Burnham Sage Boiler Control Specification Sheet

Consulting Engineer
Suggested Specification

Controls For

Multiple Burnham Commercial Cast Iron

Hot Water Boilers

January 26, 2010
Page 1 of 4
Lancaster, Pennsylvania 17605-3939
www.burnhamcommercialcastiron.com
P.O.Box 3939
Phone: 877-567-4328
2.4 Boiler Control System
A Scope of Supply
Supply a Boiler Control System to provide safety interlocks and water temperature control. The control system shall be fully integrated into the burner control cabinet and incorporate single and multiple boiler control logic, inputs, outputs and communication interfaces. The control system shall coordinate the operation of up to eight (8) fully modulating hot water boilers and boiler pumps. The control system shall simply control boiler modulation and on/off outputs based on the boiler water supply temperature and an operator-adjusted setpoint. However, using parameter menu selections, the control system shall allow the boiler to respond to remote system water temperature and outside air temperatures with Domestic Hot Water Priority (DHWP) and Warm Weather Shut Down (WWSD) or Building Automation System (BAS) firing rate demand, remote setpoint or remote start/stop commands.
B Boiler Control
Using PID (proportional-integral-derivative) based control, the remote system water temperature shall be compared with a setpoint to establish a target boiler firing rate. If the secondary loop GPM is greater than the primary loop GPM, firing rate is increased in response to secondary loop temperature decreases. When the remote system temperature is near the boiler high limit temperature, the boiler supply sensor shall limit the maximum boiler supply temperature to prevents boiler High Limit Trips. Alternately, using parameter menu selections, the control system shall allow the boiler to respond to directly to boiler supply temperature and setpoint to establish a target boiler firing rate while remote system water temperature is used for display purposes only. Each boiler’s fuel flow control valve shall be mechanically linked to the air flow control device to assure an air rich fuel/air ratio. All the logic required to ensure that pre-p urge, post -purge, light-off, and burner modulate cycles are automated shall be provided.
C Hot Water Temperature Setpoint
When the controller is in the local control mode, the control system shall establish the setpoint based on outside air temperature and a reset function curve or be manually adjusted by the operator. When enabled, the setpoint shall be adjusted above a preset minimum setpoint upon sensing a domestic hot water demand contact input. When in remote mode, the control system shall accept a Modbus or 4-20mAdc remote setpoint or firing rate demand signal from an external Building Automation System (BAS).
D Multiple Boiler Sequence
Multiple boilers shall be modulated in “Unison” (all at the same firing rate). The control system shall utilize both water temperature and boiler firing rate percent to start and stop the boilers and shall minimize the total number of boilers in operation. The control system shall start and stop boilers when the water temperature is outside the adjustable temperature limit for longer than the adjustable time delay. In order to minimize temperature deviations, the control system shall start and stop the next boiler when the “lead” boiler is at an adjustable firing rate limit for longer than the adjustable time delay. The control system shall monitor both boiler lockout and limit circuits to automatically skip over those boilers that are powered down for maintenance, tripped or otherwise will not start. When rotation is enabled the lead boiler shall automatically rotate every 1 to 168 hours. The boiler shall be run at low fire for warm-up for a preset low fire hold time. When enabled, warm weather shut down control logic shall prevent boiler operation.
E User Interface
A panel front-mounted English language, two line, sixteen character LCD message display shall be provided to display numeric data, startup and shutdown sequence status, alarm, system diagnostic, first-out messages and boiler histor ic al inf orm at ion. Histor ical i nf ormation shall include the last ten lockout and alarm conditions, number of boiler cycles, boiler hours
Page 2 of 4
Loading...
+ 2 hidden pages