Bryant 588A User Manual

Bryant
Air Conditioning
SINGLE PACKAGE GAS HEATING/ ELECTRIC COOLING UNITS
DESCRIPTION
All 588Amodelsfeatureonepiece,compactdesignandarefully self-contained units that are prewired, prepiped, and pre­charged for minimum installation expense. Unit is designed for easy use in either downflow (vertical) or horizontal applications.
STANDARD FEATURES
FACTORY-ASSEMBLED PACKAGE is a compact, fully self-
contained, gas heating/electric cooling unit that is prewired, pre­piped, and precharged for minimum installation expense.
588A units are lightweight and available in a variety of standard heating and cooling sizes with voltage options to meet residen­tial and light commercial requirements. Unit installs easily on a rooftop or a ground-level pad.
CONVERTIBLE DUCT CONFIGURATION on the 588A is de­signed for easy use in either downflow or horizontal discharge applications.
HIGH-EFFICIENCY DESIGN with SEERs (Seasonal Energy Ef­ficiency Ratios) of 10.0.
DURABLE, DEPENDABLE COMPRESSORS are designed for high efficiency. Each compressor is hermetically sealed against contamination to help promote longer life and dependable op­eration. Each compressor also has vibration isolation to provide quiet operation. Rotary, reciprocating, or scroll compressors are used. Compressors have internal high-pressure and overcur­rent protection.
DIRECT-DRIVE MULTISPEED, PSC (permanent split capaci­tor) BLOWER MOTOR is standard on all models.
DIRECT-DRIVE, PSC CONDENSER-FAN MOTORS are de-
signed to help reduce energy consumption and provide for cool­ing operation down to 40 F.
Model 588A
Sizes 018-060
11⁄2to 5 Tons
REFRIGERANT SYSTEM is designed to provide dependability. Liquid refrigerant strainers are used to promote clean, unre­stricted operation. Each unit leaves the factory with a full refrig­erant charge. Refrigerant service connections make checking operating pressures easier.
EVAPORATOR AND CONDENSER COILS are computer­designed for optimum heat transfer and cooling efficiency. Con­denser coil is fabricated of copper tube and aluminum fins and is located inside the unit for protection against damage and for long life and reliable operation. The condenser coil is internally mounted and protected by a composite grille.
Copper fin coils for condenser coil are also available by special order. These coils are recommended in applications where alu­minum fins are likely to be damaged due to corrosion. Copper fin coils are ideal for seacoast applications.
MONOPORT INSHOT BURNERS produce precise air-to-gas mixture, which provides for clean and efficient combustion. The large monoport on the inshot (or injection type) burners seldom, if ever, needs cleaning.
WEATHERIZED CABINETS are constructed of heavy-duty, phosphated, zinc-coated prepainted steel capable of withstand­ing 500 hours in salt spray. Interior surfaces of the evaporator compartment are insulated with foil-faced fiberglass to help keep the conditioned air from being affected by the outdoor am­bient temperature and provide improved air quality.Conforms to American Society of Heating, Refrigeration and Air Conditioning Engineers (ASHRAE) No. 62P. Sloped condensate pan permits an external drain.
LOW SOUND RATINGS ensure a quiet indoor and outdoor en­vironment with sound ratings as low as 7.4 bels.
EASY TO SERVICE CABINETS provide easy accessibility to serviceable components during maintenance and installation. Rounded corners are an important safety feature, and a high­quality finish ensures an attractive appearance.
LOW AND HIGH VOLTAGE ELECTRICAL ENTRIES allow low and high voltage to be brought in either through the duct panel or rear flue panel.
INTEGRATED GAS CONTROL BOARD provides safe and ef­ficient control of heating and simplifies troubleshooting through its built-in diagnostic function.
OPTIONAL BASE RAILS provide holes for rigging and han­dling as well as an elevated mounting frame that provides struc­tural support for horizontal installations.
DOWNFLOW OPTIONS is converted for downflow at factory for easy vertical ductwork connections.
Form No. PDS 588A.18.4B
FACTORY-INSTALLED OPTIONS DESCRIPTION AND USAGE
Unit With Base Rail — Unit has rigging holes and an elevated
mounting frame. SUGGESTED USE:
• Rigging holes to provide greater ease in handling. Frame to provide elevation and structural support for horizontal applications.
FIELD-INSTALLED ACCESSORY DESCRIPTION AND USAGE
Downflow Option — Unit is shipped from factory configured for
downflow application. Unit is equipped with base rail. SUGGESTED USE:
• To provide easy vertical ductwork connections.
Flat Roof Curb — Consists of galvanized steel support frame in 8-, 11-, and 14-in. high designs. Provides wood nailer to attach roof counter flashing. Insulated basepans in curbs are provided to prevent condensation. Ductwork attaches to rails provided in the roof curb. A gasket is provided to form an airtight and wa­tertight seal between unit and curb. The roof curb design meets the standards of the NRCA (National Roofing Contractors’ Association).
SUGGESTED USE:
• Slab-mounted applications when elevation of the unit above the slab is necessary.
• Rooftop application for downflow discharge.
• Curbs are preassembled and are available for flat or pitched roofs.
Pitched Roof Curb — Provided in ratios of 1, 2, 3, 4, 5, and 6 to 12 for use on pitched roof applications.
SUGGESTED USE:
• For when a roof curb is needed on a pitched roof.
Modulating Economizer — Economizer is available for down­flow or horizontal applications, and is designed for easy instal­lation. Economizer reduces energy costs and extends equipment life by allowing the use of outdoor air to supply ‘‘free’’ cooling when conditions are favorable.
Constant ventilation is recommended for light commercial appli­cations when the conditioned space is occupied.
The economizer is shipped complete with a damper motor and linkage, enthalpy control, low-voltage wiring harness, and a rainhood. Adequate wire lengths are provided (additional field­supplied wires are not required). Horizontal economizers are also furnished with a 2-in. disposable air filter and gasket material.
Modulating economizer package consists of low-leakage damp­ers with controls. The economizer will allow a fixed percentage of outdoor ventilation air into the unit whenever the evaporator fan is running.
SUGGESTED USE:
• Allows outdoor air to be used for ‘‘free’’ cooling whenever the outdoor air is below the enthalpy control setting.
• To reduce energy usage. Use whenever the hours of opera­tion at temperatures below 40 F are significant.
Two-Position Damper — In the two-position dampers, the en­thalpy control detects when outdoor air is suitable for ‘‘free’’ cooling by measuring the outdoor-air dry bulb temperature and humidity. Whenever the outdoor-air quality is acceptable for ‘‘free’’ cooling, the outdoor-air damper opens fully and the return-air damper closes, allowing outdoor air to enter the building.
SUGGESTED USE:
• Allows use of outdoor air to cool building without using com­pressor. Damper closes when evaporator fan is off to prevent cold backdraft, and wasted energy.
Manual Outdoor-Air Damper — Package consists of a manu­ally adjustable damper and includes a rainhood and birdscreen.
SUGGESTED USE:
• Toallow a fixed percentage of outdoor air for ventilation under all conditions.
• The damper may be used on either downflow or horizontal air­flow applications.
Thermostat and Subbase — These accessories provide cool­ing control for unit. Autochangeover and manual changeover types are available.
SUGGESTED USE:
• To operate and control unit, and to maintain desired building temperature.
The 0° F Low Ambient Kit — Kit permits operation down to 0° F.
SUGGESTED USE:
• When mechanical cooling is required when outdoor-air tem­perature is between 40 F and 0° F.
Natural-to-Propane Conversion Kit — Kit consists of gas ori­fices and other hardware required to convert the unit for use with LP (liquid propane) gas.
SUGGESTED USE:
• When natural gas cannot be obtained and liquid propane is used as fuel.
Filter Rack — Rack features easy installation and service­ability.
The filter rack housing is constructed of heavy-gage steel and is fully insulated. Both sides of the filter rack are flanged for easy installation.
SUGGESTED USE:
• Kit provides ability to locate filters inside the unit.
Flexible Duct Kit — Consists of 2 flexible UL-listed (Underwrit­ers’ Laboratories) ducts. The duct construction includes vapor barrier and 1-in. fiberglass insulation. The ‘‘K’’ factor is 0.23. Each duct has a square-to-round snap adapter for attachment to the accessory roof curb on one end, and a round clamp collar for attachment to the concentric diffuser box on the other end.
SUGGESTED USE:
• For use with accessory roof curb and concentric box to pro­vide an easily-installed concentric system.
Concentric Diffuser Box — Is aerodynamically designed and equipped with a combination 4-way supply and a center return diffuser. Aspecial core is provided within the diffuser box to pro­vide even 4-way distribution.
SUGGESTED USE:
• For use with accessory roof curb and concentric box to pro­vide an easily-installed concentric system.
Crankcase Heater — Warms crankcase oil to reduce refriger­ant migration and ensure proper compressor lubrication.
SUGGESTED USE:
• For use in applications where crankcase is subjected to low outside temperatures. Recommended on 208/230-v, single­phase, 024-042 units only.
Solid-State ComprotecT Device — Package consists of a con­trol to be field-wired into the unit controls, and provides a 5-minute delay in compressor operation between cooling cycles.
SUGGESTED USE:
• Prevents compressor short cycling when rapid compressor cycles may be a problem.
2
FIELD-INSTALLED ACCESSORY DESCRIPTION AND
USAGE (cont)
Lifting Bracket Kit — Provides attachment point for rigging
straps. SUGGESTED USE:
• When unit needs to be lifted or moved. The kit is not required when unit is equipped with optional base rail or downflow application.
High- and Low-Pressure Switches — Protect the unit from running at unsuitable pressures.
SUGGESTED USE:
• Provides additional safety features when needed.
MODEL DESCRIPTION
CONTENTS
Page
Model Description .................................3
ARI Cooling Capacities .............................4
Heating Capacities and Efficiencies ...................4
Dimensional Drawings ............................5-10
Specifications ..................................11,12
Selection Procedure ..............................13
Net Cooling Capacities ..........................14-16
Air Delivery ....................................17,18
Electrical Data ...................................20
Operating Sequence ..............................21
Typical Field Wiring .............................22-24
Typical Installation ................................25
Application Data .................................25
Engineers’ Specification Guide ......................26
3
ARI* COOLING CAPACITIES
UNIT 588A
018 1
NOMINAL STANDARD NET COOLING†
TONS CFM CAPACITIES (Btuh) (Bels)
1
2
600 17,000 10.0 7.4
024 2 800 24,000 10.0 7.6 030 2
1
2
1000 29,200 10.0 8.0
036 3 1200 36,000 10.0 8.0 042 3
1
2
1400 42,500 10.0 8.2
048 4 1600 47,000 10.0 8.2 060 5 1995 59,500 10.0 8.2
LEGEND
Bels Sound Levels (1 bel = 10 decibels) db dry bulb SEER — Seasonal Energy Efficiency Ratio wb wet bulb
*ARI — Air-conditioning and Refrigeration Institute.
†Rated in accordance with U.S. Government DOE (Department of En-
ergy) test procedures and/or ARI (Air Conditioning and Refrigeration Institute) Standard 210/240-89.
**All units have factory-installed time-delay relay.
††Rated in accordance with ARI Standard 270-84. NOTE: Ratings are net values, reflecting the effects of circulating fan
heat. Ratings are based on 80 F db, 67 F wb indoor entering-air tem­perature and 95 F db air entering outdoor unit.
OUTDOOR SOUND: ONE-THIRD OCTAVE BAND DATA — DECIBELS
MODEL NO. 588A Frequency (Hz) 018 024 030 036 042 048 060
63 49.8 38.1 45.7 47.8 45.5 56.0 54.3 125 56.5 55.0 58.1 59.3 61.2 65.6 65.1 250 60.3 65.3 68.7 67.4 70.4 71.5 71.5 500 59.8 67.2 64.7 68.8 69.9 71.4 72.7
1000 64.1 68.9 73.0 73.1 76.5 74.2 73.9 2000 64.1 65.5 70.2 69.5 71.3 73.3 73.4 4000 65.2 63.8 68.8 68.2 73.7 69.6 71.7 8000 56.0 60.3 66.6 65.8 65.5 67.1 66.3
SEER†**
SOUND RATINGS††
HEATING CAPACITIES AND EFFICIENCIES
UNIT 588A
018040 024040 030040
024060 030060 036060 042060
030080 036080 042080 048080 060080
036100 042100 048100 060100
036120 042120 048120 060120
048140 060140
HEATING INPUT
(Btuh)
40,000 32,800
60,000 48,600
80,000 64,800
100,000 81,000
120,000 97,200
140,000 113,000
LEGEND
AFUE — Annual Fuel Utilization Efficiency CSE California Seasonal Efficiency
NOTE: Before purchasing this appliance, read important energy cost
and efficiency information available from your retailer.
OUTPUT CAPACITY
(Btuh)
TEMPERATURE
RISE RANGE (°F)
20-50 20-50 20-50
25-55 25-55 25-55 25-55
40-70 40-70 40-70 40-70 40-70
50-80 50-80 50-80 50-80
60-90 60-90 60-90 60-90
50-80 50-80
AFUE (%) CSE (%)
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
81.0
80.0
80.0
80.0
80.0
80.0
80.0
76.5
76.5
76.5
77.5
77.5
77.5
77.5
77.5
77.5
77.5
77.5
77.5
78.0
78.0
78.0
78.0
77.5
77.5
77.5
77.5
77.5
77.5
4
DIMENSIONAL DRAWINGS
UNIT
588A018040 588A024040 27.07/688 23.35/593 588A024060 26.98/685 23.27/591 588A030040 26.71/678 23.46/596 588A030060/080 27.15/689 22.36/568 588A036060/080 27.50/698 22.48/571 588A036100/120 27.40/696 22.44/570 588A042060/080 588A042100/120 26.94/684 22.44/570
CG Center of Gravity COND — Condenser LV Low Voltage
NOTE: Clearances must be maintained to prevent recirculation of air from
outdoor-fan discharge. REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel..................................0
Unit top ................................36(914)
Side opposite ducts .........................36(914)
Compressor access .........................36(914)
(Except for NEC requirements) REQ’D CLEARANCES TO COMBUSTIBLE MATL. in. (mm)
Maximum extension of overhangs .................48(1219)
Unit top ................................14(356)
Duct side of unit ...............................0
Side opposite ducts ..........................9(229)
Bottom of unit ................................0
Flue panel ..............................30(762)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ..................42(1067)
Unit and ungrounded surfaces, control box side ..........36(914)
Unit and block or concrete walls and other
grounded surfaces, control box side ...............42(1067)
F
in./mm
9
⁄16/420.7 1815⁄16/481.0
16
9
⁄16/522.3 2215⁄16/582.6
20
UNIT
588A018040 208/230-1-60 272 123 81/37 62/28 76/35 53/24 24.1/613 588A024040 208/230-1-60 303 138 97/44 43/20 123/56 40/18 24.1/613 588A024060 208/230-1-60 315 143 100/45 46/21 126/57 43/20 24.1/613 588A030040 208/230-1-60, 208/230-3-60 320 145 100/45 47/21 126/57 47/21 24.1/613 588A030060/080 208/230-1-60, 208/230-3-60 324 147 94/43 63/29 115/52 52/24 24.1/613 588A036060/080 208/230-1-60, 208/230-3-60, 460-3-60 336 153 86/39 76/35 111/50 63/29 24.1/613 588A036100/120 208/230-1-60, 208/230-3-60, 460-3-60 348 158 89/40 79/36 114/52 66/30 24.1/613 588A042060/080 208/230-1-60, 208/230-3-60, 460-3-60 375 170 95/43 86/39 119/54 75/34 28.1/714 588A042100/120 208/230-1-60, 208/230-3-60, 460-3-60 387 176 98/45 89/40 122/55 78/35 28.1/714
G
in./mm
LEGEND
MAT’L — Material NEC National Electrical Code REQ’D — Required
CENTER OF GRAVITY in./mm
XYZ
25.07/637 20.59/523
27.01/686 22.44/570
ELECTRICAL
CHARACTERISTICS
10.85/276
12.65/321
UNIT WEIGHT
lbkgABCD E
CORNER WEIGHT
(lb/kg)
UNIT HEIGHT
(in./mm)
Unit 588A Sizes 018-042 Without Base Rail
5
DIMENSIONAL DRAWINGS (cont)
UNIT
588A018040 588A024040 26.90/683.3 20.17/512.3 588A024060 26.82/681.2 20.22/513.6 588A030040 26.57/674.9 20.1 /509.3 588A030060/080 26.93/684 21.1 /535.4 588A036060/080 27.31/693.7 21.0 /532.6 588A036100/120 27.23/691.6 21.0 /533.1 588A042060/080 588A042100/120 26.81/681 21.0 /533.7
CG Center of Gravity COND — Condenser LV Low Voltage
NOTE: Clearances must be maintained to prevent recirculation of air from
outdoor-fan discharge. REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel..................................0
Unit top ................................36(914)
Side opposite ducts .........................36(914)
Compressor access .........................36(914)
(Except for NEC requirements) REQ’D CLEARANCES TO COMBUSTIBLE MATL. in. (mm)
Maximum extension of overhangs .................48(1219)
Unit top ................................14(356)
Duct side of unit ...............................0
Side opposite ducts ..........................9(229)
Bottom of unit ................................0
Flue panel ..............................30(762)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ..................42(1067)
Unit and ungrounded surfaces, control box side ..........36(914)
Unit and block or concrete walls and other
grounded surfaces, control box side ...............42(1067)
F
in./mmGin./mm
7
⁄8/504.8 221⁄4/565.4
19
7
⁄8/606.4 261⁄4/666.8
23
LEGEND
UNIT
588A018040 208/230-1-60 296 135 87/40 68/31 82/37 59/27 27.4/697 588A024040 208/230-1-60 327 149 103/47 49/22 129/59 46/21 27.4/697 588A024060 208/230-1-60 339 155 106/48 52/24 132/60 49/22 27.4/697 588A030040 208/230-1-60, 208/230-3-60 344 157 106/48 53/24 132/60 53/24 27.4/697 588A030060/080 208/230-1-60, 208/230-3-60 356 162 102/46 71/32 123/56 60/27 27.4/697 588A036060/080 208/230-1-60, 208/230-3-60, 460-3-60 360 164 92/42 82/37 117/53 69/31 27.4/697 588A036100/120 208/230-1-60, 208/230-3-60, 460-3-60 372 169 95/43 85/39 120/55 72/33 27.4/697 588A042060/080 208/230-1-60, 208/230-3-60, 460-3-60 399 181 101/46 92/42 125/57 81/37 31.4/798 588A042100/120 208/230-1-60, 208/230-3-60, 460-3-60 411 187 104/47 95/43 128/58 84/38 31.4/798
CENTER OF GRAVITY in./mm
XYZ
25.04/636 22.72/577
13.16/334.3
26.87/682.5 21.0 /533.1
MAT’L — Material NEC National Electrical Code REQ’D — Required
ELECTRICAL
CHARACTERISTICS
14.96/380
UNIT WEIGHT
lbkgABCD E
CORNER WEIGHT
(lb/kg)
UNIT HEIGHT
(in./mm)
Unit 588A Sizes 018-060 With Optional Base Rail
6
DIMENSIONAL DRAWINGS (cont)
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel..................................0
Unit top ................................36(914)
Side opposite ducts .........................36(914)
Compressor access .........................36(914)
(Except for NEC requirements) REQ’D CLEARANCES TO COMBUSTIBLE MATL. in. (mm)
Maximum extension of overhangs .................48(1219)
Unit top ................................14(356)
Duct side of unit ...............................0
Side opposite ducts ..........................9(229)
Bottom of unit ................................0
Flue panel ..............................30(762)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ..................42(1067)
Unit and ungrounded surfaces, control box side ..........36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side .....................42(1067)
CG Center of Gravity COND — Condenser LV Low Voltage
NOTE: Clearances must be maintained to prevent recirculation of air from
outdoor-fan discharge.
UNIT
588A048080 28.76/731 23.46/596 15.35/390 588A048100/120/140 28.42/722 23.42/595 15.35/390 588A060080 28.36/720 23.27/591 15.35/390 588A060100/120/140 27.95/710 23.23/590 15.35/390
LEGEND
MAT’L — Material NEC National Electrical Code REQ’D — Required
CENTER OF GRAVITY (in./mm)
XYZ
UNIT
588A048080
588A048100/120/140
588A060080
588A060100/120/140
ELECTRICAL
CHARACTERISTICS
208/230-1-60, 208/230-3-60,
460-3-60
208/230-1-60, 208/230-3-60,
460-3-60
208/230-1-60, 208/230-3-60,
460-3-60
208/230-1-60, 208/230-3-60,
460-3-60
UNIT
WEIGHT
lbkgABCD
414 188 107/49 83/38 158/72 66/30
426 193 110/50 86/39 159/72 71/32
453 206 117/53 93/42 167/76 76/35
465 211 120/55 96/44 167/76 82/37
CORNER WEIGHT
(lb/kg)
Unit 588A, Sizes 048,060 Without Base Rail
7
DIMENSIONAL DRAWINGS (cont)
REQ’D CLEARANCES FOR SERVICING. in. (mm)
Duct panel..................................0
Unit top ................................36(914)
Side opposite ducts .........................36(914)
Compressor access .........................36(914)
(Except for NEC requirements) REQ’D CLEARANCES TO COMBUSTIBLE MATL. in. (mm)
Maximum extension of overhangs .................48(1219)
Unit top ................................14(356)
Duct side of unit ...............................0
Side opposite ducts ..........................9(229)
Bottom of unit ................................0
Flue panel ..............................30(762)
NEC REQ’D CLEARANCES. in. (mm)
Between units, control box side ..................42(1067)
Unit and ungrounded surfaces, control box side ..........36(914)
Unit and block or concrete walls and other grounded
surfaces, control box side .....................42(1067)
CG Center of Gravity COND — Condenser LV Low Voltage
NOTE: Clearances must be maintained to prevent recirculation of air from
outdoor-fan discharge.
UNIT
588A048080 28.54/724.9 20.00/508 17.66/448.6 588A048100/120/140 28.22/716.8 20.05/509.3 17.66/448.6 588A060080 28.18/715.6 20.19/512.8 17.66/448.6 588A060100/120/140 27.79/705.9 20.23/513.8 17.66/448.6
LEGEND
MAT’L — Material NEC National Electrical Code REQ’D — Required
CENTER OF GRAVITY (in./mm)
XYZ
UNIT
588A048080
588A048100/120/140
588A060080
588A060100/120/140
ELECTRICAL
CHARACTERISTICS
208/230-1-60, 208/230-3-60,
460-3-60
208/230-1-60, 208/230-3-60,
460-3-60
208/230-1-60, 208/230-3-60,
460-3-60
208/230-1-60, 208/230-3-60,
460-3-60
UNIT
WEIGHT
lb kg A B C D
438 199 113/51 89/40 164/75 72/33
450 205 116/53 92/42 165/75 77/35
477 217 123/56 99/45 173/79 82/37
489 222 126/57 102/46 173/79 88/40
CORNER WEIGHT
(lb/kg)
Unit 588A Sizes 048,060 With Optional Base Rail
8
DIMENSIONAL DRAWINGS (cont)
PART NUMBER ‘‘A’’ ‘‘B’’ PITCH
FLAT
PITCHED
NOTES:
1. Roof curb must be set up for unit being installed.
2. Seal strip must be applied as required for unit being installed.
3. Dimensions in [ ] are in millimeters.
4. Roof curb is made of 16 gage steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance 4 ft on each side.
7. Direction of airflow.
8. Insulated panels: 1-in. thick fiberglass, 1 lb density.
389099-701 89 [203] — 389100-701 119 [279] — 389101-701 149 [356] — 389103-701 89 [203] 10 389104-701 89 [203] 13 389105-701 89 [203] 16 389106-701 89 [203] 19 389107-701 89 [203] 22 389108-701 89 [203] 25
7
⁄89 [276] 1:12
9
⁄169 [344] 2:12
3
⁄89 [416] 3:12
1
⁄49 [489] 4:12
3
⁄89 [568] 5:12
5
⁄89 [651] 6:12
Roof Curb, Sizes 018-060
9
DIMENSIONAL DRAWINGS (cont)
Manual Outdoor-Air Damper
Two-Position Damper
ACCESSORY PART NUMBER ‘‘A’’
FILTER
RACK
Filter Racks and Filters
10
389093-701 21 389094-701 31 389125-701 25
11
16
9
11
16
9
11
16
9
SPECIFICATIONS
UNIT SIZE 588A 018040 024040 024060 030040 030060 030080
NOMINAL CAPACITY (tons) 1
1
2
222
1
2
1
2
2
1
2
2
OPERATING WEIGHT (lb)
Without Base Rail 272 303 315 320 324 324 With Optional Base Rail 296 327 339 344 356 356
COMPRESSOR
Type Rotary Reciprocating Quantity 11
REFRIGERANT R-22
Charge (lb) 2.60 2.75 2.75 3.40 3.40 3.40
REFRIGERANT METERING DEVICE Fixed Orifice Metering Device CONDENSER COIL
Face Area (sq ft) 5.95 5.95 5.95 5.95 5.95 5.95 Rows...Fins/in. 1...17 1...17 1...17 2...17 2...17 2...17
CONDENSER FAN
Nominal Airflow (cfm) 1700 1700 1700 1900 1900 1900 Nominal Speed (rpm) 850 850 850 1050 1050 1050 Quantity...Diameter (in.) 1...18 1...18 1...18 1...18 1...18 1...18 Motor Hp
1
8
1
8
1
8
1
4
1
4
1
4
EVAPORATOR COIL
Face Area (sq ft) 1.83 2.29 2.29 2.29 2.29 2.29 Rows...Fins/in. 3...15 3...15 3...15 3...15 3...15 3...15
EVAPORATOR FAN
Nominal Airflow (cfm) 600 800 800 1000 1000 1000 Nominal Speed (rpm) 825 1075 1075 1075 1075 1075 Diameter x Width (in.) 10x10 10x10 10x10 10x10 10x10 10x10 Motor Hp (single-phase)
(three-phase) ———
1
4
1
4
1
4
1
4
1
4
1
4
1
4
1
4
1
4
FURNACE SECTION*
Burner Orifice No. (Qty...drill size)
Natural Gas 1...32 1...32 2...38 1...32 2...38 2...32
Burner Orifice No. (Qty...drill size)
Propane Gas 1...41 1...41 2...46 1...41 2...46 2...42
RETURN-AIR FILTERS (in.)†
Throwaway 20x20 20x20 20x20 20x24 20x24 20x24
UNIT SIZE 588A 036060 036080 036100 036120 042060 042080
1
NOMINAL CAPACITY (tons) 33333
2
1
3
2
OPERATING WEIGHT (lb)
Without Base Rail 336 336 348 348 375 375 With Optional Base Rail 360 360 372 372 399 399
COMPRESSOR
Type Reciprocating Quantity 1
REFRIGERANT R-22
Charge (lb-oz) 4.30 4.30 4.30 4.30 5.20 5.20
REFRIGERANT METERING DEVICE Fixed Orifice Metering Device CONDENSER COIL
Face Area (sq ft) 5.95 5.95 5.95 5.95 7.04 7.04 Rows...Fins/in. 2...17 2...17 2...17 2...17 2...17 2...17
CONDENSER FAN
Nominal Airflow (cfm) 1900 1900 1900 1900 1900 1900 Nominal Speed (rpm) 1050 1050 1050 1050 1050 1050 Quantity...Diameter (in.) 1...18 1...18 1...18 1...18 1...18 1...18 Motor Hp
1
4
1
4
1
4
1
4
1
4
1
4
EVAPORATOR COIL
Face Area (sq ft) 3.06 3.06 3.06 3.06 3.33 3.33 Rows...Fins/in. 3...15 3...15 3...15 3...15 3...15 3...15
EVAPORATOR FAN
Nominal Airflow (cfm) 1200 1200 1200 1200 1400 1400 Nominal Speed (rpm) 1100 1100 1100 1100 1100 1100 Diameter x Width (in.) 10x10 10x10 10x10 10x10 10x10 10x10 Motor Hp (single-phase)
(three-phase)
1
2
1
2
1
2
1
2
1
2
1
2
1
2
1
2
3
4
3
4
3
4
3
4
FURNACE SECTION*
Burner Orifice No. (Qty...drill size)
Natural Gas 2...38 2...32 3...35 3...32 2...38 2...32
Burner Orifice No. (Qty...drill size)
Propane Gas 2...46 2...42 3...44 3...42 2...46 2...42
RETURN-AIR FILTERS (in.)†
Throwaway 20x24 20x24 20x24 20x24 24x24 24x24
*Based on an altitude of 0-2000 ft. †Required field-supplied filter sizes are based on the larger of the ARI-rated (Air Conditioning & Refrigeration Institute) cooling airflow or the heating
airflow at a velocity of 300 ft/min for throwaway type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
**Sq inch. Filter is mounted external to unit.
11
SPECIFICATIONS (cont)
UNIT SIZE 588A 042100 042120 048080 048100 048120 048140
NOMINAL CAPACITY (tons) 3 OPERATING WEIGHT (lb)
Without Base Rail 387 387 414 426 426 426 With Optional Base Rail 411 411 438 450 450 450
COMPRESSOR
Type Reciprocating Hermetic Scroll Quantity 11
REFRIGERANT R-22
Charge (lb) 5.20 5.20 6.50 6.50 6.50 6.50
REFRIGERANT METERING DEVICE Fixed Orifice Metering Device CONDENSER COIL
Face Area (sq ft) 7.04 7.04 8.67 8.67 8.67 8.67 Rows...Fins/in. 2...17 2...17 2...17 2...17 2...17 2...17
CONDENSER FAN
Nominal Airflow (cfm) 1900 1900 2400 2400 2400 2400 Nominal Speed (rpm) 1050 1050 1050 1050 1050 1050 Diameter x Width (in.) 1...18 1...18 1...20 1...20 1...20 1...20 Motor Hp
EVAPORATOR COIL
Face Area (sq ft) 3.33 3.33 4.44 4.44 4.44 4.44 Rows...Fins/in. 3...15 3...15 3..15 3...15 3...15 3...15
EVAPORATOR FAN
Nominal Airflow (cfm) 1400 1400 1600 1600 1600 1600 Nominal Speed (rpm) 1100 1100 1100 1100 1100 1100 Diameter x Width (in.) 10x10 10x10 10x10 10x10 10x10 10x10 Motor Hp (single-phase)
(three-phase)
FURNACE SECTION*
Burner Orifice No. (Qty...drill size)
Natural Gas 3...35 3...32 2...32 3...35 3...32 3...30
Burner Orifice No. (Qty...drill size)
Propane Gas 3...44 3...42 2...42 3...44 3...42 3...41
RETURN-AIR FILTERS (in.)†
Throwaway 24 x 24 24 x 24 24 x 30 24 x 30 24 x 30 816**
1
2
1
4
3
4
3
4
31⁄
2
1
4
3
4
3
4
4444
1
4
3
4
3
4
1
3
3
4
3
4
1
3
3
4
3
4
1
3
3
4
3
4
UNIT SIZE 588A 060080 060100 060120 060140
NOMINAL CAPACITY (tons) 5555 OPERATING WEIGHT (lb)
Without Base Rail 453 465 465 465 With Optional Base Rail 477 489 489 489
COMPRESSOR
Type Hermetic Scroll Quantity 1
REFRIGERANT R-22
Charge (lb) 7.00 7.00 7.00 7.00
REFRIGERANT METERING DEVICE Fixed Orifice Metering Device CONDENSER COIL
Face Area (sq ft) 8.67 8.67 8.67 8.67 Rows...Fins/in. 2...17 2...17 2...17 2...17
CONDENSER FAN
Nominal Airflow (cfm) 2400 2400 2400 2400 Nominal Speed (rpm) 1050 1050 1050 1050 Quantity...Diameter (in.) 1...20 1...20 1...20 1...20 Motor Hp
1
3
1
3
1
3
1
3
EVAPORATOR COIL
Face Area (sq ft) 4.44 4.44 4.44 4.44 Rows...Fins/in. 4...15 4...15 4...15 4...15
EVAPORATOR FAN
Nominal Airflow (cfm) 1995 1995 1995 1995 Nominal Speed (rpm) 1100 1100 1100 1100 Diameter x Width (in.) 10x10 10x10 10x10 10x10 Motor Hp (single-phase) 1111
(three-phase) 1111
FURNACE SECTION*
Burner Orifice No. (Qty...drill size)
Natural Gas 2...32 3...35 3...32 3...30
Burner Orifice No. (Qty...drill size)
Propane Gas 2...42 3...44 3...42 3...41
RETURN-AIR FILTERS (in.)†
Throwaway 24 x 30 24 x 30 24 x 30 960**
*Based on an altitude of 0-2000 ft.
†Required field-supplied filter sizes are based on the larger of the ARI-rated (Air Conditioning & Refrigeration Institute) cooling airflow or the heating
airflow at a velocity of 300 ft/min for throwaway type. Air filter pressure drop for non-standard filters must not exceed 0.08 in. wg.
**Sq inch. Filter is mounted external to unit.
12
SELECTION PROCEDURE
I DETERMINE COOLING AND HEATING REQUIRE-
MENTS AT DESIGN CONDITIONS:
Given:
Required Cooling Capacity (TC) ..........34,000 Btuh
Sensible Heat Capacity (SHC) ...........24,000 Btuh
Required Heating Capacity ..............60,000 Btuh
Condenser Entering-Air Temperature ............95F
Indoor-Air Temperature ...........80Fedb, 67 F ewb
Evaporator-Air Quantity ...................1200 cfm
External Static Pressure .................0.20 in. wg
Electrical Characteristics (V-Ph-Hz) ..........208-1-60
II SELECT UNIT BASED ON REQUIRED COOLING
CAPACITY.
Enter Net Cooling Capacities table at condenser entering temperature of 95 F. Unit 588A036 at 1200 cfm and 67 F ewb (entering wet bulb) will provide a total capacity of 36,000 Btuh and an SHC of 26,200 Btuh. Calculate SHC correction, if required, using Note 4 under Net Cooling Ca­pacities tables.
III SELECT HEATING CAPACITY OF UNIT TO PROVIDE
DESIGN CONDITION REQUIREMENT.
In the Heating Capacities and Efficiencies table on page 4, note that unit 588A036080 will provide 64,800 Btuh with an input of 80,000 Btuh.
IV DETERMINE FAN SPEED AND POWER REQUIRE-
MENTS AT DESIGN CONDITIONS.
Before entering the air delivery tables, calculate the total static pressure required. From the given, the Wet Coil Pressure Drop table, and the Filter Pressure Drop table on page 19, find at 1200 cfm:
External static pressure 0.20 in. wg Wet Coil 0.088 in. wg Filter 0.13 in. wg
Total static pressure 0.42 in. wg (rounded)
Enter the table for Dry Coil Air Delivery — Horizontal Dis­charge for 230 and 460 V on page 17. For 208 v operation, deduct 10% from value given. The fan will deliver 1233 cfm at 0.4 external static pressure (1370 x 0.9) at high speed and 852 cfm at 0.5 external static pressure (946 x 0.9) at low speed. The fan speed should be set at high to satisfy job requirements.
V SELECT UNIT THAT CORRESPONDS TO POWER
SOURCE AVAILABLE.
The Electrical Data table on page 20 shows that the unit is designed to operate at 208-1-60.
13
588A018 (11⁄2TONS)
Indoor
Coil Air
Cfm BF
525 0.10
600 0.12
675 0.13
588A024 (2 TONS)
Indoor
Coil Air
Cfm BF
700 0.06
800 0.07
900 0.08
Ewb
(F) 72 19.0 8.70 1.85 18.5 8.56 2.00 17.9 8.37 2.15 17.1 8.10 2.31
67 17.4 11.2 1.80 16.9 11.1 1.95 16.2 10.9 2.10 15.5 10.6 2.26 62 15.8 13.6 1.76 15.3 13.4 1.90 14.6 13.2 2.05 13.8 12.8 2.20
72 19.2 8.97 1.90 18.7 8.87 2.05 18.0 8.60 2.20 17.3 8.44 2.37 67 17.6 11.8 1.86 17.0 11.6 2.00 16.3 11.4 2.15 15.6 11.2 2.31 62 16.0 14.4 1.81 15.5 14.2 1.95 14.9 14.0 2.10 14.1 13.6 2.25
72 19.3 9.18 1.95 18.8 9.08 2.10 18.0 8.83 2.25 17.4 8.73 2.42 67 17.8 12.4 1.91 17.1 12.2 2.05 16.4 12.0 2.20 15.7 11.7 2.36 62 16.1 15.1 1.86 15.6 14.9 2.01 14.9 14.6 2.15 14.3 14.2 2.31
Ewb
(F) 72 27.8 13.2 2.69 26.3 12.7 2.84 24.6 12.1 2.97 22.9 11.6 3.10
67 25.1 16.6 2.60 23.6 16.1 2.73 22.0 15.5 2.86 20.3 14.9 2.97 62 22.5 19.8 2.51 21.1 19.3 2.63 19.6 18.5 2.74 17.9 17.6 2.85
72 28.3 13.7 2.75 26.6 13.1 2.89 25.0 12.7 3.03 23.2 12.2 3.16 67 25.6 17.6 2.65 24.0 17.1 2.82 22.4 16.5 2.92 20.6 15.9 3.03 62 23.0 21.2 2.56 21.5 20.5 2.69 20.0 19.7 2.81 18.6 18.5 2.93
72 28.7 14.2 2.80 27.0 13.7 2.95 25.3 13.2 3.09 23.5 12.7 3.21 67 26.0 18.6 2.71 24.4 18.1 2.85 22.6 17.4 2.97 20.9 16.9 3.09 62 23.4 22.3 2.62 21.9 21.5 2.75 20.5 20.5 2.88 19.2 19.2 3.01
NET COOLING CAPACITIES
Outdoor Coil Entering-Air Temperature (F)
85 95 105 115
Capacity
(Btuh x 1000)
Total Sensible Total Sensible Total Sensible Total Sensible
85 95 105 115
Capacity
(Btuh x 1000)
Total Sensible Total Sensible Total Sensible Total Sensible
Total
System
kW
Total
System
kW
Capacity
(Btuh x 1000)
Outdoor Coil Entering-Air Temperature (F)
Capacity
(Btuh x 1000)
Total
System
kW
Total
System
kW
Capacity
(Btuh x 1000)
Capacity
(Btuh x 1000)
Total
System
kW
Total
System
kW
Capacity
(Btuh x 1000)
Capacity
(Btuh x 1000)
Total
System
kW
Total
System
kW
588A030 (21⁄2TONS)
Indoor
Coil Air
Capacity
(Btuh x 1000)
Total Sensible Total Sensible Total Sensible Total Sensible
LEGEND
Ewb
(F) 72 33.7 16.3 3.16 31.7 15.6 3.33 29.9 15.0 3.49 27.6 14.2 3.62
67 30.7 21.0 3.09 28.8 20.4 3.25 26.9 19.6 3.40 24.8 18.8 3.53 62 27.5 25.2 3.01 25.8 24.4 3.16 23.9 23.4 3.30 21.9 21.9 3.44
72 34.0 16.9 3.22 32.3 16.4 3.40 30.1 15.6 3.54 28.0 15.0 3.89 67 31.1 22.3 3.15 29.2 21.6 3.32 27.2 20.9 3.46 25.0 20.1 3.59 62 28.0 26.8 3.07 26.3 25.9 3.23 24.6 24.6 3.38 22.9 22.9 3.52
72 34.5 17.6 3.28 32.4 16.9 3.44 30.5 16.4 3.61 28.1 15.6 3.74 67 31.3 23.4 3.20 29.4 22.7 3.37 27.5 22.1 3.62 25.2 21.2 3.64 62 28.4 28.2 3.13 26.9 26.9 3.30 25.3 25.3 3.45 23.6 23.6 3.59
sensible capacity (Btuh x 1000)
Cfm BF
875 0.08
1000 0.09
1125 0.10
BF Bypass Factor Ewb — Entering Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh)
NOTES:
1. Ratings are net; they account for the effects of the indoor-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used: t=t –
ldb edb
85 95 105 115
Total
System
kW
1.10 x cfm
Outdoor Coil Entering-Air Temperature (F)
Capacity
(Btuh x 1000)
Total
System
kW
t = Wet-bulb temperature corresponding to enthalpy of air
lwb
h=h –
lwb ewb
Where: h = Enthalpy of air entering indoor coil
4. The SHC is based on 80 F edb temperature of air entering indoor coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
Capacity
(Btuh x 1000)
leaving indoor coil (h )
total capacity (Btuh x 1000)
ewb
Total
System
kW
lwb
4.5 x cfm
Capacity
(Btuh x 1000)
Total
System
kW
14
588A036 (3 TONS)
Indoor
Coil Air
Cfm BF
1050 0.07
1200 0.08
1350 0.09
588A042 (31⁄2TONS)
Indoor
Coil Air
Cfm BF
1225 0.11
1400 0.12
1575 0.14
Ewb
(F) 72 41.7 19.9 3.99 39.3 19.1 4.18 37.2 18.4 4.39 34.7 17.5 4.57
67 37.6 25.4 3.86 35.5 24.7 4.05 33.2 23.8 4.23 30.9 22.9 4.41 62 33.6 30.5 3.72 31.2 29.4 3.90 28.8 28.2 4.08 26.7 26.7 4.26
72 42.3 20.7 4.08 40.2 20.1 4.29 37.6 19.2 4.48 35.0 18.3 4.66 67 38.3 27.1 3.95 36.0 26.2 4.14 33.7 25.4 4.32 31.3 24.5 4.50 62 34.2 32.5 3.81 31.9 31.4 3.99 30.0 30.0 4.17 28.1 28.1 4.37
72 42.6 21.4 4.15 40.4 20.8 4.36 37.9 20.0 4.56 35.2 19.0 4.73 67 38.7 28.5 4.03 36.4 27.7 4.22 34.0 26.8 4.41 31.6 25.9 4.58 62 34.8 34.2 3.90 32.8 32.8 4.09 31.1 31.0 4.29 29.2 29.2 4.48
Ewb
(F) 72 47.9 23.5 4.57 45.3 22.5 4.81 43.0 21.8 5.08 40.1 20.7 5.30
67 44.2 30.0 4.43 41.8 29.2 4.67 39.3 28.2 4.90 36.7 27.2 5.12 62 40.3 36.1 4.28 38.0 34.9 4.50 35.7 33.8 4.73 33.3 32.5 4.94
72 48.5 24.3 4.66 45.9 23.4 4.91 43.3 22.5 5.17 40.4 21.4 5.39 67 44.9 31.7 4.52 42.5 30.9 4.77 39.9 29.9 5.01 37.2 28.8 5.23 62 41.1 38.3 4.38 38.8 37.1 4.61 36.4 35.8 4.84 34.1 34.1 5.06
72 49.0 25.0 4.75 46.4 24.2 5.00 43.7 23.4 5.26 40.8 22.3 5.49 67 45.4 33.2 4.61 43.0 32.5 4.87 40.4 31.5 5.10 37.6 30.4 5.32 62 41.8 40.2 4.48 39.4 38.9 4.71 37.2 37.2 4.94 35.0 35.0 5.18
NET COOLING CAPACITIES (cont)
Outdoor Coil Entering-Air Temperature (F)
85 95 105 115
Capacity
(Btuh x 1000)
Total Sensible Total Sensible Total Sensible Total Sensible
85 95 105 115
Capacity
(Btuh x 1000)
Total Sensible Total Sensible Total Sensible Total Sensible
Total
System
kW
Total
System
kW
Capacity
(Btuh x 1000)
Outdoor Coil Entering-Air Temperature (F)
Capacity
(Btuh x 1000)
Total
System
kW
Total
System
kW
Capacity
(Btuh x 1000)
Capacity
(Btuh x 1000)
Total
System
kW
Total
System
kW
Capacity
(Btuh x 1000)
Capacity
(Btuh x 1000)
Total
System
kW
Total
System
kW
588A048 (4 TONS)
Indoor
Coil Air
Capacity
(Btuh x 1000)
Total Sensible Total Sensible Total Sensible Total Sensible
LEGEND
Ewb
(F) 72 52.9 25.6 4.95 50.9 24.8 5.38 48.8 24.1 5.83 46.4 23.4 6.34
67 48.3 32.7 4.85 46.4 32.1 5.28 44.2 31.2 5.73 41.5 30.2 6.22 62 43.8 39.4 4.76 41.9 38.6 5.17 39.3 37.3 5.61 36.6 35.9 6.08
72 53.7 26.4 5.07 51.7 25.9 5.50 49.2 25.1 5.95 47.0 24.3 6.45 67 49.1 34.6 4.97 47.0 33.9 5.40 44.7 33.1 5.85 42.4 32.4 6.34 62 44.5 41.9 4.87 42.6 41.1 5.29 40.1 39.7 5.74 37.7 37.6 6.22
72 53.9 27.1 5.17 52.2 26.8 5.61 49.6 26.0 6.06 47.4 25.4 6.57 67 49.6 36.4 5.08 47.5 35.9 5.51 45.2 35.1 5.96 42.8 34.2 6.46 62 45.1 44.1 4.99 43.3 43.1 5.41 41.2 41.2 5.87 39.0 39.0 6.36
sensible capacity (Btuh x 1000)
Cfm BF
1400 0.08
1600 0.10
1800 0.11
BF Bypass Factor Ewb — Entering Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh)
NOTES:
1. Ratings are net; they account for the effects of the indoor-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used: t=t –
ldb edb
85 95 105 115
Total
System
kW
1.10 x cfm
Outdoor Coil Entering-Air Temperature (F)
Capacity
(Btuh x 1000)
Total
System
kW
t = Wet-bulb temperature corresponding to enthalpy of air
lwb
h=h –
lwb ewb
Where: h = Enthalpy of air entering indoor coil
4. The SHC is based on 80 F edb temperature of air entering indoor coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
Capacity
(Btuh x 1000)
leaving indoor coil (h )
total capacity (Btuh x 1000)
ewb
Total
System
kW
lwb
4.5 x cfm
Capacity
(Btuh x 1000)
Total
System
kW
15
NET COOLING CAPACITIES (cont)
588A060 (5 TONS)
Indoor
Coil Air
Capacity
(Btuh x 1000)
Total Sensible Total Sensible Total Sensible Total Sensible
LEGEND
Ewb
(F) 72 69.4 34.2 6.53 66.2 33.2 7.05 62.9 32.1 7.60 59.5 30.9 8.19
67 62.0 43.7 6.33 58.8 42.4 6.82 55.1 41.1 7.37 52.0 40.0 7.94 62 55.0 52.4 6.14 51.8 51.0 6.62 48.7 48.7 7.17 45.8 45.8 7.77
72 70.5 35.8 6.70 67.3 34.8 7.22 63.9 33.7 7.78 60.5 32.6 8.36 67 63.1 46.7 6.50 59.5 45.3 7.00 56.0 44.0 7.54 52.8 42.8 8.12 62 56.3 56.1 6.32 53.6 53.5 6.83 51.0 50.9 7.39 48.5 48.4 7.98
72 71.3 37.4 6.88 68.1 36.3 7.39 64.5 35.3 7.95 60.8 34.1 8.53 67 63.9 49.5 6.67 60.2 48.2 7.17 56.7 46.9 7.71 53.4 45.6 8.29 62 58.2 58.1 6.52 55.6 55.6 7.03 53.0 52.8 7.59 50.4 50.3 8.18
sensible capacity (Btuh x 1000)
Cfm BF
1750 0.03
2000 0.04
2250 0.05
BF Bypass Factor Ewb — Entering Wet-Bulb SHC — Sensible Heat Capacity (1000 Btuh)
NOTES:
1. Ratings are net; they account for the effects of the indoor-fan motor power and heat.
2. Direct interpolation is permissible. Do not extrapolate.
3. The following formulas may be used: t=t –
ldb edb
85 95 105 115
Total
System
kW
1.10 x cfm
Outdoor Coil Entering-Air Temperature (F)
Capacity
(Btuh x 1000)
Total
System
kW
t = Wet-bulb temperature corresponding to enthalpy of air
lwb
h=h –
lwb ewb
Where: h = Enthalpy of air entering indoor coil
4. The SHC is based on 80 F edb temperature of air entering indoor coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.
Correction Factor = 1.10 x (1 – BF) x (edb – 80).
Capacity
(Btuh x 1000)
leaving indoor coil (h )
total capacity (Btuh x 1000)
ewb
Total
System
kW
4.5 x cfm
lwb
Capacity
(Btuh x 1000)
Total
System
kW
16
DRY COIL AIR DELIVERY* — HORIZONTAL DISCHARGE
(Deduct 10% for 208 v)
UNIT SIZE
588A
018
024, 030
036
042
048
060
*Air delivery values are based on operating voltage of 230 v or 460 v, dry coil, without filter. De-
duct wet coil and filter pressure drops to obtain external static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
MOTOR
SPEED
Low
High
Low
Med
High
Low
Med
High
Low
High
Low
High
Low
Med
High
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Watts 230 225 220 210 195 170 ————— Cfm760745725695640540————— Watts ————270235200———— Cfm————850700450———— Watts 275 275 273 269 260 257 249 — Cfm 857 835 802 782 745 717 663 — Watts 371 368 360 349 345 326 319 304 293 — Cfm 1079 1063 1027 996 978 919 865 783 726 — Watts 514 493 476 460 443 425 401 378 344 — Cfm 1409 1383 1324 1282 1223 1156 1068 984 857 — Watts 473 447 427 418 395 367 346 337 323 — Cfm 1253 1253 1172 1130 1047 946 865 829 768 — Watts 519 500 478 459 439 410 377 357 340 — Cfm 1414 1366 1287 1234 1162 1074 920 829 743 — Watts 667 634 609 593 564 541 506 469 436 422 — Cfm 1734 1639 1563 1461 1370 1292 1157 960 829 743 — Watts 678 635 604 580 550 520 493 455 430 — Cfm 1540 1515 1475 1430 1375 1280 1225 1128 1020 — Watts 820 785 750 700 680 649 612 570 — Cfm 1825 1750 1685 1610 1525 1485 1335 1215 — Watts 854 786 744 706 641 606 557 511 — Cfm 2026 1905 1830 1752 1603 1513 1367 1228 — Watts 905 846 824 804 748 683 637 — Cfm 2025 1905 1830 1752 1603 1398 1228 — Watts 1000 991 970 925 904 875 849 830 819 — Cfm 2125 2110 2085 2046 2009 1960 1900 1845 1775 — Watts 1355 1315 1265 1212 1158 1103 987 925 880 — Cfm 2480 2440 2388 2336 2266 2198 2050 1968 1890 — Watts 1435 1375 1310 1265 1175 1108 1010 915 — Cfm 2509 2450 2380 2310 2235 2160 2083 1888
230 AND 460 VOLT HORIZONTAL DISCHARGE
External Static Pressure (in. wg)
17
DRY COIL AIR DELIVERY* — VERTICAL DISCHARGE
(Deduct 10% for 208 v)
UNIT SIZE 588A
018
024,
030
036
042
048
060
*Air delivery values are based on operating voltage of 230 v or 460 v, dry coil, without filter. De-
duct wet coil and filter pressure drops to obtain external static pressure available for ducting.
NOTES:
1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at airflows below this point.
2. Dashes indicate portions of table that are beyond the blower motor capacity or are not recommended.
MOTOR
SPEED
Low
High
Low
Med
High
Low
Med
High
Low
High
Low
High
Low
Med
High
0.0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1.0
Watts 295 251 223 201 176 149 124 — Cfm 821 817 753 665 536 343 164 — Watts 401 376 346 322 294 272 250 229 219 — Cfm 1334 1253 1128 996 816 658 461 246 167 — Watts 285 284 282 278 274 270 261 251 244 230 Cfm 798 761 727 682 634 581 525 450 371 304 Watts 378 371 368 362 357 343 332 315 301 283 Cfm 1011 982 948 906 858 771 703 597 492 387 Watts 520 511 487 472 451 431 411 385 362 341 Cfm 1342 1289 1237 1181 1106 1007 892 745 610 471 Watts 460 439 423 898 379 349 322 297 270 246 Cfm 1191 1136 1081 1005 907 795 687 579 471 349 Watts 511 492 470 450 420 392 364 332 308 275 Cfm 1316 1244 1178 1104 1005 891 784 657 535 389 Watts 655 631 603 584 552 522 492 459 433 398 Cfm 1541 1458 1367 1292 1178 1053 920 806 662 509 Watts 637 612 587 560 536 493 455 — Cfm 1500 1450 1405 1350 1290 1200 1105 — Watts 790 750 700 699 639 608 574 547 — Cfm 1750 1625 1604 1509 1421 1323 1221 1094 — Watts 847 784 746 708 646 609 563 516 — Cfm 1995 1901 1822 1730 1580 1477 1319 1178 — Watts 909 852 820 801 751 687 639 — Cfm 2018 1896 1814 1729 1582 1380 1220 — Watts 970 952 928 905 880 847 804 760 — Cfm 2075 2054 2024 1994 1945 1890 1830 1762 — Watts 1291 1247 1195 1076 1025 970 921 833 810 Cfm 2395 2348 2291 2164 2099 2022 1950 1827 1804 Watts 1490 1400 1312 1270 1219 1161 1104 1045 985 930 Cfm 2530 2475 2420 2355 2289 2223 2150 2079 2008 1932
230 AND 460 VOLT VERTICAL DISCHARGE
External Static Pressure (in. wg)
18
WET COIL PRESSURE DROP
UNIT SIZE
588A
018
024
030
036
042
048
060
AIRFLOW
(cfm)
600 0.069 700 0.082 800 0.102 900 0.116 600 0.039 700 0.058 800 0.075 900 0.088
900 0.088 1000 0.095 1200 0.123 1000 0.068 1200 0.088 1400 0.108 1600 0.123 1000 0.048 1200 0.069 1400 0.088 1600 0.102 1400 0.068 1600 0.075 1800 0.088 1700 0.082 1900 0.095 2100 0.108 2300 0.123
PRESSURE DROP
(in. wg)
FILTER PRESSURE DROP (in. wg)
UNIT SIZE
588A
018, 024 20 x 20 0.05 0.07 0.08 0.10 0.12 0.13 ———————————— 030, 036 20x24————0.09 0.10 0.11 0.13 0.14 0.15 0.16 ————————
042 24x24—————— — —0.110.12 0.14 0.15 ———————
048, 060 24x30—————— — — —0.09 0.10 0.11 0.12 0.13 0.14 0.15 0.16 0.17 0.18
FILTER
SIZE (in.)
500 600 700 800 900 1000 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300
CFM
19
ELECTRICAL DATA
UNIT 588A
018 024 12.4 61 0.7 2.0 18.2 30 12 80 030 14.4 82 1.4 2.0 21.8 30 10 100 036 18.0 96 1.4 2.8 26.7 40 10 90 042 20.4 104 1.4 4.0 30.9 50 8 100 048 26.4 129 2.1 5.0 40.1 60 6 100 060 32.1 169 2.1 6.8 49.0 60 6 100
030 036 11.7 75 1.4 2.8 18.8 30 12 65 042 14.0 91 1.4 4.0 22.9 35 10 85 048 15.0 99 2.1 5.0 25.9 40 10 75 060 19.3 123 2.1 6.8 33.0 50 8 90
036 042 6.4 42 0.8 2.0 10.8 15 14 100 048 8.2 50 1.1 2.3 13.7 20 14 100 060 10.0 62 1.1 3.2 16.8 25 12 100
AWG American Wire Gage CSA Canadian Standards Association FLA Full Load Amps HACR — Heating, Air Conditioning and Refrigeration LRA Locked Rotor Amps MCA Minimum Circuit Amps MOCP — Maximum Overcurrent Protection (fuses or HACR-type
NEC National Electrical Code RLA Rated Load Amps
*Fuse or HACR breaker. †Minimum wire size is based on 60 C copper wire. If other than 60 C is
used, determine size from NEC. Voltagedrop of wire must be less than 2% of rated voltage.
NOTES:
1. In compliance with NEC requirements for multimotor and combination load equipment (refer to NEC Articles 430 and 440), the overcurrent protective device for the unit shall be fuse or HACR breaker.The CSA units may be fuse or circuit breaker.
2. Unbalanced 3-Phase Supply Voltage
Never operate a motor where a phase imbalance in supply voltage is greater than 2%.
of voltage imbalance. % Voltage Imbalance
V-PH-HZ
208/230-1-60 187 253
208/230-3-60 187 253
460-3-60 414 506
LEGEND
circuit breaker)
Use the following formula to determine the percent
= 100 x
max voltage deviation from average voltage
VOLTAGE
RANGE
Min Max RLA LRA FLA MCA MOCP*
average voltage
COMPRESSOR
7.6 45 0.7 1.8 12.0 15 14 75
9.4 66 1.4 2.0 15.5 25 12 80
5.6 40 0.8 1.4 9.2 10 14 100
COND.
FAN
MOTOR
INDOOR
FAN
FLA
Example: Supply voltage is 460-3-60.
Determine maximum deviation from average voltage. (AB) 457 – 452=5v
(BC) 464 – 457=7v (AC) 457 – 455=2v
Maximum deviation is 7 v. Determine percent of voltage imbalance.
% Voltage Imbalance = 100 x
This amount of phase imbalance is satisfactory as it is below the maximum allowable 2%.
IMPORTANT: If the supply voltage phase imbalance is more than 2%, contact your local electric utility company immediately.
POWER SUPPLY
AB = 452 v BC = 464 v AC = 455 v
Average Voltage =
= 1.53%
AWG60C MIN WIRE
SIZE
452 + 464 + 455
1371
=
3
= 457
7
457
3
MAX WIRE
LENGTH
(ft)
20
OPERATING SEQUENCE
HEATING
On a call for heating, terminal ‘‘W’’ of the thermostat is ener­gized, starting the induced-draft motor. When the hall-effect sensor on the induced-draft motor senses that it has reached the required speed, the burner sequence begins. This sequence is performed by the integrated gas control board (IGC). The indoor-fan motor is energized 45 seconds after flame is estab­lished. When the thermostat is satisfied and ‘‘W’’ is deener­gized, the indoor-fan motor stops after a 45-second time-off delay.
COOLING
With the room thermostat SYSTEM switch in the COOL position and the FAN switch in theAUTO. position, the cooling sequence of operation is as follows:
When the room temperature rises to a point that is slightly above the cooling control setting of the thermostat, the thermo­stat completes the circuit between thermostat terminal R to ter­minals Y and G. These completed circuits through the thermostat connect contactor coil (C) (through unit wire Y) and blower relay coil (BR) (through unit wire G) across the 24-v sec­ondary of transformer (TRAN).
The normally-open contacts of energized contactor (C) close and complete the circuit through compressor motor (COMP) to condenser (outdoor) fan motor (OFM). Both motors start instantly.
The set of normally-open contacts of energized relay BR close and complete the circuit through evaporator blower (indoor) fan motor (IFM). The blower motor starts instantly.
NOTE: Once the compressor has started and then has stopped, it should not be started again until 5 minutes have elapsed. The cooling cycle remains ‘‘on’’ until the room temperature drops to point that is slightly below the cooling control setting of the room thermostat. At this point, the thermostat ‘‘breaks’’ the circuit between thermostat terminal R to terminals Y and G. These open circuits deenergize contactor coil C and relay coil BR. The condenser and compressor motors stop. After a 30-second delay, the blower motor stops. The unit is in a ‘‘standby’’ condition, waiting for the next ‘‘call for cooling’’ from the room thermostat.
21
TYPICAL FIELD WIRING
NOTES:
1. If any of the original wire furnished must be replaced, it must be re­placed with type 90 C wire or its equivalent.
2. Thermostat: HH07AT174, HH01AD040, HH01AD046, HH01PC184, HH01PC185, HH07AT196 Subbase: HH93AZ040, HH93AZ207, HH93AZ176
3. Use copper conductors only.
Unit 588A Sizes 018-060; 208/230-1-60
LEGEND
AWG American Wire Gage BR Blower Relay C—Contactor CAP Capacitor CH Crankcase Heater COMP Compressor Motor CR Combustion Relay EQUIP Equipment FL Fuse Link FS Flame Sensor FU Fuse GND Ground GVR Gas Valve Relay HS Hall Effect Sensor HV TRAN — High-Voltage Transformer I—Ignitor IDM Induced-Draft Motor IFM Indoor-Fan Motor IGC Integrated Gas Control IP Internal Protector LS Limit Switch MGV Main Gas Valve
22
NEC National Electrical Code OFM — Outdoor-Fan Motor PWR — Power QT Quadruple Terminal RS Rollout Switch TRAN — Transformer
Field Splice
Terminal (Marked) Terminal (Unmarked) Splice
Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential
Only, Not to Represent Wiring
TYPICAL FIELD WIRING (cont)
NOTES:
1. If any of the original wire furnished must be replaced, it must be re­placed with type 90 C wire or its equivalent.
2. Thermostat: HH07AT174, HH01AD040, HH01AD046, HH01PC184, HH01PC185, HH07AT196 Subbase: HH93AZ040, HH93AZ207, HH93AZ176
3. Use copper conductors only.
Unit 588A Sizes 030-060; 208/230-3-60
LEGEND
AWG American Wire Gage BR Blower Relay C—Contactor CAP Capacitor CH Crankcase Heater COMP Compressor Motor CR Combustion Relay EQUIP Equipment FL Fuse Link FS Flame Sensor FU Fuse GND Ground GVR Gas Valve Relay HS Hall Effect Sensor HV TRAN — High-Voltage Transformer I—Ignitor IDM Induced-Draft Motor IFM Indoor-Fan Motor IGC Integrated Gas Control IP Internal Protector LS Limit Switch MGV Main Gas Valve
23
NEC National Electrical Code OFM — Outdoor-Fan Motor PWR — Power QT Quadruple Terminal RS Rollout Switch TRAN — Transformer
Field Splice
Terminal (Marked) Terminal (Unmarked) Splice
Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential
Only, Not to Represent Wiring
TYPICAL FIELD WIRING (cont)
NOTES:
1. If any of the original wire furnished must be replaced, it must be re­placed with type 90 C wire or its equivalent.
2. Thermostat: HH07AT174, HH01AD040, HH01AD046, HH01PC184, HH01PC185, HH07AT196 Subbase: HH93AZ040, HH93AZ207, HH93AZ176
3. Use copper conductors only.
Unit 588A Sizes 036-060; 460-3-60
LEGEND
AWG American Wire Gage BR Blower Relay C—Contactor CAP Capacitor CH Crankcase Heater COMP Compressor Motor CR Combustion Relay EQUIP Equipment FL Fuse Link FS Flame Sensor FU Fuse GND Ground GVR Gas Valve Relay HS Hall Effect Sensor HV TRAN — High-Voltage Transformer I—Ignitor IDM Induced-Draft Motor IFM Indoor-Fan Motor IGC Integrated Gas Control IP Internal Protector LS Limit Switch MGV Main Gas Valve
24
NEC National Electrical Code OFM — Outdoor-Fan Motor PWR — Power QT Quadruple Terminal RS Rollout Switch TRAN — Transformer
Field Splice
Terminal (Marked) Terminal (Unmarked) Splice
Factory Wiring Field Control Wiring Field Power Wiring Accessory or Optional Wiring To Indicate Common Potential
Only, Not to Represent Wiring
TYPICAL INSTALLATION
APPLICATION DATA
1. Condensate trap — A 2-in. condensate trap must be field supplied.
2. Ductwork — Secure downflow discharge ductwork to roof curb. For horizontal discharge applications, attach ductwork to unit with flanges.
Units are equipped with factory-installed duct covers on both the downflow and horizontal openings. Remove appropriate duct panel covers for intended discharge application. Units utilizing downflow option do not require duct panel cover removal.
3. Thermostat — Toachieve simultaneous economizer cooling and mechanical cooling, use of 2-stage cooling thermostat is recommended for all units equipped with accessory economizer.
4. Airflow — Units are draw-thru on cooling and blow-thru on heating.
5. Maximum cooling airflow — To minimize the possibility of condensate blow-off from evaporator, airflow through units should not exceed 450 cfm/ton.
Minimum cooling airflow is 350 cfm/ton. Minimum ambient operating temperature for standard units
is 40 F. With accessory low ambient temperature kit, units can operate at temperatures down to 0° F.
25
ENGINEERS’ SPECIFICATION GUIDE
GENERAL: Furnish and install single-package, outdoor heating and cooling unit utilizing a rotary, reciprocating, or scroll her­metic compressor for cooling and gas combustion for heating duty. Unit shall discharge supply air either in downflow or hori­zontal application as shown on the contract drawings. Unit shall be capable of starting and running at 125 F ambient outdoor temperature per maximum load criteria of ARI Standard 210/ 240-89. Unit shall be provided with fan time-delay to prevent cold air delivery before heat exchanger warms up. Unit shall be provided with 30-second fan time-delay after the thermostat is satisfied.
Nominal unit electrical characteristics shall be v,
ph, 60 Hz. The unit shall be capable of satisfactory opera­tion within voltage limits of to v.All unit power wir­ing shall enter unit cabinet at a single location.
COOLING CAPACITY: Total cooling capacity of the unit shall be
Btuh or greater, and sensible capacity shall be Btuh or greater at conditions of cfm evaporator entering air of F dry bulb, F wet bulb, and condenser en­tering air of F dry bulb. Total design conditions shall be a minimum of Btuh/Watt. The unit shall be capable of cool­ing operation down to 40 F.
HEATINGCAPACITY:Totalheating capacity of the unit shall be
Btuh or greater with a gas input of Btuh. CABINET:The cabinet shall be constructed of heavy duty, phos-
phated, zinc-coated, prepainted steel capable of withstanding 500 hours in salt spray. Cabinet panels shall be easily remov­able for servicing. Unit shall be equipped with factory-supplied condensate drain connection for evaporator coil. Indoor (evapo­rator) blower compartment interior cabinet surfaces shall be in­sulated with a minimum
1
⁄2-in. thick, flexible fiberglass insulation, coated on the air side. Aluminum foil-faced fiberglass insulation shall be used to meet ASHRAE standard no. 62P.
COMPRESSOR: Compressor shall be welded, fully hermetic type with factory-installed vibration isolation. Compressor motor shall be of the refrigerant-cooled type with line break thermal and current overload protection. Rotary compressors shall be standard on unit size 018. Reciprocating compressors shall be standard on unit sizes 024-042. Scroll compressors shall be standard on unit sizes 048 and 060.
CONDENSER SECTION: The condenser coils shall have aluminum-plate fins mechanically bonded to seamless copper tubes with all joints brazed. Condenser fan wheel shall be dy­namically balanced. Fan-motor bearings shall be sealed and permanently lubricated. Condenser-fan motor shall have inher-
ent automatic-reset thermal overload protection and shall be to­tally enclosed.
EVAPORATOR SECTION: Evaporator coils shall have alumi­num plate fins mechanically bonded to seamless copper tubes with all joints brazed. Evaporator fan shall be of the forward­curved, centrifugal, direct-driven type. Fan wheel shall be made from steel, be double-inlet type with forward curved blades with corrosion resistant finish and be dynamically balanced. Fan­motor bearings shall be sealed and permanently lubricated. Evaporator-fan motor shall have inherent automatic-reset ther­mal overload protection and shall be open drip-proof.
HEATING SECTION: The unit shall be equipped with an induced-draft combustion system with energy saving direct spark ignition system and redundant main gas valve. The heat exchanger shall be constructed of aluminized steel for corrosion resistance. Burners shall be of the inshot type constructed of aluminum coated steel. An integrated gas control board shall provide control of heating and simplify troubleshooting through its built-in diagnostics. All gas piping and electric supply shall enter the unit cabinet at a single location.
REFRIGERANT SYSTEM: Refrigerant system shall include a fixed orifice metering device.
CONTROLS: Unit shall be complete with self-contained control system. Unit staging shall be minimum one-cool, one-heat. In the event of a power failure, unit control system shall sequence the unit to restart. Thermostat set points shall have adjustable deadband between heat and cool. Compressors shall be pro­vided with inherent internal line break safety feature, and also overcurrent and overtemperature protection.
AGENCY CERTIFICATIONSAND STANDARDS: The unit shall be UL listed and CSA certified for safety requirements. All wiring shall be in accordance with NEC. The unit shall be rated in ac­cordance with ARI Standards 210/240-89 and 270-84. Insula­tion and adhesive shall meet NFPA 90A requirements for flame spread and smoke generation.
OPTIONS: Factory-installed options shall include: base rail and downflow application.
ACCESSORIES: Field-installed accessories shall include: flat roof curb (8, 11, or 14 in.), pitched roof curb, modulating econo­mizer,2-position damper,thermostat and subbase, low-ambient kit (Weatherprobe™ II device), natural-to-propane conversion kit, manual outdoor-air damper, filter rack, flexible duct kit, high­and low-pressure switches, ComprotecT kit, crankcase heater, lifting brackets, and concentric diffuser box.
26
Bryant
Air Conditioning
SPECIFICATIONS SUBJECT TO CHANGE WITHOUT NOTICE
UNIT MUST BE INSTALLED IN ACCORDANCE
WITH INSTALLATION INSTRUCTIONS
Copyright 1995 Carrier Corporation
Printed in U.S.A. 8/94 CATALOG NO. BY-3258-803
Loading...