Buderus GC 124 II User Manual

Installation and Service Instructions
Gas boiler
WARNING!
Installation, adjustment, modification, operation or maintenance of the heating system carried out by unqualified personnel may result in property damage, personal injury, and loss of life. The directions of this installation and maintenance manual must be followed precisely. Contact a qualified service company, service pro­vider or the gas company if support or additional information is required.
CAUTION!
Before placing this boiler in operation observe the safety instructions of this installation and mainte­nance manual.
CAUTION!
The operating manual is a component of the tech­nical documentation handed over to the operator of the heating system. Discuss the instructions in this manual with the owner or operator of the heat­ing system and ensure that they are familiar with all information required for operation of the heating system. In the Commonwealth of Massachusetts this boiler must be installed by a licensed plumber or gas fitter.
Keep this installation and maintenance manual available for future reference.
Logano GC 124 II
In the Commonwealth of Massachusetts this boiler must be installed by a licensed plumber or gas fit­ter.
C
6 720 804 440 (2012/07) EN-US
Contents
Contents
1 Safety considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Key to symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Safety instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 Product Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.1 Correct use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.2 National regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.3 Boiler Operating Conditions . . . . . . . . . . . . . . . . . . . . . . 4
2.4 Tools, materials and accessories . . . . . . . . . . . . . . . . . . . 4
2.5 Disposal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Dimensions and Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
4 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5 Moving the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
5.1 Moving the boiler with boiler cart . . . . . . . . . . . . . . . . . . 6
5.2 Lifting and carrying the boiler . . . . . . . . . . . . . . . . . . . . . 7
6 Placing the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6.1 Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6.2 Leveling the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
13 Start-up protocol . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
14 Taking the heating system out of operation . . . . . . . . . . . . . . 20
14.1 Normal system shut-down . . . . . . . . . . . . . . . . . . . . . . . 20
14.2 Emergency shut-down procedures . . . . . . . . . . . . . . . . 20
15 Boiler inspection and maintenance . . . . . . . . . . . . . . . . . . . . . 20
15.1 Why is regular maintenance important? . . . . . . . . . . . . 20
15.2 Testing the flue system, incl uding combustion air, air inlets
and Ventilation openings . . . . . . . . . . . . . . . . . . . . . . . 20
15.3 Inspection of the boiler and burner . . . . . . . . . . . . . . . . 20
15.4 Preparing boiler for cleaning . . . . . . . . . . . . . . . . . . . . . 20
15.5 Cleaning the boiler . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
15.5.1 Cleaning the boiler with brushes . . . . . . . . . . . . . . . . . . 21
15.5.2 Wet cleaning (chemical cleaning) . . . . . . . . . . . . . . . . . 22
15.6 Cleaning the burner . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
15.7 Maintenance protocol . . . . . . . . . . . . . . . . . . . . . . . . . . 25
15.8 Troubleshooting the GC124 II . . . . . . . . . . . . . . . . . . . . 27
16 Technical specifications . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
17 Electrical circuit diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
7 Boiler installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
7.1 Preparing for installation . . . . . . . . . . . . . . . . . . . . . . . . . 7
7.2 Connecting the heating system . . . . . . . . . . . . . . . . . . . . 8
7.3 Electrical connections . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7.4 Fuel gas supply connection . . . . . . . . . . . . . . . . . . . . . . 10
7.4.1 Gas connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
7.4.2 Installation at high altitudes . . . . . . . . . . . . . . . . . . . . . . 11
7.5 Filling heating system and checking for leaks . . . . . . . . 11
8 Check openings for combustion air supply and venting . . . . 12
9 Requirements for connection to chimneys or venting
systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
10 Flue pipe installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
11 Placing the heating system in operation . . . . . . . . . . . . . . . . . 14
11.1 Starting up the GC124 II . . . . . . . . . . . . . . . . . . . . . . . . 15
11.1.1 Prepare pressure measurement . . . . . . . . . . . . . . . . . . 15
11.1.2 Turning on heating system . . . . . . . . . . . . . . . . . . . . . . . 16
12 Final start-up procedures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
GC 124 II – 6 720 804 440 (2012/07)2
1 Safety considerations
1.1 Key to symbols
Warnings
Warnings in this document are identified by a warning triangle printed against a grey background. Keywords at the start of a warning indicate the type and seriousness of the ensuing risk if measures to prevent the risk are not taken.
The following keywords are defined and can be used in this document:
NOTE indicates a situation that could result in damage to property or equipment.
CAUTION indicates a situation that could result in minor to medium personal injury.
WARNING indicates a situation that could result in severe personal injury or death.
DANGER indicates a situation that will result in severe injury or death.
Important information
This symbol indicates important information where there is no risk of personal injury or property damage.
Additional symbols
Symbol Explanation
B Step in an action sequence
Æ Cross-reference to another part of the document
List entry – List entry (second level)
Table 1
1.2 Safety instructions
Observe these instructions for your safety.
The burner and control must be correctly installed and adjusted to ensure safe and economical operation of the gas boiler.
Read this installation and maintenance manual carefully and note the details on the boiler nameplate before placing the boiler in operation.
Risk of fatal injury from explosion of flammable gases
If you smell gas there is a danger of explosion.
B Never work on gas lines unless you are licensed for this type of work. B Make sure that a qualified company installs the boiler, connects gas
and ventplaces the boiler in operation, connects the electrical power, and maintains and repairs the boiler.
B No open flame! No smoking! Do not use lighters B Prevent spark formation. Do not operate electrical switches,
including telephones, plugs or door bells.
B Close main gas valve. B Open doors and windows. B Warn other occupants of the building, but do not use door bells. B Call gas company from outside the building. B If gas can be heard escaping, leave the building immediately, prevent
other people from entering, notify police and fire departments from outside the building.
Safety considerations
Risk to life from electrical shock.
B Disconnect the power supply to the boiler heating system before
conducting any work on it, e.g. turn off the heating system emergency switch outside the boiler room.
B It is not sufficient just to turn off the control. B Do not carry out electrical work unless you are qualified for this type
of work.
B Before disconnect electrical power completely and pad lock to
prevent accidental reconnection.
B Observe the local installation regulations.
Risk of fatal injury from flue gas poisoning
Insufficient ventilation or combustion air availability may cause dangerous flue gas leaks or formation.
B Make sure that inlets and outlets are not reduced in size or closed. B If faults are not corrected immediately, the boiler must not be
operated until all faults have been corrected.
B Inform the system operator and/or owner of the fault and the danger
in writing.Elektroanschluss nur durch eine Elektrofachkraft ausführen lassen.
When working on the flue gas venting equipment or vent damper leakage of flue gases may endanger the lives of people.
B Carefully observe proper operation of the vent damper. Do not start
up the boiler unless the vent damper is operating properly.
B Use only original parts when replacing parts. B When replacing the vent damper, install the new one in the specified
position.
Risk to life by poisoning by spillage of flue gases
B If the blocked vent switch trips frequently the fault must be corrected
and proper operation of the blocked vent switch test must be conducted.
Risk to life by poisoning by leakage of flue gases
B Make sure that the boiler is not equipped with a thermally controlled
flue gas vent damper after the open draft hood.
Risk of fatal injury from neglecting your own safety in case of emergency, such as with a fire
B Never put yourself at risk. Your own safety must always take priority.
Fire danger due to flammable materials or liquids
B Make sure that there are no flammable materials or liquids in the
immediate vicinity of the boiler.
B Maintain a minimum distance of 15 inches from the boiler.
Installation and maintenance
B Observe all current standards and guidelines applicable to the
installation and operation of the boiler heating system as applicable in your state or local jurisdiction.
B Clean and service the boiler system once a year. Check that the
complete heating system operates correctly.
B Immediately correct all faults to prevent system damage. B Only use original Buderus spare parts. Losses caused by the use of
parts not supplied by Buderus are excluded from the Buderus warranty.
1
GC 124 II – 6 720 804 440 (2012/07) 3
2
Product Description
2 Product Description
The boiler is a low temperature gas boiler.
The boiler consists of the following main components:
Ignition module and adjustable boiler temperature controller
Boiler jacket and front door
Boiler block with insulation
Burner
The ignition module and adjustable boiler temperature controller monitor and control all electrical and operational components of the boiler.
The boiler jacket prevents energy loss and acts as soundproofing.
The boiler block transfers the heat generated by the burner to the heating water. The insulation reduces energy loss.
1
2.3 Boiler Operating Conditions
The hot water piping system must comply with the current legislation and local regulations. If an existing boiler is replaced, the complete hot water piping system must be inspected to ensure that it is in perfect condition to ensure safe operation.
Maximum boiler temperature: 220 °F Maximum operating pressure: 58 psi
Table 2 Boiler Operating Conditions
2.4 Tools, materials and accessories
You need standard tools for the installation and maintenance of the boiler as used in boiler heating system installation and oil, gas and water installations.
The following additional items will also be useful:
Boiler cart with strap.
Cleaning brushes and/or chemical cleaning agents for wet cleaning of
the cast iron heat exchanger.
2
3
6
4
5
6 720 804 440-01.1T
Fig. 1 Logano GC124 II gas boiler
[1] Boiler front door [2] Boiler temperature controller [3] Ignition module [4] Boiler block with insulation [5] Burner [6] Boiler jacket
2.1 Correct use
The Logano GC124 II atmospheric gas boiler is designed to heat water for a hot water heating system for heating single or multiple occupancy buildings.
2.5 Disposal
B Dispose of the packaging material in an environmentally prudent
fashion.
B Dispose of any components of the heating system that require
replacement in an environmentally prudent fashion.
2.2 National regulations
The heating system must comply with the relevant regulations issued by national authorities, or the regulations issued by the National Fuel Gas Code, ANSI Z 223.1.
If specified by the local regulatory authorities the heating system must comply with the regulations of the "Standard for Controls and Safety Devices for Automatically Fired Boilers," ANSI/ASME CSD-1.
Carbon monoxide detectors must be installed as specified by the local regulations. The boiler must be serviced annually (Æ chapter 15, page 20).
GC 124 II – 6 720 804 440 (2012/07)4
3 Dimensions and Connections
VK 1¼"
Dimensions and Connections
3
GAS ½"
EL ¾"
Fig. 2 Back, side and front view, measurements in inches
* optional connection VK Boiler supply RK Boiler return EL Boiler drain GAS Gas connection
Dimensions
Boiler size
18/3 74000 13 1/8" 8" 5" 62 2 2.4 228 25/4 103000 16 3/4" 8 2/3" 5" 86 3 2.9 287 32/5 132500 20 3/8" 9 1/2" 6" 110 4 3.4 349.5
Table 3 Dimensions/specs for GC124 II
RK 1¼"
Boiler
input Btu/hr Inches Inches Inches lb/hr Qty. US Gal. lbs
A B
Vent connection II
Min. relief valve capacity
Number of Orifices
(GAS ½")*
Water
volume
6 720 804 440-02.1T
Dry weight
For the size and dimensions of the main gas orifices, refer to Æ chapter 16, page 29.
6 720 804 440-03.1T
Fig. 3 Pressure drop/boiler
GC 124 II – 6 720 804 440 (2012/07) 5
4
Scope of delivery
4Scope of delivery
B Check packaging upon receipt of delivery for damage. B Check delivery for completeness.
Component Qty Packaging method
Boiler, complete 1 1 palette B-kit components:
1-1/4" supply manifold
30 psi relief valve
long shank boiler
drain (¾")
¼" pressure/ temperature gauge
90°-elbow (1¼" x 1" NPT)
90°-elbow (1¼" x 1¼" NPT)
90°-elbow (¾" NPT nipple)
nipple1" NPT
nipple 1¼" NPT
Vent damper 1 1 cardboard box Circulator with whip 1 1 cardboard box Technical documents 1 plastic package
Table 4 Scope of delivery
1) On Palette
Accessory Qty
Cleaning Brush 1
Table 5 Scope of delivery
1 1 cardboard box
5.1 Moving the boiler with boiler cart
Move the boiler with packaging in tact and on its pallet as much as possible.
B Remove packaging straps and cardboard box from pallet. B Remove screws that secure the boiler base to the wood pallet. B Pick up boiler base from one side and slide to the edge of the pallet.
1)
1)
1)
Place a steel pipe as roller under the boiler base. Place additional steel pipes under the boiler base and roll the boiler to its final destination.
6 720 804 440-04.1T
Fig. 4 Moving the boiler with rollers
CAUTION: Risk of injury due to improper securing of the boiler during transport.
B Use a boiler coart or dolley and strap for moving the
boiler
B Secure boiler on the boiler cart. B Remove the front door during lifting or transport to
prevent unintentional opening.
5 Moving the boiler
This chapter describes how to move the boiler safely into place.
NOTICE: System damage due to uneven and rough surfaces.
B Observe the transport diagrams on the packaging to
protect the sensitive components from damage due to rough surfaces. Handle the product with care.
Protect all boiler connections from dirt if the boiler is not installed immediately following removal from packaging.
Dispose of the packaging material in an environmentally prudent fashion.
B Set the boiler cart or dolley on the front side of the boiler and put a
piece of cardboard between the two to prevent scratches.
1
6 720 804 440-05.1T
Fig. 5 Moving the boiler with dolley or boiler cart.
[1] Additional card board for protection.
GC 124 II – 6 720 804 440 (2012/07)6
B Secure boiler on the boiler cart. B Move boiler to desired location. B Place the boiler at its final postion.
5.2 Lifting and carrying the boiler
The boiler can be picked up at the both long sides of the boiler as shown.
CAUTION: Risk of injury due to carrying heavy loads. B Lift and carry the boiler with at least four people at the
designated side panel locations.
Placing the boiler
6
1
2
3
6 720 804 440-07.1T
Fig. 7 Required clearances in the boiler room
[1] Recommended service clearances [2] Required minimum clearances [3] Burner tray access door with combustion air opening as required
per ANSI Z.223.1
6 720 804 440-06.1T
Fig. 6 Lifting and carrying the boiler
6 Placing the boiler
This chapter explains how to place the boiler and position it in the boiler room.
NOTICE: System damage due to frost. B Place the boiler in a frost-free room.
The boiler is very heavy when filled with water. Check that the floor can bear the weight before installation.
6.1 Clearances
The GC124 boiler is approved for closet installation. The following minimum distances must then be maintained:
front: 2",
sides: 2",
behind open draft hood: 6",
above boiler top panel: 30".
A space of at least 33 inches is recommended in front of the boiler with the door removed to allow sufficient access space for operation and maintenance. When the door is closed, a minimum clearance of 2 inches is required at the front and sides, 2 inches clearance is also required for the flue pipe and 30 inches clearance to the ceiling. The installation location and the base must be smooth and horizontal.The boiler may be installed on a flammable base, but not on carpet.
6.2 Leveling the boiler
Level the boiler in both horizontal directions.
B Level the boiler using a level and place small wedges (not supplied) for
leveling purposes.
7 Boiler installation
This chapter describes how to install the boiler. This includes the following tasks:
Connecting the heating system
Electrical connection
Gas supply piping connection
7.1 Preparing for installation
B Unpack all boxes and containers and check all parts against the
packing lists to make sure that everything has been supplied.
Every boiler is carefully inspected and tested before it leaves the factory. However, if you discover any damage or missing parts, please inform your supplier immediately. Before disposing of packing material, make sure that no parts are still in it.
For better access remove the front door.
GC 124 II – 6 720 804 440 (2012/07) 7
7
Boiler installation
7.2 Connecting the heating system
NOTICE: Boiler damage due to moisture.
B Protect the components of the gas ignition system
from moisture (dripping, spray, rain) during installation of the boiler, during operation and during maintenance work (such as replacing the pump, replacing the control, etc.).
NOTICE: System damage due to overheating as a result of a low water condition.
B Note that a boiler installed above the level of the
heating system must be equipped with a low-water cut-off. The low-water cut-off must be in stalled during installation of the boiler and placed above the water level in the boiler without any means of shutting the water off between the boiler and low water cut-off (Æ figure 8).
NOTICE: System damage due to high temperature variations in the heating system.
B If the boiler is operated in connection with a
refrigeration system, make sure that the pipes for the refrigerated liquid are connected in parallel to the boiler system with suitable valves to prevent the refrigerated liquid from entering the boiler.
B The piping system of a boiler connected to the heating
coils of hydro-air heating systems that may be exposed to the circulation of cooled air must be equipped with a flow-control valve or some other automatic system for preventing the boiler water from circulating by gravity during the cooling cycle.
3
1
2
2
2
4
2
1
2
2
Fig. 8 Low-water cut-off installation
[1] Boiler [2] Radiator [3] Heating system with low-water cut-of [4] Heating system without low-water cut-off
6 720 804 440-08.1T
GC 124 II – 6 720 804 440 (2012/07)8
Boiler installation
7
Installation of B-kit
The relief valve and the pressure/temperature gauge are mounted on the boiler supply manifold which is attached to the VK (supply) connection of the boiler (included in B-kit).
Installing boiler supply VK: B Remove factory installed plastic inserts from boiler supply (VK), boiler
return (RK) and boiler drain (EL) connections.
B Install the 1¼"NPT nipple into boiler supply, the 1" NPT nipple into
boiler return and ¾" male NPT drain valve into boiler drain connection.
B Install 90° 1¼" x 1¼"NPT on 1¼" NPT supply nipple and face upward
and install 90° 1¼" x 1"NPT elbow on return nipple and face in desired direction.
B Install GC124 1¼" x 1¼"NPT supply manifold into supply connection
(VK) of the boiler. Do NOT place on return connection of the boiler!
B Install first 90° ¾" street elbow in upper ¾" NPT tapping of GC124 1-
1/4" supply manifold and install pressure relief valve into this ¾" tapping. Make sure to orient the discharge of the relief valve horizontally. Install the temperature/pressure gauge in the lower 3/4" tapping of the supply manifold.
1
2
We recommend installing a y-strainer (accessory) in the boiler return connection to reduce build-up of debris on the water side inside the boiler.
Ensure compliance with all state and local regulations pertaining to the installation of boiler systems.
WARNING: Fire danger due to exposure to hot water pipes.
B Maintain a minimum clearance of two inches between
non-insulated pipes carrying hot water and combustible walls and surfaces in the boiler room. A minimum of 1" high quality pipe insulation is required to permit direct contact with combustible surfaces.
7.3 Electrical connections
The electrical connections of the boiler must be made as specified by the local codes and the current regulations of the National Electrical Code, ANSI/NFPA–70.
The boiler must be grounded as specified by the regulations of the relevant local authorities; otherwise follow the regulations of the National Electrical Code, ANSI/NFPA–70.
The boiler is fully functional with the factory installed aquastat and the field installed vent damper and heating system circulation pump.
3
VK
4
6
5
7
EL
RK
8
Fig. 9 Installation of B-kit
[1] Pressure relief valve ¾" [2] 90° 3/4" street elbow [3] GC124 1-1/4" supply manifold [4] Pressure & temperature gauge [5] 90° 1-1/4" NPT elbow [6] 1-1/4" x 1" NPT nipple [7] Boiler drain ¾" NPT (backside of boiler) [8] 90° 1-1/4" NPT elbow [9] 1" NPT nipple
Install the relief valve after the leak test. (Æ chapter 7.5, page 11). The relief valve must be installed in a vertical position. The relief valve must also be installed in accordance with the requirements of the ANSI/ASME Boiler and Pressure Vessel Code, Section IV.
9
When making the electrical connections please observe the following guidelines: B Perform only electrical work, if you possess the
required certification for such work. When you do not have the required certification, have the electrical work performed by a certified electrician.
B Observe all local and state installation regulations.
6 720 804 440-09.1T
Power supply connection.
Install incoming power to the boiler per local and state codes. B Install an ON/OFF switch near the boiler per local code requirements.
6 720 804 440-10.1T
Fig. 10 ON/OFF switch (emergency shutoff switch)
GC 124 II – 6 720 804 440 (2012/07) 9
7
T
Boiler installation
Description of field installed wiring connections using factory supplied junction box.
B Remove two knock-outs from the left side of boiler panel to route
electrical feed and pump power into junction box.
B Route electrical power from the outside into junction box. B Install a metal strain relief for the incoming power line on outside of
left boiler jacket panel. (Æ figure 12).
B Just use supplied wiring nuts and double proper wiring before
powering up the boiler.
When making the electrical connections use only wires that are approved for electrical use.
Refer to the wiring diagrams for electrical details (Æ chapter 17, page 30) .
WARNING: Risk to life from electrical shock. B When conducting maintenance work label all cables
before disconnecting them.
B If cables are connected incorrectly the system may
not operate correctly with possibly dangerous consequences.
B Check that the heating system functions correctly after any
maintenance work.
WARNING: Fire danger. Hot boiler components may damage electrical wiring.
B Make sure that all cables are routed in the ducts or on
the boiler insulation.
1
6 720 804 440-12.1
Fig. 12 Strain relief for shielded electrical wiring
7.4 Fuel gas supply connection
7.4.1 Gas connections
For the gas pipe diameter required for the installation please see table 6 and table 7 (Æ page 11). Make sure that the pipe fitting has the correct thread size.
Make sure that a sediment trap is installed at the inlet for the gas supply pipe to the boiler. A manual stop valve must be installed outside the boiler jacket if required by the local code. We recommend installing a manual shut-off valve in the main gas pipe to the boiler. The gas pipe must be fastened outside the boiler.
The local codes must be observed during installation of the gas piping connections, otherwise the regulations of the National Fuel Gas Code, ANSI Z 223.1 must be followed.
B Install gas piping without any undue stress on the piping. B The Commonwealth of Massachusettes prohibits the use of copper
tubing for the gas line.
WARNING: Danger of explosion. Leakage from the gas pipes and gas connections may
cause an explosion.
B Use soap solution to find leaks.
2
Fig. 11 Electrical junction box
[1] Electrical junction box (Inside of jacket cabinet) [2] Incoming line voltage wiring [3] Furnished wiring nuts.
1
2
3
6 720 804 440-11.1T
3
6 720 804 440-13.1T
Fig. 13 Gas piping connection to gas valve – right or left side
[1] Gas feed [2] Manual shut-off valve [3] Sediment trap
GC 124 II – 6 720 804 440 (2012/07)10
Boiler installation
7
Gas carrying capacity (Æ chapter 16, page 29)
Nominal diameter of iron pipe (inches)
1/2 1.4 2.7 0.3 0.80 3/4 2.1 4.1 0.5 1.25 1 2.6 5.2 0.6 1.6 1 1/4 3.5 6.9 0.8 2.15 1 1/2 4.0 8.0 0.9 2.50
Table 6 Equivalent lengths for pipe fittings
Length of pipe in feet
10 132 278 520 1060 1600 20 92 190 350 730 1100 30 73 152 285 590 890 40 63 130 245 500 760 50 56 115 215 440 670 75 45 93 175 360 545 100 38 79 160 305 480 150 31 64 120 250 380
Table 7 Gas pipe supply volume
Equivalent lengths for pipe fittings in feet Pipe fitting type 90°-
angle Equivalent lengths in feet
Gas pipe supply volume in cubic feet of gas per hour
1/2 3/4 1 1 1/4 1 1/2
T-piece
Shut-off valve
Gas shut-off
7.4.2 Installation at high altitudes
The boiler is designed for installation at altitudes below 8500 feet above sea level.
If the installation location is over 8500 feet above sea level, please contact Buderus for another product option as the GC124 is not approved above 8500 feet operation.
NOTICE: System damage due to dirt. If the boiler is assembled and not in use, note the
following:
B Protect the boiler connections from dirt by closing the
1
connections.
7.5 Filling heating system and checking for leaks
The boiler is tested for leaks at the factory. Before placing the heating system into use, check the entire system for soundness to avoid leaks occurring during operation.
Water treatment
Have the water analyzed before filling the heating system. The water may require treatment as a result of the analysis. Please consult the local water supply company if the water is extremely hard or has a pH level below 7.0.
1 Maximum gas supply volume in cubic feet per hour, based on
a specific gas weight of 0.60 and a gas pressure of 0.5 psi or less and a pressure gradient corresponding to a water column of
0.3 inches.
Disconnect the boiler with the manual shut-off valve and physically separate the boiler from the gas piping if the gas piping system is pressure tested with a test pressure greater than 1/2 psi.
If the gas supply pipe system is pressure tested at a test pressure of 1/2 psi or less, it is sufficient to disconnect the boiler from the gas pipe system by closing the manual shut-off valve.
Use only sealant that is resistant to corrosion by LPG for pipe connection. Only a small amount of sealant must be applied to the external thread of the pipe connections.
If you wish to convert the boiler to propane, please contact Buderus for the required conversion components. Do not attempt to convert the boiler without the approved Buderus propane conversion parts and the relevant technical documentation. The technical documentation is included with the propane conversion parts.
NOTICE: System damage due to overpressure during the leak test. Pressure, control or safety components may be damaged by high pressure. B Before conducting the leak test make sure that no
pressure, control or safety components that cannot be disconnected from the water compartment of the boiler are installed.
Carry out the leak test at 1.5 times the normal operating pressure and as specified by the local codes as follows:
Maximum operating pressure Maximum test pressure
30 psi (based on supplied relief
valve)
58 psi (with special relief valve) 75 psi
Table 8 Pressure Test
B Close connection for relief valve (Æ figure 14, page 12) and all other
open connections with plugs.
B Disconnect the expansion tank from the system by closing the
expansion tank shut-off valve.
B Open mixing and shut-off valves on hot water side. B Fill boiler slowly with water from the feed water connection. B Open automatic vents slightly to allow the air to escape. B Slowly fill heating system. Observe pressure display on pressure
gauge during this process.
B Check connections and pipes for leaks. B Bleed heating system through the bleed valves on the radiators or
other air elimination components or high points in the system.
B If the pressure drops during air bleeding, water must be added. B Install pressure relief valve (Æ figure 14, page 12).
45 psi
GC 124 II – 6 720 804 440 (2012/07) 11
Loading...
+ 25 hidden pages