Bryant 581C024-060, 581B036-072 User Manual

581B036--072 581C024--060
SINGLE--PACKAGE ROOFTOP HEA TING/COOL ING ST ANDARD AND LOW NOx UNITS
Installation Instructions
TABLE OF CONTENTS
Page
INSTALLATION 1..................................
Step 1--Provide Unit Support 2.......................
ROOF CURB 2................................
SLAB MOUNT 2..............................
ALTERNATE UNIT SUPPORT 2.................
Step 2--Field Fabricate Ductwork 2...................
Step 3--Install External Trap for Condensate Drain 2.......
Step 4--Rig and Place Unit 2.........................
POSITIONING 2..............................
Step5—InstallFlueHood 4........................
Step 6 — Install Gas Piping 4........................
Step 7 — Make Electrical Connections 8................
FIELD POWER SUPPLY 8......................
FIELD CONTROL WIRING 8....................
HEAT ANTICIPATOR SETTINGS 8...............
Step 8 — Adjust Factory-Installed Options 16...........
PERFECT HUMIDITYADAPTIVE
DEHUMIDIFICATION SYSTEM 16..............
MANUAL OUTDOOR-AIR DAMPER 16..........
CONVENIENCE OUTLET 16....................
OPTIONAL ECONOMI$ER IV 18................
ECONOMI$ER IV STANDARD SENSORS 19......
ECONOMI$ER IV CONTROL MODES 20.........
Step 9 — Adjust Evaporator-Fan Speed 25..............
PRE--START--UP 41..................................
START--UP 41.......................................
SERVICE 45........................................
TROUBLESHOOTING 55.............................
START--UP CHECKLIST 60...........................

SAFETY CONSIDERA T IONS

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and qualified service personnel should install, repair, or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of cleaning coils and filters and replacing filters. All other operations should be performed by trained service personnel. When working on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use quenching cloth for unbrazing operations. Have fire extinguishers available for all brazing operations.
Recognize safety information. This is the safety--alert symbol
. When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal injury or death.
Before performing service or maintenance operations on unit, turn off main power switch to unit and install lockout tag. Ensure electrical service to rooftop unit agrees with voltage and amperage listed on the unit rating plate.
!
FIRE, EXPLOSION HAZARD
Failure to follow this warning could cause death and/or property damage.
Disconnect gas piping from unit when leak testing at pressure greater than psig will cause gas valve damage resulting in hazardous condition. If gas valve is subjected to pressure greater
1
than
/2psig, it must be replaced before use. When
pressure testing field-supplied gas piping at pressures of
1
/2psig or less, a unit connected to such piping must be
isolated by manually closing the gas valve(s).
WARNING
WARNING
1
/2psig. Pressures greater than1/
2

INSTALLATION

Unit is shipped in the vertical discharge configuration. To convert to horizontal discharge application, remove duct opening covers. Using the same screws, install covers on duct openings in basepan of unit with insulation-side down. Seals around openings must be tight. (See Fig. 1.)
1
Fig. 1 --- Horizontal Conversion Panels
Step 1 Provide Unit Support
581B,C
Roof Curb
Assemble and install accessory roof curb in accordance with instructions shipped with curb. (See Fig. 2.) Install insulation, cant strips, roofing felt, and counter flashing as shown. Ductwork must be attached to curb, not to the unit. If electric control power or gas service is to be routed through the basepan, attach the accessory thru-the-bottom service connections to the basepan in accordance with the accessory installation instructions. Connections must be installed before unit is set on roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is critical for a watertight seal. Install gasket supplied with the roof curb as shown in Fig. 2. Improperly applied gasket can result in air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig.
3. This is necessary for unit drain to function properly. Refer to Accessory Roof Curb Installation Instructions for additional information as required.
Slab Mount (Horizontal Units
Provide a level concrete slab that extends a minimum of 6 in. beyond unit cabinet. Install a gravel apron in front of condenser-coil air inlet to prevent grass and foliage from obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if required.
Alternate Unit
When the curb or adapter cannot be used, support unit with sleeper rails using unit curb or adapter support area. If sleeper rails cannot be used, support the long sides of the unit with a minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Support
Only)
Step 2 Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical discharge units. Do not connect ductwork to unit. For horizontal applications, field-supplied isolation flanges should be attached to horizontal discharge openings and all ductwork should be secured to the flanges. Insulate and weatherproof all external ductwork, joints, and roof openings with counter flashing and mastic in accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be ducted through the roof deck to comply with applicable fire codes.
C06108
A minimum clearance is not required around ductwork. Cabinet return-air static pressure (a negative condition) shall not exceed
0.35 in. wg with economizer or 0.45 in. wg without economizer. These units are designed for a minimum continuous return-air
temperature in heating of 50_F (dry bulb), or an intermittent operation down to 45_F (dry bulb), such as when used with a night setback thermostat.
To operate at lower return-air temperatures, a field-supplied outdoor air temperature control must be used to initiate both stages of heat when the temperature is below 45_F. Indoor comfort may be compromised when these lower air temperatures are used with insufficient heating temperature rise.
Step 3 Install External Trap for Condensate Drain
The unit’s3/4-in. condensate drain connections are located on the bottom and side of the unit. Unit discharge connections do not determine the use of drain connections; either drain connection can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the plug (Red) in the alternate bottom connection is tight before installing the unit.
To use the bottom drain connection for a roof curb installation, relocate the factory-installed plug (Red) from the bottom connection to the side connection. The center drain plug looks like a star connection, however it can be removed with a socket drive extension. (See Fig. 4.) The piping for the condensate drain and external trap can be completed after the unit is in place.
All units must have an external trap for condensate drainage. Install a trap 4-in. deep and protect against freeze-up. If drain line is installed downstream from the external trap, pitch the line away from the unit at 1 in. per 10 ft of run. Do not use a pipe size smaller than the unit connection (
3
/4in.). (See Fig. 5.)
1
/2-in.
Step 4 Rig and Place Unit
Inspect unit for transportation damage, and file any claim with transportation agency. Keep unit upright and do not drop. Spreader bars are not required if top crating is left on unit, and rollers may be used to move unit across a roof. Level by using unit frame as a reference. See Table 1 and 2 and Fig. 6 for additional information. Operating weight is shown in Table 1 and 2 and Fig. 6.
Lifting holes are provided in base rails as shown in Fig. 8 and 9. Refer to rigging instructions on unit.
!
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death and property damage.
All panels must be in place when rigging and lifting.
Positioning
Maintain clearance around and above unit to provide minimum distance from combustible materials, proper airflow, and service access. (See Fig. 7, 8 and 9.)
Position unit on roof curb so that the following clearances are maintained: rail inside the front and rear, 0.0 in. clearance between the roof curb and the base rail inside on the duct end of the unit. This will result in the distance between the roof curb and the base rail inside on the condenser end of the unit being approximately equal to Fig. 2, section C-C.
Do not install unit in an indoor location. Do not locate unit air inlets near exhaust vents or other sources of contaminated air.
1
WARNING
/4in. clearance between the roof curb and the base
2
1-4 [406]
DALT
DRAIN
HOLE
13/4
[44.5]
GAS POWER CONTROL
3
/4
[19] NPT
1
/2
[12.7] NPT
3
/4
[19] NPT
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A01 CRBTMPWR002A01 1
CRBTMPWR003A01
1-9
11
[551]
/16
CRBTMPWR004A01
3
/4 [19] NPT
1
/4 [31.7]
3
/4 [19] NPT
1
/4 [31.7]
1
1
/2
[12.7]
ACCESSORY
POWER
1
/2
[12.7]
ROOF CURB
ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest on curb).
6. Service clearance: 4 ft on each side.
1-2 [356]
2-0 [610]
A
581B036-072 581C024-060
UNIT SIZE
7. Direction of airflow.
8. Connector packages CRBTMPWR001A01 and 002A01 are for thru-the-curb type gas. Packages CRBTMPWR003A01 and 004A01 are for thru-the-bottom type gas connections.
581B,C
Fig. 2 --- Roof Curb Details
3
C06345
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-B B-C A-C
0.5 1.0 1.0
Fig. 3 --- Unit Leveling Tolerances
Be sure that unit is installed such that snow will not block the combustion intake or flue outlet.
581B,C
Unit may be installed directly on wood flooring or on Class A, B, or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from higher level runoff and overhangs.
Locate mechanical draft system flue assembly at least 48 in. from an adjacent building or combustible material. When unit is located adjacent to public walkways, flue assembly must be at least 7 ft above grade.
NOTE: When unit is equipped with an accessory flue discharge deflector, allowable clearance is 18 inches.
Flue gas can deteriorate building materials. Orient unit such that flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper operation of this equipment. Be sure that installation complies with all local codes and Section 5.3, Air for Combustion and Ventilation, NFGC (National Fuel Gas Code), ANSI (American National Standards Institute) Z223.1-1984 and addendum Z223.1a-1987. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
Flue vent discharge must have a minimum horizontal clearance of 4 ft from electric and gas meters, gas regulators, and gas relief equipment.
After unit is in position, remove shipping materials and rigging skids.
Step 5 Install Flue Hood
Flue hood is shipped screwed to the burner compartment access panel. Remove from shipping location and, using screws provided, install flue hood in location shown in Fig. 8 and 9.
For units being installed in California Air Quality Management Districts which require NOx emissions of 40 nanograms/joule or less, a low NOx unit must be installed.
NOTE: Low NOx units are available for 2 to 5 ton units.
C06110
CONDENSATE PAN (SIDE VIEW)
HORIZONTAL DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUG
C06003
Fig. 4 --- Condensate Drain Pan
NOTE: Trap should be deep enough to offset maximum unit static difference. A 4-in. trap is recommended.
C06004
Fig. 5 --- Condensate Drain Piping Details
Step 6 Install Gas Piping
Unit is equipped for use with type of gas shown on nameplate. Refer to local building codes, or in the absence of local codes, to ANSI Z223.1-1984 and addendum Z223.1A-1987 entitled National Fuel Gas Code. In Canada, installation must be in accordance with the CAN1.B149.1 and CAN1.B149.2 installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas connection must not be less than 4 in. wg or greater than 13 in. wg while the unit is operating. On 581B036 --072 and 581C036--060 high-heat units, the gas pressure at unit gas connection must not be less than 5 in. wg or greater than 13 in. wg while the unit is operating. For propane applications, the gas pressure must not be less than 5 in. wg or greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure drop. Do not use supply pipe smaller than unit gas connection.
4
NOTES:
OPERATING
OPERATING
B
1. Place unit on curb as close as possible to the duct end.
2. Dimensionin( )isinmillimeters.
3. Hook rigging shackles through holes in base rail as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top skid when rigging to prevent rigging straps from damaging unit.
4. Weights include base unit without economizer. See Table 1 for unit operating weights with accessory economizer.
5. Weights include base unit without the Perfect Humidityt adaptive dehumidification system. See Table 1 for unit operating weights with th e Perfect Humidityt system.
C06111
Fig. 6 --- Rigging Details
UNIT
581C
024 036 540 245 73.69 1872 35.50 902 33.31 847 048 560 254 73.69 1872 35.50 902 33.31 847 060 635 288 73.69 1872 35.50 902 41.31 1050
UNIT 581
036 530 240 73.69 1872 35.50 902 33.31 847 048 540 245 73.69 1872 35.50 902 33.31 847 060 560 254 73.69 1872 35.50 902 33.31 847 072 635 288 73.69 1872 35.50 902 41.31 1050
OPERATING
WEIGHT
lb kg in. mm in. mm in. mm
530 240
OPERATING
WEIGHT
lb kg in. mm in. mm in. mm
“A” “B” “C”
73.69 1872 35.50 902 33.31 847
“A” “B” “C”
DIMENSIONS
DIMENSIONS
581B,C
C06208
Fig. 7 --- Roof Curb Alignment
Support gas piping as shown in the table in Fig. 11. For example,
3
/4-in. gas pipe must have one field-fabricated support beam
a every 8 ft. Therefore, an 18-ft long gas pipe would have a minimum of 3 support beams, and a 48-ft long pipe would have a minimum of 6 support beams.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal injury, death and property damage.
All panels must be in place when rigging and lifting.
See Fig. 11 for typical pipe guide and locations of external manual gas shutoff valve.
NOTE: If accessory thru-the-bottom connections and roof curb are used, refer to the Thru-the-Bottom Accessory Installation Instructions for information on power wiring and gas connection piping. The power wiring, control wiring and gas piping can be routed through field-drilled holes in the basepan. The basepan is specially designed and dimpled for drilling the access connection holes.
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and/or property damage.
When connecting the gas line to the unit gas valve, the installer MUST use a backup wrench to prevent damage to the valve.
5
581B,C
C06363
COMPRESSOR
ACCESS PANEL
CONTROL BOX
Fig. 8 --- 581B 036 --072 Base Unit Dimensions
6
C06364
581B,C
COMPRESSOR
ACCESS PANEL
Fig. 9 --- 581C 024 --060 Base Unit Dimensions
7
Fig. 10 --- Flue Hood Details
*
581B,C
LEGEND
NFGC — National Fuel Gas Code
Field supplied.
NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER (in.)
1
/
3
/4or 1
1
/4or larger
1
2
Fig. 11 --- Gas Piping Guide (With Accessory
Thru--the--Curb Service Connections)
Step 7 Make Electrical Connections
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Unit cabinet must have an uninterrupted, unbroken electrical ground to minimize the possibility of personal injury if an electrical fault should occur. This ground may consist of electrical wire connected to unit ground lug in control compartment, or conduit approved for electrical ground when installed in accordance with NEC (National Electrical Code), ANSI/NFPA (National Fire Protection Association), latest edition, and local electrical codes. Do not use gas piping as an electrical
ground.
WARNING
SPACING OF SUPPORTS
X DIMENSION (ft)
6 8
10
C06114
C06115
Field Power Supply
All units except 208/230-v units are factory wired for the voltage shown on the nameplate. If the 208/230-v unit is to be connected to a 208-v power supply, the transformer must be rewired by moving the black wire from the 230-v terminal on the transformer and connecting it to the 200-v terminal from the transformer.
Refer to unit label diagram for additional information. Pigtails are provided for field service. Use factory-supplied splices or UL (Underwriters’ Laboratories) approved copper connector.
When installing units, provide a disconnect per NEC. All field wiring must comply with NEC and local
requirements. Install conduit through side panel openings indicated in Fig. 8.
Route power lines through connector to terminal connections as shown in Fig. 12.
Voltage to compressor terminals during operation must be within voltage range indicated on unit nameplate (also see Tables 3 and
4). On 3-phase units, voltages between phases must be balanced within 2% and the current within 10%. Use the formula shown in Tables 3 and 4, Note 3 to determine the percent voltage imbalance. Operation on improper line voltage or excessive phase imbalance constitutes abuse and may cause damage to electrical components. Such operation would invalidate any applicable Bryant warranty.
NOTE: If accessory thru-the-bottom connections and roof curb are used, refer to the Thru-the-Bottom Accessory Installation Instructions for information on power wiring and gas connection piping. The power wiring, control wiring and gas piping can be routed through field-drilled holes in the basepan. The basepan is specially designed and dimpled for drilling the access connection holes.(SeeFig.2.)
Field Control W
iring
Install a Bryant-approved accessory thermostat assembly according to installation instructions included with the accessory. Locate thermostat assembly on a solid wall in the conditioned space to sense average temperature in accordance with thermostat installation instructions.
Route thermostat cable or equivalent single leads of colored wire from subbase terminals through connector on unit to low-voltage connections (shown in Fig. 13 and 14).
Connect thermostat wires to matching screw terminals of low-voltage connection board. (See Fig. 13 and 14.)
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American Wire Gauge) insulated wire (35_Cminimum).For50to75ft,use no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use no. 14 AWG insulated wire (35_C minimum). All wire larger than no. 18 AWG cannot be directly connected to the thermostat and will require a junction box and splice at the thermostat.
Pass the control wires through the hole provided in the corner post; then feed wires through the raceway built into the corner post to the 24-v barrier located on the left side of the control box. (See Fig. 15). The raceway provides the UL required clearance between high and low-voltage wiring.
Heat Anticipator
Settings
Set heat anticipator settings at 0.14 amp for first stage and 0.14 for second stage heating, when available.
8
Table 1—Physical Data 581B
A
/B(
)
MotorPulleyPitchDiameterA/B(i
n.)
f
SpeedChangeperFullTurno
f
MovablePulleyMaximumFul
l
BASE UNIT 581B 036 048 060 072 NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb)
Unit Perfect HumidityAdaptive Dehumidification System EconoMi$er IV Roof Curb
COMPRESSOR
Quantity Oil (oz)
REFRIGERANT TYPE
Expansion Device Operating Charge (lb-oz)
Standard Unit Unit With Perfect Humidity Adaptive Dehumidification System
CONDENSER FAN
Quantity...Diameter (in.) Nominal Cfm Motor Hp...Rpm Watts Input (Total)
CONDENSER COIL
Rows...Fins/in. Tot a l F ace A r ea (sq f t )
EVAPORATOR COIL
Standard Unit
Rows...Fins/in. Tot a l F ace A r ea (sq f t )
Unit with Perfect Humidity Adaptive Dehumidification System
Rows...Fins/in. Tot a l F ace A r ea (sq f t )
EVAPORATOR FAN
Quantity...Size (in.) Nominal Cfm Maximum Continuous Bhp Std
Hi-Static
Motor RPM Std
Hi-Static
Motor Frame Size Std
Hi-Static
Fan Rpm Range Std
Hi-Static
Motor Bearing Type Maximum Fan Rpm Motor PulleyPitch Diameter
in.
Hi-Static
Nominal Motor Shaft Diameter (in.) Std
Hi-Static
Fan Pulley Pitch Diameter (in.) Std
Hi-Static
Belt — Type...Length (in.) Std
Hi-Static
Pulley Center Line Distance (in.) Speed Changeper Full Turn o
Movable Pulley Flange (rpm)
Movable PulleyMaximum Full
Turns from Closed Position
Hi-Static
Hi-Static
Factory Setting — Full Turns Open Std
Hi-Static
Factory Speed Setting (rpm) Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
LEGEND
Bhp — Brake Horsepower
Std
Std
Std
3 4 5 6
530 540 560 635
15 23 25 29 50 50 50 50
115 115 115 115
Scroll
1 1 1 1
42 53 50 60
R-22
AcutrolMetering Device
5-8 10-2 10-0 12- 8
12-5 18-8 20-5 23-14
Propeller
1...22 1...22 1...22 1...22 3500 3500 4100 4100
1
/4...825
1
/4...825
1
/4...1100
1
/4...1100
180 180 320 320
3/8---in. OD Enhanced Copper Tubes, Aluminum Lanced Fins
1...17 2...17 2...17 2...17
14.6 16.5 16.5 21.3 3/8---in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins
2...15 2...15 4...15 4...15
5.5 5.5 5.5 7.3
1...17 2...17 2...17 2...17
3.9 3.9 3.9 5.2 Centrifugal Type, Belt Drive
1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 1200 1600 2000 2400
1.20
2.40 1620 1725
48 56
680-1044
1075-1455
1.20 1.30/2.40* 2.40
2.40 2.90 2.90 1620 1725 1725 1725 1725 1725
48 48/56* 56 56 56 56
770-1185 1035-1460 1119-1585
1075-1455 1300-1685 1300-1685
Ball Ball Ball Ball
2100 2100 2100 2100
1.9/2.9
2.8/3.8
1/
2
5
/
8
4.5
4.5
1...A...36
1...A...39
1.9/2.0 2.4/3.4 2.4/3.4
2.8/3.8 3.4/4.4 3.4/3.4
1
/
2
5
/
8
4.0 4.0 4.0
5
/
8
5
/
8
5 7
4.0 4.5 4.5
1...A...36 1....4...40 1...A...38
1...A...39 1...A...40 1...A...40
10.0-12.4 10.0-12.4 14.7-15.5 14.7-15.5 65 65
5 6 3
1
3
826
1233
5
/
/
2
8
70 75 95 65 60 60
5 6 5 6 5 5 3 3 3
31/
2
936 1248 1305
1233 1396 1396
5
/
8
31/
2
5
/
8
31/
5
581B,C
/
8
/
8
2
/
8
9
Table 1 — Physical Data 581B (cont)
UNIT SIZE 581B 036 048 060 072 FURNACE SECTION
Rollout Switch Cutout Temp (F)† 195 195 195 195
Burner Orifice Diameter (in. ...drill size)**
Natural Gas —Std 071/072 .113...33 .113...33 .113...33 .113...33
Propane —Alt†† 071/072 .089...43 .089...43 .089...43 .089...43
Thermostat Heat Anticipator Setting (amps) 208/230/460 v First Stage .14 .14 .14 .14 Second Stage .14 .14 .14 .14 Gas Input (Btuh) First Stage/Second Stage (3---phase units) 072 50,000/ 72,000 50,000/ 72,000 50,000/ 72,000 50,000/ 72,000
581B,C
Efficiency (Steady State) (%) 072 82 82 82 82
TemperatureRiseRange 072 15---45 15---45 15---45 15 --- 45
Manifold Pressure (in. wg) Natural Gas —Std 3.5 3.5 3.5 3.5 Propane —Alt†† 3.5 3.5 3.5 3.5 Maximum Static Pressure (in. wg) 1.0 1.0 1.0 1.0 Field Gas Connection Size (in.) 1/2 1/2 1/2 1/2
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief Cutout Reset (Auto.)
LOSS-OF-CHARGE SWITCH/LOW-PRESSURE (Liquid Line) (psig)
Cutout Reset (Auto.)
FREEZE PROTECTION THERMOSTAT
Opens (F) Closes (F)
OUTDOOR-AIR INLET SCREENS RETURN-AIR FILTERS
Quantity...Size (in.)
114/115 .113...33 .113...33 .113...33 .113...33 149/150 .129...30 .129...30 .129...30
060N .102...38 .102...38 .102...38 — 090N .102...38 .102...38 .102...38 — 120N .116...32 .116...32
114115 .089...43 .089...43 .089...43 .089...43
149/150 .102...38 .102...38 .104...39
060N .082...45 .082...45 .082...45 — 090N .082...45 .082...45 .082...45 — 120N .094...42 .094...42
115 82,000/115,000 82,000/115,000 82,000/115,000 82,000/115,000
150 120,000/150,000 120,000/150,000 120,000/150,000 071II —/72,000 —/72,000 —/72,000 — 114II —/115,000 —/115,000 —/115,000 — 149II —/150,000 —/150,000
060N*** —/ 60,000 —/60,000 —/60,000 — 090N*** —/ 90,000 —/90,000 —/90,000 — 120N*** —/120,000 —/120,000
115 80 81 81 81
150 80 80 80
071 82 82 82
114 80 81 81
149 80 80
060N 80 80 80 — 090N 80 80 80 — 120N 80 80
115 55 ---85 35---65 35 ---65 35 --- 65
150 50 ---80 50---80 50 --- 80
071 15 ---45 15---45 15 ---45
114 55 ---85 35---65 35 ---65
149 50 ---80 50---80
060N 20 ---50 20---50 20 ---50 — 090N 30 ---60 30---60 30 ---60 — 120N 40 ---70 40---70
450 50
428 320
7 3
22  5
30  5 45  5
Cleanable. Screen quantity and size varies with option selected.
2...16 x 25 x 2 4...16 x 16 x 2
Throwaway
LEGEND
Bhp — Brake Horsepower
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh
heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh Heat input units have 3 burners.
††A propane kit is available as an accessory. Kit may be used at elevations as high as
2000 ft. If a propane kit is used with Low NOx units, the Low NOx baffle must be removed a nd the units will no longer be classified as Lo w NOx units. ll Three-phase standard models have heating inputs as shown. Single-phase stan­dard models have one-stage heating wi th heating input val ues.
***California compliant three-phase models.
†††California SCAQMD compliant low NO
controlled to 40 nanograms per joule or less.
models have combustion products that are
x
10
Table 2—Physical Data 581C
A
/B(
)
MotorPulleyPitchDiameterA/B(i
n.)
f
SpeedChangeperFullTurno
f
MovablePulleyMaximumFul
l
BASE UNIT 581C 024 036 048 072 NOMINAL CAPACITY (tons) OPERATING WEIGHT (lb)
Unit Perfect HumidityAdaptive Dehumidification System EconoMi$er IV Roof Curb
COMPRESSOR
Quantity Oil (oz)
REFRIGERANT TYPE
Expansion Device Operating Charge (lb-oz)
Standard Unit Unit With Perfect Humidity Adaptive Dehumidification System
CONDENSER FAN
Quantity...Diameter (in.) Nominal Cfm Motor Hp...Rpm Watts Input (Total)
CONDENSER COIL
Rows...Fins/in. Tot a l F ace A r ea (sq f t )
EVAPORATOR COIL
Standard Unit
Rows...Fins/in. Tot a l F ace A r ea (sq f t )
Unit with Perfect Humidity Adaptive Dehumidification System
Rows...Fins/in. Tot a l F ace A r ea (sq f t )
EVAPORATOR FAN
Quantity...Size (in.) Nominal Cfm Maximum Continuous Bhp Std
Hi-Static
Motor Frame Size Std
Hi-Static
Motor Rpm Fan Rpm Range Std
Hi-Static
Motor Bearing Type Maximum Fan Rpm Motor PulleyPitch Diameter
in.
Hi-Static
Nominal Motor Shaft Diameter (in.) Std
Hi-Static
Fan Pulley Pitch Diameter (in.) Std
Hi-Static
Belt — Type...Length (in.) Std
Hi-Static
Pulley Center Line Distance (in.) Speed Changeper Full Turn o
Movable Pulley Flange (rpm)
Movable PulleyMaximum Full
Turns from Closed Position
Hi-Static
Hi-Static
Factory Setting — Full Turns Open Std
Hi-Static
Factory Speed Setting (rpm) Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
Std
Std
Std
2 3 4 5
530 540 560 635
13 15 23 25 50 50 50 50
115 115 115 115
Scroll
1 1 1 1
25 42 56 53
R-22
AcutrolMetering Device
5 --- 3 7 --- 1 1 8 --- 8 12---11
1 0 --- 2 14 --- 0 14--- 13 21 --- 0
Propeller
1...22 1...22 1...22 1...22 3000 3500 3500 4100
1
/8...825
1
/8...825
1
/8...825
1
/4...1100
180 180 180 320
3/8---in. OD Enhanced Copper Tubes, Aluminum Lanced Fins
1...17 1...17 2...17 2...17
14.6 14.6 16.5 16.5 3/8---in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins
2...15 2...15 2...15 4...15
4.2 5.5 5.5 5.5
1...17 1...17 2...17 2...17
3.5 3.9 3.9 3.9 Centrifugal Type, Belt Drive
1...10 x 10 1...10 x 10 1...10 x 10 1...10 x 10 800 1200 1600 2000
0.58
1.20 1.20 1.30/2.40*
2.40 2.40 2.90
48
48 48 48/56* 56 56 56
1620 1620 1620 1725
400-1000
680-1044 770-1185 1035-1460
1075-1455 1075-1455 1300-1685
Ball Ball Ball Ball
1620 2100 2100 2100
2.4/3.2
5
/
8
7
/
8
4.0
4.5
1...A...36
1.9/2.9 1.9/2.0 2.4/3.4
2.8/3.8 2.8/3.8 3.4/4.4
1/
2
5
/
8
4.5 4.0 4.0
1
/
2
5
/
8
5 5
4.5 4.0 4.5
1...A...36 1...A...36 1....4...40
1...A...39 1...A...39 1...A...40
10.0---12.4 10.0-12.4 10.0-12.4 14.7-15.5
60
65 70 75 65 65 60
5
5 5 6 6 6 5 3 3 3
31/
2
826 936 1248
1233 1233 1396
5
/
8
31/
2
5
/
8
31/
5
756
5
3
/
8
581B,C
/
8
/
8
2
/
8
11
Table 2 — Physical Data 581C (cont)
UNIT SIZE 581C 024 036 048 060 FURNACE SECTION
Rollout Switch Cutout Temp (F)† 195 195 195 195
Burner Orifice Diameter (in. ...drill size)**
Natural Gas —Std 071/072 .113...33 .113...33 .113...33 .113...33
Propane —Alt†† 071/072 .089...43 .089...43 .089...43 .089...43
Thermostat Heat Anticipator Setting (amps) 208/230/460 v First Stage .14 .14 .14 .14 Second Stage .14 .14 .14 .14 Gas Input (Btuh) First Stage/Second Stage (3---phase units) 072 50,000/ 72,000 50,000/ 72,000 50,000/ 72,000 50,000/ 72,000
581B,C
Efficiency (Steady State) (%) 072 82 82 82 82
TemperatureRiseRange 072 15---45 15---45 15---45 15 --- 45
Manifold Pressure (in. wg) Natural Gas —Std 3.5 3.5 3.5 3.5 Propane —Alt†† 3.5 3.5 3.5 3.5 Maximum Static Pressure (in. wg) 1.0 1.0 1.0 1.0 Field Gas Connection Size (in.) 1/2 1/2 1/2 1/2
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief Cutout Reset (Auto.)
LOSS-OF-CHARGE SWITCH/LOW-PRESSURE (Liquid Line) (psig)
Cutout Reset (Auto.)
FREEZE PROTECTION THERMOSTAT
Opens (F) Closes (F)
OUTDOOR-AIR INLET SCREENS RETURN-AIR FILTERS
Quantity...Size (in.)
114/115 .113...33 .113...33 .113...33 .113...33 149/150 .129...30 .129...30 .129...30
060N .102...38 .102...38 .102...38 — 090N .102...38 .102...38 .102...38 — 120N .116...32 .116...32
114115 .089...43 .089...43 .089...43 .089...43
149/150 .102...38 .102...38 .104...39
060N .082...45 .082...45 .082...45 — 090N .082...45 .082...45 .082...45 — 120N .094...42 .094...42
115 82,000/115,000 82,000/115,000 82,000/115,000 82,000/115,000
150 120,000/150,000 120,000/150,000 120,000/150,000 071II —/72,000 —/72,000 —/72,000 — 114II —/115,000 —/115,000 —/115,000 — 149II —/150,000 —/150,000
060N*** —/ 60,000 —/60,000 —/60,000 — 090N*** —/ 90,000 —/90,000 —/90,000 — 120N*** —/120,000 —/120,000
115 80 81 81 81
150 80 80 80
071 82 82 82
114 80 81 81
149 80 80
060N 80 80 80 — 090N 80 80 80 — 120N 80 80
115 55 ---85 35---65 35 ---65 35 --- 65
150 50 ---80 50---80 50 --- 80
071 15 ---45 15---45 15 ---45
114 55 ---85 35---65 35 ---65
149 50 ---80 50---80
060N 20 ---50 20---50 20 ---50 — 090N 30 ---60 30---60 30 ---60 — 120N 40 ---70 40---70
450 50
428 320
7 3
22  5
30  5 45  5
Cleanable. Screen quantity and size varies with option selected.
2...16 x 25 x 2 4...16 x 16 x 2
Throwaway
LEGEND
Bhp — Brake Horsepower
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh
heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh Heat input units have 3 burners.
††A propane kit is available as an accessory. Kit may be used at elevations as high as
2000 ft. If a propane kit is used with Low NOx units, the Low NOx baffle must be
removed a nd the units will no longer be classified as Lo w NOx units. ll Three-phase standard models have heating inputs as shown. Single-phase stan­dard models have one-stage heating wi th heating input values.
***California compliant three-phase models.
†††California SCAQMD compliant low NO
controlled to 40 nanograms per joule or less.
models have combustion products that are
x
12
BLK
BLK
TO COMP
BLK
TO COMP
11 23
C
2321
208/230-1-60
(SIZES 581B036-060,
581C024-060)
11 23
C
2321
208/230-3-60
460-3-60
(SIZES 581B060, 072,
581C0060)
YEL
FIELD POWER SUPPLY
DISCONNECT
PER NEC
BLK
YEL
BLU
FIELD POWER SUPPLY
DISCONNECT
PER NEC
EQUIP
GND
TO COMP
14
IFC
63
11 23
YEL BLU
C
2321
208/230-3-60
480-3-60
(SIZES 581B036,048
581C036,048)
FIELD POWER SUPPLY
DISCONNECT
PER NEC
BLK
11 13
YEL BLU
C
2321
FIELD POWER SUPPLY
575-3-60
(SIZES 581B060, 072)
DISCONNECT
PER NEC
Fig. 12 --- Power Wiring Connections
(SIZES 581B036,048
581C036,048)
TO TB2
11 23
C
575-3-60
YEL
2321
FIELD POWER SUPPLY
DISCONNECT
PER NEC
BLU
581B,C
C06346
Y1
Y2
W1
W2
IPD/X
R
G
C
WIRE CONNECTIONS TO LOW-VOLTAGE SECTION
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS
ON OFF
A
LEGEND
NOTE: Un derlined letter indicates ac tive therm ostat output wh en configured for A/C operation.
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
B
C
Field Wiring
D
Fig. 13 --- Low --Voltage Connections With or
Without Economizer or Two--Position Damper
C06008
LOW VOLTAGE CONNECTIONS
INTEGRATED GAS UNIT CONTROLLER (IGC)
Fig. 14 --- Field Control Wiring
C06125
13
IFM
208
/23
0
1
6
0
S
TD1
8
72541109631070620
024
208
/23
0
1
6
0
S
TD1
8
2
110.96310.70.6
2.0
208
/23
0
-
--1--
-60
S
TD1
8
725411688107064
9
/
S
T
D
4
9
208
/23
0
-
--3--
-60
1
8
725411037710706
/
H
S
5
8
S
T
D
2
2
4
6
0
---3-
--6
0
4
1
4508151391040
3
036
H
S
2
6
(3ton
s
)
S
T
D
1
9
104
5
7
5
---3-
--60HS5
1
863214231
03†20
104†26†
P
erfec
t
208
/23
0
-
--1--
-60
S
TD1
9
72541211151150649
/
S
T
D
4
9
208
/23
0
-
--3--
-60
1
8
725411419511506
/
H
S
5
8
S
T
D
2
2
4
6
0
---3-
--6
0
4
1
4508171451080
3
048
H
S
2
6
(4ton
s
)
S
T
D
1
9
106
5
7
5
---3-
--60HS5
1
863216138
03†20
108†26†
P
erfec
t
208
/23
0
-
--1--
-60
S
TD1
8
72541251501150666
/
S
T
D
5
8
208
/23
0
-
--3--
-60
1
8
725411731231150
6
/
H
S
7
5
S
T
D
2
6
4
6
0
---3-
--6
0
4
1
45081847010803†
060
H
S
3
4
(5ton
s
)
S
T
D
2
0
106
5
7
5
---3-
--60HS5
1
863217153
03†28
119†34†
P
erfec
t
581B,C
MINIMUM UNIT
DISCONNECT SIZE
POWER SUPPLY *
CONV
OUTLET
IFM
FAN MOTOR
COMBUSTION
FLA
FLA LRA
MOCP**
MCA
NO 16.3 20 15.6 69
NO 25.6 30 24.8 101
NO 18.5 25 18.3 90
NO 19.4 25 19.3 120
NO 9.0 15 8.9 46
NO 9.4 15 9.3 60
NO 7.6 10 7.5 36
NO 7.7 10 7.6 43
NO 7.7 10 8.0 48
NO 32.7 40 31.5 130
NO 24.0 30 23.6 110
NO 24.9 30 24.6 140
NO 11.9 15 11.6 53
NO 12.3 15 12.1 67
NO 10.1 15 9.9 44
NO 10.2 15 10.0 51
NO 10.3 15 10.1 56
NO 39.4 50 38.1 187
NO 28.9 35 28.3 168
NO 30.6 35 30.2 187
NO 13.9 20 13.6 92
NO 14.7 20 14.5 102
NO 11.5 15 11.2 66
NO 12.3 15 12.1 75
YES 22.3 25 21.2 73
YES 31.6 35 30.4 106
YES 24.5 30 23.8 95
YES 25.4 30 24.9 124
YES 11.7 15 11.4 48
YES 12.1 15 11.8 63
YES 9.7 15 9.5 38
YES 9.8 15 9.6 44
YES 9.8 15 9.6 50
YES 38.7 45 37.0 135
YES 30.0 35 29.1 115
YES 30.9 35 30.1 145
YES 14.6 20 14.1 55
YES 15.0 20 14.6 70
YES 12.3 15 11.9 46
YES 12.4 15 12.0 52
YES 12.5 15 12.1 58
YES 45.4 60 43.6 191
YES 34.9 40 33.8 173
YES 36.6 40 35.8 192
YES 16.6 20 16.1 95
YES 17.4 20 17.0 104
4.9
2.2
1.9
1 0.4
4.9
2.2
1.9
1 0.4† 2.6†
1 0.6
5.8
2.6
1 0.8† 2.6†
NO 12.2 15 12.0 79
YES 13.6 15 13.2 67
YES 14.4 20 14.1 76
YES 14.4 20 14.0 80
2.0
1 0.6
1 1.9† 3.4†
Table 3—Electrical Data 581C
VOLTAGE
COMPRESSOR OFM
RANGE
581C024--- 060
NOMINAL
IFM TYPE Min Max QTY RLA LRA QTY FLA FLA
V --- P H --- H z
UNIT SIZE
024
54
7
---
---
---
---
(2 tons)
2 3 0 --- 1 --- 6 0 STD 187 254 1 16 88 1 0.7 0.6 4.9
208
STD
187 254 1 10.3 77 1 0.7 0.6
2 3 0 --- 3 --- 6 0
208
414 508 1 5.1 39 1 0.4 0.3
HS 5.8
HS 2.6
STD
STD
Perfect
Humidity
036
4 6 0 --- 3 --- 6 0
(3 tons)
5 7 5 --- 3 --- 6 0 HS 518 632 1 4.2 31 0.3† 2.0
2 3 0 --- 1 --- 6 0 STD 197 254 1 21 115 1 1.5 0.6 4.9
208
STD
187 254 1 14.1 95 1 1.5 0.6
2 3 0 --- 3 --- 6 0
208
414 508 1 7.1 45 1 0.8 0.3
HS 5.8
HS 2.6
STD
STD
Perfect
Humidity
048
4 6 0 --- 3 --- 6 0
(4 tons)
5 7 5 --- 3 --- 6 0 HS 518 632 1 6.1 38 0.3† 2.0
2 3 0 --- 1 --- 6 0 STD 187 254 1 25 150 1 1.5 0.6 6.6
208
STD
187 254 1 17.3 123 1 1.5 0.6
2 3 0 --- 3 --- 6 0
208
414 508 1 8.4 70 1 0.8 0.3†
HS 7.5
HS 3.4
STD
STD
Perfect
Humidity
060
4 6 0 --- 3 --- 6 0
(5 tons)
5 7 5 --- 3 --- 6 0 HS 518 632 1 7.1 53 0.3† 2.8
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
FLA --- Full Load Amps
{ 460v motor
NOTES:
14
MINIMUM UNI
208/2
3
0
---1---
6
0
S
T
D
1
8
725
4
1
16881070649
/
S
T
D49
208
/23
0
-
-
-36
0
1
8
725
4
1
103771070
6
/
H
S
5
2
S
T
D22
036(3
Ton
s)4
6
0
-
--3---6
0
4
1
450
8
1
513910403
H
S
2
6
S
T
D19
10403
5
7
5
-
--3---6
0
H
S51
863
2
1
423
1
2
0
104†09†26
P
erfec
t
208/2
3
0
---1---
6
0
S
T
D
1
8
725
4
1
2371261070649
/
S
T
D49
208/2
3
0
---3---
6
0
1
8
725
4
1
135931070
6
/
H
S
5
8
S
T
D22
048(4
Ton
s)4
6
0
-
--3---6
0
4
1
450
8
1
644651040
3
H
S
2
6
S
T
D19
10403
5
7
5
-
--3---6
0
H
S51
863
2
1
644
0
2
0
10409
†26
P
erfec
t
208/2
3
0
---1---
6
0
S
T
D
1
8
725
4
1
2881691150666
/
S
T
D58
208/2
3
0
---3---
6
0
1
8
725
4
1
17312311506
/
H
S
7
5
S
T
D26
060(5
Ton
s)4
6
0
-
--3---6
0
4
1
450
8
1
9621080
3
H
S
3
4
S
T
D20
0603†
H
S51
863
2
1
71501
2
8
5
7
5
3
6
0
08†03
†34
P
erfec
t
S
TD0
658
208/2
3
0
---3---
6
0
1
8
725
4
1
205156114
/
H
S
0
675
S
TD0
326
4
6
0
-
--3---6
0
4
1
450
8
1
9675106
072(6
Ton
s
)
H
S
0
334
S
T
D20
0803†
5
7
5
-
--3---6
0
H
S51
863
2
1
77561
2
8
06†03
†34
P
erfec
t
DISCONNECT SIZE
POWER SUPPLY *
CONV
OUTLET
FLA
IFM
FAN MOTOR
COMBUSTION
FLA LRA
MOCP**
NO 25.6 30 25 101
YES 31.6 35 30 106
NO 18.5 25 18 90
NO 19.4 25 19 120
NO 9.0 15 9 46
NO 9.4 15 9 60
NO 7.6 10 7 36
NO 7.7 10 8 43
NO 8.3 10 8 52
NO 35.2 45 34 139
NO 22.5 30 22 106
NO 23.4 30 23 136
NO 10.6 15 10 54
NO 11.0 15 11 68
NO 10.3 15 10 45
NO 10.4 15 10 52
NO 11.0 15 11 61
NO 44.1 60 42 206
NO 28.9 35 28 168
NO 30.6 35 30 187
NO 14.7 20 14 84
NO 15.5 20 15 94
NO 11.5 15 11 63
NO 12.3 15 12 72
NO 12.2 15 12 76
NO 32.8 40 32 200
NO 34.5 40 34 219
NO 15.2 20 15 97
NO 16.0 20 16 107
NO 12.4 15 12 69
NO 13.2 20 13 79
YES 24.5 30 24 95
YES 25.4 30 25 124
YES 11.7 15 11 48
YES 12.1 15 12 63
YES 9.7 15 9 38
YES 9.8 15 10 44
YES 10.4 15 10 54
YES 41.2 50 39 144
YES 28.5 35 27 111
YES 29.4 35 29 140
YES 13.3 15 13 56
YES 13.7 15 13 70
YES 12.5 15 12 47
YES 12.6 15 12 53
YES 13.2 15 13 63
YES 50.1 60 48 210
YES 34.9 40 34 173
YES 36.6 40 36 192
YES 17.4 20 17 87
YES 18.2 20 18 96
YES 13.6 15 13 64
YES 14.4 20 14 73
YES 14.4 20 14 77
YES 38.8 45 37 205
YES 40.5 45 39 224
YES 17.9 20 17 99
YES 18.7 25 18 109
4.9
2.2
1.9
4.9
2.2
1.9
5.8
2.6
2.0
0.6 5.8
0.3 2.6
NO 12.8 15 13 81
YES 14.6 20 14 70
YES 15.4 20 15 80
YES 15.0 20 15 83
2.0
581B,C
Table 4—Electrical Data 581B
VOLTAGE
COMPRESSOR (each) OFM (each)
RANGE
IFM TYPE Min Max QTY RLA LRA QTY FLA FLA MCA
STD
0.6 0.3†
0.8† 0.3† 3.4†
1 0.4 0.3†
1 0.4† 0.9† 2.6†
187 254 1 10.3 77 1 0.7 0.6
414 508 1 5.1 39 1 0.4 0.3
HS 5.2
HS 2.6
STD
STD
Perfect
Humidity
STD
187 254 1 13.5 93 1 0.7 0.6
HS 5.8
STD
1 0.4 0.3†
1 0.4 0.9† 2.6†
414 508 1 6.4 46.5 1 0.4 0.3
HS 2.6
STD
Perfect
Humidity
STD
187 254 1 17.3 123 1 1.5 0.6
414 508 1 9 62 1 0.8 0.3
HS 7.5
HS 3.4
STD
HS 518 632 1 7.1 50 1 2.8
STD
187 254 1 20.5 156 1 1.4
HS 0.6 7.5
STD
Perfect
Humidity
STD
0.8 0.3†
0.6† 0.3† 3.4†
414 508 1 9.6 75 1 0.6
STD
Perfect
Humidity
581B036---072
NOMINAL
V --- P H --- H z
UNIT SIZE
2 3 0 --- 1 --- 6 0 STD 187 254 1 16 88 1 0.7 0.6 4.9
208
208
036 (3 Tons) 46 0 --- 3 --- 6 0
2 3 0 --- 1 --- 6 0 STD 187 254 1 23.7 126 1 0.7 0.6 4.9
208
2 3 0 --- 3 --- 6 0
208
048 (4 Tons) 46 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0 HS 518 632 1 4.2 31 2.0
2 3 0 --- 1 --- 6 0 STD 187 254 1 28.8 169 1 1.5 0.6 6.6
208
2 3 0 --- 3 --- 6 0
208
5 7 5 --- 3 --- 6 0
060 (5 Tons) 46 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0 HS 518 632 1 6.4 40 2.0
2 3 0 --- 3 --- 6 0
208
4 6 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0 HS 518 632 1 7.7 56 1 2.8
072 (6 Tons) HS 0.3 3.4
230--- 3 60
15
Step 8 Adjust Factory--Installed Options
Perfect HumidityAdaptive Dehumidification System
Perfect Humidity system operation can be controlled by field installation of a Bryant--approved humidistat. (See Fig. 15.)
NOTE: A light commercial Thermidistatdevice (Fig. 16) can be used instead of the humidistat if desired. The Thermidistat device includes a thermostat and a humidistat. The humidistat is normally used in applications where a temperature sensor is already provided.
581B,C
% RELATIVE HUMIDITY
Fig. 15 --- Accessory Field--Installed Humidistat
Fig. 16 --- Light Commercial Thermidistat Device
To install the humidistat:
1. Route humidistat cable through hole provided in unit control box.
2. Some models may be equipped with a raceway built into the corner post located on the left side of control box (See Fig. 14). This raceway provides the required clearance between high--voltage and low voltage wiring. For models without a raceway, ensure to provide the NEC required clearance between the high--voltage and low-- voltage wiring.
3. Use a wire nut to connect humidistat cable into low­voltage wiring as shown in Fig. 17.
C06358
C06359
To install Thermidistat device:
1. Route Thermidistat cable through hole provided in unit control box.
2. Some models may be equipped with a raceway built into the corner post located on the left side of control box (See Fig. 14). This raceway provides the required clearance between high--voltage and low voltage wiring. For models without a raceway, ensure to provide the NEC required clearance between the high--voltage and low-- voltage wiring.
3. A field-supplied relay must be installed between the Thermidistat and the Humidi-Mizer circuit (recommended relay: HN61KK324). (See Fig. 18.) The relay coil is connected between the DEHUM output and C (common) of the unit. The relay controls thePerfect Humidity solenoid valve and must be wired between the Perfect Humidity fuse and the low-pressure switch. Refer to the installation instructions included with the Bryant Light Commercial Thermidistat device for more information.
Manual Outdoor
Damper
The outdoor--air hood and screen are attached to the basepan at the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building. Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws. (See Fig. 19.)
3. Remove evaporator coil access panel. Separate hood and screen from basepan by removing the 4 screws securing them. Save all screws.
4. Replace evaporator coil access panel.
5. Place hood on front of outdoor air opening panel. See Fig. 20 for hood details. Secure top of hood with the
4screwsremovedinStep3.(SeeFig.21.)
6. Remove and save 6 screws (3 on each side) from sides of the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of manual outdoor-air damper. (See Fig. 28 and 21.) Secure hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper blade by adjusting the manual outdoor-air adjustment screws on the front of the damper blade. (See Fig. 19.) Slide blade vertically until it is in the appropriate position determined by Fig. 22. Tighten screws.
9. Remove and save screws currently on sides of hood. Insert screen. Secure screen to hood using the screws. (See Fig. 21.)
Convenience
Outlet
An optional convenience outlet provides power for rooftop use. For maintenance personnel safety, the convenience outlet power is off when the unit disconnect is off. Adjacent unit outlets may be used for service tools.
16
CB Circuit Breaker CR Cooling Relay DHR Dehumidify Relay DSV Discharge Solenoid Valve HR Heater Relay LPS Low Pressure Switch LSV Liquid Solenoid Valve LT LO Low Temperature Lockout
Field Splice
Fig. 17 --- Typical Perfect Humidityt Adaptive Dehumidification System
LEGEND
Terminal (Unmarked)
Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
Humidistat Wiring (208/230--V Unit Shown)
C06128
581B,C
LCT
R
C Y1 Y2
G W1 W2
DEHUM
OC
TSTAT WIRES
LEGEND
CB Circuit Breaker LCT — Light Commercial Thermidistat™ Device LLSV — Liquid Line Solenoid Valve LT LO — Low Temperature Lockout
Fig. 18 --- Typical Rooftop Unit with Perfect Humidity
Adaptive Dehumidification System with Thermidistat Device
OUTDOOR AIR OPENING PANEL
3 SCREWS (SIDE)
R1
R1
ROOF TOP UNIT
R
C Y1 Y2
G
W1 W2
PINK
PINK
CB
3.2 AMPS
LTL O
PERFECT HUMIDITY SYSTEM
RED
24 V
PINK
FROM PERFECT HUMIDITY SYSTEM LLSV
C06360
Fig. 19 --- Damper Panel with Manual Outdoor--Air
Damper Installed
C06130
C06013
Fig. 20 --- Outdoor-- Air Hood Details
17
A
581B,C
Fig. 21 --- Outdoor-- Air Damper With
Hood Attached
Fig. 22 --- Outdoor-- Air Damper Position Setting
ECONOMI$ER IV CONTROLLER
WIRING HARNESS
CTUATOR
OUTSIDE AIR TEMPERATURE SENSOR
LOW AMBIENT SENSOR
C06131
C06132
Optional Economi$er
IV
See Fig. 23 for EconoMi$er IV component locations. NOTE: These instructions are for installing the optional
EconoMi$er IV. Refer to the accessory EconoMi$er IV when field installing an EconoMi$er IV accessory.
1. To remove the existing unit filter access panel, raise the panel and swing the bottom outward. The panel is now disengaged from the track and can be removed. (See Fig. 24.)
2. The box with the economizer hood components is shipped in the compartment behind the economizer. The EconoMi$er IV controller is mounted on top of the EconoMi$er IV. To remove the component box from its shipping position, remove the screw holding the hood box bracket to the top of the economizer. Slide the hood box out of the unit. (See Fig. 25.)
IMPORTANT: If the power exhaust accessory is to be installed on the unit, the hood shipped with the unit will not be used and must be discarded. Save the aluminum filter for use in the power exhaust hood assembly.
3. The indoor coil access panel will be used as the top of the hood. Remove the screws along the sides and bottom of the indoor coil access panel. (See Fig. 26.)
4. Swing out indoor coil access panel and insert the hood sides under the panel (hood top). Use the screws provided to attach the hood sides to the hood top. Use screws provided to attach the hood sides to the unit. (See Fig. 27.)
5. Remove the shipping tape holding the economizer barometric relief damper in place.
6. Insert the hood divider between the hood sides. (See Fig. 28 and 29.) Secure hood divider with 2 screws on each hood side. The hood divider is also used as the bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath the hood top. Insert the aluminum filter into the bottom filter rack (hood divider). Push the filter into position past the open filter clips. Close the filter clips to lock the filter into place. (See Fig. 28.)
8. Caulk the ends of the joint between the unit top panel and the hood top. (See Fig. 26.)
9. Replace the filter access panel.
10. Install all EconoMi$er IV accessories. EconoMi$er IV wiring is shown in Fig. 29.
Barometric flow capacity is shown in Fig. 30. Outdoor air leakage is shown in Fig. 33. Return air pressure drop is shown in Fig. 32.
FILTER ACCESS PANEL
C06021
Fig. 23 --- EconoMi$er IV Component Locations
COMPRESSOR ACCESS PANEL
OUTDOOR-AIR OPENING AND INDOOR COIL ACCESS PANEL
Fig. 24 --- Typical Access Panel Locations
C06023
18
Loading...
+ 42 hidden pages