Introduction
The generic 8400 controller is delivered without a temperature measuring device. It is up to you:
- to mount the desired 2-wire Pt100 onto the controller
- to calibrate the controller once the Pt100 has been mounted.
Technical data:
- connection wires of the Pt100: 26 AWG multi-conductor, PTFE jacket
- connector between the Pt100 wires and the electronic board: Molex® 90327-3304
- Pt100 : 2 wires; max. cable length = 1 m.
Unscrew to lift the cover
1
G 1/2'' external thread
INTERNAL
Mounting the sensor onto the controller
USE ONLY
Gasket
B
A
L = 14,5 mm
2
A: Pass the connector and cable
through the G1/2’’ connection
B: Screw the sensor on the 8400
- Molex® 90327-3304 connector (order code 448850) (not delivered); Use the Molex® 69008-0910 hand tool for the crimping (not delivered)
- or Molex® connector mounted on cable (order code 440258) (not delivered) ; In this case, only connect conductors N°1 and 3 to the two wires of the Pt100 sensor.
Connect the Molex® connector
to the 4-pin connector of the
3 4
electronic board
1
2
3
4
1
Place the cover back and screw the 4
screws in an alternating pattern at a torque
rating of 0.4 Nm to ensure the tightness
Generic 8400
Calibrate the controller
Once the Pt100 has been mounted onto the 8400 controller:
- plunge the Pt100 into a vessel filled with water: read out the temperature indicated by the display of the controller.
- measure the real temperature of the water inside the vessel using a thermometer and note it down.
Readout = 24.2 ˚C
Real temperature = 24.4 ˚C
Water
- Enter the Calibration mode of the controller.
- Select the T°-menu, validate and enter the difference between the real temperature and the temperature measured by the 8400, i.e. 24.4 - 24.2 = 0.2 in the example above.
> 5s
ENTER
+
0......9
ENTER
END
ENTER
ENTER
000.2
°C
0......9
*
* To enter a negative value, select the character at the left hand side of the display and press until the minus sign appears.
0......9
- Measure again the temperature of the water inside the vessel using the 8400 and check it displays 24.4 °C
Available accessory
Designation Order code
Bag with 20 Molex® connectors 448850 Bag with 20 Molex® connectors mounted on cable 440258
Subject to technical change without notice