Burnham Sage Boiler Control Instruction Manual

Sage Boiler Control
(SBC)

Instruction Manual

Introduction Quick Reference 2 Overview 4
Product Features Boiler Sequence 6 Single Boiler Control Mode 9 Multiple Boiler Control Mode 10 EMS Boiler Control Mode 11 Manual Boiler Control Mode 14 Auiliary Device 15
Front Panel Features 16 Display Mode 17 Menu Navigation 18 Setpoints Menu 19
Installation Mounting & Wiring Sensors 20 Terminal Layout 25 External Connections 26 Communication 28 Peer-To-Peer Network 30 RS485 Modbus Network 31
Application
The Sage Boiler Control (SBC) has been designed for commercial hot water boiler applications.
Intent
This instruction manual includes detailed functional, installation and setup information.
www.burnhamcommercialcastiron.com
Setup & Tuning Boiler Configuration Menu 33 System Configuration Menu 34 Setup Menu 35 Manual Mode 40
Trouble Shooting Alarm Messages 41 Diagnostics Menu 43 Sensor Resistance Chart 46 Security Menu 47
Specifications General 48 Component Description & Repair Part Numbers 49
Appendix A. Parameter Summary 50 B. Customer Parameter Worksheet 52
Warranty Rear Cover
Sage Boiler Control Front Panel (Showing Power & Alarm LEDs,
2 Line 16 Character Message Display
and 4 Pushbuttons)
Sage Boiler Control Instruction Manual Page 1 of 56 102121-01R2 - 4/11
Introduction

Quick Reference

CONTROL
MODE
LCD Display
Typical
Application
Water Setpoint
Temperature
Sensor
Setpoint Operator Operator
“On” and “Off”
Point
Outdoor Air
Reset
Domestic Hot
Water Priority
(DHWP)
Warm Weather
Shutdown
(WWSD)
Call For Heat Call For Heat
Modulation
Rate
Internal Boiler
Control
Lead Boiler
Control
Remote EMS
Control Manual
Control
Remote
Connections
Local / Remote
Input (LR)
Outlet Sensor
& Local SP
Mode
Remote Sensor
& Local SP Mode
Single Boiler Multiple Boilers
Outlet Sensor &
Remote SP
Mode
Remote Sensor
& Remote SP
Mode
Remote
Control
Mode
Energy Management System (EMS) Boiler Control
Single Boiler
Setpoint Input
Multiple Boilers
Setpoint Input
Modulation
Rate Input
Manual
Mode
Manual
Operation
Boiler Outlet Remote System Boiler Outlet Remote System Ignored Ignored
Input (C+C-) or
Modbus*
Input (C+C-) or
Modbus*
Ignored Ignored
Operator Operator Operator Operator Ignored Ignored
Option Option Ignored Ignored Ignored Ignored
Option Option Ignored Ignored Ignored Ignored
Option Option Option Option Option Ignored
Based on
Setpoints
Based on Setpoints
Based on Setpoints
Based on Setpoints
Input (RO) or
Modbus
Manually Set
Based on
Setpoint
Peer-to-Peer
Connected
Ignored Ignored Ignored Ignored
Based on
Setpoint
With Peer-to-
Peer Connected
Based on
Setpoint
With Peer-to-
Peer Connected
Based on
Setpoint
With Peer-to-
Peer Connected
Ignored Ignored
Ignored Ignored
Input (C+C-)
or Modbus
Ignored
Ignored Ignored Ignored Ignored Ignored By Operator
Ignored Ignored Closed Closed Closed Ignored
Remote On/Off
(Enable)
Input (RO)
Remote Control
Input (C+C-)
Communication
Network
Additional
Information
Enable/
Disable
No No
Peer-To-Peer
or
Modbus*
Enable/
Disable
Peer-To-Peer
or
Modbus*
Enable/
Disable
Remote
Setpoint
Peer-To-Peer
or
Modbus*
Enable/
Disable
Remote
Setpoint
Peer-To-Peer
or
Modbus*
On/Off Ignored
Remote
Modulation
Modbus
Only
Ignored
Modbus Only
Page 9 Page 10 Page 11 Page 12 Page 13 Page 14
* If Modbus is selected the Peer-To-Peer Network can not be used. Modulating Lead/Lag features require the Peer-To­Peer Network.
Sage Boiler Control Instruction Manual Page 2 of 56
Introduction
Quick Reference
Abbreviation List
Abbreviation Description
AL Flame Safeguard Alarm
BIT Boiler Inlet Temperature
BOT Boiler Outlet Temperature
BP Boiler Pump BV Blocked Vent Switch
C Common Termination Point
CA Low Combustion Air Flow
CH Call For Heat (CFH)
CS Fuel Valve Energized
DH Domestic Hot Water Heating Demand
DP Domestic Hot Water Priority (DHWP) SBC Sage Boiler Control EMS Energy Management System
GP High and Low Gas Pressure Switches
HL High Limit Aquastat
HP High Pressure Gas Switch
IN Boiler Inlet Water Temperature
LC Low Water Cutoff Switch
LL Lead Lag LO Lockout Indicator LR Local / Remote
M Electric Motor Mix 3 Way Mixing Valve OA Outside Air Temperature
OL Operating Limit Aquastat
OO Burner On / Off Switch
OUT Boiler Outlet Water Temperature
RO Remote On / Off
RST Remote System Temperature
SH Space Heating Demand
SI Spare Input (Programmable)
SO Spare Output (Programmable)
SP Setpoint (As found in “Ope rational SP” and “Remote SP” SP System Pump
VI Vent Inducer
WF Low Water Flow
WWSD Warm Weather Shutdown
Termination Number Identification (Typical):
Description
Mixing Valve
Control, (MR, MS)
Termination
Numbers
Sage Boiler Control Instruction Manual Page 3 of 56
Introduction
Overview Sage Boiler Control Overview
The Sage Boiler Control (SBC) is a complete boiler monitoring and automation system. The SBC provides advanced boiler modulation, operating control, diagnostics, multiple boiler lead-lag and auxiliary device control. The SBC provid es advanced control features in an easy to use package.
Flexible, Field Selectable Control
Control modes, water system, boiler auxiliary and modulating lead/lag control features are menu selectable without the need for external programmers, laptops or down loads. Every boiler is shipped with factory defaults that make field menu selections unnecessary unless you are applying additional control features.
Boiler Monitoring and Diagnostic Displays
The SBC’s two line by sixteen character LCD display may be used for monitoring boiler inlet and outlet, remote system and outside air temperatures, modulation rate setpoint and modulating percent and mixing valve demand percent. Additionally, the display automatically presents boiler sequence messages, alarms, hold and lockout messages. A diagnostic menu is included that provides the last 10 alarm messages and boiler inlet temperature alarm history. Boiler inlet temperature alarm history includes time and date, the lowest inlet temperature reached and the amount of time the water temperature dropped below the alarm setpoint.
Modulation Rate and On/Off Modes
The SBC may simply control boiler modulation and on/off output based on the boiler water outlet temperature and an operator adjusted setpoint. However, using parameter selections, the SBC allows the boiler modulation and on/off output to respond to remote system water and outside air temperatures, Domestic Hot Water Priority (DHWP) input or Energy Management System (EMS) modulation rate demand, remote setpoint or remote start/stop commands. Parameter selections of remote system water temperature and remote mode determine the choice of one of six different control modes.
Advanced Availability
The above control modes are menu selectable options. However, if a selected sensor fails, the SBC automatically changes to a control mode that will allow continued automatic operation of the boiler. For example, in the event of a remote system temperature sensor failure, the SBC will automatically switch to boiler outlet temperature sensor based control.
Outdoor Air Reset
When selected the modulation rate setpoint is automatically adjusted based on outside air temperature. Outdoor air “reset” setpoint saves fuel by adjusting the water temperature of a heating boiler lower as the outside air temperature increases.
Warm Weather Shutdown (WWSD)
Some boilers are used primarily for heating buildings, and the boilers can be automatically shutdown when the outdoor air temperature is warm. When outside air temperature is above the WWSD setpoint, this function will prevent the boiler, boiler pump and/or the system pump from starting.
Domestic Hot Water Priority (DHWP)
Some boilers are used primarily for building space heating, but also provide heat for the domestic hot water users. When the outdoor temperature is warm, the outdoor reset setpoint may drop lower than a desirable domestic hot water temperature. When enabled and a DHWP contact input is detected, the hot water setpoint is adjusted to be greater than a field adjustable DHWP Setpoint.
Water Side Control Outputs
In order to maximize the life and availability of hot water systems it may be desirable to automate mixing valves, boiler pumps, system pumps, and standby system pumps. The SBC makes this type of automation totally integrated and cost effective. The control of these devices is field selectable through simple yes/no menu selections.
Combustion Air Side Control Outputs
Boiler room Combustion air dampers (fresh air dampers) and Vent Inducer control outputs are field selectable options.
Peer-To-Peer Network The SBC includes state-of-the-art modulating lead-lag sequencer for up to eight (8) boilers capable of auto rotation, outdoor reset and peer-to-peer communication. The peer-peer network is truly “plug and play”. Communication is activated by simply connecting a RJ11 telephone line between boilers. The SBC provides precise boiler coordination by sequencing boilers based on both remote system water temperature and boiler modulation rate. For example, the lead boiler can be configured to start a lag boiler after operating above 90% modulation rate for longer than an adjustable time. The boilers are modulated in “unison” (parallel) modulation rate to ensure even heat distribution
Modbus Communication Interface
A factory configured RS485 Modbus interface is available for Energy Management System (EMS) or SCADA system monitoring and control.
Sage Boiler Control Instruction Manual Page 4 of 56
Introduction

Overview

Standby System Pump
Remote System
System Pump
System
Supply Water
Switch
Domestic Hot
Temperature
Feedback
Water Override
System Pump
Supply
Domestic
Hot Water
System
Modbus RS-485, RJ-11
Local / Remote Switch
High Temperature Limit
Connection
Boiler Outlet TemperatureBoiler Inlet Temperature
Primary
Spare Output
Call For Heat Relay
Fuel Valve Energized
Control
Alarm (Lockout)
Low Fire
Remote On / Off (Enable)
Lockout Indicator
Building Automation
Control
M
Mixing Valve
Boiler Pump
Low Water Flow Switch
Low Water Cutoff Switch
Return Water
Outside Air
Temperature
Sage Boiler Control
FAN
Switch
Air Flow
Combustion
Control
Modutrol Motor
Switch
Damper
Combustion Air
M
Supply
Fresh Air
Boiler On/Off
Boiler
Jacket
Fuel
Fuel Switches
Supply
Sage Boiler Control Instruction Manual Page 5 of 56
Product Features
Boiler Sequence
BOI LER STATE
LCD Display
Pa r a me ter / Notes
Boiler Disable or R em ot e On/Off
Outdoor Air T em p >
Warm Weat her Shut down Set point
Domestic Hot Water Priority
RO
O+,O-
DP
Terminal Number
-
44,30,
75
20,74
Start/ Sto p Seq u en ce St atesPre-Seq u en ce States
Parameter/Note
Boiler Disable
Warm Weather
Shutdown
Locko ut
b &ca aa
Pump Purge
Standby
Purge / Pilot Ignition
Limit Hold
-3/d - - -53 4/d
-
Low Fire / Ignition
Main I gnition
Low Fire Hold
Boiler Running
Pump Cooldown
Fan Post Purge
54/d
Boil e r Enabl e/Disable On
Domestic Hot Water Demand Monitored
Low Fire Hold
Fuel Valv e Energiz ed
Flame Saf eguard Alarm
Sys t em Pum p F eedback
Call For Heat
Recycling Limits
(LC, OO, WF, GP and HL inputs)
Limits
Inputs
Non-Recycling Limits
(Combustion Air Flow (CA Input))
Call For Heat Relay
Lockout Indicator
( M anual R es et R equire d)
Spare Output
Boiler Pump
System Pump
Relay Outputs Inter lo ck Inpu ts
Syst em Pum p Bac k up Pump
Combustion Air Damper
System Alarm
Mix ing Valve Out put
Blower High Speed
Purge %
Modulation
Firing Rat e
Modulation Outputs
Low F ire %
Blower 0 Volts
SI CS AL
SI
R+,R-
OR
BO,BC
LC , O O ,WF,
GP,HL
CA
CH
LO
VI BP SP
SO SO SO
MS,MR
V+,V-,
P+,P-
V+,V-,
P+,P-
V+,V-,
P+,P-
V+,V-,
P+,P-
V+,V-,
P+,P-
9
-
-
9
70,71,
72
8,27,
28
-
-
-
-
2,30
25,30
10
10,27/
e
10
6,79,
80 49
52
-
9,51/f
50
System Pump Feedback Monitored
Call For Heat
Recycling Limits Made
Non-Recycling Limits Made
Call For Heat Relay On
Spare Output On
Boiler Pump On
System Pump On
Starts in response to System Pump Feedback In put SI
Combustion Air Damper Open
Alarm Status is Monitored
Modulate
Notes
a. Boiler Pump is “On” when the Boiler Pump is set to “On Always” or the boiler is lead boiler and Boiler Pump is set to “On Lead” b. Boiler Pump is "On" when the Boiler Pump is set to "On Always" and WWSD is set to "WWSD of System Pump" or “Off” c. System Pump is "On" when the System Pump is set to “yes” and WWSD is set to either "WWSD of Boiler" or "Off" d. Boiler pump is "On" during Prepurge and Post Purge when Boiler Pump is set to "Purge" or boiler is lead & Boiler Pump is set to “On Lead” e. Combustion Air Damper Spare Output is maintained “On” for 2 minutes after the Call For Heat is removed. f. Modulation rate is held at purge % when low fire input is not provided.
Sage Boiler Control Instruction Manual Page 6 of 56
Product Features
Boiler Sequence (Continued) Pre-Sequence States
BOILER
STATE
LCD Display
Boiler
Disabled
Warm
Weather
Shutdown
Lockout Any Mode
Standby
Start/Stop Sequence States
BOILER
STATE
LCD Display
Pump Purge
Limit Hold Any Mode
Purge / Pilot
Ignition
Low Fire /
Ignition
Main Ignition Any Mode
Low Fire
Hold
Boiler
Running
Fan Post
Purge Pump
Cooldown
CONTROL MODE
LCD Display
Any Mode
(Except for
Remote Control)
Any Mode
(Except for
Manual Mode)
Outlet Sensor &
Local SP Mode
Remote Sensor
& Local SP
Mode
Outlet Sensor &
Remote SP
Mode
Remote Sensor
& Remote SP
Mode
Remote Control
Mode
Manual
Operation Mode
CONTROL MODE
LCD Display
Any Mode
(Except
Manual Mode)
Any Mode
Any Mode
Any Mode The modulation output is held at the Low Fire for the Low Fire Hold time. Any Mode
Any Mode
Any Mode

Description

Boiler is prevented from starting; Remote On/Off (Enable) (Terminal RO) Input is not energized.
Boiler is prevented from starting, Warm Weather Shutdown (WWSD) is enabled and outside air temperature is above the WWSD Setpoint
Boiler is prevented from starting, Flame Safeguard lockout is present. A Flame Safeguard manual reset is required Control monitors boiler outlet temperature, a Call For Heat is initiated when boiler outlet temperature is below the Operational Setpoint
Control monitors Remote System Temperature, a Call For Heat is initiated when Remote System Temperature is below the Operational Setpoint
Control monitors boiler outlet temperature, a Call For Heat is initiated when boiler outlet temperature is below the Remote Setpoint Input (Terminal C+,C- or Modbus Interface) Control monitors Remote System Temperature, a Call For Heat is initiated when Remote System Temperature is below the Remote Setpoint Input (terminal C+,C- or Modbus Interface) Control monitors Remote On/Off (Enable) input (Terminal RO or Modbus Interface), a Call For Heat is initiated when input is energized
A Call For Heat is initiated when Manual Mode Menu item Boiler On/Off is set to On

Description

Once a Call For Heat is initiated and Boiler Pump Purge is selected, the pump output is energized until the Pump Prepurge Time is complete. If the Call For Heat condition still exists at the end of the Prepurge Time (the temperature of the water at the sensor may rise with boiler water flowing passed it) the pump will continue to operate and the Call For Heat Relay is energized Power is applied to the safety limit string. If any limits does not pass power (is not energized), the alarm LED and LCD display shows the reason the start sequence is on Hold. Refer to Trouble shooting section for explanation of individual lockout and alarm messages After the limit string passes power, the fan is started, the modulation output is set to Purge Rate. When the purge period is complete, the flame safeguard sequences on the ignition transformer and pilot When the Spare Input Low Fire is selected, modulation output is set to the Low Fire Speed when the Spare Input is energized. The main gas valve input is energized and the modulation output is held constant for an ignition stabilization period
When this Low Fire Hold time is complete, the modulation output is released to modulate When water temperature is above setpoint, there is a Flame Safeguard or Limit fault, the Call For Heat is ended and the modulating output is set to Purge Rate for the Post Purge Time When Boiler Pump Purge is selected, the boiler pump remains “on” until the boiler outlet temperature is less than the Post Purge Delta (default is 5 F) above the Boiler Inlet Temperature.
Sage Boiler Control Instruction Manual Page 7 of 56
Product Features
Boiler Sequence (Continued) Multiple Boilers
185
Setpoint
High Fire Limit
(Parameter 37)
1
- Lead Boiler Start
2
- Temperature Based Lag Boiler Start
3
- Modulation % Based Lag Boiler Start
4
- Lag Boiler Stop
5
- Lead Boiler Stop
Notes
- The “Boiler Address” parameter assignment determines the boiler sequencing order.
- The Lead Boiler automatically rotates (when “Rotate” parameter is enabled) based on field adjusted time
- Lead Boiler is the first boiler to turn on and the last boiler to turn off, (First On, Last Off, FOLO).
- Lag Boilers are turned on in order and turned off in reverse order, (First On, Last Off, FOLO).
- Tripped boilers are replaced without waiting for the Boiler On Delay timer. If a tripped boiler becomes available
180
SYSTEM
BOILER
PLANT LOAD
175
TEMPERATURE
100
50
FIRING RATE
0
3 2 1 0
(# BOILERS REQURED)
Lead Boiler
Start
1
Start
st
1
Fast
Load
Change
Lag
2
2
Slow
Load
Change
3
2
Start
nd
Lag
Stop
nd
2
Lag
4 54
Stop
1st Lag
Lead Boiler
Boiler Start and Stop Peer-To-Peer Network Sequence Diagram
(3 boiler system shown, typical for up to 8 boilers)
Water temperature is below the setpoint by more than the “On Point” differential
Water temperature is below the setpoint by more than the “On Point” differential for longer than the adjustable time delay (“Boiler On Delay” parameter).
The boiler modulation rate has been above the adjustable limit (“LL Start Trigger” parameter) for longer than the time delay.
The boiler modulation rate has been below the adjustable limit (“LL Stop Trigger” parameter) for long er than the time delay. Additionally, lag boilers are stopped when water temperature is above the setpoint by more than the “Off Point” differential for longer than the “Boiler Off Delay” parameter)
The last boiler remains on line until the water temperature is above the “Off Point” setpoint for longer than the time delay.
(“Rotate After” parameter, default is 168 hours). When rotating, the lead boiler will move to the end of the lag order and the 1
st
lag boiler will become the lead. The rest of the boilers will then move up in the lag order
accordingly.
it is returned to service.
5
Stop
Sage Boiler Control Instruction Manual Page 8 of 56
Product Features
Single Boiler Control Display Shows: Outlet Sensor & Local SP Mode
Return
Water
Outside Air
Temperature
(O+, O-)
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
System
Circulator
System
Supply Water
DHW
Override
Switch (DP)
Domestic Hot Water (DHW)
Supply
Outlet Sensor & Local SP Mode Application Diagram
(Showing Relevant Connections)
Features
Setpoints
The operator selects the setpoint and on and off points from the LCD display.
Modulation Rate Control
Boiler automatically modulates to maintain the boiler outlet temperature at setpoint.
Call for Heat
The Call For Heat is determined by the setpoint, on and off points and boiler outlet temperature.
Options
Outside Air Reset
If enabled, the Outside Air Sensor will automatically adjusted the setpoint.
Warm Weather Shutdown (WWSD)
If enabled, the WWSD will disable a boiler start when outside air temperature is above a Warm Weather Shutdown (WWSD) setpoint.
Domestic Hot Water Priority (DHWP)
If enabled, the DHWP will adjust the setpoint to satisfy the DHWP setpoint when a DHWP input (DP) is energized.
Boiler Inlet
Temperature
(BI, BC)
EMS System Hardwired Connections
Lockout Indicator (LO) Soft Alarm (SO) Remote On / Off (Enable) (RO)
RJ11, RS-485 Communication
Peer-To-Peer Network for Modulating Lead/Lag
Or
Modbus Network for Touch Screen or EMS Monitoring
Selecting This Control Mode
To select Outlet Sensor & Local SP Mode set the following parameters:
System Configuration Menu: Remote Control = “No” Remote System Temperature Sensor = “No”
Remote On / Off (Enable) Input (RO) = Closed [Jumper (RO) to (C)]
If the Remote On / Off (Enable) (RO) input is opened, the Call For Heat Relay (CH) is de-energized.
Modbus Network
To establish a Modbus network set the following parameters: Communication Menu:
Protocol = Modbus Modbus Address = Give each boiler a unique address. Baud Rate = Set identical to remote system Parity = Set identical to remote system
Connect all boilers using a RJ11 ended telephone cable If the Modbus network is activated the remote system may
monitor and/or control boiler operation. Refer to page 29 for additional information.
Sage Boiler Control Instruction Manual Page 9 of 56
Product Features
Multiple Boiler Control Display Shows: Remote Sensor & Local SP Mode
Outside Air
Temperature
(O+, O-)
Remote System
Temperature
(R+,R-)
System
Circulator
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
Boiler
Circulator
Boiler Inlet
Temperature
(BI, BC)
DHW Override
Switch (DP)
Wired to Each
ECM Controller
Boiler
Circulator
RJ11, RS 485
Peer to Peer
Network
Remote System
Temperature
(R+,R-)
Outside Air
Temperature
(O+, O-)
Connects to
Up to Eight
Boilers
Domestic Hot Water Priority
(DP)
Remote Sensor & Local SP Mode Application Diagram
(Showing relevant connections for 3 boilers, typical for up to 8)
Features
Setpoints
The ope
rator selects the setpoint and on and off points
from the LCD display.
Modulation Rate Control
Boiler automatically modulates to maintain the Remote System Temperature (RST) at setpoint.
Call for Heat
The Call for Heat is determined by setpoint, on and off points and RST. If a Peer-To-Peer network is activated, a Call for Heat is also initiated when the Lead boiler modulation rate % is above an adjustable High Fire Rate Limit (parameter 37) for too long a time.
Options
Outside Air Reset
If enabled, the Outside Air Sensor will automatically adjusted the setpoint.
Warm Weather Shutdown (WWSD)
If enabled, the WWSD will disable a boiler start when temperature is above a Warm Weather Shutdown (WWSD) setpoint.
Domestic Hot Water Priority (DHWP)
If enabled, the DHWP will adjust the setpoint to satisfy the DHWP setpoint when a DHWP contact input (DP) is closed. When multiple boilers monitor the DHWP input, an isolated contact is required for each boiler.
Selecting This Control Mode
To select Remote Sensor & Local SP Mode set the following parameters:
System Configuration Menu: Remote Control = “No” Remote System Temperature Sensor = “Control”
Remote On / Off (Enable) Input (RO) = Closed [Jumper (RO) to (C)]
If the Remote On / Off (Enable) (RO) input is opened, the Call For Heat Relay (CH) is de-energized.
If the Remote System Temperature Sensor (RST) fails, the control mode is automatically switched to Outlet Sensor & Local SP Mode.
Peer-To-Peer Network
To establish a Peer-To-Peer network follow the procedure provided on page 28.
If the Peer-To-Peer network is activated the Lead boiler controls modulation rate and Call for Heat for all networked boilers. Up to 8 networked boilers are fired in “Unison” (all at the same modulation rate).
Sage Boiler Control Instruction Manual Page 10 of 56
Product Features
Energy Management System (EMS) Boiler Control Display Shows: Outlet Sensor & Remote SP Mode
Return
Water
Outside Air
Temperature
(O+, O-)
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
System
Circulator
System
Supply Water
DHW
Override
Switch (DP)
Domestic Hot Water (DHW)
Supply
Outlet Sensor & Remote SP Mode Application Diagram
(Showing relevant connections)
Features
Setpoints
The setpoint is determined by the Remote Input (C+,C-) or Modbus Input and operator sets the on and off points from the LCD display.
Modulation Rate Control
Boiler automatically modulates to maintain the boiler outlet temperature at setpoint.
Call for Heat
The Call For Heat is determined by setpoint, on and off points and boiler outlet temperature.
Options
Warm Weather Shutdown (WWSD)
If enabled, the WWSD will disable a boiler start when temperature is above a Warm Weather Shutdown (WWSD) setpoint.
Outside Air Temperature may be displayed only. Outside Air Reset and Domestic Hot Water Priority input (DP) are ignored.
Boiler Inlet
Temperature
(BI, BC)
EMS System Hardwired Connections
Lockout Indicator (LO) Soft Alarm (SO) Remote On / Off (Enable) (RO) Remote Setpoint (C+,C-)
RJ11, RS-485 Communication
Peer-To-Peer Network for Modulating Lead/La g
Or
Modbus Network for Touch Screen or EMS Monitoring
Selecting This Control Mode
To select Outlet Sensor & Remote SP Mode set the following parameters:
System Configuration Menu: Remote Control = “Remote SP” Remote System Temperature Sensor = “No”
Local / Remote Input (LR) = Closed Remote On / Off (Enable) Input (RO) = Closed [Jumper (RO) to (C)]
When the Local / Remote Input (LR) is open, Remote Input (C+,C-) is ignored and Outlet Sensor & Local SP Mode is active.
If the Remote On / Off (Enable) (RO) input is opened, the Call For Heat Relay (CH) is de-energized.
Modbus Network
To establish a Modbus network set the following parameters: Communication Menu:
Protocol = Modbus Modbus Address = Give each boiler a unique address. Baud Rate = Set identical to remote system Parity = Set identical to remote system
Connect all boilers using a RJ11 ended telephone cable If the Modbus network is activated the remote system may
monitor and/or control boiler operation. Refer to page 29 for additional information.
Sage Boiler Control Instruction Manual Page 11 of 56
Product Features
Energy Management System (EMS) Boiler Control (continued) Display Shows: Remote Sensor & Remote SP Mode
Return
Water
Outside Air
Temperature
(O+, O-)
Remote System
Temperature
(R+,R-)
System
Circulator
System
Supply Water
Features
Setpoints
The setpoint is determined by the Remote Input (C+,C-) and operator sets the on and off points from the LCD display.
Modulation Rate Control
Boiler automatically modulates to maintain the Remote System Temperature (RST) at setpoint.
Call for Heat
The Call For Heat is determined by setpoint, on and off points and Remote System Temperature. If a Peer-To­Peer network is activated, a Call for Heat is also initiated when the Lead boiler modulation rate % is above an adjustable High Fire Rate Limit (Parameter 37) for too long a time.
Options
Warm Weather Shutdown (WWSD)
If enabled, the WWSD will disable a boiler start when temperature is above a Warm Weather Shutdown (WWSD) setpoint.
Outside Air Reset and Domestic Hot Water Priority input (DP) are ignored
.
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
Boiler
Circulator
Boiler Inlet
Temperature
(BI, BC)
Remote Sensor & Remote SP Mode Application Diagram
(Showing relevant connections for 3 boilers, typical for up to 8)
Selecting This Control Mode
To select Remote Sensor & Remote SP Mode set the following parameters:
System Configuration Menu: Remote Control = “Remote SP” Remote System Temperature Sensor = “Control”
Local / Remote Input (LR) = Closed [Jumper (LR) to (C)] Remote On / Off (Enable) Input (RO) = Closed [Jumper (LR) to (C)]
When the Local / Remote Input (LR) is open, Remote Input (C+,C-) is ignored and Remote Sensor & Local SP Mode is active.
If the Remote On / Off (Enable) (RO) input is opened, the Call For Heat Relay (CH) is de-energized.
Peer-To-Peer Network
To establish a Peer-To-Peer network follow the procedure provided on page 28.
If the Peer-To-Peer network is activated the Lead boiler controls modulation rate and Call for Heat for all networked boilers. Up to 8 networked boilers are fired in “Unison” (all at the same modulation rate).
Wired to Each
ECM Controller
Boiler
Circulator
EMS System Connections
Lockout Indicator (LO) Soft Alarm (SO) Remote On / Off (Enable) (RO) Remote Setpoint (C+,C-)
Remote System
Temperature
(R+,R-)
Outside Air
Temperature
(O+, O-)
Connects to
Up to Eight
Boilers
RJ11, RS 485
Peer to Peer
Network
Sage Boiler Control Instruction Manual Page 12 of 56
Product Features
Energy Management System (EMS) Boiler Control (continued) Display Shows: Remote Control Mode
Return
Water
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
System
Circulator
System
Supply Water
Remote Control Mode Application Diagram
(Showing relevant connections)
Features
Modulation Rate Control
The Remote Input (C+,C-) or Modbus input sets modulation rate. The setpoint is ignored.
Call for Heat
The Call For Heat is determined by Remote On/Off input (RO) or Modbus input. The on and off points are ignored. The boiler will turn off if the water temperature increases past the temperature set on the Operational Temperature Limit.
Options
Outside Air Reset and Domestic Hot Water Priority input (DP) and Warm Weather Shutdown are ignored
.
Boiler Inlet
Temperature
(BI, BC)
EMS System Hardwired Connections
Lockout Indicator (LO) Soft Alarm (SO) Remote On / Off (Enable) (RO) Remote Setpoint (C+,C-)
RJ11, RS-485 Communication
Modbus Network EMS Monitoring and Control Remote Firing Rate via Modbus Remote on/off via Modbus
Selecting This Control Mode
To select Remote Control Mode set the following parameters: System Configuration Menu:
Remote Control = “Remote Mod” Remote System Temperature Sensor = “Display Only”
Local / Remote Input (LR) = Closed [Jumper (LR) to (C)]. When the Local / Remote Input (LR) is open, Remote Input
(C+,C-) is ignored and Remote Sensor & Local SP Mode is active.
Modbus Network
To establish a Modbus network set the following parameters: Communication Menu:
Protocol = Modbus Modbus Address = Give each boiler a unique address. Baud Rate = Set identical to remote system Parity = Set identical to remote system
Connect all boilers using a RJ11 ended telephone cable If the Modbus network is activated the remote system may
monitor and/or control boiler operation. Refer to page 29 for additional information.
Sage Boiler Control Instruction Manual Page 13 of 56
Product Features
Manual Boiler Control Mode Display Shows: Manual Operation Mode and Lost Sensor Blind Mode
Return
Water
Boiler
Circulator
Boiler Outlet
Temperature
(BO, BC)
System
Circulator
System
Supply Water
Boiler Inlet
Temperature
(BI, BC)
EMS System Hardwired Connections
Lockout Indicator (LO) Soft Alarm (SO) Remote On / Off (Enable) (RO)
RJ11, RS-485 Communication
Modbus Network EMS Monitoring
Manual Operation Mode and Lost Sensor Blind Mode Application Diagram
(Showing relevant connections)
MANUAL OPERATION MODE Features
Modulation Rate Control
The operator sets the modulation rate. The setpoint is ignored.
Call for Heat
The Call For Heat Relay (CH) is directly controlled by the operator. The on and off points are ignored. The boiler will turn off if the water temperature increases past the temperature set on the High Temperature
LOST SENSOR BLIND MODE
If both Remote System Temperature (RST) and boiler outlet temperature and the Remote Control input signal (C,-C+) have failed, the boiler is started and run continuously at the lowest modulation rate.
If the controller has entered Lost Sensor Blind Mode, the user may switch the boiler into manual mode or repair, replace or reconnect required temperature sensors.
Stop parameter. Options
Outside Air Reset, Warm Weather Shutdown and Domestic Hot Water Priority are ignored
.
The Spare Output (VI) and Combustion Air Damper (SO) outputs are energized when the operator starts the boiler in manual mode.
Selecting This Control Mode
Manual Mode is activated from the Manual Mode menu when Supervisor password is entered. Simply set the Boiler Man/Auto parameter to “Man” and adjust the Modulation Rate and Boiler On/Off menu items as required. Once activated the green LED flashes. To leave manual mode set the Boiler Man/Auto parameter to “Auto”.
Sage Boiler Control Instruction Manual Page 14 of 56

Product Features

Auxiliary Device Control
Return
Water
M
Fresh Air
Supply
Combustion Air
Open/Close (SO)
Damper
Boiler Inlet
Temperature
(BI, BC)
Standby System Pump
Mixing Valve
M
Control (MR, MS)
Boiler Pump
Start/Stop (BP)
Boiler Outlet
Temperature
(BO, BC)
Start/Stop (SO)
System Pump
Start/Stop (SP)
Spare Output (VI)
System Pump Feedback (SI)
System
Supply Water
Energy Management
System (EMS)
Interface
Modbus RS-485, RJ-11 Connection
Auxiliary Control Application Diagram
(Showing All Options)
Features
Mixing Valve
The primary function of the mixing valve is to protect the boiler from thermal shock and sustained flue gas condensation. When configured, the mixing valve output compares both minimum return water temperature setpoint to measured return water temperature and boiler differential temperature setpoint to measured differential temperature (boiler outlet minus inlet temperature).
If the boiler return water temperature drops below the minimum inlet water temperature setpoint (“Min In H2O Temp” parameter) or the differential temperature increases above the maximum water differential temperature setpoint (“Max H2O Delta T” parameter) the mixing valve opens to allow hot boiler outlet water to blend with cold return water. The valve repositions toward 0% recirculation after return water increases above setpoint and the differential temperature reduces below setpoint.
The mixing valve may be controlled manually from the Manual Mode menu when Supervisor password is entered. Simply set the Mixing Valve M/A parameter to “Man” and adjust the Mixing Valve % as required. Once activated the green LED flashes. To leave manual mode set the Mixing Valve M/A parameter to “Auto”
Combustion Air Damper and Vent Inducer
When the Relay (CH) is closed, the Combustion Air Damper (CAD) and Vent Inducer outputs are energized. If the CAD open position is needed to be proven, a limit switch may be wired in series with the Low Water Cut-off Switch input (LC). The alarm Message may be modified to reflect this change.
Boiler Pump
The Boiler Pump output (BP) may be configured as None, Always On, Purge or Lead On by setting the Boiler Pump (parameter 2) (refer to page 31): Always On Boiler pump runs continuously. Purge Boiler pump runs during a pump Prepurge
(Pump Prepurge (parameter 3) time before boiler starts) while the boiler is running and during a pump cooldown period (pump cooldown maintains the boiler pump running until the boiler outlet temperature is within the Postpurge Delta (parameter 4) degrees above the boiler inlet temperature).
Lead On: Boiler Pump runs continuously when the
boiler is the lead and during the fan pre­purge, while the boiler is running and during
fan post purge when a lag boiler. The boiler pump sequences are detailed on the boiler sequence diagram on page 6.
System and Standby System Pump
When configured, the System Pump output (SP) is always energized except when turned off by the Warm Weather Shutdown feature. A Standby System Pump output (SO) may be configured as a backup to the system pump. The Standby System Pump is started based on the System Pump Feedback input (SI).
Selecting This Control Mode
These control modes may be selected using the Boiler and System Configuration menus.
Sage Boiler Control Instruction Manual Page 15 of 56
Front Panel
Features
POWER LED [Steady On Green LED] indicates power is available down
stream of the Sage Boiler Control’s on board fuse.
[Flashing On Green LED] indicates manual mode operation
for boiler modulation
ALARM LED [Steady On Red LED] indicates an alarm is active. [Flashing On Red LED] indicates a lockout alarm is a c tive
and a manual reset may be required
SCREEN 2 line by 16 character display provides operational, alarm,
sequence status, configuration and diagnostic user in terface
ENTER The ENTER key has no function in display mode. The
ENTER key is used to select menus, menu items and save edited parameters as follows:
Select Mode (steady text):
Mode or select a menu or menu item
Edit Mode (blinking text):
value. Press MENU to cancel the current editing operation
UP, DOWN Select Mode (steady text):
selected display and move up and down menu items.
Edit Mode (blinking text):
decreases the value of the number being edited, or scrolls through a list of choices.
MENU Press and hold MENU to change to the Main Menu screen.
When in a sub menu screen, press MENU to move to the next higher menu. When in Edit Mode (blinking text) Press MENU to cancel the current editing operation
Press ENTER to change into Edit
Press ENTER to save the current
Press UP, DOWN to change the
Press UP, DOWN to increases or
Sage Boiler Control Instruction Manual Page 16 of 56
Front Panel
Display Mode
All values shown in Display Mode are for display only and can not be adjusted by the operator. The keys scroll through the Display Mode screens:
Standby
Low Inlet Temp
OUT 189F IN 180F RST 189F OA 180F
OUT 189F SP 180F MOD RATE SH 100%
Boiler State Alarm Message Low Inlet Temp alarm shown, refer to page 41 for
OUT Boiler Outlet Temperature IN Boiler Inlet Temperature RST Remote System Temperature
OA Outside Air Temperature
OUT or RST Boiler Outlet or Remote System Temperature SP Active Setpoint
MOD RATE Modulation Rate SH Space Heating (active when DH is not) DH Domestic Hot Water Priority
Standby boiler state shown, refer to the top of page 6 &
7 for explanation of each boiler state explanation of all possible alarm messages, the
alarm line is left blank when no alarm is active
(visible when ‘Remote Sensor’ = Display Only or Control)
(visible when ‘Outdoor Sensor’ = Display Only or Outdoor Reset)
(Remote System when ‘Remote Sensor’ = Control)
(visible when ‘DHWP’ = Yes and DP input is true)
In 180F SP 130F MIX VALVE 100%
Outlet Sensor &
Local SP Mode
LEAD BOILER 8
Cycles #,###,### Hours #,###,###
Home Screen
The Boiler State and Alarm Message screen is the ‘Home Screen’ and is reverted to when no key has been selected for longer than 30 minutes.
Alarm LED
New alarms illuminate the alarm LED and energize an alarm output (SO) (if enabled). If a lockout condition is detected, the alarm LED will blink and the lockout indication output (LI) is energized. The display Message is cleared and relays de-energize when the alarm condition is cleared.
In Boiler Inlet Temperature SP Min In H2O Temp MIX VALVE Modulation Rate
Control Mode
LEAD BOILER (0 – 8) Lead Boiler, when zero is displayed modulating
CYCLES Number of boiler cycles HOURS Number of boilers operating hours
Outlet Sensor & Local SP Mode message shown, refer
to page 2 for an overview of each control mode
lead-lag functions are not available
Sage Boiler Control Instruction Manual Page 17 of 56
Front Panel
Display Navigation
Press and hold the key to leave the Display Mode and access the Main Menu:
Main Menu
DISPLAY MODE BOILER CONFIG SYSTEM CONFIG
SETUP
SETPOINTS
COMMUNICATION
DIAGNOSTICS
SECURITY
MANUAL MODE
Arrow Keys :
Up / Down
thr oug h Lis t s
MENU
ENTER
MENU
Sub Menus
DISPLAY MODE
BOILER CONFIG
SYSTEM CONFIG
SETUP
SETPOINTS
COMMUNICATION
DIAGNOSTICS
SYSTEM
SECURITY
MANUAL MODE
Display Mode Displays: Boiler operating status, Display Only, Values Are Not Editable from this display
Configuration and Setup Menus: Sensor, boiler and system options selections
(refer to page 31)
Setpoints Menu: Operational, On, Off, Min & Max Setpoints, Editable Values (refer to page 19)
Communication Menu Modbus and Peer-To-Peer Network Selections (refer to page 27)
Diagnostic Menu: Fault and Low Inlet Temp history, Input & Output Status (refer to page 41)
System Menu: Software revision, parameter code and sensor calibration (refer to page 43)
Security Menu: Supervisor and Factory access (refer to page 45)
Manual Mode: User set Call For Heat and modulation rate. Menu is visible when supervisor password is entered (Refer to page 38)
Sage Boiler Control Instruction Manual Page 18 of 56
Front Panel
Setpoints Menu
Water Temperature
Operational SP
Call For Heat
Relay (CH)
Deg F
185 180 175
Call For Heat Settings
Factory
No.
Setting
Range / Choices Parameter and Description
Operational Setpoint
70 180 60 F to 230 F
Setpoint used in Local Setpoint Mode when not servicing a Domestic Hot Water Priority (DHWP) request
On Point
71 -5 0 F to –99 F
The boiler starts when the water temperature drops ‘On Point’ degrees below the setpoint.
Off Point
72 15 0 F to 99 F
The boiler stops when the water temperature rises ‘Off Point’ degrees above the setpoint.
High Temp Stop
The boiler stops when the boiler outlet water temperature is above the High
73 210 60 F to 230 F
Temperature Stop setpoint. This setpoint is active in every control mode. If the lead boiler’s boiler outlet temperature is above the high temperature stop all boilers are stopped.
*DHWP Setpoint
The Domestic Hot Water Priority (DHWP) Setpoint is active when DHWP Input
74 180 140 F to 230 F
(DP) closes and “DHWP” parameter is set to “yes” and Local SP Mode is selected. When the contact is closed, the boiler outlet is maintained at, or above, the DHW Setpoint.
*WWSD Setpoint
75 60 40 to 90 F
The Warm Weather Shutdown (WWSD) Setpoint used to disable boiler and or system pump operation when enabled by setting the “WWSD” parameter to “WWSD of Boiler”, “WWSD of Sys Pump” or “Both”
76 230 140 F to 230 F
Max SP
The Maximum Operational Setpoint for all possible Local and Remote modes
Min SP
77 140 60 F to 230 F
The Minimum Operational Setpoint is the lower limit for all Local and Remote modes
78 120 110 F to 235 F
Min BIT
Low Boiler Inlet Temperature alarm and event setpoint.
*Min In H2O Temp.
79 130 110 F to 180 F
Minimum Inlet Water Temperature setpoint used as the Mixing Valve inlet temperature setpoint.
*Max H2O Delta T
80 50 20 F to 50 F
Maximum Water Differential (Boiler Outlet minus Boiler Inlet) Temperature setpoint used as the Mixing Valve differential temperature setpoint.
Max Delta T Hold
81 40 20 F to 50 F
Maximum Water Differential (Boiler Outlet minus Boiler Inlet) Temperature used to hold modulation rate at low fire.
* Only visible when parameter enabled on the configuration and setup menus
Off Point On Point
Time
Sage Boiler Control Instruction Manual Page 19 of 56

Installation

Mounting & Wiring Sensors
The Sage Boiler Control (SBC) is mounted in the burner control panel and wired to the burner circuitry at the factory. These installation instructions will explain how the boiler inlet and outlet water temperature sensors are mounted in the boilers supply and return connections and wired to the SBC. Keep a copy of the boiler installation manual on hand to supplement these instructions.
MPC Boiler
1. Mount Boiler Inlet and Outlet Water Temperature Sensors a. Remove one of the ½” immersion temperature sensors from the Sage Boiler Control Parts Carton and
apply thread sealant to the threads between the probe and hex shoulder.
b. Install the sensor in the ½” tapping faci ng upward on the MPC return manifold. Refer to Figure 1. (If
an RWMT positioning plug has already been installed in this tapping, remove it and replace it with the sensor.) Make sure that the hole in the top of the return water mixing tube is aligned with the tapping in the manifold and that the sensor probe slides through this hole without interference. Wrench the sensor until watertight.
c. Remove the other ½” temperature sensor from the Sage Boiler Control Parts Ca rton and apply thread
sealant to the threads between the probe and hex shoulder.
d. Install the sensor in the ½” supply manif old tapping that faces the rear of the boiler. Refer to Figure 1.
Wrench the sensor until watertight.
2. Install Sensor Junction Box in Boiler Jacket a. The temperature sensor wiring can be run to the burner control panel under the boiler jacket, using the
internal wiring chaseway, or it can be run externally, in rigid or flexible conduit. If the sensor wiring will be run externally, proceed immediately to Part 4 of these instructions. If the sensor wiring will be run within the boiler’s internal chaseway, continue to step b. below.
b. If the jacket front, intermediate, and rear top panels have already been installed, remove them (using
the MPC manual’s installation instructions and working in reverse).
c. If the boiler control wiring has already been installed in the rear top panel, remove the two (2) screws
from the rear flange of the panel, slide the panel back, and tilt it upward in order to gain access to the primary internal junction box.
d. Remove the senso r J-box and black snap bushing from the Sage Boiler Control Parts Carton and
install the bushing in the 7/8” hole in the J-box. Mount the sensor J-box (with the snap bushing facing upward) to the inside surface of the right split rear panel using two (2) of the #8 x ½” lg. hex head SMS provided. See Figure 1.
3. Install and Connect Temperature Sensor Wiring (If Using Internal Wiring Chaseway) a. Remove the painted sensor J-box cover (with holes) from the carton. If the blank cover plate is
already mounted on the right rear split panel, remove it. Using flexible conduit and the appropriate conduit connectors (supplied by others), connect the inlet and outlet temperature sensor wiri ng to the two (2) holes in the sensor J-box cover plate. Refer to Figures 1 and 2. The conduit length should be sufficient to allow the cover plate to be installed over the sensor J-box opening in the right rear panel.
b. Install one length of shielded electronic wire cable (supplied by others). To prevent electrical
interference from the internal control/safety circuit wiring harness already installed in the chaseway, use foil-shielded, 3-conductor (22 AWG), UL-listed cable, as a minimum. The cable length should be sufficient to reach from the sensor J-box to the SBC terminals in the burner control panel, following the same path as the internal wiring harness.
c. Pull one end of the shielded cable through the snap bushing on top of the sensor J-box. Trim any
excess length from the sensor wires and connect them to the shielded cable leads in the following manner:
i. Connect one wire from each sensor to the black wire in the shielded cable.
ii. Trim the shielded cable’s silver drain wire, so that it will not come in contact with any metal
surfaces within the J-box. The drain wire is not used at this end of the cable.
Sage Boiler Control Instruction Manual Page 20 of 56
iii. Connect the second wire from the inlet temperature sensor to one of the remaining wires in
the cable. Be sure to note the color of the cable wire to ensure that it is connected to the correct terminal on the SBC in later steps.
iv. Connect the second wire from the outlet temperature sensor to the remaining wire in the
cable. Be sure to note the color of the cable wire to ensure that it is connected to the correct terminal on the SBC in later steps.
d. Mount the sensor J-box cover to the right rear panel using two (2) of the #8 x ½” lg. hex head SMS
provided. See Figure 2. Make sure that all of the exposed wires fit inside of the sensor J-box and that none of them are pinched once the cover plate is installed.
e. Using wire ties, secure the shielded cable to the primary junction box and chaseway channel in the
same manner as the internal wiring harness, as shown in the MPC installation manual.
f. When the cable reaches the end of the chaseway at the front of the boiler, secure it to the vertical
frame rail using the same cable clamps that were installed with the internal wiring harness. Refer to the MPC installation manual for details. It may be necessary to temporarily loosen the screws holding the cable clamps in place, in order to fit the shielded cable through each loop along with the internal wiring harness. If it is necessary to loosen these screws, the jacket front panel will have to be removed (if already installed).
g. The shielded cable should exit the boiler jacket through the unused hole in the side of the front panel.
Using flexible conduit and the appropriate conduit connectors (supplied by others), connect the shielded cable to the burner control panel through one of the panel knockouts n ear the SBC.
h. Connect the wire leads to the appropriate SBC terminals, as shown on the “External Connections”
label on the back of the control. (These terminals are also shown on the “Installation: Terminal Layout” page of this manual). For easier access to the SBC terminals in Power Flame burner control panels, remove the screws at the left and right edges of the top panel and rotate the top panel upward, around the hinge at the top rear of the panel box. (See the Power Flame burner manual for details and
illustration.) i. Connect the black wire and silver drain wire from the cable to the SBC’s “BC” terminal. j. Reinstall any jacket panels that may have been removed.
4. Install and Connect Temperature Sensor Wiring (If Using Electrical Conduit Outside of the Boiler Jacket) a. Using flexible conduit and the appropriate conduit connectors (supplied by others), run the inlet and
outlet temperature sensor wiring to a suitable metal junction box. To prevent electrical interference from other wiring in the burner control panel, connect the sensor wires to foil-shielded, 3-conductor (22 AWG), UL-listed cable, as a minimum. Do not make any other wiring connections inside of this junction box. Trim any excess length from the sensor wires and connect them to the shielded cable leads in the following manner:
i. Connect one wire from each sensor to the black wire in the shielded cable.
ii. Trim the shielded cable’s silver drain wire, so that it will not come in contact with any metal
surfaces within the junction box. The drain wire is not used at this end of the cable.
iii. Connect the second wire from the inlet temperature sensor to one of the remaining wires in
the cable. Be sure to note the color of the cable wire to ensure that it is connected to the correct terminal on the SBC in later steps.
iv. Connect the second wire from the outlet temperature sensor to the remaining wire in the
cable. Be sure to note the color of the cable wire to ensure that it is connected to the correct terminal on the SBC in later steps.
b. Using properly supported conduit and the appropriate connectors (supplied by others), connect the
shielded cable to the burner control panel through one of the panel knockouts n ear the SBC.
c. Connect the wire leads to the appropriate SBC terminals, as shown on the “External Connections”
label on the back of the control. (These terminals are also shown on the “Installation: Terminal Layout” page of this manual). For easier access to the SBC terminals in Power Flame burner control panels, remove the screws at the left and right edges of the top panel and rotate the top panel upward, around the hinge at the top rear of the panel box. (See the Power Flame burner manual for details and illustration.)
Connect the black wire and silver drain wire from the cable to the SBC’s “BC” terminal.
Sage Boiler Control Instruction Manual Page 21 of 56

Installation

Mounting & Wiring Sensors (Cont.)
Figure 1: Installation of SBC Components (Part 1)
Sage Boiler Control Instruction Manual Page 22 of 56

Installation

Mounting & Wiring Sensors (Cont.)
Figure 2: Installation of SBC Components (Part 2)
Sage Boiler Control Instruction Manual Page 23 of 56

Installation

Mounting & Wiring Sensors (Cont.)

V9/V11 Boilers
1. Mount Boiler Inlet and Outlet Water Temperature Sensors a. Remove one of the ½” immersion temperature sensors from the Sage Boiler Control Parts Carton and
apply thread sealant to the threads between the probe and hex shoulder.
b. Install the supply sensor in the 3/4” tapping T or J (V9, V11 respectfully) using a ¾” x ½” bushing.
Refer to Figure 3. Wrench the sensor until watertight.
c. Remove the other ½” temperature sensor from the Sage Boiler Control Parts Ca rton and apply thread
sealant to the threads between the probe and hex shoulder.
d. Install the return sensor at the lower rear return tapping, using a short 3” nipple and a 3” x 3” x 3” tee
with the branch of the tee bushed down to ½” (or, use a 3” x 3” x ½” tee, if available). For V9, use tapping C and for V11, use tapping B. Refer to Figure 3. Wrench the sensor until watertight.
2. Install and Connect Temperature Sensor Wiring
Follow the instructions above for the MPC sensor wiring, Step 4 “If Using Electrical Conduit Outside of the Boiler Jacket”.
V9
V11
Figure 3
Sage Boiler Control Instruction Manual Page 24 of 56

Installation

Terminal Layout
Alternate Connection For Outside Air Temperature and
RJ-45
(8 pin)
Remote System Temperature (10k ohm Thermister, 5Vdc)
Label 901 a
Boiler Peer-To-Peer
Communication
Network
RJ-11
(6 pin)
LC
Low Water Cutoff Switch Input
CH
Call For Heat Output
O+ O+
Outside Air Temperature (10k ohm Thermister, 5Vdc)
O-
O­R+ R+
Remote System Temperature (10k ohm Thermister, 5Vdc)
R-
R­DP
Domestic Hot Water Priority
LR
Local / Remote
RO
Remote On / Off (Enable)
SI
Spare Input (Programmable)
C
12 Vdc Common
C
24
(10k ohm Thermister, 5Vdc) Common
Vac
CA - Low Combustion Air Flow HL - Operating or High Limit GP - Gas Pressure Switch WF - Low Water Flow Switch OO - Burner On/Off Switch V-, V+ - Firing Rate Demand (0-10Vdc) P-, P+ - Firing Rate Demand (0-10 Vdc, PWM)
12
Vdc
CA
OO
V- V+ P- P+
GP WFHL
Flame Safeguard Alarm
Fuel Valve Energized
24
Vac
Power Common (-24 Vac)
Power Supply (+24 Vac)
(24 Vac)
(24 V ac)
!
12 Vdc,
0.5 A max total for LO, VI, BP,
SP and SO
Sage Boiler Control Terminal Arrangement (rear view)
Boil er Outlet Temperature
Boiler Inlet Temperature
12Vdc Common
Spare Output (Programmable)
System Pump Start/Stop
Boiler Pump Start/Stop
Vent Inducer Start/Stop
Alarm Indicator
Mixing Valve Output
(4-20 mAdc)
Remote Firing Rate or
Setpoint Input (0-10 Vdc)
CPRALCS
BC BO
BI
C C
C SO SP BP
VI LO MR MS
C­C+
Sage Boiler Control Instruction Manual Page 25 of 56

Installation

External Connections
System Water Temperature Sensor
Mount the sensor in the common header downstream of all boiler connections. Locate the sensor a minimum distance of 10 straight pipe diameters from the from flow disturbing fittings.
Outdoor Air Temperature Sensor
Mount the temperature sensor on an outside wall out of direct sunlight, preferably on a north facing wall. Do not mount sensor near exhaust of any kind, as this may affect readings.
Sage Boiler Control Instruction Manual Page 26 of 56
Installation
External Connections (Continued) Outside Air and Remote System Temperature Sensor RJ45 Connection
All boilers may be connected to the remote system temperature (RST) and the outdoor air temperature (OAT) sensors. Only one of each type sensor is needed for connections with up to eight boilers. The lead boiler is automatically enabled to monitor the sensors. As the boiler lead rotates the sensor monitoring is automatically transferred to the new lead boiler.
Boiler 2
Boiler 1
BO I L E R RUNNING
Connect s t o
Up to 8 Boil ers
Power
BOILER RUNNING
Power
Boiler 2
Alarm
Alarm
RJ-45
Power
O+ O+
O-
O­R+ R+
R-
R-
BO ILER RUNNING
Alarm
Mult i pl e Boil er Connec tion Diag ram
(Us i ng the ex tra O+, O-, R+ & R- term inal s t o dai sy chain
the boi l ers t ogether )
Boiler 1
RJ-45
Power
O+ O+
O­O-
R+ R+
R­R-
BOILER RUNNING
Alarm
RJ-45
O+ O+
O-
O­R+ R+
R-
R-
RJ-45
O+ O+
O­O-
R+ R+
R­R-
Outsi de Ai r
Temperature
Remote System
Temperature
Outsi de Ai r
Temperature
Remote
System
Temperature
Two Boiler
RJ45 C onnec tion Di agram
(Refer to Note 2)
Notes
1. Used Only For Peer-To-Peer Network
. When using Modbus Network wire Outside Air and Remote System sensor
to only one boiler.
2. Wiring from the Outside Air and Remote System Temperature sensors should use low impedance, shielded, twisted pair wire and go directly to the terminals on any one boiler. Signal wiring should not be run in the same conduit with power wiring. Wire shields may be connected to the common terminal (C) located on the same terminal block with the outside air and remote system temperature connections.
3. The RJ45 sensor cables need to be a straight through type cable that connects each pin of the connector on one end to it’s identical pin on the opposite end. Up to a total of three boilers may be connected using a RJ45 splitter. When connecting more than three boilers, it is recommended, and may be more convenient, to use the extra O+, O­, R+ & R- terminals to daisy chain the boilers together (eliminating the need for RJ45 cables and splitters and reducing the loop impedance).
Sage Boiler Control Instruction Manual Page 27 of 56
Installation
Communication
The Peer-To-Peer or Modbus networks allow boiler information, including modulation rate and on/off commands, to be sent via a standard phone cable thus avoiding the cost, time and complexity of wiring multiple signals.
RJ11
Sage Control
Boiler 1 Boiler 2
RJ11
RJ11 Splitter
(Not Inc l uded)
RJ11
Sage ControlSage Control
Boiler 3
RJ11 S plitt er
(Not Inc luded)
Connect s to
Up to 8 Boilers
Or Building
Aut om at i on S ys t em
(BAS) Modbus
Connection
Mu ltiple Boile r
RJ11 Connection Diagram
Sage Control
RJ11
Sage Control
RJ11
Boiler 1 Boiler 2
Two Bo ile r
RJ11 Connection Diagram
When Wiring Modbus Communication to a Building Automation System (BAS)
The Modbus communication connects to the same RJ11 port that is used by the peer-to-pee r communication. Connect one end of the RJ11 cable to the SBC and cut off the other end of the cable to access the individual conductors. The SBC is a 2-wire Modbus communication. Connect the "A" and "B " terminals of a four wire or six wire phone cable (as shown below) to the BAS terminals. The SBC includes two sets of A and B connections, where the A represents the active transmission state of the RS485 transmitter (as opposed to the line idle stat e). You need only to wire to one of the "A" terminals and one of the "B" terminals.
Phone cable signals (4 wire) - connect to pin black or yellow and red or green:
Wire Color Black 1 A Red 2 B Green 3 B Yellow 4 A

Notes

1.
2. Please note that all connections between boilers must be kept as short as possible. The maximum cable length
3. In all cases, the wires should be routed away from any obvious sources of electrical noise or magnetic fields
4. SBC power supply common must be grounded at each boiler to enable network communication.
Slot
Connection
Number
Use standard phone cables (although ones that have all six wires terminated at each end) and splitters to connect each boiler.
between boilers must be kept under 25 feet (average distance between all boilers). (motors, fluorescent lights, contactors, spark generators, etc.). Use a separate conduit and junction box from
the power wiring.
Sage Boiler Control Instruction Manual Page 28 of 56
Installation
Communication (Continued)
The Sage Boiler Control communication selections are found on the Communication Menu. Press and hold the key to leave the Display Mode and access the Main Menu:
Use the keys scroll down to the Communication Menu and push the key:
Communication Menu
No.
90
91 1 1-247
92 19.2
93 None
94 30
95
96
97 1 1 to 8
98 - - 6 - - - 321
Factory
Setting
Peer to
Peer
Range / Choices Parameter and Description
Peer to Peer
Modbus
Protocol
Selects between Peer-To-Peer (multiple boiler Lead/Lag control network) and a Modbus slave communication.
Modbus Address
Each boiler must be given a unique address. Only visible when Protocol equals Modbus.
9.6
19.2
38.4
Odd Even None
1-120
Seconds
Baud Rate
Units are 1000 Bits Per Second (KBPS). Only visible when Protocol equals Modbus.
Parity Only visible when Protocol equals Modbus.
Timeout Only visible when Protocol equals Modbus. Messages Rcvd
Diagnostic tool used to confirm wiring and Modbus master configuration. Only visible when Protocol equals Modbus.
Messages Sent
Diagnostic tool used to confirm wiring and Modbus master configuration. Only visible when Protocol equals Modbus.
Boiler Address
Each boiler must be given a unique address. The boiler address assignment determines the boiler sequencing order. A value of 0 disables the network communications. Only visible when Protocol equals Peer to Peer.
Online Status
Each space can be either the boiler address or a ‘ - ‘ depending on whether there is a boiler of that address on-line. Only visible when Protocol equals Peer to Peer.
Example: - - 6 - - - 321 indicates that boilers 6,3,2 and 1 are online
ENTER
MENU
Sage Boiler Control Instruction Manual Page 29 of 56
Installation
Peer-To-Peer Network
The Sage Boiler Control includes a dependable Peer-To-Peer communication network. This network allows multiple boiler modulating lead/lag control and status signals to be transferred between boilers. In order to succe ssful use this network certain requirements must be followed.
Network Relevant & Updated Parameters
When using the Peer-To-Peer network certain “Network Relevant” parameters must be configured the same in all boilers (refer to Appendix B for parameter identification). To facilitate the configuration of these “Network Relevant” parameters, a network update feature has been included. Once communications is established between all boilers in a system, changing to a “Network Relevant” parameter at the keypad of any boiler will update that parameter in all boilers. In addition to the “Network Relevant” parameters, other common parameters are also “Updated” over the network (although it is not necessary for them to be set identically among boilers on the network). If you wish to configure them differently among boilers, you will have to disconnect the boiler from the network while you change them to prevent the other boiler from being changed as well. “Network Relevant” and additional “Updated” parameters are identified in Appendix B, Parameter Summary.
Initially Establishing Peer-to-Peer Communication
A Peer-to-Peer network is established as follows:
1. Assign all boilers a unique Boiler Address between 1 and 8 and set the Protocol to Peer-to-Peer
2. Connect all boilers using a RJ11 ended telephone cable
3. Configured all “Network Relevant” parameters identically on all boilers. Unexpected boiler behavior may result if these parameter values differ among boilers on the network. When “Network Relevant” parameters are iden tical the ‘Param Code’ parameter will be identical on each boiler (refer to page 43 for parameter location).
4. When two or more boilers are properly configured for communication, the controllers “auto detect” each other and shares information.
Re-Establishing Peer-to-Peer Communication After an individual boiler Communication Failure
A Peer-to-Peer network is re-established as follows:
1. Ensure Boiler address is between 1 and 8 and is unique
2. Ensure the Protocol parameter is set to Peer-to-Peer
3. Use the ‘Param Code’ parameter to check that “Network Relevant” parameters are configured identically (refer to page 43 for parameter location).
4. Remove control power from the boiler
5. Connect the boiler to the network using a RJ11 ended telephone cable
6. Apply control power to the boiler
7. The network will “auto detect” the new boiler and assign it a position in the sequence based on the boiler address.
When a boiler is operated as a stand alone boiler, away from the network, it establishes itself as a lead boiler. If this stand alone boiler is simply re-connecting to a network of operating boilers there is a potential that boiler operation will be disrupted as the new boiler becomes lead. This potential is avoided by following the above Re-Establishing procedure.
Sage Boiler Control Instruction Manual Page 30 of 56
Installation
RS485 Modbus Network
The Sage Boiler Control includes a dependable Modbus communication network. This network allows boilers to be controlled and/or monitored by a remote system via a RS485 Modbus communication network. Each Sage Boiler Control is a Modbus slave with the following available boiler information:
Modbus Addresses

Coil Address Description Read/Write coil = 0 coil = 1 Notes

00001 00002 00003 00004 00005 00006 00007 00008 00009 00010 00011 00012 00013 00014 00015 00016 00017 00018 00019 00020 00021 00022 00023 00024 00025 00026 00027 00028 00029 00030 00031
00032 00033 00034 00035 00036 00037 00038 00039 00040 00041 00042
Outdoor Air Reset Enable/Disable Domestic Hot Water Priority (DHWP) Local / Remote Remote On / Off Modbus Command Spare Input (Programmable) Low Water Cutoff Switch Burner On / Off Switch Low Water Flow High and Low Gas Pressure Switches Operating or High Limit Low Combustion Air Flow Fuel Valve Energized Flame Safeguard Alarm Call For Heat (CFH) General Alarm Vent Inducer Boiler Pump System Pump Spare Output (Programmable) State Boiler Disabled State Weather Shutdown State Lockout State Pump Purge State Limit Hold State Purge/Pilot Ign State Low Fire/Ignition State Main Ignition State Low Fire Hold State Boiler Running State Fan Post Purge State Pump Cool Down State Standby Annunciator Low Water Level Annunciator Off Switch Annunciator Low Water Flow Annunciator Fuel Limit Annunciator High Temp Limit Annunciator Low Air Flow Annunciator FSG Lockout Annunciator Outlet Temp Fail Annunciator Inlet Temp Fail Annunciator OA Temp Fail

Disable Enable Disable Enable Local Remote

Y
Off On Off On 2 Off On 2 Off On 2 Off On 2 Off On 2 Off On 2 Off On Off On Off On Off On 4 Off On Off On Off On Off On
Off On 3 Off On 3 Off On 3 Off On 3 Off On 3 Off On 3 Off On 3 Off On 3 Off On 3 Off On 3 Off On 3 Off Off Off Off Off Off Off Off Off Off Off
Off On 1
Off On 3
On On On On On On On On On On On
3 4 4 4 4 4 4 4 4 4 4
Sage Boiler Control Instruction Manual Page 31 of 56
Installation
RS485 Modbus Network Modbus Addresses (continued)

Coil Address Description Read/Write coil = 0 coil = 1 Notes

00043 00044 00045 00046

00047

Modbus Register Address

40001 40002 40003 40004 40005 40006 40007 PCB Temperature Sensor -50 300 F 40008 40009 40010 40011

Notes

1. After a Modus communication failure, while using the Modbus connection to monitor or control ‘Comm Failure’ alarm is not cleared until a successful write to both the Remote On / Off Modbus Command (00004) and Remote Firing Rate or Remote Setpoint (40006) points have been completed, power is cycled or the ‘Protocol’ parameter is changed from Modbus to Peer-to-Peer and back again.
2. The limit string points (00006 - 00011) are only monitored when there is a Call For Heat. Additionally, if one of these items is ‘open’ items down stream are not monitored.
3. The boiler "state" points (00020 - 00032) are mutually exclusive (i.e. only one is asserted at a time). This will reflect the state of the message on the front of the boiler. Refer to page 6 for an explanation of each state.
4. The “Annunciated” points (00033 – 00046) reflect the state of the signals used to control the displayed Alarm Message. Refer to pages 39 and 40 for an explanation of each annunciator point.
5. “General Alarm” point (00015) turns “On” when the boiler is indicating any alarm condition.
To establish a Modbus network set the following parameters:
Communication Menu: Protocol = Modbus Modbus Address = Give each boiler a unique address. Baud Rate = Set identical to remote system Parity = Set identical to remote system
Connect all boilers using a RJ11 ended telephone cable
Annunciator Remote Temp Fail Annunciator Remote In Fail Annunciator Comm Fail Annunciator Low Inlet Temp Annunciator Memory Failure

Description

Boiler Outlet Water Temperature Boiler Inlet Water Temperature Outside Air Temperature Boiler Actual Setpoint Remote System Temperature Remote Firing Rate or Remote Setpoint
Firing Rate Output to Mod Motor Minimum Return Temperature Setpoint
Mixing Valve Output Control Mode
Off Off Off Off Off
Engineering

Read/

Write

-50 300 F
-50 300 F
-50 300 F 60 230 F
-50 300 F
Y
0 100 % 110 180 F 0 100 % 1 7
Units for Register
= 0

0 100 or 300 % or F 1

Engineering
Units for Register

= 100

On On On On On

Units

4 4 4 4 4
the boilers, the
Not
es
Sage Boiler Control Instruction Manual Page 32 of 56
Configuration & Tuning
Boiler Configuration Menu
Boiler operating behavior is adjusted using the configuration & tuning menus. Press and hold the key to leave the Display Mode and access the Main Menu: Use the keys scroll down to the required Menu and push the key:
No.
1 Deg F
Factory
Setting
Range / Choices Parameter and Description
Deg F Deg C
Display Units
Selects how temperature parameter values are displayed.
Boiler Pump
Activates the boiler pump output according to selected function None: No Boiler Pump. On Always: Pump Runs Continuously. Purge: Pump Runs during pump pre/post purge operations and during
call for heat.
Lead On: Pump runs continuously when the boiler is the lead and runs
2 None
None
On Always
Purge
Lead On
during the fan pre-purge, while the boiler is running and during fan post purge when a lag boiler.
Pump Prepurge
Sets length of time the boiler pump will be run prior to closing the “Call for Heat” relay (CH).
3 15
0 to 600
Seconds
Postpurge Delta
4 5
0 to 20
C or F
Sets the temperature above boiler inlet temperature that boiler outlet temperature must be below before turning off the boiler pump during pump post purge (Pump Cooldown State).
5 No 6 Yes 7 -
month / day / year
8 No
No
Yes
No
Yes
hour : minute
No
Yes
Mixing Valve
Enables the mixing valve control output and user display.
Inlet Sensor (Return Sensor)
Enables the return temperature display and control logic.
Set Time/Date
Displays and sets the time and date of the boiler’s real time clock.
Fuel Limit
Specifies a Fuel Limit such as high and low fuel gas pressure switches a re connected to input (GP). Enables Fuel Limit Hold and alarm messages.
Spare Input
Sets the function of the Spare Input Terminal (SI): Off: Ignore. Sys Pump Feedback: Input (SI) should be wired to a flow switch inserted in
the flow path of the system pump. Input (SI) indicates the system pump is operating. If output (SO) is set to System Backup Pump, system pump output (SO) is energized and System pump Feedback is de-energized the System Backup Pump output (SO) is energized.
9 Off
Off
Sys Pump
Feedback
Low Fire
Low Fire: When the Fuel Valve Energized input (CS) is not
energized and Input (SI) is energized the modulation rate is set to the “Low Fire” setpoint. When input (SI) is not energized, the modulation rate is set to “Fan Purge” setpoint. When the fuel valve energized input (CS) is
energized input (SI) is ignored. Spare Output Sets the function of the Spare Output Terminal (SO): Off: Never close output (SO). CAD: Combustion Air Damper (CAD) or fresh air damper
Closes SO relay with a call for heat, Opens SO relay 2 minutes after call for heat has been de-activated.
System Pump Feedback indicates the Primary System Pump is not operating.
10 Off
System Pump BU
Off
CAD
Soft Alarm
System Pump BU: Closes when System Pump output is activated but the
Soft Alarm: Alarm indication or warning, closes when any alarm is
active, or a condition is preventing a boiler start, including Off Switch.
ENTER
MENU
Sage Boiler Control Instruction Manual Page 33 of 56
Configuration & Tuning
System Configuration Menu
No.
20 Off
21 No
22 140 60 F to 140 F
23 220 150 F to 220 F
24 No
25 No
27 No
28
Factory
Setting
“Low Water Level”
Range / Choices Parameter and Description
Off
Isolated Demand
Shared Demand
No
Remote SP
Modbus SP Remote Mod Modbus Mod
No
Display Only
Control
No
Yes
No
Yes
16 Text
Characters
DHWP
Enables Domestic Hot Water Priority (DHWP) control feature. When input (DP) is energized DHWP becomes active as selected: Off No DHWP Isolated Demand Boiler that receives the input (DP) drops off the
Peer-To-Peer network and it’s temperature setpoint is adjusted above the DHWP Setpoint. The PID output is based on boiler outlet temperature and setpoint. If Remote SP or Remote System temperature sensors were selected, control is switched to the Boiler Outlet Sensor.
Shared Demand If the lead boiler receives the input (DP) the
temperature setpoint for all boilers on the Peer-To­Peer network is adjusted above the DHWP Setpoint
Remote Control
Sets the remote (Energy Management System) control mode as follows: No: Local setpoint and modulation rate is us ed.
Modbus and remote input (C+,C-) are ignored
Remote SP: Remote Input (C+, C-) is used as the temperature
setpoint. Parameter 22 & 23 may be used to adjust the signal range
Modbus SP: RS485 Modbus (40006) is used as the
temperature setpoint
Remote Mod: Remote Input (C+, C-) is used as the modulation
rate.
Modbus Mod: RS485 Modbus (40006) is used as the modulation
rate.
Remote 1.0 Volt=
Sets the temperature corresponding to input (C+,C-) 1Volts. Voltage below 1V is considered invalid, (failed or incorrect wired sensor).
Remote 9.0 Volt=
Sets the temperature corresponding to input (C+,C-) 9 Volts. Voltage above 9V is considered invalid, (failed or incorrect wired sensor).
Remote Sensor
Enables the Remote System Temperature sensor display and control logic: No Remote Sensor Input (R+,R-) is ignored. Display Only Remote Sensor Input (R+,R-) is used for display only Control Remote Sensor Input (R+,R-) is compared with the
temperature setpoint to establish a modulation rate
System Pump
Enables the System Pump output (SO)
LWC or CAD
Specifies a Low Water Cut-off Switch or Combustion Air Damper (Fresh Air Damper) Open switch is connected to input (LC). Enables Limit Hold and alarm messages. Limit hold display message is described by parameter 28
Alarm Message
Limit Hold and alarm message displayed corresponding to sensor connected to input (LC)
The “ENTER” key and “Up” and “Down” arrow keys are used to change the text Message.
Sage Boiler Control Instruction Manual Page 34 of 56
Configuration & Tuning
Setup Menu
No.
30 Off
31 90
32 10
33 5
34 5
35 20
36 20
37 100
38 1
39 220
Factory Setting
Range / Choices Parameter and Description
Off
WWSD of Boiler
WWSD of Sys Pump
Both
50 to 100
% Maximum
Modulation Rate
0 to 50
% Modulation Rate
60 to 900
Seconds
0 to 900
Seconds
1 to 30
Minutes
1 to 30
Minutes
40 - 100
% Modulation Rate
1 - 10
Degrees/Minute
100 - 240
C or F
WWSD
Specifies Warm Weather Shut-Down (WWSD) control of boiler and/or system pump:
Off: Ignores Warm Weather setpoint WWSD of boiler: When Outside Air Temperature (OAT) is higher than
the WWSD setpoint, inhibits boiler start
WWSD of Sys Pump: When OAT is higher than the WWSD setpoint de-
energize System Pump output (SO)
Both: When OAT is higher than the WWSD setpoint, inhibit
Call for Heat and de-energized system pump output (SO)
LL Start Trigger
Specifies the percent of maximum modulation rate the running boiler(s) must reach before calling upon additional boilers for help.
LL Stop Trigger
Specifies the modulation rate that the running boiler(s) must be below before shutting down a lag boiler
Boiler On Delay
Time Delay after On Point setpoint has been reached before starting the next boiler. Short time delay to prevent nuisance starts due to momentary temperature and modulation rate swings
Boiler Off Delay
Time Delay after the Off Point setpoint before stopping the next boiler. Short time delay to prevent nuisance stops due to momentary temperature and modulation rate swings.
%FR On Delay
Time Delay after the modulation rate is above the LL Start Trigger before starting the next boiler. Long time delay to avoid temperature going below setpoint as a result of a slow process change
%FR Off Delay
Time Delay after the modulation rate is below the LL Stop Trigger before stopping the next boiler. Long time delay to avoid temperature going above setpoint as a result of a slow process change
High Fire Limit
To maximize high efficiency condensing operation, the firing rate is limited to an adjustable value. The Sage Boiler Control will keep the boilers at this firing rate or lower as long as the boilers will handle the load. After the last boiler has started the modulation rate is released up to 100%.
Deg/Min Hold Off
Specifies a temperature rate of change that inhibits the next boiler being started or stopped. If the temperature is increasing faster than this rate of change the next boiler is not started. Also, if the temperature is decreasing faster than this rate of change the next boiler is not stopped.
Cutback Setpoint
Boiler Outlet temperature above the Cutback Setpoint causes the modulation rate to be reduced proportionally to help avoid a high temperature limit lockout. This parameter is significant while the boiler is controlled according to the remote system temperature sensor or remote input (C+,C-) or Modbus (40006) Remote Firing Rate.
Sage Boiler Control Instruction Manual Page 35 of 56
Configuration & Tuning
Setup Menu (Continued)
No.
40 150
41 5
42 Disable
43 168
Factory Setting
Range / Choices Parameter and Description
16 to 420
Seconds
3 to 120
Seconds
Disable
Enable
8-720
Hours
Net Start Dwell
The Net Start Dwell Time Delay specifies the length of time the peer-to­peer network will wait for the Main Fuel Valve Energized input (CS) to be energized after a boiler Call for Heat. If the Net Start Dwell time is exceeded before the main fuel valve is open the next boiler Call for Heat is initiated without further delay. This parameter should be longer than the sum of the pump purge and boiler purge times.
Limit Fault Time
The Limit Fault Time Delay specifies the length of time the peer-to-peer network will wait for the boiler limits input (CA) to be energized after a boiler Call for Heat. If the Limit Fault time is exceeded before the limits are energized the next boiler Call for Heat is immediately initiated.
Rotation
Enables the lead boiler role to be rotated through the boilers on the network. When disabled the boiler with the lowest network address is lead.
Rotate after
Specifies number of hours (cumulative) a lead boiler runs before passing the lead to another boiler.
Lead role will be surrendered earlier if the lead boiler is placed into manual mode, is run remotely (mode 6), fails to start, is “blind” (all input sensors failed), or is satisfying a DHWP request.
49 100
50 0
51 0
52 0
53 600
54 0
0 to 100
% Full Scale
0 to 100
% Full Scale
0-100
% Modulation Rate
0 to 100
% Modulation Rate
10 to 1200
Seconds
0 to 600
Seconds
Parameters 44 through 48 are found on the following page
Blower Spd High (Linkage Max. Position)
Percent of (0 - 10 Vdc output [V+,V-]) output that represents a 100% modulation rate. This scaling factor allows the Sage Boiler Control to display 100 % when the linkage is at rated boiler output.
Please Note
The Burner input rate adjustment must be completed before can be set. After maximum boiler firing rate is established, the Sage Controller Firing Rate Display “FR” percentage should be 100%. If boiler rate is established at less than 100% FR, that value should be entered in parameter 49 as blower speed high. This will establish the correct scaling factor and will prevent overfiring of the boiler.
Blower Spd Low (Linkage Min. Position)
Percent (0 - 10 Vdc output (V+,V-) or pulse) output that represents a 0% modulation rate. This scaling factor allows the Sage Boiler Control to display 0 % when the linkage is at minimum boiler output.
Low Fire Spd
Modulation % used for Low Fire Hold and Low Fire Start conditions. Low fire position is established by the linkage adjustment. This parameter may be left at 0%. Fan Purge Speed [Note – Fan Purge Speed used during Low Fire Hold (parameter 53)]. Burners with linkage control purge and light-off rates using the RM7800 and linkage adjustments.
Low Fire Hold
Time modulation rate is held at preset value (Low Fire Spd or Fan Purge Spd depending on the state and configuration of Spare Input) after the Fuel Valve Energized Input (CS) is energized.
Post Purge Time
Time modulation rate is held at Purge % setpoint after the Fuel Valve Energized Input (CS) is de-energized.
this parameter
Sage Boiler Control Instruction Manual Page 36 of 56
Configuration & Tuning
Setup Menu (Continued)
230 210 190 170 150 130 110
90 70
Boiler
Setpoint
Ho t Water Setpoint
Outdoor Air Temperature
-20 100800 204060
Boiler Design
Boiler Set Up
230 210 190 170 150 130 110
90 70
Temperature
Hot Water Setpoint
Outdoor Air Temperature
-20 100800 204060
Outdoor Des ign
Outdoor Set Up
Design
Set Up
Temperature
Max Setpoint
Min Setpoint
Outdoor Reset Graph
Energy used by the hot water heating system can be greatly reduced by adjusting (resetting) the operating temperature setpoint as the outdoor temperature changes. Using this approach, the heat lost from the building is matched by the heat input to the building. The control utilizes a reset curve to set the relationship between outdoor temperature and boiler outlet temperature setpoint. The reset curve is determined from the “Set Up” and the “Design” conditions as shown in the above graph and described by parameters 45, 46, 47 and 48:
No.
Factory Setting
Range / Choices Parameter and Description
Outdoor Sensor
Enables the Outside Air Temperature display and control logic: No Outside Air Input (O+O-) is ignored.
44 No
No
Display Only
Outdoor Reset
Display Only Do Not
temperature, Display Outside Air Temperature
Outdoor Reset Calculate the temperature setpoint based on outdoor
Calculate setpoint based on outdoor
temperature using a reset curve defined by Outdoor Set Up, Boiler Set Up, Outdoor Design and boiler Design parameters
Outdoor Set Up
45 55 F 40 F to 100 F
The Outdoor Set Up temperature is the outdoor temperature at which the Boiler Set Up temperature is supplied.
Boiler Set Up
46 140 F 140 F to 180 F
The Boiler Set Up Temperature is the starting boiler water temperature of the reset ratio. If the building feels cool during mild outdoor conditions, the Boiler Set Up setting should be increased.
Outdoor Design
47 30 F -20 F to 50 F
The Outdoor Design Temperature is the outdoor temperature at which the Boiler Design temperature is supplied.
Boiler Design
The Boiler Design setting is the water temperature required to satisfy the
48 180 F 150 F to 220 F
building heat loss during the Outdoor Design temperature. If the building feels cool during cold outside conditions, the Boiler Design setting should be increased.
Sage Boiler Control Instruction Manual Page 37 of 56
Configuration & Tuning
Setup Menu (Continued)
Slower Response
Factory Setting
Faster Response
Faster Response
Local PID Factory Setting
Slower Response
No.
55 41 0 to 10000
56 15 0 to 10000
57 0 0 to 10000
58 20 0 to 10000
59 30 0 to 10000
60 0 0 to 10000
Factory Setting
Range / Choices Parameter and Description
PID (I)
PID (P)
61 20 10 5 41 30 15 8 36 34 17 9 30 40 20 10 25 48 24 12
20
15 80 40 20 12 100 50 25 10 120 60 30
9 140 70 35 8 160 80 40
Typical Sage Boiler Control PID Gain and Integral Settings
Local PID P
Proportional Gain value for boiler outlet temperature sensor control Modes. A larger gain value results in tighter, more active, PID control. Gain is the primary PID modulation rate tuning adjustment and provides the immediate modulation rate response.
Pick a gain based on the desired initial response. The burner modulation rate can oscillate if the Proportional Gain is too large.
Local PID I
Integral gain value for boiler outlet temperature sensor control Modes. A smaller value makes the Integral ramp in less time (i.e., faster). Integral is a secondary PID modulation rate tuning adjustment that ramps the output over time (typically minutes) .
Based on the selected Local PID P, select the corresponding (from above table) Integral value. Repeats per minute between 0.5 and 2.0 are typical. The burner modulation rate can oscillate if the Integral time is too small.
Local PID D
The Derivative gain value for boiler outlet temperature sensor control Modes. A larger Derivative gain value produces a larger PID output contribution proportional to the rate of change of the error (Setpoint – Boiler Outlet Temperature). When set equal to zero it has no effect on the output.
Remote PID P
Proportional Gain value for Remote System Temperature sensor control Modes. Refer to Local PID P for explanation.
Remote PID I
Integral Gain value for Remote System Temperature sensor control Modes. Refer to Local PID I for explanation.
Remote PID D
Derivative Gain value for Remote System Temperature sensor control Modes. Refer to Local PID D for explanation.
½
Repeats/Minute
60
1
Repeats/Minute
30
2
Repeats/Minute
15
Sage Boiler Control Instruction Manual Page 38 of 56
Configuration & Tuning
Setup Menu (Continued)
No.
61 15 0 to 10000
62 40 0 to 10000
63 0 0 to 10000
64 15 0 to 10000
65 40 0 to 10000
66 0 0 to 10000
Factory Setting
Range / Choices Parameter and Description
Mixing Valve P
Proportional Gain value for boiler Inlet temperature sensor control mode. A larger gain value results in tighter, more active, PID control. Gain is the primary PID modulation rate tuning adjustment and provides the immediate mixing valve modulation response.
Pick a gain based on the desired initial response. The mixing valve can oscillate if the Proportional Gain is too large.
Mixing Valve I
Integral gain value for boiler inlet temperature sensor control mode. A smaller value makes the Integral ramp in less time (i.e., faster). Integral is a secondary PID modulation rate tuning adjustment that ramps the output over time (typically minutes).
Based on the selected Mixing Valve P, select the corresponding (from table on previous page) Integral value. The mixing valve can oscillate if the Integral time is too small.
Mixing Valve D
The Derivative gain value for boiler inlet temperature sensor control mode. A larger Derivative gain value produces a larger PID output contribution proportional to the rate of change of the error (Setpoint – Boiler Inlet Temperature). When set equal to zero it has no effect on the output.
Max Delta T P
Proportional Gain value for boiler differential (boiler outlet minus inlet temperature sensor) temperature control mode. Refer to Local PID P for explanation.
Max Delta T I
Integral Gain value for boiler differential (boiler outlet minus inlet temperature sensor) temperature control mode. Refer to Local PID I for explanation.
Max Delta T D
Derivative Gain Term for boiler differential (boiler outlet minus inlet temperature sensor) temperature control mode. Refer to Local PID D for explanation.
Sage Boiler Control Instruction Manual Page 39 of 56
Configuration & Tuning
Manual Mode Menu
Manual mode allows the boiler modulation rate, boiler call for head output and mixing valve position to be directly positioned by the user. These are valuable tools for trouble shooting and setup.
No.
101 Auto
102 Varies 0 to 100
103 Varies
104 Man
105 Varies 0 to 100
Factory
Setting
Range / Choices Parameter and Description
Boiler Man/Auto
Man
Auto
On,
Off
Man
Auto
Man: Remain in Manual Mode Auto: Return to Boiler Mode specified by parameter/boiler conditions
Activated only when in Supervisor Mode.
Modulation Rate
Sets the modulation rate to be used for boiler when in Manual Mode Activated only when in Supervisor Mode and Boiler Man/Auto = Man.
Boiler On/Off
Sets the boiler start/stop status when in Manual Mode No: Turn off boiler if running, otherwise remain off Yes: Turn on boiler if off, otherwise remain on.
Activated only when in Supervisor Mode and Boiler Man/Auto = Man.
Mixing Valve M/A
Man: Remain in Manual Mode Auto: Return to Control Mode specified by parameter/boiler conditions
Activated only when in Supervisor Mode.
Mixing Valve
Sets the Mixing Valve % Open to be used for valve when in Manual Mode Activated only when in Supervisor Mode and Mixing Valve M/A equals
Man.
Sage Boiler Control Instruction Manual Page 40 of 56
Trouble Shooting
Alarm Messages
Alarm Messages are shown one at a time in priority order. The message closest to the top of this List is displayed first. Following messages are not shown until the higher priority message has cleared. All alarm messag es are also stored in the Fault History.
LCD Display
Alarm Message
Low Water Level
O Flashing Red Alarm Light
Off Switch Turn Burner Switch
Low Water Flow
O Red Alarm Light
Fuel Limit
O Flashing Red
Alarm Light
High Temp Limit
O Flashing Red Alarm Light
Low Air Flow
O Flashing Red Alarm Light
FSG Fault
O Flashing Red Alarm Light
Outlet Temp Fail
O Red Alarm Light
Inlet Temp Fail
O Red Alarm Light
OA Temp Fail
O Red Alarm Light
Remote Temp
Fail
O Red Alarm Light
Recommended
Action
Manually Reset the
Low Water Cutoff
On
Ensure boiler pump is
running and boiler
water flow is
unobstructed
Manually Reset the
Fuel pressure switch
Manually Reset the
High Temperature
Aquastat
Check combustion air
blower and air
pressure switch
settings and wiring
Manually Reset
Required, Refer to
Flame Safeguard
Manual corrective
actions
Check wiring and
sensor
Check wiring and
sensor
Check wiring and
sensor
Check wiring and
sensor
Explanation
Low Water Cutoff Switch
When this option is configured and a control is installed, the manual reset low water safety relay is preventing the boiler from starting. If terminal (LC) does not receive power and the Call For Heat output (CH) is powered the “Low Water Level” Message is displayed.
Burner Switch is Off
Control switch is in the OFF position and is preventing the boiler from starting. If terminal (OO) does not receive power and the Call For Heat output (CH) is powered the “OFF Switch” Message is displayed.
Low Water Flow Switch
Low water flow is preventing the boiler from starting. If terminal (WF) does not receive power and the Call For Heat output (CH) is powered the “Low Water Flow” Message is displayed.
Low or High Gas Pressure Switch
The low or high gas pressure switch is preventing the boiler from starting. If terminal (GP) does not receive power and the Call For Heat output (CH) is powered the “Fuel Limit” Message is displayed.
High Limit Temperature
The high temperature limit (HL) (and operational temperature limit when provided) aquastat is preventing a boiler start. If terminal (HL) does not receive power and the Call For Heat output (CH) is powered the “High Temp Limit” Message is displayed.
Low Air Flow or Blocked Vent Switch Not Made
The air flow (and blocked vent switch when provided) is preventing a boiler start. If terminal (CA) does not receive power and the Call For Heat output (CH) is powered the “Low Air Flow” Message is displayed.
Flame Safeguard Fault
The Flame Safeguard is preventing a boiler start. If terminal (AL) receives power at any time, the “Flame Failure” Message is displayed.
Boiler Outlet Temperature Sensor Fail
The boiler outlet temperature sensor is not connected or is reading above or below a valid range. When the boiler outlet sensor fails and the Outlet Sensor mode was selected the control will transfer to Lost Sensor Blind Mode
Boiler Inlet Temperature Sensor Fail
The boiler inlet temperature sensor is not connected or is reading above or below a valid range. When the boiler inlet sensor fails the mixing valve output will drive to 0% and low temperature alarm and maximum water differential (boiler outlet minus boiler inlet) temperature hold are disabled.
Outside Air Temperature Sensor Fail
The outside air sensor is configured and is not connected or is reading above or below a valid range. When the outside air sensor fails the warm weather shutdown (WWSD) and outside air reset control logics are disabled.
Remote System Temperature Sensor Fail
The remote system temperature sensor is configured and is not connected or is reading above or below a valid range. If Remote System Temperature Sensor mode was selected the control will transfer to Boiler Outlet Sensor Mode.
Sage Boiler Control Instruction Manual Page 41 of 56
Trouble Shooting
Alarm Messages (continued)
LCD Display
Alarm Message
Remote Input
Fail
O Red Alarm Light
Comm Failure
O Red Alarm Light
Low Inlet Temp
O Red Alarm Light
Memory Failure
O Red Alarm Light
Recommended Action Explanation
Check wiring and
Remote System
Check wiring and
Remote System
Confirm each boiler has
a unique address
Check wiring and
sensor
Check return water
temperature. Consider
system or operational
changes to avoid low
temperature events
Call Factory
Reset all memories in
System menu:
Clr BIT History
Clr Alarm Hist
Clr Run Time Cnt
Clr Cycle Cnt
Factory Defaults
(Factory Level
Password is required)
Remote Control Input Fail
The Remote Control Input is configured and is not connected or is above or below a valid range. When the remote control input fails the following control mode changes are taken automatically:
Selected Modes Resulting Control Mode Remote Mod Outlet sensor and Local Setpoint Remote Mod & Remote Sensor Remote Sensor and Local Setpoint Remote SP Outlet Sensor and Local Setpoint Remote SP & Remote Sensor Remote Sensor and Local Setpoint
Communication Failure
The Modbus or Peer-To-Peer network has failed. When the Modbus network fails the following control mode changes are taken automatically:
Selected Modes Resulting Control Mode Modbus Mod Outlet sensor and Local Setpoint Modbus Mod & Remote Sensor Remote Sensor and Local Setpoint Modbus SP Outlet Sensor and Local Setpoint Modbus SP & Remote Sensor Remote Sensor and Local Setpoint
After a Modus communication failure, the ‘Comm Failure’ alarm is not cleared until communication is restored and a successful writes to both the Remote On / Off Modbus Command (00004) and Remote Firing Rate or Remote Setpoint (40006) points have been completed, power is cycled or the protocol parameter is changed to Peer-To-Peer and then back to Modbus.
When a Peer-To-Peer network has failed the boilers begin operation as stand alone boilers using the selected parameters.
After a Peer-To-Peer communication failure the ‘Comm Failure’ alarm is not cleared until communication is restored and the boiler rejoins a network with at least one other boiler, power is cycled or the protocol parameter is changed to Modbus and then back to Peer-To-Peer. Low Boiler Inlet Temperature If the boiler inlet temperature is below the Low boiler inlet temperature setpoint, the “Low Inlet Temp” Message is displayed and the boiler inlet temperature history is stored. See following page for additional information on Low boiler inlet temperature history storage and retrieval.
Memory Failure New software has been installed in the Sage Boiler Control or a power interruption has caused a memory failure. The Call For Heat will be prevented until the condition is cleared.
Sage Boiler Control Instruction Manual Page 42 of 56
Trouble Shooting
Diagnostic Menu
All values shown in Diagnostic Menu are for display only and cannot be adjusted by the operator. Press and hold the key to leave the Display Mode and access the Main Menu:
MENU
Use the keys scroll down to the Diagnostic Menu and push the key:
ENTER
Boiler Inlet Temperature History
Display Description
13:31 09/10/06 BOT Sensor Fail
8:45 09/10/06 Low Temp: 130F
8:45 09/10/06 Low for 1:00:02
FAULT HISTORY
The last 10 alarms are stored in memory. Use the arrow keys to scroll through
the alarms. Each alarm is displayed with the time and date it occurred.
BIT HISTORY
The last 10 Low Inlet Temperature Events are stored in memory. Each time the boiler inlet temperature is less than the “Min In H2O Temp.” parameter, a low temperature event is recorded. The BIT History screen automatically toggles between the “lowest temperature for the event” and “Duration Below Setpoint” displays and provides time and date of each event.
SYSTEM
Items provided by this menu are shown on page 43
DHW Priority
Off
Local/Remote
Off
Remote On/Off
Off
DISCRETE INPUTS
These screens provide a convenient way to trouble shoot wiring during the installation phase. Each screen provides the status of a controller input.
These displays show the status of the corresponding Discrete Input
Spare Input
Off
Low Water Cutoff
Off
Burner On / Off
Off
Low Water Flow
Off
Fuel Limit
Off
Oper./High Limit
Off
PLEASE NOTE
These displays provide limit string monitoring status. These inputs are only monitored when there is a Call For Heat. Additionally, if one of these items is ‘open’, items down stream are not monitored.
Low Air Flow
Off
Fuel Energized
Off
These displays show the status of the corresponding Discrete Input
FSG Alarm
Off
Sage Boiler Control Instruction Manual Page 43 of 56
Trouble Shooting
Diagnostic Menu (Continued)
Display Description
Call For Heat
Off
Lockout Indicator
Off
Vent Inducer
Off
Boiler Pump
Off
System Pump
Off
Spare Output
Off
Boiler Outlet
0%
Boiler Inlet
0%
Outside Air
0%
DISCRETE OUTPUTS
These screens provide a convenient way to trouble shoot wiring during the installation phase. Each screen provides the status of a controller output.
These displays show the status of the corresponding Discrete Output
ANALOG INPUTS
These screens provide a convenient way to trouble shoot wiring during the installation phase. Each screen provides the status of a controller analog input.
These displays show the status of the corresponding Analog Input
Remote System
0%
Remote Input
0%
PCB Temperature
0%
Boiler Demand
0%
Mix Valve Demand
0%
ANALOG OUTPUTS
These screens provide a convenient way to trouble shoot wiring during the installation phase. Each screen provides the status of a controller analog Output.
These displays show the status of the corresponding Analog Output
Sage Boiler Control Instruction Manual Page 44 of 56
Trouble Shooting
Diagnostic Menu (Continued) System Menu
Display Description
Software Rev.
PCB Temperature
Clr Alarm Hist
Clr Run Time Cnt
Clr Cycle Cnt
Factory Defaults
S 3.24
70 F
Clr BIT Hist
No Action
No Action
No Action
No Action
No Action
Actual RST
32 F
Actual OAT
-40 F
Actual BOT
32 F
Actual BIT
32 F
Param Code
Software Revision
Displays current Software Revision.
PCB Board Temperature
The operating range for the control is 32 to 140 F.
Clear Boiler Inlet Temperature (BIT) Memory
No Action History remains unchanged Yes Clears low BIT memory
Clear Alarm History Memory
No Action History Remains unchanged Yes Clears alarms memory
Clear Boiler Run Time Hour Accumulator Memory
Boiler Run Time Hours are displayed in Display Mode as “Hours”. No Action Hours Remain unchanged Yes Clears accumulated hours memory
Clear Boiler Start/Stop Cycle Accumulator Memory
Boiler Start/Stop cycles are displayed in Display Mode as “Cycles”. No Action Hours Remain unchanged Yes Clears accumulated cycles memory
Clear User Installed Parameter Memory
No Action Currently set parameter values are unchanged Set Sets all parameters back to their Factory Default values
Temperature Input Fine Calibration
All inputs are factory calibrated. However, it may become necessary to field
calibrate due to measuring errors resulting from long wire lengths or third party sensor use. This is a single point calibration tool. To gain the greatest benefit, it is recommended to calibrate as close as possible to the expected operating temperature and measure the temperature at the sensor location.
Remote System Temperature (RST) Outside Air Temperature (OAT) Boiler Outlet Temperature (BOT) Boiler Inlet Temperature (BIT)
Calibration Procedure:
1. Select sensor that requires field calibration
2. Run boiler to rated condition
3. Enter the Actual RST, OAT, BOT and BIT
4. Display will flash back to the default (Note Calibration number does not remain on screen)
5. Calibration is complete. A one point calibration offset is calculated and applied.
Parameter Code This number represents “Network Relevant” parameters. It can be used to
ensure that these parameters are identical when establishing a Peer-To-Peer network
.
Sage Boiler Control Instruction Manual Page 45 of 56
Trouble Shooting
Sensor Resistance Chart
Sensor Temperature vs. Resistance
Water Temperature Ohms of Water Temperature Ohms of Water Temperature Ohms of
°C °F Resistance °C °F Resistance °C °F Resistance
-22 -8 110,460 14 58 16,126 51 124 3,453
-21 -6 103,486 16 60 15,313 52 126 3,311
-20 -4 96,999 17 62 14,546 53 128 3,176
-19 -2 90,962 18 64 13,822 73 164 1,565
-18 0 85,340 19 66 13,139 74 166 1,508
-17 2 80,103 20 68 12,493 76 168 1,453
-16 4 75,222 21 70 11,884 77 170 1,401
-14 6 70,670 22 72 11,307 78 172 1,350
-13 8 66,424 23 74 10,762 79 174 1,302
-12 10 62,460 24 76 10,247 80 176 1,256
-11 12 58,759 26 78 9,760 81 178 1,212
-10 14 55,301 27 80 9,298 82 180 1,169
-9 16 52,069 28 82 8,862 83 182 1,129
-8 18 49,047 29 84 8,448 84 184 1,089
-7 20 46,220 30 86 8,056 86 186 1,052
-6 22 43,574 31 88 7,685 87 188 1,016
-4 24 41,097 32 90 7,333 88 190 981.2
-3 26 38,776 33 92 6,999 89 192 947.9
-2 28 36,601 34 94 6,682 90 194 915.9
-1 30 34,562 36 96 6,382 91 196 885.2 0 32 32,650 37 98 6,097 92 198 855.7 1 34 30,856 38 100 5,826 93 200 827.3 2 36 29,171 39 102 5,569 94 202 800.1 3 38 27,590 40 104 5,325 96 204 773.8 4 40 26,104 41 106 5,093 97 206 748.6 6 42 24,707 42 108 4,872 98 208 724.3 7 44 23,394 43 110 4,663 99 210 700.9 8 46 22,159 44 112 4,463 100 212 678.4 9 48 20,997 46 114 4,273 101 214 656.8
10 50 19,903 47 116 4,093 102 216 635.9 11 52 18,873 48 118 3,921 103 218 615.8 12 54 17,902 49 120 3,757 104 220 596.5 13 56 16,988 50 122 3,601
Sage Boiler Control Instruction Manual Page 46 of 56
Trouble Shooting
Security Menu
Passwords
There are three Access Levels in the system; Basic, Supervisor, and Factory.
At the BASIC Access Level, the user can view many parameters, but is only allowed to edit a small sub-set of the parameters that are visible.
At the SUPERVISOR Access Level, the user can view and edit most parameters that are visible. Note: not all parameters will be visible at the Supervisor Access Level.
At the FACTORY Access Level, all relevant internal parameters in the system will be visible and programmable.
The Basic Access Level is the access level at power-up if the system password parameter is not equal to zero. The Supervisor Access Level is the access level at power-up if the system password parameter is equal to zero. If the system password is non-zero, the Supervisor Access Level may be reached by entering the correct password in the Enter Password parameter.
The Factory Access Level can be reached by entering the factory password in the Enter Password parameter and holding the Enter key for at least two seconds when accepting the value entered Level parameter menu when the system has entered the Factory Access Level. Note that the Access Level parameters value will indicate "Supervisor".
To exit either of the privileged access levels (Factory and Supervisor), change the value of the Access Level parameter from "Supervisor" to "Basic". Also, if no key is pressed for ~ 1 hour, the access level will automatically revert to Basic.
No.
0 to 9999
Factory
Setting
Factory
Password
is 86
Range / Choices Parameter and Description
Access Level
Basic
Supervisor
0 to 9999
Basic: Select Basic Level Access to parameters/variables Supervisor: Select Password Level Access to parameters/variables
Enter Password
Allows user to enter password to gain access to both Supervisor Access and Factory Access Levels.
Set Password
Holds the user-defined password for the boiler. A password = 0 means no password protection. Access Level will default to Supervisor Level at power-up.
. The display will jump to the Access
Sage Boiler Control Instruction Manual Page 47 of 56
Specifications
General
Mechanical: Panel Assembly: 8 inches wide x 6 inches tall Message Display: 2 x 16 Character, 8.06 mm characters
Environmental: Operating Temp: 32 to 140 F (0 to 60 C) Storage Temp: -20 to 150 F (-28 to 65 C) Humidity Limits: 15 to 95% (non-condensing) Front Panel: NEMA 1 Electrical: Power Supply: 24Vac
Note: All 24Vac Inputs must be connected to the same phase as (PR) Internal Power Consumption: 8 VA max, 24Vac (+/- 15%), and 6 VA max, 12Vac 0.5A for LO, VI, BP, SP and SO
Discrete Inputs:
Terminal Description
DP Domestic Hot Water Priority (DHWP) 12 Vdc / 1 mA LR Local / Remote 12 Vdc / 1 mA
RO Remote On / Off (Enable) 12 Vdc / 1 mA
SI Spare Input (Programmable) 12 Vdc / 1 mA
LC Low Water Cutoff Switch 24 Vac / 1mA OO Burner On / Off Switch 24 Vac / 1mA WF Low Water Flow 24 Vac / 1mA GP High and Low Gas Pressure Switches 24 Vac / 1mA
HL Operating or High Limit 24 Vac / 1mA CA Low Combustion Air Flow 24 Vac / 1mA CS Fuel Valve Energized 24 Vac / 1mA
AL Flame Safeguard Alarm 24 Vac / 1mA
Discrete Outputs:
Terminal Description
CH Call For Heat (CFH) 24 Vac / 10A
LO Lockout Indicator 12 Vdc / 100mA
VI Spare Output 12 Vdc / 100mA BP Boiler Pump 12 Vdc / 100mA SP System Pump 12 Vdc / 100mA
SO Spare Output (Programmable) 12 Vdc / 100mA
Analog Inputs:
Terminal Description Rating
BO Boiler Outlet Water Temperature 10k Thermister, 5Vdc, 5 mA max load
BI Boiler Inlet Water Temperature 10k Thermister, 5Vdc, 5 mA max load O+
O -
R+ R -
C+ C -
Analog Outputs:
Terminal Description Rating
P+
P­V+
V-
MS MR
Outside Air Temperature 10k Thermister, 5Vdc, 5 mA max load Remote System Temperature 10k Thermister, 5Vdc, 5 mA max load
Remote Modulation Rate or Remote Setpoint
Modulation Rate Output to Mod Motor
Mixing Valve Output 4-20mA
0-10 Vdc (~100K ohm impedance)
1Vdc = 0%, 9Vdc = 100%
0 – 100 % Duty Cycle, 0V – Off, ~10V - On
4 mA = 0 % Open, 20 mA = 100% Open
Rating
Rating
0 – 10 V, 5 mA max
Sage Boiler Control Instruction Manual Page 48 of 56
Specifications
General (Continued)
Real Time Clock: Battery Backed, 2 yrs without AC Power Communications: Programming - ISP Port Boiler Peer to Peer – RS485, RTU
Time and Date Battery:
The battery is only is removed from the Sage Boiler Control. When new, the battery can power the clock for approximately 2 years with 24 Vac power removed. The clock battery has a shelf life of approximately 6 years (without ac applied). Sage Boiler Control configuration and user data are stored in non-volatile EEPROM. This battery is NOT used to retain this memory.
The battery is located at the back of the Sage Boiler Control for easy replacement.
Component Description
1. Sage Boiler Control Assembly (un-programmed).......................................................................................102106-01
Individual boiler operating and modulation rate control and modulating lead-lag controller. Built to UL and CSA standards.
2. Replacement Fuse Busman GMC-5A
Repair Part Number
used to power the time of day and date clock chip when the 24 Vac power
3. Immersion Temperature Sensor.................................................................................................................101935-01
½” NPT 10K OHM @ 25C, NTC Thermistor Type, Resistance Ratio R0/R50 = 9.07 temperature sensor for measuring water temperature in supply manifold, return manifold or system header.
4. Outdoor Temperature Sensor.................................................................................................................801SOL0012
10K OHM @ 25C, NTC Thermistor Type, Resistance Ratio R0/R50 = 9.07 outdoor ai r temperature sensor with weather proof box and protective sleeve. For use in outdoor reset applications.
5. Wire Harness (Sage to Q7800H) .........................................................................................................101976-01
6. Q7800H Flame Safeguard Sub Base...................................................................................................101182-01
7. Sage Control (programmed).................................................................................................................102436-01
8.. SBC Parts Carton, MPC [includes MPC Sensor J-Box, Snap bushing (for Sensor J-Box) and MPC
Sensor J-Box Cover (with holes)].........................................................................................................101977-01
Sage Boiler Control Instruction Manual Page 49 of 56
Network
Relevant*
Appendix A
Parameter Summary
Parameter Range / Choices
Factory
Setting
Security
Level**
Page
Update Display Units Deg F / Deg C Deg F Basic 31
Yes Boiler Pump None / On Always / Purge / On Lead None Supervisor Update If Purge, set Pump Prepurge 0 to 600 seconds 15 Supervisor Update Postpurge Delta 0 to 20 F 5 Supervisor
- Inlet Sensor Yes / No Yes Supervisor
- Mixing Valve Yes / No No Supervisor Update Set Time/Date Update Fuel Limit Yes / No No Factory Update Spare Input Off / Sys Pump Feedback / Low Fire Off Supervisor Update Spare Output Off / CAD / Sys Pump BU / Soft Alarm Off Supervisor
Yes DHWP Off / Isolated Demand / Shared Demand Off Basic 32 Yes Remote control
- Remote 1 volts = 60 F to150 F 140 Supervisor
- Remote 9 volts = 150 F to 230 F 220 Supervisor
Yes Remote Sensor No / Display Only / Control No
Yes System Pump Yes / No No Update LWC or CAD Yes / No No Update Alarm Message Low Water level
Yes WWSD
Yes LL Start Trigger 50 to100% of Modulation Rate 90
Yes LL Stop Trigger 0 to 50% of Modulation Rate 25
Yes Boiler On Delay 0 to 900 seconds 5
Yes Boiler Off Delay 0 to 900 seconds 5
Yes %FR On Delay 1 to 30 minutes 20 Factory
Yes %FR Off Delay 1 to 30 minutes 20 Factory
Yes High Fire Limit 40 - 100 % Modulation Rate 100 Supervisor
Yes Deg/Min Hold Off 1 - 10 Degrees / Minute 1 Factory
Yes Cutback Setpoint 100 F - 240 F 220 Factory
Yes Net Start Dwell 16 to 420 Seconds 120 Factory 34
Yes Limit Fault Time 3 to 120 Seconds 5 Factory
Yes Rotation Enable / Disable Disable Basic
Yes Rotation After 8 to720 hours 48 Basic
Yes Outdoor Sensor No / Display Only / Outdoor Reset No Basic
Yes Outdoor Set Up 40 F to 100 F 55 Basic
Yes Boiler Set Up 80 F to 180 F 140 Basic
Yes Outdoor Design - 20 F to 50F 30 Basic
Yes Boiler Design 80 F to 220 F 180 Basic
Parameters identified by “Yes” under the “Network Relevant” column must be configured identically on all boilers.
Unexpected boiler behavior may result if these parameter values differ among boilers on the network. Once communications is established between all boilers in a system, changes to parameters identified as “Yes” or “Update” under the “Network Relevant” column at the keypad of any boiler will update that parameter in all boilers.
** To change your current security level refer to page 46 Security Level operations.
Boiler Configuration Menu
System Configuration Menu
Setup Menu
hour : minute month / day / year
No / Remote SP / Modbus SP /
Remote Mod / Modbus Mod
Off / WWSD of Boiler / WWSD of Sys
Pump / Both
Basic
No Supervisor
Supervisor 32 Supervisor 32 Supervisor 32 Supervisor 32
Off Basic 33
Supervisor 33 Supervisor 33 Supervisor 33 Supervisor 33
31 31 31 31 31 31 31 31 31
32 32
32
33 33 33 33 33
34 34 34 35 35 35 35 35
Sage Boiler Control Instruction Manual Page 50 of 56
Appendix A
Parameter Summary (continued)
Network
Relevant*
Setup Menu (continued)
- Blower Spd High 0 to100 % of full scale 100 Factory
- Blower Spd Low 0 to100 % of full scale 0 Factory
-
Low Fire Spd 0 to100 % Modulation Rate 0 Factory
-
Fan Purge Spd 0 to100 % Modulation Rate 100 Factory
Yes
Yes Post Purge Time 0 to 600 sec 0 Factory
Yes Local PID P 0-10000 20 Supervisor 36
Yes Local PID I 0-10000 30 Supervisor
Yes Local PID D 0-10000 0 Supervisor
Yes Remote PID P 0-10000 20
Yes
Yes
Yes Mixing Valve P 0-10000 15 Supervisor 37
Yes Mixing Valve I 0-10000 40 Supervisor
Yes Mixing Valve D 0-10000 0 Supervisor
Yes Mixing Delta T P 0-10000 15
Yes Mixing Delta T I 0-10000 40
Yes Mixing Delta T D 0-10000 0
Low Fire Hold 0 to 1200 sec 0 Factory
Remote PID I Remote PID D
Parameter Range / Choices
0-10000 30 0-10000 0
Factory
Setting
Security
Level**
Supervisor 36 Supervisor 36 Supervisor 36
Supervisor 37 Supervisor 37 Supervisor 37
Page
34 34 34 34 34 34
36 36
37 37
Setpoint Menu
Yes Operational Setpoint 60 F to 230 F 180 Basic 19
Yes On point 0 F to – 99 F -5 Basic
Yes Off Point 0 F to 99 F 5 Basic
Yes High Temp Stop 60 F to 230 F 200 Basic
Yes DHWP setpoint 140 F to 230 F 180 Basic
Yes WWSD setpoint 40 F 90 F 70 Basic
Yes Max SP 140 F to 230 F 230 Supervisor
Yes Min SP 60 F to 230 F 140 Supervisor
Yes Min BIT 110 F to 235 F 120 Factory Update Min Inlet H2O Temp 110 F to 180 F 130 Supervisor Update Max H2O Delta T 20F to 50 F 50 Supervisor Update Max Delta T Hold 20F to 50 F 40 Supervisor
Communication Menu
- Protocol Peer to Peer / Modbus
- Modbus Address 1-247 1
- Baud Rate 9.6 / 19.2 / 38.4 19.2
- Parity Odd / Even / None None
- Timeout 1 Second to 120 Seconds 30
- Boiler Address 1 to 8 1 Supervisor
Parameters identified by “Yes” under the “Network Relevant” column must be configured identically on all boilers.
Unexpected boiler behavior may result if these parameter values differ among boilers on the network. Once communications is established between all boilers in a system, changes to parameters identified as “Yes” or “Update” under the “Network Relevant” column at the keypad of any boiler will update that parameter in all boilers.
** To change your current security level refer to page 46 Security Level operations.
19 19 19 19 19 19 19 19 19 19 19
Peer to Peer
Supervisor Supervisor 27 Supervisor 27 Supervisor 27 Supervisor 27
27
27
Sage Boiler Control Instruction Manual Page 51 of 56
Appendix B
Customer Parameter Worksheet
Parameter Range / Choices Units
Boiler Configuration Menu Display Units Circle one: Deg F Deg C Boiler Pump Circle one: None On Always Purge On Lead
Pump Prepurge Seconds Postpurge Delta F Inlet Sensor Circle one: Yes No Mixing Valve Circle one: Yes No Spare Input Circle one: Off Low Fire Sys Pump Feedback Spare Output Circle one: Off CAD Soft Alarm Sys Pump BU
System Configuration Menu DHWP Circle one: Off Isolated Demand Shared Demand
Remote control Remote 1 volts = F
Remote 9 volts = F Remote Sensor Circle one: No Display Only Control System Pump Circle one: Yes No LWC or CAD Circle one: Yes No Alarm Message
Circle one: No Remote SP Modbus SP Remote Mod Modbus Mod
Setup Menu
WWSD Circle one: Off WWSD of Boiler WWSD of Sys Pump Both LL Start Trigger LL Stop Trigger Boiler On Delay Seconds Boiler Off Delay Seconds High Fire Limit % Rotation Circle one: Enable Disable Rotation After Hours Outdoor Sensor Circle one: No Display Only Outdoor Reset Outdoor Set Up F Boiler Set Up F Outdoor Design F Boiler Design F Local PID P Local PID I Local PID D Remote PID P
Remote PID I Remote PID D
Mixing Valve P Mixing Valve I Mixing Valve D Mixing Delta T P Mixing Delta T I Mixing Delta T D
% %
Sage Boiler Control Instruction Manual Page 52 of 56
Appendix B
Customer Parameter Worksheet (continued)
Parameter Range / Choices Units
Setpoint Menu
Operational Setpoint F On point F Off Point High Temp Stop DHWP setpoint WWSD setpoint Max SP Min SP Min Inlet H2O Temp Max H2O Delta T Max Delta T Hold
Communication Menu
Protocol Circle one: Peer to Peer Modbus Modbus Address Baud Rate Circle one: 9.6 19.2 38.4
Parity Circle one: Odd Even None Timeout Boiler Address
Seconds
F F F F F F F F F
Sage Boiler Control Instruction Manual Page 53 of 56
SERVICE RECORD
DATE SERVICE PERFORMED
Sage Boiler Control Instruction Manual Page 54 of 56
THIS PAGE LEFT BLANK INTENTIONALLY
Sage Boiler Control Instruction Manual Page 55 of 56
Sage Boiler Control Instruction Manual Page 56 of 56
Loading...