Burkert SE30EX User Manual

INTRINSIC SAFETY
ZA de Mijelane - 33650 SAUCATS - FRANCE
Tél :+33..5.57.97.17.99 - Fax :+33.5.56.72.22.10
http ://www.ap3.fr - e-mail:ap3.mail@ap3.fr
A puissance 3 mesure industrielle
NAEV30-DI2 or DI4
Digital signals (ON/OFF)
2 or 4 channels, intrinsic safety digital inputs: Proximity detectors NAMUR, contacts…
773
rail mount on hat profile 35 mm
ATEX 94/9/CE
all connections by removable screw terminals
ready made wiring system (see option leaflet)
Digital inputs
Each of the 4 x I.S. inputs can be configured independently for a contact or a proximity detector NAMUR as per DIN 19234. Excepted DI4C type dedicated to contacts only.
I.S. inputs
Proximity detector NAMUR as per DIN 19234 or free potential contacts, relays, pressure or temperature switches or push buttons in hazardous area.
Non I.S. recopy outputs
According to the type of sensor and the chosen logic: a green LED on the front panel, in standard output, a free-potential contact for each channel without common wire. Optional open collector output on NAEV30-DI2. Cut-off power : 230 VAC – 0.5 A –120 VA Collector cut-off power:15V – 60 mA – 0.9 VA –350 Hz
Selection of the sensor type
Inductive / capacitive I.S. certified NAMUR proximity detector or free-potential contacts.
Selection of the logic
By a mini-DIP choose of the active output in presence or lack of target (proximity detector) or when contact is NO (Normally Open) or NC (Normally Closed).
Fault detector
For all inputs configured as NAMUR, all models (excluding DI4C) give a fault detector – broken line or short-circuit. In faulty case, the green front LED switches off and the red LED corresponding to the defective channel switches on. Other channels are not affected.
NAEV30 series
Other models enable the control of binary outputs (1, 2 or 4) and complete ON/OFF valve function (1 output + 2 inputs).
References NAEV30 - (1) -(2) - (3) / (4)
Supply (2)
NAEV30-
(1) : Type (2) : alimentation (3) : sortie (4) : option
inputgfunction 230Vac 115Vac 24Vdc relay collector
2 NAMUR or contact DI2N A230 A115
4 NAMUR or contact DI4N A230 A115 4 contact DI4C A230 A115 2 NAMUR or contact input with 2 output relay per channel Draining calories Example : NAEV30-DI4N-A230-0
This material bears CE mark according to directive 89/336/CEE. It complies with standards EN 50081-2 and EN50082-2. Complementary tests based on other standards and physical requirements have been carried out on several products. For more information call our technical department.
DI4N A230 A115
Power supply and connections
According to model: 230 VAC (A230) or 115 VAC (A115) +/-10% and 24 VDC +/-10% (C024) consumption 5 VA. 1 front panel yellow LED is “ON” when supply is active. All connections by removable screw terminals. Supply distribution by mean of a flat cable from one unit to the next one. This flat cable is in standard delivery.
Classification for explosive areas
NAEV30 is an intrinsic safety associated apparatus. It must be installed in safe area and connected to materials installed in zone 0, 1 or 2 - gas (G) or in zone 20, 21 or 22 - dust (D). Classification according to ATEX 94/9/CE:
I/II (M1)/(1) G/D [EEx ia] IIC Safety parameters see EC-type certificate LCIE 00ATEX 6034X Ambient operating temperature : -20°C to +60°C Recommended operating temperature : -20°C to +50°C Storage temperature : -40°C to +80°C
Dimensional and mechanical
Housing for symmetric DIN rail (hat profile 35 mm as per standard NFC63015 / EN50022) - Depth : 120 mm Width on rail 29.5mm. Height: 90 mm – 145 mm overall including space for cables. Minimal distance between rails: 180 mm opposite mount.
Conditions of installation
- Mounting NAEV30 series on DIN rail must take in account thermal
dissipation and risk of overheating generated by housings installed side by side. In case of a high concentration of NAEV30, we recommend to leave a free space of 10 mm between each group of 8 units (horizontal rail) and between each group of 4 units (vertical rail).
- Mounting in a cabinet: In this case, it is recommended to close the electrical cabinet and to ensure a circulation of fresh air even by mean of an air conditioner to keep the inside temperature at a level compatible with the recommended operating temperature among the units
impossible
X
A230: 230 V 50 Hz A115: 115 V 50 Hz
C024 0 P C024 0 P C024 0 X C024 0
P
SPD
HT
C024: 24VDC
Output (3)
P: Open collector output O: relay output
EXPLOSIVE ATMOSPHERES
EXPLOSIONSGEFAHRDETE BEREICHE
ATMOSPHERES EXPLOSIBLES
773
ATMOSPHERES EXPLOSIBLES
EXPLOSIVE ATMOSPHERES
EXPLOSIONSGEFAHRDETE BEREICHE
SELECTING the TYPE of DETECTOR and the LOGIC
To select the type of detector and the logic, remove the front panel.
NAEV30-DI2N or DI4N or DI4C
A mini-Dip enables the selection of the sensor for each channel (excepted for the –DI4C model, which has no sensor choice). The fault detector function is activated:
- in the inductive / capacitive position
- deactivated in the contact position
CARE! Connecting a contact in explosive area when a proximity
switch is configured on NAEV30-DI2N (or DI4N) will give permanent fault detection! In the opposite using proximity switch in hazardous area when a simple contact is configured will inhibit the fault detection! The logic to choose the relay active position is done channel per channel.
terminal
ALIM.
POWER SUPPLY
N A E V 3 0
This equipment has a 1-year warranty including parts and labour for all materials returned in our factory. Even when the warranty period is over, only A puissance 3 has the authority to modify and repair a certified electrical component or material for hazardous atmospheres of its own production and covered by a certificate of conformity or an EC-type examination certificate. Should this clause not adhered to, will A puissance 3 no longer be held liable for any non-conformity noticed a posteriori.
supply
line version
LNL
N
24VDC version
+_+
_
Care
POWER SUPPLY CONNECTION
DI2N
LOGIQUE
RELAIS:
AV: inductif
B A AR: contact
-capacitif
B
ON
A
ON : inductif
capacitif
OFF: contact
DETECTEUR
DI4N
ON
capteur
A
logique capteur
B
logique
capteur
C
logique capteur
D
logique
Capteur
ON : NAMUR
OFF: contact
Logique du relais
de sortie
ON : normal
OFF: inverse
DI4C
CHOIX DE LA
LOGIQUE
PAR VOIE
VOIE A
A
VOIE B
B
VOIE C
C
VOIE D
D
RELAIS :
Contact ouvert
AV
{
Présence cible Contact fermé
AR
{
Absence cible
Power distribution by mean of plug-in jumpers from one unit to its neighbour (AC or 24 VDC). All connectors are removable
!
All units are equipped with 2 terminal blocks to dispatch the auxiliary power supply: in orange colour for net supply (L N) or in black colour for 24 VDC (+ -). One block for input and one block to make a bridge to the next unit by mean of a flat cable supplied in standard. To avoid electrical chocks, all these connectors must always be obturated. If only one of the 2 terminal blocks is used (without giving supply to the next unit), the second block must be filled by the 3-points empty cap delivered in standard. Cable-layer should connect power supply wires and jumpers on both ends of the line of interfaces
Models – Functions Synoptic
on I.S. side On safe side
NAEV30-DI2N and NAEV30-DI2H
2 inputs NAMUR or contact with hysteresis option (DI2H) or w/o (DI2N).
hazarous area
safe area
Dedicated to contacts, valve position feedbacks, temperature or pressure switch, push buttons. Option P: safe side output with open collector Possibility to connect a common wire ‘+
IS side
A
a
NAEV30-DI2N
B
safe side
b
for 2 channels (3 wires instead of 4).
NAEV30- DI4N :4 inputs NAMUR or contact NAEV30-DI4C : 4 inputs contact
Dedicated to contacts, valve position feed back, temperature or pressure switches, push buttons. Option P: safe side output with open collector (Excepted for –DI4C)
Possibility to connect a common wire ‘+’ for 4 channels (5 wires instead of 8).
On NAEV30-DI4N/SPD, only A et C channels are connected, output relays are r respectively a and b for channel A, c and d for channel C.
hazardous area
D
D
safe area IS side
A
B
C
NAEV30-DI4N
safe side
IS side
D
A
B
NAEV30-DI4C
C
safe side
a
b
c d
a
b
c d
NAEV30-DI4N or DI4C
A puissance 3 mesure industrielle - ZA de Mijelane - 33650 SAUCATS - FRANCE
Tél :+ 33.5.57.97.17.99 - Fax :+33.5.56.72.22.10 - http ://www.ap3.fr - e-mail:ap3.mail@ap3.fr
Connection
- B +
- A +
B
A
Contact sec Namur, ...
- B +
B
+
D
+
Contact sec Namur, ...
- D +
+ +
SI
+ +
SI
NAEV30 - DI2N
NAEV30-DI2N
- A +
- C +
A C
L
L
N
N
+ b -
+ a -
L
ALIM.
~
POWER SUPPLY
N
a
+
NAEV30 - DI2N
+
b
NAEV30-DI2N
L
N
+ a -
+ c -
- B +
L
ALIM.
~
POWER SUPPLY
N
a b
+ +
- A +
c
+
NAEV30-DI4N or -DI4C
NAEV30 - DI2N
NAEV30-DI.ang-0502
Contact sec
SI
Namur, ...
230Vac
115Vac
L
N
+ b -
+ d -
d
+
230Vac 115Vac