor Reset
Display Only Do Not
temperature, Display Outside Air Temperature
Outdoor Reset Calculate the temperature setpoint based on outdoor
Calculate setpoint based on outdoor
temperature using a reset curve defined by Outdoor
Set Up, Boiler Set Up, Outdoor Design and boiler
Design parameters
Outdoor Set Up
45 55 F 40 F to 100 F
The Outdoor Set Up temperature is the outdoor temperature at which the
Boiler Set Up temperature is supplied.
Boiler Set Up
46 140 F 140 F to 180 F
The Boiler Set Up Temperature is the starting boiler water temperature of
the reset ratio. If the building feels cool during mild outdoor conditions,
the Boiler Set Up setting should be increased.
Outdoor Design
47 30 F -20 F to 50 F
The Outdoor Design Temperature is the outdoor temperature at which the
Boiler Design temperature is supplied.
Boiler Design
The Boiler Design setting is the water temperature required to satisfy the
48 180 F 150 F to 220 F
building heat loss during the Outdoor Design temperature. If the building
feels cool during cold outside conditions, the Boiler Design setting should
be increased.
Sage Boiler Control Instruction Manual Page 37 of 56
Typical Sage Boiler Control PID Gain and Integral Settings
Local PID P
Proportional Gain value for boiler outlet temperature sensor control Modes.
A larger gain value results in tighter, more active, PID control. Gain is the
primary PID modulation rate tuning adjustment and provides the immediate
modulation rate response.
Pick a gain based on the desired initial response. The burner modulation
rate can oscillate if the Proportional Gain is too large.
Local PID I
Integral gain value for boiler outlet temperature sensor control Modes. A
smaller value makes the Integral ramp in less time (i.e., faster). Integral is a
secondary PID modulation rate tuning adjustment that ramps the output
over time (typically minutes) .
Based on the selected Local PID P, select the corresponding (from above
table) Integral value. Repeats per minute between 0.5 and 2.0 are typical.
The burner modulation rate can oscillate if the Integral time is too small.
Local PID D
The Derivative gain value for boiler outlet temperature sensor control
Modes. A larger Derivative gain value produces a larger PID output
contribution proportional to the rate of change of the error (Setpoint – Boiler
Outlet Temperature). When set equal to zero it has no effect on the output.
Remote PID P
Proportional Gain value for Remote System Temperature sensor control
Modes. Refer to Local PID P for explanation.
Remote PID I
Integral Gain value for Remote System Temperature sensor control Modes.
Refer to Local PID I for explanation.
Remote PID D
Derivative Gain value for Remote System Temperature sensor control
Modes. Refer to Local PID D for explanation.
½
Repeats/Minute
60
1
Repeats/Minute
30
2
Repeats/Minute
15
Sage Boiler Control Instruction Manual Page 38 of 56
Configuration & Tuning
Setup Menu (Continued)
No.
61 15 0 to 10000
62 40 0 to 10000
63 0 0 to 10000
64 15 0 to 10000
65 40 0 to 10000
66 0 0 to 10000
Factory
Setting
Range / Choices Parameter and Description
Mixing Valve P
Proportional Gain value for boiler Inlet temperature sensor control mode.
A larger gain value results in tighter, more active, PID control. Gain is the
primary PID modulation rate tuning adjustment and provides the
immediate mixing valve modulation response.
Pick a gain based on the desired initial response. The mixing valve can
oscillate if the Proportional Gain is too large.
Mixing Valve I
Integral gain value for boiler inlet temperature sensor control mode. A
smaller value makes the Integral ramp in less time (i.e., faster). Integral is
a secondary PID modulation rate tuning adjustment that ramps the output
over time (typically minutes).
Based on the selected Mixing Valve P, select the corresponding (from
table on previous page) Integral value. The mixing valve can oscillate if
the Integral time is too small.
Mixing Valve D
The Derivative gain value for boiler inlet temperature sensor control mode.
A larger Derivative gain value produces a larger PID output contribution
proportional to the rate of change of the error (Setpoint – Boiler Inlet
Temperature). When set equal to zero it has no effect on the output.
Max Delta T P
Proportional Gain value for boiler differential (boiler outlet minus inlet
temperature sensor) temperature control mode. Refer to Local PID P for
explanation.
Max Delta T I
Integral Gain value for boiler differential (boiler outlet minus inlet
temperature sensor) temperature control mode. Refer to Local PID I for
explanation.
Max Delta T D
Derivative Gain Term for boiler differential (boiler outlet minus inlet
temperature sensor) temperature control mode. Refer to Local PID D for
explanation.
Sage Boiler Control Instruction Manual Page 39 of 56
Configuration & Tuning
Manual Mode Menu
Manual mode allows the boiler modulation rate, boiler call for head output and mixing valve position to be directly
positioned by the user. These are valuable tools for trouble shooting and setup.
No.
101 Auto
102 Varies 0 to 100
103 Varies
104 Man
105 Varies 0 to 100
Factory
Setting
Range / Choices Parameter and Description
Boiler Man/Auto
Man
Auto
On,
Off
Man
Auto
Man: Remain in Manual Mode
Auto: Return to Boiler Mode specified by parameter/boiler conditions
Activated only when in Supervisor Mode.
Modulation Rate
Sets the modulation rate to be used for boiler when in Manual Mode
Activated only when in Supervisor Mode and Boiler Man/Auto = Man.
Boiler On/Off
Sets the boiler start/stop status when in Manual Mode
No: Turn off boiler if running, otherwise remain off
Yes: Turn on boiler if off, otherwise remain on.
Activated only when in Supervisor Mode and Boiler Man/Auto = Man.
Mixing Valve M/A
Man: Remain in Manual Mode
Auto: Return to Control Mode specified by parameter/boiler conditions
Activated only when in Supervisor Mode.
Mixing Valve
Sets the Mixing Valve % Open to be used for valve when in Manual Mode
Activated only when in Supervisor Mode and Mixing Valve M/A equals
Man.
Sage Boiler Control Instruction Manual Page 40 of 56
Trouble Shooting
Alarm Messages
Alarm Messages are shown one at a time in priority order. The message closest to the top of this List is displayed first.
Following messages are not shown until the higher priority message has cleared. All alarm messag es are also stored in
the Fault History.
LCD Display
Alarm Message
Low Water Level
O Flashing Red
Alarm Light
Off Switch Turn Burner Switch
Low Water Flow
O Red Alarm
Light
Fuel Limit
O Flashing Red
Alarm Light
High Temp Limit
O Flashing Red
Alarm Light
Low Air Flow
O Flashing Red
Alarm Light
FSG Fault
O Flashing Red
Alarm Light
Outlet Temp Fail
O Red Alarm
Light
Inlet Temp Fail
O Red Alarm
Light
OA Temp Fail
O Red Alarm
Light
Remote Temp
Fail
O Red Alarm
Light
Recommended
Action
Manually Reset the
Low Water Cutoff
On
Ensure boiler pump is
running and boiler
water flow is
unobstructed
Manually Reset the
Fuel pressure switch
Manually Reset the
High Temperature
Aquastat
Check combustion air
blower and air
pressure switch
settings and wiring
Manually Reset
Required, Refer to
Flame Safeguard
Manual corrective
actions
Check wiring and
sensor
Check wiring and
sensor
Check wiring and
sensor
Check wiring and
sensor
Explanation
Low Water Cutoff Switch
When this option is configured and a control is installed, the manual reset
low water safety relay is preventing the boiler from starting. If terminal
(LC) does not receive power and the Call For Heat output (CH) is powered
the “Low Water Level” Message is displayed.
Burner Switch is Off
Control switch is in the OFF position and is preventing the boiler from
starting. If terminal (OO) does not receive power and the Call For Heat
output (CH) is powered the “OFF Switch” Message is displayed.
Low Water Flow Switch
Low water flow is preventing the boiler from starting. If terminal (WF) does
not receive power and the Call For Heat output (CH) is powered the “Low
Water Flow” Message is displayed.
Low or High Gas Pressure Switch
The low or high gas pressure switch is preventing the boiler from starting.
If terminal (GP) does not receive power and the Call For Heat output (CH)
is powered the “Fuel Limit” Message is displayed.
High Limit Temperature
The high temperature limit (HL) (and operational temperature limit when
provided) aquastat is preventing a boiler start. If terminal (HL) does not
receive power and the Call For Heat output (CH) is powered the “High
Temp Limit” Message is displayed.
Low Air Flow or Blocked Vent Switch Not Made
The air flow (and blocked vent switch when provided) is preventing a boiler
start. If terminal (CA) does not receive power and the Call For Heat output
(CH) is powered the “Low Air Flow” Message is displayed.
Flame Safeguard Fault
The Flame Safeguard is preventing a boiler start. If terminal (AL) receives
power at any time, the “Flame Failure” Message is displayed.
Boiler Outlet Temperature Sensor Fail
The boiler outlet temperature sensor is not connected or is reading above
or below a valid range. When the boiler outlet sensor fails and the Outlet
Sensor mode was selected the control will transfer to Lost Sensor Blind
Mode
Boiler Inlet Temperature Sensor Fail
The boiler inlet temperature sensor is not connected or is reading above or
below a valid range. When the boiler inlet sensor fails the mixing valve
output will drive to 0% and low temperature alarm and maximum water
differential (boiler outlet minus boiler inlet) temperature hold are disabled.
Outside Air Temperature Sensor Fail
The outside air sensor is configured and is not connected or is reading
above or below a valid range. When the outside air sensor fails the warm
weather shutdown (WWSD) and outside air reset control logics are
disabled.
Remote System Temperature Sensor Fail
The remote system temperature sensor is configured and is not connected
or is reading above or below a valid range. If Remote System
Temperature Sensor mode was selected the control will transfer to Boiler
Outlet Sensor Mode.
Sage Boiler Control Instruction Manual Page 41 of 56
Trouble Shooting
Alarm Messages (continued)
LCD Display
Alarm Message
Remote Input
Fail
O Red Alarm
Light
Comm Failure
O Red Alarm
Light
Low Inlet Temp
O Red Alarm
Light
Memory Failure
O Red Alarm
Light
Recommended Action Explanation
Check wiring and
Remote System
Check wiring and
Remote System
Confirm each boiler has
a unique address
Check wiring and
sensor
Check return water
temperature. Consider
system or operational
changes to avoid low
temperature events
Call Factory
Reset all memories in
System menu:
Clr BIT History
Clr Alarm Hist
Clr Run Time Cnt
Clr Cycle Cnt
Factory Defaults
(Factory Level
Password is required)
Remote Control Input Fail
The Remote Control Input is configured and is not connected or is above
or below a valid range. When the remote control input fails the following
control mode changes are taken automatically:
Selected Modes Resulting Control Mode
Remote Mod Outlet sensor and Local Setpoint
Remote Mod & Remote Sensor Remote Sensor and Local Setpoint
Remote SP Outlet Sensor and Local Setpoint
Remote SP & Remote Sensor Remote Sensor and Local Setpoint
Communication Failure
The Modbus or Peer-To-Peer network has failed. When the Modbus
network fails the following control mode changes are taken
automatically:
Selected Modes Resulting Control Mode
Modbus Mod Outlet sensor and Local Setpoint
Modbus Mod & Remote Sensor Remote Sensor and Local Setpoint
Modbus SP Outlet Sensor and Local Setpoint
Modbus SP & Remote Sensor Remote Sensor and Local Setpoint
After a Modus communication failure, the ‘Comm Failure’ alarm is not
cleared until communication is restored and a successful writes to both
the Remote On / Off Modbus Command (00004) and Remote Firing
Rate or Remote Setpoint (40006) points have been completed, power is
cycled or the protocol parameter is changed to Peer-To-Peer and then
back to Modbus.
When a Peer-To-Peer network has failed the boilers begin operation as
stand alone boilers using the selected parameters.
After a Peer-To-Peer communication failure the ‘Comm Failure’ alarm is
not cleared until communication is restored and the boiler rejoins a
network with at least one other boiler, power is cycled or the protocol
parameter is changed to Modbus and then back to Peer-To-Peer.
Low Boiler Inlet Temperature
If the boiler inlet temperature is below the Low boiler inlet temperature
setpoint, the “Low Inlet Temp” Message is displayed and the boiler inlet
temperature history is stored. See following page for additional
information on Low boiler inlet temperature history storage and retrieval.
Memory Failure
New software has been installed in the Sage Boiler Control or a power
interruption has caused a memory failure. The Call For Heat will be
prevented until the condition is cleared.
Sage Boiler Control Instruction Manual Page 42 of 56
Trouble Shooting
Diagnostic Menu
All values shown in Diagnostic Menu are for display only and cannot be adjusted by the operator. Press and hold the
key to leave the Display Mode and access the Main Menu:
MENU
Use the keys scroll down to the Diagnostic Menu and push the key:
ENTER
Boiler Inlet Temperature History
Display Description
13:31 09/10/06
BOT Sensor Fail
8:45 09/10/06
Low Temp: 130F
8:45 09/10/06
Low for 1:00:02
FAULT HISTORY
The last 10 alarms are stored in memory. Use the arrow keys to scroll through
the alarms. Each alarm is displayed with the time and date it occurred.
BIT HISTORY
The last 10 Low Inlet Temperature Events are stored in memory. Each time
the boiler inlet temperature is less than the “Min In H2O Temp.” parameter, a
low temperature event is recorded. The BIT History screen automatically
toggles between the “lowest temperature for the event” and “Duration Below
Setpoint” displays and provides time and date of each event.
SYSTEM
Items provided by this menu are shown on page 43
DHW Priority
Off
Local/Remote
Off
Remote On/Off
Off
DISCRETE INPUTS
These screens provide a convenient way to trouble shoot wiring during the
installation phase. Each screen provides the status of a controller input.
These displays show the status of the corresponding Discrete Input
Spare Input
Off
Low Water Cutoff
Off
Burner On / Off
Off
Low Water Flow
Off
Fuel Limit
Off
Oper./High Limit
Off
PLEASE NOTE
These displays provide limit string monitoring status. These inputs are only
monitored when there is a Call For Heat. Additionally, if one of these items is
‘open’, items down stream are not monitored.
Low Air Flow
Off
Fuel Energized
Off
These displays show the status of the corresponding Discrete Input
FSG Alarm
Off
Sage Boiler Control Instruction Manual Page 43 of 56
Trouble Shooting
Diagnostic Menu (Continued)
Display Description
Call For Heat
Off
Lockout Indicator
Off
Vent Inducer
Off
Boiler Pump
Off
System Pump
Off
Spare Output
Off
Boiler Outlet
0%
Boiler Inlet
0%
Outside Air
0%
DISCRETE OUTPUTS
These screens provide a convenient way to trouble shoot wiring during the
installation phase. Each screen provides the status of a controller output.
These displays show the status of the corresponding Discrete Output
ANALOG INPUTS
These screens provide a convenient way to trouble shoot wiring during the
installation phase. Each screen provides the status of a controller analog
input.
These displays show the status of the corresponding Analog Input
Remote System
0%
Remote Input
0%
PCB Temperature
0%
Boiler Demand
0%
Mix Valve Demand
0%
ANALOG OUTPUTS
These screens provide a convenient way to trouble shoot wiring during the
installation phase. Each screen provides the status of a controller analog
Output.
These displays show the status of the corresponding Analog Output
Sage Boiler Control Instruction Manual Page 44 of 56
Trouble Shooting
Diagnostic Menu (Continued)
System Menu
Display Description
Software Rev.
PCB Temperature
Clr Alarm Hist
Clr Run Time Cnt
Clr Cycle Cnt
Factory Defaults
S 3.24
70 F
Clr BIT Hist
No Action
No Action
No Action
No Action
No Action
Actual RST
32 F
Actual OAT
-40 F
Actual BOT
32 F
Actual BIT
32 F
Param Code
Software Revision
Displays current Software Revision.
PCB Board Temperature
The operating range for the control is 32 to 140 F.
Clear Boiler Inlet Temperature (BIT) Memory
No Action History remains unchanged
Yes Clears low BIT memory
Clear Alarm History Memory
No Action History Remains unchanged
Yes Clears alarms memory
Clear Boiler Run Time Hour Accumulator Memory
Boiler Run Time Hours are displayed in Display Mode as “Hours”.
No Action Hours Remain unchanged
Yes Clears accumulated hours memory
Clear Boiler Start/Stop Cycle Accumulator Memory
Boiler Start/Stop cycles are displayed in Display Mode as “Cycles”.
No Action Hours Remain unchanged
Yes Clears accumulated cycles memory
Clear User Installed Parameter Memory
No Action Currently set parameter values are unchanged
Set Sets all parameters back to their Factory Default values
Temperature Input Fine Calibration
All inputs are factory calibrated. However, it may become necessary to field
calibrate due to measuring errors resulting from long wire lengths or third party
sensor use. This is a single point calibration tool. To gain the greatest
benefit, it is recommended to calibrate as close as possible to the expected
operating temperature and measure the temperature at the sensor location.
Remote System Temperature (RST)
Outside Air Temperature (OAT)
Boiler Outlet Temperature (BOT)
Boiler Inlet Temperature (BIT)
Calibration Procedure:
1. Select sensor that requires field calibration
2. Run boiler to rated condition
3. Enter the Actual RST, OAT, BOT and BIT
4. Display will flash back to the default (Note Calibration number does
not remain on screen)
5. Calibration is complete. A one point calibration offset is calculated and
applied.
Parameter Code
This number represents “Network Relevant” parameters. It can be used to
ensure that these parameters are identical when establishing a Peer-To-Peer
network
.
Sage Boiler Control Instruction Manual Page 45 of 56
Trouble Shooting
Sensor Resistance Chart
Sensor Temperature vs. Resistance
Water Temperature Ohms of Water TemperatureOhms of Water Temperature Ohms of
°C °F Resistance °C °F Resistance °C °F Resistance
Sage Boiler Control Instruction Manual Page 46 of 56
Trouble Shooting
Security Menu
Passwords
There are three Access Levels in the system; Basic, Supervisor, and Factory.
• At the BASIC Access Level, the user can view many parameters, but is only allowed to edit a small sub-set of
the parameters that are visible.
• At the SUPERVISOR Access Level, the user can view and edit most parameters that are visible. Note: not all
parameters will be visible at the Supervisor Access Level.
• At the FACTORY Access Level, all relevant internal parameters in the system will be visible and programmable.
The Basic Access Level is the access level at power-up if the system password parameter is not equal to zero. The
Supervisor Access Level is the access level at power-up if the system password parameter is equal to zero. If the
system password is non-zero, the Supervisor Access Level may be reached by entering the correct password in the
Enter Password parameter.
The Factory Access Level can be reached by entering the factory password in the Enter Password parameter and
holding the Enter key for at least two seconds when accepting the value entered
Level parameter menu when the system has entered the Factory Access Level. Note that the Access Level parameters
value will indicate "Supervisor".
To exit either of the privileged access levels (Factory and Supervisor), change the value of the Access Level parameter
from "Supervisor" to "Basic". Also, if no key is pressed for ~ 1 hour, the access level will automatically revert to Basic.
No.
0 to 9999
Factory
Setting
Factory
Password
is 86
Range / Choices Parameter and Description
Access Level
Basic
Supervisor
0 to 9999
Basic: Select Basic Level Access to parameters/variables
Supervisor: Select Password Level Access to parameters/variables
Enter Password
Allows user to enter password to gain access to both Supervisor Access
and Factory Access Levels.
Set Password
Holds the user-defined password for the boiler. A password = 0 means
no password protection. Access Level will default to Supervisor Level at
power-up.
. The display will jump to the Access
Sage Boiler Control Instruction Manual Page 47 of 56
Specifications
General
Mechanical:
Panel Assembly: 8 inches wide x 6 inches tall
Message Display: 2 x 16 Character, 8.06 mm characters
Environmental:
Operating Temp: 32 to 140 F (0 to 60 C)
Storage Temp: -20 to 150 F (-28 to 65 C)
Humidity Limits: 15 to 95% (non-condensing)
Front Panel: NEMA 1
Electrical:
Power Supply: 24Vac
Note: All 24Vac Inputs must be connected to the same phase as (PR)
Internal Power Consumption: 8 VA max, 24Vac (+/- 15%), and 6 VA max,
12Vac 0.5A for LO, VI, BP, SP and SO
Discrete Inputs:
Terminal Description
DP Domestic Hot Water Priority (DHWP) 12 Vdc / 1 mA
LR Local / Remote 12 Vdc / 1 mA
RO Remote On / Off (Enable) 12 Vdc / 1 mA
SI Spare Input (Programmable) 12 Vdc / 1 mA
LC Low Water Cutoff Switch 24 Vac / 1mA
OO Burner On / Off Switch 24 Vac / 1mA
WF Low Water Flow 24 Vac / 1mA
GP High and Low Gas Pressure Switches 24 Vac / 1mA
HL Operating or High Limit 24 Vac / 1mA
CA Low Combustion Air Flow 24 Vac / 1mA
CS Fuel Valve Energized 24 Vac / 1mA
AL Flame Safeguard Alarm 24 Vac / 1mA
Discrete Outputs:
Terminal Description
CH Call For Heat (CFH) 24 Vac / 10A
LO Lockout Indicator 12 Vdc / 100mA
VI Spare Output 12 Vdc / 100mA
BP Boiler Pump 12 Vdc / 100mA
SP System Pump 12 Vdc / 100mA
SO Spare Output (Programmable) 12 Vdc / 100mA
Analog Inputs:
Terminal Description Rating
BO Boiler Outlet Water Temperature 10k Thermister, 5Vdc, 5 mA max load
BI Boiler Inlet Water Temperature 10k Thermister, 5Vdc, 5 mA max load
O+
O -
R+
R -
C+
C -
Analog Outputs:
Terminal Description Rating
P+
PV+
V-
MS
MR
Outside Air Temperature 10k Thermister, 5Vdc, 5 mA max load
Remote System Temperature 10k Thermister, 5Vdc, 5 mA max load
Remote Modulation Rate or Remote Setpoint
Modulation Rate Output to Mod Motor
Mixing Valve Output 4-20mA
0-10 Vdc (~100K ohm impedance)
1Vdc = 0%, 9Vdc = 100%
0 – 100 % Duty Cycle, 0V – Off, ~10V - On
4 mA = 0 % Open, 20 mA = 100% Open
Rating
Rating
0 – 10 V, 5 mA max
Sage Boiler Control Instruction Manual Page 48 of 56
Specifications
General (Continued)
Real Time Clock: Battery Backed, 2 yrs without AC Power
Communications: Programming - ISP Port
Boiler Peer to Peer – RS485, RTU
Time and Date Battery:
The battery is only
is removed from the Sage Boiler Control. When new, the battery can power the clock for
approximately 2 years with 24 Vac power removed. The clock battery has a shelf life of
approximately 6 years (without ac applied). Sage Boiler Control configuration and user data
are stored in non-volatile EEPROM. This battery is NOT used to retain this memory.
The battery is located at the back of the Sage Boiler Control for easy replacement.
Component Description
1. Sage Boiler Control Assembly (un-programmed).......................................................................................102106-01
Individual boiler operating and modulation rate control and modulating lead-lag controller.
Built to UL and CSA standards.
2. Replacement Fuse Busman GMC-5A
Repair Part Number
used to power the time of day and date clock chip when the 24 Vac power
3. Immersion Temperature Sensor.................................................................................................................101935-01
½” NPT 10K OHM @ 25C, NTC Thermistor Type, Resistance Ratio R0/R50 = 9.07 temperature
sensor for measuring water temperature in supply manifold, return manifold or system header.
4. Outdoor Temperature Sensor.................................................................................................................801SOL0012
10K OHM @ 25C, NTC Thermistor Type, Resistance Ratio R0/R50 = 9.07 outdoor ai r temperature
sensor with weather proof box and protective sleeve.
For use in outdoor reset applications.
5. Wire Harness (Sage to Q7800H) .........................................................................................................101976-01
6. Q7800H Flame Safeguard Sub Base...................................................................................................101182-01
7. Sage Control (programmed).................................................................................................................102436-01
8.. SBC Parts Carton, MPC [includes MPC Sensor J-Box, Snap bushing (for Sensor J-Box) and MPC
Sage Boiler Control Instruction Manual Page 49 of 56
Network
Relevant*
Appendix A
Parameter Summary
Parameter Range / Choices
Factory
Setting
Security
Level**
Page
Update Display Units Deg F / Deg C Deg F Basic 31
Yes Boiler Pump None / On Always / Purge / On Lead None Supervisor
Update If Purge, set Pump Prepurge 0 to 600 seconds 15 Supervisor
Update Postpurge Delta 0 to 20 F 5 Supervisor
- Inlet Sensor Yes / No Yes Supervisor
- Mixing Valve Yes / No No Supervisor
Update Set Time/Date
Update Fuel Limit Yes / No No Factory
Update Spare Input Off / Sys Pump Feedback / Low Fire Off Supervisor
Update Spare Output Off / CAD / Sys Pump BU / Soft Alarm Off Supervisor
Yes DHWP Off / Isolated Demand / Shared Demand Off Basic 32
Yes Remote control
- Remote 1 volts = 60 F to150 F 140 Supervisor
- Remote 9 volts = 150 F to 230 F 220 Supervisor
Yes Remote Sensor No / Display Only / Control No
Yes System Pump Yes / No No
Update LWC or CAD Yes / No No
Update Alarm Message Low Water level
Yes WWSD
Yes LL Start Trigger 50 to100% of Modulation Rate 90
Yes LL Stop Trigger 0 to 50% of Modulation Rate 25
Yes Boiler On Delay 0 to 900 seconds 5
Yes Boiler Off Delay 0 to 900 seconds 5
Yes %FR On Delay 1 to 30 minutes 20 Factory
Yes %FR Off Delay 1 to 30 minutes 20 Factory
Yes High Fire Limit 40 - 100 % Modulation Rate 100 Supervisor
Yes Deg/Min Hold Off 1 - 10 Degrees / Minute 1 Factory
Yes Cutback Setpoint 100 F - 240 F 220 Factory
Yes Net Start Dwell 16 to 420 Seconds 120 Factory 34
Yes Limit Fault Time 3 to 120 Seconds 5 Factory
Yes Rotation Enable / Disable Disable Basic
Yes Rotation After 8 to720 hours 48 Basic
Yes Outdoor Sensor No / Display Only / Outdoor Reset No Basic
Yes Outdoor Set Up 40 F to 100 F 55 Basic
Yes Boiler Set Up 80 F to 180 F 140 Basic
Yes Outdoor Design - 20 F to 50F 30 Basic
Yes Boiler Design 80 F to 220 F 180 Basic
∗ Parameters identified by “Yes” under the “Network Relevant” column must be configured identically on all boilers.
Unexpected boiler behavior may result if these parameter values differ among boilers on the network. Once
communications is established between all boilers in a system, changes to parameters identified as “Yes” or
“Update” under the “Network Relevant” column at the keypad of any boiler will update that parameter in all boilers.
** To change your current security level refer to page 46 Security Level operations.
Sage Boiler Control Instruction Manual Page 50 of 56
Appendix A
Parameter Summary (continued)
Network
Relevant*
Setup Menu (continued)
- Blower Spd High 0 to100 % of full scale 100 Factory
- Blower Spd Low 0 to100 % of full scale 0 Factory
-
Low Fire Spd 0 to100 % Modulation Rate 0 Factory
-
Fan Purge Spd 0 to100 % Modulation Rate 100 Factory
Yes
Yes Post Purge Time 0 to 600 sec 0 Factory
Yes Local PID P 0-10000 20 Supervisor36
Yes Local PID I 0-10000 30 Supervisor
Yes Local PID D 0-10000 0 Supervisor
Yes Remote PID P 0-10000 20
Yes
Yes
Yes Mixing Valve P 0-10000 15 Supervisor37
Yes Mixing Valve I 0-10000 40 Supervisor
Yes Mixing Valve D 0-10000 0 Supervisor
Yes Mixing Delta T P 0-10000 15
Yes Mixing Delta T I 0-10000 40
Yes Mixing Delta T D 0-10000 0
Low Fire Hold 0 to 1200 sec 0 Factory
Remote PID I
Remote PID D
Parameter Range / Choices
0-10000 30
0-10000 0
Factory
Setting
Security
Level**
Supervisor36
Supervisor36
Supervisor36
Supervisor37
Supervisor37
Supervisor37
Page
34
34
34
34
34
34
36
36
37
37
Setpoint Menu
Yes Operational Setpoint 60 F to 230 F 180 Basic 19
Yes On point 0 F to – 99 F -5 Basic
Yes Off Point 0 F to 99 F 5 Basic
Yes High Temp Stop 60 F to 230 F 200 Basic
Yes DHWP setpoint 140 F to 230 F 180 Basic
Yes WWSD setpoint 40 F 90 F 70 Basic
Yes Max SP 140 F to 230 F 230 Supervisor
Yes Min SP 60 F to 230 F 140 Supervisor
Yes Min BIT 110 F to 235 F 120 Factory
Update Min Inlet H2O Temp 110 F to 180 F 130 Supervisor
Update Max H2O Delta T 20F to 50 F 50 Supervisor
Update Max Delta T Hold 20F to 50 F 40 Supervisor
Communication Menu
- Protocol Peer to Peer / Modbus
- Modbus Address 1-247 1
- Baud Rate 9.6 / 19.2 / 38.4 19.2
- Parity Odd / Even / None None
- Timeout 1 Second to 120 Seconds 30
- Boiler Address 1 to 8 1 Supervisor
∗ Parameters identified by “Yes” under the “Network Relevant” column must be configured identically on all boilers.
Unexpected boiler behavior may result if these parameter values differ among boilers on the network. Once
communications is established between all boilers in a system, changes to parameters identified as “Yes” or
“Update” under the “Network Relevant” column at the keypad of any boiler will update that parameter in all boilers.
** To change your current security level refer to page 46 Security Level operations.
Sage Boiler Control Instruction Manual Page 51 of 56
Appendix B
Customer Parameter Worksheet
Parameter Range / Choices Units
Boiler Configuration Menu
Display Units Circle one: Deg F Deg C
Boiler Pump Circle one: None On Always Purge On Lead
Pump Prepurge Seconds
Postpurge Delta F
Inlet Sensor Circle one: Yes No
Mixing Valve Circle one: Yes No
Spare Input Circle one: Off Low Fire Sys Pump Feedback
Spare Output Circle one: Off CAD Soft Alarm Sys Pump BU
System Configuration Menu
DHWP Circle one: Off Isolated Demand Shared Demand
Remote control
Remote 1 volts = F
Remote 9 volts = F
Remote Sensor Circle one: No Display Only Control
System Pump Circle one: Yes No
LWC or CAD Circle one: Yes No
Alarm Message
Circle one: No Remote SP Modbus SP
Remote Mod Modbus Mod
Setup Menu
WWSD Circle one: Off WWSD of Boiler WWSD of Sys Pump Both
LL Start Trigger
LL Stop Trigger
Boiler On Delay Seconds
Boiler Off Delay Seconds
High Fire Limit %
Rotation Circle one: Enable Disable
Rotation After Hours
Outdoor Sensor Circle one: No Display Only Outdoor Reset
Outdoor Set Up F
Boiler Set Up F
Outdoor Design F
Boiler Design F
Local PID P
Local PID I
Local PID D
Remote PID P
Remote PID I
Remote PID D
Mixing Valve P
Mixing Valve I
Mixing Valve D
Mixing Delta T P
Mixing Delta T I
Mixing Delta T D
%
%
Sage Boiler Control Instruction Manual Page 52 of 56
Appendix B
Customer Parameter Worksheet (continued)
Parameter Range / Choices Units
Setpoint Menu
Operational Setpoint F
On point F
Off Point
High Temp Stop
DHWP setpoint
WWSD setpoint
Max SP
Min SP
Min Inlet H2O Temp
Max H2O Delta T
Max Delta T Hold
Communication Menu
Protocol Circle one: Peer to Peer Modbus
Modbus Address
Baud Rate Circle one: 9.6 19.2 38.4
Parity Circle one: Odd Even None
Timeout
Boiler Address
Seconds
F
F
F
F
F
F
F
F
F
Sage Boiler Control Instruction Manual Page 53 of 56
SERVICE RECORD
DATE SERVICE PERFORMED
Sage Boiler Control Instruction Manual Page 54 of 56
THIS PAGE LEFT BLANK INTENTIONALLY
Sage Boiler Control Instruction Manual Page 55 of 56
Sage Boiler Control Instruction Manual Page 56 of 56
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.