Bryant 394 Gas User Manual

Page 1
Installation Ins!
GAS-FIRED FORCED AIR FURNACE
394
Series G
Size 50 thru 220

INTRODUCTION

Before installing the furnace, refer to Bryant Form
No. 39003D1 “Procedure for Gas Appliances” (packaged with the equipment) for information con cerning combustion, venting, piping, and other standard installation practices. Further reference is made to the
current edition of the American National Standard “Installation of Gas Appliances and Gas Piping,” Z21.30.
Model 394 Gas Furnaces are shipped from the factory
completely assembled and wired ready for indoor heat ing installation. They are manufactured with two types of blowers: belt and direct drive. The three smaller
sizes (Series G), 50, 80, and 100. are direct drive only. All sizes incorporate a low-voltage terminal strip for convenience of field wiring (except HL and HH Models).
The optional equipment available includes: Counter flow Box; Side and Rear Drop Ducts; Side Filter Racks; Cooling Coil Housing; Combustible Floor Base Packages, for Counterflow Applications; Cooling Relay Kit, for field conversion.

CAUTION:

1 ( iiimli-!iImv liii[M,.e mus' bv ui'Killvd kii .m :ip
proved non-combustible base.
2 liL siiic icmpci.iMtii. Use ll■>l■^ no! c\».cci{ ili.i spcs-ilhil on ihc mil! i.iimu pkiic
' lie suic to chci.l' all ci'iiiiols iiii piiipci opt-i.i'ioi
upon cvimplction of installalivm.
4. Duralast filler on 125 and 137 iipflow fu.maces mus
be used with a skle filter rack or rear drop duct.
Cancels 39394D66
the manual valve knob (OFF-PILOT-ON). There is a position stop at the PILOT position. To move the manual valve knob from the PILOT position to either ON or OFF position, the manual valve knob must be depressed.
If not already checked when lighting the main burner,
check the proper operation of this valve by moving the room thermostat pointer above and below room temperature and observing that the main burners light on call for heat and go off when the pointer is moved below the room temperature setting. All Bryant auto matic gas control valves have a delay when opening or closing.

Automatic Pilot

To check the pilot operation, follow the instructions below:
Attach a low-voltage test light to electrical leads of gas valve. With thermostat set above room temperature, shut off gas supply to burners and pilot, with main manual shutoff valve. If test light goes out within 45 seconds, pilot is functioning properly. If light does not
go out within 60 seconds, replace pilot.
39394D73 3/30/72

I. CLEARANCE REQUIREMENTS

The upflow furnace design is certified for use on com bustible floors.
The Model 394 design is certified by the American Gas Association, Inc., for installation in a closet or alcove
provided the following clearances are maintained.
Sides............................................................0" (1")*
Back
............................................................
Top of Plenum.............................................3" (0")*
Vent Connector
Front............................................................6" (6")*
* Figures shown in parentheses are approved clearances
when the furnace is installed as a counterflow furnace.
Bryant Automatic Gas Control Valve
Note: On units equipped with an A-643 Bryant auto matic gas control valve, there are three positions for
...........................................

II. CONTROLS

0" (1")* 6" (6")*

Pilots with Thermocoupie Elements

The D2 100% shutoff propane and D5 100% shutoff natural gas controls have pilots equipped with thermo couple elements.
The pilot flame should surround the tip of the thermo couple. It should also extend downward to include
3/8 to 1/2 inch of the thermocouple tip. The flame must not come in contact with any other part of the thermocouple.

D2 Propane

The thermocouple transforms heat energy from the pilot flame into electrical energy. The current thus generated is sufficient to operate the 100% inline shut off valve. The Bryant automatic gas control valve is
powered externally from the transformer, and operates independently of the inline shut-off valve. When there
Page 2
UPFLOW FURNACE
A70652
A.G.A. RATINGS BTU/HR
Natural Propane
Model
No.
50-394
80-394 100-394 125-394 137-394 165-394
190-394 190,000 152,000
220-394 220,000 176,000
Model No.
50-394 16-1/4
80-394 100-394 18-1/4 125-394 20-1/4 137-394 20-1/4 165-394 28-1/4 190-394
220-394 *Optional gas inlet right and left sides provided. T = 33-5/8 and S = 3-1/2 on 50 thru 137 sizes only.
Input
50,000 40,000 50,000 40,000
80,000 64,000 75,000 60,000 100,000 80,000 100,000 80,000 125,000 137,500 165,000
A
26 46 14-5/8
16-1/4
26 26 26 26 46
36-1/4 36-1/4
28-13/16 28-13/16 28-13/16
Bonnet
Capacity
100,000 125,000 100,000 110,000 132,000 150,000 120,000
C D E
B
46 14-5/8 46 16-5/8 19-3/4 46 18-5/8 19-3/4
51 51 51
Input
Not Available
175,000
200,000 160,000
19-3/41 ¡9-3/4
18-5/8 19-3/4
26-5/8
17-3/4 2-1/2 5 6" 25-1/4
34-5/8
17-3/4
34-5/8
17-3/4 2-1/2 5 (2) 5"
Bonnet
Capacity
140,000
F G
2-9/16
1/2
2-9/16
1/2
2-3/4 5"
1/2
2-3/4
1/2
2-3/4
1/2
2-1/2 5 (2) 5" 33-1/4
Gas Connection
Sizes
Natural Propane
1/2 1/2 1/2 1/2 1/2 1/2
1/2
1/2
H
4"
12-1/4
4"
12-1/4 14-1/4 18-1/4
5". 5" 18-1/4 22-5/8
33-1/4
BOTTOM OPTIONAL
RETURN SIDE FILTER RACK
OPENING EITHER SIDE
1/2 1/2 1/2 1/2 1/2
(2) 14 X 25 X 1 .
1/2
(1) 16 X 25 X 1 (1) 20 X 25 X 1
1/2
(1) 16 X 25 X 1
1/2
(1) 20 X 25 X 1
K
J
22-5/8 22-5/8 22-5/8 22-5/8 1-1/2
23-5/16 23-5/16 23-5/16
Bottom
Filter Sizes
14 X 25 X 1 14 X 25 X 1 16 X 25 X 1 20 X 25 X 1 20 X 25 X 1
L
M
1-1/2 1-1/2 1-1/2
1-1/2
2-5/8 23
23
2-5/8
23
2-5/8
Side Filter Sizes
14 X 25 X 1 14 X 25 X 1 16 X 25 X 1 20 X 25 X 1 20 X 25 X 1
(2) 16 X 25 X 1
(2) 16 X 25 X 1
(2) 16 X 25 X 1
N P R S*
1-1/4
12 12 14 18 18
23 23 23 23 23
24 2-1/8 24 24
2-1/8
1-1/4
2-1/8
1-1/4
2-1/8
1-1/4
2-1/8
1-1/4 2-1/8
8-5/8 2-1/8 8-5/8 2-1/8 8-5/8
A66384
Approx.
Shipping
Weight
135 153 178 200 202 282
365
365
T*
2-7/8
25-7/16
2-7/8
25-7/16
2-7/8
25-7/16
2-7/8
25-7/16
2-7/8 25-7/16
30-5/8
4-1/16 4-1/16 30-5/8 4-1/16
30-5/8
is a pilot flame, the current generated by the thermo couple holds the 100% inline shut-off valve in the open position and the gas control valve controls the flow of gas. Should the pilot go out, no current will be generated by the thermocouple and the 100% inline shut-off valve will close. No gas can then flow to the pilot.
D5 Natural
Should the pilot go out, no current will be generated by the thermocouple and the pilot-relay will close, shutting off the gas to the pilot, and breaking the elec
trical circuit to the Bryant automatic gas control valve.
821/822 Adjustable Fan Control
The Model 394 Furnace incorporates the 821/822 relay for fan control. (The 821 relay is used with the
643 gas valve on furnace sizes 50 through 165 natural
gas; the 822 relay is used with the 641 valve on sizes
190 and 220 and all propane units.) The 821/822 has a field-adjustable differential. The “max. off” setting on the dial is for the longest “off” time and shortest
“on” time.
When facing the front of the furnace, the “off” cycle is lengthened by moving the adjustment lever to the
Figure 1 - Control Section (D5 pilot relay shown)
left. The “off’ cycle is shortened by moving the lever to the right. The adjustment of the “off’ cycle has the opposite effect on the “on” cycle; however, to a lesser degree.
-2-
Page 3
BASEMENT FURNACE
Model
No.
50-394
80-394 100-394 125-394 137-394 165-394 190-394
220-394
A.G.A. RATINGS BTU/HR
Natural Propane
Bonnet
Input
Capacitj Input 50,000 80,000
100,000 125,000 137,500 165,000 190,000 220,000
40,000 50,000 64,000
75,000 60,000
80,000 100,000
100,000
125,000 100,000 110,000 132,000
150,000 120,000 152,000
175,000 140,000 36-1/4 43-3/8 51 176,000
200,000 160,000 36-1/4
Bonnet
A
C
В
D
E F
H
G
J*
Capacity Nat.
40,000
80,000
Not available
40-9/16
16-1/4
40-9/16
16-1/4
40-9/16
18-1/4
40-9/16
20-1/4
40-9/16
20-1/4
43-3/8
28-1/4
43-3/8 51 34-5/8
46 46 46 46
46
14-5/8 16-5/8 18-5/8 18-5/8
19-3/4 2-1/2 19-3/4 19-3/4 19-3/4
19-3/4 2-1/2
14-5/8
51 26-5/8 17-3/4
17-3/4
34-5/8
17-3/4
2-1/2 2-1/2 2-1/2 4-1/2 4-1/2 4-1/2
4"
2-9/16
4"
2-9/16
2-3/4 5"
5"
2-3/4
5"
2-3/4 4-1/2
6" 30-5/8 4-1/16 5-1/8 2-5" 5-1/8 2-5"
25-7/16 25-7/16
25-7/16 25-7/16 25-7/16 2-7/8
30-5/8 30-5/8
GAS CON
K*
1/2
2-7/8
1/2
2-7/8
1/2
2-7/8 2-7/8 1/2
1/2 1/2 1/2
4-1/16
1/2
4-1/16
SIZES
Prop. , 1/2
14 X 25 X 1
1/2 14 X 25 X 1
16 X 25 X 1
1/2 1/2 20 X 25 X 1
20 X 25 X 1
1/2
Two 16 X 25 X 1
1/2 1/2 Two 16 X 25 X 1
Two 16 X 25 X 1
i/i
Filters
Approx.
Shipping
Weight
(Lb.)
Ratings are certified for altitudes to 2,000 feet for all gases. Ratings for altitudes over 2,000 feet are 4% less for each 1,000 feet above sea level. Return air compartment shipped separately, knocked down.
*Optional gas inlet right and left sides provided. J = 33-5/8 and K= 3-1/2 on 50 thru 137 sizes only.
COUNTERFLOW FURNACE
166
192 213 238 240 343 . 428 428
A.G.A. Ratings BTU/HR
Model
No.
50-394
80-394 100-394 125-394 137-394 165-394
190-394 220-394
Natural Propane
Bonnet
Capacity
Input
40,000
50,000
80,000 64,000 75,000 60,000 16-1/4 26 100,000 80,000 125,TO 100,000 137,500
110,000
165,000
132,000
19O,0OO
152,000
220,000
176,000
200,000 160,000
Bonnet
Capacity
Input 50,000 40,000 16-1/4 26
100,000 80,000 125,000 100,000 202Щ
Not available 150,000 120,000 175,000 140,000
A В С D Е
18-1/4 26
20-1/4 28-1/4 28-13/168026-1/4 36-1/4 28-13/16 80 34-1/4 36-1/4
26 26 75
28-13/16
— —
Н
75
80 34-3/4
*Add 1-1/4" when installed with base on combustible fioor. tOptional gas inlet right and left sides provided. L = 33-5/8 and K =
14-3/4 14-3/4
16-3/4 18-3/4 18-3/4
G
тщ
2-3/4
ТЩ
гЗТ4
2-3/4 4-1/2 5 5
F
4" 12-5/8 22-5/8 4" 12-5/8
14-5/8
5" 5" 18-518 22-5/8
18-5/8 22-5/8
5"
25-5/8
6"
33-5/8
(2) 5"
33-5/8 23-5/16
(2) 5"
Н J
22-5/8 22-5/8
23-5/16 23-5/16
3-1/2 on 50 thru 137 sizes only.
-3-
Gas Con
Kt*Lt
1-1/2
2-7/8 25-7/16 1-1/2 2-7/8 25-7/16 1-1/2
2-7/8 25-7/16 1/2 1/2
тш
1-7/8 25-7/16 1-1/2
1-7/8 4-1/16 1-7/8 4-1/16 30-5/8 1/2 1/2 1-7/8
25-7/16
2-7/8
30-5/8 1/2
30-5/8 1/2 1/2
4-1/16
Sizes
Nat. Prop.
1/2 1/2 1/2
1/2 1/2
Filters
1/2
16 X 20 X 1 166 16 X 20 X 1 185
Two 10 X 20 X 1 210
1/2
Two 14 X 20 X 1
1/2
Two 14 X 20 X 1
1/2
Two 16 X 20 X 1 Two 20 X 20 X 1 Two 20 X 20 X 1
A66383
Approx.
Shipping
Weight
(Lb.)
235 237
325 405 405
Page 4
I
Figure 2 - Control Box, Cover Removed,
No Internal Wiring Changes
TO HEATING AND COOLING CONNECTIONS OF THERMOSTAT P/N 34427D030 a 34427D031
\ TO CONDENSER
> CONTACTOR COIL
I CONNECTIONS
A68367
VOF THERMOSTAT ^P/n 34427D030
a 34427D031
] TO CONDENSER
I LOW VOLTAGE (^LEAD OR
j TERMINAL STRIP
NOTE-'
WIRE WITH* IN FIGURE 2 IS
A68368 CONDENSEFTHAS TRANSFORMER.
Figures 3 - Control Box, Cover Removed,
Showing Internal Wiring Changes
REMOVED, AND DISCARDED WHEN
TO HEATING AND COOLING CONNECTIONS

Low-Voltage Wiring

Field low-voltage connections are made at the low­l^oltage terminal strip. See Figure 6 for heating only. For Model 394 Furnaces used in conjunction with
slectric or gas air conditioning units that do not have 4n integral transformer, see Figure 2. If the 394 Fur­fiace is used in conjunction with an electric or gas air jonditioning unit having an integral transformer, see Figure 3.
Figure 3 shows a field-installed wire running from one side of the air conditioning transformer, through the
4ole marked “F” in the terminal strip to the blower
relay in the control box for the Model 394 Furnace.
The wire marked * in Figure 2 is removed from the
:ontrol box and discarded.

Limit Control

This control shuts oflF the gas and energizes the blower notor if the furnace becomes overheated.
The recommended method of checking the limit control
s to gradually block off the return air after the furnace
,ias been operating for a period of at least five minutes. \s soon as the limit has proven safe, the return air opening would be unblocked to permit normal air jirculation. By using this method to check the limit
control, it can be established that the limit is function-
ng properly and will “fail-safe” if there is a motor ailure.

Thermostat Location

The room thermostat should be located where it will re in the natural circulating path of room air. Avoid
locations where the thermostat would be exposed to cold air infiltration, drafts from windows, doors, or other openings leading to the outside, or exposure to air currents from warm or cold air registers; or to ex posure where the natural circulation of the air is cut off—such as behind doors, above or below mantels, shelves, etc.
The thermostat should not be exposed to heat from nearby radiators, fireplaces, radios, televisions, lamps, or rays from the sun. Nor should the thermostat be mounted on a wall containing pipes or warm air ducts,
or a flue or vent which could affect its operation and prevent it from properly controlling the room tempera ture. Any hole in the plaster or panel through which the wires pass from the thermostat should be adequately sealed with suitable material to prevent drafts from affecting the thermostat.
The heat anticipator on the thermostat should be set at 0.8 amps.

III. ELECTRICAL CONNECTIONS

Line-Voltage Wiring

All electrical connections are to be made in accordance with the local electrical codes. A permanent, live, separately fused electric power supply, complete with
manual switch, should be provided for the furnace.
Field wiring connections should be made in accordance
with the unit wiring diagrams.
-4-
Page 5

Adjustment of Blower Speed

^ our-Speed Direct Drive
To change motor speed taps, remove the motor tap lead (see Figure 1) and relocate it on the desired ter minal on the plug-in terminal block/speed selector located on the dividing panel. See Table I.
Belt Drive
The blower speed may be changed by opening or clos ing the motor pulley. When adjusting blower speed, be certain that the pulleys are properly aligned.
TABLE 1 - Factory Setting Blower Motor Chart
Drive Type
Unit Size
50 80
100 2
125
137 165 2 190 220
*Use when factory Relay Kit is field installed.
L
Red Blue
to
to*
4 3
1
3
1
2 1

Color Code for Speed Taps

M
Red Blue Red
to
4 3 3 1
3 2
to
to
1 1
1 1
E
4 4 3 2
B
Blue
Red Red Red
to
to
1 1 1
1 1
1
1
1
1 1 1
c
to to
1 1 1
1 1
cx
1
1
Common (white).................................................#C Tap
Hi Speed (black)
..................................................
#1 Tap
Med Speed (blue).................................................#2 Tap
Med-Lo Speed (yellow)....................................# 3 Tap
Lo Speed (red)......................................................#4 Tap
C.AUTION: When adjusting the blower .speed. ma| certain that the temperature rise acn>ss the heat changer doe.s not exceed that specified on the rati|

DRIVE TYPES

B — Belt drive heating —minimum cooling C — Belt drive heating and cooling X— Belt drive heating—maximum cooling
L — Multi-speed direct drive heating —minimum cooling
E — Multi-speed direct drive heating —maximum cooling with evaporator
blower motor relay.
M —Mutli-speed direct drive heating —minimum cooling with evaporator
blower motor relay.

IV. CARE AND MAINTENANCE

Cleaning
The heat exchanger should be examined periodically to see if there has been an accumulation of rust, soot, etc. Clean as follows;
1. Disconnect pilot tubing.
2. Disconnect electrical lead from pilot. (In case of 100% shut-off controls, disconnect pilot thermocouple
lead from pilot relay or inline shut-off valve.)
3. Remove front plate from draft diverter (4 sheet-
metal screws).
4. Remove burners and pilot as follows:
a. Remove Tinnerman clamp from burner-holding
stud.
b. Slide burner off orifice and remove under
manifold.
c. Pilot is attached to one burner and is removed
with that burner. It is not necessary to detach pilot before removing burner.
5. Remove metal angle strip holding flue baffles in place. See Figure 4.
6. Remove flue baffles. See Figure 5.
7. Use flexible-handled steel cleaning brush to loosen scale and soot. Remove scrapings from bottom of combustion chamber.
8. Reassemble furnace by reversing above procedure.
NOTE: There is a slot in the back of the heat ex changer for the back tip of the burner to fit into. When
properly placed, the burner will fit into this slot and
will be level.

Care of Blowers

All motors on the belt drive blowers are provided with oil cups and should be oiled at least twice a year with a nondetergent SAE 30 oil.

Belt Tension

Adjust tension on a V-belt so that the belt deflects approximately 3/4 to 1 inch when the pressure from one finger is applied midway between the blower and motor pulleys. Adjust the tension by turning the motor adjusting screw.

Filters

Some units are equipped with a permanent fiber filter
(recognizable by its distinct green color). To clean this filter, run water through the fibers from the leaving air side. Do not spray this filter with water-soluble oil.

Figure 4 - Flue-Baffle Retainer Strip

A66475
Figure 5 - Removing Baffles
-5-
A66476
Page 6

LINE-TO-LINE WIRING DIAGRAMS

THERMOSTAT CONNECTIONS-HEATING ONLY

note: remove \nter-
NAL JUMPER SETWIEM
1 W ^ J TERMtHALS.
I- —11
Figure 6 - Units without Heat-Cool Relay (HL Drive)
Figure 7 - Units with Heat-Cool Relay (M & E Drives)
Figure 8 - Units without Cooling Relay (B Drive)
Figure 9 - Units with Cooling Relay (C & X Drives)
1 A—Transformer
2A—Cooling Relay-SPST 2C—Heat-Cool Relay-SPDT 2G —Heating Relay-SPST
(Heat Motor Operated)
3A —Blower Motor
5A—Automatic Gas Valve 6A—Pilot Switch
(None on Propane)
7H —Limit Control-SPST
(On Counterflow Only)
7K —Limit Control-SPDT
3D —Blower Motor
Factory Line Voltage Factory Low Voltage Field Line Voltage
THERMOSTAT 34427D35 (NO ­TERM\WAL CODE). ALSO MODELS
883-P/N 344270030 OR 884­P/N 34427003» THERMOSTAT 4 SUS BASE.
OM-OFF FAN, MODEL 885
P/K| 34427033 TtiEFMOSTAT
t SUB-BASE OR THERMOSTOT
MODEL SBS P/n 344i76<l6 Wrro SUB BASE P/M 34427034.
A68372

SEQUENCE OF OPERATING-HEATING

When the thermostat calls for heat, the control circuit is closed between terminals (4 and W). Power from trans former (lA) energizes automatic gas valve coU (5A) and heating relay coil (2G) simultaneously. After a short time delay, automatic gas valve (5A) opens, permitting gas to flow to the burners where it is ignited by the gas pilot. After another delay, the heating relay switches its contacts (2G), starting blower motor (3A or 3D) on its heating speed.
When the thermostat is satisfied, the circuit between terminals (4 and W) is broken, de-energizing automatic gas valve coil (5A) and heating relay coil (2G). After a few seconds, automatic gas valve (5A) closes, stopping the flow of gas to the main burners. After a longer delay, heating relay (2G) opens its contacts to stop blower motor (3A or 3D).
If the furnace overheats for any reason, limit control (7K) will switch, breaking the circuit to automatic gas valve coil (5A) and making a circuit to heating relay coil (2G). After
a short delay, the gas valve closes, shutting off the flow of gas through the main burners. After an additional period of time, heating relay (2G) closes its contacts, energizing blower motor (3A or 3D) (if it is not already operating) on heating speed. It continues to cycle until the fault is corrected.
On counterflow furnaces, additional limit control (7H) protects against overheating also. Should this control sense a high temperature, it opens its contacts, de-energizing automatic gas valve coil (5A) which, in turn, shuts off the flow of gas to the main burners. After limit control (7H) has cooled, its contacts close, automatically energizing automatic gas valve coil (5A). After a short delay, the valve opens, permitting gas to flow to the burners where it is ignited by the pilot. Furnace blower motor (3A or 3D) may or may not be operating, since it is independent of additional limit control (7H).

SEQUENCE OF OPERATION-COOLING

When the thermostat calls for cooling, power from trans former (lA) energizes cooling relay coil (2C), closing its
contacts, and energizing blower motor (3A or 3D) on its cooling speed. It continues to operate until the thermostat is satisfied.
When the thermostat is satisfied, the circuit to terminal (G) is broken, de-energizing cooling relay coil (2C) which, in turn, opens its contacts, stopping blower motor (3 A or 3D).
-6-
Loading...