Burnham MST396 User Manual

As an
DNAGNITAREPO,NOITALLATSNI
ROFSNOITCURTSNIECIVRES
maetSageM
RELIOBLIOSSAP-3
gnikeesnehW.reilppusliororotcartnocgnitaehruoyllac,reliobotsriaperroecivresroF
gnitaRnonwohssarebmuNlaireSdnarebmuNledoMrelioBedivorp,reliobnonoitamrofni
.reliobehtfopotnodetacollebaL
rebmuNledoMrelioB rebmuNlaireSrelioB etaDnoitallatsnI
TSM
rotcartnoCgnitaeH rebmuNenohP
sserddA
ENERGY STAR® Partner, Burnham Hydronics has determined that the MST288, MST396, MST513 and MST629 meet the ENERGY STAR guidelines for Energy
efciency established by the
United States Environmental Protection Agency (EPA).
®
100618-01R4-5/08
Price - $3.00
IMPORTANT INFORMATION - READ CAREFULLY
All boilers must be installed in accordance with National, State and Local Plumbing, Heating and Electrical Codes and the regulations of the serving utilities. These Codes and Regulations may differ from this instruction manual. Authorities having jurisdiction should be consulted before installations are made. In all cases, reference should be made to the following Standards:
USA BOILERS A. Current Edition of American National Standard ANSI/NFPA 31, “Installation of Oil Burning Equipment”, for recommended installation practices. B. Current Edition of American National Standard ANSI/NFPA 211, “Chimneys, Fireplaces, Vents, and Solid Fuel Burning Appliances”, For Venting requirements. C. Current Edition of American Society of Mechanical Engineers ASME CSD-1, “Controls and Safety Devices for Automatically Fired Boilers”, for assembly and operations of controls and safety devices. D. All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or Local Regulations.
The following terms are used throughout this manual to bring attention to the presence of hazards
of various risk levels, or to important information concerning product life.
DANGER
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
WARNING
Indicates a potentially hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
Indicates a potentially hazardous situation which, if not avoided, may result in moderate or minor injury or property damage.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
CAUTION
NOTICE
NOTICE
This boiler has a limited warranty, a copy of which is printed on the back of this manual. The warranty for this boiler is valid only if the boiler has been installed, maintained and operated in
accordance with these instructions. Surface rust on cast iron sections may be attributed to the manufacturing process as well as condensation
during storage. Surface rust is normal and does not affect the performance or longevity of a boiler.
2
DANGER
DO NOT store or use gasoline or other ammable vapors or liquids in the vicinity of this or any other
appliance.
WARNING
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Failure to follow all instructions in the proper order can cause personal injury or death. Read and understand all instructions, including all those contained in component manufacturers manuals which are provided with the appliance before installing, starting-up, operating, maintaining or servicing this appliance. Keep this manual and literature in legible condition and posted near appliance for reference by owner and service technician.
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained
in this manual. Installation, maintenance, and service must be performed only by an experienced, skilled and knowledgeable
installer or service agency. All heating systems should be designed by competent contractors and only persons knowledgeable in
the layout and installation of hydronic heating systems should attempt installation of any boiler. Installation is not complete unless a safety valve is installed into 1½"" x ¾"" NPT reducing bushing,
mounted into rear section boss, at the back of rear section. See Unit-Pak Boiler Assembly and Steam Boiler Trim & Piping Sections of this manual for details.
It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating properly when the installation is completed.
This boiler is suitable for installation on combustible ooring. Do not install boiler on carpeting.
Do not tamper with or alter the boiler or controls.
Inspect ueways at least once a year - preferably at the start of the heating season. The inside of the combustion chamber, the vent system and boiler ueways should be cleaned if soot or scale has
accumulated. When cleaning this boiler, take precaution to avoid damage to burner swing door insulation. If damaged,
or if there is evidence of previous damage, burner swing door insulation must be replaced immediately. Oil Burner and Controls must be checked at least once a year or as may be necessitated.
Do not operate unit with jumpered or absent controls or safety devices. Do not operate unit if any control, switch, component, or device has been subject to water.
Appliance materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause death or serious injury and which are known to the state of California to cause cancer, birth
defects and other reproductive harm. Always use proper safety clothing, respirators and equipment when
servicing or working nearby the appliance.
3
WARNING
This boiler contains very hot water under high pressure. Do not unscrew any pipe ttings nor attempt
to disconnect any components of this boiler without positively assuring the water is cool and has no
pressure. Always wear protective clothing and equipment when installing, starting up or servicing this
boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the boiler. This boiler contains components which become very hot when the boiler is operating. Do not touch any components unless they are cool.
This boiler must be properly vented. The chimney must be inspected for any obstructions and cleaned
prior to each heating season. A clean and unobstructed chimney ue is necessary to produce the minimum draft required to safely evacuate noxious fumes that could cause personal injury or loss of life. Evidence of loose debris and or condensate induced stains at the base of the chimney ue, connector or smokepipe joints may be signs of condensing ue gases. Flue gas condensate is corrosive, which requires special
consideration and must be addressed immediately. Refer to Section V, "Venting and Air Intake Piping".
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate
combustion and ventilation air. This boiler is supplied with controls which may cause the boiler to shut down and not re-start without
service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
This boiler is designed to burn No. 2 fuel oil only. Do not use gasoline, crankcase drainings, or any oil containing gasoline. Never burn garbage or paper in this boiler. Do not convert to any solid fuel (i.e.
wood, coal). Do not convert to any gaseous fuel (i.e. natural gas, LP). All ammable debris, rags, paper,
wood scraps, etc., should be kept clear of the boiler at all times. Keep the boiler area clean and free of
re hazards. All boilers equipped with burner swing door have a potential hazard which, if ignored, can cause severe
property damage, personal injury or loss of life. Before opening swing door, unplug burner power cord from receptacle located in lower right corner of jacket front panel and turn off service switch to boiler
to prevent accidental ring of burner outside the combustion chamber. Be sure to tighten swing door
fasteners completely when service is completed.
TABLE OF CONTENTS
I. Pre-Installation . . . . . . . . . . . . . . . . . . . . 7 VII. Oil Piping . . . . . . . . . . . . . . . . . . . . . . . 37
II. Unit-Pak Boiler Assy . . . . . . . . . . . . . . . 9 VIII. System Start-Up . . . . . . . . . . . . . . . . . . 39
III. Steam Boiler Trim & Piping . . . . . . . . . . . 22 IX. Maintenance & Service Instructions . . . 45
IV. Tankless & Indirect Water Heater Piping . 24 X. Boiler Cleaning . . . . . . . . . . . . . . . . . . . 48
V. Venting & Air Intake Piping . . . . . . . . . . 27 XI. Trouble Shooting . . . . . . . . . . . . . . . . . 50
VI. Electrical . . . . . . . . . . . . . . . . . . . . . . . . 32 XII. Repair Parts . . . . . . . . . . . . . . . . . . . . . 51
4
Figure 1: MST288 Thru MST629 Steam Boiler with and without Tankless Heater
5
TABLE 1A: DIMENSIONAL DATA (SEE FIGURE 1)
Dimensions (See
Boiler
Figure 1)
Model No.
"A" "B" "C"
MST288 22-5/8" 24" 6" 15.3 14.9 20.29 607 MST396 22-5/8" 24" 6" 15.3 14.9 20.29 607 MST513 28-5/8" 30" 6" 19.7 19.3 27.29 744 MST629 34-5/8" 36" 7" 24.1 23.8 34.29 881
NOTE: 1: Maximum Working Pressure: Steam - 15 PSI
TABLE 1B: RATING DATA
Water Content (To Normal
Water Line) - Gallons
With Tankless
Heater
Non-Heater
Heat Transfer
Surface Area
- sq. Ft.
Actual Shipping
Weight (LB.)
Boiler
Burner Capacity
I=B=R NET
Ratings
Model
No.
MST288 0.75 105 92 69 288 6 8 X 8 15 86.0 MST396 1.05 147 127 95 396 6 8 X 8 15 86.0 MST513 1.35 189 164 123 513 7 8 X 8 15 86.0 MST629 1.65 231 201 151 629 7 8 X 8 15 86.0
GPH MBH
DOE Heating
Capacity MBH
Steam
MBH
Steam Sq. Ft.
Minimum Chimney
Requirements
Round
In. Dia.
Rectangle
In. x In.
Height
Ft.
AFUE
%
6
SECTION I: PRE-INSTALLATION
A. INSPECT SHIPMENT carefully for any signs of
damage.
1. All equipment is carefully manufactured, inspected
and packed. Our responsibility ceases upon delivery of crated boiler to the carrier in good condition.
2. Any claims for damage or shortage in shipment
must be led immediately against the carrier by the
consignee. No claims for variances from, or shortage
in orders, will be allowed by the manufacturer
unless presented within sixty (60) days after receipt of goods.
B. LOCATE BOILER in front of nal position before
removing crate. See Figure 1.
1. LOCATE so that vent pipe connection to chimney
will be short and direct.
2. BOILER IS SUITABLE FOR INSTALLATION
ON COMBUSTIBLE FLOOR. Boiler cannot be
installed on carpeting.
3. FOR BASEMENT INSTALLATION, provide
a solid elevated base, such as concrete, if oor is not level, or if water may be encountered on oor around boiler.
4. PROVIDE RECOMMENDED SERVICE
CLEARANCE, if applicable, as follows:
a. Clearance from Jacket Front Panel -
24" for servicing burner
24" for ueway cleaning (MST288 &
MST396)
30" for ueway cleaning (MST513)
36" for ueway cleaning (MST629)
b. Clearance from Jacket Left Side Panel -
19" for burner swing door, if opened fully with burner mounted, otherwise 1" with burner removed
12" access clearance to service rear of
boiler if right side clearance is less
than 12"
• 1" minimum if right side clearance is 12" or
larger to access and service rear of boiler.
c. Clearance from Jacket Right Side Panel -
6" minimum from external Electrical Enclosure if left side clearance is 12" or
larger to access and service rear of the boiler
24" minimum from rear tanklesss heater (if equipped) for servicing and removal of the heater
d. Clearance from Jacket Rear Panel -
12" minimum for rear smokebox cleaning
(Note: This dimension will also be
controlled by horizontal to vertical to horizontal smokepipe arrangement - See
Figures 2 and 14.)
5. For minimum clearances to combustible materials.
See Figure 2.
Figure 2: Minimum Installation Clearances To Combustible Materials (Inches)
NOTES:
1. Listed clearances comply with American National Standard ANSI/NFPA 31, Installation of Oil Burning Equipment.
2. MegaSteam™ boilers can be installed in rooms with clearances from combustible material as listed above.
Listed clearances cannot be reduced for alcove or closet
installations.
3. For reduced clearances to combustible material, protection must be provided as described in the above ANSI/NFPA 31
standard.
7
NOTICE
Clearance to venting is for single wall vent pipe. If Type L vent is used, clearance may be
reduced to the minimum required by the vent pipe
manufacturer.
C. PROVIDE COMBUSTION AND VENTILATION
AIR. Local and National Codes may apply and should
be referenced.
WARNING
Adequate combustion and ventilation air must
be provided to assure proper combustion and to maintain safe ambient air temperatures.
Do not install boiler where gasoline or other
ammable vapors or liquids, or sources of
hydrocarbons (i.e. bleaches, fabric softeners, etc.) are used or stored.
Do not install boiler in laundry room, or, in
vicinity of clothes dryer to prevent inadequate
air supply to burner and lint contamination of burner air intake openings.
1. Determine volume of space (boiler room). Rooms
communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the space.
Volume(ft3) = Length(ft) x Width(ft) x Height(ft)
2. Determine total input of all appliances in the space. Add inputs of all appliances in the space and round
the result to the nearest 1000 BTU per hour.
3. Determine type of space. Divide Volume by total
input of all appliances in space. If the result is greater than or equal to 50 ft3/1000 BTU per hour, then it is considered an unconned space. If the result is less than 50 ft3/1000 BTU per hour then the space is considered a conned space.
4. For boiler located in an unconned space of a conventionally constructed building, the fresh
air inltration through cracks around windows
and doors normally provides adequate air for
combustion and ventilation.
5. For boiler located in a conned space or an unconned space in a building of unusually tight
construction, provide outdoor air.
a. Outdoor air for combustion may be provided
with an optional Burnham Inlet Air Accessory
Kit, Part Number 611280031 (only available and suitable for use on Beckett AFG with burner enclosure cover burner). See Section V
for installation details.
or
b. Outdoor air may be provided with the use of two
permanent openings which communicate directly
or by duct with the outdoors or spaces (crawl or
attic) freely communicating with the outdoors. Locate one opening within 12 inches of top of space. Locate remaining opening within 12
inches of bottom of space. Minimum dimension of air opening is 3 inches. Size each opening per following:
i. Direct communication with outdoors.
Minimum free area of 1 square inch per 4,000 BTU per hour input of all equipment in space.
ii. Vertical ducts. Minimum free area of 1
square inch per 4,000 BTU per hour input of all equipment in space. Duct cross-sectional
area shall be same as opening free area.
iii. Horizontal ducts. Minimum free area of 1
square inch per 2,000 BTU per hour input of all equipment in space. Duct cross-sectional
area shall be same as opening free area.
Alternate method for boiler located within
conned space. Use indoor air if two
permanent openings communicate directly
with additional space(s) of sufcient volume such that combined volume of all spaces meet criteria for unconned space. Size each
opening for minimum free area of 1 square inch per 1,000 BTU per hour input of all
equipment in spaces, but not less than 100
square inches.
6. Louvers and Grilles of Ventilation Ducts
a. All outside openings should be screened and
louvered. Screens used should not be smaller
than 1/4 inch mesh. Louvers will prevent the entrance of rain and snow.
b. Free area requirements need to consider the
blocking effect of louvers, grilles, or screens
protecting the openings. If the free area of the louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
c. Louvers and grilles must be xed in the open
position, or interlocked with the equipment to open automatically during equipment operation.
8
SECTION II: UNIT-PAK BOILER ASSEMBLY
MegaSteam™ Unit-Pak Boiler Assembly Shipment
Content Check List (see Figure 3)
1. ___ Cast Iron Section/Burner Swing Door/Smoke Box Assembly Mounted on Shipping Skid:
____ MST3 (Rear Section, Heater) – Part # 100566-03 / 100045-01 / 100021-01 ____ MST4 (Rear Section, Heater) – Part # 100566-04 / 100045-01 / 100021-01 ____ MST5 (Rear Section, Heater) – Part # 100566-05 / 100045-02 / 100021-01 ____ MST3 (Rear Section, Non-Heater) – Part # 100567-03 / 100045-01 / 100021-01 ____ MST4 (Rear Section, Non-Heater) – Part # 100567-04 / 100045-01 / 100021-01 ____ MST5 (Rear Section, Non-Heater) – Part # 100567-05 / 100045-02 / 100021-01
2. ___ Control Carton
____ CG450 LWCO; W/Tankless Heater - Part # 100608-01 ____ PS801 LWCO; W/Tankless Heater - Part # 100622-01 ____ #67 LWCO; W/Tankless Heater - Part # 100678-01 ____ CG450 LWCO; L/Tankless Heater - Part # 100680-01 ____ PS801 LWCO; L/Tankless Heater - Part # 100681-01 ____ #67 LWCO; L/Tankless Heater - Part # 100679-01
3. ___ Jacket Carton
____ MST3 – Part # 100609-03 ____ MST4 – Part # 100609-04 ____ MST5 – Part # 100609-05
4. ___ Part Carton
____ MST3 & 4 - Part # 100615-01
____ MST5 - Part # 100629-01
5. ____ Insulation Wrapper
____ MST3 - Part #100614-03 ____ MST4 - Part #100614-04 ____ MST5 - Part #100614-05
6. ___ Instruction/Label Bag
____ MST (All Models) – Part # 100617-01
7. ___ Oil Burner Carton
____ Beckett MST288 – Part # 100625-01 ____ Beckett MST396 – Part # 100053-01 ____ Beckett MST513 – Part # 100054-01 ____ Beckett MST629 – Part # 100055-01
Figure 3: MegaSteam™ Unit-Pak Boiler Shipment Contents (outside container removed)
9
A. CAST IRON SECTION ASSEMBLY TAPPINGS Refer to Table 3 "Purpose of Tappings and Bosses" and
Figure 7.
1. All tappings have factory installed thread protectors.
The thread protectors must be removed prior to
jacket and piping installation.
2. Depending of installation specics and boiler build
ordered, some tappings (front section Optional Front Return, rear section Indirect Heater Supply and
Indirect Heater Limit) may not be used and must be plugged before jacket and piping installation. The appropriate size plugs for above mentioned tappings,
as well as rear section Surface Blowoff and front
section probe type LWCO tappings, are enclosed
into Part Cartons (100615-01 or 100629-01) and Control Cartons (100678-01 and 100679-01), supplied as part of MegaSteam™ Unit-Pak Boiler shipment.
B. REMOVAL OF CAST IRON SECTION/
BURNER SWING DOOR / SMOKE BOX ASSEMBLY FROM SKID.
WARNING
The Cast Iron Section/Burner Swing Door/Smoke Box Assembly has a substantial weight. Insure the travel path to permanent location, as well as mounting surface at boiler permanent location, are structurally sound and rated to handle the boiler weight and water content (refer to Table 1A). Otherwise, a potentially hazardous situation could result in death, serious injury and substantial property damage.
1. Move crated Cast Iron Section/Burner Swing
Door/Smoke Box Assembly and part cartons on the shipping skid as close to nal permanent location as possible.
2. Remove all fasteners at crate skid. Lift outside container. Examine the skid contents for damage due to shipping and handling.
3. Remove Insulation Wrapper, Control Carton, Jacket Carton, Part Carton and Oil Burner Carton from skid and set aside.
4. Instruction/Label Bag is afxed to Section Assembly tie rod. Remove the bag and locate MegaSteam™
Boiler Installation, Operating and Service Instruc­tion manual. READ AND UNDERSTAND ALL INSTRUCTIONS BEFORE ATTEMPTING UNIT HANDLING AND INSTALLATION.
5. The Cast Iron Section/Burner Swing Door/Smoke
Box Assembly is secured to shipping skid with four
lag screws. Remove the screws and discard.
6. For manual Cast Iron Section/Burner Swing Door/
Smoke Box Assembly removal prepare one piece of
4” x 4” x 16” lg. (or two pieces of 2” x 4” x 16” lg.)
and two pieces of 1” Sch. 40 black pipe to be used
as handles. Suggested pipe length for each handle is 72” (3-section); 78” (4-section) and 84” (5-section).
7. Place wooden block(s) 12” from rear of skid as
shown. See Figure 4 “ Boiler Removal from Skid”.
8. Insert 1” Sch. 40 black pipe handles thru leg holes in
front and rear section legs. Center rear pipe ends on
wooden block(s). See Figure 4.
9. For best leverage, the pipe handles should extend 48” minimum beyond front section face.
10. Using the pipe handles, lift the Cast Iron Section/
Burner Swing Door/Smoke Box Assembly until adjustable legs are elevated above the skid deck boards.
11. Remove the skid from underneath the Cast Iron
Section/Burner Swing Door/Smoke Box Assembly.
12. Lower pipe handles until front adjustable legs touch the oor. Place wood blocks under front legs, if required, before lowering, to provide hand clearance.
13. To lower rear of the Cast Iron Section/Burner Swing
Door/Smoke Box Assembly tilt unit slightly forward by pushing on smokebox, or, lift pipes protruding thru rear legs, until wooden block(s) can be removed (see Figure 4). Slowly allow the weight of boiler to tilt backward until rear legs rest on oor.
14. If wood blocks were placed under front legs, lift pipe handles; remove the blocks and lower front legs to oor. Remove pipe handles.
15. Move Cast Iron Section/Burner Swing Door/Smoke
Box Assembly to permanent position by sliding or
walking.
CAUTION
Do not drop boiler when removing from skid and moving to permanent position.
C. PROCEDURE TO OPEN, CLOSE AND
SECURE BURNER SWING DOOR.
Throughout this manual you will be instructed to open
and close Burner Swing Door for various reasons. There is a proper and improper method of closing and securing the door opened for front jacket panel
installation, inspection, cleaning or eld service. Refer
to Figures 5A, 5B, 5C and paragraphs D “Jacket Front Panel Installation”, and, F “Closing/Securing Burner Swing Door” for details.
D. JACKET FRONT PANEL INSTALLATION.
In order to install front jacket panel Burner Swing Door
and door mounting bracket need to be removed. As
shipped, the door would open to the left side.
10
Figure 4: Boiler Removal from Skid
11
1. To open/remove Burner Swing Door (mounted on Cast Iron Section/Burner Swing Door/Smoke Box
Assembly) and door mounting bracket for front jacket panel installation:
a. Loosen but not remove door left side latching
hardware (3/8”-16 x 1-3/4” tap bolt).
b. Loosen and remove door right side latching
hardware (3/8”-16 x 1-3/4” tap bolt and 5/16”
washer) and set aside.
c. Remove door left side latching hardware (3/8”-
16 x 1-3/4” tap bolt and 5/16” washer) and set
aside.
d. Lift the door off mounting bracket and set aside.
e. Remove two 5/16”-18 – ¾” hex head cap screws
securing door mounting bracket to front section
and set aside.
f. Remove door mounting bracket and set aside. g. Note/mark cap screw bosses on front section
left side; locate/mark similar two bosses directly
opposite on front section right side. These four
front section bosses are front jacket panel and door mounting bracket attachment points.
See also Figure 7 “Purpose of Tappings & Bosses”.
2. Open Jacket Carton and locate jacket front panel
(has factory attached 1” berglass insulation). See also “Repair Parts” Section, “Jacket Assembly” illustration for part identication.
3. Open Part Carton, locate Hardware Bag, remove two 5/16”-18 x ½” Phillips pan head machine screws.
4. Place front jacket panel over front section
attachment bosses and align jacket holes with front section boss holes.
5. Firstly, install two 5/16”-18 x ½” Phillips pan head machine screws hand tight to secure front jacket panel right side to casting
6. Secondly, insert 5/16”-18 – ¾” hex head cap
screw thru door mounting bracket upper hole
and upper hole on left side of front jacket panel
simultaneously, and, fasten the bracket and panel to
casting hand tight.
7. Thirdly, insert 5/16”-18 – ¾” hex head cap
screw thru door mounting bracket lower hole
and lower hole on left side of front jacket panel
simultaneously, and, fasten the bracket and panel to
casting hand tight.
8. Finally, tighten both sets of hardware to secure the bracket and front jacket panel.
9. Inspect berglass rope located on the swing door. The rope must be evenly distributed around the perimeter of the door groove and cannot bunch or
overhang. Repair or replace, if the rope is damaged,
or, there is a gap between the rope ends.
10. Inspect burner swing door insulation for damage and
proper type.
By design, for all models, cast bars on front section
between the combustion chamber, and, between the left and right side 2nd and 3rd pass ueways should
make an impression in door insulation to seal the
chambers.
12
Figure 5A: Partial Front View - Burner Swing Door Mounted to Boiler - Fully Closed and Secured
By design, door insulation on model MST629
have two by-pass pockets cast into the insulation centered on the bar between the combustion chamber and 3rd pass ueways. By design, door insulation on models MST288, MST396 & MST513 will not have any by-pass pockets. If insulation is
damaged, or, improper type regarding the pockets, it
must be replaced.
will
11. Upon inspection completion, lift door and place
integral cast hinge pins into door mounting bracket
slotted holes. Do not close and secure door at this
time, proceed to installing stainless steel ueway bafes.
12. Locate/remove four #8 x ½” shoulder sheet metal screws from Hardware Bag, then, install them into
front panel ange holes.
Figure 5B: Top View - Burner Swing Door Mounted to Cast Iron Block Assembly (Jacket Removed for Clarity)
13
Figure 5C: Top View - Burner Swing Door Fully Closed but Not Properly Secured or Sealed
E. FLUEWAY BAFFLE INSTALLATION.
Flueway bafes are enclosed into Part Carton. Bafe
requirements differ by boiler model, see Table 2.
TABLE 2: BAFFLE USAGE
Boiler
Model
MST288 None MST396
P/N 100042-01
MST629
NOTE: Read caution statement before proceeding.
Bafe Usage
2nd Pass 3rd Pass
(2)
NoneMST513
CAUTION
These bafes will generate higher efciencies
and lower stack temperatures. Under certain conditions, a lower gross stack temperature entering the chimney has the potential to be cooled below the dew point and create condensate on interior surfaces. Flue gas
condensate is corrosive, which requires
special consideration and must be addressed immediately.
DO NOT install bafes until you have read Section V, "Venting" completely.
1. To install ueway bafes, provided in miscellaneous
part cartons, as follows, refer to Figure 6 and
Table 2:
14
Models MST396, MST513 and MST629 - To
install ueway bafe in 2nd pass ueway on left side of boiler, hold bafe with word "Left" readable at the top. Slide bafe in ueway until position tab touches ns on right side of 2nd pass ueway. To install ueway bafe in 2nd pass ueway on right side of boiler, hold bafe with word "Right" readable at the top. Slide bafe in ueway until position tab touches ns on left
side of 2nd pass ueway.
F. CLOSING / SECURING BURNER SWING
DOOR.
1. To close and secure Burner Swing Door:
a. From fully open position, rotate the door to the
closed position.
b. Lift door upward into the build-in cast ramp/door
rest (protruding from the bottom of the front
section casting – see Figure 5A).
c. Use one hand to apply pressure directly to the
door to hold it in closed position while re­installing earlier removed door-latching hardware
(3/8”-16 x 1-3/4” tap bolt and 5/16” washer).
Prior to re-installation, apply a drop of supplied
Anti-seize (pouch provided in Part Carton) to both tap bolts for rust protection and to facilitate easy removal, if burner door is to be open for
inspection and service. ALWAYS INSTALL RIGHT SIDE LATCHING HARDWARE FIRST, THEN INSTALL EARLIER REMOVED LEFT SIDE HINGE HARDWARE (3/8”-16 X 1-3/4” TAP BOLT AND 5/16” WASHER) SECOND. Apply additional pressure while hand tightening
the hardware as far as possible and then release
the pressure.
Figure 6: Flueway Bafe Positioning/Orientation in
Flueways
NOTICE
When securing burner swing door make sure door
is drawn-in equally on both sides.
d. Use a hand or socket wrench to tighten door
hardware. ALWAYS START WITH RIGHT SIDE TAP BOLT FIRST. Use an alternating
tightening method from right side tap bolt to left side tap bolt to tighten door equally, until
sealed, without applying excessive torque. NEVER TIGHTEN LEFT SIDE TAP BOLT FIRST, OR, EITHER PIECE OF HARDWARE 100% WITHOUT USING THE ALTERNATING METHOD DESCRIBED ABOVE. See Figure 5B.
e. Failure to follow the prescribed procedure could
cause thread damage to casting and /or leak at the door seal. IF LEFT SIDE TAP BOLT IS TIGHTENED BEFORE RIGHT SIDE TAP BOLT, RIGHT SIDE OF THE DOOR CAN NOT BE DRAWN-IN TO PROVIDE AN AIR­TIGHT SEAL, as shown in Figure 5C. Applying excessive torque will only cause thread damage.
G. JACKET REAR PANEL INSTALLATION.
1. Locate jacket rear panel (has factory attached 3”
berglass insulation) inside Jacket Carton. See also “Repair Parts” Section, “Jacket Assembly” illustration for part identication.
2. Locate and remove from Hardware Bag rear panel mounting hardware – (2 pcs) 5/16”-18 x 3” lg. tap studs, (2 pcs) 5/16”-18 plated acorn nuts, (2 pcs) 5/8” x 2-9/32” round spacers and (2 pcs) 5/16”-18 x ½” Phillips pan head machine screws.
3. Locate rear panel two lower attachment bosses on rear section. See Figure 7 “Purpose of Tappings &
Bosses”.
4. Thread both 5/16”-18 x 3” lg. tap studs, with short threaded end, into lower attachment bosses on rear
section.
5. Install both 5/8” x 2-9/32” round spacers over tap
studs.
6. Place rear jacket panel over rear section, so both
tap studs clear thru lower panel holes, rear section cleanout openings clear thru matching panel cutouts
and brass sample port plug clears panel matching
hole.
7. Secure panel bottom to studs with acorn nuts hand
tight.
8. Align upper panel attachment holes with smokebox upper attachment bosses and install 5/16”-18 x ½”
Phillips pan head machine screws hand tight.
9. Securely tighten rear jacket panel mounting hardware.
10. Locate/remove four #8 x ½” shoulder sheet metal screws from Hardware Bag, then, install them into
rear panel ange holes.
H. FLUE CLEANOUT COVERS AND SMOKEBOX
COLLAR INSTALLATION.
1. Remove two cast iron Cleanout Covers, cast iron
Smokebox Collar and the tube of hi-temperature
silicon adhesive sealant from Part Carton. See also
“Repair Parts” Section, “Bare Boiler Assembly” illustration for part identication.
2. Check the rope gasket factory attached to the covers. Repair or replace, if the rope is damaged, or, there is
a gap between the rope ends.
3. Locate/remove four 5/16”-18 – 7/8” hex head cap screws from Hardware Bag.
4. Apply a drop of supplied Anti-seize (pouch provided
in Part Carton) to each of four (4) 5/16”-18 x 7/8” hex head cap screws for rust protection and to facilitate easy removal for future service.
5. Position left Cleanout Cover over rear section
cleanout opening, align section boss holes with Cleanout Cover holes, install both 5/16”-18 – 7/8”
hex head cap screws hand tight, then, alternately tighten them with open end or socket wrench.
15
Figure 7: Purpose of Tappings and Bosses
TABLE 3: PURPOSE OF TAPPINGS & BOSSES
Tapping
Location
A ¼" - 18 Pressure Gauge B ¼" - 18 Pressure Limit
C ¾" - 14
D ½" - 14
E 2" - 11½" Supply (Front & Rear Tappings) F ¾" - 14 Safety Valve G 1½" - 11½ Condensate Return H 1¼" - 11½ Optional Front Return J 1½" - 11½ Surface Blowoff (Plugged) K 1" - 11½ Indirect Water Heater Supply L ½" - 14 Indirect Water Heater Limit
Q ¼" - 18 Smokebox Pressure Tapping
R ½"-14
Size, NPT Boss Location
M (4 pcs) 5/16" - 18
N (2 pcs)
P (10 pcs) 5/16" - 18
Thread Size
UNC
3/8" - 16 Burner Swing Door
Less Heater
Water Gauge Glass (Probe LWCO)
Water Gauge Glass, Pressuretrol &
Jacket Front Panel, Burner Swing
Jacket Rear Panel, Smoke Box Collar,
Operating
Steam Boiler
With Heater
Probe LWCO - Std.
Plugged (Float LWO)
LWCO (Float LWCO)
Door Mounting Bracket
Cleanout Covers
L4006
Control
Plugged
16
6. Repeat above steps with right Cleanout Cover.
7. Apply the adhesive sealant to the underside of the collar, all around, at the inside corner of the collar
outer ring. Insure adhesive bead is complete all
around and without gaps.
8. Place the collar over smokebox tongue and align collar integral mounting ear slots with smokebox bosses.
9. Thread-in both 5/16”-18 – 7/8” hex head cap screws
hand tight, then, alternately tighten them with open end or socket wrench.
I. INSULATION WRAPPER AND BURNER
POWER OUTLET RECEPTACLE WITH HARNESS INSTALLATION.
1. Insulation Wrapper is vacuum packed/sealed in
plastic bag at the factory.
2. Carefully cut the plastic bag and remove Insulation
Wrapper. The wrapper will expand upon removal.
3. Unfold Insulation Wrapper, position it over section
assembly centered left to right and align two
wrapper upper holes with 2" NPT pipe tappings in front and rear section top.
4. Insure wrapper ts snugly around rear section tankless heater collar/ mounting ange (if boiler
is equipped with tankless heater) and trim the insulation at tankless heater cutout. Do not trim off
insulation on boilers having non-heater rear section.
5. Tack Insulation Wrapper bottom ends under section assembly, between front and rear section legs.
6. Locate and remove Burner Power Outlet Receptacle with factory attached Burner Harness from Control Carton.
7. Feed Molex end of Burner Harness thru front jacket panel right side outlet receptacle cutout. Insure that the receptacle middle prong opening is facing down. Snap the receptacle into front jacket panel. Temporarily, stuff Molex end of Burner Harness
between front panel insulation and insulation wrapper near boiler top.
J. SIDE AND TOP JACKET PANEL
INSTALLATION.
1. Pick up Left Side Jacket Panel from Jacket Carton.
See also “Repair Parts” Section, “Jacket Assembly” illustration for part identication.
2. Place Left Side Jacket Panel over four #8 x ½” shoulder sheet metal screws, earlier installed at
Front and Rear Jacket Panel side anges, so teardrop cutouts in the side panel inside anges engage all
four screws simultaneously.
3. Slide the panel downwards to lock all screws securely.
4. Pick up Right Side Jacket Panel from Jacket Carton.
See also “Repair Parts” Section, “Jacket Assembly” illustration for part identication.
5. Pick up Molex end of Burner Harness stuffed
between front panel insulation and insulation
wrapper and feed it thru Right Side Jacket Panel front cutout, letting the harness connector to hang over the cutout edge temporarily.
6. Place Right Side Jacket Panel, clearing rear section
tankless heater collar/ mounting ange, over four
#8 x ½” shoulder sheet metal screws, previously
installed at Front and Rear Jacket Panel side anges, so teardrop cutouts in the side panel inside anges
engage all four screws simultaneously.
7. Slide the panel downwards to lock all screws securely.
8. Pick up Top Jacket Panel from Jacket Carton.
9. Place the panel between side panels upper inside anges and slide it forward, until top panel front ange U-bend locks over front panel top ange, and, top panel rear ange is positioned over rear jacket
panel.
10. Locate/remove two #8 x ½” sheet metal screws from Hardware Bag.
11. Install both screws into top panel rear ange to
secure the top panel to rear jacket panel.
K. EXTERNAL ELECTRICAL ENCLOSURE
MOUNTING.
1. Remove two #8 x ½” shoulder sheet metal screws and one #8 x ½” sheet metal screw from Hardware Bag.
2. Install both #8 x ½” shoulder sheet metal screws
into Right Side Jacket Panel, at two upper corners of the panel front cutout.
3. Locate and remove External Electrical Enclosure
assembly from Control Carton.
4. Remove the enclosure cover and set aside.
5. Pick Molex connector end of Burner Harness and
feed it inside the enclosure, thru bushed hole at
enclosure lower left corner, next to transformer/ relay.
6. Place the enclosure over installed shoulder sheet metal screws, so teardrop cutouts in the enclosure
base engage both screws simultaneously, then, slide
the enclosure downwards to lock it in place.
7. Install #8 x ½” sheet metal screw thru enclosure
base lower hole, located to the right of transformer/
relay, into right side panel to secure the enclosure.
8. Plug-in burner harness Molex connector into dedicated burner harness receptacle inside the
enclosure (lower left off transformer/relay). See “
Control Plug-In Diagram” label attached to inside of
the enclosure cover for details.
9. Do not install the enclosure cover yet; proceed to control installation.
17
L. TRIM AND CONTROLS INSTALLATION.
Pressure Limit Installation.
1. Locate and remove L404F Pressure Limit with factory attached harness from Control Carton.
2. Locate and remove 1/4" NPT x 1-7/8" x 4 x 90° syphon enclosed in Part Carton.
3. Review and locate pressure limit tapping on front
section. See Table 3 “ Purpose of Tappings &
Bosses” and Figure 7.
4. Thread 1-7/8" lg. syphon-threaded short end into
the bottom of Pressure Limit with factory attached harness. Do not tighten the syphon by holding the limit case; apply a wrench to the brass hex below
the case.
5. Thread ¼" NPT x 4" lg. syphon-threaded long end into pressure limit tapping on front section. See Figure 8 "Pressure Limit Installation.
6. L404F pressure limit does not require leveling. The
pressure limit nal orientation must be parallel to boiler front, having the harness on the right side.
7. Pick-up the pressure limit harness Molex end and
feed it into the enclosure, thru top ange rear left
7/8” hole; then, snap-in harness BX connector into the hole, and, plug Molex connector into dedicated pressure limit receptacle inside the enclosure (upper left off transformer/relay). See “ Control Plug-In
Diagram” label attached to inside of the enclosure
cover for details.
2. Install the probe into the appropriate front section tapping. See Figure 7 “Purpose of Tappings &
Bosses”.
3. Slip LWCO with factory attached harness over the
probe and clamp in place. Note that CG450 LWCO will be positioned right side up, with diagnostic LED(s) on the top ange, while PS801 LWCO will be positioned upside down, with diagnostic LED(s) on the bottom ange. Connect the wire(s) between the probe and control per manufacturer’s
instructions.
4. Pick-up the LWCO harness Molex end and feed it into the enclosure, thru external electrical enclosure
top ange front left 7/8” hole; then, snap-in harness
BX connector into the hole, and, plug-in Molex connector into dedicated LWCO receptacle inside the enclosure (middle left off transformer/relay). See
“ Control Plug-In Diagram” label attached to inside
of the enclosure cover for details.
N. PRESSURE GAUGE AND GAUGE GLASS
INSTALLATION.
1. Remove the 6” water gauge glass set from Part Carton.
2. Install the gauge glass using the two ½” NPT
tappings to the right of the probe LWCO. See Figure 7 “Purpose of Tappings & Bosses”.
3. Thread the pressure gauge into 1/4” NPT tapping of the front section. See Figure 7 “Purpose of Tappings
& Bosses”. Tighten with wrench applied to the
square shank of the gauge.
Figure 8: Pressure Limit Installation
M. PROBE LWCO (HYDROLEVEL CG450,
OR, MCDONNELL-MILLER PS801-120) INSTALLATION.
1. Remove either Hydrolevel CG450 LWCO with
factory attached harness and Hydrolevel probe
#EL1214, or, McDonnell-Miller PS801-120 with
factory attached harness and #153875 probe from
Control Carton.
CAUTION
Do not apply pressure to gauge case, as this may result in inaccurate readings.
O. FLOAT LWCO (MCDONNELL-MILLER #67),
AND GAUGE GLASS INSTALLATION.
1. Pre-assemble oat-type LWCO per Figure 9 "Float-
Type LWCO and Gauge Glass Installation".
2. Install two ½” NPT x 2½" long Sch 40 brass nipples,
supplied loose inside Control Carton (disregard two
½" NPT x 1½" long brass nipples provided with #67 LWCO package) and ½" NPT brass unions into upper and lower front section tappings. See Table 3 "Purpose of Tappings & Bosses" and Figure 7.
3. Install water gauge glass on low water cut-off
assembly tee ttings.
4. Do not remove ¼” NPT plug factory installed on top of #67 LWCO.
5. Insure that 3/8" NPT plug (provided within #67
LWCO package) is installed at bottom of #67
LWCO.
6. Remove #67 LWCO J-box cover.
18
Figure 9: Float-Type LWCO and Pressure Limit Installation
19
7. Screw LWCO to External Wiring Enclosure wiring harness (end with fork and female disconnect
terminals) connector into low water cut-off J-box top tting, and attach wires to the terminals per
LWCO wiring detail shown in Figure 9 "Float-Type LWCO and Gauge Glass Installation".
8. Re-install #67 LWCO J-box cover.
9. Pick-up the LWCO harness Molex end and feed it into the enclosure, thru external electrical enclosure
top ange front left 7/8” hole; then, snap-in harness
BX connector into the hole, and, plug-in Molex connector into dedicated LWCO receptacle inside the enclosure (middle left off transformer/relay). See
“ Control Plug-In Diagram” label attached to inside
of the enclosure cover for details.
10. Pick-up the pressure limit harness Molex end and feed it into the enclosure, thru External
Electrical Enclosure top ange rear left 7/8” hole;
then, snap-in harness BX connector into the hole, and, plug-in Molex connector into dedicated pressure limit receptacle inside the enclosure (upper left off transformer/relay). See “ Control Plug-In Diagram”
label attached to inside of the enclosure cover for
details.
P. AQUASTAT CONTROLLER INSTALLATION
(BOILERS WITH TANKLESS HEATER ONLY).
1. On boilers with tankless heater, install the L4006A
aquastat controller well (found in Part Carton) into ½” NPT tapping in tankless heater plate.
2. Remove the L4006A aquastat controller with factory attached harness from Control Carton.
3. Slip the bulb of the aquastat controller into the well
and secure the controller in place with the set screw.
WARNING
Aquastat bulb must be fully inserted into the
well.
4. Feed the L4006A aquastat controller harness end
thru external electrical enclosure top ange middle right bushed hole. See “ Control Plug-In Diagram” label attached to inside of the enclosure cover for
details.
5. See Figures 18, 19 and 20 (whichever applicable)
for tankless heater aquastat connection details.
6. Using needle nose pliers form hook on harness each stripped end and wrap hooks around screws under terminals "R" and "G" of the R8285C Transformer­Relay; then, tighten screws securely.
Q. SAFETY VALVE AND DRAIN VALVE
INSTALLATION.
1. Remove safety valve and related piping (3/4”
NPT x 3” lg. black nipple, 3/4” NPT x 8” lg. black
nipple, ¾” NPT 90° black elbow and ¾” NPT black
coupling) from Part Carton.
2. Thread 3/4" NPT x 3” lg. black nipple into rear
section safety valve tapping, install ¾” NPT 90°
black elbow facing upward, then, thread 3/4" NPT x 8” lg. black nipple into the elbow, and, install ¾” NPT black coupling onto nipple end.
3. Thread safety valve into the ¾” NPT black coupling.
Pipe the safety valve discharge as shown in Figure 11 “ Recommended Boiler Piping For Gravity Return Steam Boiler” shown in Section III of this
manual. Installation of the safety valve must be
consistent with ANSI/ASME Boiler and Pressure Vessel Code, Section IV.
WARNING
Safety valve discharge piping must be piped near
oor to eliminate potential of severe burns. Do
not pipe in any area where freezing could occur. Do not install any shut-off valves, plugs or caps.
4. Remove 1-1/2" NPT x 5” lg. black nipple, 1-1/2” x 1-1/2” x ¾” NPT black tee and drain valve from
Part Carton.
NOTICE
Lower rear section Tapping "H" is used for standard condensate return on steam boilers.
5. Thread 1-1/2" NPT x 5” lg. black nipple into lower
rear section tapping, then, install 1-1/2” x 1-1/2” x
¾” NPT black tee onto nipple end. Black tee side outlet may be oriented to either left, or, right side.
6. Install the drain valve into black tee ¾” NPT side
outlet.
R. OIL BURNER INSTALLATION.
1. Install oil burner, refer to Figure 10. a. Open burner carton and remove contents. b. Check oil nozzle in burner for size, angle and
type, inspect electrode settings, check head
setting, check air band and air shutter settings, refer to Table 8 at rear of this manual.
c. Place oil burner gasket on burner and align holes.
CAUTION
Do not install burner without gasket.
d. Remove three (3) 5/16-18 x 3/4 lg. cap screw
from burner swing door used for mounting burner.
e. Thread (1) 5/16-18 x 3/4 lg. cap screw,
approximately three (3) full turns, into tapping
located at 12:00 o'clock on burner swing door.
20
Loading...
+ 44 hidden pages