Bryant 393U User Manual

393U
Installation Instructions
GAS FIRED FORCED AIR FURi^ACE
The Bryant Model 393 forced air, gas-fired furnace may be installed as an
1.2.Upflow Furnace Counter-Flow Furnace
(except sizes 175 and 200)
Basement Furnace
This instruction contains complete procedures for
installing the unit as an Upflow Furnace.
When the furnace is used as a counter-flow, a counter-flow box and instructions are provided. When it is used as a basement model, a drop duct
and instructions are provided. The Series C and D
Counter-Flow Boxes are interchangeable.
/1 \ fr
"iKJ V fl
Series D
39393D2
I
Rev. 3/17/65
Before beginning installation, read these instruc tions carefully.
When making a Counter-Flow or Basement installa tion, also read the separate instructions furnished with the additional equipment required.
install the furnace in accordance with the require ments of the local utility or authority having juris diction.
The installer is referred to the American Standard “Installation of Gas Appliances and Gas Piping,” ASA Z21.30-1964, as a sound and practical guide to be followed when making the installation.
INSPECTION
Check the power supply available to be sure it
agrees with the information on the wiring diagram and the blower motor in the furnace.
Check the gas specification on the A.G.A. rating plate to be sure that the type of gas for which the unit is equipped is the same as the gas supply available.
Model 393 Furnace
FILTERS
When the furnace air distribution system is used for cooling, it is recommended in certain instances that the throw-away filters be discarded and the perma nent type, multi-velocity filters be substituted. The following table gives the air flows above which these high velocity filters should be used.
Size
80 100 1000 125
150 175 200
Air Flow - cfm
800
1240 1490 1800 1800
Leave these instructions on or near the furnace. Permanent filters are not required on Size 50.

UPFLOW

FURNACE

Model No.
50-393 46 26 16% 14% 20
80-393 46 100-393 46 26 18% 165% 20 125-393 46 150-393 175-393 51
200-393 250-393 300-393 350-393 400-393
A
51
•28%
■ 51 28%
MODEL
NO.
50-393 50,000
*80-393 ! 100-393 100,000 125-393 150-393 150,000
175-393 175,000 140,000
200-393 200,000 160,000 250-393 250,000
300-393 350-393
400-393
The 250, 300, 350 & 400 sizes are multiples of the 1 25, 1 50,
*For LP Gas, ModeJ Designation 80-V-393, A.G.A. Input 75,000,
283% 36%
Sizes 250 thru. 400 are multiples of sizes 125, 150, 175 and 200 respectively. Refer to the dimensions of smaller sizes to obtain overall’ dimensions for the
larger sizes. Provide clearance dimension between units for gas service and casing expansion. Refer to installation instructions for clearance.
C D E F G H
В
26 16%
26 20%
INPUT
*80,000
125,000
300,000 240,000 350,000 280,000
400,000 320,000
145% 20
185% 20
265%
28%
345% 345% 173%
36%
A.G.A. RATINGS BTU/HR GAS CONNECTION
23%
1%
23%
1%
3
1%
3 5" 18%
BONNET
40,000 64,000
80,000 100,000 120,000
200,000
'%
53%
2'%
43% (2)5" 33%
2'%
43% (2)5" 33%
21%
'%
1% 1% 1/2
'% '% % % %
%
% % %
(2) 1%
(2) % (2) 5% (21 % (2) % (2) %
(2) %
175 & 200 respectively.
Bonnet Capacity 60,000.
173% 173%
CAPACITY NAT.
J К
4" 12% 22% 4" 12% 5"
6" 25%
SIZES
MFD. Prop.
. '/2
’% '% % 1/2
% %
(2) % (2) 1/2
(2) % (2) %
22%
14% 22%
22%
23%
23% 25% 23% 25%
1%
(2) %
L M N P
23
12
1%
12 23
1%
14 23
1%
18 23
11%
25%
23 23 23
BOTTOM FILTER
SIZES
14 X 25 X 1 14 X 25 X 1 16 X 25 X 1 1 6 X 25 X 1 20 X 25 X 1
(2) 14 X 25 X 1 (2} 16 X 25 X 1
(1} 16 X 25 X 1
(1) 20 X 25 X 1
(1) 16 X 25 X 1 (1) 20 X 25 X 1
(2) 20 X 25 X 1 (4) 14 X 25 X 1
(2} 16 X 25 X 1
.(2) 20 X 25 X 1
(2) 16 X 25 X 1 (2) 20 X 25 X 1
24 24 24
SIDE FILTER
SIZES
14 X 25 X 1 14 X 25 X 1
20 X 25 X 1
(2) 16 X 25 X 1
(2) 16 X 25 X 1 (2) 20 X 25 X 1
[4} 1 6 X 25 X 1
[4} 1 6 X 25 X 1
(4) 16 X 25 X 1
1% 1%
1% 2% 8% 2% 2'%
R s
23%
2
1%
2 23% 2 23%
23%
2
4 30% 8% 4 8%
4
APPROX. SHIPPING WEIGHT
135 155 178 200 275
355
355 400
550 710
710
27% 27% 27% 27%
30%
30% .
t
393U
-2-

COUNTERFLOW

EZD
G
AIR OUTLET
A.G.A. RATINGS
MODEL
NO.
50-393, ^0,000
**80-393
100-393 125-393 1 25,000 1 00,000 75 150-393 150,000 120,000 80
* Add 1 when installed with base on combustible fioor.
** For LP Gas, Model Designation 80-V-393, A.G.A. Input 75,000, Bonnet Capacity 60,000.
BTU/HR
BONNET
CAPACITY
INPUT
80,000 64,000
100,000
40,000
80,000 75
* A В C D E F
75
26 16V4
75
26 26 26 20Й 18% 3 5" 283Л
143^
16'Л 14?4
16%
1814
28 26%
2% 2% 3 5"
5Ув 6" 25% 23%
4" 4"
G
22%
12% 12% 22% 14% 22% 18% 22%

FURNACE

*
H
J К
2% 27%
1%
2% 27%
1%
2% 27%
l'/2
2%
1%
4
2Ув
GAS CONNECTION
1
NAT. MFD.
% 'A
Vi 'A
27%
% 'A
30%
% %
SIZES
.'A 'A
'A 'A
Prop.
'A
%
FILTERS
16 X 20 X 1
16 X 20 X 1 Two 10 X 20 X 1 Two 14 X 20 X 1 Two 16 X 20 X 1
APPROX. SHIPPING
WEIGHT
(LB.)
166 185 210 235 325

BASEMENT

FURNACE

RATINGS
A.G.A.
ВТ
INPUT
200,000 250,000
400,000
U/HR
BONNET
CAPACITY
64,000
80,000 46 100,000 46 120,000 140,000 160,000 200,000 240,000 280,000
320.000
MODEL
NO.
50-393 50,000 40,000 *80-393 80,000 100-393 1 00,000 125-393 1 25,000
150-393 150,000 175-393 175,000 200-393 250-393 300-393 300,000 350-393 350,000 400-393
Ratings ore approved for altitudes to less for each 1,000 feet above sea
* For LP Gas, Model Designation 80-V-
A В c D
46 40% 16%
.46
40% 16% 40%
40% 20% 51 43% 28% 26% 17% 51 43% 36% 34% 17%
43% 36% 34%
51.
Sizes 250 through 400 are multiples of sizes 125, 150, 1.75, and 200 respectively. Refer to the dimensions of the smaller sizes to obtain overall dimensions for the larger sizes. Provide clearance dimensions between units for gas service and casing expansion. Refer to tnstallation instructions for minimum clearances.
2,000 feet for all gases. Ratings for altitudes over 2,000 feet are 4%
level. Return air compartment shipped separately, knocked down.
393, A.G.A. Input 75,000 Bonnet Capacity 60,000.
14% 14У, 20
18% 16У,
18Уа
E F G H J К
20
20 20
173%
23% 23%
3
3 53/s b" 43%
2-5" 30%
43%
2-5" 30%
4" 27% 4" 27%
5"
27% 2%
5"
27% 23% 30% 4
2% 2% 2%
2% 4% 4% 4%
2% 23%
4
4
■ 3 -
GAS CONNECTION
SIZES
NAT. MFD. Prop.
'A 'A 'A 'A 'A 'A 'A 'A
% % % 3% %
% 'A
% 3% •
'A 'A
3%
•%
FILTERS
14 X 25 X 1 166 14 X 25 X 1 16 X 25 X 1 213
20 X 25 X 1 Two 1 6 X 25 X 1 Two 1 6 X 25 X 1 Two 1 6 X 25 X 1
APPROX.
SHIPPING
WEIGHT
(LB.)
192
238 343 428 428
393U
GAS

CONTROL

OPTIONS

Gas and Control Type
Components
City Gas
04 05
Bryant Automatic Pilot Bryant Gas Control Valve
Gas Pressure Regulator *
Transformer
Pilot Gas Filter **
X
X
X
X X X
X X
100% Shut Off
T. C. Pilot
Pilot Relay
Inline 100% Shut Off Valve
- X -
- -
* On the sizes 50, 80, 100 & 125 for natural gas only,
the regulator is part of a combination regulator, main gas shut-off and pilot shut-off.
** Mfd. gas only.
LP Gas
02
X
X
X X
X
X
Figure 2 — Thermocouple Pilot
02 & 05 Controls
-
-
nr
4
Figure 4 — Slotted Port Burner
393U
Figure 1 - D2 Controls
641 Valve - 732 Pilot
-4-

LOCATING THE UNIT

1. This gas furnace is approved for use on combus tible floors except when installed as a counter-flow furnace. When installed as a counter-flow furnace on a combustible floor it must be installed on an approved base.
2. The furnace is A.G.A. approved for the following clearances from combustible construction in a clos
et or alcove installation.
Sides
.......................
0" (!")*
Back........................0" (1")*
t Top of plenum. . . 3" (0")*
Vent connector . . 6" (6")* Front
.......................
6" (6")*
* Figures shown in parentheses are approved clear ances when the furnace is installed as a counter flow furnace.
t Refer to ASA Z21.30-1954 for clearances in open
area installations.
This gas furnace is not approved for use with air conditioning units mounted upstream from the fur nace heat exchanger. The cooling coil should either be downstream of the furnace heat exchanger or the
flow of cooling air should be by-passed around the
heat exchanger. If this parallel arrangement is used,
the dampers or other means used to control the flow of air must be adequate to prevent chilled air from
entering the furnace. If these dampers are manually
operated, they must be equipped with means to pre
vent operation of either unit unless the damper is
in the full heat or full cool position.
8. In general, when the furnace is installed in a large open space, there will be enough air for com bustion and ventilation. However, when the unit is installed in buildings of unusually air-tight con struction, or when the furnace is located in very restricted spaces such as closets or utility rooms, special provisions must be made for combustion,
ventilating, and draft hood dilution air.
3. Locate the furnace as close to the chimney as possible. The furnace should also be located as centrally as possible to the distribution system.
4. Provide ample space for servicing and cleaning. Consult your local approval agency for any special
clearance requirements.
5. The furnace should be level. Use shims as required, if the floor or foundation is not completely
level.
6. Advise owner to leave all air passageways to the furnace free of obstruction in order that there will be no interference with combustion and venti
lating air.
7. The furnace is designed for use with summer air conditioning. Therefore consideration should be
given to leaving ample space for a later installation of air conditioning equipment, if the air conditioning equipment is not being installed as part of the orig
inal furnace installation. Bryant manufactures a coil box for upflow furnaces.
If air conditioning will be added at a later date, the coil box, if installed on the original installation,
will save time and money later. A coil box is not
needed for counter-flow furnaces.
When the unit is installed in a confined space, pro vide the confined space with two permanent open ings, one near the top of the enclosure and one near the bottom. These openings must freely communicate with interior areas that have adequate infiltration air from the outside. Each opening must have a free area of not less than one square inch for each 1000 Btu/hr of rated input of oil appliances located within the enclosure.
If it is not practicable to connect the two openings to interior space, or if the interior space has in sufficient infiltration air, then it is necessary to connect the openings to the outside. If air openings are directly to outdoors, the minimum free area should be one square inch per 3000 Btu/hr of input rating or in accordance with Z21.30-1964 or latest edition, “American Standards for Installation of Gas Appliances and Gas Piping.”
It is strongly recommended that the installer consult the “American Standards Installation of Gas Ap pliances and Gas Piping,” ASA Z21.30-1964.
9. In restricted spaces it is very important that the return air ducts be sealed firmly into the furnace so that the return air will be kept separate from the combustion and ventilating air.
- 5 -
393U

GAS PIPING

The gas supply line should be a separate line direct from the meter to the furnace. Check local utility for recommendations concerning existing lines. Choose a supply pipe size large enough to keep the pres sure loss as low as practicable. The supply pipe should never be smaller than the inlet to the gas valve. For pipe capacities at 0.3 inches w.c. pres
sure drop, see Iron Pipe Capacity table below.
Observe local codes for all gas pipe installation. The following are pertinent recommendations:
1. Avoid low spots in long runs of pipe. These low spots may trap water in the supply line. It is best to slope all pipe 1/4 inch in 15 feet to prevent traps. All horizontal runs should slope to risers.
Risers should be used to connect to the furnace and
to the meter.
2. Install a drip leg in the riser leading to the furnace. This drip leg will serve as a trap for dirt or condensate.
This drip leg can be installed by connecting a TEE to the riser leading to the furnace, so that the straight-through section of the TEE is vertical. Then connect a capped nipple to this TEE. The capped nipple should extend below the level of the gas controls, with the cap resting on the floor.
3. Install the main manual gas shut-off valve in the supply line five feet above the floor. Install the valve (supplied) so that the pilot manual cock is on
the inlet side of the valve. (See Figure 5.)
IRON PIPE CAPACITY (See Notes 1 & 2)
Length of Pipe
in Feet
15 30 45 60 75 90
105
120 150 109 180
1. All values shown are based on a pressure drop of 0.3" w.c. and using gas with a specific gravity value of 0.60 Consult local utility for local variations.
2. To convert to capacities for gas of different specific gravity, multiply the capacity values by the multi pliers shown at the extreme right on table.
Pipe Capacity in Cubic Feet Per Hour
for Diameters Shown
1/2" 3/4"
76 52 43 99 38 86 173 380
172 120 241 535 .40
77 70 141 65
1"
345
199
155
131
120 270
100
1-1/4" Specific Gravity
750 .35
435 .45
345 .55 310 285
242 225
Figure 6
Multiplier to Use
for Different Specific Gravity
Multiplier
1.31
1.23
1.16
.50
.60 .65 .962 .70
1.10
1.04
1.00
.926
393U
- 6 -
Sizes 50, 80,100 8s 125 using natural gas are equip
ped with a factory-installed combination pressure regulator and main shut off - pilot supply shut off valve. This control is inside the furnace cabinet. A separate manual shut-off valve is not supplied with these furnaces. Consult local codes regarding the need for placing a separate shut-off valve out
side the furnace cabinet as shown in Figure 5. Where a gum filter is required by local regulations,
place filter between manual gas cock and pilot
cock. See Figure 6. Place a ground joint union between the gas control
manifold and the manual gas shut-off valve.
4. Support all piping with appropriate straps, hang ers, etc. This will maintain proper slope of the lines as installed and will remove unnecessary strain on the furnace and its controls. It will also prevent the piping from being moved accidentally from its installed position.
5. Joint compounds — (pipe dope) should be applied sparingly and only to the male threads of the joints. Consult local supplier for type of compound to be
used with LP gas.
6. After all connections have been made, purge
the lines and check for leakage. Never purge a line
into a combustion chamber. Never use matches, candles, flame, or other sources of ignition for the
purpose of checking leakage.
3. Run pipe as directly as possible with a minimum number of turns. The maximum length of horizontal run should not exceed 75 percent of the height of the chimney.
4. Maintain a minimum of 1/4 inch per linear foot upward slope from the furnace to the chimney on all, horizontal runs.
5. Rigidly support the flue pipe with hangers and straps to insure that there will be no movement after installation.
6. Extend the flue connection pipe through the chimney wall flush with the inner face of the chim ney liner. Never connect into a chimney serving an open fireplace, unless the fireplace opening is
sealed off.
7. The chimney or gas vent should extend high enough above the roof or neighboring obstruction so that wind from any direction will not create a positive pressure in the vicinity of the outlet of the chimney or gas vent. The installer is referred to Part V of American Standard “Installation of
Gas Appliances and Gas Piping, ASA Z21.30-1964 for detailed information on chimney and gas vent use. In general the chimney or gas vent should extend 3 feet higher than the point of emergence through the roof, and at least 2 feet higher than any
object within a radius of 15 feet.
8. If more than one appliance is vented into the same chimney, the cross sectional area of the chim ney must be as large as the largest flue pipe being
connected, plus 50 percent of the cross sectional areas of the additional flue pipes being connected.
VENTING THE FURNACE
Consult local codes. Unless the local codes direct otherwise the furnace may be vented to a permanent chimney, or to a listed Type B or Type C gas vent.
This Bryant gas-fired furnace has a built in draft diverter. Therefore, it remains only to connect the furnace vent collar to the chimney or gas vent to be used. The following recommendations are made:
1. Select a flue connection material that is satis factory for the installation, and that meets the requirements of the local codes.
2. The flue connection pipe must be the same size as the outlet collar on the furnace. No reduction in this size is permissible in the pipe run.
9. If more than one appliance is manifolded into
the same flue connecting pipe, the cross sectional area of this manifold pipe must be as large as the sum of the cross sectional areas of the pipes con necting into it.
393U
- 7 -
BLOWERS
Direct Drive:
Listed below are the color codes for the different motor speed taps:
High Speed — Black Medium Speed - Blue Medium-low Speed — Yellow Low Speed - Red
Wiring Diagram, Figure 10 shows these furnaces as wired at the factory. Remove the transformer (two screws) from the junction box and expose the termi nal block. Check the fan control lead to see if it is connected to the motor speed tap that will give the
blower speed needed for the installation. If the fan control lead is not connected to the proper motor speed tap, or if you wish to change to another speed, simply switch the lead to the motor speed tap that you want connected. The lead is equipped with a spade connector.
Important:
If there are variations in voltage at the motor, there will be significant variations in the air de livery and temperature rise values. If the supplied voltage is less than 115 volts the blower will run slower and the temperature rise will be greater. On the other hand, if the voltage is greater than 115 volts the blower will run faster and the temperature
rise values will be lower. If there is doubt about the value and fluctuation of voltage consult local electric utility. The Number 4 tap should be used on installations where the voltage is 125 volts or higher.
Larger Motors:
For some installations the installer may wish to
substitute a larger motor than the one supplied the furnace. A separate mounting hole is provided in each end plate of the blower cage to be used when motors larger than 1/3 HP are installed. This is an extruded hole requiring self-tapping bolts. Figure 7 is a photo of a 1/2 HP motor mounted in place of a smaller motor. Note that the lower mounting hole is used. When ordering a 1/2 HP motor for installation be sure that the frame is a size 56. When ordering still larger motors, be sure that the frame size is compatible with space available in the blower com partment.
When the lower mounting holes are used it will, of
course, be necessary to use a longer belt than the one supplied with the smaller motors.
Belt Drive:
The motors supplied with the belt drive have an adjustable motor pulley. The air delivery rate is controlled by the position of this adjustable motor pulley. When the pulley is in the fully open position, the air delivery rate is at a minimum, and conse
quently the temperature rise across the furnace is
at the maximum.
When the pulley is in the fully closed position, the air delivery rate is maximum and consequently the temperature rise across the furnace is at a minimum. In order to change the opening on the pulley simply loosen the set screw with an Allen wrench. Screw the pulley clockwise to close, and counter-clockwise open. Once positioned, tighten the set screw on the
flat of the motor shaft.
393U
Figure 7
- 8 -
TABLE [
DIRECT DRIVE BLOWERS - HEATING ONLY
Furnace
Size
50 1/6
80 1/6 100 125
Motor
H.P.
1/5 1/4
No. of
Speed Taps
4 4 4 2
Ext. S. P.
Inches Water
0.12
0.12
0.15
0.20
Temp. Rise Degrees F.
50-70 75-95
75-95 1 870 75-95
Factory Setting
3 3
1
t Values shown are for 115 volt power supply
tt Temp rise is 60° F TABLE II
HEATING AND COOLING BLOWERS
Furnace
Size
50 1/6
80 1/6
80 1/3 4
100
100 1/3
125
d n a — does not apply * _ speed tap not recommended for heating § Values shown are for 115 volt power supply
Motor
H.P.
1/6
1/3
No. of
Speed Taps
4
4
4
4
4
80-90
Temp. Rise Degrees F.
Motor Speed Taps
Hi
*
*
* ie
*
*
Med
*
80-90
90-100
70-75
80-90
Med-Lo Lo
60-70
95-105
*
75-85
90-100
80-90
*
*
*
*
Ext. S.P.
In. w.c.
0.32
0.30
0.35
0.40
0.30
0.35
0.40
0.50
0.30
0.35
0.40
0.30
0.35
0.40
0.50
0.30
0.35
0.40
0.50
Cooling Air Flow-CFM§ at Motor Speeds Shown
Hi Med 710 810
785
760
1185
1160
1130
1080
830 805 775
1250 1215 1200 1110
1525 1500 1470 1400
85° F Temp. Rise
Med-Lo
610
660 645 625
980 965 940 895
675 655
635
1030 1015 1000
960
1060 1045
1030 1010
tCFM at
tt 615
695
1090
485 510
500
490
865 850 830 815
505 495 490
900 890 870 830
925 910 900 860
Lo
d n a d n a
d n a d n a
d n a d n a d n a d n a
d n a d n a
d n a d n a
d n a d n a d n a
d n a d n a d n a d n a
TABLE III
BELT DRIVE BLOWERS
Heating Heating and Cooling
Furnace
Size
80
100
125
150
175 1/3 5„ T.O. 1475 83° F 1/2 5 T.O.
200
Motor
H.P.
1/6 3 T.O. 1/4
. 1/4 4/2 T.O.
1/3
1/3
Factory
Setting
3 T.O. 730
5 T.O.
5 T.O.
CFM
@ 0.20
570
950
1160
1475 94° F
Temp.
Rise
97° F
95° F
92° F
90° F 1/2 5 T.O. 1160
Motor
H.P.
1/3 4 1/3 1/3
1/2 5 T.O. 1280 68° F
3/4
3/4
1/2
3/4 5
Factory
Setting
4 T.O. 930 75° F
4/2 T.O.
5 T.O. 1600
5 T.O. 1500 5
CFM
@0.20
T.O.
T.O. 1500 T.O. 1500
790
950 92° F 1080 36M
1500
Temp.
Rise 70° F 1080
90° F 65° F 2280 60M
81° F
81° F 93° F 2400 54M
93° F 2400 66M
Max. CFM
@ 0.40
1270
1800 1840
2400 54M 2400 66M
Approx.
A/C Capacity
30M 36M
48M 48M
393U
ELECTRICAL CONNECTIONS
START-UP AND ADJUSTMENT
All electrical connections are to be made in accord ance with the local codes governing such wiring.
A permanent, live, separately fused electric power supply, complete with manual switch, should be
provided for the furnace. The room thermostat should be located where it will
be in the natural circulating path of room air. Avoid
locations where the thermostat would be exposed to
cold air infiltration, drafts from windows, doors, or other openings leading to the outside; or exposure to air currents from warm or cold air registers; or to exposure where the natural circulation of the air is
cut off such as behind doors, above or below man
tels, shelves, etc.
The thermostat should not be exposed to heat from
nearby radiators, fireplaces, radios, televisions,
lamps, or rays from the sun. Nor should the thermo
stat be mounted on a wall containing pipes or warm
air ducts, or a flue or vent which could affect its
operation and prevent it from properly controlling the room temperature. Any hole in the plaster or
panel through which the wires pass from the thermo
stat should be adequately sealed with suitable material to prevent drafts from affecting the thermo
stat.
INSTALLING THE UNIT
Sizes 50, 80,100 & 125 for natural gas are complete ly assembled at the factory. All other units are
shipped fully assembled with the exception of the
manual main shut-off valve, pilot feed tube, and
pilot gas filter, which are shipped loose. The filter
is snpplied for manufactured gas units only.
The order to be followed in setting the unit in place and making all the necessary connections (gas, electric, venting, duct work, etc.) is left to the discretion of the installer. Recommendations listed on pages 5 to 7 of this instruction should be fol lowed. When making the gas piping installation as
described on page 6, assemble the pilot manual shut
off valve in the threaded boss provided at the inlet
side of the main manual gas shut-off valve. If the
installation is for manufactured gas, install the gum
filter between the two valves. Cut the pilot feed tube to the desired length and connect the pilot
manual shut-off to the pilot.
Check to be sure that all connections have been properly made, then proceed as follows:
Light the pilot using the procedure outlined on the Lighting Instruction Plate attached to the furnace. However, when lighting the pilot for the first time, perform the following additional steps:
1. If the supply line was not purged prior to con necting the furnace, it will be full of air. Since it would take a long time to vent this air through the small pilot port, it is recommended that the pilot supply line be disconnected at the pilot shut-off valve and the supply line be allowed to purge until the odor of gas is detected. Never purge gas lines
into the combustion chamber. Immediately upon
detection of gas odor, re-connect the pilot supply tube. Allow 5 minutes to elapse and light the pilot in accordance with the instructions on the front of
the furnace.
2. The pilot flame should be soft blue in color.
a. For city gas controls (D4) this flame should be
of sufficient length to provide good impingment on the mono-metal element of the Bryant pilot. Flame should extend upward between the carry-over ports
of the two adjacent burners.
b. For LP gas controls (D2), the flame should
surround the tip of the thermocouple element of the
pilot and extend downward to include 3/8 inch to
1/2 inch of the thermocouple. The flame must never come in contact with any other part of the thermo
couple or its lead wire. The flame lies under the
carry-over ports of the burners and merges with the carry-over flames. D5 controls have the same pilot.
3. If the pilot flame does not have the appearance
described above, it may be adjusted by means of the
manual pilot shut-off valve.
a. If the valve is equipped with an adjustable
screw, turn the handle to the full-open position and
remove the screw cap on the valve handle, thus
exposing the adjustable screw. Turn adjusting screw until flame has the desir-ed appearance. Replace
screw cap.
b. If the valve is not equipped with the adjusting
screw, adjustment of the flame is effected by alter
ing the position of the valve handle.
For furnaces with D2 or D5 controls the pilot feed
tube is connected to the pilot relay.
393U
- 10 -
Light Main Burners using the procedure contained on
the metal Lighting Instruction Plate attached to the front of the furnace.
Adjust Gas Rate. Set the room thermostat on call
for heat and adjust the gas rate as follows:
1. City Gases - Measure gas input at the meter. The burners are equipped with fixed orifices, sized to produce the rated input shown on the rating plate. If measured and rated input are not approximately the same, the gas pressure regulator may be adjusted
as follows:
a. To increase input: Turn pas pressure regu
lator adjusting screw ‘clockwise’. (Adjusting screw
is concealed under the regulator sealing cap).
b. To decrease input: Turn the adjusting screw
‘counter-clockwise’. The manifold pressure should
be set as follows:
Manufactured Gas - 3 inches w.c. Natural Gas - 3 inches w.c.
Maximum pressure departure from recommended pres
sure should be plus or minus 0.3 inches w.c.
2. LP Gas - LP gas units are not equipped with gas pressure regulators. Burner orifices are sized
to give the rated input at a manifold pressure of
11 inches w.c. Since meters are not normally used with LP gas, it will be necessary in most cases to check the manifold pressure and adjust the regulator at the supply tank to provide a pressure of 11 inches w.c.
3. If the input in item (1) or (2) above is too great or too little, install new orifices or re-drill the existing orifices (whichever is necessary) to obtain the rated input. Be sure the rated input is obtained without any appreciable change in manifold gas pressure.
Adjust Main Burner Flame — The main burner flame
should be clear blue, almost transparent, with a well­defined inner cone. If there is insufficient primary air, the flame will be yellow-tipped. If there is too much primary air the flame will be well-defined, but with a tendency to dance or lift off the burner ports.
CHECK CONTROLS
Bryant Diaphragm Gas Control Valve —if not already
checked when lighting the main burner, check the proper operation of this valve by moving the room thermostat pointer above and below room temperature and observe that the main burners light on call for heat and go off when the pointer is moved below the
room temperature setting. However, there will be
approximately a 30 second delay on ignition and
extinction.
Automatic Pilot - To check the pilot operation
follow the instructions below:
1. Set the room thermostat on call for heat.
There is a delay before burners light.
2. After burners have lit, shut off the pilot gas valve.
3. The automatic pilot will break the electrical circuit to the gas valve and the burners will shut off.
Limit Control - This control functions to shut off
the gas if the furnace becomes over-heated. The method of checking satisfactory operation is left to the discretion of the installer. Extreme caution
should always be employed.
Blower Adjustment - It is important that the blower
speed be adjusted before there is any attempt to
adjust the fan control switch.
The blower speed is set at the factory. Under no
circumstances should the temperature rise across the furnace be allowed to exceed 105 degrees F
on all sizes except the size 50. On the size 50,
the temperature rise must not be allowed to exceed
70 degrees F. After the desired air flow or tempera ture rise across the furnace has been obtained, the installation should be complete. However, it may be
necessary to change the factory setting on the Fan
Control Switch. This may be done as described under the discussion on controls.
1. Allow furnace to operate 15 minutes.
2. Adjust each burner by closing the air shutter until a slight yellow tip appears on the flame; then open the air shutter just enough to clear the yellow from the flame.
- n -
393U

CLEANING THE FURNACE

L Disconnect gas tubing from pilot.
2. Disconnect electrical lead from pilot. (In case of 100% shut-off controls disconnect pilot thermo couple lead from pilot relay).
3. Remove front plate from draft diverter (4 sheet
metal screws.)
4. Remove burners and pilot as follows.
a. Remove tinnerman clamp from burner holding
stud.
b. Lift burner off holding stud, twist and pull
forward.
c. Pilot is attached to one burner and is removed with that burner. It is not necessary to detach pilot before removing burner. See Figure 3 for photograph
of burner; also pilot attached.
5. Remove metal angle strip holding flue baffles in place. See Figure 8.
6. Remove flue baffles. See Figure 9.
7. Use a flexible-handled steel cleaning brush to loosen scale and soot. Remove these scrapings from
bottom of combustion chamber.
8. Re-assemble furnace by reversing the above pro
cedure. Note: There is a slot in the back of the heat exchanger for the back tip of the burner to fit into. When properly placed, the burner will fit into
this slot and will be level.

CARE AND MAINTENANCE

Care of Blowers. All motors on the belt drive blow
ers are provided with oil cups and should be oiled at least twice a year with a good grade of SAE 30 oil. The motors on the direct drive blowers are
sealed units and do not require the addition of oil.
Blower bearings are semi-permanently lubricated. This lubrication is normally good for 3 to 5 years. When necessary to add lubricant, use Plastic E, obtainable from Bryant’s Service Parts Department.
Filters. Filters should be examined frequently for
clogging due to dirt. The disposable filters should be replaced when they become dirty. Permanent type of filters may be cleaned using clear water. Be sure
to coat the filter with water soluble oil after clean
ing.
Cleaning. The heat exchanger should be examined
periodically to see if there has been an accumula tion of rust, soot, etc. Clean as required.
Figure 8 — Note metal angle strip held by 3 screws
393Ü
Figure 9 — Remove baffles
- 12 -
Figure 10 — Wiring for 4-Speed Direct Drive
Figure 11 — Wiring for 4-Speed Direct Drive Using Relay
- 13-
393U
393U
Figure 13 - Belt Drive Wiring
- 14-
<n
c
<
o
3
-+
3*
CQ
Q
3
(£2
O 3
o
3
TOP VIEW
ITEM DESCRIPTION
7” DIA MANIFOLD 5" PIPE
7” PIPE 10” X 7” REDUCING CAP 10” TEE
10” PIPE
7” ELBOW /
FRONT VIEW
NOTE:­USE THIS ARRANGEMENT FOR HIGH CEILING INSTALLATIONS.
Sizes 350 iV. 400
CO
VO
CO
c
c
•5’
c
3
SIZE
2.50
ELBOW
A 5”
6”
REDUCING CAP
B 8" X S’­8” X 6”
TEE
C
8”
PIPE (fccomm)
D 5” dia X 6” Ig 6” dia X 6” Ig
•“SPACF. SIZF 250 (TWO 125’&) 4” APART TO PROVIDE SPACE FOR GAS PIPING.
►—SPACE 300 (TWO ISO’s)
1” APART TO PERMIT EXPANSION AND CONTRACTION
PIPE
PIPE
F
8” 10” S"
MI N MIN
G
11” 0“
II
8”
E 5” 6“
Loading...