Burnham 4FHL-345A, 4FHL-107A, 4FHL-127A, 4FHL-209A, 4FHL-240A Installation And Operating Instructions Manual

...
INSTALLATION AND OPERATING
INSTRUCTIONS FOR
4FH SERIES FIRETUBE BOILERS
Commercial Boilers
This manual must only be used by a qualied heating installer/service technician.
BEFORE installing, read all instructions in this manual and all other information shipped with the boiler. Post all instructions and manuals near the boiler for reference by service personnel. Perform steps in the order given. Failure to comply could result in severe personal injury, death or substantial property damage.
Ce manuel ne doit être utilisé que par des techniciens qualiés en entretien et
installation d’appareil de chauffage. Lire l’ensemble des directives et toute autre information reçue avec la chaudière AVANT l’installation. Conserver ces directives
près de la chaudière an que le personnel d’entretien puisse s’y référer. Exécuter les étapes dans l’ordre donné. Ne pas se conformer aux directives peut engendrer des
blessures graves, la mort ou d’importants dommages matériels.
For service and repairs to the heating plant, call your local representatives. When seeking information on the boiler, provide series and size designation shown on rating plate.
Boiler Number __________________ Type Firing________________ Type System _________
Project______________________________________________________________
Address_________________________________________________ Phone No._____________
1
IMPORTANT INFORMATION -
READ AND SAVE THESE INSTRUCTIONS FOR REFERENCE
All boilers must be installed in accordance with National, State and Local Plumbing, Heating and Electrical Codes and the regulations of the serving utilities. These Codes and Regulations may differ from this instruction manual. Authorities having jurisdiction should be consulted before installations are made. In all cases, reference should be made to the following Standards:
USA BOILERS
A. Current Edition of American National Standard ANSI/NFPA 31, “Installation of Oil Burning Equipment,” for
recommended installation practices.
B. Current Edition of National Fuel Gas Code, NFPA 54/ANSI Z223.1.
C. Current Edition of American National Standard ANSI/NFPA 211, “Chimneys, Fireplaces, Vents, and Solid Fuel
Burning Appliances,” for venting requirements.
D. Current Edition of American Society of Mechanical Engineers ASME CSD-1, “Controls and Safety Devices for
Automatically Fired Boilers,” for assembly and operations of controls and safety devices.
E. All wiring on boilers installed in the USA shall be made in accordance with the National Electrical Code and/or
Local Regulations.
CANADIAN BOILERS
A. Current Edition of Canadian Standards Association CSA B139, “Installation Code for Oil Burning Equipment,”
for recommended Installation Practices.
B. The equipment shall be installed in accordance with the current Installation Code for Gas Burning Appliances and
Equipment, CSA B149, and applicable Provincial Regulations for the class; which should be carefully followed in all cases. Authorities having jurisdiction should be consulted before installations are made.
C. All wiring on boilers installed in Canada shall be made in accordance with the Canadian Electrical Code and/or
Local Regulations.
Hazard denitions
The following dened terms are used throughout this manual to bring attention to the presence of hazards of various
risk levels or to important information concerning the life of the product.
Indicates an imminently hazardous situation which, if not avoided, will result in death, serious injury or substantial property damage.
Indicates a potentially hazardous situation which, if not avoided, could result in death, serious injury or substantial property damage.
Indicates a potentially hazardous situation which, if not avoided, may result in moderate or minor injury or property damage.
Indicates special instructions on installation, operation, or maintenance which are important but not related to personal injury hazards.
Dénitions des dangers
Les termes suivants sont utilisés tout au long de ce manuel an de souligner la présence de dangers dont le
niveau de risque varie ou de mettre en relief de l’information cruciale quant à la durée de vie du produit.
Indique une situation de danger imminent qui, si elle n’est pas évitée, peut causer la mort, de graves blessures ou d’importants dommages matériels.
Indique une situation de danger potentiel qui, si elle n’est pas évitée, cause la mort, de graves blessures ou d’importants dommages matériels.
Indique une situation de danger potentiel qui, si elle n’est pas évitée, peut causer des blessures mineures ou de légers dommages matériels.
2
Indique des directives particulières, importantes, mais sans risque de blessure, lors de l’installation, de l’utilisation ou de l’entretien.
This boiler has a limited warranty, a copy of which is printed on the back of this manual. It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating properly
when the installation is complete. The warranty for this boiler is valid only if the boiler has been installed, maintained and operated in accordance with these instructions.
Cette chaudière est sous garantie limitée, dont un exemplaire apparaît à l’arrière du manuel.
Il incombe à l’installateur de s’assurer que les dispositifs sont correctement xés et en état de marche au terme de
l’installation. La garantie pour cette chaudière est valable seulement si le produit est installé, entretenu et utilisé selon les présentes directives.
DO NOT store or use gasoline or other ammable vapors or liquids in the vicinity of this or any other appliance.
If you smell gas or fuel oil vapors, do not try to operate the burner/boiler system. Do not touch any electrical switch or use any phone in the building. Immediately call the gas or oil supplier from a remotely located phone.
Burner/boiler systems produce steam or hot water in a pressurized vessel by mixing extremely ammable gaseous, liquid or solid fuels with air to produce combustion and very hot products of combustion. Explosions, res severe
personal injury, death and/or property damage will result from improper, careless or inadequate installation, operation or maintenance of fuel-burning and boiler equipment.
NE PAS entreposer ou utiliser de l’essence ou toute autre matière inammable gazeuse ou liquide à proximité de la
chaudière ou de tout autre appareil. Si vous sentez une odeur de gaz ou de mazout, ne pas tenter d’utiliser le système de brûleur/chaudière. Ne pas
toucher les interrupteurs ni se servir des téléphones du bâtiment. Appeler immédiatement le fournisseur de gaz ou de mazout à partir d’un autre endroit.
Les systèmes de brûleur/chaudière produisent de la vapeur ou de l’eau chaude en mélangeant des carburants
hautement inammables gazeux, liquides ou solides avec de l’air dans une cuve sous pression pour produire une
combustion et des résidus très chauds. Des explosions, des incendies, des blessures graves, la mort ou d’importants dommages matériels peuvent découler d’une installation, d’une utilisation ou d’un entretien inadéquat ou négligé de l’équipement de combustion et de la chaudière.
3
Improper installation, adjustment, alteration, service or maintenance can cause property damage, personal injury or loss of life. Failure to follow all instructions in the proper order can cause personal injury or death. Read and understand all instructions, including all those contained in component manufacturers manuals which are provided with the appliance before installing, starting-up, operating, maintaining or servicing this appliance. Keep this manual and literature in legible condition and posted near appliance for reference by owner and service technician.
Keep boiler area clear and free from combustible materials, gasoline and other ammable vapors and liquids.
This boiler requires regular maintenance and service to operate safely. Follow the instructions contained in this manual. Installation, maintenance, and service must be performed only by an experienced, skilled and knowledgeable installer
or service agency. All heating systems should be designed by competent contractors and only persons knowledgeable in the layout
and installation of heating systems should attempt installation of any boiler. It is the responsibility of the installing contractor to see that all controls are correctly installed and are operating
properly when the installation is completed. Installation is not complete unless a pressure relief valve is installed.
This boiler is NOT suitable for installation on combustible ooring.
Do not tamper with or alter the boiler or controls. Retain your contractor or a competent serviceman to assure that the unit is properly adjusted and maintained.
Clean boiler at least once a year - preferably at the start of the heating season to remove soot and scale. The inside of the combustion chamber should also be cleaned and inspected at the same time.
Have Burner and Controls checked at least once a year or as may be necessitated. Do not operate unit with jumpered or absent controls or safety devices. Do not operate unit if any control, switch, component, or device has been subject to water.
Toute installation, altération, réparation, ou tout réglage ou entretien inadéquat peut provoquer des dommages matériels, une blessure ou une perte de vie. Ne pas se conformer aux directives dans l’ordre donné peut causer des blessures ou la mort. S’assurer de bien les comprendre, y compris celles des manuels du fabricant accompagnant les composants fournis avant d’installer, d’utiliser, de réparer, de démarrer ou d’entretenir cet appareil. Conserver ce
manuel et toute autre documentation en bonne condition près de l’appareil aux ns de référence pour le propriétaire
ou le technicien en entretien et réparation. Garder l’espace autour de la chaudière dégagé et exempt de matières combustibles, d’essence et d’autres vapeurs
et liquides inammables.
Pour fonctionner de façon sécuritaire, cette chaudière nécessite un entretien régulier. Suivre les directives de ce manuel.
L’installation, les réparations et l’entretien doivent être effectués uniquement par un installateur ou un organisme
de service expérimenté et qualié.
Tout système de chauffage devrait être conçu par des entrepreneurs compétents, et seules les personnes qualiées
pour l’installation de tel système devraient s’en charger.
Il incombe à l’installateur de s’assurer que les dispositifs de contrôle sont correctement xés et en état de marche
au terme de l’installation.
L’installation n’est pas terminée tant qu’une soupape de sûreté n’est pas xée.
Cette chaudière NE PEUT être installée sur un plancher combustible.
Ne pas modier la chaudière ou ses commandes. S’assurer que l’unité est correctement réglée et entretenue auprès
d’un entrepreneur ou d’un technicien compétent. Nettoyer la suie et le tartre accumulés au moins une fois par année, si possible, au début de la saison froide. Au
même moment, nettoyer et inspecter l’intérieur de la chambre de combustion.
Faites vérier le brûleur et ses commandes au moins une fois par an ou lorsque nécessaire. Ne pas faire fonctionner
si les commandes ou les dispositifs de sûreté sont absents ou installés à l’aide de cavaliers. Ne pas faire fonctionner si une commande, un interrupteur, un composant ou un dispositif est entré en contact avec de l’eau.
4
Appliance materials of construction, products of combustion and the fuel contain alumina, silica, heavy metals, carbon monoxide, nitrogen oxides, aldehydes and/or other toxic or harmful substances which can cause death or serious injury and which are known to the state of California to cause cancer, birth defects and other reproductive harm. Always use proper safety clothing, respirators and equipment when servicing or working nearby the appliance.
This boiler contains very hot water under high pressure. Do not unscrew any pipe ttings nor attempt to disconnect any
components of this boiler without positively assuring the water is cool and has no pressure. Always wear protective clothing and equipment when installing, starting up or servicing this boiler to prevent scald injuries. Do not rely on the pressure and temperature gauges to determine the temperature and pressure of the boiler. This boiler contains components which become very hot when the boiler is operating. Do not touch any components unless they are cool.
This appliance must be properly vented and connected to an approved vent system in good condition. Do not operate boiler with the absence of an approved vent system.
This boiler needs fresh air for safe operation and must be installed so there are provisions for adequate combustion and ventilation air.
The interior of the venting and air intake systems must be inspected and cleaned before the start of the heating season and should be inspected periodically throughout the heating season for any obstructions. Clean and unobstructed venting and air intake systems are necessary to allow noxious fumes that could cause injury or loss of life to vent
safely and will contribute toward maintaining the boiler’s efciency.
This boiler is supplied with controls which may cause the boiler to shut down and not re-start without service. If damage due to frozen pipes is a possibility, the heating system should not be left unattended in cold weather; or appropriate safeguards and alarms should be installed on the heating system to prevent damage if the boiler is inoperative.
This boiler is designed to burn No. 2 fuel oil, natural and/or LP gas only. Do not use gasoline, crankcase drainings, or any oil containing gasoline. Never burn garbage or paper in this boiler. Do not convert to any solid fuel (i.e. wood,
coal). All ammable debris, rags, paper, wood scraps, etc., should be kept clear of the boiler at all times. Keep the boiler area clean and free of re hazards.
Always keep the oil supply valve shut off if the burner is shut down for an extended period of time.
Probe and oat type low water cutoff devices require annual inspection and maintenance. Refer to instructions in
Section IV for inspection and cleaning instructions.
Les matériaux d’assemblage de l’appareil, les produits de combustion et le combustible contiennent de l’alumine, de la silice, des métaux lourds, du monoxyde de carbone, des oxydes d’azote, des aldéhydes ou d’autres substances toxiques ou dangereuses pouvant causer la mort ou des blessures graves, et qui ont été reconnues par l’État de la Californie comme causes de cancer, d’anomalies congénitales et d’autres problèmes de l’appareil reproducteur. Toujours utiliser des vêtements, des appareils respiratoires et de l’équipement de sécurité appropriés lors du travail ou de l’entretien près de l’unité.
Cette chaudière contient de l’eau très chaude sous haute pression. Ne pas dévisser les raccords de tuyau ni tenter de retirer tout composant sans s’assurer hors de tout doute que l’eau est froide et la pression inexistante. Toujours
porter des vêtements et de l’équipement de protection pour installer, démarrer ou réparer cet appareil an d’éviter les échaudures. Ne pas se er aux jauges de pression et de température de la chaudière pour déterminer ces variables.
Certains composants de cet appareil deviennent très chauds lors du fonctionnement. Ne pas toucher les composants qui ne sont pas froids.
Cet appareil doit être installé dans un endroit bien aéré et raccordé à un système de ventilation certié en bonne
condition. Ne pas faire fonctionner sans ventilation. Pour fonctionner de façon sécuritaire, cette chaudière nécessite de l’air frais et doit être installée de façon à ce que
les conditions de combustion et de ventilation soient adéquates. L’intérieur des prises d’air et des conduites d’évacuation doit être inspecté et nettoyé avant la saison froide, puis
inspecté régulièrement en cours de saison pour prévenir les engorgements. La propreté et l’absence d’obstruction des prises d’air et des conduites d’évacuation sont nécessaires à l’évacuation sécuritaire des émanations toxiques
pouvant causer des blessures ou la mort, et contribuent à maintenir l’efcacité de la chaudière.
Cette chaudière est munie de commandes pouvant provoquer un arrêt qui l’empêchera de redémarrer si elle n’est pas réparée. Si le gel des tuyaux peut causer un bris, ne pas laisser le système de chauffage sans surveillance en temps
froid, ou encore, installer une alarme ou une protection appropriée au système an de prévenir des dommages si la chaudière est inefcace.
Cette chaudière est conçue pour n’utiliser que du mazout lourd no 2, du gaz naturel ou du gaz de pétrole liquéé. Ne
pas utiliser d’essence, de vidanges de carter de moteur ou toute huile contenant de l’essence. Ne pas faire brûler de déchets ni de papier dans la chaudière. Ne pas utiliser de combustible solide (bois, charbon). Tenir tout débris, tissu, papier, résidu de bois ou autre loin de la chaudière en tout temps. Garder l’espace autour de l’appareil propre et sans risque d’incendie.
Toujours fermer la vanne d’alimentation de mazout si le brûleur est arrêté pour une durée prolongée.
Les interrupteurs à bas niveau d’eau de type sonde ou de type otteur doivent être inspectés et entretenus annuellement.
Voir les directives de la section IV concernant l’inspection et le nettoyage.
5
Burner/boiler system, as used throughout this manual, shall mean all mechanical and/or electrical equipment including the boiler, burner, pumps, compressors, feed water systems and all associated piping, electrical and control systems used and maintained in the boiler room.
Le terme « système de brûleur/chaudière » utilisé dans ce manuel signie tout équipement mécanique ou électrique, y
compris la chaudière, le brûleur, les pompes, les compresseurs, le système d’eau d’alimentation et sa tuyauterie, ainsi que les systèmes électriques et de contrôle utilisés ou conservés dans la chaufferie.
6
TABLE OF CONTENTS
SECTION I General information
Introduction ...................................................................................................................................... 8
Setting the Unit ................................................................................................................................ 8-9
Flue Outlet, Stack, and Breeching ................................................................................................... 9
Combustion Air Requirements ......................................................................................................... 9-10
SECTION II Installation Instructions
Boiler Piping .................................................................................................................................... 11
Tankless Heater Piping .................................................................................................................... 12
Flow Regulation ............................................................................................................................... 12
Hot Water Tempering ....................................................................................................................... 13
Heater Flushing ............................................................................................................................... 13
Hard Water ...................................................................................................................................... 13
Bottom Blowdown Piping ................................................................................................................. 13
Boiler Installation ............................................................................................................................. 14-15
SECTION III Operating Instructions
Filling System .................................................................................................................................. 16
Adjusting Burner .............................................................................................................................. 16
Testing Controls ............................................................................................................................... 16-17
Initial Cleaning, Steam Boilers......................................................................................................... 17
Initial Cleaning, Water Boilers ......................................................................................................... 17-18
Water Boiler Operation .................................................................................................................... 18
Boiler Water Treatment .................................................................................................................... 18
pH or Alkalinity Test ......................................................................................................................... 18
Warnings about Frequent Water Addition ........................................................................................ 18-19
Minimum Water Quality Requirements ............................................................................................ 19
SECTION IV Service Instructions
Boiler Shutdown and Cool Down Procedures ................................................................................. 20
Cleaning Boiler Heating Surfaces.................................................................................................... 20-21
Turbulators ...................................................................................................................................... 21
Maintenance of Low Water Cutoff Devices...................................................................................... 21-22
Checking Burner & Controls ............................................................................................................ 22
Lubrication ....................................................................................................................................... 22
Checking Safety Valve ..................................................................................................................... 22
Attention to Boiler while not in Operation ........................................................................................ 23
Ordering Repair Parts...................................................................................................................... 23
Periodic Testing Recommended Check List .................................................................................... 24-25
WARRANTY...................................................................................................................... Back Cover
7
SECTION I — GENERAL INFORMATION
INTRODUCTION
1. Refer to burner manufacturer’s installation manual provided for proper venting of the gas train components that require atmospheric pressure to balance a diaphragm.
2. All cover plates, enclosures and guards
must be in place at all times, except during
maintenance and service.
3. Insulate all steam and hot water piping, ttings
and connections and all other hot components and equipment from personnel contact.
4. Assure all pipes, ttings, electrical controls and all other associated burner/boiler equipment
is of proper design and construction for the intended use and provides adequate protection from electrical shock and harmful physical contact to personnel.
5. A leak-tight fuel delivery conduit and control system must be maintained at all times.
6. Products of combustion must be transported
from the boiler/burner system to the outdoors
in an approved, leak tight, insulated venting system. The boiler room must be positively ventilated to prevent a concentration of products of combustion and a reduction in
the amount of oxygen in the air.
7. For optimum performance and serviceability from this unit adhere to the following recommendations:
A. Clean retubes at least once a year,
preferably at the end of the heating season to remove soot and scale. Inside surfaces of
the furnace, front and rear smokeboxes, and
reversing chamber should also be cleaned at the same time.
B. Have the burner and controls checked at
least once a year or as necessary.
C. Retain your contractor or a competent
serviceman to assure that the unit is properly adjusted and maintained.
1. GENERAL INFORMATION
The boiler is designed specically for forced draft ring, is available with oil, gas or combination gas/oil burners, and operates with a combustion efciency of
over 80%.
This manual gives the necessary information for the proper installation, operation, maintenance and service of units. For special installation problems,
contact Burnham Commercial, P.O. Box 3939
Lancaster, PA 17604, Phone: 888-791-3790.
2. INSPECT SHIPMENT carefully for any signs of damage.
A. All Equipment is carefully manufactured,
inspected and packed. Our responsibility ceases upon delivery of boiler to the carrier in good condition.
B. Any Claims for damage or shortage in
shipment must be led immediately against
the carrier by the consignee. No claims for variances from, or shortage in, orders will be allowed by the manufacturer unless presented within sixty (60) days after receipt of goods.
C. Boiler model explanation is as follows:
Series 4FH: 4FHW-827-50-GO-PF 1 2 3 4 5
1. Medium: “W” for 30 psig water boiler, “PW” for 31 thru 160 psig water boiler, “L” for 15 psig steam boiler.
2. Heating surface for the 4FH.
3. Heating surface: “50” designates 5.0 sq ft heating surface per boiler horsepower.
4. Fuel: “G” for natural gas, “O” for #2 fuel oil,
“GO” for combination gas/oil.
5. Burner manufacturer: “PF” for Power Flame, “WEB” for Webster, “WHT” for Weishaupt.
3. SETTING THE UNIT
Most boilers are equipped with lifting lugs to be used in maneuvering the boiler into position. On large boilers, where four lifting lugs are supplied, all four lugs should be used when lifting the boiler.
A. Lifting and Rigging
Use of a spreader beam is preferred but not
mandatory. An approved, inspected, and rated sling suitable for the total published boiler weight shall be used. The correct WLL (working load limit) shall be calculated based on the
sling angle used, and the WLL must not exceed
the sling rated capacity. The sling angle (angle between the sling and the load) must not be less than 60 deg. The boiler must be lifted as level as practical (less than 5 degree tilt). Refer to the boiler submittal drawing for dry boiler weight.
8
The unit should be located in the boiler room so as to provide ease of venting and adequate clearance for maintenance, serviceability and installation of piping.
The tube pull space listed in the Burnham Commercial product catalog must be provided at the front of the boiler. The coil pull space must be maintained at the front of units equipped with tankless coils. Floor construction should have adequate load bearing characteristics to bear
the weight of the boiler lled with water. A boiler
foundation is recommended if the boiler room
oor is weak, uneven or if a water condition exists. These boilers are not for installation on combustible ooring.
B. Installation Clearance
Minimum clearances to combustible walls shall be as follows:
1. Models 4FH-63A thru 180: 6" sides, rear and above
2. Models 4FH-209A thru 3075A: 18" sides, rear, and above
3. Minimum recommended service clearances: 18".
See boiler submittal drawings for tube pull clearance requirements.
If desiccant package was ordered, be sure to remove from the boiler furnace using the rear access, and from the waterside using the manhole cover.
4. FLUE OUTLET, STACK, AND BREECHING
The maximum weight limit on the boiler ue outlets
is as follows:
1. Series 4FH: 250 lb
2. All stack/economizer weights exceeding the limits
above will need to be independently supported.
Stack design: The stacks shall be installed in compliance with NFPA 54, ANSI Standard Z223.1, state and local codes, using a category III product for positive, non-condensing appliances. The boiler ue outlets are generally sized for the correct stack diameter, but there
are exceptions to this.
The 4FH Series boilers are equipped with a ue
outlet stub to accept a slip-on stack connection.
The boilers are optimally designed to run with a ue
outlet pressure of .10-.30”wc pressure. The stack design, taking into account the draft effect and all friction losses, should arrive at 0.0"wc +/- .10"wc pressure at the inlet. Horizontal runs should be kept to a minimum. This will ensure the boiler will meet
the maximum capacity, and will light off and have
stable and consistent combustion.
On installations where a natural draft stack is used,
causing high breeching drafts, the boiler locking blade damper (on boilers equipped with one) may require adjusting, or one may need to be installed at the boiler breeching. In multiple boiler installations, or in installations where the breeching draft may vary considerably, automatic draft controls in combination with a motorized damper may be required.
5. COMBUSTION AIR REQUIREMENTS
All boiler rooms must be adequately vented to provide enough combustion air to the boiler for proper
tuning and operation, to prevent oxygen depletion, possible carbon monoxide formation, possible
accumulation of fuel fumes, and possible equipment
explosions. A free ow of combustion air will aid the
proper operation of the burner and allow for proper venting of the boiler. The instructions below must be followed to properly size make-up air openings in the boiler room. Consult NFPA-54 National Fuel Gas Code, NFPA-31 Installation of Oil Burning Equipment for more
detailed explanations, and local codes for additional
guidance for boiler rooms below grade and other
specic situations.
Two general methods may be used:
1. When one permanent opening is used: The opening shall commence within 12" of the top of the enclosure (boiler room) and the opening shall communicate directly with the outdoors, or through a vertical or horizontal duct with the outdoors. The opening shall have a minimum
free area of 1 sq in per 3,000 BTU/hr total input
of all equipment in the enclosure, and not less than the sum of the areas of all equipment vent connectors.
2. When two permanent openings are used: One opening location shall begin within 12" of the top of the enclosure, and the other opening location shall begin within 12" of the bottom of the enclosure. When communication is directly with the outdoors, or through vertical ducts, each opening shall have a minimum free area of 1 sq
in per 4,000 BTU/hr total input of all equipment
in the enclosure. Where communicating with the outdoors through horizontal ducts, each opening shall have a minimum free area of 1 sq in per
2,000 BTU/hr total input of all equipment in the
enclosure.
9
Duct size, if used, shall have a minimal cross
sectional area equal to the opening size.
Outside air openings may be protected by mesh,
grills, or louvers. When doing so, the free area sizing must be compensated for the blocking effect of such obstructions. Protective mesh must be no smaller than 1/4". If the free area of the grilles and louvers is unknown, use 20-25% free area for wood louvers, and use 60-75% free area for metal louvers and grilles.
Closeable louvers must be electrically interlocked
with the burner to prevent the burner from ring if the
louvers fail to open or remain open.
The boiler room should not be under negative
pressure at any time.
Adjustment to air opening and duct size shall be
made to boilers at higher altitude installations (above 1,000 ft). An adjustment of 3.5% per 1,000 ft of elevation is recommended.
7. NORMAL BOILER WATER LEVEL
The normal boiler water level is the water height where the steam boiler water level should operate at. If
using an on/off pump control, this will correspond with
the “pump-off” level. The following dimensions represent the vertical distance from the reference point to the Normal Water Level.
Series 4FH Firebox – Reference point is from the top of the boiler base
4FHL-63A/107A 40-3/4"
4FHL-127A/209A 48-1/2"
4FHL-240A/345A 55"
4FHL-360A/450A 66-3/16"
4FHL-563A/675A 69"
4FHL-827/993 74"
4FHL-1157/1323 85-1/2"
4FHL-1654 100-1/4"
4FHL-1985/2645 114-1/4"
4FHL-3075A 122-1/2"
6. LOCATION OF ASME STAMPING DATA
The ASME stamping data is located as follows:
1. Series 4FH: Sizes 63 thru 675, on the left side of
the boiler shell near the front, under a 3 x 6 cover
plate. Sizes 827 thru 3075, on the right side front tubesheet.
10
SECTION II — INSTALLATION INSTRUCTIONS
1. BOILER PIPING A. Water Boiler
Attach supply and return piping lines and insert plugs and bushings in connections as required. Supply and return piping headers are detailed in Figure 2.
It is important to comply with the minimum piping requirements in order to ensure maximum performance and reliability on steam boilers, particular attention should be given to the construction of the supply header.
Il est important de respecter les exigences minimales en
matière de tuyauterie pour assurer une efcacité et une abilité optimales des chaudières à vapeur, en portant
une attention particulière à l’assemblage du collecteur d’alimentation.
The nominal temperature differential between supply and
return water recommended for Burnham retube water
boilers is 20°F. As a precaution against thermal shock, this differential should never exceed 40°F.
When differentials in excess of 30°F are anticipated on
rebox boilers, the return water should enter the boiler at the top tting (normally the supply) and the supply water should leave the boiler through the bottom tting (normally the return). This ow pattern directs the return water over
the relatively cool third pass rather than directly against the rear of the furnace.
The boiler should not be operated for any length of time at a temperature setting that allows the formation of condensation in the tubes or smokebox. This generally dictates a minimum setting of approximately 140°F on the low limit on systems with a 20°F system differential. On cold start up, condensation can be expected until the boiler warms up. If formation of condensate persists, the low limit should be adjusted upward until condensate no longer forms.
Water boilers and low pressure steam boilers must have a set LFH at 120° minimum to avoid condensation. High pressure steam should have a minimum LFH temperature of 180°F.
L’écart de température nominale de l’eau d’alimentation et de l’eau de retour recommandé pour les chaudières
ignitubulaires Burnham est de 11° C (20°F). An de prévenir
un choc thermique, cet écart ne devrait jamais dépasser 22°C (40°F).
Lorsque des écarts supérieurs à 17°C (30°F) sont prévus sur une chaudière à foyer intérieur, l’eau de retour devrait entrer par le raccord du haut (l’alimentation), et l’eau d’alimentation devrait sortir par le raccord du bas (le retour). Ce schéma de circulation dirige l’eau de retour vers le troisième passage, plus tempéré, plutôt que vers l’arrière directement.
La chaudière ne devrait fonctionner en aucun moment à une température favorisant la formation de condensation dans les tubes ou la boîte à fumée. Cette obligation force généralement un réglage minimal d’environ 600°C (140°F) comme limite inférieure sur les systèmes dont l’écart nominal est de 11°C (20°F). Lors d’un démarrage à froid, un effet de condensation est à prévoir jusqu’à ce que la chaudière se réchauffe. Si la formation de condensat persiste, la limite inférieure de température doit être ajustée à la hausse jusqu’à ce qu’il n’y ait plus de condensation.
Les chaudières à eau et les chaudières à vapeur basse pression doivent avoir une température à faible risque d’incendie (LFH) paramétrée à un minimum de 67°C
(120°F) an d’éviter la condensation. Les chaudières à
vapeur haute pression doivent avoir une température LFH minimale de 100°C (180°F).
11
Flow Rate Based On Delta-T
APPROXIMATE BOILER WATER FLOW RATE REQUIRED (GPM) – SERIES 4FH
BOILER SIZE
(bhp)
63A 43 29 22
78A 53 36 27
92A 63 42 31
107A 73 49 37
127A 87 58 44
154A 106 71 53
180A 124 83 62
209A 144 96 72
240A 166 111 83
277A 192 128 96
311A 216 144 108
345A 241 161 120
360A 251 168 126
450A 317 211 158
563A 400 267 200
675A 483 322 242
827 591 394 295
993 708 472 354
1157 823 549 411
1323 939 626 469
1654 1166 777 583
1985 1399 933 700
2315 1638 1092 819
2645 1878 1252 939
3075A 2186 1457 1093
20º Delta T 30º Delta T 40º Delta T
Boiler Waterside Pressure Drop
Due to the large internal water reservoir and
a design having very little ow restriction, the waterside ow pressure drop is less than 1 psi. This is applicable to all ow rates, including the highest ow rate corresponding with a 20ºF delta T.
B. Steam Supply Connection & Piping
Most steam boilers are supplied with a anged
steam outlet connection, with the exception of the
smallest boilers, which may have a threaded pipe connection. All low pressure steam boilers (15
psig) are supplied with a class 150 anged steam
connection. All high pressure steam boilers (over
15 psig) are supplied with a class 300 anged
steam connection.
changes within the boiler can create stresses in the boiler metal. These stresses can cause damage to the boiler by loosening tubes, or in more severe instances can crack tube sheet ligaments,furnaces, or waterlegs.
B. If temperature differentials approach 40°F,
to help prevent temperature uctuations and
insure proper circulation through the boiler, a recirculation loop as shown in Figure 3 should be
considered. The recirculation ow should be at least 1/2 GPM/BHP at all times when the boiler is
online for operation.
3. TANKLESS HEATER
Install an automatic mixing valve at the tankless heater outlet to avoid risk of burns or scalding due to excessively
hot water at the xtures. Adjust and maintain the mixing
valve in accordance with the manufacturer’s instructions.
Installer une vanne mélangeuse automatique au chauffe­eau sans réservoir pour éviter les risques de brûlure causés par une température excessive de l’eau dans la plomberie. Ajuster la vanne mélangeuse conformément aux instructions du fabricant, et la maintenir ainsi.
A. If boiler is ordered with tankless heater, connect
tankless heater piping as shown in Figure 2.
B. The following guidelines should be followed when
piping the tankless heaters:
4. FLOW REGULATION
If ow through the heater is greater than its rating,
the supply of adequate hot water may not be able to keep up
with the demand. For this reason a ow regulator matching
the heater rating should be installed in the cold water line to
the heater. The ow regulator should preferably be located below the inlet so it's not subjected to excess temperatures
that may occur during “off” periods when it is possible for the heat to be conducted back through the supply line. The
ow regulator also limits the ow of supply water regardless
of inlet pressure variations in the range of 20 to 120 psi.
2. RECOMMENDED WATER BOILER RECIRCULATION LOOP
The following guidelines relating to system water
temperature uctuation and ow through the boiler
must be observed.
A. It is important to operate your boiler in such a
manner as to prevent temperature uctuation of
more then 40°F at any time. Rapid temperature
12
FIGURE 2
SCHEMATIC TANKLESS HEATER PIPING
5. TEMPERING OF HOT WATER Installation of an automatic mixing valve will
lengthen the delivery of the available hot water by mixing some cold water with the hot. This prevents excessive
and possibly scalding hot water. Higher temperature hot water is possible by piping the hot water from the heater
prior to entering the mixing valve. The mixing valve
should be “trapped” by installing it below the cold water inlet to heater to prevent lime formation in the valve.
6. FLUSHING THE BOILER All water contains some sediment which settles on
the inside of the coil. Consequently, the heater should be periodically backwashed. This is accomplished by installing hose bibs as illustrated and allowing water at city pressure to run into hosebib A, through the heater, and out hosebib B until the discharge is clear. The tees in which the hosebibs are located should be the same size as heater connections to minimize pressure drop.
rating plates), must meet or exceed the minimum
required relieving capacity as stamped on the boiler rating plate.
Install the valve(s) in the ttings supplied on the top
of the boiler using appropriate pipe dope. In some cases, reducing bushings are required to adapt the relief valve
inlet to the boiler tting. When required, the bushings are
supplied by Burnham. Using the bushings is NOT a code violation. Always install the relief valves in the vertical position with no intervening valve.
Pipe the relief valve to a safe point of discharge, with same pipe size as the valve outlet connection – never reduce. The discharge piping shall be arranged as short as possible, and properly supported to prevent stresses on the relief valve. Never install a valve or plug on the relief valve outlet piping.
A method of gravity drain must be employed in the discharge pipe at or near each relief valve and where condensate may collect. Where a vertical discharge pipe is used, a drip pan elbow is highly recommended.
10. BOTTOM BLOWDOWN PIPING
See suggested piping schematics for bottom blowdown piping. The bottom blowdown connection on the boiler has been properly sized according to ASME Code. DO NOT reduce the blowdown piping size from the boiler connection to the point of discharge. Do not
use galvanized pipe or ttings.
Valve ratings:
For ASME Section IV low pressure steam (15 psig) and water boilers, the valve pressure rating shall meet
or exceed the boiler MAWP rating, as stamped on the
boiler, but in no case less than 30 psig. The minimum temperature rating of the valves shall be 250F.
7. HARD WATER
May be applicable to some city and particularly well
water. Have your water analyzed by a qualied water
treatment specialist to determine if a water softener,
conditioner or ltration is required. Treated water will
ensure longer tankless heater life and performance and is also benecial to all the piping and xtures in the building.
8. FUEL SUPPLY PIPING
For information regarding gas supply line piping schematic and sizing, drip leg, gas pressure regulator, oil supply line piping schematic and sizing, oil pump,
and oil lter, please refer to the BURNER
INSTALLATION AND OPERATION MANUAL.
9. RELIEF VALVES
Boiler relief valves are normally shipped loose and have been properly sized for your boiler. The aggregate capacity of the relief valves (as stamped on the valve
13
INSTALLATION INSTRUCTIONS
FIGURE 3
TS-71-176-B
14
FIGURE 4
TS-71-130-D
INSTALLATION INSTRUCTIONS
FIGURE 5
TS-3-101-4
FIGURE 6
TS-71-131-D
15
SECTION III — OPERATING INSTRUCTIONS
1. ALWAYS INSPECT INSTALLATION BEFORE STARTING BURNER.
2. FILL HEATING SYSTEM WITH WATER.
Any time that raw water is introduced to the boiler it must be heated to at least 180ºF immediately to dissipate the dissolved gases which can otherwise cause internal corrosion to the boiler.
Chaque fois que de l’eau non traitée est introduite dans la chaudière, il faut immédiatement la chauffer jusqu’à 100°C (180°F) pour dissiper les gaz dissous qui, autrement, pourraient provoquer de la corrosion interne.
A. Steam Boilers Fill boiler to normal water line.
Water should be visible in the gauge glass. After boiler is in operation, make up water should be added slowly to maintain the water level.
B. Hot Water Boilers In a hot water heating
system, the boiler and the entire system (other than the tank) must be full of water for satisfactory operation. Water should be added to the system until the boiler pressure gauge registers normal system design operating pressure. To ensure that the system is full, water should come out of all air vents when opened.
ON A HOT WATER SYSTEM THE PRESSURE MUST NOT EXCEED 30 POUNDS UNLESS THE BOILER IS ESPECIALLY DESIGNED FOR A HIGHER MAXIMUM WORKING PRESSURE. IF A BOILER PRESSURE EXCEEDS PRESSURE SETTING OF SAFETY RELIEF VALVE, VALVE WILL RELIEVE IMMEDIATELY, BUT CAUSE OF RELIEF MUST BE INVESTIGATED AND CORRECTED. EXCESS PRESSURE IS DANGEROUS, IN ADDITION, COULD CAUSE DAMAGE TO HEATING SYSTEM, PERSONAL INJURY OR SERIOUS PROPERTY DAMAGE. DO NOT draw water from the boiler while in use. When adding water while boiler is in operation, do not open the supply valve fully, but add water slowly.
LES SYSTÈMES À EAU CHAUDE NE DOIVENT PAS ÊTRE SOUMIS À UNE PRESSION DÉPASSANT 30 LIVRES, À MOINS QUE LA CHAUDIÈRE SOIT CONÇUE SPÉCIALEMENT POUR UNE PRESSION DE FONCTIONNEMENT PLUS ÉLEVÉE. SI LA PRESSION INTERNE DE LA CHAUDIÈRE DÉPASSE LA PRESSION PARAMÉTRÉE DE LA SOUPAPE DE SÛRETÉ, CETTE DERNIÈRE RELÂCHERA DE LA PRESSION IMMÉDIATEMENT, MAIS LA CAUSE DE CETTE DÉCOMPRESSION DOIT ÊTRE EXAMINÉE ET CORRIGÉE. LA PRESSION EXCESSIVE EST DANGEREUSE. DE PLUS, ELLE POURRAIT ENDOMMAGER LE SYSTÈME DE CHAUFFAGE OU CAUSER DES BLESSURES OU DES DOMMAGES MATÉRIELS SÉRIEUX.
NE PAS soutirer de l’eau de la chaudière lorsque celle-ci est en marche. Si la chaudière fonctionne, ne pas y ajouter de l’eau en ouvrant complètement la vanne d’alimentation; ajouter l’eau lentement.
3. BURNER A. Check wiring of all fuel valves. Verify that wiring
is correct according to the factory supplied wiring diagram.
B. Leave all manual fuel valves closed. This includes
manual shutoff valves supplied with the boiler and facility installed valves at the boiler site.
C. Perform all burner pre-startup checks according
to the burner manufacturer's specications. Refer
to the burner manufacturer's installation manual furnished with the boiler.
D. Turn boiler on and verify that fuel valves are
closed during the burner pre-purge cycle. Turn boiler off and disconnect power.
E. Adjust burner according to the burner
manufacturer's specications. Target CO2 level is 13% for optimum efciency, but a range of
12.5-13.0% is acceptable.
4. TEST CONTROLS
Before installation of the boiler is considered complete the operation of the boiler controls should be checked, particularly the low water cutoff and the high limit control.
16
Avant que l’installation de la chaudière soit considérée
comme terminée, vérier le fonctionnement de ses
dispositifs de contrôle, en particulier les interrupteurs à bas niveau d’eau et le contrôleur de température maximale.
A. Check Operating Control Raise and lower
operating control setting as required to start and stop burner.
B. Warning Check High Limit Control
Jumper Operating Control Terminals. Allow Burner to operate until shut down by limit. Installation is not considered complete until this check has been made. REMOVE JUMPER.
C. Check Low Water Cut-Off control with water
level at normal waterline. Raise operating control setting to allow burner to operate. Open boiler drain to allow water level to drop until burner operation is shut down by low water cutoff.
DO NOT ALLOW THE BOILER TO OPERATE BELOW THE MINIMUM PERMISSIBLE WATER LEVEL AS INDICATED ON THE BOILER.
NE PAS LAISSER LA CHAUDIÈRE FONCTIONNER LORSQUE LE NIVEAU D’EAU EST PLUS BAS QUE LE SEUIL INDIQUÉ SUR LA CHAUDIÈRE.
Close boiler drain and rell to normal water line.
Unless boiler is equipped with a manual reset low water
cutoff, burner should automatically restart during ll.
Reset operating control.
PROBE AND FLOAT TYPE LOW WATER CUT-OFF DEVICES REQUIRE ANNUAL INSPECTION AND MAINTENANCE. Refer to Service Instructions, Section IV for proper cleaning instructions.
LES INTERRUPTEURS À BAS NIVEAU D’EAU DE TYPE SONDE ET DE TYPE FLOTTEUR DOIVENT ÊTRE INSPECTÉS ET ENTRETENUS ANNUELLEMENT. Se reporter aux directives sur l’entretien, à la section IV, pour connaître les directives de nettoyage adéquat.
D. Check Operating Control on boiler equipped
with a tankless heater. With burner off, draw hot water until burner starts, then turn off hot water and check burner shut down.
5. CLEANING A NEW STEAM BOILER
Oil, grease & sediments which accumulate in a new boiler and piping must be removed from the system in order to prevent an unsteady water line and carryover of the water into the supply main above the boiler. Operate the boiler with steam in the entire system for a few days allowing the condensate to return to the boiler. If the condensate can temporarily be wasted, operate the boiler only for the length of time it takes for condensate to run clear. If the latter cannot be achieved or if the condensate is returned to the boiler, boil out the boiler using the SURFACE BLOWOFF connection on the boilers so equipped.
A. Drain boiler until water is just visible in gauge
glass. Run temporary pipe line from the surface blow-off to an open drain or some other location where hot water may be discharged safely.
Do not install valve in this line. Certain state and local codes may restrict
the use of some chemicals listed for cleaning and maintaining the boiler. Check with local authorities before proceeding with the use of any chemicals.
B. Drain about 5 gallons of hot water from boiler into
a container and dissolve into it 1 pound o caustic soda and one pound of trisodium phosphate for each 50 gallons of boiler water. Additional
containers may be required to dissolve sufcient
chemicals for large models. Remove safety valve
and add solution to boiler water through exposed
tapping.
Use extreme care in handling these chemicals.
Caustic soda is harmful to skin, clothing and eyes. Do not permit the dry material or the concentrated solution to come into contact with the skin or clothing.
C. Close all valves leading to and from the system to
isolate the cleaning solution from the system.
D. Start Burner and operate sufciently to boil the
water without producing steam pressure. Boil for
about 5 hours. Open boiler feed pipe sufciently
to permit a steady trickle of water from the surface blowoff pipe. Continue this slow boiling
and trickle of overow for several hours until the water coming from the overow is clear.
E. Stop burner and drain boiler in a manner and
location that hot water can be discharged safety.
F. When the boiler has cooled to 120°F or less rell
boiler to normal water line. If water in gauge glass does not appear to be clear, repeat steps A thru E, boiling out the boiler for a longer time.
G. Remove temporary piping, plug tapping and/or
reinstall safety valve. Boil to bring water
temperature to 180ºF promptly in order to drive
off any dissolved gases in the fresh water.
6. CLEANING A WATER BOILER
The oil and grease which accumulate in a new hot water boiler can be washed out in the following manner.
A. Remove safety relief valve using extreme care to
avoid damaging it.
17
Certain state and local codes may restrict the use of some chemicals listed for cleaning and maintaining the boiler. Check with local authorities before proceeding with the use of any chemicals.
L’utilisation de certains des produits chimiques indiqués pour le nettoyage et l’entretien de la chaudière peut être restreinte par les codes municipaux ou provinciaux. Il convient de s’informer auprès des autorités locales avant de procéder à l’utilisation de tout produit chimique.
B. Drain about 5 gallons of hot water from boiler into a container and dissolve into it 1 pound of caustic soda and one pound of trisodium phosphate for each 50 gallons of boiler water.
C. Add solution through exposed tapping, and
reinstall safety valve.
D. Fill the entire system with water. E. Start ring the boiler. F. Circulate the water though the entire system. G. Vent the system, including the radiation. H. Allow boiler water to reach operating
temperature, if possible.
I. Continue to circulate the water for a few hours. J. Stop ring the boiler. K. Drain the system in a manner and to a location
that hot water can be discharged safely.
L. When the boiler has cooled down to 120°F or
less, remove plugs from all available returns and wash the water side of the boiler as thoroughly as possible, using a high-pressure water stream.
M. Rell the system with fresh water, and bring
water temperature to 180°F promptly in order to drive off any dissolved gases.
7. WATER BOILER OPERATION
The following guidelines relating to system water
temperature uctuation and ow through boiler must be
observed.
A. It is important to operate your boiler in such a
manner as to prevent temperature uctuation of
more than 40°F at any time. Rapid temperature changes within the boiler can create stresses in the boiler metal. These stresses can cause damage to the boiler by loosening tubes, or in more severe instances can crack tube sheet ligaments, furnaces, or waterlegs.
B. It is equally important to insure that there is
circulation through the boiler of at least 1/2 GPM/ BHP at all times when the boiler is ring.
8. BOILER WATER TREATMENT
Boiler water treatment will help maximize the
effectiveness and prolong the life of pressure vessels.
The general objectives of boiler water treatment are:
A. Remove corrosive gases from feedwater and
boiler water.
B. Prevent sludge and scale deposits on the water
side heating surfaces.
C. Prevent foaming and carryover.
Consult with a local water treatment company regularly engaged in the treatment of boiler water for advice in maintaining the proper feedwater, boiler water, and condensate chemistry.
Pour obtenir des conseils sur le maintien d’une composition chimique adéquate pour l’eau d’alimentation, l’eau de la chaudière et le condensat, consulter le personnel d’une station de traitement des eaux locale qui traite régulièrement des eaux de chaudière.
Certain state and local codes may restrict the use of
some chemicals listed for cleaning and maintaining the boiler. Check with local authorities before proceeding with the use of any chemicals.
9. MAKE PH OR ALKALINITY TEST
After boiler and system have been cleaned and
relled as previously described, test the pH of the water
in the system. This can easily be done by drawing a small sample of boiler water and testing with hydrion paper which is used in the same manner as litmus
paper, except it gives exact readings. A small color chart
on the side of the hydrion dispenser gives the reading
in pH. Hydrion paper is inexpensive and obtainable
from any chemical supply house or through your local druggist. The pH should be higher than 8.3 but lower than 10.5. Add some washout chemical (caustic soda), if
necessary, to bring the pH within the specied range.
10. FREQUENT WATER ADDITION
If, during normal operation, it is necessary to add water
more frequently than once a month, consult a qualied
service technician to check your system for leaks.
S’il est nécessaire d’ajouter de l’eau plus d’une fois par mois à une chaudière utilisée normalement, consulter un
technicien d’entretien qualié an de vérier la présence
de fuites dans votre système.
A leaky system will increase the volume of make-up
water supplied to the boiler which can signicantly
shorten the life of the boiler. Entrained in make-up water
are dissolved minerals and oxygen. When the fresh,
cool make-up water is heated in the boiler the minerals
18
fall out as sediment and the oxygen escapes as a gas.
Both can result in reduced boiler life. The accumulation of sediment can eventually isolate the water from contacting the cast iron. When this happens the cast
iron in that area gets extremely hot and eventually cracks. The presence of free oxygen in the boiler creates
a corrosive atmosphere which, if the concentration becomes high enough, can corrode the cast iron through from the waterside. Since neither of these failure types are the result of a casting defect the warranty does not apply. Clearly it is in everyone’s best interest to prevent this type of failure. The maintenance of system integrity is the best method to achieve less makeup water.
Oxygen contamination of the boiler water will cause corrosion of iron and steel boiler components, and can lead to boiler failure. Burnham’s standard warranty does not cover problems caused by oxygen contamination of boiler water or scale (lime) build-up caused by frequent water addition or by improper water chemistry as shown below.
Une contamination de l’eau de la chaudière par l’oxygène provoque la corrosion des composants en fer et en acier, et peut mener à une défaillance. La garantie standard de Burnham ne couvre pas les problèmes causés par la contamination de l’eau de la chaudière par l’oxygène ou l’accumulation de tartre (calcaire) qui découlent de l’ajout fréquent d’eau ou d’une composition chimique inadéquate comme illustré ci-dessous.
In order to ensure long product life, oxygen sources should be eliminated. This can be accomplished by taking the following measures:
A. Repairing system leaks to eliminate the need for
addition of make-up water.
B. Eliminating open tanks from the system. C. Eliminating and/or repairing ttings which allow
oxygen absorption.
D. Use of non-permeable materials in the distribution
system.
E. Isolating the boiler from the system water by
installing a heat exchanger.
Minimum Water Quality Requirements
pH - 8.3 - 10.5
TDS - 3500 ppm
Total alkalinity ppm as CaCO
Total copper ppm - .05
Oily matter ppm -1
total harness ppm -3 Chlorides - < 50 ppm
There are many possible causes of oxygen contamination such as:
A. Addition of excessive make-up water as a result
of system leaks.
B. Absorption through open tanks and ttings. C. Oxygen permeable materials in the distribution
system.
D. Suction at pump and valve seals.
- 1200
3
19
SECTION IV — SERVICE INSTRUCTIONS
See item 10 under Operating Instruction if it becomes necessary to add water to the boiler more frequently than once a month.
Se reporter à l’article 10 dans la section Instructions de fonctionnement si le remplissage de la chaudière devient nécessaire plus d’une fois par mois.
1. GENERAL Inspection should be conducted annually. Service
as frequently as specied in paragraphs below. Before
service or maintenance is performed complete boiler
shutdown/cooldown procedure.
2. BOILER SHUT DOWN AND COOLDOWN PROCEDURE
NOTE: This procedure is generally required in
preparation for corrective or preventative maintenance in the unit. This procedure must be supervised by an
individual who is thoroughly qualied in operation and
maintenance of the equipment at hand. This is written with Steam Boilers in mind, but the principles are applicable to Hot Water Boilers as well.
A. Decrease plant load as much as possible. B. Turn boiler switch off. If control power from
burner is used to support accessories, leave on until boiler system has cooled down.
C. Shut and lock manual gas and oil valves as
applicable.
D. In single boiler installations, some small steam
loads can remain on to assist in a controlled cooldown of the boiler (i.e., deaerator). In multiple boiler installations, shut down the non-return valve and the back up valve. Lock them shut.
E. Allow the boiler feed pump to remain active. As
the boiler cools down, the water level is reduced by demand or shrinkage. It is best to be aware of the boiler level at all times.
F. When boiler pressure has decreased to 5 to
10 psi on the pressure gauge, open the boiler manual vent valve on the top of the boiler. This is to act as a sentinel against the increase in pressure and to prevent the boiler from going into a vacuum. Lock the valve open.
NOTE: Depending on the size of the boiler, the large mass of heating surfaces that are still hot can cause the boiler water temperature to increase, even if the gauge pressure is “0”. It is better to allow the entire system to cool gradually, never force cool the boiler as damage
can also be inicted due to “thermal shock.”
G. When boiler and water are below 120°F, shut off
power to the unit and lock out the circuit breakers.
H. If required, open front and rear doors for
3. CLEAN THE BOILER HEATING SURFACES
AND FLUE
At least once each year, preferably at the end of the heating season.
Remove all accumulations of soot with a wire brush and vacuum. Remove all obstructions. Replace deteriorated parts and support properly. Seal all joints.
observation of reside surfaces.
I. Drain boiler down as far as required. (Usually
completely.) Make sure the vent valve on the top of the boiler remains open. Open and lock the
oat control low water cutoff drain valves. These
will serve as additional vents.
J. Shut and lock the boiler feed valves, and any
blowdown valves that can be affected by other boilers in the same facility (i.e., bottom blow down valves can tie into a common blowdown separator in a multiple boiler installation).
K. If necessary to remove handhole and/or manhole
plates for water side inspection or maintenance,
use extreme caution. Loosen the nuts securing
the arch enough to allow the plate to drop
approximately 1/8 inch when tapped loose with
a mallet. Once again, ensure the pressure in the boiler is “0” before loosening the plate. Remove the plate the remainder of the way. Wear gloves and eye protection at all times.
A. Clean the Vent System
Vent system should be checked annually for:
1. Obstructions.
2. Accumulations of soot.
3. Deterioration of vent pipe or vent accessories due to condensation or other reasons.
4. Proper support no sags, particularly in horizontal runs.
5. Tightness of joints.
B. Clean the Boiler Heating Surfaces
At the end of the heating season, clean boiler
heating surfaces thoroughly. Access to boiler
retubes may be gained by removing the front and rear smokeboxes or smokebox doors.
Where applicable, remove the turbulators, paying close attention to which tubes have turbulators.
20
Clean retubes with ue brush and reinstall
turbulators. If turbulators are corroded or deteriorated, replacing them will ensure a high
level of boiler efciency. Remove soot and rust
and reseal the boiler.
Turbulator quantities are shown below. Access to
turbulator replacement is from the front smokebox.
Turbulators should be installed and removed from the front of the boiler only.
Series 4FH: All 4FH Series boilers come equipped
with turbulators in all third pass tubes (upper rows of tubes), with quantities as follows:
1. Sizes 63A/107A quantity of (18).
2. Sizes 127A/209A quantity of (22).
3. Sizes 240A/345A quantity of (40).
4. Sizes 360A/450A quantity of (46).
5. Sizes 563A/675A quantity of (56).
6. Sizes 827/993 quantity of (54).
7. Sizes 1157/1323 quantity of (72).
8. Size 1654 quantity of (93).
9. Size 1985/2315 quantity of (109).
10. Size 2645 quantity of 113.
11. Size 3075A quantity of (151).
4. BOTTOM BLOWDOWN PROCEDURE
Burnham high pressure steam boilers are equipped with two bottom blowdown connections. Bottom blowdown should be done while the boilers are under
pressure, with the burner off or at low re. There should
be two quick-opening valves and one downstream
slow-opening valve. Open the slow-opening valve rst.
Slowly open the front quick-opening valve to warm up the piping and blowdown separator. Open the valve for
a few seconds with a quick blast to ush out sludge and
sediment from the bottom of the boiler. Do not lower the boiler water level by more than ½". Close the valve, then repeat for the rear quick-opening valve. Close the slow­opening valve. Make sure all valves are closed. A water treatment consultant can recommend an appropriate manual blowdown schedule, but is generally done once per shift.
Water columns should be blown down once per shift to keep the internal parts of the pump control and low water cutoff free from sediment. If the boiler is equipped with a “water column bypass” switch, depress the switch while performing the blowdown. Close the valve and release the switch.
5. MAINTENANCE OF LOW WATER CUTOFF DEVICES
Probe and oat type low water cutoff devices require annual
inspection and maintenance.
Les interrupteurs à bas niveau d’eau de type sonde ou
de type otteur doivent être inspectés et entretenus
annuellement.
A. Probe Type Low Water Cut Off Although these
devices are solid state in design, the probe is
exposed to possible contamination in the boiler
water.
It is important to physically remove the probe from the boiler tapping annually and inspect it for accumulation of scale or sediment.
Following these steps inspect, clean and/or
replace the probe:
1. Turn off electric service to the boiler.
2. Drain boiler water to a level below the tapping for the probe.
3. Disconnect the wiring connections between the low water cutoff and the probe.
4. Dismount the low water cutoff control from the probe.
5. Unscrew the probe from the boiler tapping.
6. Inspect that portion of the probe that is
exposed to the boiler water for scale or
sediment buildup.
7. Light deposits may be removed by wiping the probe with a damp cloth. Wiping the probe with a cloth soaked in vinegar will remove more tenacious lime deposits. The most stubborn deposits may be removed from the probe by using diluted amount (3 part of water to 1 part) of phosphoric acid (H2PO4).
21
Exercise caution when handling phosphoric acid and follow the instruction label on its container.
Faire preuve de prudence lors de la manipulation d’acide phosphorique et suivre les directives qui se trouvent sur l’étiquette du contenant.
8. Wire brushing of the probe is not recommended.
9. Clean the pipe threads of the probe to remove old, hardened pipe dope and other foreign matter.
10. Apply a moderate amount of good quality pipe dope to the pipe threads on the probe, leaving
the rst two threads bare. Do not use PTFE (Teon) tape.
11. Screw the probe into the boiler tapping.
12. Mount the low water cutoff control on the probe.
13. Reconnect the control to probe wiring.
14. Fill the boiler to its normal waterline.
15. Add boiler water treatment compound as needed (see Section III Item 8).
16. Restore electric service to boiler.
17. Fire burner to raise water temperature to
above 180°F to drive off free oxygen.
when this type of control is used. Check the oat for
evidence of collapse and check mercury bulb (where applicable) for mercury separation or discoloration. DO NOT ATTEMPT TO REPAIR MECHANISM IN THE FIELD. Complete replacement mechanisms, including necessary gaskets and installation instructions, are available from the manufacturer.
6 SURFACE BLOWDOWN PROCEDURE
The purpose of the Surface Blowoff connection is to provide a means to remove impurities that collect near the surface of the water level on steam boilers, and to bleed off a small portion of the boiler water to lower the level of TDS (total dissolved solids). This will decrease boiler foaming and improve steam quality.
The following Surface Blowoff connections are provided as standard:
A. Series 4FH: Sizes 63 thru 345, (1) tting left side
of boiler, sizes 360 thru 3075, (1) tting right side
of boiler.
B. The amount and frequency of surface blowoff is
based on the amount of TDS you are targeting, the amount of make-up water, and the amount of TDS in the make-up water. The following is an
example for a 250hp steam boiler:
1. Approximate evaporating rate at full capacity: 250 bhp x 34.5 = 8625 lb/hr
2. Make-up water (i.e. 20%): 1725 lb/hr
BEFORE RETURNING BOILER TO SERVICE: Follow the low water cutoff check out procedure in Section III Item 4 Part C.
AVANT DE RETOURNER LA CHAUDIÈRE POUR UN
ENTRETIEN : Suivre la procédure de vérication du
dispositif de coupure du combustible en cas de bas niveau d’eau de la section III, article 4, partie C.
B. Float Type Low Water Cut-Off During the
heating season, if external low water cutoff is on
the boiler, the blow off valve should be opened once a month (use greater frequency where
conditions warrant), to ush out the sediment
chamber so the device will be free to function properly.
Low water cutoffs and water feeders should be
dismantled annually by qualied personnel, to the extent necessary to insure freedom from obstructions
and proper functioning of the working parts. Inspect connecting lines to boiler for accumulation of mud, scale,
etc., and clean as required. Examine all visible wiring
for brittle or worn insulation and make sure electrical contacts are clean and that they function properly. Give
special attention to solder joints on bellows and oat
3. TDS of make-up water (i.e.): 400 ppm
4. Max TDS recommended in the boiler water:
3500 ppm
5. Reduction factor: 3500/400 = 8.75
6. Surface blowoff rate: 1725 / 8.75 = 197 lb/hr x hr/60 min x gal/8.34 lb = .4 gpm
In this example .4 gpm would be the continuous
blowdown rate to keep the boiler water TDS at 3500
ppm. This is a good starting point and may need ne
adjustment during actual operation.
7. CHECK BURNER AND CONTROLS at least
once a year. See Item 4 under Operating Instructions for control checks. See Burner Manual for burner tests and adjustments.
8. LUBRICATE BOILER COMPONENTS according
to manufacturer’s instructions. Generally, this involves burner and circulator.
9. CHECK SAFETY VALVE at the start of each
heating season and once or twice during the season to be sure it is in working condition. To do this, fasten wire or cord to the lever of the valve and pull the lever standing a safe distance away from the valve.
22
10. ATTENTION TO THE BOILER WHILE NOT IN OPERATION.
If a boiler is not used during the winter months, and it is in a place subject to freezing, it must be fully drained to prevent freezing damage.
Si une chaudière est hors fonction durant l’hiver dans un endroit où la température est sujette à descendre sous le point de congélation, il convient de la purger entièrement
an de prévenir l’endommagement par le gel.
A. Steam Boilers Procedure for taking steam
boilers off line at the end of heating season: Drain off boiler water until it runs clear while holding the boiler temperature between 180
and 200ºF. Then rell to top of gauge glass.
B. Water Boilers Since a water boiler is a
closed system, no draining/relling should be
necessary.
C. Note any time raw water is introduced into the
boiler it must be immediately heated to 180°F to drive off dissolved gases. If water treatment
is used, sufcient water treatment compound
should be added to condition the make-up water.
11. REPAIR PARTS
Give boilers series and model number when ordering repair parts. All repair parts can be ordered through your local representative or call us at 888-791-3790.
23
PERIODIC TESTING RECOMMENDED CHECK LIST
ITEM FREQUENCY ACCOMPLISHED BY REMARKS Gauges, monitors, and Daily Operator Make visual inspection and
indicators record readings in log
Instrument and equipment Daily Operator Make visual check against settings recommended specications
Firing rate control Weekly Operator Verify factory settings
Semi-annually Service Technician Verify factory settings Annually Service Technician Check with combustion test
Igniter Weekly Operator Make visual inspection, check
ame signal strength, if on
display (see "combustion safety controls)
Fuel Valves Pilot and Main Weekly Operator Open limit switch - make aural
and visual check - check valve position indicators and check
fuel meters if so tted
Pilot and Main Annually Service Technician Perform leakage tests - refer to Gas or Oil burner instructions
Combustion Safety Controls Flame Failure Weekly Operator If ame display installed, read
and log; for both pilot and main
ames, notify service
organization if readings are very high, very low or
uctuating; refer to burner
instructions.
Flame Signal Strength Weekly Operator If ame display installed, read
and log; for both pilot and main
ames, notify service
organization if readings are very
high, very low, or uctuating;
refer to burner instructions.
Pilot Turndown Tests As required/ Service Technician Required after any adjustments Annually to ame scanner mount or pilot
burner; verify annually - refer to burner instructions
Low Water Fuel Daily/Weekly Operator Refer to control instructions Cutoff and Alarm Semi-annually Operator Perform a slow drain test in
accordance with ASME Boiler and Pressure Vessel Code Section VI
High Limit Safety Control Annually Service Technician Refer to control instructions
Operating Control Annually Service Technician Refer to control instructions
Air Proving Switch Monthly Operator Refer to burner instructions
24
PERIODIC TESTING RECOMMENDED CHECK LIST
ITEM FREQUENCY ACCOMPLISHED BY REMARKS Atomizing Air/Steam Annually Service Technician Refer to burner instructions
High and Low Gas Monthly Operator Refer to burner instructions Pressure Interlocks
High and Low Oil Monthly Operator Refer to burner instructions Pressure Interlocks
High and Low Oil Monthly Operator Refer to burner instructions Temperature Interlocks
Fuel Valve Interlock Annually Service Technician Refer to burner instruction Switch
Purge Switch Annually Service Technician Refer to burner instructions
Burner Position Interlock Annually Service Technician Refer to burner instructions
Low Fire Start Interlock Annually Service Technician Refer to burner instructions
Automatic Changeover At Least Annually Service Technician Under supervision of gas utility Control (dual fuel)
Safety Valves As required Operator In accordance with procedure in
Section VI, ASME Boiler and Pressure Vessel Code, Recommended Rules for Care and Operation of Heating Boilers or Section VII for power boilers.
Inspect Burner Components Semi-annually Service Technician Refer to burner instructions Boiler Hydro-Test Annually Service Technician Performed as required, in
accordance with NBIC Part 2,
not to exceed 90% of relief
valve setting.
25
26
27
Commercial Boilers
LIMITED WARRANTY
LIMITED WARRANTY
Subject to the terms and conditions herein, Seller warrants to the original owner at the original installation site that products manufactured by Seller (“Products”) comply, at the time of manufacture, with recognized hydronics industry regulatory agency standards and requirements therein effect and will be free from defects in materials and workmanship for a period of 12 months after the date of start-up or 18 months after the date of shipment, whichever shall be less (the “Warranty Period”)
REMEDY
A. The sole remedy for breach of this warranty is
expressly limited to the repair or replacement of any
part found to be defective under conditions of normal use within the Warranty Period. Installation is not included.
B. Warranty The owner must notify the original installer of the Product and Seller (Attention: Burnham
Commercial, PO Box 3939, Lancaster, PA 17604) in
writing, within the Warranty Period, providing a detailed description of all claimed defects. Transportation to a factory or other designated facility for repairs of any products or items alleged defective shall, in all events, be the responsibility and at the cost of the owner.
E. The suitability of any Product for any particular application.
F. Any failure resulting from misuse, modication, not
authorized by Seller in writing, improper installation or lack of proper maintenance.
G. Equipment furnished by the owner, either mounted or unmounted, or when contracted for by owner to be installed or handled.
Seller’s liability under this warranty shall not in any case
exceed the amount paid for the Product found defective.
THIRD-PARTY WARRANTIES
For goods or components not manufactured by Seller, the warranty obligations of Seller shall, in all respects, conform
and be limited to the warranty actually extended to Seller by
its vendors.
SEVERABILITY
To the extent that any provisions of this warranty would be
void or prohibited under applicable law, such provisions
shall be limited in effect to the minimum extent necessary to
render the remaining provisions hereof enforceable.
EXCLUSIONS
Seller shall have no liability for: A. Incidental, special or consequential damages, such as loss of the use of products, facilities or production,
inconvenience, loss of time or labor expense involved
in the repairing or replacing of the alleged defective Product.
B. The performance of any Product under conditions varying materially from those under such Products is usually tested under industry standards as of the shipment time.
C. Any damage to the Product due to abrasion, erosion, corrosion, deterioration, abnormal temperatures or the
inuence of foreign matter or energy.
D. The design or operation of owner’s plant or equipment or of any facility or system of which any Product may be made a part.
28
NO OTHER WARRANTIES
Seller makes no implied warranty of merchantability or
tness for a particular purpose, or other warranties with respect to any products or services except as expressly set
forth in this limited warranty.
Form No. 81460434 - 2/17
Printed in the U.S.A.
Lancaster, PA 17601
Phone: 888-791-3790
www.burnhamcommercial.com
Loading...