Bryant 359AAV User Manual

Page 1
359AAV DIRECT OR NON--DIRECT VENT 4--WAY MULTIPOISE CONDENSING GAS FURNACE
Installation Instructions
SPECIAL VENTING REQUIREMENTS
FOR INSTALLATIONS IN CANADA
t, PVC Cement for Flue Gas Venting, rated Class IIA, 65
(1)
deg C. must be used with this venting system - do not mix primers and cements from one manufacturer with a vent system from a different manufacturer. Follow the manufacturer’s instructions in the use of primer and cement and never use primer or cement beyond its expiration date.
The safe operation, as defined by ULC S636, of the vent system is based on following these installation instructions, the vent system manufacturer’s installation instructions, and proper use of primer and cement. All fire stop and roof flashing used with this system must be UL listed material. Acceptability under Canadian standard CSA B149 is dependent upon full compliance with all installation instructions. Under this standard, it is recommended that the vent system be checked once a year by qualified service personnel.
The authority having jurisdiction (gas inspection authority, municipal building department, fire department, etc) should be consulted before installation to determine the need to obtain a permit.
*IPEX System 636™ is a trademark of IPEX Inc.
CONSIGNES SPÉCIALES POUR L’IN-
STALLATION DE VENTILLATION AU
CANADA
L’installation faite au Canada doit se conformer aux exigences du code CSA B149. Ce systême de ventillation doit se composer de tuyaux, raccords, ciments et apprêts conformes au ULC S636. La tuyauterie de ventillation des gaz, ses accessoires, le terminal concentrique mural ainsi que l’ensemble du drain de condensat extérieur ont été certifiés ULCS 636 pour l’application des composantes Royal Pipe, IPEX PVC qui sont certifiées à ce standard. Au Canada, l’apprêt et le ciment doivent être du même fabricant que le système d’évacuation. L’apprêt GVS-65 (Purple) et le ciment-solvant GVS-65 doivent être utilisé avec les Royal Pipe. Système IPEX 636, apprêt PVC/CPVC, Purple pour évacuation des gaz de combustion et système IPEX 636(1)t, ciment PVC pour évacuation des gaz de combustion, coté classe IIA, 65 deg C. doivent être utilisés avec le système d’évacuation IPEX 636 – Ne pas combiner l ’apprêt et le ciment d’un manufacturier avec un système d’évacuation d’un manufacturier différent.
Bien suivre les indications du manufacturier lors de l’utilisation de l’apprêt et du ciment et ne pas utiliser ceux-ci si la date d’expiration est atteinte.
L’opération sécuritaire, tel que définit par ULC S636, du système de ventilation est basé sur les instructions d’installation suivantes, ainsi que l’usage approprié de l’apprêt et ciment. Tout arrët feu et solin de toit utilisés avec ce système doivent être des matériaux listés UL. L’acceptation du standard Canadien CSA B419 est directement relié à l’installation conforme aux instructions ci­haut mentionnées. Le standard Canadien recommande l’ inspection par un personel qualifié et ce, une fois par année.
Les autoritées ayant juridiction (inspecteurs de gas, inspecteurs en bâtiments, département des incendies, etc) devraient être consultées avant l’installation afin de déterminer si un permis est requis.
1
Page 2
Required Notice for Massachusetts Installations
IMPORTANT
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA--54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements: a. For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used
in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back--up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
359AAV
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard
wired carbon monoxide detector with alarm and battery back--up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner
shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one--half (1/2) inch in size, ”GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
5. EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
(1.) The equipment listed in Chapter 10 entitled ”Equipment Not Required To Be Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
(2.) Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part for residential purposes.
c. MANUFACTURER REQUIREMENTS -- GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
d. MANUFACTURER REQUIREMENTS -- GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When
the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
e. A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
2
Page 3
NOTE: Read the entire instruction manual before starting the installation.
NOTE: Please retain these instructions with the furnace after installation for future reference.
SAFETY CONSIDERATIONS
!
CAUTION
FURNACE RELIABILITY HAZARD
Failure to follow this warning could result in personal injury, death or property damage. Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure.
Application of this furnace should be indoors with special attention given to vent sizing and material combustion air requirements, gas input rate, air temperature rise, unit leveling, and unit sizing.
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory--authorized and listed kits or accessories when modifying this product.
Recognize safety information. This is the safety--alert symbol
. When you see this symbol on the furnace and in instructions
or manuals, be alert to the potential for personal injury. Understand the signal words DANGER, WARNING, and
CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury. Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing and gloves when handling parts.
TABLE OF CONTENTS
PAGE
IMPORTANT INFORMATION 2.........................
SAFE INSTALLATION REQUIREMENTS 4...............
COMBUSTION & VENTILATION AIR 9..................
CONCENTRIC TERMINATION 31.......................
GAS SUPPLY & PIPING 33.............................
ELECTRICAL WIRING 37..............................
DUCTWORK & FILTER 38.............................
359AAV
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with unit and other safety precautions that may apply.
These instructions cover the minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
Wear safety glasses and work gloves. Have a fire extinguisher available during start--up and adjustment procedures and service calls.
CHECKS & ADJUSTMENTS 40.........................
FURNACE MAINTENANCE 42.........................
SEQUENCE OF OPERATION & DIAGNOSTICS 42.........
I
G
S
E
N
D
C
E
Use of the AHRI Certified TM Mark indicates a manufacturer’s participation in the program. For verification of certification for individual products, go to www.ahridirectory.org.
D
CERTIFIED
E
R
I
T
F
I
Always Ask For
3
Page 4
SAFE INSTALLATION
REQUIREMENTS
S Install correct filter type and size. S Unit MUST be installed so electrical components are protected
from direct contact with water.
!
WARNING
FIRE, EXPLOSION, AND ASPHYXIATION HAZARD
Failure to follow this warning could result in personal injury or death.
Improper adjustment, alteration, service, maintenance or installation could cause personal injury, death and/or property damage.
Installation or repairs made by unqualified persons could result in hazards to you and others. Installation MUST conform to local codes or, in the absence of local codes, with codes of all governmental authorities having jurisdiction.
The information contained in this manual is intended for use by a qualified service agency that is experienced in such work,
359AAV
is familiar with all precautions and safety procedures required in such work, and is equipped with the proper tools and test instruments.
NOTE: This furnace is design--certified by the CSA International (formerly AGA and CGA) for installation in the United States and Canada. Refer to the appropriate codes, along with this manual, for proper installation.
S Use only the type of gas approved for this furnace (see Rating
Plate on unit). Overfiring will result in failure of heat
exchanger and cause dangerous operation. (Furnaces can be converted to Propane gas with approved kit.)
S Install this furnace only in a location and position as specified
in “Installation” of these instructions.
S Provide adequate combustion and ventilation air to the furnace
as specified in “ Combustion and Ventilation Air” of these instructions.
S Combustion products must be discharged outdoors. Connect
this furnace to an approved vent system only, as specified in “Vent and Combustion Air Piping” of these instructions.
S Never test for gas leaks with an open flame. Use a
commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in “Gas Supply and Piping, Final Check” of these instructions.
S Always install furnace to operate within the furnace’s intended
temperature--rise range with a duct system which has an external static pressure within the allowable range, as specified in the Service and Maintenance manual. See furnace rating plate.
S When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by a duct(s) sealed to the furnace casing and terminating outside the space containing the furnace.
S A gas--fired furnace for installation in a residential garage must
be installed as specified in “Installation” of these instructions.
S This furnace is not to be used for temporary heating of
buildings or structures under construction.
S This furnace is NOT approved for installation in mobile
homes, trailers or recreation vehicles.
S Seal around supply and return air ducts.
Safety Rules
Your unit is built to provide many years of safe and dependable service providing it is properly installed and maintained. However, abuse and/or improper use can shorten the life of the unit and create hazards for you, the owner.
The U.S. Consumer Product Safety Commission encourages installation of carbon monoxide alarms. There can be various sources of carbon monoxide in a building or dwelling. The sources could be gas--fired clothes dryers, gas cooking stoves, water heaters, furnaces, gas--fired fireplaces, wood fireplaces.
Carbon monoxide can cause bodily injury and/or death. Carbon monoxide or “CO” is a colorless and odorless gas produced when fuel is not burned completely or when the flame does not receive sufficient oxygen.
Therefore, to help alert people of potentially dangerous carbon monoxide levels, you should have a commercially available carbon monoxide alarm that is listed by a nationally recognized testing agency in accordance with Underwriters Laboratories Inc. Standard for Single and Multiple Station Carbon Monoxide Alarms, ANSI/UL 2034 or the CSA 6.19--01 Residential Carbon Alarming Devices installed and maintained in the building or dwelling concurrently with the gas--fired furnace installation (see Note below). The alarm should be installed as recommended by the alarm manufacturer’s installation instructions.
There can be numerous sources of fire or smoke in a building or dwelling. Fire or smoke can cause bodily injury, death, and/or property damage. Therefore, in order to alert people of potentially dangerous fire or smoke, you should have fire extinguisher and smoke alarms listed by Underwriters Laboratories installed and maintained in the building or dwelling (see Note below).
NOTE: The manufacturer of your furnace does not test any alarms and makes no representations regarding any brand or type of alarms.
To ensure safe and efficient operation of your unit, you should do the following:
1. Thoroughly read this manual and labels on the unit.
This will help you understand how your unit operates and the hazards involved with gas and electricity.
2. Do not use this unit if any part has been under water.
Immediately call a qualified service technician to inspect the unit and to replace any part of the control system and any gas control which has been under water.
3. Never obstruct the vent grilles, or any ducts that provide air to the unit. Air must be provided for proper combustion and ventilation of flue gases.
4
Page 5
Frozen Water Pipe Hazard
INSTALLATION
!
WATER DAMAGE TO PROPERTY HAZARD
Failure to follow this caution may result in property damage. Do not leave your home unattended for long periods during
freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes and resultant damage.
Your furnace is designed solely to provide a safe and comfortable living environment. The furnace is NOT designed to ensure that water pipes will not freeze. It is equipped with several safety devices that are designed to turn the furnace off and prevent it from restarting in the event of various potentially unsafe conditions.
If your furnace remains off for an extended time, the pipes in your home could freeze and burst, resulting in water damage.
If the structure will be unattended during cold weather you should take these precautions.
1. Turn off the water supply to the structure and drain the wa­ter lines if possible and add an antifreeze for potable water to drain traps and toilet tanks. Open faucets in appropriate areas.
2. Have someone check the structure frequently during cold weather to make sure it is warm enough to prevent pipes from freezing. Instruct them on a service agency to call to provide service, if required.
3. Install a reliable remote sensing device that will notify somebody of freezing conditions within the home.
CAUTION
-- o r --
-- o r --
Winter Shutdown
If you go away during the winter months and do not leave the heat on in your home, the plastic transition box and the condensate trap on the furnace must be protected from freeze damage. (See Fig. 10 through Fig. 19 )
1. Disconnect the drain fitting that is located downstream of the combustion blower. Insert a funnel into the hose and pour four(4) ounces of sanitary type (RV) antifreeze into the condensate trap. Reconnect the stub on the vent drain fitting. Secure with the hose clamp.
2. Disconnect the condensate trap. Insert a funnel into the hose and and pour four(4) (ounces of sanitary type (RV) antifreeze into the plastic Transition box. Squeeze the hose together near the end and quickly reconnect the hose to the stub on the condensate trap. Secure with the hose clamp.
When you return home, your furnace will be ready to start, as it is not necessary to drain the antifreeze from the furnace.
5
/8″(16 mm)OD rubber hose from the vent
5
/8″ (16 mm) OD rubber hose to the
3
/4″ (19 mm) OD rubber hose from the
3
/4″ (19 mm) OD rubber
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
This furnace can NOT be common vented or connected to any type B, BW or L vent or vent connector, nor to any portion of a factory--built or masonry chimney. If this furnace is replacing a previously common-vented furnace, it may be necessary to resize the existing vent and chimney to prevent oversizing problems for the other remaining appliance(s). See Venting and Combustion Air Check in Gas Vent Installation section. This furnace MUST be vented to the outside.
Installation Positions
This furnace can be installed in an upflow, horizontal (either left or right) or downflow airflow position. DO NOT install this furnace on its back. For the upflow position, the return air ductwork can be attached to either the left or right side panel and/or the bottom. For horizontal and downflow positions, the return air ductwork must be attached to the bottom. The return air ductwork must never be attached to the back of the furnace.
Location and Clearances
1. Refer to Fig. 1 for typical installation and basic connect­ing parts required. Refer to Fig. 4 for typical horizontal direct vent installation and basic connecting parts required. Supply and return air plenums and duct are also required.
2. If furnace is a replacement, it is usually best to install the furnace where the old one was. Choose the location or evaluate the existing location based upon the minimum clearance and furnace dimensions (Fig. 2).
!
FROZEN AND BURST PIPE HAZARD
Failure to follow this caution may result in property damage. Special precautions MUST be made is installing furnace in
an area which may drop below freezing. This can cause improper operation or damage to equipment. If furnace environment has the potential of freezing, the drain trap and drain line must be protected. The use of electric heat tape or RV antifreeze is recommended for these installations. (See “Condensate Trap Freeze Protection Section”)
CAUTION
359AAV
5
Page 6
Aluminum or non--rusting shield recommended.
°
°
*8(203.2mm) Min. 20(6.1m) Max. in same atmospheric zone
Vent Pipes MUST be supported Horizontally and
Vertically
* Increase minimum from 8 tained temperatures 0
(See Vent Termination Shielding for dimensions).
Inlet Pipe (not used on Single Pipe model)
*8(203.2mm) Min.
DISCHARGE AIR
(203.2mm) to 18″(457.2mm) for cold climates (sus-
F(-17°C) and below for 24 or more consecutive hours).
20(6.1m) Max. in sameatmospheric zone
359AAV
Fig. 1 -- Typical Upflow Installation
See Vent Termination Shielding in Vent Section.
Inlet Pipe (not used on Single Pipe model)
Vent Pipes MUST be supportedHorizon­tally and Vertically
*
Increase minimum from 8″to 18″(203 to 457 mm) for cold climates (sustained temperatures
F (-18°C ) and ) below for 24 or more consecutive hours).
0
*8″ Min. (203 mm) 20Max. in same (6 M) atmosphericzone
Couplingoninside and outside ofwall to restrain vent pipe
*8″ Min. (203 mm) 20Max. (6.1 M) in same atmospheric zone
25--23--33a
Fig. 2 -- Typical Downflow Installation
Installation Requirements
1. Install furnace level.
2. This furnace is NOT to be used for temporary heat of
buildings or structures under construction.
3. Install furnace as centralized as practical with respect to the heat distribution system.
4. Install the vent pipes as short as practical, and in accordance to these instructions. (See Ve n t a n d Combustion Air Piping section).
5. Maintain clearance for fire safety and servicing. A front clearance of 24(607 mm) required and 30(762mm) recommended for access to the burner, controls and filter. See clearance requirements in Fig. 4.
6. Use a raised base for upflow furnace if the floor is damp or wet at times.
7. For downflow installations, non combustible subbase must be used under the furnace unless installation is on a non combustible floor surface. This requirement applies even when a coil box or cabinet is used.
Coupling on ends of exhaust pipe. Total pipe & coupling out­side structure = 8
(203.2mm)
2 5 -- 23 -- 3 3
A07700
8Min. (203 mm)
A07762
8. For horizontal installations, line contact is permissible only between lines formed by intersection of back and two sides of furnace jacket, and building joists, studs or framing.
9. Residential garage installations require:
S Burners and ignition sources installed at least 18″ (457 mm)
above the floor.
S Located or physically protected from possible damage by a
vehicle.
10. Local codes may require a drain pan under the entire furnace and condensate trap when the furnace is installed in attic application.
This furnace may be used for construction heat provided that all the following conditions are met:
S The furnace is permanently installed with all electrical wiring,
piping, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
S The furnace is controlled by a thermostat. It may not be “hot
wired” to provide heat continuously to the structure without thermostatic control.
S Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
S The temperature of the return air to the furnace is maintained
between 55° F(13° C) and 80° F(27° C) , with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
S The air temperature rise is within the rated rise range on the
furnace rating plate, and the firing rate has been set to the rating plate value.
S The filters used to clean the circulating air during the
construction process must be either changed or thoroughly cleaned prior to occupancy.
S The furnace, ductwork and filters are cleaned as necessary to
remove drywall dust and construction debris from all HVAC system components after construction is completed.
S After construction is complete, verify furnace operating
conditions including ignition, input rate, temperature rise and venting according to these instructions.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Do NOT operate furnace in a corrosive atmosphere containing chlorine, fluorine or any other damaging chemicals, which could shorten furnace life.
Refer to Combustion & Ventilation Air section, Contaminated Combustion Air for combustion air evaluation and remedy.
6
Page 7
Furnace Installation Considerations
The installation of the furnace for a given application will dictate the position of the furnace, the airflow, ductwork connections, vent and combustion air piping. Consideration must be given to the following:
Condensate Trap and Drain Lines
The supplied condensate trap must be attached to the furnace side panel on either the left or right side. For horizontal installations, the drain trap is vertically attached to the side panel below the furnace. A minimum clearance of 6(152 mm) below the furnace is required for the condensate trap. Downward slope of the condensate drain line from the condensate trap to the drain location must be provided. Adequate freeze protection of the drain trap and the drain line must be provided. See “Condensate Drain Trap” section for further details.
Leveling
Proper leveling of the furnace must be provided to insure proper drainage of the condensate from the furnace. The furnace must be level to within1/4″ (6 mm) from front to back and from side to side for upflow and downflow installations or top to bottom for horizontal installations.
Vent and Combustion Air Connections
For venting information literature, contact www.Bryant.com with the complete model and serial number of the furnace.
On the Dual Certified furnace, the vent and combustion air pipes attach to the furnace through the top panel for the upflow and horizontal installations. For the downflow installation, the vent and combustion air pipes attach to the furnace through the alternate locations on the furnace side panels.
NOTE: On the Direct Vent furnace, the vent pipe attaches to the furnace through the side panels. The combustion air pipe attaches to the top panel or to the alternate location on the side panel.
On the Single Pipe furnace, the vent pipe attaches to the furnace through the furnace side panels.
NOTE: Repositioning of the combustion blower is required for the vent pipe connection to the furnace through the “right side” panel. See “Vent and Combustion Air Piping” section for further details.
Horizontal Furnace Installation
Inlet Pipe (not used on Single Pipe model)
Ven t Pipe
Condensate Trap
NOTE: 6
bottom clearance required for condensate trap.
A07703
Fig. 3 -- Typical Horizontal Installation
This furnace can be installed horizontally in an attic, basement, crawl space, alcove, or suspended from a ceiling in a basement or utility room (See Fig. 3). Do not install furnace on its back as safety control operation will be adversely affected.
359AAV
7
Page 8
F
AIR INTAKE
VENT
A B
TOP
H
G
E
LEFT SIDE
TRAP (KO) (COUNTERFLOW)
GAS
VENT
AIR INTAKE (KO) (ALTERNATE)
TRAP (KO) UPFLOW/HORIZONTAL
1
359AAV
2
/
4
13
(336.6)
(57.2)
1
/
4
THERMOSTAT
(KO)
13
4
(122.2)
/
16
611/
(177.5)
(177.8)
7
16
ELECTRICAL
11/
(318)
11/
16
(34.9)
13/
8
241/
(611.2)
175/
16
(439.7)
111/
16
(42.9)
4
(27)
1311/
16
(347.7)
3111/
16
(804.9)
(758.8)
297/
8
283/
4
(730.3)
16
1913/
16
(503.2)
FRONT
MINIMUM CLEARANCES TO COMBUSTIBLE
MATERIALS FOR ALL UNITS -- in (mm)
REAR 0
FRONT (combustion air openings in furnace and in structure)
Required For Service
3(76.2)
*
24(609.6)
ALL SIDES Of SUPPLY PLENUM 1(25.4)
SIDES 0
VENT 0
TOP OF FURNACE 1(25.4)
*
30(762mm) clearance recommended for furnace removal.
Horizontal position: Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket, and building joists, studs or framing.
NOTE: Evaporator “A” coil drain pan dimensions may vary from furnace duct opening size. Always consult evaporator specifications for duct size requirements.
Furnace is designed for bottom return or side return.
Return air through back of furnace is NOT allowed.
1
1
/
4
(31.7)
7
1
(47.6 )
D
C
359AAV036060
359AAV036080
359AAV048080
359AAV060100
/
8
Unit
Capacity
215/
(549.3)
8
24
(609.6)
47/
(123.8)
8
Drawing is representative, but some models may vary
BOTTOM
1
/
23
8
(587.4) (98.4)
37/
8
ALL DIMENSIONS: in (mm)
Cabinet Bottom Top
A B
1
/
19
8
(485.8)
3
/
22
4
(577.9)
223/
4
(577.9)
241/
2
(622.3)
175/
(447.7)
211/
(539.8)
211/
(539.8)
(584.2)
C
D E F G H
21/
143/
8
8
(54)
115/
4
16
(49.2)
115/
16
4
(49.2)
7
23
/
16
(11.1)
(374.7)
183/
(476.3)
183/
(476.3)
23
(584.2)
43/
4
8
(111.1)
43/
8
4
(111.1)
43/
4
8
(111.1)
43/
8
(111.1)
41/
(114.3)
41/
(114.3)
41/
(114.3)
41/
(114.3)
7
/
2
8
(73)
11/
GAS (KO)
(109.5)
45/
16
3
(60.3 )
2
/
8
(27)
16
281/
2
(723.9)
1
18
/
2
(469.9)
RIGHT SIDE
3
/
4
TYPE
(19.1)
TRAP (KO) (COUNTERFLOW)
ELECTRICAL (KO)
AIR INTAKE (KO)
297/
(758.8)
16
8
273/
(690.6)
16
215/
(549.3)
413/
(122.2)
11/
(27)
175/
(439.7)
16
16
(177.8)
8
16
111/
16
(42.9)
7
4
(123.8)
3
/
1
16
(30.2)
913/
16
(249.2)
3311/
(855.7)
KO = KnockOut
21/
(63.5)
21/
(63.5)
25/
(66.7)
21/
(57.2)
91/
2
2
(241.3)
91/
2
2
(241.3)
113/
8
8
(288.9)
121/
4
4
(311.2)
2
2
2
2
7
/
8
(ALTERNATE)
VENT (KO) TRAP (KO) HORIZONTAL
THERMOSTAT
215/
(549.3)
24
(609.6)
40
(1016)
21/
4
(57.2)
131/
4
(336.6)
(KO)
8
17/
(47.6)
8
Specifications are subject to change without notice.
Fig. 4 -- Dimensions and Clearances
8
A09268B
Page 9
Gas Vent
Ventilated Attic
Top Above Insulation
Outlet Air (1)
This installation NOT approved in Canada
Gable Vent
alternate Inlet Air (1)
Gas Vent
Sot Vent
Ventilated Attic
Top Above Insulation
Gable Vent
Outlet Air (1)
Gas Vent
Outlet Air (2)
OutletAir (1)
Ventilated Crawl Space
alternate Inlet Air (1)
Inlet Air (1)
Fig. 5 -- Outside Air
(This is ONLY a guide. Subject to codes of country having jurisdiction).
COMBUSTION & VENTILATION AIR For Single Pipe Installation
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Use methods described here to provide combustion and ventilation air.
Furnaces require ventilation openings to provide sufficient air for proper combustion and ventilation of flue gases. All duct or openings for supplying combustion and ventilation air must comply with the gas codes, or in the absence of local codes, the applicable national codes.
Combustion and ventilation air must be supplied in accordance with one of the following:
NOTE: The Combustion & Ventilation Air Section in this document, uses tables and information from the ANSI Z223.1/NFPA 54. For use in Canada, use CSA B149.1 for this information.
1. Section 9.3, Air for Combustion and Ventilation, of the National Fuel Gas Code, (NFGC), ANSI Z223.1--2009/NFPA 54--2009 in the U.S.,
2. Sections 8.2, 8.3, 8.5, 8.6, 8.7, and 8.8 of National Stand­ard of Canada, Natural Gas and Propane Installation Code (NSCNGPIC), CSA B149.1--10 in Canada,
3. Applicable provisions of the local building code.
This furnace can NOT be common vented or connected to any type B, BW or L vent or vent connector, nor to any portion of a factory--built or masonry chimney. Multistory venting is NOT permitted. If this furnace is replacing a previously common-vented furnace, it may be necessary to resize the existing vent and chimney to prevent oversizing problems for the other remaining appliance(s). See “Venting and Combustion Air Check” in this section. This furnace MUST be vented to the outside.
When the installation is complete, check that all appliances have adequate combustion air and are venting properly. See Venting
Sot Vent
Inlet Air (2)
Inlet Air (1)
Minimum One Inlet and One Outlet Air Supply is Required MaybeinanyCombinationShown
Inlet Air Opening Must be Within12 in.
Outlet Air Opening Must be Within12 in. (304.8mm) of ceiling
(1) 1 Square Inch per 4000 BTUH
(2) 1 Square Inch per 2000 BTUH
Inlet Air (2)
(304.8mm) of oor
A07704
And Combustion Air Check in “Gas Vent Installation” Section in this manual.
Outdoor Combustion Air Method
A space having less than 50 cubic feet per 1,000 BTUH (4.8 M3/kW) input rating for all gas appliances installed in the space requires outdoor air for combustion and ventilation.
Air Openings and Connecting Ducts
1. Total input rating for all gas appliances in the space
MUST be considered when determining free area of open­ings.
2. Connect ducts or openings directly to the outdoors.
3. When screens are used to cover openings, the openings
MUST be no smaller than
1
/4″ (6 mm) mesh.
4. The minimum dimension of air ducts MUST NOT be less
than 3(76 mm).
5. When sizing a grille, louver, or screen use the free area of
opening. If free area is NOT stamped or marked on grill or louver, assume a 20% free area for wood and 60% for met­al. Screens shall have a mesh size not smaller than
1
/4″ (6
mm) .
Confined Space Installation
NOTE: A confined space is defined as an area with less than 50 cubic feet per (1.4 for all gas appliances installed in the area.
3
M) 1,000 BTUH (2.33 cm2/kW) input rating
Requirements
1. Provide the space with sufficient air for proper combustion and ventilation of flue gases using horizontal or vertical ducts or openings.
2. Fig. 5 illustrates how to provide combustion and ventila­tion air when two permanent openings, one inlet and one outlet, are used.
a. One opening MUST commence within 12(305 mm)
of the floor and the second opening MUST commence within 12(305 mm) of the ceiling.
b. Size openings and ducts per Ta b le 1 .
c. Horizontal duct openings require 1 square inch of free
area per 2,000 BTUH (1,1 cm for all gas appliances in the space (see Ta bl e 1 ) .
9
2
/kW) of combined input
359AAV
Page 10
d. Vertical duct openings or openings directly communic-
ating with the outdoors require 1 square inch of free area per 4,000 BTUH (5.5 cm
2
/kW) for combined in-
put of all gas appliances in the space (see Ta b le 1 ).
3. When one permanent outdoor opening is used, the opening requires:
a. 1 sq. in of free area per 3,000 BTUH (7 cm
combined input of all gas appliances in the space (see Table 1) and
b. not less than the sum of the areas of all vent connect-
ors in the space.
The opening shall commence within 12(305 mm) of the top of the enclosure. Appliances shall have clearances of at least 1(25 mm) from the sides and back and 6from the front. The opening shall directly communicate with the outdoors or shall communicate through a vertical or horizontal duct to the outdoors
359AAV
BTUH
Input
Rating
60,000 30 sq. in. (194 cm2) 20 sq. in. (129 cm2) 15 sq. in. (97 cm2) 5(127 mm)
80,000 40 sq. in. (258 cm2) 26.7 sq. in. (172 cm2) 20.0 sq. in. (129 cm2) 5(127 mm)
100,000 50 sq. in. (322 cm2) 33.3 sq. in. (215 cm2) 25 sq. in. (161 cm2) 6(152 mm)
EXAMPLE: Determining Free Area
Furnace 100,000 Furnace 100,000
Two Horizontal Ducts
(sq. in./2,000 BTUH)
Water Heater
+
+
30,000
Water Heater
30,000
Minimum Free Area Required for Each Opening or Duct to Outdoors
=
=
2
/kW) for
Table 1 – Free Area
Single Opening
(sq. in./3,000 BTUH)
Total Input
(130,000 ÷ 4,000)
Total Input
(130,000 ÷ 2,000)
or spaces (crawl or attic) that freely communicate with the outdoors.
4. Combination of Indoor and Outdoor Air shall have:
a. Indoor openings that comply with the Indoor Com-
bustion Air Method below and
b. Outdoor openings located as required in the Outdoor
Combustion Air Method above and
c. Outdoor openings sized as follows.
(1.) Calculate the Ratio of all Indoor Space volume
divided by required volume for Indoor Combus- tion Air Method.
(2.) Outdoor opening size reduction Factor is 1 minus
the Ratio in 1) above.
(3.) Minimum size of Outdoor openings shall be the
size required in Outdoor Combustion Air Meth­od above multiplied by reduction Factor.
Two Vertical Ducts or Open-
ings
(sq. in./4,000 BTUH)
= 32.5 Sq. In. Vertical
= 65 Sq. In. Horizontal
Round Duct
(sq. in. /4,000
BTUH)
Indoor Combustion Air (Unconfined Space)
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Most homes will require additional air from outdoors for combustion and ventilation. A space with at least 50 cubic feet per 1,000 Btuh (4.8 M tight construction may need outdoor air, supplied through ducts, to supplement air infiltration for proper combustion and ventilation of flue gasses.
Standard and Known- Air-Infiltration Rate Methods
© NFPA&AGA
Indoor air is permitted for combustion and ventilation, if the Standard or Known--Air--Infiltration Rate Method is used.
The Standard Method may be used, if the space has no less volume than 50 cubic feet per 1,000 BTUH (4.8 M rating for all gas appliances installed in the space. The standard
3
/kW) Input rating or homes with
3
/kW) input
method permits indoor air to be used for combustion and ventilation air.
The Known Air Infiltration Rate Method shall be used if the infiltration rate is known to be less than 0.40 air changes per hour (ACH) and equal to or greater than 0.10 ACH. Infiltration rates greater than 0.60 ACH shall not be used. The minimum required volume of the space varies with the number of ACH and shall be determined per Ta bl e 2 or Equations 1 and 2. Determine the minimum required volume for each appliance in the space, and add the volumes together to get the total minimum required volume for the space.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to supply additional air by means of ventilation grilles or ducts could result in personal injury or death.
An unconfined space or homes with tight construction may not have adequate air infiltration for proper combustion and ventilation of flue gasses. Most homes will require additional air.
10
Page 11
Table 2 – Minimum Space Volume for 100% Combustion and Ventilation Air from Indoors -- Ft3(M3)
Other Than Fan --- Assisted Total
ACH 30 40 50 50 75 100 125
0.60 1,050 (29.7) 1,400 (39.2) 1,750 (49.0) 1,250 (35.0) 1,875 (52.5) 2,500 (70.0) 3,125 (87.5)
0.50 1,260 (35.3) 1,680 (47.0) 2,100 (58.8) 1,500 (42.0) 2,250 (63.0) 3,000 (84.0) 3,750 (105.0)
0.40 1,575 (44.1) 2,100 (58.8) 2,625 (73.5) 1,875 (52.5) 2,813 (78.8) 3,750 (105.0) 4,688 (131.3)
0.30 2,100 (58.8) 2,800 (78.4) 3,500 (98.0) 2,500 (70.0) 3,750 (105.0) 5,000 (140.0) 6,250 (175.0)
0.20 3,150 (88.2) 4,200 (117.6) 5,250 (147.0) 3,750 (105.0) 5,625 (157.5) 7,500 (210.0) 9,375 (262.5)
0.10 6,300 (176.4) 8,400 (235.2 10,500 (294.0) 7,500 (210.0) 11,250 (315.0) 15,000 (420.0) 18,750 (525.0)
0.00 NP NP NP NP NP NP NP
ACH = Air Changes per Hour NP = Not Permitted Table 2 Minimum Space Volumes were determined by using the
following equations from the National Fuel Gas Code ANSI Z223.1/NFPA 54--2009, 9.3.2.2:
1. For appliances other than fan--assisted appliances (such as a draft hood--equipped water heater), calculate using the following equation:
Required Volume
2. For fan--assisted appliances (such as this furnace), calcu- late using the following equation:
Required Volume
where:
I
= all appliances other than fan--assisted input in Btu
other
per hour
I
= fan--assisted appliance input in Btu per hour
fan
ACH = air change per hour (percent of volume of space
exchanged per hour, expressed as a decimal)
3. For purposes of this calculation, an infiltration rate greater than 0.60 ACH shall not be used in the equations above.
The following requirements apply to the Standard Method and to the Known Air Infiltration Rate Method.
S Adjoining rooms can be considered part of a space, if there are
no closeable doors between rooms.
S Combining spaces on the same story. Each opening shall have
a minimum free area of at least 1 in. mm2/kW) of the total input rating of all appliances in the space but not less than 100 in. commence within 12 in. (305 mm) of the top, and one opening shall commence within 12 in. (305 mm) of the bottom, of the enclosure. The minimum dimension of air openings shall not be less than 3 in. (76 mm).
S Combining spaces in different stories. The volumes of spaces
on different stories shall be considered as communicating spaces where such spaces are connected by one or more openings in doors or floors having a total minimum free area of
2
2in.
/1,000 BTUH (4,400 mm2/kW) of total input rating of all
appliances.
S An attic or crawl space may be considered a space that freely
communicates with the outdoors provided there are adequate ventilation openings directly to outdoors. Openings MUST remain open and NOT have any means of being closed off.
other
fan
(1,000 Btuh)
3
21 ft
²
ACH
15 ft
²
ACH
2
(0.06 m2). One opening shall
(
1000 Btu / hr
3
2
I
(
1000 Btu / hr
/1,000 BTUH (2,200
I
fan
other
)
)
Ventilation openings to outdoors MUST be at least 1 square inch of free area per 4,000 BTUH (550 mm rating for all gas appliances in the space.
S In spaces that use the Indoor Combustion Air Method,
infiltration should be adequate to provide air for combustion, ventilation and dilution of flue gases. However, in buildings with unusually tight construction, additional air MUST be provided using the methods described in section titled Outdoor Combustion Air Method:
S Unusually tight construction is defined as Construction with:
1. Walls and ceilings exposed to the outdoors have a continu­ous, sealed vapor barrier. Openings are gasketed or sealed and
2. Doors and openable windows are weather stripped and
3. Other openings are caulked or sealed. These include joints around window and door frames, between sole plates and floors, between wall--ceiling joints, between wall panels, at penetrations for plumbing, electrical and gas lines, etc.
Ventilation Air
Some provincial codes and local municipalities require ventilation or make--up air be brought into the conditioned space as replacement air. Whichever method is used, the mixed return air temperature across the heat exchanger MUST not fall below 60° so that flue gases will not condense excessively in the heat exchanger. Excessive condensation will shorten the life of the heat exchanger and possibly void your warranty.
Venting and Combustion Air Check
NOTE: If this installation replaces an existing furnace from a commonly vented system, the original venting system may no longer be sized to properly vent the attached appliances. An improperly sized venting system may cause the formation of condensate in the vent and the leakage or spillage of vent gases. To make sure there is adequate combustion air for all appliances, MAKE THE FOLLOWING CHECK.
Typical Gas Water Heater
The following information is supplied to allow the installer to make adjustments to the setup of existing appliances, IF REQUIRED, based on good trade practices, local codes, and
Fan--- assisted Total (1,000’s Btuh)
2
Vent Pipe
Fig. 6 -- Vent Check
Draft Hood
/kW) of total input
Match
359AAV
A07688
11
Page 12
good judgement of the installer. Manufacturer does NOT take responsibility for modifications made to existing equipment.
Air Check” in this section. This furnace MUST be vented to the outside.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow the steps outlined below for each appliance connected to the venting system being placed into operation, could result in carbon monoxide poisoning or death:
The following steps shall be followed for each appliance connected to the venting system being placed into operation, while all other appliances connected to the venting system are not in operation:
1. Seal any unused openings in the venting system.
2. Inspect the venting system for proper size and horizontal pitch, as required in the National Fuel Gas Code, ANSI Z223.1/NFPA 54 or CSA B149.1, Natural
359AAV
Gas and Propane Installation Code and these instructions. Determine that there is no blockage or restriction, leakage, corrosion and other deficiencies which could cause an unsafe condition.
3. As far as practical, close all building doors and windows and all doors between the space in which the appliance(s) connected to the venting system are located and other spaces of the building.
4. Close fireplace dampers.
5. Turn on clothes dryers and any appliance not connected to the venting system. Turn on any exhaust fans, such as range hoods and bathroom exhausts, so they are operating at maximum speed. Do not operate a summer exhaust fan.
6. Follow the lighting instructions. Place the appliance being inspected into operation. Adjust the thermostat so appliance is operating continuously.
7. Test for spillage from draft hood equipped appliances at the draft hood relief opening after 5 minutes of main burner operation. Use the flame of a match or candle. (Fig. 6.)
8. If improper venting is observed, during any of the above tests, the venting system must be corrected in accordance with the National Fuel Gas Code, ANSI
Z223.1/NFPA 54 and/or CSA B149.1, Natural Gas and Propane Installation Code.
9. After it has been determined that each appliance connected to the venting system properly vents when tested as outlined above, return doors, windows, exhaust fans, fireplace dampers and any other gas--fired burning appliance to their previous conditions of use.
For Two Pipe Installation (Direct Vent)
This furnace can NOT be common vented or connected to any type B, BW or L vent or vent connector, nor to any portion of a factory--built or masonry chimney. If this furnace is replacing a previously common-vented furnace, it may be necessary to resize the existing vent and chimney to prevent oversizing problems for the other remaining appliance(s). See “Venting and Combustion
VENT AND COMBUSTION AIR PIPING
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Use methods described here to provide combustion and ventilation air.
Dual Certified (359AAV Models)
This furnace is certified as a category IV appliance. This furnace can be installed as a direct vent furnace using outside air for combustion or the furnace can use air from inside the structure for combustion. The INLET air pipe is optional. If combustion air comes from inside the structure, adequate make up air MUST be provided to compensate for oxygen burned. See Confined Space Installation in the Combustion and Ventilation Air chapter. If combustion air is drawn from outside the structure, it MUST be taken from the same atmospheric pressure zone as the vent pipe.
Contaminated Combustion Air
Installations in certain areas or types of structures will increase the exposure to chemicals or halogens that may harm the furnace.
The following areas or types of structures may contain or have exposure to the substances listed below. The installation must be evaluated carefully as it may be necessary to provide outside air for combustion.
S Commercial buildings. S Buildings with indoor pools. S Furnaces installed in laundry rooms. S Furnaces installed in hobby or craft rooms. S Furnaces installed near chemical storage areas. S Permanent wave solutions for hair. S Chlorinated waxes and cleaners. S Chlorine based swimming pool chemicals. S Water softening chemicals. S De--icing salts or chemicals. S Carbon tetrachloride. S Halogen type refrigerants. S Cleaning solvents (such as perchloroethylene). S Printing inks, paint removers, varnishes, etc. S Hydrochloric acid. S Sulfuric Acid. S Solvent cements and glues S Antistatic fabric softeners for clothes dryers. S Masonry acid washing materials.
Vent and Combustion Air Piping Guidelines
This furnace is approved for venting with Schedule 40 PVC, CPVC, ABS fittings, and Cellular Core and SDR--26 PVC pipe.
.
12
Page 13
Applicable ASTM Standards for Vent Materials
Materials
ABS D1527 __ F628
PVC D1785 D2241 F891
CPVC F441 F442 --- --- F438 --- --- F493
ABS to
PVC
Sch. 40
Pipe
--- --- --- --- --- --- --- --- --- --- D3138
SDR Pipe
Cell Core Pipe
Fittings Primer
D2468
&
D2661
D2466
&
D2665
Solvent
Cement
--- --- D2235
F656 D2564
NOTE:
1. In Canada, all pipe, fittings & cements must conform to applicable CSA standards or to local codes having juris­diction.
2. Only use solvent cements that are marked for use with the specific venting material.
3. ABS to PVC transition joints REQUIRE a special solvent cement that meets the requirements of ASTM D3138.
4. Refer to ASTM D2855 for general procedure to use for cementing plastic pipe and fittings.
NOTE: In order to create a seal that allows future removal of pipe, RTV sealant MUST be used on the inlet pipe where it joins to the furnace.
NOTE: All vent piping MUST be installed in compliance with local codes or ordinances, these instructions, good trade practices, and codes of country having jurisdiction.
1. Determine the best routing and termination for the vent pipe and air inlet pipe by referring to all of the instructions and guidelines in this Section.
2. Determine the size required for the vent pipe and air inlet pipe.
3. Loosely assemble all venting parts without adhesive (pipe joint cement) for correct fit before final assembly.
4. Furnace shall be installed so as to prevent the accumula­tion of condensate.
5. Use of vertical piping is preferred because there will be some moisture in the flue gases that may condense as it leaves the vent pipe (See Instructions For Horizontal Ve n ts ).
6. The vertical vent pipe MUST be supported so that no weight is allowed to rest on the combustion blower.
7. Exhaust vent piping or air inlet piping diameter MUST NOT be reduced.
8. All exhaust vent piping from the furnace to termination MUST slope upwards. A minimum of
1
/4″ (6 mm) per foot of run is required to properly return condensate to the fur­nace drain system.
9. Use DWV type long radius elbows whenever possible, as they provide for the minimum slope on horizontal runs and they provide less resistance in the vent system. If DWV elbows cannot be used, use two, 45° elbows when pos­sible. On horizontal runs the elbows can be slightly mis­aligned to provide the correct slope.
10. All horizontal pipe runs MUST be supported at least every
five feet with galvanized strap or other rust resistant ma­terial. NO sags or dips are permitted.
11. All vertical pipe runs MUST be supported every six feet
where accessible.
12. The minimum pipe run length is 2(.6 M).
13. The piping can be run in the same chase or adjacent to supply or vent pipe for water supply or waste plumbing. It can also be run in the same chase with a vent from another 90+ furnace.
NOTE:InNO case can the piping be run in a chase where temperatures can exceed 140° F(60° C). or where radiated heat from adjacent surfaces would exceed 140° F(60° C).
14. The vent outlet MUST be installed to terminate in the same atmospheric pressure zone as the combustion air in­let.
15. The vent system can be installed in an existing unused chimney provided that:
S Both the exhaust vent and air intake run the length of the
chimney.
S No other gas fired appliance or fireplace (solid fuel) is vented
into the chimney.
S The top of the chimney MUST be sealed flush or crowned up
to seal against rain or melting snow so ONLY the piping protrudes.
S The termination clearances showninFig.7and8 are
maintained.
16. Furnace applications with vertical vents requiring vent dia­meter increaser fittings must have increaser fittings in­stalled in vertical portion of the vent. Condensate will be trapped in the vent if the vent diameter is increased prior to having an elbow turned upward. This could cause nuis­ance tripping of the pressure switch.
Combustion Air and Vent Piping Insulation Guidelines
NOTE: Use closed cell, neoprene insulation or equivalent. If Fiberglass or equivalent insulation is used it must have a vapor barrier. Use R values of 7 up to 10,(2.1 --3.0M) R--11if exposure exceeds 10. If Fiberglass insulation is used, exterior to the structure, the pipe MUST be boxed in and sealed against moisture.
1. When the vent or combustion air pipe height above the roof exceeds 30(762 mm), or if an exterior vertical riser is used on a horizontal vent to get above snow levels, the ex­terior portion MUST be insulated.
2. When combustion air inlet piping is installed above a sus­pended ceiling, the pipe MUST be insulated with moisture resistant insulation such as Armaflex or other equivalent type of insulation.
3. Insulate combustion air inlet piping when run in warm, hu­mid spaces.
Sizing Combustion Air and Vent Pipe
Consult Ta bl e 3 to select the proper diameter exhaust and combustion air piping. Exhaust and combustion air piping is sized for each furnace BTUH size based on total lineal vent length (on inlet or outlet side), and number of 90° elbows required. Two 45° elbows can be substituted for one 90° elbow. The elbow or elbows used for vent termination outside the structure ARE counted, including elbows needed to bring termination above expected snow levels. The elbow inside the furnace on the 359AAV IS NOT included in the count.
359AAV
13
Page 14
Table 3 – Pipe Diameter Table
PIPE DIAMETER TABLE
359AAV MODEL
60,000 BTUH Furnaces
10(3.0 M) & (3) 90° elbows with 1.5(13 mm) PVC pipe
40(12.1M)&(5)90° elbows with 2(51 mm) PVC pipe or
70(21.3M)&(5)90° elbows with 3(76 mm) PVC pipe
80,000 BTUH Furnace
40(12.1M)&(5)90° elbows with 2(51 mm) PVC pipe or
40(12.1M)&(5)90° elbows with 3(76 mm) PVC pipe
100,000 BTUH Furnace
10 (3.0 M) & (2) 90° elbows with 2(51 mm) PVC pipe or
40(12.1M)&(5)90° elbows with 3(76 mm) PVC pipe
Elbows are DWV Long Radius Type for 2(51 mm) and 3 (76 mm) vents.
If more than five elbows are required, reduce the length of both the inlet and exhaust pipes 5(1.5 M) for each additional elbow used. If less than five elbows are required, the length can be INCREASED by 5(1.5 M) for each additional elbow NOT used.
359AAV
NOTE: It is allowable to use larger diameter pipe and fitting than shown in the tables but not smaller diameters than shown.
For “Concentric Termination Kit” Venting see Table 4 in this manual.
Vent Termination Clearances
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Inlet and outlet pipes may NOT be vented directly above each other.
1. Determine termination locations based on clearances spe­cified in following steps and as shown in Fig. 7, 8, Fig. 21 through Fig. 23.
For “Concentric Termination Kit” clearances, see Fig. 30
through Fig. 35 in this manual.
2. For Direct Vent Installation refer to Fig. 7 for vent termin­ation clearances.
3. For Single Pipe Installation refer to Fig. 8 for vent termin­ation clearances.
14
Page 15
12 inches (30 cm) for applieances >10,000 Btuh(3 kW) and <
100,000 Btuh(30kW), 36 inches (91cm) for
appliances > 100,000 Btuh(30kW)
359AAV
Fig. 7 -- Direct Vent Termination Clearance
15
A06675
Page 16
359AAV
Fig. 8 -- Other than Direct Vent Termination Clearance
16
Page 17
Condensate Drain Trap
This furnace removes both sensible and latent heat from the products of combustion. Removal of the latent heat results in condensation of the water vapor. The condensate is removed from the furnace through the drains in the plastic transition and the vent fitting. The drains connect to the externally mounted condensate drain trap on the left or right side of the furnace.
The start--up of a new furnace will involve a cycle or two of the furnace to properly prime the condensate trap with water. Until the trap is fully primed, some condensate will be pulled into the combustion blower. The furnace may cycle on the pressure switch connected to the plastic transition box due to condensate buildup. After the trap is primed, the condensate will start draining from the furnace. The combustion blower will clear out any remaining condensate in the blower housing through the vent fitting downstream of the blower. Note that the condensate trap can also be primed by pouring water into the
1
the
/2″ ID drain hose from either the gutter or the white PVC tee trap. Using a funnel pour eight (8) ounces of water into1/2″(13 mm) ID drain hose. Water will flow through the drain hose and into the condensate drain trap. This will prime both the vent and the transition sides of the trap. Reconnect the drain hose to the original component, either the gutter or the PVC tee trap.
The condensate drain trap supplied with the furnace MUST be used. The drain connection on the condensate drain trap is sized
3
for
/4″ PVC or CPVC pipe, however alternate1/2″(13 mm) CPVC (nominal5/8″ O.D.) or vinyl tubing with a minimum inner diameter (I.D.) of5/8″ may also be used, as allowed by local codes. Alternate drain pipes and hoses may be used as allowed by local codes.
The drain line must maintain a slope toward the drain.1/4″ (6 mm) per foot is recommended. Installation of an overflow line is recommended when the1/4″ (6 mm) per foot slope to the condensate drain cannot be maintained. A drain tube clip is included in the furnace to prevent kinking/buckling of the drain tube. The clip should remain in the furnace (between the door switch plate and the blower shelf, Fig.
9) during operation. See Fig. 19 for proper routing and installation of the overflow.
DO NOT trap the drain line in any other location than at the condensate drain trap supplied with the furnace.
!
CAUTION
FROZEN AND BURST WATER PIPE HAZARD
Failure to follow this caution may result in property damage. If a condensate pump is installed, a plugged condensate drain
or a failed pump may cause the furnace to shut down. Do not leave the home unattended during freezing weather without turning off water supply and draining water pipes or otherwise protecting against the risk of frozen pipes.
1
/2″ drain hose. Remove
1
/2″(13 mm) ID
1
/4″ (6 mm) per foot downward
If possible, DO NOT route the drain line where it may freeze. The drain line must terminate at an inside drain to prevent freezing of the condensate and possible property damage.
1. A condensate sump pump MUST be used if required by
local codes, or if no indoor floor drain is available. The condensate pump must be approved for use with acidic condensate.
2. A plugged condensate drain line or a failed condensate pump will allow condensate to spill. If the furnace is in­stalled where a condensate spill could cause damage, it is recommended that an auxiliary safety switch be installed to prevent operation of the equipment in the event of pump failure or plugged drain line. If used, an auxiliary safety switch should be installed in the R circuit (low voltage) ONLY.
3. If the auxiliary switch in the condensate pump is used, the furnace may shut down due to a blocked condensate line or failed pump. To prevent frozen water pipes see the “Frozen Water Pipe Hazard” Installation Section of this manual.
Drain Tube
Blower Shelf
Representative drawing only, some models may vary in appearance.
Clip
Door Switch
A07705
Fig. 9 -- Drain Tube Clip Location
Condensate Drain Trap Freeze Protection
Special precautions MUST be made if installing furnace in an area which may drop below freezing. This can cause improper operation or damage to the equipment. If the the furnace environment has the potential of freezing, the drain trap and drain line must be protected. Use 3 to 6 watt per foot at 115 volt, 40° F (4° C) self--regulating shielded and waterproof heat tape. Wrap the drain trap and drain line with the heat tape and secure with the ties. Follow the heat tape manufacturer’s recommendations.
359AAV
17
Page 18
Plastic Caps (2) Yellow or black
Ven t Dr ain &Clamps
Dual Pressure Switch Detail
FLOW
AIR
Coupling & Clamps (Optional)
Drain Tee
Drain Tube Black Rubber
1
/
ID & Clamps
2
EXHAUST
INLET
On Some Models ONLY
V
E
N
T
IN
ON
OFF
Relief Tube Black Rubber
3
/
ID
16
359AAV
Drain Tube Corrugated & Clamps
Drain Connector Black PVC
3
/
PVC X1/
4
(Loose parts bag)
2
CPVC
Casing Grommet Black Rubber
5
/
ID
8
(Loose parts bag)
Drain Line Vent Tee
1
/
CPVC (Field supplied)
2
Representative drawing only, some models may vary in appearance.
Upflow Installations Top Vent (See Fig.
10)
S Remove knockout from the side of the furnace casing where
drain tube will exit.
5
S Install casing grommet (black rubber
grommet -- in loose parts bag)
S Install the
1
/2″(13 mm) CPVC street elbow on discharge of trap
S Install the black PVC tube connector (
(13 mm) CPVC from loose parts bag) as shown in the illustration above.
5
S Cut the black drain tube (
to length to fit between trap and tube connector through
/8″(16 mm) ID -- in loose parts bag)
grommet.
S Clamp both ends of the drain tube using clamps provided.
/8″ (16 mm) ID
3
/4″ (18 mm) PVC x1/2″
5
/
ID
8
3
/
PVC or
4
Drain Tube Black Rubber Cut length to fit (Loose parts bag)
Fig. 10 -- Upflow Installations Top Vent
S Glue the CPVC street elbow to the trap using appropriate
cleaner and solvent cement.
S The field supplied
vent tee must vent outside the furnace cabinet (see exploded view above).
NOTE: It is recommended that all PVC piping and fitting connections be fit up and inspected before final cementing. Tr ap must be primed before operation. Verify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
NOTE: “PVC” is used as a generic term. Pipe and fitting materials used must be acceptable to the local code officials having jurisdiction.
Single Pressure Switch
Street Elbow
1
/
CPVC
2
(Loose parts bag)
5
/
ID & Clamps,
8
3
/4″ PVC or1/2″(13 mm) CPVC drain line
2 5 -- 2 4 -- 8 0
A07706
18
Page 19
Plastic Cap
°
°
Yellow or black
Coupling & Clamps (Optional)
PVC Coupling
2
INLET
On Some Models ONLY
Ven t Dr ain &Clamps
Either: The PVC Drain Tee or a field supplied 2
Dual Pressure Switch Detail
FLOW
FLOW
AIR
AIR
Drain Connector Black PVC
3
/
PVC X1/
4
(Loose parts bag)
2
CPVC
Casing Grommet Black Rubber
5
/
ID
8
(Loose parts bag)
PVC Tee
EXHAUST
Tee Trap White PVC (loose parts bag)
Drain Tube Black Rubber
1
/
ID & Clamps
2
Drain Tube Corrugated
5
/
ID & Clamps
8
V
E
N
T
IN
ON
OFF
3
/
ID Rubber Tube
16
Single Pressure Switch
359AAV
SIDE VIEW
Rotate downward
to 10
5
NOTE: Built--in channel will
be angled 5° to 10° also.
Drain Line Vent Tee
3
/
4
PVC or1/
CPVC (Field supplied)
2
Representative drawing only, some models may vary in appearance.
Fig. 11 -- Upflow Installations Vent through Left Side
Upflow Installations Vent through Left Side (See Fig. 11)
S Remove drain tee from inducer discharge and remove black
drain tube (1/2″(13 mm) ID) from bottom of drain tee.
S Install Vent Pipe grommet in side of casing. S Cut an appropriate length of 2(51 mm) PVC pipe long
enough to exit the cabinet and connect the vent drain to either:
— A standard field supplied 2(51 mm) PVC tee, or —A2″ PVC coupling fastened onto the drain tee.
S Install tee trap into bottom of tee. S Remove knockout from the side of the furnace casing where
drain tube will exit.
S Install the1/2″ (13 mm)CPVC street elbow on discharge of trap S Install the black PVC drain connector (
1
/2″(13 mm) CPVC from loose parts bag) as shown in the
3
/4″(19 mm) PVC x
25--24--81
A07707
illustration above.
5
S Cut the black drain tube (
/8″(16 mm) ID -- in loose parts bag) to length to fit between trap and tube connector through grommet.
S Clamp both ends of the drain tube using clamps provided. S Glue the CPVC street elbow to the trap using appropriate
cleaner and solvent cement.
S Connect the tee trap and the main drain line exiting the casing
as shown in Fig. 19.
NOTE: It is recommended that all PVC piping and fitting connections be fit up and inspected before final cementing. Both
the internal trap and the external tee trap must be primed before operation. Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
19
Page 20
°
°
Plastic Cap
Yellow or black
INLET
On Some Models ONLY
Ven t Dr ain &Clamps
Dual
Relief Tube Black Rubber
3
/
ID
16
V
E
N
T
IN
ON
OFF
2
PVC
Coupling
Either: The PVC Drain Tee or a field supplied 2
PVC Tee
Single Pressure Switch Detail
Pressure Switch
EXHAUST
359AAV
Drain Tube Corrugated
5
/
ID&Clamps
8
AIRFLOW
Tee Trap White PVC (loose parts bag)
Elbows Tubes (2) & Clamps Black,
1
/
ID (loose parts bag)
2
Barbed Coupling, (loose parts bag)
1
/
OD
2
Drain Line Vent Tee
1
/
CPVC (Field supplied)
or
2
3
/
PVC
4
SIDE VIEW
Rotate downward 5
to 10
Drain Connector Black PVC
3
/
PVC X1/
4
(Loose parts bag)
2
CPVC
NOTE: Built--in channel will
be angled 5° to 10° also.
Representative drawing only, some models may vary in appearance.
Fig. 12 -- All Models Vent Through Right Side
All Models Vent through Right Side (See Fig. 12)
S Disconnect the black drain tube between the drain vent and the
trap.
S Rotate the inducer 180° for a right side vent after loosening the
4 inducer attachment screws. Reinstall and retighten the inducer screws to 20(2.26 newton meter) pounds torque.
S Using the
bag connect together with the 2 short tubes and connect the lower discharge port of the vent drain to the trap. Secure all connections with clamps.
S Install the vent pipe grommet into the casing S Cut an appropriate length of 2(51 mm) PVC pipe long
enough to exit the cabinet and connect the vent drain to either:
S Install tee trap into bottom section of tee. S Remove knockout from the side of the furnace casing where
drain tube will exit.
S Install casing grommet (black rubber5/8″(16 mm) ID grommet
1
/2″(13 mm) OD barbed coupling in the loose parts
1
/2″(13 mm) ID elbow
— A standard field supplied 2(51 mm) PVC tee, or —A2″ (51 mm) PVC coupling fastened onto the drain
tee.
Casing Grommet Black Rubber
5
(Loose parts bag)
-- in loose parts bag)
1
S Install the S Install the black PVC tube connector (
1
/2″(13 mm) CPVC from loose parts bag) as shown in the
illustration above
/2″(13 mm) CPVC street elbow on discharge of trap
3
/4″(19 mm) PVC x
S Cut the black drain tube (5/8″(16 mm) ID -- in loose parts bag)
to length to fit between trap and tube connector through grommet.
S Clamp both ends of the drain tube using clamps provided. S Glue the CPVC street elbow to the trap using appropriate
cleaner and solvent cement.
S Connect the tee trap and the main drain line exiting the casing
as shown in Fig. 19.
S Note: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Both the internal trap and the external tee trap must be primed before operation. Verify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
20
/
8
CPVC
A07708
Page 21
Plastic Cap
°
°
Yellow or black
Coupling & Clamps (Optional)
Vent D rain &Clamps
Single Pressure Switch Detail
FLOW
AIR
Either: The PVC Drain Tee or a field supplied 2 PVC Tee
(51 mm)
SIDE VIEW
Rotate downward
to 10
5
EXHAUST
2″(51 mm) PVC Coupling
Dual Pressure Switch
FLOW
AIR
NOTE: Built--in channel will be angled 5° to 10° also.
Relief Tube Black Rubber
3
/
16
On Some Models ONLY
INLET
(5 mm) ID
359AAV
Tee Trap White PVC (loose parts bag)
Elbow Tube Black Rubber
1
/2″″ID (13 mm) & Clamps
(Loose Parts Bag)
Drain Tube Black, Cut at straight section
Leave room for clamp
Drain Tube Black Rubber
1
/
ID (13 mm) & Clamps
2
WARNING Move Caps to top of trap
5
/
(16 mm) ID Corrugated
8
Cut Here
Barbed Coupling1/ (loose parts bag)
Fig. 13 -- Downflow Left--Side Vent and Trap
Downflow Left--Side Vent and Trap (See Fig. 13).
Remove the inducer mounting screws, rotate the inducer 180° and retighten the inducer screws to 20(2.26 newton meters) pounds torque.
Disconnect the hoses from the trap assembly, and remove trap and trap mounting bracket from the blower compartment. Using cover plate and gasket provided in the loose parts bag, cover the hole from the burner compartment to the blower compartment and secure with screws.
Move the caps to the top of the trap and mount the trap externally to the left side of the unit using the two(2) screws provided.
Cut the
5
/8″ (16 mm) ID corrugated hose as shown above and fasten the 90° bend end to the trap and fasten the straight end to the transition drain. Secure both connections with clamps.
Reconnect the
1
/2″ (13 mm) ID drain hose from the vent drain to the trap and secure with a clamp. In some cases, additional length will be required for this hose. Use the Black plastic1/2″ (13 mm) OD barbed coupling and a suitable section of
1
/2″ (13 mm) ID hose to make the connection. Secure all connections with clamps
Connect the
3
/16″ (5 mm) ID relief tube from the small port on
the trap to the top port of the transition as shown in the picture.
Flexible Tubing Connector,
3
/
(5 mm) OD (loose parts bag)
16
Relief Tube, Extension Black Rubber,
3
/
(5 mm) ID Cut to fit
OFF
ON
(13 mm) OD
2
16
(loose parts bag)
Trap Connection
Preassemble & insert into furnace
“Clamp ears” Pointed OUT
25--24--69
A07767
In some cases, additional hose length will be needed. Use the clear plastic3/16″ (5 mm) OD flexible tubing connector and a suitable length of extra
3
/16″ (5 mm) ID hose to make this
connection. Install the vent pipe grommet into the casing Cut an appropriate length of 2(51 mm) PVC pipe long , enough
to exit the cabinet and connect the vent drain to either:
S A2″ (51 mm) PVC coupling fastened onto the drain tee
Install tee trap into bottom section of tee and glue pipe. Remove knockout from the side of the furnace casing where drain
tube will exit. Connect the tee trap and the main drain line exiting the casing as
shown in Fig. 19. NOTE: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Both
the external trap and the external tee trap must be primed before operation. Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
21
Page 22
°
°
Plastic Cap
Yellow or black
Trap Connection
“Clamp ears” Pointed OUT
Vent D rain &Clamps
NOTE: Built--in channel will
be angled 5° to 10° also.
359AAV
Single Pressure Switch Detail
SIDE VIEW
Rotate downward
to 10
5
AIR
FLOW
Elbow Tube Black Rubber
1
/
(13 mm) ID & Clamps
2
(Loose Parts Bag)
Dual Pressure Switch
Drain Tube Corrugated
5
/
Black, ID&Clamps
(16 mm)
8
ON
Barbed Coupling
1
/
(13 mm) OD
2
(Loose Parts Bag)
Relief Tube Black Rubber
3
/
(5 mm) ID
16
Drain Hose Black Rubber
1
/
(13 mm) ID Cut to
2
Fit & Clamps
On Some Models
Preassemble & insert into furnace
Coupling & Clamps (Optional)
2″(51 mm) PVC Coupling
ONLY
INLET
Either: The PVC DrainTeeorafield
AIR FLOW
supplied 2
(51 mm) PVC Tee
Tee Trap White PVC (loose parts bag)
Drain Connector Black
OFF
3
/
PVC
(19 mm)
4
1
PVC X
/2″
CPVC (Loose parts bag)
(13 mm)
WARNING Move Caps to top of trap
Drain Tube Black Rubber,
5
(loose parts bag)
/
ID (16 mm) Cut to fit & Clamps
8
Fig. 14 -- Downflow Right--Side Vent and Trap
Downflow Right--Side Vent and Trap (See Fig. 14)
Remove the drain tee if installed. Disconnect the hoses from the trap assembly, and remove trap
and trap mounting bracket from the blower compartment. Using cover plate and gasket provided in the loose parts bag, cover the hole from the burner compartment to the blower compartment and secure with screws.
Move the caps to the top of the trap and mount the trap externally to the right side of the unit using the two(2) screws provided.
Connect the corrugated drain tube from the transition box to the trap as shown. If an extension is required, use the black PVC tube connector and the black loose parts bag. Cut tube to length. Secure all connections with clamps.
Connect the drain hose from the Vent Drain to the trap. If an extension is required, use the black coupling, connect a black1/2″ (13 mm) ID elbow tube and a suitable section of a
5
/8″ (16 mm) ID drain tube in the
1
/2″ (13 mm) OD barbed
1
/2″ (13 mm) ID drain tube to make
connection from the vent drain to the trap. Secure all connections with clamps.
Install the vent pipe grommet into the casing Cut an appropriate length of 2(51 mm) PVC pipe long , enough
to exit the cabinet and connect the vent drain to either:
S A2″ (51 mm) PVC coupling fastened onto the drain tee
Install tee trap into bottom section of tee and glue pipe. Remove knockout from the side of the furnace casing where drain
tube will exit. Connect the tee trap and the main drain line exiting the casing as
shown in Fig. 19. NOTE: Note: It is recommended that all PVC piping and fitting
connections be fit up and inspected before final cementing. Both
the external trap and the external tee trap must be primed before operation. Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
A07768
22
Page 23
Ven t Dr ain
&Clamps
Alternate Orientation
EXHAUST
Plastic Caps Yellow or black
Dual Pressure Switch
ON
OFF
T N
E
V
IN
AIR
FLOW
Single Pressure Switch Detail
AIR FLOW
Relief Tube Black Rubber
3
/
ID
16
Flexible Tubing Connector
3
/
OD (Loose Parts Bag)
16
Relief Tube Extension Black Rubber Cut to Fit (Loose Parts Bag)
Trap Connection
“Clamp ears” Pointed OUT
Preassemble & insert into furnace
359AAV
3
/
ID
16
Field Supplied Tee
Coupling & Clamps (Optional)
Drain Tube Black Rubber
1
/
2
Cap and Clamp
Tee Trap White PVC
Open End
(loose parts bag)
Representative drawing only, some models may vary in appearance.
Fig. 15 -- Horizontal Left through Top
Horizontal Left through Top (See Fig. 15)
S Disconnect the hoses from the trap assembly, and remove trap
and trap mounting bracket from the blower compartment. Using cover plate and gasket provided in the loose parts bag, cover the hole from the burner compartment to the blower compartment and secure with screws.
S Remove knockout from the side of the furnace casing where
drain tube will exit.
S Mount the trap externally to the bottom side of the unit using
the 2 screws provided in the location shown.
S Cut the corrugated tube as shown in the illustration above.
Connect the corrugated hose from the transition to the trap. Secure connections with clamps.
S Remove the black
tee. Install a yellow cap and clamp over the open drain port of the drain tee.
S Connect the black
Drain to the trap. Secure connections with clamps.
1
/2″(13 mm) ID drain tube from the drain
1
/2″(13 mm) ID drain tube from the Vent
ID & Clamps
Remove KO before mounting Trap
5
/
Drain Tube Corrugated Cutatstraightsection
Leave room for clamp
3
S Connect the
/16″(5 mm) ID relief tube to the middle port on
the trap. If an extension is required, use the
ID & Clamps
8
Cut Here
3
/16″(5 mm) OD
A07709
flexible tubing connector and the black3/16″(5 mm) ID relief tube in the loose parts bag. Cut tube to length. Secure all connections with clamps.
S Cut an appropriate length of 2″ (51 mm) PVC pipe, long
enough to exit the cabinet and connect the vent drain to either:
— A standard field supplied 2(51 mm) PVC tee, or —A2″ (51 mm) PVC coupling fastened onto the drain
tee.
S Install tee trap into bottom section of tee. S Connect the tee trap and the main drain line exiting the casing
as shown in Fig. 19.
NOTE: It is recommended that all PVC piping and fitting connections be fit up and inspected before final cementing. Both
the external trap and the external tee trap must be primed before operation. Verify all condensate drain connections are
securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
23
Page 24
Alternate Orientation
Field Supplied Tee
Single Pressure Switch Detail
Yellow or black Plastic Cap
EXHAUST
Level or Sloped towards Tee
Dual Pressure Switch
Relief Tube Black Rubber
3
/
ID
16
FLOW
AIR
Ven t Dr ain &Clamps
Elbow Tube Black Rubber
1
/
ID & Clamps
2
(Loose Parts Bag)
Tee Trap White PVC
359AAV
(loose parts bag)
On Some Models ONLY
INLET
ON
T
N
E
V
IN
Flexible Tubing Connector
3
Representative drawing only, some models may vary in appearance.
Horizontal Left--Side Vent (See Fig. 16)
S Remove the drain tee from the Vent Drain if installed. S Rotate the inducer 180° for a side vent after loosening the 4
inducer attachment screws. Reinstall and retighten the inducer screws to 20(2.26 newton meters) pounds torque.
S Disconnect the hoses from the trap assembly, and remove trap
and trap mounting bracket from the blower compartment. Using cover plate and gasket provided in the loose parts bag, cover the hole from the burner compartment to the blower compartment and secure with screws.
S Remove knockout from the side of the furnace casing where
drain tube will exit.
S Mount the trap externally to the bottom side of the unit using
the 2 screws provided in the location shown.
S Cut the corrugated tube as shown in the illustration above.
Connect the corrugated hose from the transition to the trap. Secure connections with clamps.
S Connect the black
1
/2″(13 mm) ID drain tube from the Vent
Drain to the trap. If an extension is required, use the black
1
/2″(13 mm) OD flexible tubing connector and the black
1
/2″(13 mm) ID drain tube in the loose parts bag. Cut tube to
OFF
/
OD (Loose Parts Bag)
16
Relief Tube Extension Black Rubber (Loose Parts Bag)
3
/
16
ID Cut to Fit
Fig. 16 -- Horizontal Left--Side Vent
length. Secure connections with clamps.
S Connect the
the trap. If an extension is required, use the3/16″OD flexible tubing connector and the black the loose parts bag. Cut tube to length.
S Cut an appropriate length of 2″ (51 mm) PVC pipe, fittings
and extension pipe long enough to exit the cabinet and connect the vent drain to either:
— A standard field supplied 2(51 mm) PVC tee, or —A2″ (51 mm) PVC coupling fastened onto the drain
tee.
S Install tee trap into bottom section of tee. S Important: The pipe to the tee trap must be level or sloping
towards the tee trap
S Connect the tee trap and the main drain line exiting the casing
as shown in Fig. 19.
NOTE: It is recommended that all PVC piping and fitting connections be fit up and inspected before final cementing. Both the external trap and the external tee trap must be primed before operation. Verify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
Barbed Coupling
1
/
OD (Loose Parts Bag)
2
Drain Tube Black Rubber
1
/
ID & Clamps
2
WARN ING Move Caps to top of trap
Drain Tube Black,5/
Cut at straight section
Leave room for clamp
3
/16″(5 mm) ID relief tube to the middle port on
ID Corrugated
8
Cut Here
2 5 -- 2 4 -- 8 8
3
/16″(5 mm) ID relief tube in
A07710
24
Page 25
Trap Connection
“Clamp ears” Pointed OUT
Single Pressure Switch Detail
FLOW
AIR
Plastic Cap Yellow or black
Alternate Orienta­tion
Preassemble & insert into furnace
Relief Tube Rubber Tube
3
/
ID
16
Flexible Tubing Connector
3
/
OD (Loose Parts Bag)
16
Relief Tube Extension Black Rubber Cut to Fit (Loose Parts Bag)
3
/
ID
16
Drain Tube Corrugated Cut at straight section
Coupling & Clamps (Optional)
WARN ING Add Cap and Clamp
Dual Pressure Switch
5
/8″″ID & Clamps
Ven t Dr ain &Clamps
IN
V E N
T
OFF
ON
Drain Tube Black Rubber
1
/
ID & Clamps
2
Field Supplied Tee
EXHAUST
Tee Tra p White PVC (loose parts bag)
Elbow Tube Black Rubber1/ ID & Clamps (Loose Parts Bag)
INLET
On Some Models ONLY
Barbed Coupling1/ (Loose Parts Bag)
OD
2
2
359AAV
Leave room for clamp
Representative drawing only, some models may vary in appearance.
Fig. 17 -- Horizontal Right through Top
Horizontal Right through Top (See Fig.
17)
S Disconnect the hoses from the trap assembly, and remove trap
and trap mounting bracket from the blower compartment. Using cover plate and gasket provided in the loose parts bag, cover the hole from the burner compartment to the blower compartment and secure with screws.
S Remove knockout from the side of the furnace casing where
drain tube will exit.
S Mount the trap externally to the bottom side of the unit using
the 2 screws provided in the location shown.
S Cut the corrugated tube as shown in the illustration above.
Connect the corrugated hose from the transition to the trap. Secure connections with clamps.
S Connect the black
Drain to the trap. If an extension is required, use the black1/2″ (13 mm) OD barbed coupling and the black
1
/2″ (13 mm) ID drain tube from the Vent
1
/2″(13 mm) ID
Cut Here
drain tube in the loose parts bag. Cut tube to length. Secure connections with clamps.
S Connect the
3
/16″ (5 mm) ID relief tube to the middle port on the trap. If an extension is required, use the clear OD flexible tubing connector and the black3/16″(5 mm) ID relief tube in the loose parts bag. Cut tube to length.
S Cut an appropriate length of 2″ (51 mm) PVC pipe, fittings
and extension pipe long enough to exit the cabinet and connect the vent drain to a standard field supplied 2(51 mm) PVC tee
S Install tee trap into bottom section of tee. S Connect the tee trap and the main drain line exiting the casing
as shown in Fig. 19.
NOTE: It is recommended that all PVC piping and fitting connections be fit up and inspected before final cementing. Both the external trap and the external tee trap must be primed before operation. Verify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
3
/16″(5 mm)
A07711
25
Page 26
AIR FLOW
Plastic Cap Yel low or b lac k
Coupling & Clamps (Optional)
Single Pressure Switch Detail
Ven t Dr ain &Clamps
EXHAUST
Field Supplied Tee
Level or Sloped
towards Tee
Tee Tra p White PVC
359AAV
Relief Tube Black Rubber
3
/
ID
16
Flexible Tubing Connector
3
/
OD (Loose Parts Bag)
16
Relief Tube Extension Black Rubber Cut to Fit (Loose Parts Bag)
3
/
16
IN
V
E N T
OFF
ON
ID
Elbow Tube Black Rubber
1
/
ID & Clamps
2
(Loose Parts Bag)
INLET
(loose parts bag)
On Some Models ONLY
Alternate Orientation
Dual Pressure Switch
5
/
Drain Tube Corrugated,
Cut at straight section
ID & Clamps
8
Drain Tube Black Rubber
1
/
ID & Clamps
2
Barbed Coupling (Loose Parts Bag)
1
/
OD
2
Leave room for clamp
Cut Here
Representative drawing only, some models may vary in appearance.
Fig. 18 -- Horizontal Right Side Vent
Horizontal Right Side Vent (See Fig. 18)
S Disconnect drain tee if installed S Disconnect the hoses from the trap assembly, and remove trap
and trap mounting bracket from the blower compartment. Using cover plate and gasket provided in the loose parts bag, cover the hole from the burner compartment to the blower compartment and secure with screws.
S Remove knockout from the side of the furnace casing where
drain tube will exit.
S Mount the trap externally to the bottom side of the unit using
the 2 screws provided in the location shown.
S Cut the corrugated tube as shown in the illustration above.
Connect the corrugated hose from the transition to the trap. Secure connections with clamps.
S Connect the black
Drain to the trap. If an extension is required, use the1/2″(13 mm) OD barbed coupling and the black tube in the loose parts bag. Cut tube to length. Secure
1
/2″(13 mm) ID drain tube from the Vent
1
/2″(13 mm) ID drain
A07712
connections with clamps.
S Connect the3/16″ (5 mm) ID relief tube to the middle port on
the trap. If an extension is required, use the clear3/16″OD splice connector and the black loose parts bag. Cut tube to length.
S Cut an appropriate length of 2″ (51 mm) PVC pipe, fittings
3
/16″(5 mm) ID relief tube in the
and extension pipe long enough to exit the cabinet and connect the vent drain to either:
— A standard field supplied 2(51 mm) PVC tee, or —A2″ (51 mm) PVC coupling fastened onto the drain
tee.
S Install tee trap into bottom section of tee. S Important: The pipe to the tee trap must be level or sloping
towards the tee trap.
S Connect the tee trap and the main drain line exiting the casing
as shown in Fig. 19.
NOTE: It is recommended that all PVC piping and fitting connections be fit up and inspected before final cementing. Both
the external trap and the external tee trap must be primed
26
Page 27
before operation. Verify all condensate drain connections are securely clamped. A coupling and clamps (in loose part bag) may be installed as shown for future servicing of the vent system.
Connecting Vent and Combustion Air Piping
!
WARNING
INLET
EXHAUST
V
E
N
T
IN
Open Tee
Tee Tr ap
Evaporator
Coil Drain Line (Optional)
Main Drain Line
Condensate Trap
Representative drawing only, some models may vary in appearance.
ON
OFF
A07713
Fig. 19 -- Connecting Tee Trap to Condensate Trap and Main
Drain Line
The tee trap must be connected to the main condensate drain line as conceptually shown above. Different installations may require slightly different orientations. The following steps apply to all installations.
1. The tee trap should be installed as close to the side or top of the furnace as practical. Minimize the distance between the inducer and the tee trap as much as possible.
2. An open tee is to be used at the tee trap discharge. The top end of the tee should be open to the atmosphere to elimin­ate potential air lock problems.
3. The drain line from the tee trap is to be connected to the furnace condensate trap drain line as shown above.
4. Condensate drain lines from a cooling coil may be connec­ted downstream of the connection point of the tee trap and furnace condensate trap.
IMPORTANT: Prime both traps with water before operation. Failure to prime the traps may result in discharge of flue gases from the condensate drain line and open tee for a period of time, and may result in temporary lockout of the furnace upon start up. Main drain line construction is left to the discretion of the installer. It may be made of either rigid pipe or flexible tube.
1
/
Tube ID should NOT be less than
.
2
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Cement or mechanically seal all joints, fittings, etc. to prevent leakage of flue gasses.
Refer to Fig. 10 through Fig. 18 that corresponds to the installation position of the furnace for the application.
Preassemble the vent and combustion air piping from the furnace to the vent termination. Do not cement the pipe joints until the pipe preassembly process is complete.
Combustion Air Pipe Connection (Dual Certified or
Direct Vent)
Install the air intake coupling and gasket to the furnace with the four(4) screws:
NOTE: The air intake coupling and gasket can be installed to the top panel, or to the alternate air intake locations on either the left or right side panels of the furnace.
For downflow installation, the air intake coupling and gasket must be installed to the alternate air intake location on either the left or right side panels. Remove the 3” (76 mm) hole plug from the furnace accessory bag and relocate to the open hole in the furnace panel. Use four screws to seal the four mounting holes in the top panel next to the hole plug. Drill four 7/64” (3 mm) diameter holes in the casing using the air intake coupling as the template.
The air intake coupling is sized for 2(51 mm) PVC pipe. Install the combustion air pipe to the air intake coupling using
RTV sealant to provide for future serviceability.
Vent Pipe Connection
Install the vent pipe grommet to the furnace panel. Locate the grommet in the furnace panel at a location directly away from the vent fitting on the combustion blower. The grommet snaps into the 3(76 mm) hole on the furnace panel. NOTE: Depending on the installation position, the vent pipe grommet will be installed to the top panel or to the alternate location on the side panels. If needed, remove the 3(76 mm) hole plug from the loose parts bag and relocate to the open hole in the furnace panel. (See Fig. 10 or Fig. 19.)
Install the vent pipe to the rubber coupling, the vent fitting or the PVC vent extension pipe. Securely attach using the clamp or PVC cement as required.
NOTE: The vent fitting MUST be installed with the air flow marking arrow pointed toward the vent pipe. (See Fig. 20.) Some installations require the vent fitting to be installed with a5° to 10° downward slope. (See Fig. 10 through Fig. 19.)
359AAV
27
Page 28
Rubber Coupling
°
°
°
°
°
&Clamps
Vent Pipe
90
Vent Extension Pipe (Side Panel Exit)
Tee
Elbow
SIDE VIEW
Rotate downward 5
Vent Pipe (Top Panel Exit)
NOTE: The 90° elbow is approved for use inside the furnace ONLY.
Vent Fitting &Clamps
to 10
359AAV
NOTE: Built--in channel will be angled 5° to 10° also.
Fig. 20 -- Proper Sealing Procedure for Combustion Blower
Joining Pipe and Fittings
SEE VENT AND COMBUSTION AIR PIPING, vent and Combustion Air Piping Guidelines in this manual for applicable
ASTM Standards for vent materials.
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Observe all cautions and warnings printed on material containers.
Provide adequate ventilation and do NOT assemble near heat source or open flame. Do NOT smoke while using solvent cements and avoid contact with skin or eyes.
Combustion Blower
A07714
primer to inside surface of socket and outside of pipe. Do NOT allow primer to dry before applying cement.
3. Apply a thin coat of cement evenly in the socket. Quickly apply a heavy coat of cement to the pipe end and insert pipe into fittings with a slight twisting movement until it bottoms out.
NOTE: Cement MUST be fluid while inserting pipe. If NOT, recoat pipe.
4. Hold the pipe in the fitting for 30 seconds to prevent the tapered socket from pushing the pipe out of the fitting.
5. Wipe all excess cement from the joint with a rag. Allow 15 minutes before handling. Cure time varies according to fit, temperature and humidity.
Connecting Vent Pipes and Termination (Direct Vent)
NOTE: For direct vent applications, combustion air intake and vent MUST terminate in the same atmospheric pressure zone. If installation is in a cold climate (sustained temperatures 0°F (--18°C)and below for 24 or more consecutive hours), increase the minimum distance between vent pipe and air intake from 8 to 18(203 to 457 mm).
1. Install all couplings, nipples and elbows using proper pro­cedures for Joining Pipe and Fittings and maintain spa­cing between vent and combustion air piping as indicated in Fig. 21 through Fig. 23.
8” 203.2mm* MIN. 20’(6.1m) MAX
EXHAUST
INLET
12 ” (304.8mm) MIN.
GRADE LEVEL
OR
Fig. 21 -- Sidewall Termination 12” (305 mm) or More Above
Snow Level or Grade Level
*18 in. (457.2mm) Minimum for cold climates (sustained tem­peratures 0 for 24 or more consecutive hours)
8” (203.2mm)
MIN.
F(- 17
C) and below
A07715
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Do NOT use solvent cement that has become curdled, lumpy or thickened and do NOT thin. Observe precautions printed on containers. For applications below 32_F(0_C), use only low temperature type solvent cement. Poor joints may lead to disconnected or leaking vent pipe joints allowing carbon monoxide to enter the living space.
1. Cut pipe end square, remove ragged edges and burrs. Chamfer end of pipe, then clean fitting, socket and pipe joint of all dirt, grease, or moisture.
NOTE: Stir the solvent cement frequently while using. Use a natural bristle brush or the dauber supplied with the cement. The proper brush size is one inch.
2. After checking pipe and socket for proper fit, wipe socket and pipe with cleaner-primer. Apply a liberal coat of
Horizontal Termination
1. Cut two holes. 2--1/2″ (64 mm) for 2″ (51 mm) pipe, 3″ (76 mm) for 2-­mm) pipe. Do NOT make the holes oversized, or it will be necessary to add a sheet metal or plywood plate on the outside with the correct size hole in it.
2. Check hole sizes by making sure it is smaller than the couplings or elbows that will be installed on the outside. The couplings or elbows MUST prevent the pipe from be­ing pushed back through the wall.
3. Extend vent pipe and combustion air pipe through the wall
3
/4″ (19 mm) to 1″ (25 mm) and seal area between pipe
and wall.
4. Install the couplings, nipple and termination elbows as shown and maintain spacing between vent and combustion air piping as indicated in Fig. 21 and Fig. 22.
A metal shield is recommended 18x18″ (457 mm x 457 mm) min. or 18(457 mm) min. diameter around the vent termination at the exterior wall to protect the house exterior materials from flue product or condensation (freezing) damage.
28
1
/2″ (64 mm) pipe, or 31/2″ (89 mm) for 3″ (76
Page 29
8” (203.2mm)* MIN.
_
_
°
20’ (6.1m) MAX
*18 in. (457.2mm) Minimum for cold climates [sustained 0 (-17
C) and below for 24 or
more consecutive hours]
8” (203.2mm)
MIN.
F
protective material should be attached and sealed (if necessary) to the building before attaching the vent terminal.
12 ” (304.8mm) MIN.
INLET
EXHAUST
GRADE LEVEL
OR
SNOW LEVEL
A07716
Fig. 22 -- Sidewall Termination with Exterior Risers to Get
Above Snow Level or Grade Level
Using Exterior Risers
1. Install elbows and pipe to form riser as shown in Fig. 22.
2. Secure vent pipe to wall with galvanized strap or other rust resistant material to restrain pipe from moving.
3. Insulate pipe with Armaflex or equivalent moisture resist­ant closed cell foam insulation or fiberglass insulation if boxed in and sealed against moisture.
Vent Termination Shielding
Under certain wind conditions some building materials may be affected by flue products expelled in close proximity to unprotected surfaces. Sealing or shielding of the exposed surfaces with a corrosion resistant material (such as aluminum sheeting) may be required to prevent staining or deterioration. The
OVERHANG
(304.8mm) MIN
.
INLET
12 in. (304.8mm) MIN. Ground Level OR Snow Level
SIDE VIEW
12 in.
FRONT VIEW
EXHAUST
Same Joist
Space
12 in.
90
Fig. 23 -- Recommended Alternate Installation
for Sustained Cold Weather
(0_F & below for 24 or more consecutive hours)
359AAV
(304.8mm)
25- 23- 73
A07699
B
A
A
2 5 -- 0 0 -- 0 6
A=12″ (304.8mm) Above roof or snow accumulation level B=8″ (203.2mm) Min., 20′ (6.1m) Maximum, except in areas with extreme cold temperatures [sustained 0°F(--17°C) and below for 24 or more consecutive hours], the 18(457.2mm) Min.
Fig. 24 -- Rooftop Termination
A07717
29
Page 30
Vertical Termination
°
°
°
°
1. Fig. 24 shows the proper installation and clearances for vertical vent termination. The vertical roof termination should be sealed with a plumbing roof boot or equivalent flashing. The inlet of the intake pipe and end of the ex­haust vent must be terminated no less than 12(305 mm) above the roof or snow accumulation level, and 12(305 mm) away from a vertical wall or other protrusion.
2. If the vent system is installed in an existing chimney make sure clearances shown in Fig. 23 are maintained. Horizont­al section before the termination elbow can be extended on the inlet air to provide necessary clearance.
Multi Vent Termination Clearances
When two (2) or more furnaces are vented near each other, each furnace must be individually vented.
Two (2) vent terminations may be installed as shown in Fig. 25, 26, 27, 28 and 29, but the next vent termination must be at least 36(914 mm) away from first 2 terminations. It is important that
359AAV
vent terminations be made as shown to avoid recirculation of flue gases.
“A”
Exhaust
“A”
Inlet
8 in. (203.2mm) Min. 20 in. (6.1m) Max.
(304.8mm) Min.
12 in. Grade or Snow Level
Dimension “A” is touching or 2 in. (50.8mm) maximum separation
18 in. (457.2mm) Min. for Cold Climates [Sustained 0 24 hours or more consecutive hours]
F(- 17
(203.2mm)
8 in. Min.
C) and below for
A07696
Fig. 27 -- Sidewall Inlet Vent and Exhaust--Air Termination
12 in. (304.8mm)
Min. Grade or Snow Level
Combustion Air
2” (50.8mm) Max.
36” Min .
(914.4mm)
Fig. 25 -- Concentric Vent and Combustion--Air
Roof Termination
1 in.
(25.4mm)
Combustion Air
Maximum
Ven t
OR
36” Min.
(914.4mm)
Exhaust
A07718
8 in.
Exhaust
(203.2mm) Min.
20 in.
(6.1m) Max.
“A”
18 in.
(457.2mm) Min. for Cold Climates [Sustained 0 24 hours or more consecutive hours]
8 in. (203.2mm) Min.
12 in. (457.2mm) Min. Grade or
Inlet
Snow Level
“A”
F(- 17°C) and below for
Dimension “A” is touching or 2 in. (503.8mm) maximum separation.
A07697
Fig. 28 -- Sidewall Inlet Vent and Exhaust--Air Termination
with Exterior Risers
8 in.
(203.2mm) Min.
20 in. (6.1m) Max.
Inlet
“A”
Ven t
Exhaust
25--22--02d
Dimension “A” is touching or 2 in. (503.8mm) maximum separation.
A07695
Fig. 26 -- Concentric Vent and Combustion Air
Sidewall Termination
Exhaust
12 in. (304.8mm) Min. Grade or Snow Level
(457.2mm) Min. for Cold Climates
18 in. [Sustained 0 24 hours or more consecutive hours]
F(- 17°C) and below for
25--22--43
Fig. 29 -- Rooftop Inlet Vent and Exhaust--Air Termination
30
A07698
Page 31
CONCENTRIC TERMINATION
Vent Termination Clearances
!
WARNING
CARBON MONOXIDE POISONING, FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Inlet and outlet pipes may NOT be vented directly above each other (standard vent terminals).
1. Determine termination locations based on clearances spe-
cified in following steps and as shown in Fig. 7, Fig. 30 through Fig. 35.
2. The vent termination must be located at least 12(305 mm) above ground or normally expected snow accumula­tion levels.
3. Do NOT terminate over public walkways. Avoid areas where condensate may cause problems such as above planters, patios, or adjacent to windows where steam may cause fogging.
4. The vent termination shall be located at least 4(1.2 M) horizontally from any electric meter, gas meter, gas regu­lator, and any relief equipment. These distances apply ONLY to U.S. installations.
5. The vent termination is to be located at least 3(.91 M) above any forced air inlet located within 10(3.1 M); (3.1 M) and at least 10(3.1 M) from a combustion air intake of another appliance, except another direct vent furnace in­take.
6. In Canada, the Canadian Fuel Gas Code takes precedence over the preceding termination instructions.
Concentric Vent Termination - Kit # KGAVT0701CVT & KGAVT0801CVT
These kits are for vertical or horizontal termination of the combustion air inlet and the exhaust vent pipes on Category IV gas--fired condensing furnaces. The KGAVT0801CVT kit can be used for 3 (76 mm) diameter pipe systems. The KGAVT0701CVT kit can be used for 2(51 mm) diameter pipe system. Refer to Table 4 for the correct pipe size for the furnace. Both the combustion air inlet and the exhaust vent pipes must attach to the termination kit. The termination kit must terminate outside the structure and must be installed per the instructions outlined below for vertical or horizontal termination. Vertical termination is preferred. Field supplied pipe and fittings are required to complete the installation.
Vertical & Horizontal Termination
1. Determine the pipe diameters required for the installation from Table 4 and Fig. 32.
2. Determine the best location for the termination kit. See Fig. 31 for vertical termination or Fig. 35 for horizontal termination. Roof termination is preferred since it is less susceptible to damage, has reduced intake contaminants and less visible vent vapor. For side wall termination, con­sideration should be given to: 1) possible damage from the vapors to plants/shrubs, other equipment and building ma­terials, 2) possible damage to the terminal from foreign ob­jects, 3) wind effects that may cause recirculation of flue products, debris or light snow and 4) visible vent vapor.
3. Cut one 5(127 mm) diameter hole through the structure for the KGAVT0801CVT Kit or one 4(102 mm) diamet­er hole for the KGAVT0701CVT Kit .
Kit Contents: 3 in. (76) Rain Cap or 2 in. (51) Rain Cap 3 in. (76) Diameter SDR-26 Pipe, 19-1/2 in. (495) Long or 4 in. (102) Diameter SDR-26 Pipe, 24 in. (610) Long, 2 in. (51) Diameter SDR-26 Pipe, 31-5/8 in. (803) Long or 2-1/2 in. (64) Diameter SDR-26 Pipe, 37-1/8 in. (943) Long, 3 in. (76) Y Concentric Fitting or 2 in. (51) Y Concentric Fitting
Nominal 3 in. (76) or 4 in. (102) Dia. SDR-26 Pipe
2 in. (51) or 3 in. (76) Dia.
Y Concentric Fitting
2 in. (51) or 2-1/2 in. (64)
Dia. SDR--26 Pipe
2 in. (51) or 3 in. (76) Dia.
Rain Cap
A07719
Fig. 30 -- Kit Components
Ven t
Combustion Air
Roof Boot/ Flashing (Field Supplied)
Ven t
Note: Support must be eld installed to secure termination kit to structure.
Maintain 12 in. ance above highest anticipated snow level. Max. of 24 in. (609.6mm) above roof.
Support (Field Supplied)
(304.8mm) min. clear-
45°Elbow (Field Supplied)
Combustion Air
25--22--02
A07720
Fig. 31 -- Concentric Vent Roof Installation
4. Dimension D may be lengthened to 60(1524 mm) max. or shortened by cutting the pipes to 12(305 mm) min. Dimension A will change according to D dimension. (See Fig. 32).
5. Partially assemble the concentric vent termination kit. Clean and cement the parts using the procedures for Join­ing Pipe and Fittings section of the manual. A) Cement the Y Concentric fitting to the longest of the two straight kit pipes. (See Fig. 30) B) Cement the rain cap to the shortest of the straight kit parts. (See Fig. 30).
NOTE: A field supplied stainless steel screw may be used to secure the rain cap to the pipe instead of cementing when field disassembly is desired for cleaning (See Fig. 33).
359AAV
31
Page 32
B PVC Vent/Exhaust
C
1
1
/2″
(38 mm)
Model A* B C D**
KGAVT0801CVT 387/
KGAVT0701CVT 333/
* = Dimension will change accordingly as dimension D is lengthened or shortened. **= Dimension D may be lengthened to 60may also be shortened by cutting the pipes provided in the kit to 12minimum.
359AAV
Fig. 32 -- Concentric Vent Dimensional Drawing
B PVC Intake/Combustion Air
8
8
D
A
3 41/
2 31/
2
2
Table 4 – Concentric Termination Kit
Concentric Termination Kit KGAVT0801CVT &
KGAVT0701CVT Venting Table for
359AAV Models
60,000 Btuh Furnaces
KGAVT0701CVT --- 5′ & (3) 90° elbows with 2(51 mm) PVC pipe or
KGAVT0701CVT --- 35′ & (4) 90° elbows with 2(51 mm) PVC pipe or KGAVT0801CVT --- 65′ & (4) 90° elbows with 3(76 mm) PVC pipe
80,000 Btuh Furnace
KGAVT0701CVT --- 35′ & (4) 90° elbows with 2(51 mm) PVC pipe or KGAVT0801CVT --- 35′ & (4) 90° elbows with 3(76 mm) PVC pipe
100,000 Btuh Furnace
KGAVT0701CVT --- 5& (2) 90° elbows with 2(51 mm) PVC
pipe or KGAVT0801CVT --- 35′ & (4) 90° elbows with 3(76 mm) PVC pipe
1. Do not include the field supplied 45° elbow in the total el­bow count.
2. If more elbows are required, reduce the length of both t he inlet andthe exhaustpipes five feet for each additional elbow used.
3. Elbows are DWV long radius type for 2 mm) vents. NOTE: Feet of pipe is whichever pipe run is the longest, either inlet or outlet side.
If assembly needs to be extended to meet height or side wall thickness requirement, the two pipes supplied in the kit may be replaced by using the same diameter solid, single (no coupling connections) field supplied SDR--26 PVC (ASTM D2241) pipes. Do not extend dimension D more than 60(1524 mm). (See Fig.
32).
Do not use field supplied couplings to extend the pipes. Airflow restriction will occur and the furnace pressure switch may cause intermittent operation.
(51 mm) and 3(76
211/
165/
8
8
A09195
Drill clearance hole in rain cap and pilot hole in vent pipe.
Stainless steel screw (Field supplied)
A07722
Fig. 33 -- Rain Cap to Vent Pipe Assembly
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
When using the alternate screw assembly method, drill a clearance hole in the rain cap and a pilot hole in the vent pipe for the screw size being used. Failure to drill adequate holes may cause cracking of the PVC components, allowing flue gasses to be recirculated.
6. Install the Y concentric fitting and the pipe assembly through the structure’s hole. For vertical termination, in­stall the parts through the field supplied roof boot/flashing.
NOTE: Do not allow insulation or other materials to accumulate inside the pipe assembly when installing through the structure’s hole.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Do not operate the furnace with the rain cap removed as recirculating of the flue gasses may occur. Water may also collect inside the larger combustion air pipe and flow to the burner enclosure.
7. Secure the assembly to the structure as shown in Fig. 31 or Fig. 35 using field supplied metal strapping or equival­ent material.
NOTE: Ensure the termination height is above the roof surface or anticipated snow level as shown in Fig. 31 for vertical termination. Ensure the termination location clearance dimensions are as shown in Fig. 34 and Fig. 35 for horizontal termination.
8. Install the rain cap and the small diameter pipe assembly in the Y concentric fitting and the large pipe assembly. Ensure that the small diameter pipe is bottomed out and securely cemented in the Y concentric fitting.
32
Page 33
Roof Overhang
12″ (304.8mm) min.
1(25.4mm) max.
Combustion Air
Vent
Maintain 12(304.8mm) clearance above highest anticipated snow level or grade whichever is greater.
Fig. 34 -- Concentric Vent and Combustion--Air
Side Termination
25--22--02
A07736
Strap (Field Supplied)
Vent
Combustion Air
Note:
Securing strap must be field installed to prevent movement of termina­tion kit in side wall.
45° Elbow (Field Supplied)
Combustion Air
Vent
Flush to 1(25.4mm) max.
25--22--02
A07723
Fig. 35 -- Concentric Vent Sidewall Attachment
9. Cement the furnace combustion air and vent pipes to the concentric vent termination assembly. See Fig. 34 or Fig. 35 for proper pipe attachment.
10. Operate the furnace through one heat cycle to ensure com­bustion air and vent pipes are properly connected to the concentric termination connections.
GAS SUPPLY AND PIPING
!
WARNING
FIRE AND EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Models designated for Natural Gas are to be used with Natural Gas ONLY, unless properly converted to use with Propane gas.
NOTE: The rating plate is stamped with the model number, gas type and gas input rating. In addition, models manufactured for sale in Canada have orifice size information stamped on the rating plate.
Gas Supply Requirements
Gas supply pressure should be within minimum and maximum values listed on rating plate. Pressures are usually set by gas suppliers.
(See Propane Gas Conversion Kit instruction manual for furnaces converted to Propane gas)
S Use only the Type of gas approved for this furnace. See rating
plate for approved gas type.
1
S A
/8″ NPT plugged tapping, accessible for a test gauge connection,must be installed immediately upstream of the gas supply connection to furnace.
S Gas supply pressure should be within minimum and maximum
values listed on rating plate. Pressures are usually set by gas suppliers.
S Gas input must not exceed the rated input shown on the rating
plate. Overfiring will result in failure of heat exchanger and cause dangerous operation.
S Do not allow minimum supply pressure to vary downward.
Doing so will decrease input to furnace. Refer to Table 5 for Gas supply. Refer to Table 6 or 7 for manifold pressures.
Table5–GasPressures
Gas Type
Natural 7in.w.c.
Propane 11in. w.c.
Recommended Max. Min.
(1744 Pa)
(2740 Pa)
Supply Pressure
14in. w.c.
(3487 Pa)
14in. w.c.
(3487 Pa)
4.5in. w.c.
(1121 Pa)
11in. w.c.
(2740 Pa)
Gas Piping Requirements
NOTE: The gas supply line must be installed by a qualified service technician in accordance with all building codes.
NOTE: In the state of Massachusetts.
a. Gas supply connections MUST be performed by a li-
censed plumber or gas fitter.
b. When flexible connectors are used, the maximum
length shall not exceed 36(914 mm).
c. When lever handle type manual equipment shutoff
valves are used, they shall be T--handle valves.
d. The use of copper tubing for gas piping is NOT ap-
proved by the state of Massachusetts.
1. Install gas piping in accordance with local codes, or in the absence of local codes, the applicable national codes. Re­fer to the current edition of NFPA 54/ANSI Z223.1 for proper gas pipe size.
2. It is recommended that a manual equipment shutoff valve be installed in the gas supply line outside the furnace. Locate valve as close to the furnace as possible where it is readily accessible. Refer to Fig. 36 .
3. Use black iron or steel pipe and fittings or other pipe ap­proved by local code.
4. Use pipe thread compound which is resistant to natural and Propane gases.
5. Use ground joint unions and install a drip leg no less than 3long to trap dirt and moisture before it can enter gas control valve inside furnace.
NOTE: Refer to Fig. 36 and Fig. 37 for the general layout at the furnace. The rules listed apply to natural and Propane gas pipe installations.
NOTE: Install the gas pipe grommet to the furnace side panel with the gas pipe entry. If needed, remove the 2” (51 mm) hole plug from the plastic accessory bag and relocate to the open hole in the furnace side panel.
6. Use two pipe wrenches when making connections to pre­vent gas valve from turning.
359AAV
33
Page 34
7. Install a manual shut--off valve external to furnace casing and tighten all joints securely.
8. If local codes allow the use of flexible gas appliance con­nectors, always use a new listed connector. Do not use a connector which has previously serviced an­other gas appliance.
9. Flexible corrugated metal gas connector may NOT be used inside the furnace or be secured or supported by the furnace or ductwork.
10. Properly size gas pipe to handle combined appliance load or run gas pipe directly from gas meter or Propane gas reg­ulator.
11. Install correct pipe size for run length and furnace rating.
12. Measure pipe length from gas meter or Propane second stage regulator to determine gas pipe size.
Additional Propane Connection Requirements
359AAV
1. Have a licensed Propane gas dealer make all connections at storage tank and check all connections from tank to fur­nace.
2. If copper tubing is used, it MUST comply with limitation set in National Fuel Gas Code or CGA codes.
3. Two--stage regulation of Propane gas is recommended.
Propane Conversion
Supply Pressure
!
WARNING
FIRE HAZARD
Failure to follow this warning could result in personal injury or death.
Do NOT set input rating above that shown on rating plate.
1. A1/8″ NPT plugged tapping, accessible for a test gauge connection, must be installed immediately upstream of the gas supply connection to the furnace.
2. Gas input to burners MUST NOT exceed the rated input shown on rating plate.
3. Do NOT allow minimum gas supply pressure to vary downward. Doing so will decrease input to furnace. Refer to Table 6 and 7 for normal gas supply and manifold pressures.
Manifold Gas Pressure Adjustment
SEE CHECKS AND ADJUSTMENTS, Manifold Gas Pressure Adjustment in this manual.
!
WARNING
FIRE, EXPLOSION HAZARD
Failure to follow this warning could result in personal injury or death.
A Propane conversion accessory kit is required when operating the furnace with Propane gas.
An accessory kit shall be used to convert to propane gas use, see the furnace rating plate for the Propane conversion accessory kit part number.
34
Page 35
*
Drip Leg and Union, Union* should be outside the
*
cabinet. Manual shut- off valve MUST be upstream of dripleg, union, and furnace.
Use elbows and 3″pipe nipple to connect valve to piping when using right side gas pipe entry.
O
N
O
F
F
Propane Low pres­sure switch REQUIRED.
pipe
O
N
O
F
F
3 nipple
Union may be installed inside the cabinet when necessary
because of clearances.
Representative drawing only, some models may vary in appearance.
Fig. 36 -- Typical Gas Piping for Upflow
Manual shut- off valve
Vent Pipe Grommet (Single Pipe)
O
N O
F
F
Models may have 1 or 2 pressure switches
Alternative installation
359AAV
A07724
Use elbows and 3″(76 mm) pipe nipple to connect valve to piping when using left side gas pipe entry.
Propane low pressure switch.
Drip Leg and Union, Union* should be outside the cabinet. Manual shut--off valve MUST be upstream of dripleg, union, and furnace.
Union may be installed inside the cabinet when necessary
because of clearances.
Fig. 37 -- Typical Gas Piping for Downflow
Manual shut- off valve
Gas Pipe Grommet (Single Pipe)
Alternative installation
A09206
35
Page 36
Table 6 – Natural Gas Manifold Pressure (in wc) 20,000 BTU per Burner*
MEAN ELEVATION FEET ABOVE SEA LEVEL Ft. (M)
HEATING
VALUE
BTU/CU.
FT.
700 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 44 3.7
725 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 44 3.7 44 3.4
750 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 44 3.5 44 3.2
775 --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- --- 44 3.5 44 3.2 44 3.0
800 --- --- --- --- --- --- --- --- --- --- --- --- 44 3.6 44 3.3 44 3.0 44 2.8
825 --- --- --- --- --- --- --- --- 44 3.7 44 3.4 44 3.1 44 2.9 44 2.6
850 --- --- --- --- --- --- --- --- 44 3.5 44 3.2 44 2.9 44 2.7 44 2.5
875 --- --- --- --- 44 3.5 44 3.3 44 3.0 44 2.8 44 2.5 47 3.4
900 --- --- --- --- 44 3.3 44 3.1 44 2.8 44 2.6 47 3.5 48 3.6
925 44 3.7 44 3.2 44 2.9 44 2.7 44 2.5 48 3.7 48 3.4
359AAV
950 44 3.5 44 3.0 44 2.8 44 2.6 47 3.4 48 3.5 48 3.3
975 44 3.3 44 2.8 44 2.6 47 3.5 48 3.7 48 3.4 49 3.6
1000 44 3.2 44 2.7 44 2.5 47 3.3 48 3.5 48 3.2 49 3.4
1050 44 2.9 44 2.5 48 3.7 48 3.4 49 3.7 --- --- --- --- --- --- --- ---
1100 46 3.3 48 3.7 48 3.4 49 3.7 --- --- --- --- --- --- --- --- --- --- --- ---
* When installing the 100,000 BTU furnace in downflow or horizontal positions, firing rate is reduced to 19,500 BTU/cell. Subtract 0.2” w.c from the manifold pressures listed in table above for the correct manifold pressure.
Conversion: 1 in wc = 249 Pa
Bold--- indicates factory orifice size.
NOTE: Natural gas data is based on 0.60 specific gravity. For fuels with different specific gravity consult the National Fue l Gas Code ANSI Z223.1 ---2009/NFPA
54--- 2009 or National Standard of Canada, Natural Gas And Propane Installation Code CSA B149.1--- 10. In the USA, derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design--- certified by CSA.
{In Canada, the input rating must be derated 5% (Natural Gas) and 10% (Propane Gas) fo r altitudes of 2,000 to 4,500 (609.6 to 1371.6m) above sea level. Use
the 2001 to 3000 (609.9 to 914.4m) column in Tables 6 and 7.
0 to 2000 2001 to 3000† 3001 to 4000 4001 to 5000 5001 to 6000 6001 to 7000 7001 to 8000
(0 to 610) (610.1 to 914)† (914.1 to 1219)
Orifice
Mnfld Press
Orifice
Mnfld Press
Orifice
Mnfld Press
(1219.1 to
1524)
Orifice
Mnfld Press
(1524.1 to
1829)
Orifice
Mnfld Press
(1829.1 to
2134)
Orifice
Mnfld Press
(2134.1 to
2438)
Orifice
Mnfld Press
Table 7 – LPG or Propane Gas Manifold Pressure (in wc)*
HEATING
VALUE
BTU/CU.
FT.
2500
Orifice
Size
2500
Orifice
Size
‡ Applies to 100,000 BTU models when installed in the downflow or horizontal applications
Conversion: 1 in wc = 249 Pa NOTE: Propane data is based on 1.53 specific gravity. For fuels with different specific gravity consult the National Fuel Gas Code ANSI Z223.1 ---2009/NFPA
54--- 2009 or National Standard of Canada, Natural Gas and Propane Installation Code CSA B149.1--- 10. In the USA, derating of these furnaces at 2% (Natural Gas) and 4% (Propane Gas) has been tested and design--- certified by CSA.
{In Canada, the input rating must be derated 5% (Natural Gas) and 10% (Propane Gas) fo r altitudes of 2,000 to 4,500 (609.6 to 1371.6m) above sea level. Use
the 2001 to 3000 (609.9 to 914.4m) column in Tables 6 and 7.
FURNACE
INPUT
BTU/
BURNER
20000
19500‡
0 to 2000 2001 to 3000† 3001 to 4000 4001 to 5000 5001 to 6000 6001 to 7000 7001 to 8000
(0 to 610)
10.0 8.9 8.4 10.0 10.0 10.0 10.0
#55 #55 #55 #56 #56 #56 #56
9.9 8.4 8.0 10.0 10.0 10.0 9.6
#55 #55 #55 #56 #56 #56 #56
(610.1 to
914)†
The burner orifice part nos. are as follows: Orifice #41 333730--701
Orifice #42 333730--702 Orifice #43 333730--703 Orifice #44 333730--704 Orifice #45 333730--705 Orifice #46 333730--709 Orifice #47 333730--710 Orifice #48 333730--711 Orifice #49 333730--712 Orifice #54 333730--706 Orifice #55 333730--707 Orifice #56 333730--708
MEAN ELEVATION FEET ABOVE SEA LEVEL Ft (M)
(914.1 to
1219)
(1219.1 to
1524)
(1524.1 to
1829)
General Derating Rules
1. These furnaces may be used at full input rating when in­stalled at altitudes up to 2,000(610 M). When installed above 2,000(610 M), the input must be decreased 2% (natural) or 4% (Propane) for each 1000(305 M) above sea level in the USA. In Canada, the input rating must be derated 5% (natural) or 10% (Propane) for each 1000(305 M) above sea level. See Table 6 or 7 for required high altitude input rate.
2. For operation with natural gas at altitudes above 2,000 (610 M), orifice change and/or manifold pressure adjust­ments may be required for the gas supplied. First consult
(1829.1 to
2134)
(2134.1 to
2438)
36
Page 37
your local gas supplier, then refer to Table 6 for required pressure change and/or orifice change for high altitudes.
3. For operation with Propane gas, gas orifices MUST be changed and manifold pressure MUST be maintained as per Table 7 . Orifices can be ordered through our distribut­or. (See Fig. 38).
Nameplate Sea Level Input Rate x (Multiplier) [USA]
Elevation
2001- 3000 0.95 0.90
3001- 4000 0.93 0.86
4001- 5000 0.91 0.82
5001- 6000 0.89 0.78
6001- 7000 0.87 0.74
7001- 8000 0.85 0.70
* Based on mid---range of elevation.
High Altitude Input Rate =
High Altitude Multiplier
Natural Gas Propane Gas
High Altitude Air Pressure Switch
Altitudes over 4,000(1219 M) may require a different air pressure switch than the one installed at the factory. Check parts list for pressure switch and consult your distributor for part number and availability. In Canada, provincial codes may govern installation of switch. Check with governing authorities.
Changing Orifices for High Altitude
!
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Turn OFF electric power (at disconnect) and gas supply (at manual valve in gas line) when installing orifices. Lockout and tag with appropriate label. Installation of orifices requires a qualified service technician.
NOTE: Main burner orifices can be changed for high altitudes.
1. Disconnect gas line from gas valve.
2. Remove manifold from furnace.
3. Remove the orifices from the manifold and replace them with properly sized orifices.
4. Tighten orifices so it is seated and gas tight. (See Fig. 38)
5. Reinstall manifold. Ensure burners do NOT bind on new orifices.
Natural Gas Input Rating Check
SEE CHECKS AND ADJUSTMENTS, Natural Gas Input Rating Check in this manual.
Measure from face of orifice tothebacksideofthe manifold.
1.11″ (28.2mm)
1.21(30.8mm)
A07725
Fig. 38 -- Changing Orifices
Final Gas Piping Check
!
WARNING
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections. A fire or explosion could result causing property damage, personal injury and/or loss of life.
1. The furnace and the equipment shut off valve must be dis­connected from the gas supply piping system during any pressuretestingofthatsystemattestpressuresinexcessof
1
/2PSIG. Close the manual shut--off valve before testing
at such pressures.
2. When installation is complete, test all pipe connections for leaks with the gas pressure less than valve.
3. The furnace must be isolated from the gas supply system by closing the equipment shut off valve during any pres­sure testing of the gas supply system at test pressure equal to or less than
4. Apply a commercial soap solution to all joints to test for leaks. Correct any leaks indicated by bubbles.
5. Correct even the smallest leak at once.
6. Check for leaks at gas valve and orifice connections to the burner manifold while the furnace is operating.
1
/2PSI (3.5 kPa).
1
/2PSIG to the gas
ELECTRICAL WIRING
Power Supply Wiring
The furnace MUST be electrically wired and grounded in accordance with local codes, or in the absence of local codes with the latest edition of The National Electric Code, ANSI NFPA 70 and/or The Canadian Electric Code CSA C22.1.
The power supply to the furnace connections must be between 104 VAC and 127 VAC during furnace operation for acceptable performance.
Field wiring connections must be made inside the furnace connection box. A suitable strain relief should be used at the point the wires exit the furnace casing.
Copper conductors shall be used. Line voltage wires should conform to temperature limitation of 63° F(35° C) rise and be sized for the unit maximum amps stated on the rating plate. Add the full load amps for potential field--installed accessories such as electronic air cleaners and humidifiers that would receive power from the furnace control. The furnace control is rated for a maximum of 1.0 amp combined for EAC and HUM. Consult NEC or local codes for proper wire and circuit sizing.
NOTE: Furnace will not have normal operation if line polarity is reversed. Check ALL field and control connections prior to operation.
Junction Box (J- Box) Relocation
The J--box is installed on left side of casing. An alternate j--box location on right side can be used.
1. Remove bag containing two hole plugs and two self tap­ping screws from loose parts bag in blower compartment.
2. Remove two screws holding J--Box to casing.
3. Move large hole plug from right to left J--Box location.
4. Clip wire tie holding J--Box wires.
359AAV
37
Page 38
5. Move J--Box to alternate location and attach using two self
tapping screws from bag.
6. Apply two hole plugs from bag at left J--Box location.
Thermostat
Thermostat location has an important effect on the operation of the unit. Follow instructions included with thermostat for correct mounting and wiring.
Low voltage connections to furnace must be made on terminal board of furnace control.
Heat anticipator setting will need to be measured if 24VAC humidifier is installed. Measure current in series from R to W at the thermostat. Be sure 24VAC humidifier is wired up to control. Allow furnace to operate for 2 minutes before recording the AC amperage reading. Set anticipator on thermostat to recorded value.
Optional Equipment
All wiring from furnace to optional equipment MUST conform to
359AAV
local codes or, in the absence of local codes with the latest edition of The National Electric Code, ANSI NFPA 70 and/or The Canadian Electric Code CSA C22.1. Install wiring in accordance with manufacturer’s instructions. The wiring MUST have a minimum temperature rating of 105° C.
Humidifier/Electronic Air Cleaner
The furnace is wired for humidifier and/or electronic air cleaner connection.
!
CAUTION
REDUCED FURNACE LIFE HAZARD
Failure to follow this caution may result in reduced furnace life.
Do NOT exceed 115V/1.0 amp. maximum current load for both the EAC terminal and the HUM terminal combined.
NOTE: Junction Box can be mounted to either the left or right side.
115V. 60 Hz
HOT
NEUT.
W
BK
G
Connection
Box
Ground
Low Voltage Terminal Board
W
G
R
NOTE: 115 VAC/60Hz/single--phase Operating voltage range*: 127 VAC max, 104 VAC min.
* Permissible limits of voltage at which unit will operate satisfactorily
Representative drawing only, somemodels mayvary in appearance.
R
G
W
Y
G
O
N
O F
F
Models may have 1 or 2 pressure switches
A07726
Fig. 39 -- Electrical Connections
Furnace Control Fuse
The 24V circuit contains a 5--amp, automotive--type fuse located on furnace control. (See Fig. 40.) Any electrical shorts of 24V wiring during installation, service, or maintenance may cause fuse to blow. If fuse replacement is required, use only a fuse of identical size (5 amp.)
HUMIDIFIER -- The 24V HUM is energized when the pressure switch closes on a call for heat. The 115V HUM (called HUM on Control) is energized when the inducer is energized.
ELECTRONIC AIR CLEANER -- EAC is energized when there is a blower speed call, except is NOT energized when blower operates in the hard--wired continuous fan mode.
Furnace Control
The furnace control is preset at the factory with a fixed blower ON delay of 30 seconds in the heating mode. The blower OFF timing is preset at 140 seconds. If desired, the fan OFF delay can be reset to obtain the longest delay times while still maintaining comfort levels. See “Furnace Wiring Diagram” .
Blower Off Delay Jumper
24 VAC HUM
FUSE
Diagnostic Light
115 VAC HUM
EAC
A07727
Fig. 40 -- Control Board
DUCTWORK AND FILTER
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Do NOT draw return air from inside a closet or utility room where furnace is located. Return air duct MUST be sealed to furnace casing.
38
Page 39
Installation
A
NOTE: Design and install the air distribution system to comply with Air Conditioning Contractors of America manuals and/or NFPA pamphlets 90A and 90B or other approved methods that conform to local codes and good trade practices.
1. When furnace supply ducts carry air outside furnace area, seal return air duct to furnace casing and terminate duct outside furnace space.
2. Install air conditioning cooling coil (evaporator) on outlet side of furnace.
3. For furnaces installed without a cooling coil it is recom­mended that the outlet duct be provided with a removable access panel. This panel should be accessible when the furnace is installed so the exterior of the heat exchanger can be viewed for inspections. The access panel MUST be sealed to prevent leaks.
4. If separate evaporator and blower units are used, install good sealing dampers for air flow control. Chilled air go­ing through the furnace could cause condensation and shorten the furnace life.
NOTE: Dampers (field supplied) can be either automatic or manual. Manually operated dampers MUST be equipped with a means to prevent furnace or air conditioning operation unless damper is in the full heat or cool position.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Cool air passing over heat exchanger can cause condensate to form resulting in heat exchanger failure.
=14 /2″ (368.3mm) Height of Cutout for16″ x25″ (406.4 x 635mm) Filter
1
B=22
/2″ (571.5mm) Width of Cutout for 16″ x25″ (406.4 x 635mm) Filter
B
Embossed Area on Side of Furnace
A
Fig. 41 -- Side Return Air Cutout
2. Bottom returns can be made by removing the knockout
panel in the furnace base. Do NOT remove knock-out ex­cept for a bottom return.
3. Installation of locking-type dampers are recommended in all branches, or in individual ducts to balance system’s air flow.
4. Non-combustible, flexible duct connectors are recommen­ded for return and supply connections to furnace.
5. If air return grille is located close to the fan inlet, install at least one, 90° air turn between fan and inlet grille to re­duce noise.
NOTE: To further reduce noise, install acoustical air turning vanes and/or line the inside of duct with acoustical material.
Furnace Bottom
A07728
Sizing
Existing or new ductwork MUST be sized to handle the correct amount of airflow for either heating only or heating and air conditioning.
359AAV
Connections
NOTE: On upflow installations, return air can enter through either side, both sides, or the bottom. On horizontal installations the return air must enter through the knockout opening in the lower panel of the furnace. Return air can not of the furnace. When the furnace is located in an area near or adjacent to the living area, the system should be carefully designed with returns to minimize noise transmission through the return grille. Any blower moving a high volume of air will produce audible noise which could be objectionable to when the unit is located very close to living areas. It is advisable to route the return air ducts under the floor or through the attic.
1. For side connections using a 16x25″ (406 x 635 mm) filter, cut out the embossed area shown in Fig. 41. This will provide a 14 ate opening.
NOTE: Furnaces with 5 ton cooling rating may require both (left and right) side return or one side and bottom return. Side return air duct(s) is not permitted with horizontal furnace installation.
1
/2″ x221/2″ (368 x 572 mm) approxim-
enter through rear
Insulation
1. Insulate ductwork installed in attics or other areas exposed to outside temperatures with a minimum of 2(51 mm) insulation and vapor barrier.
2. Insulate ductwork in indoor unconditioned areas with a minimum of 1(25 mm) insulation with indoor type vapor barrier.
Filters
A Filter must be used: Filters are not supplied with these furnaces, but can be purchased
from the distributor. Use either filter type:
S Washable, high velocity filters are based on a maximum
air flow rating of 600 FPM.
S Disposable, low velocity filters are based on a maxim-
um air flow of 300 FPM when used with filter grille.
S See Circulating Air Blower Data for additional data.
NOTE: Disposable, low velocity filters may be replaced with washable, high velocity filter providing they meet the minimum size areas. Washable, high velocity filters can be replaced ONLY with same type and size.
39
Page 40
Fig. 42 -- Side Mounted Filter Rack
Filter Installation using Optional Filter Rack
When installing or removing a bottom mounted filter, slide the two side filter clips to the back of the furnace BEFORE installing or removing. This will allow the filter to clear the front raised edge of the furnace. Insert filter into side clips first and push filter
359AAV
back until it is fully engaged into back clip. When filter is in place, slide clips back into place midway on filter as shown in Fig. 43 and Fig. 44.
Center Clip s i d e -- t o -- s i d e
9(152.4mm)
Slide filter clips towards back before removing
Fig. 43 -- Bottom Mounted Filter Rack
25--24--18--1
A07729
A07691
Using Optional Standoff Filter Rack
A07731
Fig. 45 -- Standoff Filter Rack
Addition Of Air Conditioning
When a refrigeration coil is used in conjunction with this unit, it must be installed parallel with or on the discharge side of the unit to avoid condensation on the heat exchanger. All furnaces are designed with a break--away duct flange on the supply air side of the furnace. This allows for installation in the horizontal right or downflow applications. The coil installation instructions must be consulted for proper coil location and installation procedures. With a parallel flow arrangement, dampers must be installed to prevent chilled air from entering the furnace. If manually operated dampers are used, they must be equipped with a means to prevent operation of either unit unless the damper is in full heat or full cool position.
A3″ (76 mm) clearance is required on the right side of the furnace in order to run the condensate drain line. Copper or plastic tubing may be used for the condensate drain line.
CHECKS AND ADJUSTMENTS
NOTE: Verify the input rate of the furnace.
!
WARNING
11/
in.
2
(38.1)
26 Ga. Galvanized Steel FAST part number 1008482
Fig. 44 -- Filter Clip Construction
Refer to Fig. 45 and for guidelines to install filters. Furnaces which require larger filter media and have limited clearances on one side of furnace, require a standoff filter rack, see Fig. 45, available from your distributor.
3
in.
(76.2)
(31.8)
11/
in.
4
11
/
in.
16
(27)
A07730
FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death and /or property damage.
Turn OFF gas at shut off before connecting manometer.
Start- up
NOTE: Refer to the start--up procedures in the “User’s Information Manual”ortothe“Operating Instructions Label”on
the furnace.
!
WARNING
ELECTRICAL OPERATION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
If any sparks, odors or unusual noises occur, immediately shut OFF power to the furnace. Check for wiring errors or obstruction to blower.
40
Page 41
Gas Supply Pressure
Gas supply pressure should be within minimum and maximum values listed on rating plate (minimum and maximum pressures, refer to Table 5). Pressures are usually set by gas suppliers.
Manifold Gas Pressure Adjustment
NOTE: Make adjustment to manifold pressure with burners operating.
1. Remove the burner compartment door.
2. Remove the blower compartment door. Place a jumper
across furnace controls R to W. Replace blower compart- ment door.
3. With gas OFF, connect manometer to tapped opening on
gas valve. Use manometer with a 0 to 15 inches of water column range.
4. Turn gas ON and remove adjustment screw cover on gas
valve. Turn adjusting screw counterclockwise to decrease manifold pressure and clockwise to increase pressure.
NOTE: Adjustment screw cover MUST be replaced on gas control valve before reading manifold pressure and operating furnace.
5. Set manifold pressure to value as shown in Table 6 or 7
under GAS SUPPLY AND PIPING section in this manu- al.
6. When the manifold pressure is properly set, replace the ad­justment screw cover on the gas control valve.
Example
Natural Gas BTU Content
1,000 3,600 48 75,000
No. of Seconds Per Hour
1,000 x 3,600 ÷ 48 = 75,000 BTUH
3. Remove jumper wire from R to W.
4. Relight all appliances and ensure all pilots are operating.
Time Per
Cubic Foot in
Seconds
BTU Per
Hour
Main Burner Flame Check
Allow the furnace to run approximately 10 minutes then inspect the main burner. See Fig. 47.
Check for the following (Fig. 47):
S Stable and blue flames. Dust may cause orange tips or wisps of
yellow, but flames MUST NOT have solid, yellow tips.
S Flames extending directly from burner into heat exchanger. S Flames do NOT touch sides of heat exchanger
If any problems with main burner flames are noted, it may be necessary to adjust gas pressures, or check for drafts.
Burner Face
.
359AAV
Regulator Adjustment Under Cap
INLET
Inlet Pressure
1
/8NPT
Tap
ON
IN
OFF
HONEYWELL
Outlet Pressure Tap
1
/8NPT
OUTLET
A07732
Fig. 46 -- Typical Gas Valve
7. Remove blower compartment door. Remove jumper wire from thermostat connection on furnace control board. Re­move manometer connection from manifold pressure tap, and replace plug in manifold.
8. Check for leaks at plug.
9. Replace the burner and blower compartment doors.
Natural Gas Input Rating Check
NOTE: The gas meter can be used to measure input to furnace. Rating is based on a natural gas BTU content of 1,000 BTU’s per cubic meter. Check with gas supplier for actual BTU content.
1. Turn OFF gas supply to all appliances and start furnace. Use jumper wire on R to W for Heat.
2. Time how many seconds it takes the smallest dial on the gas meter to make one complete revolution. Refer to
Example.
NOTE: If meter uses a 2 cubic foot dial, divide results
(seconds) by two.
A07734
Fig. 47 -- Main Burner
NOTE: For igniter location see Fig. 48.
1/
2
(52.4)
5
/16(8)
16
1
/4(6.4)
NOTE: Flame sensor has a different orientation in all 050 models.
A07735
Fig. 48 -- Igniter Location
Temperature Rise Check
The blower speed MUST be set to give the correct air temperature rise through the furnace as marked on the rating plate. Temperature rise is the difference between supply and return air temperatures.
To check temperature rise,use the following procedure:
1.Place thermometers in supply and return air registers as close to furnace as possible, avoiding direct radiant heat from heat exchangers.
2.Operate furnace continuously for 15 minutes with all registers and duct dampers open.
3.Take reading and compare with range specified on rating plate.
4.If the correct amount of temperature rise is NOT obtained, it may be necessary to change blower speed. A higher blower speed
41
Page 42
will lower the temperature rise. A lower blower speed will increase the temperature rise.
Changing Blower Speed
!
WARNING
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal injury or death.
Turn OFF power to furnace before changing speed taps.
NOTE: The speed taps that the manufacturer sets from the factory for this product are based on a nominal 400 CFM per ton cooling and the basic mid range on the temperature rise for heating.
Since the manufacturer cannot establish the static pressure that will be applied to the unit, it is the responsibility of the installer dealer/contractor to select the proper speed taps for
359AAV
the application when the unit is installed.
If it is necessary to change speeds, refer to steps below.
!
CAUTION
REDUCED FURNACE LIFE HAZARD
Failure to follow this caution may result in reduced furnace life.
Use ONLY the blower motor speed taps insert indicated in the Circulation Air Blower Data for setting air temperature rise.
Table 8 – Blower Speed Chart
Wire Color Motor Speed
Black High
Orange* M e d --- Hi gh
Blue Medium
Red Low
* Med ---High speed may not be provided on all models.
1. Refer to Furnace Wiring Diagram for location of the heat­ing and cooling speed taps located on the furnace control as well as location of unused blower motor speed leads. Use the chart (Table 8) to determine the blower motor speed settings.
2. Change the heat or cool blower motor speed by removing the motor lead from the “Heat”or“Cool” terminal and replace it with the desired motor speed lead from the “Unused Motor Lead” location. Connect the wire previ­ously removed from the “Heat”or“Cool” terminal to the vacated “Unused Motor Lead” terminal.
3. If the same speed must be used for both heating and cool­ing, remove the undesired motor speed lead from the “Heat”or“Cool” terminal and connect that lead to the open terminal at “Unused Motor Lead” location. Attach a jumper between the “Heat”and“Cool” terminals and the remaining motor speed lead.
NOTE: For motors with (4) speed leads, it will be necessary to tape off the terminal of the motor speed lead removed from the “Heat”or“Cool” terminal with electrical tape since an open terminal will not be available at the “Unused Motor Lead” location.
Continuous- Fan Operation using “G”
Energizing the “G” terminal on the furnace control provides continuous fan operation. This is done by connecting the G terminal of the thermostat to the G terminal on the furnace control. When the FAN switch is turned from auto to ON the fan will operate continuously at “HEAT” speed. EAC will be energized in this mode.
NOTE: In heating, the fan will turn off during furnace ignition and warm up then restart at heating speed.
Hard Wired Continuous Fan Operation
A terminal is provided on the furnace control board located in the circulating blower compartment for operation of the continuous fan option. This connection is intended for the low speed motor tap, and has a lower contact rating (8 amps) than the heat and cool taps. When the low speed blower lead is connected to this terminal, this will provide low speed blower operation whenever the other two speeds (Heat or Cool) are not energized.
Thoroughly check the system after modification to ensure the proper operation of the circulating air blower in all modes of operation.
Separate Speed Selections for Heat, Cool, and Continuous Fan
Connect low speed lead from circulating motor to the “Cont.” terminal at the furnace control. The appropriate motor leads should already be connected to the “Heat”and“Cool” terminals.
Heating and Continuous Blower Speed the Same
If it is necessary to operate the heating speed and continuous blower speed using the same blower speed, connect a jumper between the “Heat”and“Cont.” terminals on the furnace control.
NOTE: There should be only ONE motor lead going to the “Heat”and“Cont.” terminals.
FURNACE MAINTENANCE
!
WARNING
FIRE, EXPLOSION, OR CARBON MONOXIDE HAZARDS
Failure to follow this warning could result in personal injury, death and/or property damage.
It is recommended that the furnace be inspected and serviced on an annual basis (before the heating season) by a qualified service technician.
!
WARNING
ELECTRICAL SHOCK, FIRE OR EXPLOSION HAZARD
Failure to follow this warning could result in personal injury, death, and/or property damage.
Before servicing, disconnect all electrical power to furnace. Lockout and tag with appropriate label.
When servicing controls, label all wires prior to disconnecting. Reconnect wires correctly.
Verify proper operation after servicing.
42
Page 43
See “User’s Information Manual” and the “Service Manual”.
SEQUENCE OF OPERATION
& DIAGNOSTICS
Following is the normal operating sequence:
Cooling (Y) Request:
24VAC signals applied to Y & G terminals of FCB (furnace control board)
S Cool motor speed is energized after 5 second Cool Fan On
Delay time.
Y & G signals removed from FCB
S Cool motor speed is de--energized after 90 second Cool Fan
Off Delay time.
Continuous Circulating Fan (G) Request:
S 24 VAC signal is applied to G terminal of the FCB. S Heat motor speed is energized without delay. S G signal removed from FCB. S Heat motor speed is de--energized after 5 second delay.
NOTE:
(1.) Furnace de--energizes the fan during the heat ex-
changer warm--up period on a call for Heating that occurs during a G request unless a blower motor lead is connected to the Cont terminal on the FCB, in which case see NOTE 2).
(2.) Heating or Cooling requests received during a Fan
request cause the fan speed to change to the ap­propriate heat or cool speed after the Fan on Delay time expires. The fan returns to continuous circulating speed after the selected Fan Off Delay time expires following loss of the Heating or Cooling request.
Continuous Circulating Fan Hard- Wired (Cont) Request
Field selected low speed motor tap installed on “CONT” terminal.
S Low speed is energized when power applied to furnace.
Operates at this speed continuously while there are no other blower demands from furnace control. Fan demands from furnace control for heat, cool or “G” will override hard--wired speed tap.
NOTE: EAC is NOT active for hard--wired mode but IS active for fan demands from furnace control for heat, cool and “G”.
Heating (W) Request:
Heating (W) Request:
S 24 VAC signal applied to W terminal of FCB.
S Inducer motor turns on and the pressure switch(es) close(s) S Following a 15 second prepurge delay, after the pressure
switches closes, the igniter begins a 17 second warm--up.
S The gas valve is energized, the main burners light and flame is
sensed.
S The igniter is de--energized after the main burners ignite. S FCB will delay blower operation for the 30 seconds timed from
the opening of the gas valve.
S W signal removed from FCB. S The gas valve de--energizes and the main burners go out. S The inducer runs for a 15 second postpurge period. S The fan stays at Heat speed. S The fan de--energizes after the selected Heat Fan Off Delay
time expires, timed from the gas valve de--energizing.
HUMIDIFIER -- The 24V HUM is energized when the pressure switch closes on a call for heat. The 115V HUM (called HUM on Control) is energized when the inducer is energized.
ELECTRONIC AIR CLEANER -- EAC is energized when there is a blower speed call. It is NOT energized when blower operates in the hard--wired continuous fan mode.
NOTE: If a new Heating request arrives while the control is waiting in the Heat Fan Off Delay time, the FCB will wait for the selected Heat Fan Off Delay then start a new heating cycle as long as the heat call remains.
Heating Request with Gas Shut Off:
24 VAC signal applied to W terminal of FCB. The FCB will attempt 4 cycles for ignition then go to soft lockout for 3 hours then try for ignition again as long as the heat call remains. Power reset will clear lockout.
S Inducer motor turns on S Following a 15 second prepurge delay, the igniter begins warm
up.
S The igniter glows red--hot for 22 seconds, then turns off. The
FCB flashes error code 6.
S The igniter stays off for 17 seconds, then begins to warm up
again.
S The igniter glows red hot for 22 seconds then turns off. The
FCB continues flashing error code 6.
S The igniter stays off for 17 seconds, then begins to warm up
again.
S The igniter glows red hot for 22 seconds then turns off. The
FCB continues flashing error code 6.
S The igniter stays off for 17 seconds, then begins to warm up
again.
S The igniter glows red hot for 22 seconds then turns off. The
FCB proceeds to soft lockout and stops flashing error code 6 and begins flashing error code 6 + 1.
S The inducer motor de--energizes after a 15 second post purge.
359AAV
43
Page 44
Blower Off Delay Jumper
24 VAC HUM
Diagnostic Light
115 VAC HUM
359AAV
FUSE
Fig. 49 -- Control Board
Control Board Diagnostic Codes
OFF = 24VAC or 115VAC is off, fuse is open Heartbeat = Normal operation or no previous Diagnostic Code ON SOLID = Soft Lockout --- Furnace Control Error (1 hr. delay) If code repeats immediately following power reset then replace
control 1Flash =Notused 2Flashes = Pressure switch(es) closed when should be open 3Flashes = Pressure switch open when should be closed 4Flashes = Limit or roll--- out switch open (less than 2 minutes) 5Flashes = Flame sensed out of sequence 6Flashes = Failure to ignite or flame sense lost while running 6+1Flashes = Soft Lockout --- Max trials for ignition reached (3 hr delay) 7Flashes = Soft Lockout --- Limit or roll---out switch open longer than two minutes (1 hr delay) (roll---out switch requires manual
reset) 8Flashes = Permanent Lockout --- Gas valve relay contact stuck closed or miswired gas valve (power reset only) 10 Flashes = Line voltage (115VAC) polarity reversed. If twinned, refer to twinning kit instructions
* If status code recall is needed, briefly (2 --- 3 seconds) remove then reconnect one limit switch wire (main or rollout) to display last stored status code. Do not removepowerorblowerdoorbeforeinitiatingstatus code recall or code will be lost. Code is automatically cleared after 72 hours or upon power reset.
* Proper flame sense microamps: 0.7 microamps D.C. minimum, 2.0 --- 4.0 microamps nominal
A07733
E2010 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 12/10
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
44
Catalog No. II359AAV--- 0 3
Replaces: II359AAV---02
Loading...