Operating Instructions Type 0406
Design:
2-way solenoid valve, internally piloted, normally closed
(Circuit function A).
Seal Materials and Fluids handled:
See Table1.
Fluid and Ambient Temperature:
See Table 1.
Pressure Range:
Minimum pressure differential between inlet and outlet port is
14 PSI.
Maximum inlet pressure see label on valve.
Installation:
Before installing valve ensure that piping etc. is free of foreign
matter (metal fillings, seal material, welding scale etc.). PTFE
tape is recommended for sealing ports. Arrow on valve body
gives flow direction. Installation as required but preferable
with coil uppermost. Installation in this position tends to
prevent foreign matter remaining in pilot valve (increased
life). A strainer upstream of valve, protects against effects of
foreign matter. Do not put any loads on coil unit. Pipework
should be supported such that valve body is not under strain.
Do not allow a pipe-end or sealing material to block the pilot
bore within the valve outlet. Inlet and outlet of valve must be
fullbore and pipework unrestricted.
Marking (example):
Body Material
BR = Brass
Seal Material
EPDM = EPDM
FKM = FKM
EG = PTFE Seat and Graphite seal
Circuit Function
A = Normally Closed
Table 1 Seal materials
Fluid Tempera-
tures [°F]
Air Fluid T.
Ambient
Water Fluid T.
Neutral
gas
Light oil Fluid T.
LP-gas Fluid T.
Steam Fluid T.
Ambient
Fluid T.
Ambient
Ambient
Ambient
Ambient
Ethylene (A)
Propylene
+ 32 to + 275
+ 14 to + 130
+ 50 to + 212
+ 32 to + 130
+ 32 to + 275
+ 14 to + 130
+ 50 to + 194
+ 14 to + 130
+ 32 to + 140
+ 14 to + 130
+ 212 to + 275
+ 14 to + 130
PTFE (G)
+ 32 to + 356
+ 14 to + 130
+ 32 to + 212
+ 32 to + 130
+ 32 to + 356
+ 32 to + 130
+ 50 to + 194
+ 14 to + 130
+ 32 to + 140
+ 14 to + 130
+ 212 to + 356
+ 14 to + 130
Recorder No.
Voltage / Frequency / Power Consumption
Maximum Pressure
Operating Instructions 0605/08_EU-EN_00893146
Operating Instructions
Bürkert Company Locations
Wiring Diagram
Electrical Connection Type 2509
Power*
Ground (green dot)
Power*
* Orientation is not important
Electrical Connection:
Ensure supply voltage/frequency corresponds with that on label.
Voltage tolerance is ± 10 %.
Available Electrical Connections see “Marking”.
Wiring diagram see above.
For this product to be considered UL-listed and CSA approved
for General Purpose and FM approved for Hazardous Locations
Division 2, it must be in conjunction with the type 2509 cable plug
connector (Electrically Operated Valves Parts, YSYI2).
The connector and gasket must be assembled to the valve with the
screw provided after the connection of the wire leads. This valve
and connector assembly is delivered together and is to be used as
one unit.
For valves to be used in Intrinsically Safe Applications the positive
pole is identified by a “+” on the pin or wire No. 1 has to be connected to the “+”.
See Control Drawing for the Rules of Interconnection.
Warning:
All valves to be used in Intrinsically Safe Applications must be
clearly marked as Intrinsically Safe Apparatus.
Trouble-Shooting:
Check port connections, minimum operating pressure differential
if required and supply voltage. Ensure pilot hole in piston is clear
and pilot bore in the valve outlet is not abstracted. If core does not
pull in, check for short circuit, coil burn-out or foreign matter impeding core movement. A jammed or missing core causes the coil
to overheat in the case of AC supply.
Warning:
These products are designed to operate in a wide variety of applications, it is the user’s responsibility to select a model that is
appropriate for the application. This product is designed to be
installed only by suitably qualified and trained personnel.
Specifications should not be exceeded under any circumstances.
The torque for the terminal screw on type 2509 is 0,5 Nm
(4,4 lbf-in.).
Germany
Contact address:
Bürkert Fluid Control Systems
Sales Center
Chr.-Bürkert-Str. 13-17
D-74653 Ingelfingen
Tel. + 49 (0) 7940 - 10 91 111
Fax + 49 (0) 7940 - 10 91 448
E-mail: info@de.buerkert.com
International
Contact addresses can be found on the Internet at:
Changes made to this product will render any applicable warranty
null and avoid.
Specifications subject to change without notice.
Any questions? Please call Bürkert Contromatic Technical Service
at (949) 223 31 00.
www.burkert.com