Installation and servicing of air-conditioning equipment can be
hazardous due to system pressure and electrical components.
Only trained and qualified service personnel should install, repair,
or service air-conditioning equipment.
Untrained personnel can perform basic maintenance functions of
cleaning coils and filters and replacing filters. All other operations
should be performed by trained service personnel. When working
on air-conditioning equipment, observe precautions in the
literature, tags and labels attached to the unit, and other safety
precautions that may apply.
Follow all safety codes. Wear safety glasses and work gloves. Use
quenching cloth for unbrazing operations. Have fire extinguishers
available for all brazing operations.
Recognize safety information. This is the safety--alert symbol
. When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation,
reliability, or operation.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Before performing service or maintenance operations
on unit, turn off main power switch to unit and install
lockout tag. Ensure electrical service to rooftop unit
agrees with voltage and amperage listed on the unit
rating plate.
!
FIRE, EXPLOSION HAZARD
Failure to follow this warning could cause death and/or
property damage.
Disconnect gas piping from unit when leak testing at
pressure greater than
psig will cause gas valve damage resulting in hazardous
condition. If gas valve is subjected to pressure greater
1
than
/2psig, it must be replaced before use. When
pressure testing field-supplied gas piping at pressures of
1
/2psig or less, a unit connected to such piping must be
isolated by manually closing the gas valve(s).
WARNING
WARNING
1
/2psig. Pressures greater than1/
2
INSTALLATION
Unit is shipped in the vertical discharge configuration. To convert
to horizontal discharge application, remove duct opening covers.
Using the same screws, install covers on duct openings in
basepan of unit with insulation-side down. Seals around
openings must be tight. (See Fig. 1.)
1
Page 2
Fig. 1 --- Horizontal Conversion Panels
Step 1 —Provide Unit Support
581B,C
Roof Curb
Assemble and install accessory roof curb in accordance with
instructions shipped with curb. (See Fig. 2.) Install insulation,
cant strips, roofing felt, and counter flashing as shown. Ductworkmust be attached to curb, not to the unit. If electric control power
or gas service is to be routed through the basepan, attach the
accessory thru-the-bottom service connections to the basepan in
accordancewiththeaccessoryinstallationinstructions.
Connections must be installed before unit is set on roof curb.
IMPORTANT: The gasketing of the unit to the roof curb is
critical for a watertight seal. Install gasket supplied with the roof
curb as shown in Fig. 2. Improperly applied gasket can result in
air leaks and poor unit performance.
Curb should be level. Unit leveling tolerances are shown in Fig.
3. This is necessary for unit drain to function properly.Refer to
Accessory Roof Curb Installation Instructions for additional
information as required.
Slab Mount (Horizontal Units
Provide a level concrete slab that extends a minimum of 6 in.
beyond unit cabinet. Install a gravel apron in front of
condenser-coil air inlet to prevent grass and foliage from
obstructing airflow.
NOTE: Horizontal units may be installed on a roof curb if
required.
Alternate Unit
When the curb or adapter cannot be used, support unit with
sleeper rails using unit curb or adapter support area. If sleeper
rails cannot be used, support the long sides of the unit with a
minimum of 3 equally spaced 4-in. x 4-in. pads on each side.
Support
Only)
Step 2 —Field Fabricate Ductwork
Secure all ducts to roof curb and building structure on vertical
discharge units. Do not connect ductwork to unit. For horizontal
applications, field-supplied isolation flanges should be attached to
horizontal discharge openings and all ductwork should be secured
to the flanges. Insulate and weatherproof all external ductwork,
joints, and roof openings with counter flashing and mastic in
accordance with applicable codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier.
If a plenum return is used on a vertical unit, the return should be
ducted through the roof deck to comply with applicable fire
codes.
C06108
A minimum clearance is not required around ductwork. Cabinet
return-air static pressure (a negative condition) shall not exceed
0.35 in. wg with economizer or 0.45 in. wg without economizer.
These units are designed for a minimum continuous return-air
temperature in heating of 50_F (dry bulb), or an intermittent
operation down to 45_F (dry bulb), such as when used with a
night setback thermostat.
To operate at lower return-air temperatures, a field-supplied
outdoor air temperature control must be used to initiate both
stages of heat when the temperature is below 45_F. Indoor
comfort may be compromised when these lower air temperatures
are used with insufficient heating temperature rise.
Step 3 —Install External Trap for Condensate
Drain
The unit’s3/4-in. condensate drain connections are located on the
bottom and side of the unit. Unit discharge connections do not
determine the use of drain connections; either drain connection
can be used with vertical or horizontal applications.
When using the standard side drain connection, ensure the plug
(Red) in the alternate bottom connection is tight before installing
the unit.
To use the bottom drain connection for a roof curb installation,
relocate the factory-installed plug (Red) from the bottom
connection to the side connection. The center drain plug looks
like a star connection, however it can be removed with a
socket drive extension. (See Fig. 4.) The piping for the
condensate drain and external trap can be completed after the unit
is in place.
All units must have an external trap for condensate drainage.
Install a trap 4-in. deep and protect against freeze-up. If drain line
is installed downstream from the external trap, pitch the line away
from the unit at 1 in. per 10 ft of run. Do not use a pipe size
smaller than the unit connection (
3
/4in.). (See Fig. 5.)
1
/2-in.
Step 4 —Rig and Place Unit
Inspect unit for transportation damage, and file any claim with
transportation agency. Keep unit upright and do not drop.
Spreader bars are not required if top crating is left on unit, and
rollers may be used to move unit across a roof. Level by using
unit frame as a reference. See Table 1 and 2 and Fig. 6 for
additional information. Operating weight is shown in Table 1 and
2 and Fig. 6.
Lifting holes are provided in base rails as shown in Fig. 8 and 9.
Refer to rigging instructions on unit.
!
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury, death and property damage.
All panels must be in place when rigging and lifting.
Positioning
Maintain clearance around and above unit to provide minimum
distance from combustible materials, proper airflow, and service
access. (See Fig. 7, 8 and 9.)
Position unit on roof curb so that the following clearances are
maintained:
rail inside the front and rear, 0.0 in. clearance between the roof
curb and the base rail inside on the duct end of the unit. This will
result in the distance between the roof curb and the base rail
inside on the condenser end of the unit being approximately
equal to Fig. 2, section C-C.
Do not install unit in an indoor location. Do not locate unit air
inlets near exhaust vents or other sources of contaminated air.
1
WARNING
/4in. clearance between the roof curb and the base
2
Page 3
1-4
[406]
DALT
DRAIN
HOLE
13/4
[44.5]
GASPOWERCONTROL
3
/4
[19] NPT
1
/2
[12.7] NPT
3
/4
[19] NPT
CONNECTOR
PKG. ACCY.
BC
CRBTMPWR001A01
CRBTMPWR002A011
CRBTMPWR003A01
1-9
11
[551]
/16
CRBTMPWR004A01
3
/4 [19] NPT
1
/4 [31.7]
3
/4 [19] NPT
1
/4 [31.7]
1
1
/2
[12.7]
ACCESSORY
POWER
1
/2
[12.7]
ROOF CURB
ACCESSORY
CRRFCURB001A01
CRRFCURB002A01
NOTES:
1. Roof curb accessory is shipped disassembled.
2. Insulated panels.
3. Dimensions in [ ] are in millimeters.
4. Roof curb: galvanized steel.
5. Attach ductwork to curb (flanges of duct rest
on curb).
6. Service clearance: 4 ft on each side.
1-2
[356]
2-0
[610]
A
581B036-072
581C024-060
UNIT
SIZE
7.Direction of airflow.
8. Connector packages CRBTMPWR001A01
and 002A01 are for thru-the-curb type gas.
Packages CRBTMPWR003A01 and 004A01
are for thru-the-bottom type gas connections.
581B,C
Fig. 2 --- Roof Curb Details
3
C06345
Page 4
MAXIMUM ALLOWABLE
DIFFERENCE (in.)
A-BB-CA-C
0.51.01.0
Fig. 3 --- Unit Leveling Tolerances
Be sure that unit is installed such that snow will not block the
combustion intake or flue outlet.
581B,C
Unit may be installed directly on wood flooring or on Class A, B,
or C roof-covering material when roof curb is used.
Although unit is weatherproof, guard against water from higher
level runoff and overhangs.
Locate mechanical draft system flue assembly at least 48 in. from
an adjacent building or combustible material. When unit is
located adjacent to public walkways, flue assembly must be at
least 7 ft above grade.
NOTE: When unit is equipped with an accessory flue discharge
deflector, allowable clearance is 18 inches.
Flue gas can deteriorate building materials. Orient unit such that
flue gas will not affect building materials.
Adequate combustion-air space must be provided for proper
operation of this equipment. Be sure that installation complies
with all local codes and Section 5.3, Air for Combustion and
Ventilation, NFGC (National Fuel Gas Code), ANSI (American
National Standards Institute) Z223.1-1984 and addendum
Z223.1a-1987. In Canada, installation must be in accordance with
the CAN1.B149.1 and CAN1.B149.2 installation codes for gas
burning appliances.
Flue vent discharge must have a minimum horizontal clearance of
4 ft from electric and gas meters, gas regulators, and gas relief
equipment.
After unit is in position, remove shipping materials and rigging
skids.
Step 5 —Install Flue Hood
Flue hood is shipped screwed to the burner compartment access
panel. Remove from shipping location and, using screws
provided, install flue hood in location shown in Fig. 8 and 9.
For units being installed in California Air Quality Management
Districts which require NOx emissions of 40 nanograms/joule or
less, a low NOx unit must be installed.
NOTE: Low NOx units are available for 2 to 5 ton units.
C06110
CONDENSATE PAN (SIDE VIEW)
HORIZONTAL
DRAIN OUTLET
NOTE: Drain plug is shown in factory-installed position.
DRAIN PLUG
C06003
Fig. 4 --- Condensate Drain Pan
NOTE: Trap should be deep enough to offset maximum unit static
difference. A 4-in. trap is recommended.
C06004
Fig. 5 --- Condensate Drain Piping Details
Step 6 —Install Gas Piping
Unit is equipped for use with type of gas shown on nameplate.
Refer to localbuilding codes, or in the absence of local codes,
to ANSI Z223.1-1984 and addendum Z223.1A-1987 entitled
National Fuel Gas Code. In Canada, installation must be in
accordancewiththeCAN1.B149.1andCAN1.B149.2
installation codes for gas burning appliances.
For natural gas applications, gas pressure at unit gas connection
must not be less than 4 in. wg or greater than 13 in. wg while the
unit is operating. On 581B036 --072 and 581C036--060 high-heat
units, the gas pressure at unit gas connection must not be less than
5 in. wg or greater than 13 in. wg while the unit is operating. For
propane applications, the gas pressure must not be less than 5 in.
wg or greater than 13 in. wg at the unit connection.
Size gas supply piping for 0.5 in. wg maximum pressure drop.
Do not use supply pipe smaller than unit gas connection.
4
Page 5
NOTES:
OPERATING
OPERATING
B
1. Place unit on curb as close as possible to the duct end.
2. Dimensionin( )isinmillimeters.
3. Hook rigging shackles through holes in base rail as shown in detail “A.” Holes in base rails are centered around the unit center of gravity. Use wooden top skid
when rigging to prevent rigging straps from damaging unit.
4. Weights include base unit without economizer. See Table 1 for unit operating weights with accessory economizer.
5. Weights include base unit without the Perfect Humidityt adaptive dehumidification system. See Table 1 for unit operating weights with th e Perfect Humidityt
system.
Support gas piping as shown in the table in Fig. 11. For example,
3
/4-in. gas pipe must have one field-fabricated support beam
a
every 8 ft. Therefore, an 18-ft long gas pipe would have a
minimum of 3 support beams, and a 48-ft long pipe would have a
minimum of 6 support beams.
!
WARNING
PROPERTY DAMAGE HAZARD
Failure to follow this warning could result in personal
injury, death and property damage.
All panels must be in place when rigging and lifting.
See Fig. 11 for typical pipe guide and locations of external
manual gas shutoff valve.
NOTE: If accessory thru-the-bottom connections and roof curb
are used, refer to the Thru-the-Bottom Accessory Installation
Instructions for information on power wiring and gas
connection piping. The power wiring, control wiring and gas
piping can be routed through field-drilled holes in the basepan.
The basepan is specially designed and dimpled for drilling the
access connection holes.
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage.
When connecting the gas line to the unit gas valve, the
installer MUST use a backup wrench to prevent damage
to the valve.
5
Page 6
581B,C
C06363
COMPRESSOR
ACCESS PANEL
CONTROL BOX
Fig. 8 --- 581B 036 --072 Base Unit Dimensions
6
Page 7
C06364
581B,C
COMPRESSOR
ACCESS PANEL
Fig. 9 --- 581C 024 --060 Base Unit Dimensions
7
Page 8
Fig. 10 --- Flue Hood Details
*
581B,C
LEGEND
NFGC — National Fuel Gas Code
Field supplied.
NOTE: Follow all local codes.
SPACING OF SUPPORTS
STEEL PIPE
NOMINAL DIAMETER (in.)
1
/
3
/4or 1
1
/4or larger
1
2
Fig. 11 --- Gas Piping Guide (With Accessory
Thru--the--Curb Service Connections)
Step 7 —Make Electrical Connections
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Unit cabinet must have an uninterrupted, unbroken
electrical ground to minimize the possibility of personal
injury if an electrical fault should occur. This ground
may consist of electrical wire connected to unit ground
lug in control compartment, or conduit approved for
electrical ground when installed in accordance with
NEC (National Electrical Code), ANSI/NFPA (National
Fire Protection Association), latest edition, and local
electrical codes. Do not use gas piping as an electrical
ground.
WARNING
SPACING OF SUPPORTS
X DIMENSION (ft)
6
8
10
C06114
C06115
Field Power Supply
All units except 208/230-v units are factory wired for the voltage
shown on the nameplate. If the 208/230-v unit is to be connected
to a 208-v power supply, the transformer must be rewired by
moving the black wire from the 230-v terminal on the
transformer and connecting it to the 200-v terminal from the
transformer.
Refer to unit label diagram for additional information. Pigtails
are provided for field service. Use factory-supplied splices or UL
(Underwriters’ Laboratories) approved copper connector.
When installing units, provide a disconnect per NEC.
Allfield wiringmustcomplywithNECand local
requirements.
Install conduit through side panel openings indicated in Fig. 8.
Route power lines through connector to terminal connections as
shown in Fig. 12.
Voltage to compressor terminals during operation must be within
voltage range indicated on unit nameplate (also see Tables 3 and
4). On 3-phase units, voltages between phases must be balanced
within 2% and the current within 10%. Use the formula shown in
Tables 3 and 4, Note 3 to determine the percent voltage
imbalance. Operation on improper line voltage or excessive phase
imbalance constitutes abuse and may cause damage to electrical
components. Such operation would invalidate any applicable
Bryant warranty.
NOTE: If accessory thru-the-bottom connections and roof curb
are used, refer to the Thru-the-Bottom Accessory Installation
Instructions for information on power wiring and gas connection
piping. The power wiring, control wiring and gas piping can be
routed through field-drilled holes in the basepan. The basepan is
specially designed and dimpled for drilling the access connection
holes.(SeeFig.2.)
Field Control W
iring
Install a Bryant-approved accessory thermostat assembly
according to installation instructions included with the accessory.
Locate thermostat assembly on a solid wall in the conditioned
space to sense average temperature in accordance with thermostat
installation instructions.
Route thermostat cable or equivalent single leads of colored wire
from subbase terminals through connector on unit to low-voltage
connections (shown in Fig. 13 and 14).
Connect thermostat wires to matching screw terminals of
low-voltage connection board. (See Fig. 13 and 14.)
NOTE: For wire runs up to 50 ft, use no. 18 AWG (American
Wire Gauge) insulated wire (35_Cminimum).For50to75ft,use
no. 16 AWG insulated wire (35_C minimum). For over 75 ft, use
no. 14 AWG insulated wire (35_C minimum). All wire larger
than no. 18 AWG cannot be directly connected to the thermostat
and will require a junction box and splice at the thermostat.
Pass the control wires through the hole provided in thecorner
post; then feed wires through the raceway built into the corner
post to the 24-v barrier located on the left side of the control box.
(See Fig. 15). The raceway provides the UL required clearance
between high and low-voltage wiring.
Heat Anticipator
Settings
Set heat anticipator settings at 0.14 amp for first stage and 0.14
for second stage heating, when available.
8
Page 9
Table 1—Physical Data 581B
A
/B(
)
MotorPulleyPitchDiameterA/B(i
n.)
f
SpeedChangeperFullTurno
f
MovablePulleyMaximumFul
l
BASE UNIT 581B036048060072
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Unit
Perfect Humidity Adaptive Dehumidification System
EconoMi$er IV
Roof Curb
COMPRESSOR
Quantity
Oil (oz)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb-oz)
Standard Unit
Unit With Perfect Humidity Adaptive Dehumidification System
CONDENSER FAN
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
Watts Input (Total)
CONDENSER COIL
Rows...Fins/in.
Tot a l F ace A r ea (sq f t )
EVAPORATOR COIL
Standard Unit
Rows...Fins/in.
Tot a l F ace A r ea (sq f t )
Unit with Perfect Humidity Adaptive Dehumidification System
Rows...Fins/in.
Tot a l F ace A r ea (sq f t )
EVAPORATOR FAN
Quantity...Size (in.)
Nominal Cfm
Maximum Continuous BhpStd
Hi-Static
Motor RPMStd
Hi-Static
Motor Frame SizeStd
Hi-Static
Fan Rpm RangeStd
Hi-Static
Motor Bearing Type
Maximum Fan Rpm
Motor PulleyPitch Diameter
in.
Hi-Static
Nominal Motor Shaft Diameter (in.)Std
Hi-Static
Fan Pulley Pitch Diameter (in.)Std
Hi-Static
Belt — Type...Length (in.)Std
Hi-Static
Pulley Center Line Distance (in.)
Speed Changeper Full Turn o
Movable Pulley Flange (rpm)
Movable PulleyMaximum Full
Turns from Closed Position
Hi-Static
Hi-Static
Factory Setting — Full Turns OpenStd
Hi-Static
Factory Speed Setting (rpm)Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
LEGEND
Bhp — Brake Horsepower
Std
Std
Std
3456
530540560635
15232529
50505050
115115115115
Scroll
1111
42535060
R-22
Acutrol Metering Device
5-810-210-012- 8
12-518-820-523-14
Propeller
1...221...221...221...22
3500350041004100
1
/4...825
1
/4...825
1
/4...1100
1
/4...1100
180180320320
3/8---in. OD Enhanced Copper Tubes, Aluminum Lanced Fins
1...172...172...172...17
14.616.516.521.3
3/8---in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins
2...152...154...154...15
5.55.55.57.3
1...172...172...172...17
3.93.93.95.2
Centrifugal Type, Belt Drive
1...10 x 101...10 x 101...10 x 101...10 x 10
1200160020002400
1.20
2.40
1620
1725
48
56
680-1044
1075-1455
1.201.30/2.40*2.40
2.402.902.90
162017251725
172517251725
4848/56*56
565656
770-11851035-14601119-1585
1075-14551300-16851300-1685
BallBallBallBall
2100210021002100
1.9/2.9
2.8/3.8
1/
2
5
/
8
4.5
4.5
1...A...36
1...A...39
1.9/2.02.4/3.42.4/3.4
2.8/3.83.4/4.43.4/3.4
1
/
2
5
/
8
4.04.04.0
5
/
8
5
/
8
5
7
4.04.54.5
1...A...361....4...401...A...38
1...A...391...A...401...A...40
10.0-12.410.0-12.414.7-15.514.7-15.5
65
65
5
6
3
1
3
826
1233
5
/
/
2
8
707595
656060
565
655
333
31/
2
93612481305
123313961396
5
/
8
31/
2
5
/
8
31/
5
581B,C
/
8
/
8
2
/
8
9
Page 10
Table 1 — Physical Data 581B (cont)
UNIT SIZE 581B036048060072
FURNACE SECTION
Rollout Switch Cutout Temp (F)†195195195195
Burner Orifice Diameter (in. ...drill size)**
Natural Gas —Std071/072.113...33.113...33.113...33.113...33
Thermostat Heat Anticipator Setting (amps)
208/230/460 v
First Stage.14.14.14.14
Second Stage.14.14.14.14
Gas Input (Btuh)
First Stage/Second Stage (3---phase units)07250,000/ 72,00050,000/ 72,00050,000/ 72,00050,000/ 72,000
Manifold Pressure (in. wg)
Natural Gas —Std3.53.53.53.5
Propane —Alt††3.53.53.53.5
Maximum Static Pressure (in. wg)1.01.01.01.0
Field Gas Connection Size (in.)1/21/21/21/2
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief
Cutout
Reset (Auto.)
Cleanable. Screen quantity and size varies with option selected.
2...16 x 25 x 24...16 x 16 x 2
Throwaway
LEGEND
Bhp — Brake Horsepower
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh
heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh
Heat input units have 3 burners.
††A propane kit is available as an accessory. Kit may be used at elevations as high as
2000 ft. If a propane kit is used with Low NOx units, the Low NOx baffle must be
removed a nd the units will no longer be classified as Lo w NOx units.
ll Three-phase standard models have heating inputs as shown. Single-phase standard models have one-stage heating wi th heating input val ues.
***California compliant three-phase models.
†††California SCAQMD compliant low NO
controlled to 40 nanograms per joule or less.
models have combustion products that are
x
10
Page 11
Table 2—Physical Data 581C
A
/B(
)
MotorPulleyPitchDiameterA/B(i
n.)
f
SpeedChangeperFullTurno
f
MovablePulleyMaximumFul
l
BASE UNIT 581C024036048072
NOMINAL CAPACITY (tons)
OPERATING WEIGHT (lb)
Unit
Perfect Humidity Adaptive Dehumidification System
EconoMi$er IV
Roof Curb
COMPRESSOR
Quantity
Oil (oz)
REFRIGERANT TYPE
Expansion Device
Operating Charge (lb-oz)
Standard Unit
Unit With Perfect Humidity Adaptive Dehumidification System
CONDENSER FAN
Quantity...Diameter (in.)
Nominal Cfm
Motor Hp...Rpm
Watts Input (Total)
CONDENSER COIL
Rows...Fins/in.
Tot a l F ace A r ea (sq f t )
EVAPORATOR COIL
Standard Unit
Rows...Fins/in.
Tot a l F ace A r ea (sq f t )
Unit with Perfect Humidity Adaptive Dehumidification System
Rows...Fins/in.
Tot a l F ace A r ea (sq f t )
EVAPORATOR FAN
Quantity...Size (in.)
Nominal Cfm
Maximum Continuous BhpStd
Hi-Static
Motor Frame SizeStd
Hi-Static
Motor Rpm
Fan Rpm RangeStd
Hi-Static
Motor Bearing Type
Maximum Fan Rpm
Motor PulleyPitch Diameter
in.
Hi-Static
Nominal Motor Shaft Diameter (in.)Std
Hi-Static
Fan Pulley Pitch Diameter (in.)Std
Hi-Static
Belt — Type...Length (in.)Std
Hi-Static
Pulley Center Line Distance (in.)
Speed Changeper Full Turn o
Movable Pulley Flange (rpm)
Movable PulleyMaximum Full
Turns from Closed Position
Hi-Static
Hi-Static
Factory Setting — Full Turns OpenStd
Hi-Static
Factory Speed Setting (rpm)Std
Hi-Static
Fan Shaft Diameter at Pulley (in.)
Std
Std
Std
2345
530540560635
13152325
50505050
115115115115
Scroll
1111
25425653
R-22
Acutrol Metering Device
5 --- 37 --- 1 18 --- 812---11
1 0 --- 214 --- 014--- 1321 --- 0
Propeller
1...221...221...221...22
3000350035004100
1
/8...825
1
/8...825
1
/8...825
1
/4...1100
180180180320
3/8---in. OD Enhanced Copper Tubes, Aluminum Lanced Fins
1...171...172...172...17
14.614.616.516.5
3/8---in. OD Enhanced Copper Tubes, Aluminum Double-Wavy Fins
2...152...152...154...15
4.25.55.55.5
1...171...172...172...17
3.53.93.93.9
Centrifugal Type, Belt Drive
1...10 x 101...10 x 101...10 x 101...10 x 10
800120016002000
0.58
1.201.201.30/2.40*
2.402.402.90
48
484848/56*
565656
1620162016201725
400-1000
680-1044770-11851035-1460
1075-14551075-14551300-1685
BallBallBallBall
1620210021002100
2.4/3.2
5
/
8
7
/
8
4.0
4.5
1...A...36
1.9/2.91.9/2.02.4/3.4
2.8/3.82.8/3.83.4/4.4
1/
2
5
/
8
4.54.04.0
1
/
2
5
/
8
5
5
4.54.04.5
1...A...361...A...361....4...40
1...A...391...A...391...A...40
10.0---12.410.0-12.410.0-12.414.7-15.5
60
657075
656560
5
556
665
333
31/
2
8269361248
123312331396
5
/
8
31/
2
5
/
8
31/
5
756
5
3
/
8
581B,C
/
8
/
8
2
/
8
11
Page 12
Table 2 — Physical Data 581C (cont)
UNIT SIZE 581C024036048060
FURNACE SECTION
Rollout Switch Cutout Temp (F)†195195195195
Burner Orifice Diameter (in. ...drill size)**
Natural Gas —Std071/072.113...33.113...33.113...33.113...33
Thermostat Heat Anticipator Setting (amps)
208/230/460 v
First Stage.14.14.14.14
Second Stage.14.14.14.14
Gas Input (Btuh)
First Stage/Second Stage (3---phase units)07250,000/ 72,00050,000/ 72,00050,000/ 72,00050,000/ 72,000
Manifold Pressure (in. wg)
Natural Gas —Std3.53.53.53.5
Propane —Alt††3.53.53.53.5
Maximum Static Pressure (in. wg)1.01.01.01.0
Field Gas Connection Size (in.)1/21/21/21/2
HIGH-PRESSURE SWITCH (psig)
Standard Compressor Internal Relief
Cutout
Reset (Auto.)
Cleanable. Screen quantity and size varies with option selected.
2...16 x 25 x 24...16 x 16 x 2
Throwaway
LEGEND
Bhp — Brake Horsepower
**60,000 and 72,000 Btuh heat input units have 2 burners. 90,000 and 120,000 Btuh
heat input units have 3 burners. 115,000 Btuh heat input units and 150,000 Btuh
Heat input units have 3 burners.
††A propane kit is available as an accessory. Kit may be used at elevations as high as
2000 ft. If a propane kit is used with Low NOx units, the Low NOx baffle must be
removed a nd the units will no longer be classified as Lo w NOx units.
ll Three-phase standard models have heating inputs as shown. Single-phase standard models have one-stage heating wi th heating input values.
***California compliant three-phase models.
†††California SCAQMD compliant low NO
controlled to 40 nanograms per joule or less.
models have combustion products that are
x
12
Page 13
BLK
BLK
TO COMP
BLK
TO COMP
1123
C
2321
208/230-1-60
(SIZES 581B036-060,
581C024-060)
1123
C
2321
208/230-3-60
460-3-60
(SIZES 581B060, 072,
581C0060)
YEL
FIELD POWER SUPPLY
DISCONNECT
PER NEC
BLK
YEL
BLU
FIELD POWER SUPPLY
DISCONNECT
PER NEC
EQUIP
GND
TO COMP
14
IFC
63
1123
YELBLU
C
2321
208/230-3-60
480-3-60
(SIZES 581B036,048
581C036,048)
FIELD POWER SUPPLY
DISCONNECT
PER NEC
BLK
1113
YELBLU
C
2321
FIELD POWER SUPPLY
575-3-60
(SIZES 581B060, 072)
DISCONNECT
PER NEC
Fig. 12 --- Power Wiring Connections
(SIZES 581B036,048
581C036,048)
TO TB2
1123
C
575-3-60
YEL
2321
FIELD POWER SUPPLY
DISCONNECT
PER NEC
BLU
581B,C
C06346
Y1
Y2
W1
W2
IPD/X
R
G
C
WIRE
CONNECTIONS
TO
LOW-VOLTAGE
SECTION
COOL STAGE 1
FAN
HEAT STAGE 1
COOL STAGE 2
HEAT STAGE 2
24 VAC HOT
24 VAC COM
N/A
OUTDOOR AIR
SENSOR
THERMOSTAT DIPSWITCH SETTINGS
ON
OFF
A
LEGEND
NOTE: Un derlined letter indicates ac tive therm ostat output wh en
configured for A/C operation.
Y1/W2
G
W/W1
Y/Y2
O/W2
R
C
S1
S2
B
C
Field Wiring
D
Fig. 13 --- Low --Voltage Connections With or
Without Economizer or Two--Position Damper
C06008
LOW VOLTAGE
CONNECTIONS
INTEGRATED GAS UNIT
CONTROLLER (IGC)
Fig. 14 --- Field Control Wiring
C06125
13
Page 14
IFM
208
/23
0
1
6
0
S
TD1
8
72541109631070620
024
208
/23
0
1
6
0
S
TD1
8
2
110.96310.70.6
2.0
208
/23
0
-
--1--
-60
S
TD1
8
725411688107064
9
/
S
T
D
4
9
208
/23
0
-
--3--
-60
1
8
725411037710706
/
H
S
5
8
S
T
D
2
2
4
6
0
---3-
--6
0
4
1
4508151391040
3
036
H
S
2
6
(3ton
s
)
S
T
D
1
9
104
5
7
5
---3-
--60HS5
1
863214231
03†20
104†26†
P
erfec
t
208
/23
0
-
--1--
-60
S
TD1
9
72541211151150649
/
S
T
D
4
9
208
/23
0
-
--3--
-60
1
8
725411419511506
/
H
S
5
8
S
T
D
2
2
4
6
0
---3-
--6
0
4
1
4508171451080
3
048
H
S
2
6
(4ton
s
)
S
T
D
1
9
106
5
7
5
---3-
--60HS5
1
863216138
03†20
108†26†
P
erfec
t
208
/23
0
-
--1--
-60
S
TD1
8
72541251501150666
/
S
T
D
5
8
208
/23
0
-
--3--
-60
1
8
725411731231150
6
/
H
S
7
5
S
T
D
2
6
4
6
0
---3-
--6
0
4
1
45081847010803†
060
H
S
3
4
(5ton
s
)
S
T
D
2
0
106
5
7
5
---3-
--60HS5
1
863217153
03†28
119†34†
P
erfec
t
581B,C
MINIMUM UNIT
DISCONNECT SIZE
POWER SUPPLY *
CONV
OUTLET
IFM
FAN MOTOR
COMBUSTION
FLA
FLALRA
MOCP**
MCA
NO16.32015.669
NO25.63024.8101
NO18.52518.390
NO19.42519.3120
NO9.0158.946
NO9.4159.360
NO7.6107.536
NO7.7107.643
NO7.7108.048
NO32.74031.5130
NO24.03023.6110
NO24.93024.6140
NO11.91511.653
NO12.31512.167
NO10.1159.944
NO10.21510.051
NO10.31510.156
NO39.45038.1187
NO28.93528.3168
NO30.63530.2187
NO13.92013.692
NO14.72014.5102
NO11.51511.266
NO12.31512.175
YES22.32521.273
YES31.63530.4106
YES24.53023.895
YES25.43024.9124
YES11.71511.448
YES12.11511.863
YES9.7159.538
YES9.8159.644
YES9.8159.650
YES38.74537.0135
YES30.03529.1115
YES30.93530.1145
YES14.62014.155
YES15.02014.670
YES12.31511.946
YES12.41512.052
YES12.51512.158
YES45.46043.6191
YES34.94033.8173
YES36.64035.8192
YES16.62016.195
YES17.42017.0104
4.9
2.2
1.9
10.4
4.9
2.2
1.9
10.4†2.6†
10.6
5.8
2.6
10.8†2.6†
NO12.21512.079
YES13.61513.267
YES14.42014.176
YES14.42014.080
2.0
10.6
11.9†3.4†
Table 3—Electrical Data 581C
VOLTAGE
COMPRESSOROFM
RANGE
581C024--- 060
NOMINAL
IFM TYPEMinMaxQTYRLALRAQTYFLAFLA
V --- P H --- H z
UNIT SIZE
024
54
7
---
---
---
---
(2 tons)
2 3 0 --- 1 --- 6 0STD1872541168810.70.64.9
208
STD
187254110.37710.70.6
2 3 0 --- 3 --- 6 0
208
41450815.13910.40.3
HS5.8
HS2.6
STD
STD
Perfect
Humidity
036
4 6 0 --- 3 --- 6 0
(3 tons)
5 7 5 --- 3 --- 6 0HS51863214.2310.3†2.0
2 3 0 --- 1 --- 6 0STD19725412111511.50.64.9
208
STD
187254114.19511.50.6
2 3 0 --- 3 --- 6 0
208
41450817.14510.80.3
HS5.8
HS2.6
STD
STD
Perfect
Humidity
048
4 6 0 --- 3 --- 6 0
(4 tons)
5 7 5 --- 3 --- 6 0HS51863216.1380.3†2.0
2 3 0 --- 1 --- 6 0STD18725412515011.50.66.6
208
STD
187254117.312311.50.6
2 3 0 --- 3 --- 6 0
208
41450818.47010.80.3†
HS7.5
HS3.4
STD
STD
Perfect
Humidity
060
4 6 0 --- 3 --- 6 0
(5 tons)
5 7 5 --- 3 --- 6 0HS51863217.1530.3†2.8
HACR --- Heating, Air Conditioning and Refrigeration
IFM --- Indoor (Evaporator) Fan Motor
LRA --- Locked Rotor Amps
MCA --- Minimum Circuit Amps
MOCP --- Maximum Overcurrent Protection
NEC --- National Electrical Code
OFM --- Outdoor (Condenser) Fan Motor
RLA --- Rated Load Amps
* The values listed in this table do not include power exhaust. See power exhaust table for power exhaust requirements.
** Fuse or HACR breaker
FLA --- Full Load Amps
{ 460v motor
NOTES:
14
Page 15
MINIMUM UNI
208/2
3
0
---1---
6
0
S
T
D
1
8
725
4
1
16881070649
/
S
T
D49
208
/23
0
-
-
-36
0
1
8
725
4
1
103771070
6
/
H
S
5
2
S
T
D22
036(3
Ton
s)4
6
0
-
--3---6
0
4
1
450
8
1
513910403
H
S
2
6
S
T
D19
10403
†
5
7
5
-
--3---6
0
H
S51
863
2
1
423
1
2
0
104†09†26
†
P
erfec
t
208/2
3
0
---1---
6
0
S
T
D
1
8
725
4
1
2371261070649
/
S
T
D49
208/2
3
0
---3---
6
0
1
8
725
4
1
135931070
6
/
H
S
5
8
S
T
D22
048(4
Ton
s)4
6
0
-
--3---6
0
4
1
450
8
1
644651040
3
H
S
2
6
S
T
D19
10403
†
5
7
5
-
--3---6
0
H
S51
863
2
1
644
0
2
0
10409
†26
†
P
erfec
t
208/2
3
0
---1---
6
0
S
T
D
1
8
725
4
1
2881691150666
/
S
T
D58
208/2
3
0
---3---
6
0
1
8
725
4
1
17312311506
/
H
S
7
5
S
T
D26
060(5
Ton
s)4
6
0
-
--3---6
0
4
1
450
8
1
9621080
3
H
S
3
4
S
T
D20
0603†
H
S51
863
2
1
71501
2
8
5
7
5
3
6
0
08†03
†34
†
P
erfec
t
S
TD0
658
208/2
3
0
---3---
6
0
1
8
725
4
1
205156114
/
H
S
0
675
S
TD0
326
4
6
0
-
--3---6
0
4
1
450
8
1
9675106
072(6
Ton
s
)
H
S
0
334
S
T
D20
0803†
5
7
5
-
--3---6
0
H
S51
863
2
1
77561
2
8
06†03
†34
†
P
erfec
t
DISCONNECT SIZE
POWER SUPPLY *
CONV
OUTLET
FLA
IFM
FAN MOTOR
COMBUSTION
FLALRA
MOCP**
NO25.63025101
YES31.63530106
NO18.5251890
NO19.42519120
NO9.015946
NO9.415960
NO7.610736
NO7.710843
NO8.310852
NO35.24534139
NO22.53022106
NO23.43023136
NO10.6151054
NO11.0151168
NO10.3151045
NO10.4151052
NO11.0151161
NO44.16042206
NO28.93528168
NO30.63530187
NO14.7201484
NO15.5201594
NO11.5151163
NO12.3151272
NO12.2151276
NO32.84032200
NO34.54034219
NO15.2201597
NO16.02016107
NO12.4151269
NO13.2201379
YES24.5302495
YES25.43025124
YES11.7151148
YES12.1151263
YES9.715938
YES9.8151044
YES10.4151054
YES41.25039144
YES28.53527111
YES29.43529140
YES13.3151356
YES13.7151370
YES12.5151247
YES12.6151253
YES13.2151363
YES50.16048210
YES34.94034173
YES36.64036192
YES17.4201787
YES18.2201896
YES13.6151364
YES14.4201473
YES14.4201477
YES38.84537205
YES40.54539224
YES17.9201799
YES18.72518109
4.9
2.2
1.9
4.9
2.2
1.9
5.8
2.6
2.0
0.65.8
0.32.6
NO12.8151381
YES14.6201470
YES15.4201580
YES15.0201583
2.0
581B,C
Table 4—Electrical Data 581B
VOLTAGE
COMPRESSOR (each)OFM (each)
RANGE
IFM TYPEMinMaxQTYRLALRAQTYFLAFLAMCA
STD
0.60.3†
0.8†0.3†3.4†
10.40.3†
10.4†0.9†2.6†
187254110.37710.70.6
41450815.13910.40.3
HS5.2
HS2.6
STD
STD
Perfect
Humidity
STD
187254113.59310.70.6
HS5.8
STD
10.40.3†
10.40.9†2.6†
41450816.446.510.40.3
HS2.6
STD
Perfect
Humidity
STD
187254117.312311.50.6
414508196210.80.3
HS7.5
HS3.4
STD
HS51863217.15012.8
STD
187254120.515611.4
HS0.67.5
STD
Perfect
Humidity
STD
0.80.3†
0.6†0.3†3.4†
41450819.67510.6
STD
Perfect
Humidity
581B036---072
NOMINAL
V --- P H --- H z
UNIT SIZE
2 3 0 --- 1 --- 6 0STD1872541168810.70.64.9
208
208
036 (3 Tons)46 0 --- 3 --- 6 0
2 3 0 --- 1 --- 6 0STD187254123.712610.70.64.9
208
2 3 0 --- 3 --- 6 0
208
048 (4 Tons)46 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0HS51863214.2312.0
2 3 0 --- 1 --- 6 0STD187254128.816911.50.66.6
208
2 3 0 --- 3 --- 6 0
208
5 7 5 --- 3 --- 6 0
060 (5 Tons)46 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0HS51863216.4402.0
2 3 0 --- 3 --- 6 0
208
4 6 0 --- 3 --- 6 0
5 7 5 --- 3 --- 6 0HS51863217.75612.8
072 (6 Tons)HS0.33.4
230--- 3 60
15
Page 16
Step 8 —Adjust Factory--Installed Options
Perfect Humidity Adaptive Dehumidification
System
Perfect Humidity system operation can be controlled by field
installation of a Bryant--approved humidistat. (See Fig. 15.)
NOTE: A light commercial Thermidistat device (Fig. 16) can
be used instead of the humidistat if desired. The Thermidistat
device includes a thermostat and a humidistat. The humidistat is
normally used in applications where a temperature sensor is
already provided.
581B,C
% RELATIVE HUMIDITY
Fig. 15 --- Accessory Field--Installed Humidistat
Fig. 16 --- Light Commercial Thermidistat Device
To install the humidistat:
1. Route humidistat cable through hole provided in unit
control box.
2. Some models may be equipped with a raceway built into
the corner post located on the left side of control box (See
Fig. 14). This raceway provides the required clearance
between high--voltage and low voltage wiring. For models
without a raceway, ensure to provide the NEC required
clearance between the high--voltage and low-- voltage
wiring.
3. Use a wire nut to connect humidistat cable into lowvoltage wiring as shown in Fig. 17.
C06358
C06359
To install Thermidistat device:
1. Route Thermidistat cable through hole provided in unit
control box.
2. Some models may be equipped with a raceway built into
the corner post located on the left side of control box (See
Fig. 14). This raceway provides the required clearance
between high--voltage and low voltage wiring. For models
without a raceway, ensure to provide the NEC required
clearance between the high--voltage and low-- voltage
wiring.
3. A field-supplied relay must be installed between the
Thermidistat and the Humidi-Mizer circuit (recommended
relay: HN61KK324). (See Fig. 18.) The relay coil is
connected between the DEHUM output and C (common)
of the unit. The relay controls thePerfect Humidity
solenoid valve and must be wired between the Perfect
Humidity fuse and the low-pressure switch. Refer to the
installation instructions included with the Bryant Light
Commercial Thermidistat device for more information.
Manual Outdoor
Damper
The outdoor--air hood and screen are attached to the basepan at
the bottom of the unit for shipping.
Assembly:
1. Determine quantity of ventilation required for building.
Record amount for use in Step 8.
2. Remove and save outdoor air opening panel and screws.
(See Fig. 19.)
3. Remove evaporator coil access panel. Separate hood and
screen from basepan by removing the 4 screws securing
them. Save all screws.
4. Replace evaporator coil access panel.
5. Place hood on front of outdoor air opening panel. See
Fig. 20 for hood details. Secure top of hood with the
4screwsremovedinStep3.(SeeFig.21.)
6. Remove and save 6 screws (3 on each side) from sides of
the manual outdoor-air damper.
7. Align screw holes on hood with screw holes on side of
manual outdoor-air damper. (See Fig. 28 and 21.) Secure
hood with 6 screws from Step 6.
8. Adjust minimum position setting of the damper blade by
adjusting the manual outdoor-air adjustment screws on the
front of the damper blade. (See Fig. 19.) Slide blade
vertically until it is in the appropriate position determined
by Fig. 22. Tighten screws.
9. Remove and save screws currently on sides of hood.
Insert screen. Secure screen to hood using the screws. (See
Fig. 21.)
Convenience
Outlet
An optional convenience outlet provides power for rooftop use.
For maintenance personnel safety, the convenience outlet power
is off when the unit disconnect is off. Adjacent unit outlets may
be used for service tools.
Fig. 17 --- Typical Perfect Humidityt Adaptive Dehumidification System
LEGEND
Terminal (Unmarked)
Splice
Factory Wiring
Field Control Wiring
Field Power Wiring
Humidistat Wiring (208/230--V Unit Shown)
C06128
581B,C
LCT
R
C
Y1
Y2
G
W1
W2
DEHUM
OC
TSTAT WIRES
LEGEND
CB— Circuit Breaker
LCT — Light Commercial Thermidistat™ Device
LLSV — Liquid Line Solenoid Valve
LT LO — Low Temperature Lockout
Fig. 18 --- Typical Rooftop Unit with Perfect Humidity
Adaptive Dehumidification System with Thermidistat Device
OUTDOOR
AIR OPENING
PANEL
3 SCREWS
(SIDE)
R1
R1
ROOF TOP UNIT
R
C
Y1
Y2
G
W1
W2
PINK
PINK
CB
3.2 AMPS
LTL O
PERFECT HUMIDITY SYSTEM
RED
24 V
PINK
FROM
PERFECT HUMIDITY SYSTEM
LLSV
C06360
Fig. 19 --- Damper Panel with Manual Outdoor--Air
Damper Installed
C06130
C06013
Fig. 20 --- Outdoor-- Air Hood Details
17
Page 18
A
581B,C
Fig. 21 --- Outdoor-- Air Damper With
Hood Attached
Fig. 22 --- Outdoor-- Air Damper Position Setting
ECONOMI$ER IV
CONTROLLER
WIRING
HARNESS
CTUATOR
OUTSIDE AIR
TEMPERATURE SENSOR
LOW AMBIENT
SENSOR
C06131
C06132
Optional Economi$er
IV
See Fig. 23 for EconoMi$er IV component locations.
NOTE:These instructions are for installing the optional
EconoMi$er IV. Refer to the accessory EconoMi$er IV when
field installing an EconoMi$er IV accessory.
1. To remove the existing unit filter access panel, raise the
panel and swing the bottom outward. The panel is now
disengaged from the track and can be removed. (See
Fig. 24.)
2. The box with the economizer hood components is shipped
in the compartment behind the economizer. The
EconoMi$er IV controller is mounted on top of the
EconoMi$er IV. To remove the component box from its
shipping position, remove the screw holding the hood box
bracket to the top of the economizer. Slide the hood box
out of the unit. (See Fig. 25.)
IMPORTANT: If the power exhaust accessory is to be installed
on the unit, the hood shipped with the unit will not be used and
must be discarded. Save the aluminum filter for use in the power
exhaust hood assembly.
3. The indoor coil access panel will be used as the top of the
hood. Remove the screws along the sides and bottom of
the indoor coil access panel. (See Fig. 26.)
4. Swing out indoor coil access panel and insert the hood
sides under the panel (hood top). Use the screws provided
to attach the hood sides to the hood top. Use screws
provided to attach the hood sides to the unit. (See Fig. 27.)
5. Remove the shipping tape holding the economizer
barometric relief damper in place.
6. Insert the hood divider between the hood sides. (See
Fig. 28 and 29.) Secure hood divider with 2 screws on
each hood side. The hood divider is also used as the
bottom filter rack for the aluminum filter.
7. Open the filter clips which are located underneath the
hood top. Insert the aluminum filter into the bottom filter
rack (hood divider). Push the filter into position past the
open filter clips. Close the filter clips to lock the filter into
place. (See Fig. 28.)
8. Caulk the ends of the joint between the unit top panel and
the hood top. (See Fig. 26.)
9. Replace the filter access panel.
10. Install all EconoMi$er IV accessories. EconoMi$er IV
wiring is shown in Fig. 29.
Barometric flow capacity is shown in Fig. 30. Outdoor air
leakage is shown in Fig. 33. Return air pressure drop is shown in
Fig. 32.
FILTER ACCESS PANEL
C06021
Fig. 23 --- EconoMi$er IV Component Locations
COMPRESSOR
ACCESS PANEL
OUTDOOR-AIR OPENING AND
INDOOR COIL ACCESS PANEL
Fig. 24 --- Typical Access Panel Locations
C06023
18
Page 19
x
R
o
B
d
o
o
H
Fig. 25 --- Hood Box Removal
CAULK
INDOOR
COIL
ACCESS
PANEL
HERE
HOOD BOX
BRACKET
SIDE
PANEL
TOP
SIDE
PANEL
INDOOR
COIL
ACCESS
PANEL
C06024
Supply Air Temperature (SAT) Sensor
The supply air temperature sensor is a 3k ohm thermistor located
at the inlet of the indoor fan. (See Fig. 34.) This sensor is factory
installed. The operating range of temperature measurement is 0
to 158_F . See Table 5 for sensor temperature/resistance values.
The outdoor air temperature sensor (HH57AC074) is a 10 to 20
mA device used to measure the outdoor-air temperature. The
outdoor-air temperature is used to determine when the
EconoMi$er IV can be used for free cooling. The sensor is
factory-installed on the EconoMi$er IV in the outdoor airstream.
(See Fig. 23 and 33.) The operating range of temperature
measurement is 40_ to 100_F.
DIVIDER
OUTSIDE
AIR
HOOD
CLEANABLE
BAROMETRIC
RELIEF
ALUMINUM
FILTER
FILTER
FILTE
CLIP
Fig. 28 --- Filter Installation
The temperature sensor looks like an eyelet terminal with wires
running to it. The sensor is located in the “crimp end” and is
sealed from moisture.
Outdoor Air Lockout Sensor
The Economi$er IV is equipped with an ambient temperature
lockout switch located in the outdoor air stream which is used to
lockout the compressors below a 42_F ambient temperature. (See
Fig. 23.)
19
C06027
Page 20
Economi$er IV Control
APPLICATION
Modes
Determine the EconoMi$er IV control mode before set up of the
control. Some modes of operation may require different
sensors. (See Table 6.) The EconoMi$er IV is supplied from the
factory with a supply--air temperature sensor and an outdoor-- air
temperature sensor. This allows for operation of the EconoMi$er
IV with outdoor air dry bulb changeover control. Additional
accessories can be added to allow for different types of
changeover control and operation of the EconoMi$er IV and unit.
Outdoor Dry Bulb Changeover
The standard controller is shipped from the factory configured for
outdoor dry bulb changeover control. The outdoor--air and
supply--air temperature sensors are included as standard. For this
control mode, the outdoor temperature is compared to an
adjustable set point selected on the control. If the outdoor-air
temperature is above the set point, the EconoMi$er IV will adjust
the outdoor-air dampers to minimum position. If the outdoor air
temperature is below the set point, the position of the outdoor air
dampers will be controlled to provide free cooling using outdoor
air. When in this mode, the LED next to the free cooling set point
581B,C
potentiometer will be on. The changeover temperature set point is
controlled by the free cooling set point potentiometer located on
the control. (See Fig. 35.) The scale on the potentiometer is A, B,
C, and D. See Fig. 36 for the corresponding temperature
changeover values.
Table6—Economi$erIVSensorUsage
APPLICATION
Outdoor Air
Dry Bulb
Differential
Dry Bulb
Single EnthalpyHH57AC078
Differential
Enthalpy
CO2for DCV
Control using a
Wall-Mounted
Sensor
CO
2
CO2for DCV
Control using a
Duct-Mounted
Sensor
CO
2
*CRENTDIF004A00 and CRTEMPSN002A00 accessories are used on m a ny
different base units. As such, these kits may contain parts that will not be
needed for installation.
† 33ZCSENCO2 is an accessory CO
** 33ZCASPCO2 is an accessory aspirator box required for duct-mounted
applications.
†† CRCBDIOX005A00 is an accessory that contains both 33ZC SENCO2
and 33ZCASPCO2 accessories.
ECONOMI$ER IV WITH OUTDOOR AIR
33ZCSENCO2†
33ZCASPCO2**
DRY BULB SENSOR
Accessories Required
None. The outdoor air dry bulb sensor
is factory installed.
CRTEMPSN002A00*
HH57AC078
and
CRENTDIF004A00*
33ZCSENCO2
O
and
sensor.
2
CRCBDIOX005A00††
R
Differential Dry Bulb Control
For differential dry bulb control the standard outdoor dry bulb
sensor is used in conjunction with an additional accessory dry
bulb sensor (part number CRTEMPSN002A00). The accessory
sensor must be mounted in the return airstream. (See Fig. 37.)
Wiring is provided in the EconoMi$er IV wiring harness. (See
Fig. 29.)
In this mode of operation, the outdoor-air temperature is
compared to the return-air temperature and the lower temperature
airstream is used for cooling. When using this mode of
changeover control, turn the enthalpy setpoint potentiometer fully
clockwise to the D setting. (See Fig. 35.)
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part number
HH57AC078) is required. Replace the standard outdoor dry bulb
temperature sensor with the accessory enthalpy sensor in the same
mounting location. (See Fig. 23 and 33.) When the outdoor air
enthalpy rises above the outdoor enthalpy changeover set point,
the outdoor-air damper moves to its minimum position. The
outdoor enthalpy changeover set point is set with the outdoor
enthalpy set point potentiometer on the EconoMi$er IV
controller. The set points are A, B, C, and D. (See Fig. 38.) The
factory-installed 620-ohm jumper must be in place across
terminals SR and SR+ on the EconoMi$er IV controller. (See Fig.
23 and 39.)
Differential Enthalphy Control
For differential enthalpy control, the EconoMi$er IV controller
usestwoenthalpysensors(HH57AC078and
CRENTDIF004A00), one in the outside air and one in the return
air duct. The EconoMi$er IV controller compares the outdoor air
enthalpy to the return air enthalpy to determine EconoMi$er IV
use. The controller selects the lower enthalpy air (return or
outdoor) for cooling. For example, when the outdoor air has a
lower enthalpy than the return air, the EconoMi$er IV opens to
bring in outdoor air for free cooling.
Replace the standard outside air dry bulb temperature sensor with
the accessory enthalpy sensor in the same mounting location.
(See Fig. 23.) Mount the return air enthalpy sensor in the return
air duct. (See Fig. 37.) Wiring is provided in the EconoMi$er IV
wiring harness. (See Fig. 29.) The outdoor enthalpy changeover
set point is set with the outdoor enthalpy set point potentiometer
on the EconoMi$er IV controller. When using this mode of
changeover control, turn the enthalpy setpoint potentiometer fully
clockwise to the D setting.
20
Page 21
FOR OCCUPANCY CONTROL
REPLACE JUMPER WITH
FIELD-SUPPLIED TIME CLOCK
8
7
581B,C
DCV— Demand Controlled Ventilation
IAQ — Indoor Air Quality
LA — Low Ambient Lockout Device
OAT — Outdoor-Air Temperature
POT— Potentiometer
RAT— Return-Air Temperature
1. 620 ohm, 1 watt 5% resistor should be removed only when using differential
enthalpy or dry bulb.
2. If a separate field-supplied 24 v transformer is used for the IAQ sensor power
supply, it cannot have the secondary of the transformer grounded.
3. For field-installed remote minimum position POT, remove black wire jumper
between P and P1 and set control minimum position POT to the minimum
position.
C06028
6000
5000
4000
3000
2000
1000
0
0.050.100.150.200.250.300.35
FLOW IN CUBIC FEET PER MINUTE (cfm)
STATIC PRESSURE (in. wg)
C06032
Fig. 32 --- Return--Air Pressure Drop
HH57AC078 ENTHALPY
SENSOR
C7400A1004
+
MOUNTING PLATE
C06361
Fig. 33 --- Enthalpy Sensor and Mounting Plate
21
Page 22
(
)+(TR
x
)
581B,C
SUPPLY AIR
TEMPERATURE
SENSOR
MOUNTING
LOCATION
SUPPLY AIR
TEMPERATURE
SENSOR
Fig. 34 --- Supply Air Sensor Location
C06033
Minimum Position Control
There is a minimum damper position potentiometer on the
EconoMi$er IV controller. (See Fig. 35.) The minimum damper
position maintains the minimum airflow into the building during
the occupied period.
When using demand ventilation, the minimum damper position
represents the minimum ventilation position for VOC (volatile
organic compound) ventilation requirements. The maximum
demand ventilation position is used for fully occupied ventilation.
When demand ventilation control is not being used, the minimum
position potentiometer should be used to set the occupied
ventilation position. The maximum demand ventilation position
should be turned fully clockwise.
Adjust the minimum position potentiometer to allow the
minimum amount of outdoor air, as required by local codes, to
enter the building. Make minimum position adjustments with at
least 10_F temperature difference between the outdoor and
return-air temperatures.
To determine the minimum position setting, perform the
following procedure:
1. Calculate the appropriate mixed air temperature using the
following formula:
C06034
Fig. 35 --- EconoMi$er IV Controller Potentiometer
and LED Locations
Indoor Air Quality (IAQ) Sensor Input
The IAQ input can be used for demand control ventilation control
based on the level of CO
measured in the space or return air
2
duct.
Mount the accessory IAQ sensor according to manufacturer
specifications. The IAQ sensor is wired to the AQ and AQ1
terminals of the controller. Adjust the DCV potentiometers to
correspond to the DCV voltage output of the indoor air quality
sensor at the user-determined set point. (See Fig. 40.)
If a separate field-supplied transformer is used to power the IAQ
sensor, the sensor must not be grounded or the EconoMi$er IV
control board will be damaged.
Exhaust Set Point Adjustment
The exhaust set point will determine when the exhaust fan runs
based on damper position (if accessory power exhaust is
installed). The set point is modified with the Exhaust Fan Set
Point (EXH SET) potentiometer. (See Fig. 35.) The set point
represents the damper position above which the exhaust fans will
be turned on. When there is a call for exhaust, the EconoMi$er IV
controller provides a 45 15 second delay before exhaust fan
activation to allow the dampers to open. This delay allows the
damper to reach the appropriate position to avoid unnecessary fan
overload.
OA
T
Ox
100
RA
100
=T
M
TO= Outdoor-Air Temperature
OA = Percent of Outdoor Air
= Retur n-Air Tem perat ure
T
R
RA = Percent of Return Air
= Mixed-Air Temperature
T
M
As an example, if local codes require 10% outdoor air during
occupied conditions, outdoor-air temperature is 60_F, a nd
return-air temperature is 75_F.
(60 x .10) + (75 x .90) = 73.5_F
2. Disconnect the supply air sensor from terminals T and T1.
3. Ensure that the factory-installed jumper is in place across
terminals P and P1. If remote damper positioning is being
used, make sure that the terminals are wired according to
Fig. 29 and that the minimum position potentiometer is
turned fully clockwise.
4. Connect 24 vac across terminals TR and TR1.
5. Carefully adjust the minimum position potentiometer
until the measured supply air temperature matches the
calculated value.
6. Reconnect the mixed air sensor to terminals T and T1.
Remote control of the EconoMi$er IV damper is desirable when
requiringadditionaltemporaryventilation.Ifa
field-supplied remote potentiometer (Honeywell part number
S963B1128) is wired to the EconoMi$er IV controller, the
minimum position of the damper can be controlled from a remote
location.
22
Page 23
To control the minimum damper position remotely, remove the
(
)+(TR
x
)
factory-installed jumper on the P and P1 terminals on the
EconoMi$er IV controller. Wire the field-supplied potentiometer
to the P and P1 terminals on the EconoMi$er IV controller. (See
Fig. 39.)
Damper Movement
Damper movement from full open to full closed (or vice versa)
1
/2minutes.
takes 2
Thermostats
The EconoMi$er IV control works with conventional thermostats
that have a Y1 (cool stage 1), Y2 (cool stage 2), W1 (heat stage
1), W2 (heat stage 2), and G (fan). The EconoMi$er IV control
does not support space temperature sensors. Connections are
made at the thermostat terminal connection board located in the
main control box.
19
LED ON
18
17
mA
14
13
12
11
10
16
15
9
40
45
LED OFF
50
D
LED ON
C
LED OFF
60
55
65
DEGREES FAHRENHEIT
70
LED ON
LED OFF
75
B
LED ON
A
LED OFF
100
90
95
85
80
C06035
Fig. 36 --- Outside Air Temperature
Changeover Set Points
ECONOMI$ER IV
CONTROLLER
ECONOMI$ER IV
Occupancy Control
The factory default configuration for the EconoMi$er IV control
is occupied mode. Occupied mode is provided by the black
jumper from terminal TR to terminal N. When unoccupied mode
is desired, install a field-supplied timeclock function in place of
the jumper between TR and N. (See Fig. 29.) When the timeclock
contacts are closed, the EconoMi$er IV control will be in
occupied mode. When the timeclock contacts are open (removing
the 24-v signal from terminal N), the EconoMi$er IV will be in
unoccupied mode.
Typically the maximum ventilation rate will be about 5 to 10%
more than the typical cfm required per person, using normal
outside air design criteria.
Demand Controlled Ventilation (DCV)
When using the EconoMi$er IV for demand controlled
ventilation, there are some equipment selection criteria which
should be considered. When selecting the heat capacity and cool
capacity of the equipment, the maximum ventilation rate must be
evaluated for design conditions. The maximum damper position
must be calculated to provide the desired fresh air.
A proportional anticipatory strategy should be taken with the
following conditions: a zone with a large area, varied occupancy,
and equipment that cannot exceed the required ventilation rate at
design conditions. Exceeding the required ventilation rate means
the equipment can condition air at a maximum ventilation rate
that is greater than the required ventilation rate for maximum
occupancy. A proportional-anticipatory strategy will cause the
fresh air supplied to increase as the room CO
even though the CO
the CO
level reaches the set point, the damper will be at
2
set point has not been reached. By the time
2
level increases
2
maximum ventilation and should maintain the set point.
In order to have the CO
sensor control the economizer damper in
2
this manner, first determine the damper voltage output for
minimum or base ventilation. Base ventilation is the ventilation
required to remove contaminants during unoccupied periods. The
following equation may be used to determine the percent of
outside-air entering the building for a given damper position. For
best results there should be at least a 10 degree difference in
outside and return-air temperatures.
581B,C
GROMMET
RETURN AIR TEMPERATURE
SENSOR
RETURN DUCT
(FIELD-PROVIDED)
Fig. 37 --- Return Air Temperature or Enthalpy
Sensor Mounting Location
C06036
OA
T
Ox
100
RA
100
=T
M
TO= Outdoor-Air Temperature
OA = Percent of Outdoor Air
= Retur n-Air Tem perat ure
T
R
RA = Percent of Return Air
= Mixed-Air Temperature
T
M
Once base ventilation has been determined, set the minimum
damper position potentiometer to the correct position.
23
Page 24
581B,C
CONTROL
CURVE
1
2
1
4
A
B
C
D
1
CONTROL POINT
APPROX.
2
8
1
6
deg. F (deg. C)
AT 50% RH
73 (23)
70 (21)
67 (19)
63 (17)
4
3
32
30
28
ENTHALPY BTU PER POUND DRY AIR
26
4
2
2
2
0
55
(13)
50
C
(10)
45
D
(7)
40
(4)
35
(2)
3
(16)
B
85
(29)90(32)95(35)
46
4
4
42
40
8
3
6
70
(21)
0
0
1
65
(18)
60
A
80
(27)
75
(24)
0
9
80
70
0
6
50
0
4
100
105
(41)
110
(43)
(38)
RELATIVE HUMIDITY (%)
30
20
0
1
35
40
45
50
55
60
(2)
(4)
(10)
(7)
(13)
(16)
65
(18)
APPROXIMATE DRY BULB TEMPERATURE--degrees F (degrees C)
Fig. 38 --- Enthalpy Changeover Set Points
The same equation can be used to determine the occupied or
maximum ventilation rate to the building. For example, an output
of 3.6 volts to the actuator provides a base ventilation rate of 5%
and an output of 6.7 volts provides the maximum ventilation rate
of 20% (or base plus 15 cfm per person). Use Fig. 37 to
determine the maximum setting of the CO
sensor. For example,
2
a 1100 ppm set point relates to a 15 cfm per person design. Use
the 1100 ppm curve on Fig. 40 to find the point when the CO
sensor output will be 6.7 volts. Line up the point on the graph
with the left side of the chart to determine that the range
configuration for the CO
sensor should be 1800 ppm. The
2
EconoMi$er IV controller will output the 6.7 volts from the CO
sensor to the actuator when the CO2concentration in the space is
at 1100 ppm. The DCV set point may be left at 2 volts since the
sensor voltage will be ignored by the EconoMi$er IV
CO
2
controller until it rises above the 3.6 volt setting of the minimum
position potentiometer.
Once the fully occupied damper position has been determined, set
the maximum damper demand control ventilation potentiometer
to this position. Do not set to the maximum position as this can
result in over-ventilation to the space and potential high-humidity
levels.
A
B
C
70
(21)
D
75
(24)
80
(27)
(29)90(32)95(35)
105
85
100
(38)
(41)
110
(43)
HIGH LIMIT
CURVE
C06037
TR1
TR
24
24 Vac
Vac
COM
HOT
+
12
3
EF1
EF
_
5
4
2V10V
EXH
Open
2V10V
DCV
2V10V
Free
Cool
B
A
EXH
DCV
DCV
C
D
Min
Pos
Max
Set
Set
N1
N
P1
P
T1
2
2
T
AQ1
AQ
SO+
SO
SR+
SR
C06038
Fig. 39 --- EconoMi$er IV Control
24
Page 25
6000
5000
CO SENSOR MAX RANGE SETTING
2
4000
3000
2000
1000
RANGE CONFIGURATION (ppm)
0
2345678
DAMPER VOLTAGE FOR MAX VENTILATION RATE
Fig. 40 --- CO2Sensor Maximum Range Setting
Sensor Configuration
CO
2
The CO
sensor has preset standard voltage settings that can be
2
selected anytime after the sensor is powered up. (See Table 7.)
Use setting 1 or 2 for Bryant equipment. (See Table 7.)
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to select the preset number. (See
Tab le 7.)
4. Press Enter to lock in the selection.
5. Press Mode to exit and resume normal operation.
The custom settings of the CO
sensor can be changed anytime
2
after the sensor is energized. Follow the steps below to change the
non-standard settings:
1. Press Clear and Mode buttons. Hold at least 5 seconds
until the sensor enters the Edit mode.
2. Press Mode twice. The STDSET Menu will appear.
3. Use the Up/Down button to toggle to the NONSTD menu
and press Enter.
4. Use the Up/Down button to toggle through each of the
nine variables, starting with Altitude, until the desired
setting is reached.
5. Press Mode to move through the variables.
6. Press Enter to lock in the selection, then press Mode to
continue to the next variable.
Dehumidification of Fresh Air with DCV Control
Information from ASHRAE indicates that the largest humidity
load on any zone is the fresh air introduced. For some
applications, a device such as an energy recovery unit can be
added to reduce the moisture content of the fresh air being
brought into the building when the enthalpy is high. In most
cases, the normal heating and cooling processes are more than
adequate to remove the humidity loads for most commercial
applications.
If normal rooftop heating and cooling operation is not adequate
for the outdoor humidity level, an energy recovery unit and/or a
dehumidification option should be considered.
800 ppm
900 ppm
1000 ppm
1100 ppm
Step 9 —Adjust Evaporator--Fan Speed
Adjust evaporator-fan speed to meet jobsite conditions.
Tables 8 and 9 show fan rpm at motor pulley settings. Tables 10
and 14 show maximum amp draw of belt-drive motor. Table 13
shows sound data. Refer to Tables 15--34 for performance data.
See Table 11 for accessory static pressure drop. See Fig. 41 for
the Perfect Humidity system static pressure drops.
Belt Drive
Fan motor pulleys are factory set for speed shown in Table 1 or 2.
Check pulley alignment and belt tension prior to start-up.
To change fan speed:
NOTE: Once the required flange position is determined for the
correct blower rpm, it is recommended (bu not required) that the
variable pitch pulley be replaced with a corresponding size fixed
sheave pulley.
To align fan and motor pulleys, loosen fan pulley setscrews and
slide fan pulley along fan shaft. Make angular alignment by
loosening motor from mounting.
Additional motor and fan alignment, as well as angular alignment
can be made by loosening the four motor mounting bolts from
the mounting plate.
To adjust belt tension:
25
Motors
1. Shut off the unit power supply and tag disconnect.
2. Loosen the belt by loosening the fan motor mounting nuts.
(See Fig. 42.)
3. Loosen movable pulley flange setscrew. (See Fig. 43.)
4. Screw movable flange toward fixed flange to increase
speed and away from fixed flange to decrease speed.
Increasing fan speed increases load on motor. Do not
exceed maximum speed specified in Table 1 or 2.
5. Set movable flange at nearest keyway of pulley hub and
tighten setscrew. (See T able 1 or 2 for speed change for
each full turn of pulley flange.)
6. Adjust belt tension and align fan and motor pulleys per
guidance below.
1. Loosen the two motor mounting nuts as shown in Fig. 42.
Some models may have a third mounting nut located on
the opposite side of the fan motor mounting plate.
2. Slide motor mounting plate away from fan scroll for
proper belt tension (
1
/2-in.deflectionwith8to10lbof
force) and tighten mounting nuts.
3. Adjust lock bolt and nut on mounting plate to secure
motor in fixed position.
C06039
581B,C
Page 26
Table 7—CO
BuildingControlSystem
Sensor Standard Settings
2
SETTINGEQUIPMENTOUTPUT
1
Interface w/Standard
2
Building Control System
3
4
5
Economizer
6
7
Health & SafetyProportional—
8
Parkin g/Air Intakes/
9
581B,C
LEGEND
ppm — Parts Per Million
Loading Docks
0.35
0.3
0.25
VENTILATION
RATE
(cfm/Person)
ProportionalAny
ProportionalAny
ExponentialAn y
Proportional15
Proportional20
Exponential15
Exponential20
Proportional—
ANALOG
OUTPUT
0-10V
4-20 mA
2-10V
7-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
0-10V
4-20 mA
CO
CONTROL RANGE
2
(ppm)
0-2000100050
0-2000100050
0-2000110050
0-1100110050
0- 90090050
0-1100110050
0- 90090050
0-99995000500
0-200070050
OPTIONAL
RELAY SETPOINT
(ppm)
RELAY
HYSTERESIS
(ppm)
DELTA P IN. WG
0.2
0.15
0.1
0.05
4&5ton
6 ton
3 ton
0
0
1000
2000
3000
4000
5000
6000
C06133
Fig. 41 --- Perfect Humidityt Adaptive Dehumidification System Static Pressure Drop (in. wg)
Fig. 42 --- Belt Drive Motor Mounting
C06134
Fig. 43 --- Indoor--Fan Pulley Adjustment
C06041
26
Page 27
Table 8—581B and 581C Fan Rpm at Motor Pulley Setting With Standard Motor*
Three
1.20100
0
Three
1.20100
0
Three
2.40212
0
072
Three
2.40212
0
036
Three
2.40212
0
048
Three
2.40212
0
060
Three
2.90261
5
072
Three
2.90261
5
UNIT
024
036
048
060
072
*Approximate fan rpm shown (standard motor/drive).
Table 10—Evaporator-Fan Motor Data — Standard Motor
UNIT
581B
581C
024
036
048
060
072
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the
fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
Table 12—Evaporator-Fan Motor Data — High-Static Motors
UNIT
581B
036
048
060
072
LEGEND
Bhp — Brake Horsepower
*Extensive motor and electrical testing on these units ensures that the full horsepower and watts range of the motors can be utilized with confidence. Using the
fan motors up to the ratings shown in this table will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
UNIT
PHASE
MAXIMUM
CONTINUOUS BHP*
MAXIMUM
OPERATING WATTS*
Three2.402120
Three2.402120
Three2.902615
Three2.902615
UNIT VOLTAGE
208/2306.7
4603.0
5753.0
208/2306.7
4603.0
5753.0
208/2308.6
4603.9
5753.9
208/2308.6
4603.9
5753.9
MAXIMUM
AMP DRAW
27
Page 28
Table 13—581B Outdoor Sound Power (Total Unit)
UNITRATIN
G
WEIGHTE
D
(Cfm)
ARI
UNIT
036, 048
060, 072
LEGEND
ARI --- Air Conditioning and Refrigeration Institute
1. Values include losses for filters, unit casing, and wet coils. See Table 11 and Fig. 38 for accessory/FIOP static pressure information.
2. Extensive motor and electrical testing on these units ensures that the full range of the motor can be utilized with confidence. Using the
fan motors up to the ratings shown will not result in nuisance tripping or premature motor failure. Unit warranty will not be affected.
See Tables 8 and 9 for additional information.
3. Use of a field-supplied motor may affect wire sizing. Contact your Bryant representative to verify.
4. Interpolation is permissible. Do not extrapolate.
Table 15—Fan Performance 581C 024 — Vertical Discharge Units; Standard Motor (Belt Drive)**
1. Grey cells indicate field-supplied drive is required.
2. Maximum continuous bhp is 2.90.
3. See general fan performance notes.
LEGEND
Bhp — Brake Horsepower
Watts — Input Watts to Motor
*Motor drive range: 1300 t o 1685 rpm. All other rpms require field-supplied drive.
40
Page 41
PRE-START-UP
!
FIRE, EXPLOSION, ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury, death and/or property damage:
1. Follow recognized safety practices and wear
protectivegoggles when checking or servicing a
refrigerant system.
2.Do not operate the compressor or provide any
electric power to the unit unless the compressor terminal
cover is in place and secured.
3. Do not remove the compressor terminal cover until
all electrical sources are disconnected and tagged with
lockout tags.
4. Relieve all pressure from the system before touching
or disturbing anything inside the terminal box if a
refrigerant leak is suspected around the compressor
terminals. Use accepted methods to recover the
refrigerant.
5. Never attempt to repair a soldered connection while
the refrigerant system is under pressure.
6. Do not use a torch to remove any component. The
system contains oil and refrigerant under pressure. To
remove a component, wear protective goggles and
proceed as follows:
a. Shut off electrical power to the unit and tag
b. Recover refrigerant to relieve all pressure
c. Cut component connection tubing with a
d. Carefully unsweat the remaining tubing
Proceed as follows to inspect and prepare the unit for initial
start-up:
1. Remove all access panels.
2. Read and follow instructions on all WARNING,
CAUTION, and INFORMATION labels attached to, or
shipped with, unit.
3. Make the following inspections:
a. Inspect for shipping and handling damages such as
broken lines, loose parts, or disconnected wires, etc.
b. Inspectfor oil at all refrigerant tubing connectionsand on
unit base. Detecting oil generally indicates a refrigerant
leak. Leak-test all refrigerant tubing connections using
electronic leak detector, halide torch, or liquid-soap
solution.
c. Inspect all field-wiring and factory-wiring connections.
Be sure that connectionsarecompleted and tight. Be sure
that wires are not in contact with refrigerant tubing or
sharp edges.
d. Inspect coil fins. If damaged during shipping and
handling, carefully straighten fins with a fin comb.
4. Verify the following conditions:
a. Make sure that condenser-fan blade are correctly
positioned in fan orifice. See Condenser-Fan Adjustment
section for more details.
b. Make sure that air filter(s) is in place.
WARNING
disconnect.
from the system using both high-pressure
and low-pressure ports.
tubing cutter, and remove the component
from the unit.
stubs when necessary. Oil can ignite when
exposed to a torch flame.
c. Make sure that condensate drain trap is filled with water
to ensure proper drainage.
d. Make sure that all tools and miscellaneous loose parts
have been removed.
START-UP
Unit Preparation
Make sure that the unit has been installed in accordance with
installation instructions and applicable codes.
Gas Piping
Check gas piping for leaks.
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
Disconnect gas piping from unit when leak testing at
pressure greater than
psig will cause gas valve damage resulting in hazardous
condition. If gas valve is subjected to pressure greater
1
than
/2psig, it must be replaced before use. When
pressure testing field-supplied gas piping at pressures of
1
/2psig or less, a unit connected to such piping must be
isolated by manually closing the gas valve.
Return--Air Filters
Make sure the correct filters are installed in the unit (See Table 1
or 2). Do not operate the unit without return-air filters.
Outdoor--Air Inlet Screens
Outdoor-air inlet screen(s) must be in place before operating the
unit.
Compressor Mounting
Compressors are internally spring mounted. Do not loosen or
remove the compressor holddown bolts.
Internal Wiring
Check all electrical connections in unit control boxes; tighten
them as required.
Refrigerant Service Ports
Each unit system has 4 Schrader--type service ports: one on the
suction line, one on the liquid line, and 2 on the compressor
discharge line. Be sure that caps on the ports are tight. Two
additional Schrader valves are located under the high-- pressure
and low--pressure switches, respectively.
High Flow Refrigerant Valves
Two high flow valves are located on the hot gas tube coming out
of the compressor and the suction tube going into the compressor.
Large black plastic caps identify these valves. These valves have
O-- rings inside which screw the cap onto a brass body to prevent
leaks. No field access to these valves is available at this time.
Ensure the plastic caps remain on the valves and are tight or the
possibility of refrigerant leakage could occur.
WARNING
1
/2psig. Pressures greater than1/
2
581B,C
41
Page 42
Compressor Rotation
A
150,000BTUH
V
A
Natural
Liqui
d
Natural
Liqui
d
Gas
Propane
Gas
Propane
Orifice
Orifice
Orifice
Orifice
V
A
On 3-phase units be certain that the compressor is rotating in the
proper direction. To determine whether or not compressor is
rotating in the proper direction:
1. Connect the service gauges to suction and discharge
pressure fittings.
2. Energize the compressor.
3. The suction pressure should drop and the discharge
pressure should rise, as is normal on any start-up.
If the suction pressure does not drop and the discharge pressure
does not rise to normal levels:
1. Note that the indoor fan (006 and 007 three-phase units
only) is probably also rotating in the wrong direction.
2. Turn off power to the unit and tag disconnect.
3. Reverse any two of the unit power leads.
4. Turn on power to the unit and energize the compressor.
The suction and discharge pressure levels should now move to
their normal start-up levels.
581B,C
NOTE: When the compressor is rotating in the wrong direction,
the unit makes more noise and does not provide cooling.
Cooling
Set the space thermostat to the OFF position. Set the system
selector switch at COOL position and the fan switch at AUTO
position. Adjust the thermostat to a setting below room
temperature. The compressor starts when contactor closes.
Check the unit charge. Refer to Refrigerant Charge section.
Reset the thermostat at a position above room temperature. The
compressor will shut off. Evaporator fan will shut off after a
30--second delay.
To Shut Off Unit -- Set the system selector switch at OFF
position. Resetting the thermostat at a position above room
temperature shuts off the unit temporarily until the space
temperature exceeds the thermostat setting. Units are equipped
with a Cycle-LOC protection device. The unit shuts down on
any safety trip and remains off; an indicator light on the
thermostat comes on. Check the reason for the safety trip.
Main Burners
Main burners are factory set and should require no adjustment.
TO CHECK ignition of main burners and heating controls, move
thermostat set point above room temperature and verify that the
burners light and evaporator fan is energized. Check heating
effect, then lower the thermostat setting below the room
temperature and verify that the burners and evaporator fan turn
off.
Refer to Tables 35 and 36 for the correct orifice to use at high
altitudes.
Table 35—Altitude Compensation*
581B 036--072, 581C 024-- 060 Standard Units
72,000 AND
115,000 BTUH
ELE
TION
(ft)
0-2,000
2,000
3,000
4,000
5,000
6,000
7,000
8,000
9,000
10,000
11,000
12,000
13,000
14,000
*As the height above sea level increases, there is less oxygen per cubic
foot of air. Therefore, heat input rate should be reduced at higher altitudes.
†Orifices available through your Bryant distributor.
1. Purge gas supply line of air by opening union ahead of the
gas valve. If gas odor is detected, tighten union and wait 5
minutes before proceeding.
2. Turn on electrical supply and manual gas valve.
3. Set system switch selector at HEAT position and fan
switch at AUTO or ON position. Set heating temperature
lever above room temperature.
4. The induced-draft motor will start.
5. After a call for heating, the main burners should light
within 5 seconds. If the burner does not light, then there is
a 22-second delay before another 5-second try. If the
burner still does not light, the time delay is repeated. If the
burner does not light within 15 minutes, there is a lockout.
To reset the control, break the 24 v power to W1.
6. The evaporator-fan motor will turn on 45 seconds after
burner ignition.
7. The evaporator-fan motor will turn off in 45 seconds after
the thermostat temperature is satisfied.
8. Adjust airflow to obtain a temperature rise within the
range specified on the unit nameplate.
NOTE: The default value for the evaporator-fan motor on/off
delay is 45 seconds. The Integrated Gas Unit Controller (IGC)
modifies this value when abnormal limit switch cycles occur.
Based upon unit operating conditions, the on delay can be
reduced to 0 seconds and the off delay can be extended to180
seconds. When one flash of the LED (light-emitting diode) is
observed, the evaporator-fan on/off delay has been modified.
If the limit switch trips at the start of the heating cycle during the
evaporator on delay, the time period of the on delay for the next
cycle will be 5 seconds less than the time at which the switch
tripped. (Example: If the limit switch trips at 30 seconds, the
evaporator-fan on delay for the next cycle will occur at 25
seconds.) To prevent short-cycling, a 5-second reduction will
only occur if a minimum of 10 minutes has elapsed since the last
call for heating.
The evaporator-fan off delay can also be modified. Once the call
for heating has ended, there is a 10-minute period during which
the modification can occur. If the limit switch trips during this
period, the evaporator-fan off delay will increase by 15 seconds.
A maximum of 9 trips can occur, extending the evaporator-fan off
delay to 180 seconds.
To restore the original default value, reset the power to the unit.
To Shut Off Unit —Set system selector switch at offposition.
Resetting heating selector lever below room temperature will
temporarily shut unit off until space temperature falls below
thermostat setting.
Safety Relief
A soft solder joint at the suction line fitting provides pressure
relief under abnormal temperature and pressure conditions.
Ventilation (Continuous Fan)
Set fan and system selector switches at ON and OFF positions,
respectively. Evaporator fan operates continuously to provide
constant air circulation. When the evaporator--fan selector switch
is turned to the OFF position, there is a 30--second delay before
the fan turns off.
Operating Sequence
Cooling -- Units Without Economizer
When thermostat calls for cooling, terminals G and Y1 are
energized. The indoor-fan contactor (IFC), reversing valve
solenoid (RVS) and compressor contactor are energized and
indoor-fan motor, compressor, and outdoor fan starts. The
outdoor fan motor runs continuously while unit is cooling.
Heating -- Units Without
When the thermostat calls for heating, terminal W1 is energized.
To prevent thermostat short--cycling, the unit is locked into the
Heating mode for at least 1 minute when W1 is energized. The
induced--draft motor is energized and the burner ignition
sequence begins. The indoor (evaporator) fan motor (IFM) is
energized 45 seconds after a flame is ignited. On units equipped
for two stages of heat, when additional heat is needed, W2 is
energized and the high--fire solenoid on the main gas valve
(MGV) is energized. When the thermostat is satisfied and W1 is
deenergized, the IFM stops after a 45--second time--off delay.
Cooling -- Units With Economi$er
When free cooling is not available, the compressors will be
controlled by the zone thermostat. When free cooling is available,
the outdoor-air damper is modulated by the EconoMi$er IV
control to provide a 50_ to 55_F supply-air temperature into the
zone. As the supply-air temperature fluctuates above 55_ or
below 50_F, the dampers will be modulated (open or close) to
bring the supply-air temperature back within the set point limits.
Integrated EconoMi$er IV operation on single-stage units
requires a 2-stage thermostat (Y1 and Y2).
For EconoMi$er IV operation, there must be a thermostat call for
the fan (G). This will move the damper to its minimum position
during the occupied mode.
If the increase in cooling capacity causes the supply--air
temperature to drop below 45_F, then the outdoor-- air damper
position will be fully closed. If the supply --air temperature
continues to fall, the outdoor--air damper will close. Control
returns to normal once the supply--air temperature rises above
48_F.
If optional power exhaust is installed, as the outdoor--air damper
opens and closes, the power exhaust fans will be energized and
deenergized.
If field--installed accessory CO
EconoMi$er IV control, a demand controlled ventilation strategy
will begin to operate. As the CO
above the CO
will be increased proportionally. As the CO
because of the increase in fresh air, the outdoor--air damper will
be proportionally closed. Damper position will follow the higher
demand condition from DCV mode or free cooling mode.
Damper movement from full closed to full open (or vice versa)
will take between 1--1/2 and 2--1/2 minutes.
If free cooling can be used as determined from the appropriate
changeover command (switch, dry bulb, enthalpy curve,
differential dry bulb, or differential enthalpy), a call for cooling
(Y1 closes at the thermostat) will cause the control to modulate
the dampers open to maintain the supply air temperature set point
at 50_ to 55_F.
As the supply air temperature drops below the set point range of
50_ to 55_F, the control will modulate the outdoor--air dampers
closed to maintain the proper supply--air temperature.
set point, the minimum position of the damper
2
Economizer
IV
sensors are connected to the
2
level in the zone increases
2
level decreases
2
581B,C
43
Page 44
Heating -- Units With Economi$er
IV
When the room temperature calls for heat, the heating controls are
energized as described in the Heating, Units Without Economizer
section. During the occupied mode, whenever the indoor fan
contactor is energized, the economizer damper moves to the
minimum position.
Units With Perfect Humidity
Dehumidification
System
Adaptive
Normal Design Operation
When the rooftop operates under the normal sequence of
operation, the compressors will cycle to maintain indoor
conditions. (See Fig. 44.)
The Perfect Humidity adaptive dehumidification system includes
a factory-installed Motormaster low ambient control to keep the
head and suction pressure high, allowing normal design cooling
mode operation down to 0F.
Subcooling Mode
When subcooling mode is initiated, this will energize (close) the
liquid line solenoid valve (LLSV) forcing the hot liquid
581B,C
refrigerant to enter into the subcooling coil. (See Fig. 45.)
As the hot liquid refrigerant passes through the subcooling/ reheat
dehumidification coil, it is exposed to the cold supply airflow
coming through the evaporator coil. The liquid is further
subcooled to a temperature approaching the evaporator
leaving-air temperature. The liquid then enters a thermostatic
expansion valve (TXV) where the liquid drops to a lower
pressure. The TXV does not have a pressure drop great enough to
change the liquid to a 2-phase fluid, so the liquid then enters the
Acutrol device at the evaporator coil.
The liquid enters the evaporator coil at a temperature lower than
in standard cooling operation. This lower temperature increases
the latent capacity of the rooftop unit. The refrigerant passes
through the evaporator and is turned into a vapor. The air passing
over the evaporator coil will become colder than during normal
operation. However, as this same air passes over the subcooling
coil, it will be slightly warmed, partially reheating the air.
Subcooling mode operates only when the outside air
temperature is warmer than 40_F. A factory-installed temperature
switch located in the condenser section will lock out subcooling
mode when the outside temperature is cooler than 40_F.
The scroll compressors are equipped with crankcase heaters to
provide protection for the compressors due to the additional
refrigerant charge required by the subcooling/reheat coil.
When in subcooling mode, there is a slight decrease in system
total gross capacity (5% less), a lower gross sensible capacity
(20% less), and a greatly increased latent capacity (up to 40%
more).
Hot Gas Reheat Mode
When the humidity levels in the space require humidity control, a
hot gas solenoid valve (specific to hot gas reheat mode only) will
open to bypass a portion of hot gas refrigerant around the
condenser coil. (See Fig. 46.)
This hot gas will mix with liquid refrigerant leaving the
condensercoilandflowtothesubcooling/reheat
dehumidification coil. Now the conditioned air coming off the
evaporator will be cooled and dehumidified, but will be warmed
to neutral conditions (72_Fto75_F) by the subcooling/reheat
dehumidification coil.
C06135
Fig. 44 --- Perfect Humidityt Normal
Design Cooling Operation
C06136
Fig. 45 --- Perfect Humidity Subcooling
Mode Operation
C06137
Fig. 46 --- Perfect Humidity Hot Gas
Reheat Mode Operation
See Table 37 for the Perfect Humidity adaptive dehumidification
system sequence of operation.
44
Page 45
Table 37—Perfect Humidity Adaptive Dehumidification System Sequence of Operation and
System Response — Single Compressor Unit (581C 024--060, 581B 036-- 072)
THERMOSTAT INPUTECONOMIZER FUNCTION581B,C UNIT OPERATION
HY1Y2OAT. < Economizer Set PointEconomizerComp. 1Subcooling ModeHot Gas Reheat Mode
Off——
OnOnOnNoOffOnYesNo
OnOnOffNoOffOnYesNo
OnOnOnYesOnOnYesNo
OnOnOffYesOnOnNoYe s
OnOffOffNoOffOnNoYes
NOTE: On a th ermostat call for W1, all cooling and dehumidification will be off.
LEGEND
OAT --- Outdoor Air Temperature
Normal Operation
The net effect of the rooftop when in hot gas reheat mode is to
provide nearly all latent capacity removal from the space when
sensible loads diminish (when outdoor temperature conditions are
moderate). When in hot gas reheat mode, the unit will operate to
provide mostly latent capacity and extremely low sensible heat
ratio capability.
Similar to the subcooling mode of operation, hot gas reheat mode
operates only when the outside air temperature is warmer than
40_F. Below this temperature, a factory installed outside air
temperature switch will lockout this mode of operation.
SERVICE
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could cause personal
injury or death.
When sevicing unit, shut off all electrical power to unit
and install lockout tag.
Step 1 —Cleaning
Inspect unit interior at the beginning of heating and cooling
season and as operating conditions require.
Evaporator
1. Turn unit power off, tag disconnect. Remove evaporator
coil access panel.
2. If economizer or two-position damper is installed, remove
economizerbydisconnectingMolexplugand
removing mounting screws.
3. Slide filters out of unit.
4. Clean coil using a commercial coil cleaner or dishwasher
detergent in a pressurized spray canister. W ash both sides
of coil and flush with clean water. For best results,
back-flush toward return-air section to remove foreign
material. Flush condensate pan after completion.
5. Reinstall economizer and filters.
6. Reconnect wiring.
7. Replace access panels.
Condenser
Inspect coil monthly. Clean condenser coil annually, and as
required by location and outdoor air conditions.
Coil
WARNING
Coil
One--Row Coils
Wash coil with commercial coil cleaner. It is not necessary to
remove top panel.
2-Row Coils
Clean coil as follows:
1. Turn off unit power, tag disconnect.
2. Remove top panel screws on condenser end of unit.
3. Remove condenser coil corner post. (See Fig. 47.) To hold
top panel open, place coil corner post between top panel
and center post. (See Fig. 48.)
C06044
Fig. 47 --- Cleaning Condenser Coil
581B,C
45
C06045
Fig. 48 --- Propping Up Top Panel
Page 46
581B,C
4. Remove screws securing coil to compressor plate and
5. Remove fastener holding coil sections together at return
6. Use a water hose or other suitable equipment to flush
7. Secure inner and outer coil rows together with a
8. Reposition the outer coil section and remove the coil
Condensate
Check and clean each year at the start of the cooling season. In
winter, keep the drain dry or protect it against freeze-up.
Filters
Clean or replace at the start of each heating and cooling season, or
more often if operating conditions require it. Replacement filters
must be the same dimensions as the original filters.
Outdoor--Air Inlet Scr
Clean the screens with steam or hot water and a mild detergent.
Do not use disposable filters in place of screens.
Fig. 49 --- Separating Coil Sections
compressor access panel.
end of condenser coil. Carefully separate the outer coil
section 3 to 4 in. from the inner coil section. (See Fig. 49.)
down between the 2 coil sections to remove dirt and
debris. Clean the outer surfaces with a stiff brush in the
normal manner.
field-supplied fastener.
corner post from between the top panel and center post.
Reinstall the coil corner post and replace all screws.
Drain
eens
Step 2 —Lubrication
Compressor
The compressor is charged with the correct amount of oil at the
factory.
Fan Motor
Fan motor bearings are permanently lubricated. No further
lubrication is required.No lubrication of condenser-fan or
evaporator-fan motors is required.
Bearings
Step 3 —Condenser--Fan Adjustment
Shut off unit power supply. Remove condenser-fan assembly
(grille, motor, motor cover, and fan) and loosen fan hub
setscrews. Adjust fan height as shown in Fig. 50. Tighten
setscrews and replace condenser-fan assembly.
C06046
UNIT
024-060 and 072 (208/230 v)
072 (460 v)
Fig. 50 --- Condenser--Fan Adjustment
FAN HEIGHT (in.) - A
2.75
3.50
C06138
Step 4 —EconoMi$er IV Adjustment
Refer to Optional EconoMi$er IV section.
Step 5 —Evaporator Fan Belt Inspection
Check condition of evaporator belt or tension during heating and
cooling inspections or as conditions require. Replace belt or
adjust as necessary.
Step 6 —High Pressure Switch
The high-pressure switch contains a Schrader core depressor, and
is located on the compressor hot gas line. This switch opens at
428 psig and closes at 320 psig. No adjustments are necessary.
Step 7 —Loss--of--Charge Switch
The loss-of-charge switch contains a Schrader core depressor, and
is located on the compressor liquid line. This switch opens at 7
psig and closes at 22 psig. No adjustments are necessary.
Step 8 —Freeze--Stat
The freeze-stat is a bimetal temperature-sensing switch that is
located on the “hair-pin” end of theevaporator coil. The switch
protects the evaporator coil from freeze-up due to lack of airflow.
The switch opens at 30_F and closes at 45_F. No adj u stm ents are
necessary.
Step 9 —Refrigerant Charge
Amount of refrigerant charge is listed on unit nameplate (also
refer to Table 1). Refer to HVAC Servicing Procedures literature
available at your local distributor and the following procedures.
Unit panels must be in place when unit is operating during
charging procedure. Unit must operate a minimum of 10 minutes
before checking or adjusting refrigerant charge.
An accurate superheat, thermocouple-type or thermistor-type
thermometer, and a gauge manifold are required when using the
superheat charging method for evaluating the unit charge. Do not
use mercury or small dial-type thermometers because they are not
adequate for this type of measurement.
Charge
No
Use standard evacuating techniques. After evacuating system to
500 microns, weigh in the specified amount of refrigerant. (Refer
to Table 1 or 2 and unit information plate.)
46
Page 47
Low Charge
Cooling
Using Cooling Charging Charts, Fig. 51--54 and 59--62, vary
refrigerant until the conditions of the charts are met. Note the
charging charts are different from type normally used. Charts are
based on charging the units to the correct superheat for the
various operating conditions. Accurate pressure gauge and
temperature sensing device are required. Connect the pressure
gauge to the service port on the suction line. Mount the
temperature sensing device on the suction line and insulate it so
that outdoor ambient temperature does not affect the reading.
Indoor-air cfm must be within the normal operating range of the
unit.
Perfect Humidity
System Charging
The system charge for units with the Perfect Humidity adaptive
dehumidification system is greater than that of the standard unit
alone. The charge for units with this option is indicated on the
unit nameplate drawing. Also refer to Fig. 55-- 58. To charge
systems using the Perfect Humidity adaptive dehumidification
system, fully evacuate, recover, and recharge the system to the
nameplate specified charge level. To check or adjust refrigerant
charge on systems using the Perfect Humidity adaptive
dehumidification system, charge per Fig. 55--58.
NOTE: When using the charging charts, it is important that only
the subcooling/reheat dehumidification coil liquid line solenoid
valve be energized. The subcooling/reheat dehumidification coil
liquid line solenoid valve MUST be energized to use the charging
charts and the outdoor motor speed controller jumpered to run the
fanatfullspeed.
The charts reference a liquid pressure (psig) and temperature at a
point between the condenser coil and the subcooling/reheat
dehumidification coil. A tap is provided on the unit to measure
liquid pressure entering the subcooling/reheat dehumidification
coil.
IMPORTANT: The subcooling mode charging charts (Fig.
55--58) are to be used ONLY with units having the Perfect
Humidity adaptive dehumidification system. DO NOT use
standard charge (Fig. 51--54 and 59--62) for units with Perfect
Humidity system, and DO NOT use Fig. 55--58 for standard
units.
Take the outdoor ambient temperature and read the suction
pressure gauge. Refer to charts to determine what suction
temperature should be. If suction temperature is high, add
refrigerant. If suction temperature is low, carefully recover some
of the charge. Recheck the suction pressure as charge is adjusted.
NOTE: When using the charging charts, it is important that only
the subcooling/reheat dehumidification coil liquid line solenoid
valve be energized. The subcooling/reheat dehumidification coil
liquid line solenoid valve MUST be energized to use the charging
charts and the outdoor motor speed controller jumpered to run the
fanatfullspeed.
Step 10 —Flue Gas Passageways
To inspect the flue collector box and upper areas of the heat
exchanger:
1. Remove the combustion blower wheel and motor
assembly according to directions in Combustion-Air
Blower section below.
2. Remove the 3 screws holding the blower housing to the
flue cover.
3. Remove the flue cover to inspect the heat exchanger.
4. Clean all surfaces as required using a wire brush.
Clean periodically to ensure proper airflow and heating
efficiency. Inspect blower wheel every fall and periodically
during heating season. For the first heating season, inspect blower
wheel bimonthly to determine proper cleaning frequency.
To inspect blower wheel, remove draft hood and screen. Shine a
flashlight into opening to inspect wheel. If cleaning is required,
remove motor and wheel as follows:
1. Slide burner access panel out.
2. Remove the 5 screws that attach induced-draft motor
assembly to the vestibule cover.
3. Slide the motor and blower wheel assembly out of the
blower housing. The blower wheel can be cleaned at this
point. If additional cleaning is required, continue with
Steps 4 and 5.
4. To remove blower from the motor shaft, remove
2setscrews.
5. To remove motor, remove the 4 screws that hold the
581B,C
motor to mounting plate. Remove the motor cooling fan
by removing one setscrew. Then remove nuts that hold
motor to mounting plate.
6. To reinstall, reverse the procedure outlined above.
Step 12 —Limit Switch
Remove blower access panel (Fig. 8). Limit switch is located on
the fan deck.
Step 13 —Burner Ignition
Unit is equipped with a direct spark ignition 100% lockout
system. Integrated Gas Unit Controller (IGC) is located in the
control box (Fig. 13). A single LED on the IGC provides a visual
display of operational or sequential problems when the power
supply is uninterrupted. The LED can be observed through the
viewport. When a break in power occurs, the IGC will be reset
(resulting in a loss of fault history) and the evaporator fan on/off
times delay will be reset. During servicing, refer to the label on
the control box cover or Table 39 for an explanation of LED error
code descriptions.
If lockout occurs, unit may be reset by interrupting power supply
to unit for at least 5 seconds.
Normal Operation
Hardware Failure
Evaporator Fan On/Off D el ay Modified
Limit Switch Fault
Flame Sense Fault
4 Consecutive Limit Switch Faults
Ignition L ockout Fault
Induced-Draft Motor Fault
Rollout Switch Fault
Internal Control Fault
Software Lockout
Step 14 —Main Burners
At the beginning of each heating season, inspect for deterioration
or blockage due to corrosion or other causes. Observe the main
burner flames and adjust, if necessary.
!
CAUTION
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in reduced furnace
life.
When servicing gas train, do not hit or plug orifice spuds.
Removal and Replacement of Gas Train
(See Fig. 63 and
1. Shut off manual gas valve.
2. Shut off power to unit, tag disconnect.
3. Remove compressor access panel.
4. Slide out burner compartment side panel.
5. Disconnect gas piping at unit gas valve.
6. Remove wires connected to gas valve. Mark each wire.
7. Remove induced-draft motor, igniter, and sensor wires at
the Integrated Gas Unit Controller (IGC).
8. Remove the 2 screws that attach the burner rack to the
vestibule plate.
9. Remove the gas valve bracket.
10. Slide the burner tray out of the unit (Fig. 64).
11. To reinstall, reverse the procedure outlined above.
12. Reinstall burners on rack.
INDUCEDDRAFT
MOTOR
MOUNTING
PLATE
BURNER
SECTION
INDUCEDDRAFT
MOTOR
MANIFOLD
PRESSURE
TA P
64)
Fig. 63 --- Burner Section Details
ROLLOUT
SWITCH
FLUE
EXHAUST
VESTIBULE
PLATE
BLOWER
HOUSING
GAS
VALV E
C06152
LEGEND
LED — Light-Emitting Diode
*A 3-second pause exists between LED error code flashes. If more than
one error code exists, all applicable codes will be displayed in numerical sequence.
†Indicates a code that is not an error. The unit will continue to operate
when this code is displayed.
IMPORTANT: Refer to Troubleshooting Tables for additional
information.
OFM— Outdoor (Condenser) Fan Motor
OLR— Overload Relay
P—Plug
PL— Plug Assembly
QT— Quadruple Terminal
RS— Rollout Switch
SAT— Supply Air Temperature Sensor
TRAN — Transformer
Field Splice
Marked Wire
Terminal (Marked)
Terminal (Unmarked)
Terminal Block
NOTES:
1. If any of the original wire furnished must be replaced, it must
be replaced with type 90 C wire or its equivalent.
2. Three phase motors are protected under primary single
phasing conditions.
3. Use copper conductors only.
4. TRAN is wired for 230 v unit. If unit is to be run with 208 v
power supply, disconnect BLK wire from 230 v tap (ORN)
and connect to 208 v tap (RED). Insulate end of 230 v tap.
Splice
Splice (Marked)
Factory Wiring
Field Control Wiring
Field Power Wiring
Accessory or Optional Wiring
To indicate common potential only;
not to represent wiring.
C06147
54
Page 55
TROUBLESHOOTING
Unit Troubleshooting
Refer to Tables 39--43 for unit troubleshooting details.
Economi$er IV Troubleshooting
See Table 44 for EconoMi$er IV logic.
A functional view of the EconoMi$er IV is shown in Fig. 60.
Typical settings, sensor ranges, and jumper positions are also
shown. An EconoMi$er IV simulator program is available from
your Bryant distributor to help with EconoMi$er IV training and
troubleshooting.
Economi$er IV Pr
This procedure is used to prepare the EconoMi$er IV for
troubleshooting. No troubleshooting or testing is done by
performing the following procedure.
NOTE: This procedure requires a 9-v battery, 1.2 kilo-ohm
resistor, and a 5.6 kilo-ohm resistor which are not supplied with
the EconoMi$er IV.
IMPORTANT: Be sure to record the positions of all
potentiometers before starting troubleshooting.
1. Disconnect power at TR and TR1. All LEDs should be
off. Exhaust fan contacts should be open.
2. Disconnect device at P and P1.
3. Jumper P to P1.
4. Disconnect wires at T and T1. Place 5.6 kilo-ohm resistor
across T and T1.
5. Jumper TR to 1.
6. Jumper TR to N.
7. If connected, remove sensor from terminals S
Connect 1.2 kilo-ohm 4074EJM checkout resistor across
terminals S
8. Put 620-ohm resistor across terminals S
9. Set minimum position, DCV set point, and exhaust
potentiometers fully CCW (counterclockwise).
10. Set DCV maximum position potentiometer fully CW
(clockwise).
11. Set enthalpy potentiometer to D.
12. Apply power (24 vac) to terminals TR and TR1.
Differential
To check differential enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Place 620-ohm resistor across S
3. Place 1.2 k ilo-ohm resistor across S
Cool LED should be lit.
4. Remove 620-ohm resistor across S
LED should turn off.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
Enthalpy
Single
To check single enthalpy:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Set the enthalpy potentiometer to A (fully CCW). The
Free Cool LED should be lit.
3. Set the enthalpy potentiometer to D (fully CW). The Free
Cool LED should turn off.
4. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
eparation
and +.
O
Enthalpy
and +.
R
and +.
O
and +. The Free
R
and +. The Free Cool
O
O
and +.
DCV (Demand Controlled Ventilation) and Power
Exhaust
To check DCV and Power Exhaust:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Ensure terminals AQ and AQ1 are open. The LED for
both DCV and Exhaust should be off. The actuator should
be fully closed.
3. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The LED for both DCV and Exhaust
should turn on. The actuator should drive to between 90
and 95% open.
4. Turn the Exhaust potentiometer CW until the Exhaust
LED turns off. The LED should turn off when the
potentiometer is approximately 90%. The actuator should
remain in position.
5. Turn the DCV set point potentiometer CW until the DCV
LED turns off. The DCV LED should turn off when the
potentiometer is approximately 9v. The actuator should
drive fully closed.
6. Turn the DCV and Exhaust potentiometers CCW until the
Exhaust LED turns on. The exhaust contacts will close 30
to 120 seconds after the Exhaust LED turns on.
7. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
DCV Minimum and Maximum
Position
To check the DCV minimum and maximum position:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Connect a 9-v battery to AQ (positive node) and AQ1
(negative node). The DCV LED should turn on. The
actuator should drive to between 90 and 95% open.
3. Turn the DCV Maximum Position potentiometer to
midpoint. The actuator should drive to between 20 and
80% open.
4. Turn the DCV Maximum Position potentiometer to fully
CCW. The actuator should drive fully closed.
5. Turn the Minimum Position potentiometer to midpoint.
The actuator should drive to between 20 and 80% open.
6. Turn the Minimum Position Potentiometer fully CW. The
actuator should drive fully open.
7. Remove the jumper from TR and N. The actuator should
drive fully closed.
8. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
Supply-- Air
Input
To check supply-air input:
1. Make sure EconoMi$er IV preparation procedure has been
performed.
2. Set the Enthalpy potentiometer to A. The Free Cool LED
turns on. The actuator should drive to between 20 and
80% open.
3. Remove the 5.6 kilo-ohm resistor and jumper T to T1. The
actuator should drive fully open.
4. Remove the jumper across T and T1. The actuator should
drive fully closed.
5. Return EconoMi$er IV settings and wiring to normal
after completing troubleshooting.
581B,C
55
Page 56
Economi$er IV Troubleshooting
Completion
This procedure is used to return the EconoMi$er IV to operation.
No troubleshooting or testing is done by performing the
following procedure.
1. Disconnect power at TR and TR1.
2. Set enthalpy potentiometer to previous setting.
3. Set DCV maximum position potentiometer to previous
setting.
4. Set minimum position, DCV set point, and exhaust
potentiometers to previous settings.
Table39—LEDErrorCodeServiceAnalysis
5. Remove 620-ohm resistor from terminals SRand +.
6. Remove 1.2 kilo-ohm checkout resistor from terminals S
and +. If used, reconnect sensor from terminals SOand +.
7. Remove jumper from TR to N.
8. Remove jumper from TR to 1.
9. Remove 5.6 kilo-ohm resistor from T and T1. Reconnect
wires at T and T1.
10. Remove jumper from P to P1. Reconnect device at P and
P1.
11. Apply power (24 vac) to terminals TR and TR1.
O
Hardware Failure.
(LED OFF)
Fan ON/OFF Delay Modified
(LED/FLASH)
581B,C
Limit Switch Fault.
(LED 2 Flashes)
Flame Sense Fault.
(LED 3 Flashes)
4ConsecutiveLimit
Switch Faults.
(LED 4 Flashes)
Ignition Lockout.
(LED 5 Flashes)
Induced-Draft Motor Fault.
(LED 6 Flashes)
Rollout Switch Fault.
(LED 7 Flashes)
Internal Control Fault.
(LED 8 Flashes)
Temporary Software
Lockout
(LED 9 Flashes)
SYMPTOMCAUSEREMEDY
Loss of power to control module (IGC).Check 5 amp fuse on IGC, power to unit, 24-v circuit breaker, and
High limit switch opens during heat
exchanger warm-up period before fan-on
delay expires.
Limit switch opens within three minutes
after blower-off delay timing in Heating
mode.
High temperature limit switch is open.Check the operation of the indoor (evaporator) fan motor.
The IGC sensed flame that should not be
present.
Inadequate airflow to unit.Check operation of indoor (evaporator) fan motor and that supply-air
Unit unsuccessfully attempted ignition for
15 minutes.
IGC does not sense that induced-draft
motor is operating.
Rollout switch has opened.Rollout switch will automatically reset, but IGC will continue to
Microprocessor has sensed an error in the
software or hardware.
Electrical interference is impeding the IGC
software.
transformer. Units without a 24-v circuit breaker have an internal
overload in the 24-v transformer. If the overload trips, allow
10 minutes for automatic reset.
Ensure unit is fired on rate and temperature rise is correct.
Ensure units’ external static pressure is within application guidelines.
Ensure that the supply-air temperature rise is in accordance with
the range on the unit nameplate.
Reset unit. If problem persists, replace control board.
temperature rise agrees with range on unit nameplate information.
Check ignitor and flame sensor electrode spacing, gaps, etc.
Ensure that flame sense and ignition wires are properly
terminated. Verify that unit is obtaining proper amount of gas.
Check for proper voltage. If motor is operating, check the
speed sensor plug/IGC Terminal J2 connection. Proper
connection: PIN 1— White, PIN 2 — Red, PIN 3 — Black.
lock out unit. Check gas valve operation. Ensure that induceddraft blower wheel is properly secured to motor shaft.
Reset unit at unit d isconnect.
If error code is not cleared by resetting unit power, replace the IGC.
Reset 24-v to control board or turn thermostat off and then on. Fault
will automatically reset itself in one hour.
!
CAUTION
COMPONENT DAMAGE HAZARD
Failure to follow this caution may result in component
damage.
If the IGC must be replaced, be sure to ground yourself to
dissipate any electrical charge that may be present before
handling new control board. The IGC is sensitive to static
electricity and may be damaged if the necessary precautions
are not taken.
LEGEND
IGC --- Integrated Gas Unit Controller
LED --- L i g h t --- E m i t t i n g D i o d e
IMPORTANT: Refer to heating troubleshooting for additional
heating section troubleshooting information.
56
Page 57
Table 40— Heating Service Analysis
BurnersWillNo
t
g
Nogasatmainburner
s.Checkgaslineforairpurgeasnecessar
y.Afterpurginggaslineofai
r,allowga
s
InadequateHeating
.
Toomuchoutdoorair
.
Characteristics
.
combustionair)resultsin
:
Aldehydeodors,CO(carbonmonoxide),
WillNotEnergize
.
ExcessiveSuperheat.
PROBLEMCAUSEREMEDY
Burners Will Not
Ignite.
Inadequate Heating.Dirty air filter.Clean or replace filter as necessary.
Poor Flame
Characteristics.
Burners Will Not
Tu r n Off.
Misaligned spark electrodes.Check flame ignition and sensor electrode positioning. Adjust as needed.
No gas at main burners.Check gas linefor air purge as necessary.After purging gas line ofair, allow gas
Water in gas line.Drain water and install drip leg to trap water.
No power to furnace.Check power supply, fuses, wiring, and circuit breaker.
No 24 v power supply to control circuit.Check transformer. Transformers with internal overcurrent protection require a
Miswired or loose connections.Check all wiring and wirenut connections.
Burned-out heat anticipator in thermostat.Replace thermostat.
Broken thermostat wires.Run continuity check. Replace wires, if necessary.
Gas input to unit too low.Check gas pressure at ma nifold. Clock gas meter for input. If too low, increase
Unit undersized for application.Replace with proper unit or add additional unit.
Restricted airflow.Clean filter, replace filter, or remove any restrictions.
Blower speed too low.Use high speed tap, increase fan speed, or install optional blower, as suitable
Limitswitchcyclesmainburners.Check rotation of blower, thermostat heat anticipator settings, and temperature
Too m uch outdoor air.Adjust minimum position.
Incomplete combustion (lack of
combustion air) results in:
Aldehyde odors, CO (carbon monoxide),
sooting flame, or floating flame.
Unit is locked into Heating mode for a
one minute minimum.
to dissipate for at least 5 minutes before attempting to relight unit.
Check gas valve.
cool-down period before resetting. Check 24-v circuit breaker; reset if necessary.
manifold pressure or replace with correct orifices.
for individual units, Adjust pulley.
rise of uni t. Adjust as needed.
Check economizer operation.
Check all screws around flue outlets and burner compartment. Tighten as nec-
essary.
Cracked heat exchanger.
Overfired unit — reduce input, change orifices, or adjust gas line or manifold
pressure.
Check vent for restriction. Clean as necessary.
Check orifice to burner alignment.
Wait until mandatory one-minute time period has elapsed or reset power to
unit.
581B,C
Table 41—Perfect Humidity Adaptive Dehumidification System Subcooling Mode Service Analysis
Subcooling Mode (Liquid Reheat)
Will Not Energize.
Low System Capacity.Low refrigerant charge or frosted evaporator coil.1. Check charge amount. Charge per Fig. 55 ---58.
Loss of Compressor Superheat
Conditions with Subcooling/Reheat
Dehumidification Coil Energized.
PROBLEMCAUSEREMEDY
No power to control transformer from
evaporator-fan motor.
No power from control transformer t o liquid line
solenoid valve.
Liquid line solenoid valve will not operate.1. Solenoid coil defective; replace.
Liquid line solenoid valve will not open.Valve is stuck closed; replace valve.
Thermostatic expansion valve (TXV).1. Check TXV bulb mounting, and secure tightly to suc-
Check power source and evaporator-fan relay. Ensure all
wire connections are tight.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow
low-pressure switch to reset. Replace switch if it will
not close.
3. Transformer bad; check transformer.
2. Solenoid valve stuck open; replace.
2. Evaporator coil frosted; check and replace low-pressure switch if necessary.
tion line.
2. Replace TXV if stuck open or closed.
Table 42—Perfect Humidity Adaptive Dehumidification System Hot Gas Reheat Mode Service Analysis
Reheat Mode Will Not Energize.No power to control transformer from
Loss of Compressor Superheat
Conditions with Subcooling/Reheat
Dehumidification Coil Energized.
Excessive Supe rheat.Liquid line solenoid valve will not operate.Valve is stuck, replace valve.
PROBLEMCAUSEREMEDY
evaporator-fan motor.
No power from control transformer to hot gas
line solenoid valve
Hot gas line solenoid valve will not operate.1. Solenoid coil defective; replace.
Low refrigerant charge or frosted evaporator coil.1. Check charge amount. Charge per Fig. 55 ---58.
Thermostatic expansion valve (TXV).1. Check TXV bulb mounting, and secure tightly to suc-
Hot gas line solenoid valve will not close.Valve is stuck; replace valve.
Check power source and evaporator-fan relay. Ensure all
wire connections are tight.
1. Fuse open; check fuse. Ensure continuity of wiring.
2. Low-pressure switch open. Cycle unit off and allow
low-pressure switch to reset. Replace switch if it will
not close.
3. Transformer bad; check transformer.
2. Solenoid valve stuck closed; replace.
2. Evaporator coil frosted; check and replace low-pressure switch if necessary.
Power failure.Call power company.
Fuse blown or circuit breaker tripped.Replace fuse or reset circuit breaker.
Defective thermostat, contactor, transformer, or
control relay.
Insufficient line voltage.Determine cause and correct.
Incorrect or faulty wiring.Check wiring diagram and rewire correctly.
Thermostat setting too high.Lower thermostat setting below room tempera-
Faulty wiring or loose connections in compressor circuit.
Compressor motor burned out, seized, or internal overload open.
One leg of 3-phase power dead.Replace fuse or reset circuit breaker. Determine
Refrigerant overcharge or undercharge.Recover refrigerant, evacuate system, and re-
Defective compressor.Replace and determine cause.
Insufficient line voltage.Determine cause and correct.
Blocked condenser.Determine cause and correct.
Defective run/start capacitor, overload, or start
relay.
Defective thermostat.Replace thermostat.
Faulty condenser-fan motor or capacitor.Replace.
Restriction in refrigerant system.Locate restriction and remove.
Dirty air filter.Replace filter.
Unit undersized for load.Decrease load or increase unit size.
Thermostat set too low.Reset thermostat.
Low refrigerant charge.Locate leak, repair, and recharge.
Leaking valves in compressor.Replace compressor.
Air in system.Recover refrigerant, evacuate system, and re-
Condenser coil dirty or restricted.Clean coil or remove restriction.
Dirty air filter.Replace filter.
Dirty condenser coil.Clean coil.
Refrigerant overcharged.Recover excess refrigerant.
Air in system.Recover refrigerant, evacuate system, and re-
Condenser air restricted or air short-cycling.Determine cause and correct.
Low refrigerant charge.Check for leaks, repair, and recharge.
Compressor valves leaking.Replace compressor.
Restrictioninliquidtube.Remove restriction.
High heat load.Check for source and eliminate.
Compressor valves leaking.Replace compressor.
Refrigerant overcharged.Recover excess refrigerant.
Dirty air filter.Replace filter.
Low refrigerant charge.Check for leaks, repair, and recharge.
Metering device or low side restricted.Remove source of restriction.
Insufficient evaporator airflow.Increase air quantity. Check filter and replace if
Temperature too low in conditioned area.Reset thermostat.
Outdoor ambient below 25 F.Install low-ambient kit.
Time off delay not finished.Wait for 30-second off delay.
Replace component.
ture.
Check wiring an d repair or replace.
Determine cause. Replace compressor .
Determine cause and replace.
cause.
charge to nameplate.
Determine cause and replace.
charge.
charge.
necessary.
58
Page 59
Table 44—EconoMi$er IV Input/Output Logic
D
d
C
l
V
Outd
R
Y1Y
2
Belowse
t
Hig
h
Low
MinimumpositionClosed
Low
Hig
h
Modulating(betweenmin
.
Modulating(betwee
n
Abovese
t
Hig
h
Low
Modulating††(betweenmin
.
Modulating††(betwee
n
Low
Hig
h
ModulatingModulating†††
INPUTSOUTPUTS
eman
ontro
entilation (DCV)
Below set
(DCV LED O ff)
Above set
(DCV LED On)
*For single enthalpy control, the module compares outdoor enthalpy to the ABCD set point.
†Power at N terminal determines Occupied/Unoccupied setting: 24 vac (Occupied), no power (Unoccupied).
**Modulation is based on the supply-air sensor signal.
††Modulation is based on the DCV signal.
***Modulation is based on the greater of DCV and supply-air sensor signals, between minimum position and either maximum position (DCV) or fully open (sup-
ply-air signal).
†††Modulation is based on the greater of DCV and supply-air sensor signals, between closed and either maximum position (DCV) or fully open (supply-airsig-
nal).
High
(Free Cooling LED Off)
Low
(Free Cooling LED On)
High
(Free Cooling LED Off)
Low
(Free Cooling LED On)
Enthalpy*CompressorNTerminal†
oor
Low
Y1 Y2
eturn
On OnOnOn
Stage Stage
12
Minimum positionClosed
OccupiedUnoccupied
Damper
On OffOnOff
Off OffOffOff
High
On OnOnOff
On OffOffOff
Modulating** (between min.
position and full-open)
Modulating** (between
closed and full-open)
Off OffOffOffMinimum positionClosed
Low
High
On OnOnOn
On OffOnOff
Off OffOffOff
On OnOnOff
Modulating†† (between min.
position and DCV maximum)
Modulating†† (between
closed and DCV
maximum)
Modulating***Modulating†††
On OffOffOff
Off OffOffOff
581B,C
C06053
Fig. 67 --- EconoMi$er IV Functional View
59
Page 60
START-UP CHECKLIST
(Remove and Store in Job File)
I. PRELIMINARY INFORMATION
MODEL NO.:SERIAL NO.:
DA TE:TECHNICIAN:
II. PRE-START-UP (insert checkmark in box as each item is completed)
jVERIFY THA T JOBSITE VOLT AGE AGREES WITH VOLT AGE LISTED ON RA TING PLA TE
jVERIFY THA T ALL P ACKAGING MATERIALS HA VE BEEN REMOVED FROM UNIT
jREMOVE ALL SHIPPING HOLDDOWN BOLTS AND BRACKETS PER INSTALLA TION INSTRUCTIONS
jVERIFY THA T CONDENSA TE CONNECTION IS INSTALLED PER INSTALLA TIO N INSTRUCTI ONS
jCHECK ALL ELECTRICAL CONNECTIONS AND TERMINALS FOR TIGHTNESS
jCHECK GAS PIPING FOR LEAKS
jCHECK THA T RETURN (INDOOR) AIR FIL TERS ARE CLEAN AND IN PLACE
581B,C
jVERIFY THAT UNIT INST ALLATION IS LEVEL
jCHECK F AN WHEELS AND PROPELLER FOR LOCATION IN HOUSING/ORIFICE AND SETSCREW
TIGHTNESS
jCHECK TO ENSURE THA T ELECTRICAL WIRING IS NOT IN CONT ACT WITH REFRIGERANT LINES
OR SHARP METAL EDGES
j CHECK PULLEY ALIGNMEN T AND BELT TENSION PER INSTALLA TI ON INSTRUC TION S
III. START-UP
ELECTRICAL
SUPPL Y VOLT AGEL1-L2L2-L3
L3-L1
COMPRESSOR AMPSL1L2L3
INDOOR-FAN AMPSL1L2L3
TEMPERATURES
OUTDOOR-AIR TEMPERA TURE
RETURN-A IR TEMPERATURE
COOLING SUPPLY AIR
DB
DBWB
DB
HEATINGSUPPLYAIRDB
PRESSURES (Cooling Mode)
GAS INLET PRESSURE
GAS MANIFOLD PRESSURE
IN.WG
IN.WG (HIGH FIRE)
REFRIGERANT SUCTIONPSIG
REFRIGERANT DISCHARGE
PSIG
jVERIFY THA T 3-PHASE FAN MOTOR AND BLOWER ARE ROTATING IN CORRECT DIRECTION. IF THEY
ARE NOT ROTATING IN CORRECT DIRECTION, LOCKING COLLAR MUST BE RE--TIGHTENED AFTER
CORRECTING DIRECTION OF ROTATION
jVERIFY THA T 3-PHASE SCROLL COMPRESSOR IS ROTATING IN THE CORRECT DIRECTION
jVERIFY REFRIGERANT CHARGE USING CHARGING CHAR TS
E2007 Bryant Heating & Coo ling Systems 7310 W. Morris St. Indianapolis, IN 46231Printed in U.S.A.Edition Date: 2/07
Manufacturer reserves the right to discontinue, or change at any ti me, specifications or designs without notice and without incurring obligations.
60
Catalog No. II581B---C ---36 --- 1
Replaces: II 581B --- 36--- 7
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.