Burnham HF SERIES, HF-98, HF-122, HF-147, HF-173 Operating/service Instructions Manual

Price - $3.00
INSTALLATION, OPERATING AND
SERVICE INSTRUCTIONS FOR
HF SERIES OIL FIRED BOILER
BEFORE INSTALLATION: READ THIS MANUAL
SAVE THESE INSTRUCTIONS
For service or repairs to boiler, call your heating contractor. When seeking information on boiler, provide Boiler Model Number and Serial N umber as shown on Rating Label.
Boiler Model Number Boiler Serial Number Installation Date
HF ____-____
Heating C ontractor Phone Number
Address
8143709R3-12/99
6_ _ _ _ _ _ _
1
IMPORTANT INFORMATION - READ CAREFULLY
All boilers must be installed in accorda nce with National, State and Local Plumbing, Heating and E lectrical Codes and the regu lations of the servi ng utilities. These C odes and Regulations may diffe r from this instruction manual. Authorities having jurisdiction should be consulted before install ations are made. In all cases, reference sh ould be m ade to the followi ng Standards: All wiring on boil ers installed in the U SA shall be made in accor dance with the N ational Electrical Cod e and/or Lo cal Regulations.
USA BOILERS
C urrent Editio n of American Na t iona l Standard ANSI/NFPA 31, “Installa t ion o f Oil Burni ng
A.
Equipment”, for r ecomm en ded installation practices. Current Edition of American National Standard ANSI/NFPA 211, “Chimneys, Fireplaces,
B.
Vents, and Solid Fuel Burning Appliances”, For Venting requirements.
C.
Current Edition of Amer ican Society of Mechanical Engineers ASME CSD-1, "Con trols and Safety Devices for Automatically Fired Boilers", for assembly and operations of controls and safety devices.
CA NAD IAN B OILERS
Current Edition of Canadian Stand ards Association CSA B139, "Installation Code of Oil
A.
Burning Equipment", for recomm en ded installation practices.
The following terms are used throughout this manual to bring attention to the presence of hazards of various risk levels, or to important information concerning product life.
DANGER
Indicates an imm in ently hazardou s situation w hic h, if n ot av oid ed, w ill re su lt in d eath , serious injury or substantial property damage.
WA R N I NG
Indic ates a potentially hazardous situation which, if not avoided, could re sult in death, serious injury or substantial property damage.
Indic ates a potentially hazardous situation which, if not av oided, may resu lt in modera te or minor injury or property damage.
Indicates special instructions on installation, operation, or m aintenance which are importa nt but not related to personal injury hazards.
CAU TION
NOTICE
Th is boiler has a limited w a rra nty, a c o py o f which is printe d on t he back of t his m a nua l. It is the respons ibility of the in stalling cont ractor to see th at all controls are correctly in stalled and a re oper a t ing p rop e rly when the ins tallatio n is co mplete. The war ran ty fo r t his boiler is v a lid only if the boiler h as been installed, maintained and operated in accordance with these instructions.
NOTICE
2
DA NGER
DO NOT store or use gasoline or other flammable vapors or liquids in the vicinity of this or any other appliance.
WAR NING
Impro per installation, ad justment, alteration, servic e or mainte na nce can cause p roperty damage, personal injury or loss of life. Fai lure to follow all instructions in the proper order can cause personal i njury or death. Read and understand all instructions, inc luding all those con tained in compone nt manufac turers manuals w hich are p rovided with th e appliance before installing, starting-up, operating, maintaining or servicing this applia nce. Keep this manual and literature in legible condition and posted near appliance for reference by owner an d service technic ian.
This boiler requires regular maintenance and service to operate safely. Fo llow the instructions contained in this manual. Installation, maintenance, and service must be performed only by an experienced, skilled and knowledgeable installer or service agency. All heating systems should be designed by competent contractors and only persons knowledgeable in the layout and installation of hydronic heating systems should attempt installation of any boiler. It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating properly when the installation is completed. Installation is not complete unless a pressure relief valve is installed into the tapping located on top of app liance - See Section III of this ma nual for details.
This boiler is not su itable for installation o n c ombusti ble flooring, unless install ed with a comb ustible floor shield (avai lable at extra cost). Do n ot install boiler on carpeting .
Do not tam per with or alter the boiler or controls. Re tain your contractor or a compet ent se rv ice man to assur e th at th e unit is p ro perly adjus ted an d m ain tained . Have Firetu be s cleane d at l eas t once a ye ar - prefe rab ly at th e star t o f the he ating sea son to remove soot and scale. The inside of combustion cha mber should also be cle aned and ins pecte d at the same time . Have Oil B urn er and Contro ls ch ecke d at l eas t once a ye ar or as may be n ecess itate d. Do not operate unit with jumpered or abs ent controls or safety devices. Do no t operate unit if any control, switch, c omponent, or device has been subject to water.
3
WARNING
Appliance materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause death or serious injury and which are known to the state of California to cause cancer, birth d efects and other reproductive harm. Always use pro per safety clothing, respirators and equipment when servicing or wor king nearby the appliance.
This boiler contains very hot water under high p ressures. Do not unscrew any pipe fittings nor attempt to disconnect any comp onents of this boil er without positively assuring the water is cool and has no pressure. Always wear protective clothing and equipment when installing, starting up or servicing this boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the temper ature and pressure of the b oiler. This boiler contains components w hich become very hot when the boiler is operating. D o not touch any components unless they are cool. This appliance must be properly vented and connected to an approved vent system in good condition. Do not ope rate boiler with the absence of an unapproved ve nt system. This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air. The interior of the venting and air intake systems must b e inspected and cleaned before the start of the heating season and should be inspected periodically throughout the heating season for any obstructions. Clean and unobstructed venting and air intake systems are necessary to allow noxious fumes that could cause injury or loss of life to vent safely and will con tribute toward maintaining th e boiler's efficiency. This boiler is supplied with controls which may cause the boiler to shut down and not re-start withou t service. If dam age du e to frozen pipe s is a pos sibility, the he ating system should not be left unatttend ed in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative. This boiler is designed to b urn No. 2 fuel oil only. D o not use gasoline, crankcase drai nings, or any oil containing gasoline. Never burn garbage or paper in this boiler. Do not convert to any solid fuel (i. e. wood, co al) or gaseous fuel (i. e. natu ral gas, LP/propane). All flam mable debris, rags, paper, wood scraps, etc., should be kept clear of the boiler at all times. Keep the boiler area clean and free of fire hazards.
Do not operate boiler on combustible floor without a factory supplied floor shield. Concrete over wood joists is considered combustible flooring. Do not operate on masonry floors, which may contain moisture.
T ables of Contents
I. General Information ............................. 5
II. Installation Instructions ......................... 8
III. System Start-Up ................................... 18
I V . Service and Cleaning............................ 23
V . Repair Parts .......................................... 2 4
4
I: General Information
Figure 1: HF Packaged Boiler (HF-98/HF-173)
Table 1:
Description HF-98 HF-122 HF-147 HF-173 DOE Heating Capacity (MB H) 104 132 154 184
IBR Net Water rating (MBH) 90 115 134 160 Firing Rate (gal/hr) .85 1.10 1.25 1.50 Nozzle Spec ification .75 x 45° B .90 x 45° B 1.00 x 45° B 1.25 x 45° B Stac k D ia me te r (inc h) 6 6 7 7 Nu mber of Tub es 12 12 18 18 Boiler Water Cap. (gal.) 20 20 40 40 Supply S i ze ( F PT) 2 2 Return S ize (FPT) 2 2 Tankless Heater Size (gal/min) 4 (5 Optional) 4 (5 Optiona l) 5 5 Chimney Size (min) 8" x 8" x 15' 8" x 8" x 15' 8" x 8" x 15' 8" x 8" x 15' Approx. Shipping Wt. ( lb.) 450 450 720 720
DIMENSIONS Max. Working Pressure: 30 PSI (Water Only)
A O verall Width (in.) 18-1/8 18-1/8 24 24 B O verall Length Boiler (in.) 24-1/2 24-1/2 31-3/4 31-3/4 C Jacket Height ( in.) 37-3/4 37-3/4 46-3/4 46-3/4 D J acket Length (in.) 18 18 21-3/4 21-3/4 E Jacket Width ( in.) 18-1/8 18-1/8 22 22 F S moke Outlet Height (in.) 25-1/4 25-1/4 30 30 G Overall Leng th w/Burner (in.) 33 33 39 39
WATER RAT INGS AND S PECIFICATIONS
1.
Notes:
Firing rates based on 140,000 BTU per gallon of oil
2.
IBR net wa t e r r at in gs ba s ed o n a pi c k -up al lo wan c e of 1. 15
3.
Manufacturer should be consulted before selecting a boiler for installations having unusual piping and pick-up requirements.
4.
Firebox d raft setting: -.02 in ches w ater column
5.
Ratings based on 13.0% CO
2
5
A. INSPECT SHIPMENT carefully for any signs of damage.
1 . ALL EQUIPMENT is carefully manufactured,
inspected and packed. Our responsibility ceases upon delivery of the crated boiler to the carrier in good condition.
2. ANY CLAIMS for damage or shortage of shipment must filed immediately against the carrier by the consignee. No claims for variances from, or shortage in orders, will be allowed by the manufac­turer unless presented within sixty (60) days after receipt of goods.
B. LOCATE BOILER in front of final position before
removing crate.
1. LOCATE so that smoke pipe connection to chim­ney will be short and direct. BOILER IS NOT SUITABLE FOR INSTALLATION ON COMBUS­TIBLE FLOOR unless combustible floor shield, supplied by Burnham, is used. DO NOT install on carpeting.
2. FOR BASEMENT INSTALLATION, provide a concrete base if floor is not perfectly level, or if water may be encountered on floor around boiler.
3. PROVIDE SERVICE CLEARANCE of at least 48” from the front of the jacket for servicing of burner and removal of tankless heater.
For minimum clearances to combustible materials. See Figure 2.
Figure 2: Minimum Clearances to Combustible Materials
NOTE:
1. Listed clearances comply with American National Standard ANSI/NFPA 31, Installation of Oil Burning Equipment.
2. HF boilers can be installed in rooms with clearances from combustible material as listed above. Listed clearances can not be reduced for alcove or closet installations.
3. For reduced clearances to combustible material, protection must be provided as described in the above ANSI/NFPA 31 standard.
6
C. PROVIDE AIR SUPPLY AND VENTILATION to
accommodate proper combustion. If natural ventilation is inadequate, provide a screened opening or duct from the boiler room to the outside. The opening or duct must be sized so the boiler input will not exceed 4,000 BTUH/Sq. In. of free area. If other air consuming appliances are near the boiler, the air inlet should be larger. Consult respective manufacturers.
D. VENTILATION AIR must be provided to maintain the
ambient temperature at safe limits. Local and national codes may apply and should be referenced.
1. In unconfined spaces (basement) in buildings of conventional frame, brick, or stone construction, infiltration normally is adequate to provide air for ventilation.
2. In confined spaces, two permanent openings, one near the top of the enclosure and one near the bottom, shall be provided. Each opening shall have a free area of not less than 1 sq. inch per 1000 BTUH of the total input of all appliances in the space.
E. PROVIDE COMBUSTION AND VENTILATION AIR.
Local code provisions may apply and should be referenced.
WARNING
Adequate combustion and ventilation air must be provided to assure proper combustion.
1 . Determine volume of space (boiler room). Rooms
communicating directly with the space in which the appliances are installed, through openings not furnished with doors, are considered a part of the space.
Volume(ft3) = Length(ft) x Width(ft) x Height(ft)
2 . Determine total input of all appliances in the space.
Add inputs of all appliances in the space and round the result to the nearest 1000 BTU per hour.
3 . Determine type of space. Divide Volume by total
input of all appliances in space. If the result is greater than or equal to 50 ft3/1000 BTU per hour,
then it is considered an unconfined space. If the result is less than 50 ft3/1000 BTU per hour then the space is considered a confined space.
4 . For boiler located in an unconfined space of a
conventionally constructed building, the fresh air infiltration through cracks around windows and doors normally provides adequate air for combus­tion and ventilation.
5 . For boiler located in a confined space or an uncon-
fined space in a building of unusually tight con­struction, provide outdoor air with the use of two permanent openings which communicate directly or by duct with the outdoors or spaces (crawl or attic) freely communicating with the outdoors. Locate one opening within 12 inches of top of space. Locate remaining opening within 12 inches of bottom of space. Minimum dimension of air opening is 3 inches. Size each opening per following:
a. Direct communication with outdoors. Minimum
free area of 1 square inch per 4,000 BTU per hour input of all equipment in space.
b. Vertical ducts. Minimum free area of 1 square
inch per 4,000 BTU per hour input of all equip­ment in space. Duct cross-sectional area shall be same as opening free area.
c. Horizontal ducts. Minimum free area of 1 square
inch per 2,000 BTU per hour input of all equip­ment in space. Duct cross-sectional area shall be same as opening free area.
Alternate method for boiler located within confined space. Use indoor air if two permanent
openings communicate directly with additional space(s) of sufficient volume such that combined volume of all spaces meet criteria for unconfined space. Size each opening for minimum free area of 1 square inch per 1,000 BTU per hour input of all equipment in spaces, but not less than 100 square inches.
6 . Louvers and Grilles of Ventilation Ducts
a. All outside openings should be screened and
louvered. Screens used should not be smaller than 1/4 inch mesh. Louvers will prevent the entrance of rain and snow.
b. Free area requirements need to consider the
blocking effect of louvers, grilles, or screens protecting the openings. If the free area of the louver or grille is not known, assume wood louvers have 20-25 percent free area and metal louvers and grilles have 60-75 percent free area.
c. Louvers and grilles must be fixed in the open
position, or interlocked with the equipment to open automatically during equipment operation.
7
II. Installation Instructions
WARNING
Failure to properly pipe boiler ma y result in improper operation and d amage to boiler or structu re .
Oxyg en c ont amin atio n of boile r wa te r will c ause c orrosio n o f iro n an d st eel bo iler components, a nd c an lead to boiler failure. Burnham's Standard Warranty does not cover problems caused by o xygen contam ination of boiler wa ter or scale (lime) bu ild-up caused by frequent addition of water.
A. Design a piping system and install boiler which will
prevent oxygen contamination of boiler water and frequent water additions.
1. There are many possible causes of oxygen contami­nation such as:
a. Addition of excessive make-up water as a result
of system leaks. b. Absorption through open tanks and fittings. c. Oxygen permeable materials in the distribution
system.
2. In order to insure long product life, oxygen sources should be eliminated. This can be accomplished by taking the following measures:
a. Repairing system leaks to eliminate the need for
addition of make-up water. b. Eliminating open tanks from the system. c. Eliminating and/or repairing fittings which
allow oxygen absorption. d. Use of non-permeable materials in the distribu-
tion system. e. Isolating the boiler from the system water by
installing a heat exchanger.
WARN ING
System supply and return piping must be conn ected to corr ect boiler pipe.
Burnham recommends sizing the s ystem circulator to su pply sufficient flow (GPM) to allow a 20°F temper ature diff eren tial i n the s ys tem . When s izing the system circu lator, the pressu re drop of all radiators, baseboard and radiant tubing and all connecting piping must be considered.
3. Connect System supply and return piping to boiler. See Figures 8 and 9. Also, consult I=B=R Installa­tion and Piping Guides. Maintain minimum ½ inch
clearance from hot water piping to combustible materials.
a. If this boiler is used in connection with refrig-
eration systems, the boiler must be installed so that the chilled medium is piped in parallel with the heating boiler using appropriate valves to prevent the chilled medium from entering the boiler. See Figure 3. Also, consult I=B=R Installation and Piping Guides.
b. If this boiler is connected to heating coils
located in air handling units where they may be exposed to refrigerated air, the boiler piping must be equipped with flow control valves to prevent gravity circulation of boiler water during the operation of the cooling system.
c. If boiler is used with an Alliance™ Indirect-
Fired Domestic Water Heater, install the Alliance as a separate heating zone. Refer to the Alliance Installation, Operating, and Service Instructions for additional information.
d. Use a system bypass if the boiler is to be
operated in a system which has a large volume or excessive radiation where low boiler water temperatures may be encountered (i.e. converted gravity circulation system, etc.) The bypass should be the same size as the supply and return lines with valves located in the bypass and return line as illustrated in Figure 4 in order to regulate water flow for maintenance of higher boiler water temperature. Set the bypass and return valves to a half throttle position to start. Operate boiler until the system water tempera­ture reaches its normal operating range. Adjust the valves to maintain 180°F to 200°F boiler water temperature and greater the 120°F return temperature. Adjust both valves simultaneously. Closing the boiler return valve while opening the bypass valve will raise the boiler return temperature. Opening the boiler return valve while closing the by-pass valve will lower the boiler return temperature.
e. A water boiler installed above radiation level
must be provided with a low water cutoff device as part of the installation.
8
Figure 3: Recommended Piping for Combination
Heating and Cooling (Refrigeration) System
9
Loading...
+ 19 hidden pages