SINGLE PACKAGE
GAS HEATING/
ELECTRIC COOLING UNITS
DESCRIPTION
All 588Amodelsfeatureonepiece,compactdesignandarefully
self-contained units that are prewired, prepiped, and precharged for minimum installation expense. Unit is designed for
easy use in either downflow (vertical) or horizontal applications.
STANDARD FEATURES
FACTORY-ASSEMBLED PACKAGE is a compact, fully self-
contained, gas heating/electric cooling unit that is prewired, prepiped, and precharged for minimum installation expense.
588A units are lightweight and available in a variety of standard
heating and cooling sizes with voltage options to meet residential and light commercial requirements. Unit installs easily on a
rooftop or a ground-level pad.
CONVERTIBLE DUCT CONFIGURATION on the 588A is designed for easy use in either downflow or horizontal discharge
applications.
HIGH-EFFICIENCY DESIGN with SEERs (Seasonal Energy Efficiency Ratios) of 10.0.
DURABLE, DEPENDABLE COMPRESSORS are designed for
high efficiency. Each compressor is hermetically sealed against
contamination to help promote longer life and dependable operation. Each compressor also has vibration isolation to provide
quiet operation. Rotary, reciprocating, or scroll compressors are
used. Compressors have internal high-pressure and overcurrent protection.
DIRECT-DRIVE MULTISPEED, PSC (permanent split capacitor) BLOWER MOTOR is standard on all models.
DIRECT-DRIVE, PSC CONDENSER-FAN MOTORS are de-
signed to help reduce energy consumption and provide for cooling operation down to 40 F.
Model 588A
Sizes 018-060
11⁄2to 5 Tons
REFRIGERANT SYSTEM is designed to provide dependability.
Liquid refrigerant strainers are used to promote clean, unrestricted operation. Each unit leaves the factory with a full refrigerant charge. Refrigerant service connections make checking
operating pressures easier.
EVAPORATOR AND CONDENSER COILS are computerdesigned for optimum heat transfer and cooling efficiency. Condenser coil is fabricated of copper tube and aluminum fins and
is located inside the unit for protection against damage and for
long life and reliable operation. The condenser coil is internally
mounted and protected by a composite grille.
Copper fin coils for condenser coil are also available by special
order. These coils are recommended in applications where aluminum fins are likely to be damaged due to corrosion. Copper
fin coils are ideal for seacoast applications.
MONOPORT INSHOT BURNERS produce precise air-to-gas
mixture, which provides for clean and efficient combustion. The
large monoport on the inshot (or injection type) burners seldom,
if ever, needs cleaning.
WEATHERIZED CABINETS are constructed of heavy-duty,
phosphated, zinc-coated prepainted steel capable of withstanding 500 hours in salt spray. Interior surfaces of the evaporator
compartment are insulated with foil-faced fiberglass to help
keep the conditioned air from being affected by the outdoor ambient temperature and provide improved air quality.Conforms to
American Society of Heating, Refrigeration and Air Conditioning
Engineers (ASHRAE) No. 62P. Sloped condensate pan permits
an external drain.
LOW SOUND RATINGS ensure a quiet indoor and outdoor environment with sound ratings as low as 7.4 bels.
EASY TO SERVICE CABINETS provide easy accessibility to
serviceable components during maintenance and installation.
Rounded corners are an important safety feature, and a highquality finish ensures an attractive appearance.
LOW AND HIGH VOLTAGE ELECTRICAL ENTRIES allow low
and high voltage to be brought in either through the duct panel
or rear flue panel.
INTEGRATED GAS CONTROL BOARD provides safe and efficient control of heating and simplifies troubleshooting through
its built-in diagnostic function.
OPTIONAL BASE RAILS provide holes for rigging and handling as well as an elevated mounting frame that provides structural support for horizontal installations.
DOWNFLOW OPTIONS is converted for downflow at factory for
easy vertical ductwork connections.
Form No. PDS 588A.18.4B
FACTORY-INSTALLED OPTIONS DESCRIPTION AND USAGE
Unit With Base Rail — Unit has rigging holes and an elevated
mounting frame.
SUGGESTED USE:
• Rigging holes to provide greater ease in handling. Frame to
provide elevation and structural support for horizontal
applications.
FIELD-INSTALLED ACCESSORY DESCRIPTION AND USAGE
Downflow Option — Unit is shipped from factory configured for
downflow application. Unit is equipped with base rail.
SUGGESTED USE:
• To provide easy vertical ductwork connections.
Flat Roof Curb — Consists of galvanized steel support frame in
8-, 11-, and 14-in. high designs. Provides wood nailer to attach
roof counter flashing. Insulated basepans in curbs are provided
to prevent condensation. Ductwork attaches to rails provided in
the roof curb. A gasket is provided to form an airtight and watertight seal between unit and curb. The roof curb design meets
the standards of the NRCA (National Roofing Contractors’
Association).
SUGGESTED USE:
• Slab-mounted applications when elevation of the unit above
the slab is necessary.
• Rooftop application for downflow discharge.
• Curbs are preassembled and are available for flat or pitched
roofs.
Pitched Roof Curb — Provided in ratios of 1, 2, 3, 4, 5, and 6
to 12 for use on pitched roof applications.
SUGGESTED USE:
• For when a roof curb is needed on a pitched roof.
Modulating Economizer — Economizer is available for downflow or horizontal applications, and is designed for easy installation. Economizer reduces energy costs and extends
equipment life by allowing the use of outdoor air to supply ‘‘free’’
cooling when conditions are favorable.
Constant ventilation is recommended for light commercial applications when the conditioned space is occupied.
The economizer is shipped complete with a damper motor and
linkage, enthalpy control, low-voltage wiring harness, and a
rainhood. Adequate wire lengths are provided (additional fieldsupplied wires are not required). Horizontal economizers are
also furnished with a 2-in. disposable air filter and gasket
material.
Modulating economizer package consists of low-leakage dampers with controls. The economizer will allow a fixed percentage
of outdoor ventilation air into the unit whenever the evaporator
fan is running.
SUGGESTED USE:
• Allows outdoor air to be used for ‘‘free’’ cooling whenever the
outdoor air is below the enthalpy control setting.
• To reduce energy usage. Use whenever the hours of operation at temperatures below 40 F are significant.
Two-Position Damper — In the two-position dampers, the enthalpy control detects when outdoor air is suitable for ‘‘free’’
cooling by measuring the outdoor-air dry bulb temperature and
humidity. Whenever the outdoor-air quality is acceptable for
‘‘free’’ cooling, the outdoor-air damper opens fully and the
return-air damper closes, allowing outdoor air to enter the
building.
SUGGESTED USE:
• Allows use of outdoor air to cool building without using compressor. Damper closes when evaporator fan is off to prevent
cold backdraft, and wasted energy.
Manual Outdoor-Air Damper — Package consists of a manually adjustable damper and includes a rainhood and birdscreen.
SUGGESTED USE:
• Toallow a fixed percentage of outdoor air for ventilation under
all conditions.
• The damper may be used on either downflow or horizontal airflow applications.
Thermostat and Subbase — These accessories provide cooling control for unit. Autochangeover and manual changeover
types are available.
SUGGESTED USE:
• To operate and control unit, and to maintain desired building
temperature.
The 0° F Low Ambient Kit — Kit permits operation down to
0° F.
SUGGESTED USE:
• When mechanical cooling is required when outdoor-air temperature is between 40 F and 0° F.
Natural-to-Propane Conversion Kit — Kit consists of gas orifices and other hardware required to convert the unit for use
with LP (liquid propane) gas.
SUGGESTED USE:
• When natural gas cannot be obtained and liquid propane is
used as fuel.
Filter Rack — Rack features easy installation and serviceability.
The filter rack housing is constructed of heavy-gage steel and is
fully insulated. Both sides of the filter rack are flanged for easy
installation.
SUGGESTED USE:
• Kit provides ability to locate filters inside the unit.
Flexible Duct Kit — Consists of 2 flexible UL-listed (Underwriters’ Laboratories) ducts. The duct construction includes vapor
barrier and 1-in. fiberglass insulation. The ‘‘K’’ factor is 0.23.
Each duct has a square-to-round snap adapter for attachment
to the accessory roof curb on one end, and a round clamp collar
for attachment to the concentric diffuser box on the other end.
SUGGESTED USE:
• For use with accessory roof curb and concentric box to provide an easily-installed concentric system.
Concentric Diffuser Box — Is aerodynamically designed and
equipped with a combination 4-way supply and a center return
diffuser. Aspecial core is provided within the diffuser box to provide even 4-way distribution.
SUGGESTED USE:
• For use with accessory roof curb and concentric box to provide an easily-installed concentric system.
Crankcase Heater — Warms crankcase oil to reduce refrigerant migration and ensure proper compressor lubrication.
SUGGESTED USE:
• For use in applications where crankcase is subjected to low
outside temperatures. Recommended on 208/230-v, singlephase, 024-042 units only.
Solid-State ComprotecT Device — Package consists of a control to be field-wired into the unit controls, and provides a
5-minute delay in compressor operation between cooling
cycles.
SUGGESTED USE:
• Prevents compressor short cycling when rapid compressor
cycles may be a problem.
2
FIELD-INSTALLED ACCESSORY DESCRIPTION AND
USAGE (cont)
Lifting Bracket Kit — Provides attachment point for rigging
straps.
SUGGESTED USE:
• When unit needs to be lifted or moved. The kit is not required
when unit is equipped with optional base rail or downflow
application.
High- and Low-Pressure Switches — Protect the unit from
running at unsuitable pressures.
SUGGESTED USE:
• Provides additional safety features when needed.
MODEL DESCRIPTION
CONTENTS
Page
Model Description .................................3
ARI Cooling Capacities .............................4
Heating Capacities and Efficiencies ...................4
Face Area (sq ft)5.955.955.955.955.955.95
Rows...Fins/in.1...171...171...172...172...172...17
CONDENSER FAN
Nominal Airflow (cfm)170017001700190019001900
Nominal Speed (rpm)850850850105010501050
Quantity...Diameter (in.)1...181...181...181...181...181...18
Motor Hp
1
⁄
8
1
⁄
8
1
⁄
8
1
⁄
4
1
⁄
4
1
⁄
4
EVAPORATOR COIL
Face Area (sq ft)1.832.292.292.292.292.29
Rows...Fins/in.3...153...153...153...153...153...15
EVAPORATOR FAN
Nominal Airflow (cfm)600800800100010001000
Nominal Speed (rpm)82510751075107510751075
Diameter x Width (in.)10x1010x1010x1010x1010x1010x10
Motor Hp (single-phase)
(three-phase)———
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
FURNACE SECTION*
Burner Orifice No. (Qty...drill size)
Natural Gas1...321...322...381...322...382...32
Burner Orifice No. (Qty...drill size)
Propane Gas1...411...412...461...412...462...42
RETURN-AIR FILTERS (in.)†
Throwaway20x2020x2020x2020x2420x2420x24
UNIT SIZE 588A036060036080036100036120042060042080
1
⁄
NOMINAL CAPACITY (tons)33333
2
1
3
⁄
2
OPERATING WEIGHT (lb)
Without Base Rail336336348348375375
With Optional Base Rail360360372372399399
Face Area (sq ft)5.955.955.955.957.047.04
Rows...Fins/in.2...172...172...172...172...172...17
CONDENSER FAN
Nominal Airflow (cfm)190019001900190019001900
Nominal Speed (rpm)105010501050105010501050
Quantity...Diameter (in.)1...181...181...181...181...181...18
Motor Hp
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
1
⁄
4
EVAPORATOR COIL
Face Area (sq ft)3.063.063.063.063.333.33
Rows...Fins/in.3...153...153...153...153...153...15
EVAPORATOR FAN
Nominal Airflow (cfm)120012001200120014001400
Nominal Speed (rpm)110011001100110011001100
Diameter x Width (in.)10x1010x1010x1010x1010x1010x10
Motor Hp (single-phase)
(three-phase)
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
1
⁄
2
3
⁄
4
3
⁄
4
3
⁄
4
3
⁄
4
FURNACE SECTION*
Burner Orifice No. (Qty...drill size)
Natural Gas2...382...323...353...322...382...32
Burner Orifice No. (Qty...drill size)
Propane Gas2...462...423...443...422...462...42
RETURN-AIR FILTERS (in.)†
Throwaway20x2420x2420x2420x2424x2424x24
*Based on an altitude of 0-2000 ft.
†Required field-supplied filter sizes are based on the larger of the ARI-rated (Air Conditioning & Refrigeration Institute) cooling airflow or the heating
airflow at a velocity of 300 ft/min for throwaway type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
**Sq inch. Filter is mounted external to unit.
11
SPECIFICATIONS (cont)
UNIT SIZE 588A042100042120048080048100048120048140
NOMINAL CAPACITY (tons)3
OPERATING WEIGHT (lb)
Without Base Rail387387414426426426
With Optional Base Rail411411438450450450
Face Area (sq ft)7.047.048.678.678.678.67
Rows...Fins/in.2...172...172...172...172...172...17
CONDENSER FAN
Nominal Airflow (cfm)190019002400240024002400
Nominal Speed (rpm)105010501050105010501050
Diameter x Width (in.)1...181...181...201...201...201...20
Motor Hp
EVAPORATOR COIL
Face Area (sq ft)3.333.334.444.444.444.44
Rows...Fins/in.3...153...153..153...153...153...15
EVAPORATOR FAN
Nominal Airflow (cfm)140014001600160016001600
Nominal Speed (rpm)110011001100110011001100
Diameter x Width (in.)10x1010x1010x1010x1010x1010x10
Motor Hp (single-phase)
(three-phase)
FURNACE SECTION*
Burner Orifice No. (Qty...drill size)
Natural Gas3...353...322...323...353...323...30
Burner Orifice No. (Qty...drill size)
Propane Gas3...443...422...423...443...423...41
RETURN-AIR FILTERS (in.)†
Throwaway24 x 2424 x 2424 x 3024 x 3024 x 30816**
1
⁄
2
1
⁄
4
3
⁄
4
3
⁄
4
31⁄
2
1
⁄
4
3
⁄
4
3
⁄
4
4444
1
⁄
4
3
⁄
4
3
⁄
4
1
⁄
3
3
⁄
4
3
⁄
4
1
⁄
3
3
⁄
4
3
⁄
4
1
⁄
3
3
⁄
4
3
⁄
4
UNIT SIZE 588A060080060100060120060140
NOMINAL CAPACITY (tons)5555
OPERATING WEIGHT (lb)
Without Base Rail453465465465
With Optional Base Rail477489489489
Face Area (sq ft)8.678.678.678.67
Rows...Fins/in.2...172...172...172...17
CONDENSER FAN
Nominal Airflow (cfm)2400240024002400
Nominal Speed (rpm)1050105010501050
Quantity...Diameter (in.)1...201...201...201...20
Motor Hp
1
⁄
3
1
⁄
3
1
⁄
3
1
⁄
3
EVAPORATOR COIL
Face Area (sq ft)4.444.444.444.44
Rows...Fins/in.4...154...154...154...15
EVAPORATOR FAN
Nominal Airflow (cfm)1995199519951995
Nominal Speed (rpm)1100110011001100
Diameter x Width (in.)10x1010x1010x1010x10
Motor Hp (single-phase)1111
(three-phase)1111
FURNACE SECTION*
Burner Orifice No. (Qty...drill size)
Natural Gas2...323...353...323...30
Burner Orifice No. (Qty...drill size)
Propane Gas2...423...443...423...41
RETURN-AIR FILTERS (in.)†
Throwaway24 x 3024 x 3024 x 30960**
*Based on an altitude of 0-2000 ft.
†Required field-supplied filter sizes are based on the larger of the ARI-rated (Air Conditioning & Refrigeration Institute) cooling airflow or the heating
airflow at a velocity of 300 ft/min for throwaway type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
Enter Net Cooling Capacities table at condenser entering
temperature of 95 F. Unit 588A036 at 1200 cfm and 67 F
ewb (entering wet bulb) will provide a total capacity of
36,000 Btuh and an SHC of 26,200 Btuh. Calculate SHC
correction, if required, using Note 4 under Net Cooling Capacities tables.
III SELECT HEATING CAPACITY OF UNIT TO PROVIDE
DESIGN CONDITION REQUIREMENT.
In the Heating Capacities and Efficiencies table on page 4,
note that unit 588A036080 will provide 64,800 Btuh with an
input of 80,000 Btuh.
IV DETERMINE FAN SPEED AND POWER REQUIRE-
MENTS AT DESIGN CONDITIONS.
Before entering the air delivery tables, calculate the total
static pressure required. From the given, the Wet Coil
Pressure Drop table, and the Filter Pressure Drop table on
page 19, find at 1200 cfm:
External static pressure0.20 in. wg
Wet Coil0.088 in. wg
Filter0.13 in. wg
Total static pressure0.42 in. wg (rounded)
Enter the table for Dry Coil Air Delivery — Horizontal Discharge for 230 and 460 V on page 17. For 208 v operation,
deduct 10% from value given. The fan will deliver 1233 cfm
at 0.4 external static pressure (1370 x 0.9) at high speed
and 852 cfm at 0.5 external static pressure (946 x 0.9) at
low speed. The fan speed should be set at high to satisfy
job requirements.
V SELECT UNIT THAT CORRESPONDS TO POWER
SOURCE AVAILABLE.
The Electrical Data table on page 20 shows that the unit
is designed to operate at 208-1-60.
1. Ratings are net; they account for the effects of the indoor-fan motor
power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used:
t=t –
ldbedb
8595105115
Total
System
kW
1.10 x cfm
Outdoor Coil Entering-Air Temperature (F)
Capacity
(Btuh x 1000)
Total
System
kW
t= Wet-bulb temperature corresponding to enthalpy of air
lwb
h=h –
lwbewb
Where: h= Enthalpy of air entering indoor coil
4. The SHC is based on 80 F edb temperature of air entering indoor
coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
Capacity
(Btuh x 1000)
leaving indoor coil (h)
total capacity (Btuh x 1000)
ewb
Total
System
kW
4.5 x cfm
lwb
Capacity
(Btuh x 1000)
Total
System
kW
16
DRY COIL AIR DELIVERY* — HORIZONTAL DISCHARGE
(Deduct 10% for 208 v)
UNIT
SIZE
588A
018
024,
030
036
042
048
060
*Air delivery values are based on operating voltage of 230 v or 460 v, dry coil, without filter. De-
duct wet coil and filter pressure drops to obtain external static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of
rated cooling capacity. Evaporator coil frosting may occur at airflows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not
recommended.
*Air delivery values are based on operating voltage of 230 v or 460 v, dry coil, without filter. De-
duct wet coil and filter pressure drops to obtain external static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of
rated cooling capacity. Evaporator coil frosting may occur at airflows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not
recommended.
AWG— American Wire Gage
CSA— Canadian Standards Association
FLA— Full Load Amps
HACR — Heating, Air Conditioning and Refrigeration
LRA— Locked Rotor Amps
MCA— Minimum Circuit Amps
MOCP — Maximum Overcurrent Protection (fuses or HACR-type
NEC— National Electrical Code
RLA— Rated Load Amps
*Fuse or HACR breaker.
†Minimum wire size is based on 60 C copper wire. If other than 60 C is
used, determine size from NEC. Voltagedrop of wire must be less than
2% of rated voltage.
NOTES:
1. In compliance with NEC requirements for multimotor and combination
load equipment (refer to NEC Articles 430 and 440), the overcurrent
protective device for the unit shall be fuse or HACR breaker.The CSA
units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is
greater than 2%.
of voltage imbalance.
% Voltage Imbalance
V-PH-HZ
208/230-1-60187253
208/230-3-60187253
460-3-60414506
LEGEND
circuit breaker)
Use the following formula to determine the percent
= 100 x
max voltage deviation from average voltage
VOLTAGE
RANGE
MinMaxRLALRAFLAMCAMOCP*
average voltage
COMPRESSOR
7.6450.71.812.0151475
9.4661.42.015.5251280
5.6400.81.49.21014100
COND.
FAN
MOTOR
INDOOR
FAN
FLA
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage.
(AB) 457 – 452=5v
(BC) 464 – 457=7v
(AC) 457 – 455=2v
Maximum deviation is 7 v.
Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the
maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than
2%, contact your local electric utility company immediately.
POWER SUPPLY
AB = 452 v
BC = 464 v
AC = 455 v
Average Voltage =
= 1.53%
AWG60C
MIN WIRE
SIZE
452 + 464 + 455
1371
=
3
= 457
7
457
3
MAX WIRE
LENGTH
(ft)
20
OPERATING SEQUENCE
HEATING
On a call for heating, terminal ‘‘W’’ of the thermostat is energized, starting the induced-draft motor. When the hall-effect
sensor on the induced-draft motor senses that it has reached
the required speed, the burner sequence begins. This sequence
is performed by the integrated gas control board (IGC). The
indoor-fan motor is energized 45 seconds after flame is established. When the thermostat is satisfied and ‘‘W’’ is deenergized, the indoor-fan motor stops after a 45-second time-off
delay.
COOLING
With the room thermostat SYSTEM switch in the COOL position
and the FAN switch in theAUTO. position, the cooling sequence
of operation is as follows:
When the room temperature rises to a point that is slightly
above the cooling control setting of the thermostat, the thermostat completes the circuit between thermostat terminal R to terminals Y and G. These completed circuits through the
thermostat connect contactor coil (C) (through unit wire Y) and
blower relay coil (BR) (through unit wire G) across the 24-v secondary of transformer (TRAN).
The normally-open contacts of energized contactor (C) close
and complete the circuit through compressor motor (COMP) to
condenser (outdoor) fan motor (OFM). Both motors start
instantly.
The set of normally-open contacts of energized relay BR close
and complete the circuit through evaporator blower (indoor) fan
motor (IFM). The blower motor starts instantly.
NOTE: Once the compressor has started and then has stopped,
it should not be started again until 5 minutes have elapsed.
The cooling cycle remains ‘‘on’’ until the room temperature
drops to point that is slightly below the cooling control setting of
the room thermostat. At this point, the thermostat ‘‘breaks’’ the
circuit between thermostat terminal R to terminals Y and G.
These open circuits deenergize contactor coil C and relay coil
BR. The condenser and compressor motors stop. After a
30-second delay, the blower motor stops. The unit is in a
‘‘standby’’ condition, waiting for the next ‘‘call for cooling’’ from
the room thermostat.
21
TYPICAL FIELD WIRING
NOTES:
1. If any of the original wire furnished must be replaced, it must be replaced with type 90 C wire or its equivalent.
AWG— American Wire Gage
BR— Blower Relay
C—Contactor
CAP— Capacitor
CH— Crankcase Heater
COMP— Compressor Motor
CR— Combustion Relay
EQUIP— Equipment
FL— Fuse Link
FS— Flame Sensor
FU— Fuse
GND— Ground
GVR— Gas Valve Relay
HS— Hall Effect Sensor
HV TRAN — High-Voltage Transformer
I—Ignitor
IDM— Induced-Draft Motor
IFM— Indoor-Fan Motor
IGC— Integrated Gas Control
IP— Internal Protector
LS— Limit Switch
MGV— Main Gas Valve
24
NEC— National Electrical Code
OFM — Outdoor-Fan Motor
PWR — Power
QT— Quadruple Terminal
RS— Rollout Switch
TRAN — Transformer
Field Splice
Terminal (Marked)
Terminal (Unmarked)
Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To Indicate Common Potential
Only, Not to Represent Wiring
TYPICAL INSTALLATION
APPLICATION DATA
1. Condensate trap — A 2-in. condensate trap must be field
supplied.
2. Ductwork — Secure downflow discharge ductwork to roof
curb. For horizontal discharge applications, attach ductwork
to unit with flanges.
Units are equipped with factory-installed duct covers on both
the downflow and horizontal openings. Remove appropriate
duct panel covers for intended discharge application. Units
utilizing downflow option do not require duct panel cover
removal.
3. Thermostat — Toachieve simultaneous economizer cooling
and mechanical cooling, use of 2-stage cooling thermostat
is recommended for all units equipped with accessory
economizer.
4. Airflow — Units are draw-thru on cooling and blow-thru on
heating.
5. Maximum cooling airflow — To minimize the possibility of
condensate blow-off from evaporator, airflow through units
should not exceed 450 cfm/ton.
Minimum cooling airflow is 350 cfm/ton.
Minimum ambient operating temperature for standard units
is 40 F. With accessory low ambient temperature kit, units
can operate at temperatures down to 0° F.
25
ENGINEERS’ SPECIFICATION GUIDE
GENERAL: Furnish and install single-package, outdoor heating
and cooling unit utilizing a rotary, reciprocating, or scroll hermetic compressor for cooling and gas combustion for heating
duty. Unit shall discharge supply air either in downflow or horizontal application as shown on the contract drawings. Unit shall
be capable of starting and running at 125 F ambient outdoor
temperature per maximum load criteria of ARI Standard 210/
240-89. Unit shall be provided with fan time-delay to prevent
cold air delivery before heat exchanger warms up. Unit shall be
provided with 30-second fan time-delay after the thermostat is
satisfied.
Nominal unit electrical characteristics shall bev,
ph, 60 Hz. The unit shall be capable of satisfactory operation within voltage limits oftov.All unit power wiring shall enter unit cabinet at a single location.
COOLING CAPACITY: Total cooling capacity of the unit shall be
Btuh or greater, and sensible capacity shall be
Btuh or greater at conditions ofcfm evaporator entering
air ofF dry bulb,F wet bulb, and condenser entering air ofF dry bulb. Total design conditions shall be a
minimum ofBtuh/Watt. The unit shall be capable of cooling operation down to 40 F.
HEATINGCAPACITY:Totalheating capacity of the unit shall be
Btuh or greater with a gas input ofBtuh.
CABINET:The cabinet shall be constructed of heavy duty, phos-
phated, zinc-coated, prepainted steel capable of withstanding
500 hours in salt spray. Cabinet panels shall be easily removable for servicing. Unit shall be equipped with factory-supplied
condensate drain connection for evaporator coil. Indoor (evaporator) blower compartment interior cabinet surfaces shall be insulated with a minimum
1
⁄2-in. thick, flexible fiberglass
insulation, coated on the air side. Aluminum foil-faced fiberglass
insulation shall be used to meet ASHRAE standard no. 62P.
COMPRESSOR: Compressor shall be welded, fully hermetic
type with factory-installed vibration isolation. Compressor motor
shall be of the refrigerant-cooled type with line break thermal
and current overload protection. Rotary compressors shall be
standard on unit size 018. Reciprocating compressors shall be
standard on unit sizes 024-042. Scroll compressors shall be
standard on unit sizes 048 and 060.
CONDENSER SECTION: The condenser coils shall have
aluminum-plate fins mechanically bonded to seamless copper
tubes with all joints brazed. Condenser fan wheel shall be dynamically balanced. Fan-motor bearings shall be sealed and
permanently lubricated. Condenser-fan motor shall have inher-
ent automatic-reset thermal overload protection and shall be totally enclosed.
EVAPORATOR SECTION: Evaporator coils shall have aluminum plate fins mechanically bonded to seamless copper tubes
with all joints brazed. Evaporator fan shall be of the forwardcurved, centrifugal, direct-driven type. Fan wheel shall be made
from steel, be double-inlet type with forward curved blades with
corrosion resistant finish and be dynamically balanced. Fanmotor bearings shall be sealed and permanently lubricated.
Evaporator-fan motor shall have inherent automatic-reset thermal overload protection and shall be open drip-proof.
HEATING SECTION: The unit shall be equipped with an
induced-draft combustion system with energy saving direct
spark ignition system and redundant main gas valve. The heat
exchanger shall be constructed of aluminized steel for corrosion
resistance. Burners shall be of the inshot type constructed of
aluminum coated steel. An integrated gas control board shall
provide control of heating and simplify troubleshooting through
its built-in diagnostics. All gas piping and electric supply shall
enter the unit cabinet at a single location.
REFRIGERANT SYSTEM: Refrigerant system shall include a
fixed orifice metering device.
CONTROLS: Unit shall be complete with self-contained control
system. Unit staging shall be minimum one-cool, one-heat. In
the event of a power failure, unit control system shall sequence
the unit to restart. Thermostat set points shall have adjustable
deadband between heat and cool. Compressors shall be provided with inherent internal line break safety feature, and also
overcurrent and overtemperature protection.
AGENCY CERTIFICATIONSAND STANDARDS: The unit shall
be UL listed and CSA certified for safety requirements. All wiring
shall be in accordance with NEC. The unit shall be rated in accordance with ARI Standards 210/240-89 and 270-84. Insulation and adhesive shall meet NFPA 90A requirements for flame
spread and smoke generation.
OPTIONS: Factory-installed options shall include: base rail and
downflow application.