Buderus Logamatic R2107 Quick Start Manual

Bulletin Number: TBG-21 | Model: Logamatic R2107 Controls
Technical service bulletin
Logamatic R2107 Quick Start Guide
Introduction
This bulletin is intended to address basic applications for the Logamatic R2107. For more advanced applications and functionality, please refer to the Logamatic R2107 Operating Instructions, Installation and Service Instructions and Applications Manual.
Procedure - Level 1 - Basic Settings
• To set day:
Hold
• To set time:
Hold
is selected.
• To set Warm Weather Shutdown (WWSD) temp:
Hold
temperature.
and turn dial until proper day is selected.
1...7
and turn dial clockwise until proper time
and turn dial to appropriate
Procedure - Level 2 - Programming Settings
Hold together
Turn dial
BLR TEMP”.
Then push
reach the settings below:
FREEZE TEMP - 41°F (default)
BUILDING RESP - Change from default (2) to (1) for wood frame
construction
PUMP LOGIC - 104° F (default)
MAX TEMP - Must change to 194°F
• To change BUILDING RESP:
While on the BUILDING RESP setting, hold
1...7
, , then release.
ve clicks clockwise. This brings you to
and turn the dial appropriately to
and turn
• For 24 hour Domestic Hot Water:
Hold
Release
turn the dial back to “CIRCUIT 1”.
When using hydro-air systems, you must also change
day/night temp.
• To change day temp:
Hold
• To change night temp:
Push
to 84° F.
and turn dial until "DHW PROD" appears.
and then press . Then re-hold and
and turn dial clockwise to 86° F.
then hold and turn dial clockwise
dial
• To change MAX TEMP:
While on the MAX TEMP setting, hold
dial
Push
CIRCUIT 1”.
Then push
reach the following settings on the next page:
counter-clockwise.
clockwise to 194° F.
then turn dial clockwise once to
and turn the dial appropriately to
and turn
Bulletin Number: TBG-21 | Logamatic R2107 Quick Start Guide Technical service bulletin
REF TEMP – Will change according to system design. Program to
the following:
1. Baseboard – 160 °F
2. Hydro-Air – 128 °F
3. Panel Rads – 155 °F
4. Cast Iron Rads – 150 °F
• To change REF TEMP:
While on the REF TEMP setting, hold
dial
to proper design temperature
and turn
REMOTE 1 - default is OFF, but must be changed to ON when
using BFU.
• To change REMOTE 1:
While on the REMOTE 1 setting, hold
dial
to select ON.
and turn
ROOM COMP – you only get this setting when you turn on BFU
and this must be set to 18.
• To change ROOM COMP:
Use the following under CIRCUIT 2:
REF TEMP – Rule of thumb: set REF TEMP 10 °F lower than
design water temp
Examples:
1. Staple up (No Plates) 135 °F
2. Below sub-oor w/ plates 125 °F
3. Quick-track (or equal) 115 °F
4. Slab (nothing over) 90 °F
** All other settings under CIRCUIT 2 will follow same rules as CIRCUIT 1.
Additional Rules
1. Never use a BFU with a hydro-air
2. If you are using the hydro-air settings above and circuit 2 for radiant, you must adjust circuit 2 temp down. Raising the day temp setting to 86 will also have an effect on circuit 2.
3. All settings listed above are starting points only – the heating curve may need to be adjusted further after the system is up and running. It is always best to start the curve low and work up from there.
While on the ROOM COMP setting, hold
dial
clockwise to select 18.
and turn
OASETBACK – This must always be changed! Change to
SETBACK when using standard themostats (no BFU) and RMSETBACK if using BFU room sensor.
• To change OASETBACK:
While on the OASETBACK setting, hold
dial
to select proper setting.
and turn
OFFSET – Will change according to system design. Program for
the following:
1. Baseboard, Panel Rads, and Cast Iron Rads – 0 (default)
2. Hydro-Air – Must be changed to 9
3.
• To change OFFSET:
While on the OFFSET setting, hold
dial
Data subject to change without notice | BTC 463002101 A | 08.2010
clockwise until 9 is selected.
and turn
Bosch Thermotechnology Corp. 50 Wentworth Ave Londonderry, NH 03053 Tel:
(603) 552-1100
Fax: (603) 584-1681 www.buderus.us