Burnham Sage Boiler Control Instruction Manual

4 (1)
Sage Boiler Control
(SBC)

Instruction Manual

Introduction Quick Reference 2 Overview 4
Product Features Boiler Sequence 6 Single Boiler Control Mode 9 Multiple Boiler Control Mode 10 EMS Boiler Control Mode 11 Manual Boiler Control Mode 14 Auiliary Device 15
Front Panel Features 16 Display Mode 17 Menu Navigation 18 Setpoints Menu 19
Installation Mounting & Wiring Sensors 20 Terminal Layout 25 External Connections 26 Communication 28 Peer-To-Peer Network 30 RS485 Modbus Network 31
Application
The Sage Boiler Control (SBC) has been designed for commercial hot water boiler applications.
Intent
This instruction manual includes detailed functional, installation and setup information.
www.burnhamcommercialcastiron.com
Setup & Tuning Boiler Configuration Menu 33 System Configuration Menu 34 Setup Menu 35 Manual Mode 40
Trouble Shooting Alarm Messages 41 Diagnostics Menu 43 Sensor Resistance Chart 46 Security Menu 47
Specifications General 48 Component Description & Repair Part Numbers 49
Appendix A. Parameter Summary 50 B. Customer Parameter Worksheet 52
Warranty Rear Cover
Sage Boiler Control Front Panel (Showing Power & Alarm LEDs,
2 Line 16 Character Message Display
and 4 Pushbuttons)
Sage Boiler Control Instruction Manual Page 1 of 56 102121-01R2 - 4/11
Introduction

Quick Reference

CONTROL
MODE
LCD Display
Typical
Application
Water Setpoint
Temperature
Sensor
Setpoint Operator Operator
“On” and “Off”
Point
Outdoor Air
Reset
Domestic Hot
Water Priority
(DHWP)
Warm Weather
Shutdown
(WWSD)
Call For Heat Call For Heat
Modulation
Rate
Internal Boiler
Control
Lead Boiler
Control
Remote EMS
Control Manual
Control
Remote
Connections
Local / Remote
Input (LR)
Outlet Sensor
& Local SP
Mode
Remote Sensor
& Local SP Mode
Single Boiler Multiple Boilers
Outlet Sensor &
Remote SP
Mode
Remote Sensor
& Remote SP
Mode
Remote
Control
Mode
Energy Management System (EMS) Boiler Control
Single Boiler
Setpoint Input
Multiple Boilers
Setpoint Input
Modulation
Rate Input
Manual
Mode
Manual
Operation
Boiler Outlet Remote System Boiler Outlet Remote System Ignored Ignored
Input (C+C-) or
Modbus*
Input (C+C-) or
Modbus*
Ignored Ignored
Operator Operator Operator Operator Ignored Ignored
Option Option Ignored Ignored Ignored Ignored
Option Option Ignored Ignored Ignored Ignored
Option Option Option Option Option Ignored
Based on
Setpoints
Based on Setpoints
Based on Setpoints
Based on Setpoints
Input (RO) or
Modbus
Manually Set
Based on
Setpoint
Peer-to-Peer
Connected
Ignored Ignored Ignored Ignored
Based on
Setpoint
With Peer-to-
Peer Connected
Based on
Setpoint
With Peer-to-
Peer Connected
Based on
Setpoint
With Peer-to-
Peer Connected
Ignored Ignored
Ignored Ignored
Input (C+C-)
or Modbus
Ignored
Ignored Ignored Ignored Ignored Ignored By Operator
Ignored Ignored Closed Closed Closed Ignored
Remote On/Off
(Enable)
Input (RO)
Remote Control
Input (C+C-)
Communication
Network
Additional
Information
Enable/
Disable
No No
Peer-To-Peer
or
Modbus*
Enable/
Disable
Peer-To-Peer
or
Modbus*
Enable/
Disable
Remote
Setpoint
Peer-To-Peer
or
Modbus*
Enable/
Disable
Remote
Setpoint
Peer-To-Peer
or
Modbus*
On/Off Ignored
Remote
Modulation
Modbus
Only
Ignored
Modbus Only
Page 9 Page 10 Page 11 Page 12 Page 13 Page 14
* If Modbus is selected the Peer-To-Peer Network can not be used. Modulating Lead/Lag features require the Peer-To­Peer Network.
Sage Boiler Control Instruction Manual Page 2 of 56
Introduction
Quick Reference
Abbreviation List
Abbreviation Description
AL Flame Safeguard Alarm
BIT Boiler Inlet Temperature
BOT Boiler Outlet Temperature
BP Boiler Pump BV Blocked Vent Switch
C Common Termination Point
CA Low Combustion Air Flow
CH Call For Heat (CFH)
CS Fuel Valve Energized
DH Domestic Hot Water Heating Demand
DP Domestic Hot Water Priority (DHWP) SBC Sage Boiler Control EMS Energy Management System
GP High and Low Gas Pressure Switches
HL High Limit Aquastat
HP High Pressure Gas Switch
IN Boiler Inlet Water Temperature
LC Low Water Cutoff Switch
LL Lead Lag LO Lockout Indicator LR Local / Remote
M Electric Motor Mix 3 Way Mixing Valve OA Outside Air Temperature
OL Operating Limit Aquastat
OO Burner On / Off Switch
OUT Boiler Outlet Water Temperature
RO Remote On / Off
RST Remote System Temperature
SH Space Heating Demand
SI Spare Input (Programmable)
SO Spare Output (Programmable)
SP Setpoint (As found in “Ope rational SP” and “Remote SP” SP System Pump
VI Vent Inducer
WF Low Water Flow
WWSD Warm Weather Shutdown
Termination Number Identification (Typical):
Description
Mixing Valve
Control, (MR, MS)
Termination
Numbers
Sage Boiler Control Instruction Manual Page 3 of 56
Introduction
Overview Sage Boiler Control Overview
The Sage Boiler Control (SBC) is a complete boiler monitoring and automation system. The SBC provides advanced boiler modulation, operating control, diagnostics, multiple boiler lead-lag and auxiliary device control. The SBC provid es advanced control features in an easy to use package.
Flexible, Field Selectable Control
Control modes, water system, boiler auxiliary and modulating lead/lag control features are menu selectable without the need for external programmers, laptops or down loads. Every boiler is shipped with factory defaults that make field menu selections unnecessary unless you are applying additional control features.
Boiler Monitoring and Diagnostic Displays
The SBC’s two line by sixteen character LCD display may be used for monitoring boiler inlet and outlet, remote system and outside air temperatures, modulation rate setpoint and modulating percent and mixing valve demand percent. Additionally, the display automatically presents boiler sequence messages, alarms, hold and lockout messages. A diagnostic menu is included that provides the last 10 alarm messages and boiler inlet temperature alarm history. Boiler inlet temperature alarm history includes time and date, the lowest inlet temperature reached and the amount of time the water temperature dropped below the alarm setpoint.
Modulation Rate and On/Off Modes
The SBC may simply control boiler modulation and on/off output based on the boiler water outlet temperature and an operator adjusted setpoint. However, using parameter selections, the SBC allows the boiler modulation and on/off output to respond to remote system water and outside air temperatures, Domestic Hot Water Priority (DHWP) input or Energy Management System (EMS) modulation rate demand, remote setpoint or remote start/stop commands. Parameter selections of remote system water temperature and remote mode determine the choice of one of six different control modes.
Advanced Availability
The above control modes are menu selectable options. However, if a selected sensor fails, the SBC automatically changes to a control mode that will allow continued automatic operation of the boiler. For example, in the event of a remote system temperature sensor failure, the SBC will automatically switch to boiler outlet temperature sensor based control.
Outdoor Air Reset
When selected the modulation rate setpoint is automatically adjusted based on outside air temperature. Outdoor air “reset” setpoint saves fuel by adjusting the water temperature of a heating boiler lower as the outside air temperature increases.
Warm Weather Shutdown (WWSD)
Some boilers are used primarily for heating buildings, and the boilers can be automatically shutdown when the outdoor air temperature is warm. When outside air temperature is above the WWSD setpoint, this function will prevent the boiler, boiler pump and/or the system pump from starting.
Domestic Hot Water Priority (DHWP)
Some boilers are used primarily for building space heating, but also provide heat for the domestic hot water users. When the outdoor temperature is warm, the outdoor reset setpoint may drop lower than a desirable domestic hot water temperature. When enabled and a DHWP contact input is detected, the hot water setpoint is adjusted to be greater than a field adjustable DHWP Setpoint.
Water Side Control Outputs
In order to maximize the life and availability of hot water systems it may be desirable to automate mixing valves, boiler pumps, system pumps, and standby system pumps. The SBC makes this type of automation totally integrated and cost effective. The control of these devices is field selectable through simple yes/no menu selections.
Combustion Air Side Control Outputs
Boiler room Combustion air dampers (fresh air dampers) and Vent Inducer control outputs are field selectable options.
Peer-To-Peer Network The SBC includes state-of-the-art modulating lead-lag sequencer for up to eight (8) boilers capable of auto rotation, outdoor reset and peer-to-peer communication. The peer-peer network is truly “plug and play”. Communication is activated by simply connecting a RJ11 telephone line between boilers. The SBC provides precise boiler coordination by sequencing boilers based on both remote system water temperature and boiler modulation rate. For example, the lead boiler can be configured to start a lag boiler after operating above 90% modulation rate for longer than an adjustable time. The boilers are modulated in “unison” (parallel) modulation rate to ensure even heat distribution
Modbus Communication Interface
A factory configured RS485 Modbus interface is available for Energy Management System (EMS) or SCADA system monitoring and control.
Sage Boiler Control Instruction Manual Page 4 of 56
Introduction

Overview

Standby System Pump
Remote System
System Pump
System
Supply Water
Switch
Domestic Hot
Temperature
Feedback
Water Override
System Pump
Supply
Domestic
Hot Water
System
Modbus RS-485, RJ-11
Local / Remote Switch
High Temperature Limit
Connection
Boiler Outlet TemperatureBoiler Inlet Temperature
Primary
Spare Output
Call For Heat Relay
Fuel Valve Energized
Control
Alarm (Lockout)
Low Fire
Remote On / Off (Enable)
Lockout Indicator
Building Automation
Control
M
Mixing Valve
Boiler Pump
Low Water Flow Switch
Low Water Cutoff Switch
Return Water
Outside Air
Temperature
Sage Boiler Control
FAN
Switch
Air Flow
Combustion
Control
Modutrol Motor
Switch
Damper
Combustion Air
M
Supply
Fresh Air
Boiler On/Off
Boiler
Jacket
Fuel
Fuel Switches
Supply
Sage Boiler Control Instruction Manual Page 5 of 56
Product Features
Boiler Sequence
BOI LER STATE
LCD Display
Pa r a me ter / Notes
Boiler Disable or R em ot e On/Off
Outdoor Air T em p >
Warm Weat her Shut down Set point
Domestic Hot Water Priority
RO
O+,O-
DP
Terminal Number
-
44,30,
75
20,74
Start/ Sto p Seq u en ce St atesPre-Seq u en ce States
Parameter/Note
Boiler Disable
Warm Weather
Shutdown
Locko ut
b &ca aa
Pump Purge
Standby
Purge / Pilot Ignition
Limit Hold
-3/d - - -53 4/d
-
Low Fire / Ignition
Main I gnition
Low Fire Hold
Boiler Running
Pump Cooldown
Fan Post Purge
54/d
Boil e r Enabl e/Disable On
Domestic Hot Water Demand Monitored
Low Fire Hold
Fuel Valv e Energiz ed
Flame Saf eguard Alarm
Sys t em Pum p F eedback
Call For Heat
Recycling Limits
(LC, OO, WF, GP and HL inputs)
Limits
Inputs
Non-Recycling Limits
(Combustion Air Flow (CA Input))
Call For Heat Relay
Lockout Indicator
( M anual R es et R equire d)
Spare Output
Boiler Pump
System Pump
Relay Outputs Inter lo ck Inpu ts
Syst em Pum p Bac k up Pump
Combustion Air Damper
System Alarm
Mix ing Valve Out put
Blower High Speed
Purge %
Modulation
Firing Rat e
Modulation Outputs
Low F ire %
Blower 0 Volts
SI CS AL
SI
R+,R-
OR
BO,BC
LC , O O ,WF,
GP,HL
CA
CH
LO
VI BP SP
SO SO SO
MS,MR
V+,V-,
P+,P-
V+,V-,
P+,P-
V+,V-,
P+,P-
V+,V-,
P+,P-
V+,V-,
P+,P-
9
-
-
9
70,71,
72
8,27,
28
-
-
-
-
2,30
25,30
10
10,27/
e
10
6,79,
80 49
52
-
9,51/f
50
System Pump Feedback Monitored
Call For Heat
Recycling Limits Made
Non-Recycling Limits Made
Call For Heat Relay On
Spare Output On
Boiler Pump On
System Pump On
Starts in response to System Pump Feedback In put SI
Combustion Air Damper Open
Alarm Status is Monitored
Modulate
Notes
a. Boiler Pump is “On” when the Boiler Pump is set to “On Always” or the boiler is lead boiler and Boiler Pump is set to “On Lead” b. Boiler Pump is "On" when the Boiler Pump is set to "On Always" and WWSD is set to "WWSD of System Pump" or “Off” c. System Pump is "On" when the System Pump is set to “yes” and WWSD is set to either "WWSD of Boiler" or "Off" d. Boiler pump is "On" during Prepurge and Post Purge when Boiler Pump is set to "Purge" or boiler is lead & Boiler Pump is set to “On Lead” e. Combustion Air Damper Spare Output is maintained “On” for 2 minutes after the Call For Heat is removed. f. Modulation rate is held at purge % when low fire input is not provided.
Sage Boiler Control Instruction Manual Page 6 of 56
Product Features
Boiler Sequence (Continued) Pre-Sequence States
BOILER
STATE
LCD Display
Boiler
Disabled
Warm
Weather
Shutdown
Lockout Any Mode
Standby
Start/Stop Sequence States
BOILER
STATE
LCD Display
Pump Purge
Limit Hold Any Mode
Purge / Pilot
Ignition
Low Fire /
Ignition
Main Ignition Any Mode
Low Fire
Hold
Boiler
Running
Fan Post
Purge Pump
Cooldown
CONTROL MODE
LCD Display
Any Mode
(Except for
Remote Control)
Any Mode
(Except for
Manual Mode)
Outlet Sensor &
Local SP Mode
Remote Sensor
& Local SP
Mode
Outlet Sensor &
Remote SP
Mode
Remote Sensor
& Remote SP
Mode
Remote Control
Mode
Manual
Operation Mode
CONTROL MODE
LCD Display
Any Mode
(Except
Manual Mode)
Any Mode
Any Mode
Any Mode The modulation output is held at the Low Fire for the Low Fire Hold time. Any Mode
Any Mode
Any Mode

Description

Boiler is prevented from starting; Remote On/Off (Enable) (Terminal RO) Input is not energized.
Boiler is prevented from starting, Warm Weather Shutdown (WWSD) is enabled and outside air temperature is above the WWSD Setpoint
Boiler is prevented from starting, Flame Safeguard lockout is present. A Flame Safeguard manual reset is required Control monitors boiler outlet temperature, a Call For Heat is initiated when boiler outlet temperature is below the Operational Setpoint
Control monitors Remote System Temperature, a Call For Heat is initiated when Remote System Temperature is below the Operational Setpoint
Control monitors boiler outlet temperature, a Call For Heat is initiated when boiler outlet temperature is below the Remote Setpoint Input (Terminal C+,C- or Modbus Interface) Control monitors Remote System Temperature, a Call For Heat is initiated when Remote System Temperature is below the Remote Setpoint Input (terminal C+,C- or Modbus Interface) Control monitors Remote On/Off (Enable) input (Terminal RO or Modbus Interface), a Call For Heat is initiated when input is energized
A Call For Heat is initiated when Manual Mode Menu item Boiler On/Off is set to On

Description

Once a Call For Heat is initiated and Boiler Pump Purge is selected, the pump output is energized until the Pump Prepurge Time is complete. If the Call For Heat condition still exists at the end of the Prepurge Time (the temperature of the water at the sensor may rise with boiler water flowing passed it) the pump will continue to operate and the Call For Heat Relay is energized Power is applied to the safety limit string. If any limits does not pass power (is not energized), the alarm LED and LCD display shows the reason the start sequence is on Hold. Refer to Trouble shooting section for explanation of individual lockout and alarm messages After the limit string passes power, the fan is started, the modulation output is set to Purge Rate. When the purge period is complete, the flame safeguard sequences on the ignition transformer and pilot When the Spare Input Low Fire is selected, modulation output is set to the Low Fire Speed when the Spare Input is energized. The main gas valve input is energized and the modulation output is held constant for an ignition stabilization period
When this Low Fire Hold time is complete, the modulation output is released to modulate When water temperature is above setpoint, there is a Flame Safeguard or Limit fault, the Call For Heat is ended and the modulating output is set to Purge Rate for the Post Purge Time When Boiler Pump Purge is selected, the boiler pump remains “on” until the boiler outlet temperature is less than the Post Purge Delta (default is 5 F) above the Boiler Inlet Temperature.
Sage Boiler Control Instruction Manual Page 7 of 56
Product Features
Boiler Sequence (Continued) Multiple Boilers
185
Setpoint
High Fire Limit
(Parameter 37)
1
- Lead Boiler Start
2
- Temperature Based Lag Boiler Start
3
- Modulation % Based Lag Boiler Start
4
- Lag Boiler Stop
5
- Lead Boiler Stop
Notes
- The “Boiler Address” parameter assignment determines the boiler sequencing order.
- The Lead Boiler automatically rotates (when “Rotate” parameter is enabled) based on field adjusted time
- Lead Boiler is the first boiler to turn on and the last boiler to turn off, (First On, Last Off, FOLO).
- Lag Boilers are turned on in order and turned off in reverse order, (First On, Last Off, FOLO).
- Tripped boilers are replaced without waiting for the Boiler On Delay timer. If a tripped boiler becomes available
180
SYSTEM
BOILER
PLANT LOAD
175
TEMPERATURE
100
50
FIRING RATE
0
3 2 1 0
(# BOILERS REQURED)
Lead Boiler
Start
1
Start
st
1
Fast
Load
Change
Lag
2
2
Slow
Load
Change
3
2
Start
nd
Lag
Stop
nd
2
Lag
4 54
Stop
1st Lag
Lead Boiler
Boiler Start and Stop Peer-To-Peer Network Sequence Diagram
(3 boiler system shown, typical for up to 8 boilers)
Water temperature is below the setpoint by more than the “On Point” differential
Water temperature is below the setpoint by more than the “On Point” differential for longer than the adjustable time delay (“Boiler On Delay” parameter).
The boiler modulation rate has been above the adjustable limit (“LL Start Trigger” parameter) for longer than the time delay.
The boiler modulation rate has been below the adjustable limit (“LL Stop Trigger” parameter) for long er than the time delay. Additionally, lag boilers are stopped when water temperature is above the setpoint by more than the “Off Point” differential for longer than the “Boiler Off Delay” parameter)
The last boiler remains on line until the water temperature is above the “Off Point” setpoint for longer than the time delay.
(“Rotate After” parameter, default is 168 hours). When rotating, the lead boiler will move to the end of the lag order and the 1
st
lag boiler will become the lead. The rest of the boilers will then move up in the lag order
accordingly.
it is returned to service.
5
Stop
Sage Boiler Control Instruction Manual Page 8 of 56
Product Features
Single Boiler Control Display Shows: Outlet Sensor & Local SP Mode
Return
Water
Outside Air
Temperature
(O+, O-)
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
System
Circulator
System
Supply Water
DHW
Override
Switch (DP)
Domestic Hot Water (DHW)
Supply
Outlet Sensor & Local SP Mode Application Diagram
(Showing Relevant Connections)
Features
Setpoints
The operator selects the setpoint and on and off points from the LCD display.
Modulation Rate Control
Boiler automatically modulates to maintain the boiler outlet temperature at setpoint.
Call for Heat
The Call For Heat is determined by the setpoint, on and off points and boiler outlet temperature.
Options
Outside Air Reset
If enabled, the Outside Air Sensor will automatically adjusted the setpoint.
Warm Weather Shutdown (WWSD)
If enabled, the WWSD will disable a boiler start when outside air temperature is above a Warm Weather Shutdown (WWSD) setpoint.
Domestic Hot Water Priority (DHWP)
If enabled, the DHWP will adjust the setpoint to satisfy the DHWP setpoint when a DHWP input (DP) is energized.
Boiler Inlet
Temperature
(BI, BC)
EMS System Hardwired Connections
Lockout Indicator (LO) Soft Alarm (SO) Remote On / Off (Enable) (RO)
RJ11, RS-485 Communication
Peer-To-Peer Network for Modulating Lead/Lag
Or
Modbus Network for Touch Screen or EMS Monitoring
Selecting This Control Mode
To select Outlet Sensor & Local SP Mode set the following parameters:
System Configuration Menu: Remote Control = “No” Remote System Temperature Sensor = “No”
Remote On / Off (Enable) Input (RO) = Closed [Jumper (RO) to (C)]
If the Remote On / Off (Enable) (RO) input is opened, the Call For Heat Relay (CH) is de-energized.
Modbus Network
To establish a Modbus network set the following parameters: Communication Menu:
Protocol = Modbus Modbus Address = Give each boiler a unique address. Baud Rate = Set identical to remote system Parity = Set identical to remote system
Connect all boilers using a RJ11 ended telephone cable If the Modbus network is activated the remote system may
monitor and/or control boiler operation. Refer to page 29 for additional information.
Sage Boiler Control Instruction Manual Page 9 of 56
Product Features
Multiple Boiler Control Display Shows: Remote Sensor & Local SP Mode
Outside Air
Temperature
(O+, O-)
Remote System
Temperature
(R+,R-)
System
Circulator
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
Boiler
Circulator
Boiler Inlet
Temperature
(BI, BC)
DHW Override
Switch (DP)
Wired to Each
ECM Controller
Boiler
Circulator
RJ11, RS 485
Peer to Peer
Network
Remote System
Temperature
(R+,R-)
Outside Air
Temperature
(O+, O-)
Connects to
Up to Eight
Boilers
Domestic Hot Water Priority
(DP)
Remote Sensor & Local SP Mode Application Diagram
(Showing relevant connections for 3 boilers, typical for up to 8)
Features
Setpoints
The ope
rator selects the setpoint and on and off points
from the LCD display.
Modulation Rate Control
Boiler automatically modulates to maintain the Remote System Temperature (RST) at setpoint.
Call for Heat
The Call for Heat is determined by setpoint, on and off points and RST. If a Peer-To-Peer network is activated, a Call for Heat is also initiated when the Lead boiler modulation rate % is above an adjustable High Fire Rate Limit (parameter 37) for too long a time.
Options
Outside Air Reset
If enabled, the Outside Air Sensor will automatically adjusted the setpoint.
Warm Weather Shutdown (WWSD)
If enabled, the WWSD will disable a boiler start when temperature is above a Warm Weather Shutdown (WWSD) setpoint.
Domestic Hot Water Priority (DHWP)
If enabled, the DHWP will adjust the setpoint to satisfy the DHWP setpoint when a DHWP contact input (DP) is closed. When multiple boilers monitor the DHWP input, an isolated contact is required for each boiler.
Selecting This Control Mode
To select Remote Sensor & Local SP Mode set the following parameters:
System Configuration Menu: Remote Control = “No” Remote System Temperature Sensor = “Control”
Remote On / Off (Enable) Input (RO) = Closed [Jumper (RO) to (C)]
If the Remote On / Off (Enable) (RO) input is opened, the Call For Heat Relay (CH) is de-energized.
If the Remote System Temperature Sensor (RST) fails, the control mode is automatically switched to Outlet Sensor & Local SP Mode.
Peer-To-Peer Network
To establish a Peer-To-Peer network follow the procedure provided on page 28.
If the Peer-To-Peer network is activated the Lead boiler controls modulation rate and Call for Heat for all networked boilers. Up to 8 networked boilers are fired in “Unison” (all at the same modulation rate).
Sage Boiler Control Instruction Manual Page 10 of 56
Product Features
Energy Management System (EMS) Boiler Control Display Shows: Outlet Sensor & Remote SP Mode
Return
Water
Outside Air
Temperature
(O+, O-)
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
System
Circulator
System
Supply Water
DHW
Override
Switch (DP)
Domestic Hot Water (DHW)
Supply
Outlet Sensor & Remote SP Mode Application Diagram
(Showing relevant connections)
Features
Setpoints
The setpoint is determined by the Remote Input (C+,C-) or Modbus Input and operator sets the on and off points from the LCD display.
Modulation Rate Control
Boiler automatically modulates to maintain the boiler outlet temperature at setpoint.
Call for Heat
The Call For Heat is determined by setpoint, on and off points and boiler outlet temperature.
Options
Warm Weather Shutdown (WWSD)
If enabled, the WWSD will disable a boiler start when temperature is above a Warm Weather Shutdown (WWSD) setpoint.
Outside Air Temperature may be displayed only. Outside Air Reset and Domestic Hot Water Priority input (DP) are ignored.
Boiler Inlet
Temperature
(BI, BC)
EMS System Hardwired Connections
Lockout Indicator (LO) Soft Alarm (SO) Remote On / Off (Enable) (RO) Remote Setpoint (C+,C-)
RJ11, RS-485 Communication
Peer-To-Peer Network for Modulating Lead/La g
Or
Modbus Network for Touch Screen or EMS Monitoring
Selecting This Control Mode
To select Outlet Sensor & Remote SP Mode set the following parameters:
System Configuration Menu: Remote Control = “Remote SP” Remote System Temperature Sensor = “No”
Local / Remote Input (LR) = Closed Remote On / Off (Enable) Input (RO) = Closed [Jumper (RO) to (C)]
When the Local / Remote Input (LR) is open, Remote Input (C+,C-) is ignored and Outlet Sensor & Local SP Mode is active.
If the Remote On / Off (Enable) (RO) input is opened, the Call For Heat Relay (CH) is de-energized.
Modbus Network
To establish a Modbus network set the following parameters: Communication Menu:
Protocol = Modbus Modbus Address = Give each boiler a unique address. Baud Rate = Set identical to remote system Parity = Set identical to remote system
Connect all boilers using a RJ11 ended telephone cable If the Modbus network is activated the remote system may
monitor and/or control boiler operation. Refer to page 29 for additional information.
Sage Boiler Control Instruction Manual Page 11 of 56
Product Features
Energy Management System (EMS) Boiler Control (continued) Display Shows: Remote Sensor & Remote SP Mode
Return
Water
Outside Air
Temperature
(O+, O-)
Remote System
Temperature
(R+,R-)
System
Circulator
System
Supply Water
Features
Setpoints
The setpoint is determined by the Remote Input (C+,C-) and operator sets the on and off points from the LCD display.
Modulation Rate Control
Boiler automatically modulates to maintain the Remote System Temperature (RST) at setpoint.
Call for Heat
The Call For Heat is determined by setpoint, on and off points and Remote System Temperature. If a Peer-To­Peer network is activated, a Call for Heat is also initiated when the Lead boiler modulation rate % is above an adjustable High Fire Rate Limit (Parameter 37) for too long a time.
Options
Warm Weather Shutdown (WWSD)
If enabled, the WWSD will disable a boiler start when temperature is above a Warm Weather Shutdown (WWSD) setpoint.
Outside Air Reset and Domestic Hot Water Priority input (DP) are ignored
.
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
Boiler
Circulator
Boiler Inlet
Temperature
(BI, BC)
Remote Sensor & Remote SP Mode Application Diagram
(Showing relevant connections for 3 boilers, typical for up to 8)
Selecting This Control Mode
To select Remote Sensor & Remote SP Mode set the following parameters:
System Configuration Menu: Remote Control = “Remote SP” Remote System Temperature Sensor = “Control”
Local / Remote Input (LR) = Closed [Jumper (LR) to (C)] Remote On / Off (Enable) Input (RO) = Closed [Jumper (LR) to (C)]
When the Local / Remote Input (LR) is open, Remote Input (C+,C-) is ignored and Remote Sensor & Local SP Mode is active.
If the Remote On / Off (Enable) (RO) input is opened, the Call For Heat Relay (CH) is de-energized.
Peer-To-Peer Network
To establish a Peer-To-Peer network follow the procedure provided on page 28.
If the Peer-To-Peer network is activated the Lead boiler controls modulation rate and Call for Heat for all networked boilers. Up to 8 networked boilers are fired in “Unison” (all at the same modulation rate).
Wired to Each
ECM Controller
Boiler
Circulator
EMS System Connections
Lockout Indicator (LO) Soft Alarm (SO) Remote On / Off (Enable) (RO) Remote Setpoint (C+,C-)
Remote System
Temperature
(R+,R-)
Outside Air
Temperature
(O+, O-)
Connects to
Up to Eight
Boilers
RJ11, RS 485
Peer to Peer
Network
Sage Boiler Control Instruction Manual Page 12 of 56
Product Features
Energy Management System (EMS) Boiler Control (continued) Display Shows: Remote Control Mode
Return
Water
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
System
Circulator
System
Supply Water
Remote Control Mode Application Diagram
(Showing relevant connections)
Features
Modulation Rate Control
The Remote Input (C+,C-) or Modbus input sets modulation rate. The setpoint is ignored.
Call for Heat
The Call For Heat is determined by Remote On/Off input (RO) or Modbus input. The on and off points are ignored. The boiler will turn off if the water temperature increases past the temperature set on the Operational Temperature Limit.
Options
Outside Air Reset and Domestic Hot Water Priority input (DP) and Warm Weather Shutdown are ignored
.
Boiler Inlet
Temperature
(BI, BC)
EMS System Hardwired Connections
Lockout Indicator (LO) Soft Alarm (SO) Remote On / Off (Enable) (RO) Remote Setpoint (C+,C-)
RJ11, RS-485 Communication
Modbus Network EMS Monitoring and Control Remote Firing Rate via Modbus Remote on/off via Modbus
Selecting This Control Mode
To select Remote Control Mode set the following parameters: System Configuration Menu:
Remote Control = “Remote Mod” Remote System Temperature Sensor = “Display Only”
Local / Remote Input (LR) = Closed [Jumper (LR) to (C)]. When the Local / Remote Input (LR) is open, Remote Input
(C+,C-) is ignored and Remote Sensor & Local SP Mode is active.
Modbus Network
To establish a Modbus network set the following parameters: Communication Menu:
Protocol = Modbus Modbus Address = Give each boiler a unique address. Baud Rate = Set identical to remote system Parity = Set identical to remote system
Connect all boilers using a RJ11 ended telephone cable If the Modbus network is activated the remote system may
monitor and/or control boiler operation. Refer to page 29 for additional information.
Sage Boiler Control Instruction Manual Page 13 of 56
Product Features
Manual Boiler Control Mode Display Shows: Manual Operation Mode and Lost Sensor Blind Mode
Return
Water
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
System
Circulator
System
Supply Water
Boiler Inlet
Temperature
(BI, BC)
EMS System Hardwired Connections
Lockout Indicator (LO) Soft Alarm (SO) Remote On / Off (Enable) (RO)
RJ11, RS-485 Communication
Modbus Network EMS Monitoring
Manual Operation Mode and Lost Sensor Blind Mode Application Diagram
(Showing relevant connections)
MANUAL OPERATION MODE Features
Modulation Rate Control
The operator sets the modulation rate. The setpoint is ignored.
Call for Heat
The Call For Heat Relay (CH) is directly controlled by the operator. The on and off points are ignored. The boiler will turn off if the water temperature increases past the temperature set on the High Temperature
LOST SENSOR BLIND MODE
If both Remote System Temperature (RST) and boiler outlet temperature and the Remote Control input signal (C,-C+) have failed, the boiler is started and run continuously at the lowest modulation rate.
If the controller has entered Lost Sensor Blind Mode, the user may switch the boiler into manual mode or repair, replace or reconnect required temperature sensors.
Stop parameter. Options
Outside Air Reset, Warm Weather Shutdown and Domestic Hot Water Priority are ignored
.
The Spare Output (VI) and Combustion Air Damper (SO) outputs are energized when the operator starts the boiler in manual mode.
Selecting This Control Mode
Manual Mode is activated from the Manual Mode menu when Supervisor password is entered. Simply set the Boiler Man/Auto parameter to “Man” and adjust the Modulation Rate and Boiler On/Off menu items as required. Once activated the green LED flashes. To leave manual mode set the Boiler Man/Auto parameter to “Auto”.
Sage Boiler Control Instruction Manual Page 14 of 56

Product Features

Auxiliary Device Control
Return
Water
M
Fresh Air
Supply
Combustion Air
Open/Close (SO)
Damper
Boiler Inlet
Temperature
(BI, BC)
Standby System Pump
Mixing Valve
M
Control (MR, MS)
Boiler Pump
Start/Stop (BP)
Boiler Outlet
Temperature
(BO, BC)
Start/Stop (SO)
System Pump
Start/Stop (SP)
Spare Output (VI)
System Pump Feedback (SI)
System
Supply Water
Energy Management
System (EMS)
Interface
Modbus RS-485, RJ-11 Connection
Auxiliary Control Application Diagram
(Showing All Options)
Features
Mixing Valve
The primary function of the mixing valve is to protect the boiler from thermal shock and sustained flue gas condensation. When configured, the mixing valve output compares both minimum return water temperature setpoint to measured return water temperature and boiler differential temperature setpoint to measured differential temperature (boiler outlet minus inlet temperature).
If the boiler return water temperature drops below the minimum inlet water temperature setpoint (“Min In H2O Temp” parameter) or the differential temperature increases above the maximum water differential temperature setpoint (“Max H2O Delta T” parameter) the mixing valve opens to allow hot boiler outlet water to blend with cold return water. The valve repositions toward 0% recirculation after return water increases above setpoint and the differential temperature reduces below setpoint.
The mixing valve may be controlled manually from the Manual Mode menu when Supervisor password is entered. Simply set the Mixing Valve M/A parameter to “Man” and adjust the Mixing Valve % as required. Once activated the green LED flashes. To leave manual mode set the Mixing Valve M/A parameter to “Auto”
Combustion Air Damper and Vent Inducer
When the Relay (CH) is closed, the Combustion Air Damper (CAD) and Vent Inducer outputs are energized. If the CAD open position is needed to be proven, a limit switch may be wired in series with the Low Water Cut-off Switch input (LC). The alarm Message may be modified to reflect this change.
Boiler Pump
The Boiler Pump output (BP) may be configured as None, Always On, Purge or Lead On by setting the Boiler Pump (parameter 2) (refer to page 31): Always On Boiler pump runs continuously. Purge Boiler pump runs during a pump Prepurge
(Pump Prepurge (parameter 3) time before boiler starts) while the boiler is running and during a pump cooldown period (pump cooldown maintains the boiler pump running until the boiler outlet temperature is within the Postpurge Delta (parameter 4) degrees above the boiler inlet temperature).
Lead On: Boiler Pump runs continuously when the
boiler is the lead and during the fan pre­purge, while the boiler is running and during
fan post purge when a lag boiler. The boiler pump sequences are detailed on the boiler sequence diagram on page 6.
System and Standby System Pump
When configured, the System Pump output (SP) is always energized except when turned off by the Warm Weather Shutdown feature. A Standby System Pump output (SO) may be configured as a backup to the system pump. The Standby System Pump is started based on the System Pump Feedback input (SI).
Selecting This Control Mode
These control modes may be selected using the Boiler and System Configuration menus.
Sage Boiler Control Instruction Manual Page 15 of 56
Front Panel
Features
POWER LED [Steady On Green LED] indicates power is available down
stream of the Sage Boiler Control’s on board fuse.
[Flashing On Green LED] indicates manual mode operation
for boiler modulation
ALARM LED [Steady On Red LED] indicates an alarm is active. [Flashing On Red LED] indicates a lockout alarm is a c tive
and a manual reset may be required
SCREEN 2 line by 16 character display provides operational, alarm,
sequence status, configuration and diagnostic user in terface
ENTER The ENTER key has no function in display mode. The
ENTER key is used to select menus, menu items and save edited parameters as follows:
Select Mode (steady text):
Mode or select a menu or menu item
Edit Mode (blinking text):
value. Press MENU to cancel the current editing operation
UP, DOWN Select Mode (steady text):
selected display and move up and down menu items.
Edit Mode (blinking text):
decreases the value of the number being edited, or scrolls through a list of choices.
MENU Press and hold MENU to change to the Main Menu screen.
When in a sub menu screen, press MENU to move to the next higher menu. When in Edit Mode (blinking text) Press MENU to cancel the current editing operation
Press ENTER to change into Edit
Press ENTER to save the current
Press UP, DOWN to change the
Press UP, DOWN to increases or
Sage Boiler Control Instruction Manual Page 16 of 56
Front Panel
Display Mode
All values shown in Display Mode are for display only and can not be adjusted by the operator. The keys scroll through the Display Mode screens:
Standby
Low Inlet Temp
OUT 189F IN 180F RST 189F OA 180F
OUT 189F SP 180F MOD RATE SH 100%
Boiler State Alarm Message Low Inlet Temp alarm shown, refer to page 41 for
OUT Boiler Outlet Temperature IN Boiler Inlet Temperature RST Remote System Temperature
OA Outside Air Temperature
OUT or RST Boiler Outlet or Remote System Temperature SP Active Setpoint
MOD RATE Modulation Rate SH Space Heating (active when DH is not) DH Domestic Hot Water Priority
Standby boiler state shown, refer to the top of page 6 &
7 for explanation of each boiler state explanation of all possible alarm messages, the
alarm line is left blank when no alarm is active
(visible when ‘Remote Sensor’ = Display Only or Control)
(visible when ‘Outdoor Sensor’ = Display Only or Outdoor Reset)
(Remote System when ‘Remote Sensor’ = Control)
(visible when ‘DHWP’ = Yes and DP input is true)
In 180F SP 130F MIX VALVE 100%
Outlet Sensor &
Local SP Mode
LEAD BOILER 8
Cycles #,###,### Hours #,###,###
Home Screen
The Boiler State and Alarm Message screen is the ‘Home Screen’ and is reverted to when no key has been selected for longer than 30 minutes.
Alarm LED
New alarms illuminate the alarm LED and energize an alarm output (SO) (if enabled). If a lockout condition is detected, the alarm LED will blink and the lockout indication output (LI) is energized. The display Message is cleared and relays de-energize when the alarm condition is cleared.
In Boiler Inlet Temperature SP Min In H2O Temp MIX VALVE Modulation Rate
Control Mode
LEAD BOILER (0 – 8) Lead Boiler, when zero is displayed modulating
CYCLES Number of boiler cycles HOURS Number of boilers operating hours
Outlet Sensor & Local SP Mode message shown, refer
to page 2 for an overview of each control mode
lead-lag functions are not available
Sage Boiler Control Instruction Manual Page 17 of 56
Loading...
+ 39 hidden pages