The Bryant Model 393 forced air, gas-fired furnace
may be installed as an
1.2.Upflow Furnace
Counter-Flow Furnace
(except sizes 175 and 200)
Basement Furnace
This instruction contains complete procedures for
installing the unit as an Upflow Furnace.
When the furnace is used as a counter-flow, a
counter-flow box and instructions are provided.
When it is used as a basement model, a drop duct
and instructions are provided. The Series C and D
Counter-Flow Boxes are interchangeable.
/1 \ fr
"iKJ V fl
Series D
39393D2
I
Rev. 3/17/65
Before beginning installation, read these instruc
tions carefully.
When making a Counter-Flow or Basement installa
tion, also read the separate instructions furnished
with the additional equipment required.
install the furnace in accordance with the require
ments of the local utility or authority having juris
diction.
The installer is referred to the American Standard
“Installation of Gas Appliances and Gas Piping,”
ASA Z21.30-1964, as a sound and practical guide
to be followed when making the installation.
INSPECTION
Check the power supply available to be sure it
agrees with the information on the wiring diagram
and the blower motor in the furnace.
Check the gas specification on the A.G.A. rating
plate to be sure that the type of gas for which the
unit is equipped is the same as the gas supply
available.
Model 393 Furnace
FILTERS
When the furnace air distribution system is used for
cooling, it is recommended in certain instances that
the throw-away filters be discarded and the perma
nent type, multi-velocity filters be substituted. The
following table gives the air flows above which
these high velocity filters should be used.
Size
80
1001000
125
150
175
200
Air Flow - cfm
800
1240
1490
1800
1800
Leave these instructions on or near the furnace. Permanent filters are not required on Size 50.
Sizes 250 thru. 400 are multiples of sizes 125, 150, 175 and 200 respectively. Refer to the dimensions of smaller sizes to obtain overall’ dimensions for the
larger sizes. Provide clearance dimension between units for gas service and casing expansion. Refer to installation instructions for clearance.
CDEFGH
В
2616%
2620%
INPUT
*80,000
125,000
300,000240,000
350,000280,000
400,000320,000
145%20
185%20
265%
28%
345%
345%173%
36%
A.G.A. RATINGS BTU/HRGAS CONNECTION
23%
1%
23%
1%
3
1%
35"18%
BONNET
40,000
64,000
80,000
100,000
120,000
200,000
'%
53%
2'%
43%(2)5"33%
2'%
43%(2)5"33%
21%
'%
1%1%1/2
'%
'%
%%%
%
%%%
(2) 1%
(2) %(2) 5%
(21 %(2) %(2) %
(2) %
175 & 200 respectively.
Bonnet Capacity 60,000.
173%
173%
CAPACITYNAT.
JК
4"12%22%
4"12%
5"
6"25%
SIZES
MFD.Prop.
. '/2
’%'%
%1/2
%%
(2) %(2) 1/2
(2) %(2) %
22%
14%22%
22%
23%
23%25%
23%25%
1%
(2) %
LMNP
23
12
1%
1223
1%
1423
1%
1823
11%
25%
23
23
23
BOTTOM FILTER
SIZES
14 X 25 X 1
14 X 25 X 1
16 X 25 X 11 6 X 25 X 1
20 X 25 X 1
Ratings ore approved for altitudes to
less for each 1,000 feet above sea
* For LP Gas, Model Designation 80-V-
AВcD
4640%16%
.46
40%16%
40%
40%20%
5143%28%26%17%
5143%36%34%17%
43%36%34%
51.
Sizes 250 through 400 are multiples of sizes 125, 150, 1.75, and 200 respectively. Refer to the dimensions
of the smaller sizes to obtain overall dimensions for the larger sizes. Provide clearance dimensions between
units for gas service and casing expansion. Refer to tnstallation instructions for minimum clearances.
2,000 feet for all gases. Ratings for altitudes over 2,000 feet are 4%
level. Return air compartment shipped separately, knocked down.
393, A.G.A. Input 75,000 Bonnet Capacity 60,000.
14%
14У,20
18%16У,
18Уа
EFGHJК
20
20
20
173%
23%
23%
3
3
53/sb"
43%
2-5"30%
43%
2-5"30%
4"27%
4"27%
5"
27%2%
5"
27%23%
30%4
2%
2%
2%
2%
4%
4%
4%
2%
23%
4
4
■ 3 -
GAS CONNECTION
SIZES
NAT. MFD. Prop.
'A'A
'A'A
'A'A'A
'A
%%%
3%
%
%'A
%
3% •
'A
'A
3%
•%
FILTERS
14 X 25 X 1166
14 X 25 X 1
16 X 25 X 1213
20 X 25 X 1
Two 1 6 X 25 X 1
Two 1 6 X 25 X 1
Two 1 6 X 25 X 1
APPROX.
SHIPPING
WEIGHT
(LB.)
192
238
343
428
428
393U
GAS
CONTROL
OPTIONS
Gas and Control Type
Components
City Gas
0405
Bryant Automatic Pilot
Bryant Gas Control Valve
Gas Pressure Regulator *
Transformer
Pilot Gas Filter **
X
X
X
XXX
XX
100% Shut Off
T. C. Pilot
Pilot Relay
Inline 100% Shut Off Valve
-X-
--
* On the sizes 50, 80, 100 & 125 for natural gas only,
the regulator is part of a combination regulator, main
gas shut-off and pilot shut-off.
** Mfd. gas only.
LP Gas
02
——
X
X
XX
X
X
Figure 2 — Thermocouple Pilot
02 & 05 Controls
-
-
nr
4
Figure 4 — Slotted Port Burner
393U
Figure 1 - D2 Controls
641 Valve - 732 Pilot
-4-
LOCATING THE UNIT
1. This gas furnace is approved for use on combus
tible floors except when installed as a counter-flow
furnace. When installed as a counter-flow furnace
on a combustible floor it must be installed on an
approved base.
2. The furnace is A.G.A. approved for the following
clearances from combustible construction in a clos
et or alcove installation.
Sides
.......................
0" (!")*
Back........................0" (1")*
t Top of plenum. . . 3" (0")*
Vent connector . . 6" (6")*
Front
.......................
6" (6")*
* Figures shown in parentheses are approved clear
ances when the furnace is installed as a counter
flow furnace.
t Refer to ASA Z21.30-1954 for clearances in open
area installations.
This gas furnace is not approved for use with air
conditioning units mounted upstream from the fur
nace heat exchanger. The cooling coil should either
be downstream of the furnace heat exchanger or the
flow of cooling air should be by-passed around the
heat exchanger. If this parallel arrangement is used,
the dampers or other means used to control the flow
of air must be adequate to prevent chilled air from
entering the furnace. If these dampers are manually
operated, they must be equipped with means to pre
vent operation of either unit unless the damper is
in the full heat or full cool position.
8. In general, when the furnace is installed in a
large open space, there will be enough air for com
bustion and ventilation. However, when the unit is
installed in buildings of unusually air-tight con
struction, or when the furnace is located in very
restricted spaces such as closets or utility rooms,
special provisions must be made for combustion,
ventilating, and draft hood dilution air.
3. Locate the furnace as close to the chimney as
possible. The furnace should also be located as
centrally as possible to the distribution system.
4. Provide ample space for servicing and cleaning.
Consult your local approval agency for any special
clearance requirements.
5. The furnace should be level. Use shims as
required, if the floor or foundation is not completely
level.
6. Advise owner to leave all air passageways to
the furnace free of obstruction in order that there
will be no interference with combustion and venti
lating air.
7. The furnace is designed for use with summer air
conditioning. Therefore consideration should be
given to leaving ample space for a later installation
of air conditioning equipment, if the air conditioning
equipment is not being installed as part of the orig
inal furnace installation.
Bryant manufactures a coil box for upflow furnaces.
If air conditioning will be added at a later date, the
coil box, if installed on the original installation,
will save time and money later. A coil box is not
needed for counter-flow furnaces.
When the unit is installed in a confined space, pro
vide the confined space with two permanent open
ings, one near the top of the enclosure and one near
the bottom. These openings must freely communicate
with interior areas that have adequate infiltration
air from the outside. Each opening must have a free
area of not less than one square inch for each
1000 Btu/hr of rated input of oil appliances located
within the enclosure.
If it is not practicable to connect the two openings
to interior space, or if the interior space has in
sufficient infiltration air, then it is necessary to
connect the openings to the outside. If air openings
are directly to outdoors, the minimum free area
should be one square inch per 3000 Btu/hr of input
rating or in accordance with Z21.30-1964 or latest
edition, “American Standards for Installation of Gas
Appliances and Gas Piping.”
It is strongly recommended that the installer consult
the “American Standards Installation of Gas Ap
pliances and Gas Piping,” ASA Z21.30-1964.
9. In restricted spaces it is very important that the
return air ducts be sealed firmly into the furnace so
that the return air will be kept separate from the
combustion and ventilating air.
- 5 -
393U
Loading...
+ 10 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.