Burkert 0411 User Manual

Operating Instructions Type 0411
Voltage 12V or 24V
UL / UR valid with
class 2 power supply only
Design:
3-way solenoid valve, internally piloted, normally closed (Circuit function C) or normally open (Circuit function D). With manual override.
Seal Materials and Fluids handled:
See Table1.
Fluid and Ambient Temperature: For Hazardous Locations Div. 1 (T6 rated)
Max. Ambient Temperature 104 °F (40 °C) Max. Fluid Temperature 140 °F (60 °C)
For Hazardous Locations Div. 2 and Ordinary Locations:
See Table1.
Pressure Range:
Minimum pressure differential between inlet and outlet port is 15 PSI. Maximum inlet pressure see label on valve.
Installation:
Installation position as required. Ensure exhaust outlets for pilot valve and main valve remain unrestricted but protect against entry of dust, water and foreign matter. Pipework should be clean. Do not put any loads on coil unit. Pipework should be supported and installed to prevent strain on valve body. Fittings should be sealed with PTFE tape, max. torque 80 in-lbs. 1/4 inch trough holes are provided for mounting. Maximum torque for mounting 25 in-lbs.
Marking (example):
Body Material
PL = Polyamide Plastic
Seal Material
NBR = NBR FKM = FKM
Circuit Function
C = Normally Closed D = Normally Open
Table 1 Seal materials
Fluid Tempera-
tures [°F]
Air Fluid T.
Neutral gas
Ambient Fluid T.
Ambient
Buna "N" (B) FKM (F)
+ 14 to + 140 + 14 to + 130
+ 14 to + 140 + 14 to + 130
+ 14 to + 140 + 14 to + 130
+ 14 to + 140 + 14 to + 130
Recorder No.
Voltage / Frequency / Power Consumption
Maximum Pressure
Approvals
The valve is either approved as
General Purpose valve for Hazardous Locations
Class I, Division 1, Group A, B, C, D Class II, Division 1, Group E, F, G Class III, Division 1 and 2 Operating Temperature T 6
or
FM approved as
Nonincendive for Hazardous Locations Class I, Division 2, Group A, B, C, D Class II, Division 2, Group F, G Class III, Division 1 and 2
Operating Temperature T 4A UL listed for Ordinary locations CSA approved for Ordinary locations
See label on the valve.
Operating Instructions 0605/08_EU-EN_00893137
Operating Instructions
Bürkert Company Locations
Wiring Diagram
Electrical Connection Type 2509
Power*
Ground (green dot)
Power*
* Orientation is not important
Electrical Connection:
Ensure supply voltage/frequency corresponds with that on label. Voltage tolerance is ± 10 %. Available Electrical Connections see “Marking”. Wiring diagram see above.
For this product to be considered UL-listed and CSA approved for General Purpose and FM approved for Hazardous Locations Division 2, it must be in conjunction with the type 2509 cable plug connector (Electrically Operated Valves Parts, YSYI2). The connector and gasket must be assembled to the valve with the screw provided after the connection of the wire leads. This valve and connector assembly is delivered together and is to be used as one unit.
For valves to be used in Intrinsically Safe Applications the positive pole is identified by a “+” on the pin or wire No. 1 has to be con­nected to the “+”. See Control Drawing for the Rules of Interconnection.
Warning:
All valves to be used in Intrinsically Safe Applications must be clearly marked as Intrinsically Safe Apparatus.
Trouble-Shooting:
Check port connections, minimum operating pressure differential if required and supply voltage. Ensure pilot hole in piston is clear and pilot bore in the valve outlet is not abstracted. If core does not pull in, check for short circuit, coil burn-out or foreign matter im­peding core movement. A jammed or missing core causes the coil to overheat in the case of AC supply.
Warning:
These products are designed to operate in a wide variety of ap­plications, it is the user’s responsibility to select a model that is appropriate for the application. This product is designed to be installed only by suitably qualified and trained personnel. Specifications should not be exceeded under any circumstances.
The torque for the terminal screw on type 2509 is 0,5 Nm (4,4 lbf-in.).
Germany
Contact address:
Bürkert Fluid Control Systems Sales Center Chr.-Bürkert-Str. 13-17 D-74653 Ingelfingen Tel. + 49 (0) 7940 - 10 91 111 Fax + 49 (0) 7940 - 10 91 448 E-mail: info@de.buerkert.com
International
Contact addresses can be found on the Internet at:
Changes made to this product will render any applicable warranty null and avoid.
Specifications subject to change without notice.
Any questions? Please call Bürkert Contromatic Technical Service at (949) 223 31 00.
www.burkert.com
Loading...