Type S020
About these operating instructions
1. ABOUT THESE OPERATING
INSTRUCTIONS
These operating instructions describe the entire life cycle of the fitting.
Please keep these operating instructions in a safe place, accessible to
all users and any new owners.
These operating instructions contains important safety
information.
Failure to comply with these instructions can lead to hazardous
situations.
• These operating instructions must be read and understood.
1.1. Symbols used
danger
Warns against an imminent danger.
• Failure to observe this warning can result in death or in serious
injury.
Warning
Warns against a potentially dangerous situation.
• Failure to observe this warning can result in serious injury or
even death.
attention
Warns against a possible risk.
• Failure to observe this warning can result in substantial or minor
injuries.
note
Warns against material damage.
• Failure to observe this warning may result in damage to the
fitting or system.
Indicates additional information, advice or important
recommendations.
Refers to information contained in this manual or in other
documents.
→ Indicates a procedure to be carried out.
English
5
Type S020
Intended use
2. INTENDED USE
Use of insertion fittings that does not comply with the instructions could present risks to people, nearby installations
and the environment.
• The S020 fitting is intended for installation in a pipe, of an
insertion device.
• Use this fitting in compliance with the specifications and conditions of commissioning and use given in the contractual documents, in these operating instructions and in the user manual for
the device which is inserted into it.
• Safe and trouble-free operation of the fitting depends on its
proper transport, storage and installation, as well as careful
operation and maintenance.
• Only use this fitting as intended.
→ Observe any existing restraints when the fitting is exported.
3. BASIC SAFETY
INFORMATION
This safety information does not take into account:
• any contingencies or occurences that may arise during installation,
use and maintenance of the devices.
• the local safety regulations for which the operating company is res-
ponsible including the staff in charge of installation and maintenance.
Danger due to high pressure in the installation.
Danger due to high temperatures of the fluid.
Danger due to the nature of the fluid.
Various dangerous situations
To avoid injury take care:
• to prevent any unintentional power supply switch-on.
• to ensure that installation and maintenance work are
carried out by qualified, authorised personnel in possession of
the appropriate tools.
• to guarantee a set or controlled restarting of the process, after a
power supply interruption.
• to use the fitting only if in perfect working order and in compliance with the instructions provided in these operating
instructions.
6
English
Type S020
General information
4. GENERAL INFORMATION
Various dangerous situations (cont'd)
To avoid injury take care:
• to observe the general technical rules when installing and using
the fitting.
• not to use this fitting in explosive atmospheres.
• not to use fluid that is incompatible with the materials from which
the fitting is made.
• not to use this fitting in an environment incompatible with the
materials from which it is made.
• not to subject the fitting to mechanical loads (by placing objects
on top of it or by using it as a step, for example).
• not to make any internal or external modifications to the fitting.
note
The fitting may be damaged by the fluid in contact with.
• Systematically check the chemical compatibility of the component materials of the fitting and the fluids likely to come into
contact with it (for example: alcohols, strong or concentrated
acids, aldehydes, alkaline compounds, esters, aliphatic compounds, ketones, halogenated aromatics or hydrocarbons,
oxidants and chlorinated agents).
4.1. Manufacturer's address and
international contacts
To contact the manufacturer of the fitting, use following address:
Bürkert SAS
Rue du Giessen
BP 21
F-67220 TRIEMBACH-AU-VAL
The addresses of our international branches can be found on the
last pages of these operating instructions.
They can also be found on the Internet at: www.burkert.com
4.2. Warranty conditions
The condition governing the legal warranty is the conforming use of
the S020 in observance of the operating conditions specified in this
manual.
4.3. Information on the Internet
You can find the operating instructions and the technical data sheet
regarding the type S020 at: www.burkert.com
English
7
Type S020
Description
5. DESCRIPTION
5.1. Area of application
The S020 fitting simplifies the installation of insertion devices for measuring flow, pH, oxidation reduction potential (REDOX) or conductivity
on DN6 to DN400 pipes.
The fitting S020 is available in various versions for the installation of
measuring devices with a G2'' nut or measuring devices with a clamp
process connection.
The S020 measuring chamber is used:
• on the one hand, to install an insertion device for measuring the
pH, the oxidation reduction potential or the conductivity in a pipe
• and, on the other hand, to guarantee that the measurement sensor
is fully covered by the fluid.
6. TECHNICAL DATA
6.1. Conditions of use
Fluid
temperature
Ambient
temperature
Pressure
class
6.2. Available certificates
• Certificate 3.1, S020 in stainless steel only
• Certificate 2.2
• Surface roughness certificate
• Calibration certificate
• FDA approval (with EPDM seal), S020 in stainless steel only
depends on the device inserted and the material
from which the S020 fitting is made. Refer to the
operating instructions for the device and to the temperature/fluid pressure dependency curve in Fig. 5.
If the ranges are different, use the most restrictive
range.
depends on the device inserted into the S020.
Refer to the related operating instructions.
depends on the device inserted and the material
from which the S020 fitting is made. Refer to the
operating instructions for the device and to the temperature/fluid pressure dependency curve in Fig. 5.
If the pressure classes are different, take the lowest
value into account.
8
English
Type S020
Technical data
6.3. General technical data
6.3.1. Diameters available
The diameters available depend on the design of the S020 fitting.
Consult the technical data sheets for the S020 fittings and
the device inserted to determine the appropriate DN.
Table 1: Diameters available depending on the design of the fitting
Design of the S020DN available
T fittings for measuring devices with
a G2'' nut
T fittings for measuring devices with
a clamp process connection
Welding socket with radius, for measuring devices with a G2'' nut
Plastic fusion spigotDN65 to DN400
Screw-on
1)
Welding socket for measuring
devices with clamp connection
Saddle
1)
1)
Only for the flow measurement.
DN6 to DN65
DN32 to DN100
DN50 to DN350
DN100 to DN400
DN32 to DN100
DN50 to DN200
6.3.2. Materials
Table 2: Materials depending on the design of the S020 fitting
Design of the S020Materials
BodyAdapterSeal
T fittings for measuring devices with a
G2'' nut
T fittings for measuring devices with
a clamp process
connection
Welding socket with
radius, for measuring
devices with a G2''
nut
Fusion spigot
Welding socket
for measuring
devices with clamp
connection
Fig. 2: Dimensions of the measurement chamber (in mm)
41
ø 33.6
80.2
2.70
ø 60
19
English
Type S020
Technical data
6.4. K factors
6.4.1. Terms of reference
The K factors have all been determined under the following terms
of reference: fluid = water, water and room temperatures of 20°C,
minimum upstream and downstream distances respected, appropriate pipe dimensions.
6.4.2. Calculation of K factors (in pulse/
litre) for saddles, fusion spigots,
welding sockets with radius or
screw-ons
The calculation does not apply to T fittings or welding
sockets for measuring devices with a clamp connection.
In addition to the terms of reference mentioned above, the K factors
for saddles, fusion spigots, welding sockets with radius and screwons have been determined as a function of the external diameter
(D
) and the wall thickness (s
material
tables.
) of the pipe given in the
material
→ When the dimensions of the pipe are slightly different from
dimensions D and s given in the tables, recalculate the K factor
using one of the following formulae:
These formulae can only be applied if the dimensions of the
pipe vary by +/-5% compared with the theoretical dimensions given in the tables.
2
d
Kn = Kt x
t
2
d
n
Fig. 3: Fitting used with a paddle-wheel flowmeter
2
d
Kn = Kt x
n
2
d
t
Fig. 4: Fitting used with an electromagnetic flowmeter
Kn = recalculated K factor
= K factor given in the table
K
t
= D
d
t
= internal diameter of the pipe
d
n
material
- 2s
= theoretical internal diameter of the pipe
material
calculated using the values D
s
given in the tables, for each fitting
material
material (D
the pipe and s
pipe)
= external diameter of
material
= thickness of the
material
material
and
20
English
Type S020
Technical data
6.4.3. K factors (in pulse/litre) for T fittings used with a 8041 or 8045 with a G2'' nut
We advise not to use a type 8041 or 8045 measuring device in an S020 fitting in brass as drifts in measurement may occur.
If the measuring device does not automatically convert the K factor, use the following conversion formulae before setting the parameters of the device:
• K factor in pulse/US gallon = K factor in pulse/litre x 3.785
• K factor in pulse/UK gallon = K factor in pulse/litre x 4.546
Two versions of the S020 in DN15 and DN20 exist, having different K factors.
Only version 2, identified by the "v2" marking, is available from March 2012. The "v2" marking can be found:
• on the bottom of the DN15 fitting in plastic:
V2
• on the side of the DN15 or DN20 fitting in metal:
V2
English
21
Type S020
Technical data
Table 16: K factors depending on the connections and standards and materials of the T fittings used with a 8041 or 8045 with G2" nut
6.4.4. K factors (in pulse/litre) for T
fittings and welding sockets used
with a 8041 or a 8045 with clamp
connection
Table 17: K factors of the T fittings for measuring devices with clamp
connection
Type of connection
and standard
acc. to SMS 3008 5.2310.415.924.7acc. to BS 4825 /
ASME BPE
acc. to DIN 11850
range 2
acc. to ISO 4200-----
DN40DN50DN65DN80DN100
5.3310.416.725.750.3
----52.7
6.4.5. K factors (in pulse/litre) for T fittings
used with a 8020, 8024, 8025 or
8026
If the measuring device does not automatically convert the K
factor, use the following conversion formulae before setting
the parameters of the device:
• K factor in pulse/US gallon = K factor in pulse/litre x 3.785
• K factor in pulse/UK gallon = K factor in pulse/litre x 4.546
Two versions of the S020 in DN15 and DN20 exist, having
different K factors.
Only version 2, identified by the "v2" marking, is available
from March 2012. The "v2" marking can be found:
• on the bottom of the DN15 fitting in plastic:
V2
• on the side of the DN15 or DN20 fitting in metal:
V2
Do not use a fitting S020 in sizes DN6, DN8, DN15, DN15
Version 2 (V2) or DN20 Version 2 (V2) with a paddle-wheel
flowmeter types 8020, 8024, 8025, 8026.
English
23
Type S020
Technical data
Table 18: K factors depending on the connections and standards and materials of the T fittings used with a 8020, 8024, 8025 or 8026
When the dimensions of the pipe are slightly different from dimensions D and s given in the table, recalculate the K factor using one of
the formulae in chap. 6.4.2.
If the measuring device does not automatically convert the K factor, use the following conversion formulae before setting the parameters of the device:
• K factor in pulse/US gallon = K factor in pulse/litre x 3.785
• K factor in pulse/UK gallon = K factor in pulse/litre x 4.546
Table 19: K factors, external diameters and theoretical cross-sections of saddles
8020, 8024, 8025, 80268041, 8045External diameters and theoretical cross-sections
PVCPE / PPPVCPE / PP
D
PVC
[mm]
s
PVC
[mm]
D
PP
[mm]
s
PP
[mm]
English
25
Type S020
Technical data
6.4.7. K factors (in pulse/l) of the fusion spigots and welding sockets with radius for
measuring devices with a G2'' nut
When the dimensions of the pipe are slightly different from dimensions D and s given in the table, recalculate the K factor using one of
the formulae in chap. 6.4.2.
If the measuring device does not automatically convert the K factor, use the following conversion formulae before setting the parameters of the device:
• K factor in pulse/US gallon = K factor in pulse/litre x 3.785
• K factor in pulse/UK gallon = K factor in pulse/litre x 4.546
Table 20: K factors, external diameters and theoretical cross sections of the welding sockets with radius, for measuring devices with a G2''
nut, and of the fusion spigots in plastic, used with a 8020, 8024, 8025 or 8026
Measuring device inserted8020, 8024, 8025, 8026External diameters and theoretical cross-sections
(C): short sensor version
(L): long sensor version
D
PVDF
[mm]
s
PVDF
[mm]
English
27
Type S020
Technical data
6.4.8. K factors (in pulse/litre) for screw-ons
When the dimensions of your pipe are slightly different from dimensions D and s given in the table, recalculate the K factor using one
of the formulae in chap. 6.4.2.
If the measuring device does not automatically convert the K factor, use the following conversion formulae before setting the parameters of the device:
• K factor in pulse/US gallon = K factor in pulse/litre x 3.785
• K factor in pulse/UK gallon = K factor in pulse/litre x 4.546
Table 22: K factors, external diameters and theoretical cross-sections of screw-ons
Risk of injury due to high pressure in the installation.
• Stop the circulation of fluid, cut off the pressure and drain the
pipe before loosening the process connections.
Risk of injury due to high fluid temperatures.
• Use safety gloves to handle the fitting.
• Stop the circulation of fluid and drain the pipe before loosening
the process connections.
Risk of injury due to the nature of the fluid.
• Respect the prevailing regulations on accident prevention and safety
relating to the use of hazardous products.
Warning
Risk of injury due to non-conforming installation.
• Fluidic installation can only be carried out by qualified and authorised personnel with the appropriate tools.
• Observe the installation instructions for the measuring device
inserted into the fitting.
Risk of injury due to an uncontrolled restart.
• Ensure that the restart of the installation is controlled after any
interventions on it.
Warning
Risk of injury if the fluid pressure / temperature dependency
is not respected.
• Take into account the fluid pressure / temperature dependency
according to the materials from which the fitting is made (see
Fig. 5) and to the measuring device used (see the relevant user
manual).
• Comply with the Pressure Directive 97/23/EC.
Warning
Danger due to non-conforming commissioning.
Non-conforming commissioning may lead to injuries and damage
the fitting and its surroundings.
• Before commissioning, make sure that the staff in charge have
read and fully understood the contents of these operating
instructions.
• In particular, observe the safety recommendations and intended
use.
• The installation must only be commissioned by suitably trained
staff.
English
29
Type S020
Installation and commissioning
P (bar)
16
15
14
13
12
PVDF
11
10
9
8
PVC + PP
7
6
5
4
3
2
1
0
-200+20 +40 +60 +80 +100 +120
1)
Except DN100 for measuring devices with clamp connection
Metal
(PN16)
PVC (PN10)
PP (PN10)
1)
DN100 for measuring
devices with clamp connection
(PN10)
PVDF (PN10)
+150
T (°C)
Fig. 5: Fluid pressure / temperature dependency curves for T
fittings used on their own
7.2. Installation onto the pipe
7.2.1. Recommandations for installing the
S020 fitting on the pipe
→ To measure the pH or the oxidation reduction potential, install
a U-shaped bypass in order to prevent the electrode drying out
and to allow calibration without stopping the process.
Fig. 6: Bypass installation of the fitting
→ For measuring the flow and depending on the design of the
pipes, respect the minimum distances in accordance with the
standard EN ISO 5167-1, from which the diagrams in Fig. 7 are
excerpted.