Bryant 355CAV A Series Troubleshooting Manual

troubleshooting guide
Variable Speed, Step-Modulating Electronic Condensing 355CAV Four-Way Multipoise Gas Furnace Series A
INDEX
PAGE
Safety Considerations................................................................................. 1
Instructions.................................................................................................. 1
Example ...................................................................................................... 2
General........................................................................................................ 2
Sequence of Operation ............................................................................... 2
Single-Stage Thermostat and Step-Modulating Heating
(Adaptive Mode)................................................................................ 2
Two-Stage Thermostat and Two-Stage Low/High Heating.............4
Two-Stage Thermostat and Two-Stage Medium/High Heating...... 4
Cooling Mode ....................................................................................5
Single-Speed Cooling ........................................................................ 5
Single-Stage Thermostat and Two-Speed Cooling (Adaptive
Mode) ................................................................................................. 5
Two-Stage Thermostat and Two-Speed Cooling ............................. 5
Thermidistat Mode............................................................................. 6
Super-Dehumidify Mode................................................................... 6
Continuous-Blower Mode ................................................................. 6
Heat Pump Defrost............................................................................. 7
Component Test.................................................................................7
Service/Status Code Instructions ............................................................... 8
Start Here .................................................................................................. 10
Rapid Flashing AMBER LED.................................................................11
Improper Cooling Air Flow .....................................................................12
Medium And/Or High Heat Temperature Rise Too Low....................... 13
Status Code 11 - No Previous Code......................................................... 15
Status Code 12 - Blower On After Power Up ......................................... 15
Status Code 13 - Limit Circuit Lockout .................................................. 16
Status Code 14 - Ignition Lockout ........................................................... 17
Status Code 15 - Blower Motor Lockout................................................. 17
Status Code 21 - Gas Heating Lockout.................................................... 17
Status Code 22 - Abnormal Flame-Proving Signal.................................18
Status Code 23 - Pressure Switch Did Not Open....................................18
Status Code 24 - Secondary Voltage Fuse Is Open................................. 19
Status Code 25 - Model Selection or Setup Error ...................................21
Status Code 31 - Medium-Heat Switch or HPSR Relay did not
Close or Reopen...............................................................................22
Status Code 32 - Low-Heat Pressure Switch Did Not Close or
Reopened.......................................................................................... 24
Status Code 33 - Limit Circuit Fault........................................................ 26
Status Code 34 - Ignition-Proving Fault..................................................28
Status Code 41 - Blower Motor Fault...................................................... 30
Status Code 42 - Inducer Motor Fault .....................................................32
Status Code 43 - Low-Heat Pressure Switch Open While Medium-
Heat Pressure Switch Is Closed....................................................... 34
Status Code 45 – Control Circuitry Lockout...........................................34
Cleanup and Start-Up Instructions........................................................... 35
APPENDIX A - Board Layout & Wiring Schematic ............................. 36
APPENDIX B - ECM Blower Motor Description & Operation............38
APPENDIX C - Pressure Check Diagram ..............................................40
APPENDIX D - Static Pressure Reading Location Diagrams................41
APPENDIX E - Quick Reference Information ....................................... 43
Cancels: NEW SM355CAV-01
APPENDIX F - Furnace Staging Algorithm...........................................44
SAFETY CONSIDERATIONS
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning coils, or cleaning and replacing filters. All other operations should be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with the unit, and other safety precautions that may apply.
Follow all safety codes. In the United States, follow all safety codes including the National Fuel Gas Code (NFGC) NFPA 54-2006/ANSI Z223.1-2006. In Canada, refer to the National Standard of Canada Natural Gas and Propane Installation Codes (NSCNGPIC), CSA B149.1-05.
Wear safety glasses and work gloves. Have a fire extinguisher available during start-up, adjustment procedures, and service calls.
Recognize safety information. This is the safety-alert symbol . When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION, and NOTE. The words DANGER, WARNING, and CAUTION are used with the safety-alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies hazards which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury, or product and property damage. NOTE is used to highlight suggestions which will result in enhanced installation, reliability, or operation.
INSTRUCTIONS
This guide uses your expertise and observations to lead you to the trouble spot as efficiently as possible. This is only intended as a guide and should not be used blindly. Your experience and expertise are of high value when troubleshooting this unit. Do not disregard all of your instincts.
The variable speed furnace control was designed with diagnostic capabilities built in. A AMBER LED is used to flash a status code which will lead you to one of the sections as listed in the Index.
You should ALWAYS begin in the START HERE section (see Index for page number) which will guide you to the appropriate section where a minimal number of steps will be used to correct the problem.
10-08
!
- 1 -
Once in a section, read the ACTION. An ACTION may have a number in the GO TO column. Do whatever the ACTION says, then proceed to the step indicated in the GO TO column.
If the ACTION is a question (a question will have a number in the YES or NO column), answer it YES or NO. If the answer is YES, go to the step indicated in the YES column. If the answer is NO, go to the step indicated in the NO column.
Let’s try our guide out using the EXAMPLE section below, and see how it works. Suppose that the problem is a defective low heat pressure switch (for example the contacts will not open). This is an internal problem and cannot simply be seen. We go to the START HERE section to Step 1.
EXAMPLE
Start Here Section
STEP ACTION YES NO GO TO
1. Step 1 tells us to remove main furnace door first and NOT TO REMOVE THE BLOWER
2 19 ACCESS PANEL. It then asks the question, “Is AMBER LED status light on?”. If the low heat pressure switch was defective, a pressure switch did not open status code would be flashing, so the answer is YES. We go to Step 2.
2. Step 2 asks the question, “Is the AMBER LED status light blinking rapidly without a pause?”.
3 4 If the low heat pressure switch was defective, a pressure switch did not open status code would be flashing, so the answer is NO. We go to Step 4.
4. Step 4 asks the question, “Is the AMBER LED status light blinking ON/OFF slowly with a
5 7 combination of short and long flashes?”. If the low heat pressure switch was defective, a pressure switch did not open status code would be flashing, so the answer is YES. We go to Step 5.
5. Step 5 tells us to determine the status code. The status code is a 2 digit number with the first
6 digit determined by the number of short flashes and the second digit by the number of long flashes. So we count the short and long flashes and see that status code 23 is flashing and go to Step 6.
6. Step 6 tells us to go to status code 23 section INDEX
GENERAL
The furnace must have a 115-vac power supply properly connected and grounded. Correct polarity must be maintained to enable gas heating operation.
The gas service pressure must not exceed 0.5 psig (14-in.wc), and no less than 0.16 psig (4.5-in.wc).
Thermostat wire connections to the furnace at R and W/W1 are the minimum required for gas heating operation. W2 must be connected for 2-stage heating thermostats. Y/Y2 and G are required to be connected to the furnace for single-stage cooling and heat pumps. Y1, Y/Y2, and G are required for two-stage cooling and heat pumps. G is required for continuous-fan. C
OM-24V is required for some clock
thermostats. These connections must be made at the 24-vac terminal block on the furnace control. (See Appendix A)
This furnace can be installed with either a single-stage heat/cool or a two-stage heat/cool thermostat.
!
CAUTION: This furnace is equipped with a manual reset switch in the gas control area. The switch will open and shut off power to the gas valve, if a flame rollout or overheating condition occurs in the gas control area. DO NOT bypass the switch. Correct inadequate combustion­air supply, component failure before resetting the switch.
Before operating the furnace, check each manual reset switch for continuity. If necessary, press and release the button to reset the switch.
SEQUENCE OF OPERATION
Using the schematic diagram in Appendix A, follow the sequence of operation through the different modes. Read and follow the wiring diagram very carefully.
Note: If a power interruption occurs during a call for heat (W/W1 or W/W1-and-W2), the control will start a 90-second blower-only ON period two seconds after power is restored, if the thermostat is still calling for gas heating. The amber LED light will flash code 12 during the 90-second period, after which the LED will be ON continuous, as long as no faults are detected. After the 90-second period, the furnace will respond to the thermostat normally.
The blower access panel must be installed for power to be conducted through the blower door interlock switch ILK to the furnace control CPU, transformer TRAN, inducer motor IDM, blower motor BLWM, hot-surface igniter HSI, throttling valve TV, and gas valve GV.
1. SINGLE-STAGE THERMOSTAT AND STEP­MODULATING HEATING (ADAPTIVE MODE)
Note: Low-heat only switch SW1-2 selects the low-heat only
operation mode when ON. Medium-heat only switch SW4-2 selects medium-heat only operation mode when ON. If both switches are ON the furnace control will default to medium-heat. If either or both switches are ON the furnace control will operate at two-stages only as referenced in Section 2 below. If both switches are OFF the furnace control will operate in the adaptive heating mode in response to a call for heat. When the W2 thermostat terminal is energized it will always cause high-heat operation as long as the R to W circuit is closed, regardless of the setting of the low-heat or medium-heat only switches.
- 2 -
This furnace can operate as a step-modulating furnace with a single-stage thermostat because the furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low-heat, medium-heat, or high-heat operation. This selection is based upon the stored history of the length of previous gas-heating periods of the single-stage thermostat.
The furnace will start up in either medium-, or high-heat. The furnace will operate in low-heat after starting and operating for 1 minute at medium-heat before transitioning to low-heat. The furnace control CPU determines the combined low-heat and medium-heat on-time (from 0 to 16 minutes) which is permitted before switching to high-heat.
If the power is interrupted, the stored history is erased and the furnace control CPU will select medium-heat for 1 minute, low­heat for 15 minutes and then switch to high-heat, as long as the thermostat continues to call for heat. Subsequent selection is based on stored history of the thermostat cycle times.
The wall thermostat "calls for heat", closing the R to W circuit. The furnace control CPU performs a self-check, verifies the low­heat and medium-heat pressure switch contacts LPS and MPS are open, then de-energizes the HPSR relay to close the NC contact.
a. Inducer Prepurge Period - The furnace control CPU
turns on inducer motor IDM and slowly increases the inducer motor speed. After the low-heat pressure switch LPS closes the furnace control CPU continues to increase the inducer motor speed until the medium-heat pressure switch MPS closes. When the medium-heat pressure switch MPS closes, throttling valve TV is energized, inducer motor RPM is noted by the furnace control CPU, and a 25-second prepurge period begins. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor during medium-heat prepurge, the first minute of medium-heat mode, and low-heat mode.
Note: The heat cycle can start in either high- or medium-
heat. If a high-heat cycle is initiated, the furnace control CPU will continue to increase the inducer motor speed after the medium-heat pressure switch MPS closes. When the medium-heat pressure switch closes, throttling valve TV is energized, inducer motor RPM is noted by the furnace control CPU, and a 25-second prepurge period begins. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor in high-heat pre­purge, and high-heat mode.
b. Igniter Warm-Up - At the end of the prepurge period, the
Hot-Surface Igniter HSI is energized for a 17-second igniter warm-up period.
c. Trial-For-Ignition Sequence - When the igniter warm-up
period is completed the main gas valve relay contact GVR closes to energize the gas valve solenoid GV-M. The gas valve solenoid GV-M permits gas flow to the burners where it is ignited. Five seconds after the GVR closes, a 2-second Flame-Proving period begins. The HSI igniter will remain energized until flame is sensed or until the 2-second flame proving period begins.
If the furnace control CPU selects high-heat operation, the high-heat gas valve solenoid GV-HI is energized when the high-heat pressure switch HPS closes.
d. Flame-Proving - When the burner flame is proved at the
flame-proving sensor electrode FSE, the furnace control CPU begins the blower-ON delay period and continues to hold the gas valve GV-M open. If the burner flame is not proved within two seconds, the control CPU will close the gas valve GV-M, and the control CPU will repeat the ignition sequence for up to three more Trials-For-Ignition before going to Ignition-Lockout. Lockout will be reset automatically after three hours, by momentarily interrupting 115 vac power to the furnace, or by interrupting 24 vac power at SEC1 or SEC2 to the furnace control CPU (not at W/W1, G, R, etc.).
If flame is proved when flame should not be present, the furnace control CPU will lock out of Gas-Heating mode and operate the inducer motor IDM at full speed until flame is no longer proved.
e. Inducer Speed Change – If the cycle starts in medium-
heat, the furnace control CPU reduces the inducer speed slightly after flame sense. The reduction in speed in medium-heat is to optimize combustion for maximum efficiency. If the cycle starts in high-heat, the furnace control CPU increases the inducer speed 15 seconds after flame sense.
f. Blower-On delay – If the burner flame is proven the
blower-ON delay for low-heat and high-heat are as follows:
Medium-heat – 60 seconds after the gas valve GV-M is opened the blower motor BLWM is turned ON at low- or medium-heat airflow.
High-heat – 35 seconds after the gas valve GV-M is opened the BLWM is turned ON at high-heat airflow.
Simultaneously, the humidifier terminal HUM and electronic air cleaner terminal EAC-1 are energized and remain energized throughout the heating cycle.
g. Switching from Medium- to Low-Heat – If the furnace
control switches from medium-heat to low-heat, the furnace control will turn the blower ON at low-heat airflow, energize the HPSR relay to open the NC contact, and slowly decrease the inducer motor speed. When the HPSR relay is energized and the NC contact opens the throttling valve TV is de-energized and the gas flow reduces to low­heat rate.
Switching from Low- to Medium-Heat – If the furnace
control CPU switches from low-heat to medium-heat, the furnace control CPU will de-energize the HPSR relay to close the NC contact and slowly increase the inducer motor speed until the medium-heat pressure switch MPS closes. When the medium-heat pressure switch MPS closes, the throttling valve solenoid TV is energized and the inducer motor RPM is noted by the furnace control CPU. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor in medium-heat and high-heat mode. The blower motor BLWM will transition
- 3 -
to medium-heat airflow five seconds after the furnace control CPU switches from low-heat to medium-heat.
Switching from Low- to High-Heat – If the furnace
control CPU switches from low-heat to high-heat, the furnace control CPU will de-energize the HPSR relay to close the NC contact and slowly increase the inducer motor speed until the medium-heat pressure switch MPS closes. When the medium-heat pressure switch MPS closes, the throttling valve solenoid TV is energized and the inducer motor RPM is noted by the furnace control CPU. The RPM is used to evaluate vent system resistance. This evaluation is then used to determine the required RPM necessary to operate the inducer motor in medium- and high-heat mode. The blower motor BLWM will transition to high-heat airflow five seconds after the furnace control CPU switches from low-heat to high-heat. As the inducer RPM gradually increases the high-heat pressure switch HPS closes and the gas valve solenoid GV-HI is energized.
Switching from Medium- to High-Heat – If the furnace
control CPU switches from medium-heat to high-heat, the furnace control CPU will gradually increase the inducer motor speed to the required high-heat RPM. The blower motor BLWM will transition to high-heat airflow five seconds after the furnace control CPU switches from medium-heat to high-heat. As the inducer RPM gradually increases the high-heat pressure switch HPS closes and the gas valve solenoid GV-HI is energized.
Switching from High- to Medium- or Low-Heat – The
furnace control CPU will not switch from high-heat to medium- or low-heat while the thermostat R to W circuit is closed when using a single-stage thermostat.
h. Blower-Off Delay - When the thermostat is satisfied, the
R to W circuit is opened, de-energizing the gas valve GV­M, stopping gas flow to the burners, and de-energizing the throttling valve TV, and humidifier terminal HUM. The inducer motor IDM will remain energized for a 15-second post-purge period. The blower motor BLWM and air cleaner terminal EAC-1 will remain energized at low-heat airflow or transition to low-heat airflow for 90, 120, 150, or 180 seconds (depending on selection at blower-OFF delay switches). The furnace control CPU is factory-set for a 120­second blower-OFF delay.
2. TWO-STAGE THERMOSTAT AND TWO-STAGE LOW/HIGH HEATING
Note: In this mode the low-heat only switch SW1-2 must be
ON to select the low-heat only operation mode in response to closing the thermostat R to W1 circuit. Closing the thermostat R to W1-and-W2 circuits always causes high-heat operation, regardless of the setting of the low-heat only switch.
The furnace will start up in either medium-, or high-heat. The furnace will operate in low-heat after starting and operating for 1 minute at medium-heat before transitioning to low-heat.
The wall thermostat "calls for heat", closing the R to W1 circuit for low-heat or closing the R to W1-and-W2 circuits for high­heat. The furnace control performs a self-check, and verifies the low-heat and medium-heat pressure switch contacts LPS and
MPS are open, then de-energizes the HPSR relay to close the NC contact.
The start up and shut down functions and delays described above apply to the 2-stage low/high heating mode as well, except for switching from high- to low-heat.
a. Switching from High- to Low-Heat - If the thermostat
R to W2 circuit opens, and the R to W1 circuit remains closed, the furnace control CPU will gradually decrease the inducer motor speed to the required medium-heat RPM. When the inducer motor IDM reduces pressure sufficiently, the high-heat pressure switch HPS will open and the high­heat gas valve solenoid GV-HI will be de-energized. The gas valve solenoid GV-M will remain energized as long as the low-heat pressure switch LPS remains closed. When the inducer motor speed gets within 15% of the required medium-heat RPM the furnace control CPU will start a 5 second blower airflow change delay. After the 5 second blower airflow change delay is completed the blower airflow will transition to low-heat airflow. At this point the furnace control CPU will energize the HPSR relay to open the NC contact and slowly decrease the inducer motor speed to the required low-heat RPM. When the HPSR relay is energized and the NC contact opens the throttling valve TV is de-energized and the gas flow reduces to low­heat rate. When the inducer motor IDM reduces pressure sufficiently, the medium-heat pressure switch MPS will open.
3. TWO-STAGE THERMOSTAT AND TWO-STAGE MEDIUM/HIGH HEATING
Note: In this mode the medium-heat only switch SW4-2 must
be ON to select the medium-heat only operation mode in response to closing the thermostat R to W1 circuit. Closing the thermostat R to W1-and-W2 circuits always causes high-heat operation, regardless of the setting of the medium-heat only switch.
The wall thermostat "calls for heat", closing the R to W1 circuit for medium-heat or closing the R to W1-and-W2 circuits for high-heat. The furnace control performs a self-check, and verifies the low-heat and medium-heat pressure switch contacts LPS and MPS are open, then de-energizes the HPSR relay to close the NC contact.
The start up and shut down functions and delays described above apply to the 2-stage medium/high heating mode as well, except for switching from high- to medium-heat.
a. Switching from High- to Medium-Heat – If the
thermostat R to W2 circuit opens, and the R to W1 circuit remains closed, the furnace control CPU will gradually decrease the inducer motor speed to the required medium­heat RPM. When the inducer motor IDM reduces pressure sufficiently, the high-heat pressure switch HPS will open and the high-heat gas valve solenoid GV-HI will be de­energized. The gas valve solenoid GV-M will remain energized as long as the low-heat pressure switch LPS remains closed. When the inducer motor speed gets within 15% of the required medium-heat RPM the furnace control CPU will start a 5 second blower airflow change delay. After the 5 second blower airflow change delay is completed the blower airflow will transition to medium­heat airflow.
- 4 -
4. COOLING MODE
The thermostat "calls for cooling".
a. Single-Speed Cooling
The thermostat closes the R to G-and-Y circuits. The R to Y circuit starts the outdoor unit, and the R to G-and-Y/Y2 circuits start the furnace blower motor BLWM on cooling airflow. Cooling airflow is based on the A/C selection shown in Table 1.
The electronic air cleaner terminal EAC-1 is energized with 115 vac when the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y circuits are opened. The outdoor unit will stop, and the furnace blower motor BLWM will continue operating at cooling airflow for an additional 90 seconds. Jumper Y/Y2 to DHUM to reduce the cooling off-delay to 5 seconds. (See Fig. 1.)
b. Single-Stage Thermostat and Two-Speed Cooling
(Adaptive Mode)
This furnace can operate a two-speed cooling unit with a single-stage thermostat because the furnace control CPU includes a programmed adaptive sequence of controlled operation, which selects low-cooling or high-cooling operation. This selection is based upon the stored history of the length of previous cooling period of the single-stage thermostat.
Table 1
AIR CONDITIONING (A/C) OR CONTINUOUS-FAN (CF)
BASED ON 350 CFM/TON (SETUP SWITCH SW1-5 OFF)
MODEL
SIZE
060, 3T-080
5T-080, 100
120
BASED ON 400 CFM/TON (SETUP SWITCH SW1-5 ON)
MODEL
SIZE
060, 3T-080
5T-080, 100
120
1. DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2. DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
3. SWITCH POSITIONS ARE ALSO SHOWN ON FURNACE WIRING DIAGRAM
Note: The air conditioning relay disable jumper ACRDJ must be connected to enable the adaptive cooling mode in response to a call for cooling. (See Fig. 1.) When in place the furnace control CPU can turn on the air conditioning relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to high-cooling.
AIRFLOW SELECTION CHART
SETUP SWITCH SW3 POSITIONS
525
DEF.
DEF.
DEF.
DEF.
DEF.
DEF.
700
2
700
875 1050
2
700 8752 1050
SETUP SWITCH SW3 POSITIONS
600
800
2
800
2
800 10002 1200
1000
1000 1200
875
1050
1225
1225
1200
1400
1400
1225
1225
1750
1750
1400
2000
2000
1
1
1
1
1225
1750
2100
1400
2000
2100
1
1400
1400
1400
1
1600
1600
The furnace control CPU can start up the cooling unit in either low- or high-cooling. If starting up in low-cooling, the furnace control CPU determines the low-cooling on­time (from 0 to 20 minutes) which is permitted before switching to high-cooling.
If the power is interrupted, the stored history is erased and the furnace control CPU will select low-cooling for up to 20 minutes and then energize the air conditioning relay ACR to energize the Y/Y2 terminal and switch the outdoor unit to high-cooling, as long as the thermostat continues to call for cooling. Subsequent selection is based on stored history of the thermostat cycle times.
The wall thermostat “calls for cooling”, closing the R to G-and-Y circuits. The R to Y1 circuit starts the outdoor unit on low-cooling speed, and the R to G-and-Y1 circuits starts the furnace blower motor BLWM at low­cooling airflow which is the true on-board CF selection as shown in Table 1.
If the furnace control CPU switches from low-cooling to high-cooling, the furnace control CPU will energize the air conditioning relay ACR. When the air conditioning relay ACR is energized the R to Y1-and-Y2 circuits switch the outdoor unit to high-cooling speed, and the R to G-and­Y1-and-Y/Y2 circuits transition the furnace blower motor BLWM to high-cooling airflow. High-cooling airflow is based on the A/C selection shown in Table 1.
Note: When transitioning from low-cooling to high­cooling the outdoor unit compressor will shut down for 1 minute while the furnace blower motor BLWM transitions to run at high-cooling airflow.
The electronic air cleaner terminal EAC-1 is energized with 115 vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y circuit are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC-1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off-delay to 5 seconds. (See Fig. 1.)
c. Two-Stage Thermostat and Two-Speed Cooling
Note: The air conditioning relay disable jumper ACRDJ must be disconnected to allow thermostat control of the outdoor unit staging. (See Fig. 1.)
The thermostat closes the R to G-and-Y1 circuits for low­cooling or closes the R to G-and-Y1-and-Y2 circuits for high-cooling. The R to Y1 circuit starts the outdoor unit on low-cooling speed, and the R to G-and-Y1 circuit starts the furnace blower motor BLWM at low-cooling airflow which is the true on-board CF selection as shown in Table
1. The R to Y1-and-Y2 circuits start the outdoor unit on high-cooling speed, and the R to G-and-Y/Y2 circuits start the furnace blower motor BLWM at high-cooling airflow. High-cooling airflow is based on the A/C selection shown in Table 1.
- 5 -
The electronic air cleaner terminal EAC-1 is energized with 115 vac whenever the blower motor BLWM is operating.
When the thermostat is satisfied, the R to G-and-Y1 or R to G-and-Y1-and-Y2 circuits are opened. The outdoor unit stops, and the furnace blower BLWM and electronic air cleaner terminal EAC-1 will remain energized for an additional 90 seconds. Jumper Y1 to DHUM to reduce the cooling off-delay to 5 seconds. (See Fig. 1.)
5. THERMIDISTAT MODE
The dehumidification output, DHUM on the Thermidistat should be connected to the furnace control thermostat terminal DHUM. When there is a dehumidify demand, the DHUM input is activated, which means 24 vac signal is removed from the DHUM input terminal. In other words, the DHUM input logic is reversed. The DHUM input is turned ON when no dehumidify demand exists. Once 24 vac is detected by the furnace control on the DHUM input, the furnace control operates in Thermidistat mode. If the DHUM input is low for more than 48 hours, the furnace control reverts back to non­Thermidistat mode.
The cooling operation described in item 3. above also applies to operation with a Thermidistat. The exceptions are listed below:
a. When the R to G-and-Y1 circuit is closed and there is a
demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 86% of low-cooling airflow which is the true on-board CF selection as shown in Table 1.
b. When the R to G-and Y/Y2 circuit is closed and there is a
demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 86% of high­cooling airflow. High-cooling airflow is based on the A/C selection shown in Table 1.
c. When the “call for cooling” is satisfied and there is a
demand for dehumidification, the cooling blower-off delay is decreased from 90 seconds to 5 seconds.
6. SUPER-DEHUMIDIFY MODE
Super-Dehumidify mode can only be entered if the furnace control is in the Thermidistat mode and there is a demand for dehumidification. The cooling operation described in item 3. above also applies to operation with a Thermidistat. The exceptions are listed below:
a. Low Cooling – When the R to Y1 circuit is closed, R to G
circuit is open, and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 65% of low-cooling airflow for a maximum of 10 minutes each cooling cycle or until the R to G circuit closes or the demand for dehumidification is satisfied. Low­cooling airflow is the true on-board CF selection as shown in Table 1.
b. High Cooling – When the R to Y/Y2 circuit is closed, R to
G circuit is open, and there is a demand for dehumidification, the furnace blower motor BLWM will drop the blower airflow to 65% of high-cooling airflow for a maximum of 10 minutes each cooling cycle or until the R
to G circuit closes or the demand for dehumidification is satisfied. High-cooling airflow is based on the A/C selection shown in Table 1.
c. Cooling Off-Delay – When the “call for cooling” is
satisfied and there is a demand for dehumidification, the cooling blower-off delay is decreased from 90 seconds to 5 seconds.
7. Continuous Blower Mode
When the R to G circuit is closed by the thermostat, the blower motor BLWM will operate at continuous blower airflow. Continuous blower airflow selection is initially based on the CF selection shown in Table 1. Factory default is shown in Table
1. Terminal EAC-1 is energized as long as the blower motor BLWM is energized.
During a call for heat, the furnace control CPU will transition the blower motor BLWM to continuous blower airflow, low­heat airflow, or the midrange airflow, whichever is lowest. The blower motor BLWM will remain ON until the main burners ignite then shut OFF and remain OFF for the blower-ON delay (60 seconds in medium-heat, and 35 seconds in high-heat), allowing the furnace heat exchangers to heat up more quickly, then restarts at the end of the blower-ON delay period at low­heat, medium-heat, or high-heat airflow respectively.
The blower motor BLWM will revert to continuous-blower airflow after the heating cycle is completed. In medium- or high-heat, the furnace control CPU will drop the blower motor BLWM to low-heat airflow during the selected blower-OFF delay period before transitioning to continuous-blower airflow.
When the thermostat "calls for low-cooling", the blower motor BLWM will switch to low-cooling airflow. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds at low-cooling airflow before transitioning back to continuous-blower airflow.
When the thermostat "calls for high-cooling", the blower motor BLWM will switch to high cooling airflow. When the thermostat is satisfied, the blower motor BLWM will operate an additional 90 seconds at high-cooling airflow before transitioning back to continuous-blower airflow.
When the R to G circuit is opened, the blower motor BLWM will continue operating for an additional 5 seconds, if no other function requires blower motor BLWM operation.
a. Continuous Blower Speed Selection from Thermostat
To select different continuous-blower airflows from the room thermostat, momentarily turn off the FAN switch or push-button on the room thermostat for 1-3 seconds after the blower motor BLWM is operating. The furnace control CPU will shift the continuous-blower airflow from the factory setting to the next highest CF selection airflow as shown in Table 1. Momentarily turning off the FAN switch again at the thermostat will shift the continuous­blower airflow up one more increment. If you repeat this procedure enough you will eventually shift the continuous­blower airflow to the lowest CF selection as shown in Table 1. The selection can be changed as many times as
- 6 -
desired and is stored in the memory to be automatically used following a power interruption.
8. HEAT PUMP DEFROST
When installed with a heat pump, the furnace control automatically changes the timing sequence to avoid long blower off times during demand defrost cycles. Whenever W/W1 is energized along with Y1 or Y/Y2, the furnace control CPU will transition to or bring on the blower motor BLWM at cooling airflow, low-heat airflow, or the midrange airflow, whichever is lowest. The blower motor BLWM will remain on until the main burners ignite then shut OFF and remain OFF for 25 seconds before coming back on at heating airflow. When the W/W1 input signal disappears, the furnace control begins a normal inducer post-purge period while changing the blower airflow. If Y/Y2 input is still energized the furnace control CPU will transition the blower motor BLWM airflow to cooling airflow. If Y/Y2 input signal disappears and the Y1 input is still energized the furnace control CPU will transition the blower motor BLWM to low-cooling airflow. If both the Y1 and Y/Y2 signals disappear at the same time, the blower motor BLWM will remain on at low-heat airflow for the selected blower-OFF delay period. At the end of the blower-OFF delay, the blower motor BLWM will shut OFF unless G is still energized, in which case the blower motor BLWM will operate at continuous blower airflow.
9. COMPONENT TEST
The furnace features a component test system to help diagnose a system problem in the case of a component failure. To initiate the component test procedure, ensure that there are no thermostat inputs to the control and all time delays have expired. Turn on setup switch SW1-6. (See Appendix A)
Note: The component test feature will not operate if the control is receiving any thermostat signals or until all time delays have expired.
The component test sequence is as follows:
a. The furnace control CPU turns the inducer motor IDM ON
at medium speed and keeps it ON through step c.
b. After waiting 10 seconds the furnace control CPU turns
the hot surface igniter ON for 15 seconds, then OFF.
c. The furnace control CPU then turns the blower motor
BLWM on at midrange airflow for 15 seconds, then OFF.
d. After shutting the blower motor OFF the furnace control
CPU shuts the inducer motor IDM OFF.
Note: The EAC terminals are energized when the blower is operating.
After the component test is completed, 1 or more status codes (11, 25, 41, or 42) will flash. See Service Label on blower access panel or Service/Status Code Instructions for explanation of status codes.
Note: To repeat component test, turn setup switch SW1-6 to OFF and then back ON.
- 7 -
SERVICE/STATUS CODE INSTRUCTIONS
If status code recall is needed disconnect the “R” thermostat lead, reset power, and put setup switch “SW1-1” in the ON position. To clear the status code history put setup switch “SW1-1” in the ON position and jumper thermostat terminals “R”, “W/W1”, and “Y/Y2” simultaneously until status code #11 is flashed.
LED CODE STATUS
CONTINUOUS OFF - Check for 115 VAC at L1 and L2, and 24 VAC at SEC-1 and SEC-2. CONTINUOUS ON - Control has 24 VAC power. RAPID FLASHING - Line voltage (115 VAC) polarity
reversed.
EACH OF THE FOLLOWING STATUS CODES IS A TWO DIGIT NUMBER WITH THE FIRST DIGIT DETERMINED BY THE NUMBER OF SHORT FLASHES AND THE SECOND DIGIT BY THE NUMBER OF LONG FLASHES.
11 NO PREVIOUS CODE – Stored status codes are erased automatically after 72 hours or as specified above. 12 BLOWER ON AFTER POWER UP – (115 VAC or 24 VAC) – Blower runs for 90 seconds, if unit is powered up during a call for heat (R-
W/W1 closed) or (R-W/W1 opens) during the blower on-delay period.
13 LIMIT CIRCUIT LOCKOUT – Lockout occurs if the limit, or flame rollout switch is open longer than 3 minutes or 10 successive limit trips
occurred during high-heat. Control will auto reset after 3 hours. Refer to status code #33.
14 IGNITION LOCKOUT – Control will auto reset after 3 hours. Refer to status code #34. 15 BLOWER MOTOR LOCKOUT – Indicates the blower failed to reach 250 RPM or the blower failed to communicate within 30 seconds after
being turned ON in two successive heating cycles. Control will auto reset after 3 hours. Refer to status code #41.
21 GAS HEATING LOCKOUT – Control will NOT auto reset. Check for:
- Mis-wired gas valve.
- Defective control (valve relay).
22 ABNORMAL FLAME-PROVING SIGNAL – Flame is proved while gas valve is de-energized. Inducer will run until fault is cleared. Check
for:
- Leaky gas valve.
- Stuck-open gas valve.
23 PRESSURE SWITCH DID NOT OPEN – Check for:
- Obstructed pressure tubing.
- Pressure switch stuck closed.
24 SECONDARY VOLTAGE FUSE IS OPEN – Check for :
- Short circuit in secondary voltage (24 VAC) wiring.
25 MODEL SELECTION OR SETUP ERROR – Either Indicates the model plug (PL4) is missing or incorrect or setup switch “SW1-1” or
“SW1-6” is positioned improperly. If code flashes only 4 times on power-up control is defaulting to model selection stored in memory. Check the following:
- Thermostat call with “SW1-1” ON.
- Thermostat call with “SW1-6” ON.
- “SW1-1” and “SW1-6” both ON together.
- Two different furnace models twinned.
- Wiring diagram for model plug number and resistance values if code flashes continuously.
- Board does not recognize new model plugs HK70EZ017 – 021. New board software version V12 or later required.
31 MEDIUM-HEAT PRESSURE SWITCH OR HPSR RELAY DID NOT CLOSE OR REOPENED – Indicates the medium-heat pressure
switch input failed to close on a call for medium- or high-heat, or opened during medium- or high-heat. Control relay may be defective or gas valve is mis-wired. Refer to status code #32.
32 LOW-HEAT PRESSURE SWITCH DID NOT CLOSE OR REOPENED – Indicates the low-heat pressure switch input failed to close on a
call for low-heat, or opened during low-heat. If opens during blower on-delay period , blower will come on for the selected blower off-delay. If opens during low heat within 5 minutes after ignition the next heating cycle will be restricted to high-heat. Check for:
- Proper vent sizing.
- Plugged condensate drain.
- Low inlet gas pressure (if LGPS used).
- Excessive wind.
- Restricted combustion air supply.
- Improper pressure switch wiring.
- Failed or “Out-of-Calibration” pressure switches.
- Water in vent piping, possible sagging pipe.
- Disconnected or obstructed pressure tubing.
- 8 -
33 LIMIT CIRCUIT FAULT – Indicates the limit, or flame rollout is open or the furnace is operating in high-heat only mode due to 2 successive
low or medium heat limit trips. Blower will run at medium heat airflow for 4 minutes or until open switch remakes whichever is longer. If open longer than 3 minutes, code changes to lockout #13. If open less than 3 minutes status code #33 continues to flash until blower shuts off. Flame rollout switch requires manual reset. Check for:
- Proper rear air baffle.
- Loose blower wheel.
- Defective switch or connections.
- Improper low- or medium- heat gas input adjustment.
- Stuck high-heat solenoid in gas valve
- Improper or misaligned limit and/or limit shield.
34 IGNITION PROVING FAILURE – Control will try three more times before lockout #14 occurs. If flame signal is lost during blower on-delay
period, blower will come on for the selected blower off-delay. Check for:
- Low inlet gas pressure.
- Control ground continuity.
- Gas valve defective or turned off.
- Defective Hot Surface Igniter.
- Manual valve shut off.
- Oxide buildup on flame sensor (clean with fine steel wool).
- Proper flame sense micro amps (.5 micro amps DC min., 4.0 – 6.0 nominal).
- Green/Yellow wire MUST be connected to furnace sheet metal.
- Inadequate flame carryover or rough ignition.
- Flame sensor must not be grounded.
41 BLOWER MOTOR FAULT – Indicates the blower failed to reach 250 RPM or the blower failed to communicate within the prescribed time
limits. Thirty seconds after being turned ON or ten seconds during steady-state operation.
42 INDUCER MOTOR FAULT – Indicates the inducer has not started within 20 seconds after a call for heat, the inducer motor RPM is outside its
valid range of operation, or the inducer RPM signal was lost for 5 seconds during operation. Check for:
- Proper vent sizing.
- Restricted combustion air supply.
- Failed inducer motor.
- Improper motor wiring.
43 LOW-HEAT PRESSURE SWITCH OPEN WHILE MEDIUM-HEAT PRESSURE SWITCH IS CLOSED – Check for:
- Low inlet gas pressure (if LGPS used).
- Plugged condensate drain.
- Improper pressure switch wiring.
- Water in vent piping, possible sagging pipe.
- Stuck open low-heat pressure switch.
- Disconnected or obstructed pressure tubing.
45 CONTROL CIRCUITRY LOCKOUT – Auto-reset after 1 hour lockout due to:
- Flame sense circuit failure.
- Gas valve relay stuck open.
- Software check error. Reset power to clear lockout. Replace control if status code repeats.
COMPONENT TEST
To initiate the component test sequence, shut “OFF” the room thermostat or disconnect the “R” thermostat lead. Reset power and then put setup switch “SW1-6” in the ON position to start the component test sequence. Once initiated the furnace control will turn the inducer ON at high-heat speed. The inducer motor will run for the entire test. The hot surface igniter and blower motor will be turned ON for 15 seconds each. When the blower is turned OFF the inducer will be turned OFF. When the component test is completed one or more of the following codes will flash.
LED CODE DESCRIPTION
11 Indicates the blower motor tested OK. Visual check of inducer motor and hot surface igniter required. 25 SETUP ERROR – Same as code 25 above. 41 BLOWER MOTOR FAULT – Indicates blower motor failed test. Check blower, wiring, and furnace control. 42 INDUCER MOTOR FAULT – Indicates inducer motor failed test. Check inducer, wiring, and furnace control.
To repeat component test turn setup switch “SW1-6” OFF and then back ON. After component test is completed put setup switch “SW1-6” in the OFF position and reconnect the “R” thermostat lead.
- 9 -
START HERE - If a problem exists, the service technician should always begin troubleshooting here.
SPECIAL NOTE: ALL VOLTMETERS ARE NOT THE SAME - YOUR VOLTAGE READINGS WILL VARY. THIS APPLIES TO THE
ENTIRE CONTENT OF THIS TROUBLESHOOTING MANUAL. THEY ARE NOT ABSOLUTE VALUES. CORRECT 115-VAC VOLTAGE, CURRENT, AND POWER MEASUREMENTS CANNOT BE TAKEN ON VARIABLE SPEED FURNACES UNLESS USING A TRUE RMS METER.
STEP ACTION YES NO GO TO
1. Remove main furnace door first. DO NOT REMOVE BLOWER ACCESS PANEL! Record status of AMBER LED. See Service/Status Code Instructions.
Is AMBER LED status light on?
2. Is the AMBER LED status light blinking rapidly without a pause? 3 4
3. Go to the page number indicated in the Index for RAPID FLASHING LED. INDEX
4. Is the AMBER LED status light blinking ON/OFF slowly with a combination of short and long flashes?
5. Determine status code. The status code is a 2 digit number with the first digit determined by the number of short flashes and the second digit by the number of long flashes.
6. Go to page number indicated in the Index for the section covering the status code. INDEX
7. To retrieve previous codes, disconnect the User Interface ABCD connector (if used) or the R thermostat lead (if used) from the furnace control board and wait for the blower to turn off if it is running. Put setup switch SW1-1 in the ON position and record the status codes listed in the status code history. The status codes will flash in the order of occurrence. Read status codes until an 11 code flashes. After the 11 code flashes the status codes will repeat.
8. Was there a previous status code other than code 11?
Note: Status codes are erased after 72 hours or can be manually erased by putting setup switch SW1-1 in the ON position and jumpering R, W/W1, and Y/Y2 simultaneously until status code 11 is flashed.
9. Go to page number indicated in the Index for the section covering the first previous status code.
10. Does the problem appear to be low cooling airflow? 11 12
11. Go to page number indicated in Index for the section covering IMPROPER COOLING AIRFLOW.
12. Set thermostat to call for heat and set the thermostat fan control to AUTO position if equipped. 13
13. Does the furnace respond to the call for heat? 14 28
14. Observe operation of furnace for 20 minutes or until AMBER LED status light starts blinking. 15
15. Does the AMBER LED status light blink ON/OFF slowly with a combination of short and long flashes?
16. Is the temperature rise below the range specified on the rating plate when the unit is operating in medium and/or high heat?
Note: If the temperature rise is above the range specified on the rating plate refer to the Start­Up and Adjustment section in the Installation, Start-Up, and Operating Instructions.
17. Go to page number indicated in Index for the section covering MEDIUM AND/OR HIGH HEAT TEMPERATURE RISE TOO LOW (COLD BLOW).
18. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. INDEX
19. Make sure power is being supplied to the furnace. 20
20. Check fuses, breakers, or manual disconnects to be sure they are correctly set. If not, reset them and go back to step 1.
21. Remove blower access panel and depress door switch. Use a piece of tape to hold switch closed.
22. Is 115-vac across L1 and L2? 24 23
23. Turn power off. Check continuity of power leads and door switch. If necessary repair power leads and/or replace door switch.
24. Is 24-vac across SEC-1 and SEC-2? 25 26
25. Replace the variable speed furnace control. 18
2 19
5 7
6
8
9 10
INDEX
INDEX
5 16
17 18
INDEX
21
22
18
- 10 -
STEP ACTION YES NO GO TO
26. Is 115-vac across the transformer leads? 27 25
27. Replace the transformer. 18
28. Is 24-vac across W/W1 and on the variable speed furnace control?
You will not be able to check for voltage across W/W1 and C connected to a User Interface at the ABCD connector. Go to step 29.
29. You have a defective thermostat, or a break in wiring between thermostat and furnace. Fix problem.
30. Disconnect all thermostat leads from the thermostat terminal block and jumper R to W/W1.
Does the furnace respond to the call for heat?
31. You have an incompatible thermostat. Do any of the following:
1. Wire the thermostat C terminal to C
2. Isolate the W/W1 input with a relay.
3. Install ballast resistor across W/W1 and C
4. Replace the thermostat with a compatible model.
OM-24V.
OM-24V.
OM-24V if the furnace is
30 29
18
31 25
18
RAPID FLASHING AMBER LED - Indicates line voltage polarity is reversed, furnace is not grounded, or the transformers are out of phase in twinned units.
STEP ACTION YES NO GO TO
1. Is this furnace twinned with another furnace? 7 2
2. Remove blower access panel and depress door switch. Use a piece of tape to hold switch closed.
3. Is 115-vac across L2 and chassis ground? 4 20
4. Line voltage polarity is reversed. Fix problem. 5
5. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. INDEX
6. Replace the variable speed furnace control. 5
7. Remove blower access panels and depress door switch in each unit. Use tape to hold switches closed.
8. Is the AMBER LED status light blinking rapidly in only one of the twinned units? 9 16
9. Are the fuses, breakers, or manual disconnects to the problem unit correctly set? 11 10
10. Fix problem. 5
11. Are the Auxiliary Limit switches properly set? 12 10
12. Do you have 115-vac across L1 and L2 in the problem unit? 13 15
13. Do you have 24-vac across SEC-1 and SEC-2 in the problem unit? 6 14
14. Replace the transformer. 5
15. Turn power off to both units. Check continuity of power leads and door switch in the problem unit. If necessary repair power leads and/or replace door switch in the problem unit.
16. Check the furnace circuit breaker location in the service panel.
On single-phase (residential) systems, each furnace circuit breaker should be located directly across from each other in service panel, or each furnace circuit breaker should be located on the same side of service panel, but must skip 1 space to be connected to the same leg of the 1­phase power supply.
On 3-phase (commercial) systems, each furnace circuit breaker should be located directly across from each other in service panel, or each furnace circuit breaker should be located on the same side of service panel, but must skip 2 spaces to be connected to the same leg of the 3­phase power supply.
17. Check the 115-vac power lead connections at the variable speed furnace control of each furnace. The BLACK lead goes to L1 and the WHITE lead goes to L2.
18. Check the 115-vac transformer lead connections at the variable speed furnace control of each furnace. The BLACK lead goes to L1 and the WHITE lead goes to L2.
19. If the circuit breaker location and the 115-vac wiring is correct reverse the transformer secondary lead connections SEC-1 and SEC-2 in the MAIN furnace.
20. Is the furnace properly grounded back to the service panel? 6 10
3
8
5
17
18
19
5
- 11 -
IMPROPER COOLING AIR FLOW - Generally, this indicates the Y/Y2 thermostat lead is not properly connected. If User Interface is connected to ABCD connector then the wrong size outdoor unit could be configured in the User Interface.
STEP ACTION YES NO GO TO
1. Remove blower access panel and depress door switch. Use a piece of tape to hold switch closed.
2. Set thermostat to call for cooling. If thermostat does not have G connection jumper across thermostat terminals R and G.
3. Make sure thermostat fan control is in the AUTO position if equipped. 4
4. Do you have 24-vac across Y/Y2 and COM-24V on the variable speed furnace control? 8 5
5. You have a defective thermostat, or a break in the wiring between the thermostat and the furnace, or the Y/Y2 thermostat terminal is not wired to the thermostat.
6. Fix the problem. 7
7. Go to page number indicated in Index for CLEANUP AND START-UP INSTRUCTIONS. INDEX
8. Are the air conditioning airflow select switches A/C set to the proper airflow as required by the condensing unit? Typical airflow is based on 350 CFM/TON (See Table 2.)
9. Set the air conditioning airflow select switches A/C to the proper airflow as required by the condensing unit. (See Table 2.)
10. Disconnect the G thermostat lead or jumper if used. 11
11. Does the blower motor turn off in 5 seconds when the G thermostat lead is disconnected?
Note: When using a Thermidistat the blower may change airflow when the G thermostat lead is disconnected and a call to dehumidify is active.
12. Replace the variable speed furnace control. 7
13. Reconnect the G thermostat lead or jumper and observe operation of furnace in cooling mode for 10 minutes.
14. Does the furnace operate properly in cooling mode? 15 16
15. - Check outdoor unit for correct suction pressure and verify charge.
- Check filter(s) and ductwork for restrictions.
- Check furnace coil.
16. Does the AMBER LED abruptly shut off as the blower comes up to speed? 17 24
17. Do you have less than 17-vac between R and COM-24V on the variable speed furnace control? 18 24
18. Do you have less than 90-vac between L1 and L2 on the variable speed furnace control? 19 20
19. Make sure the wire gage between main fuse box and furnace complies with wire size specification in Installation, Start-Up, and Operating Instructions.
20. Disconnect the R thermostat lead. 21
21. Do you have less than 17-vac between R and COM-24V on the variable speed furnace control? 22 23
22. Replace transformer. 7
23. Check the thermostat wire gage between furnace and thermostat, and furnace and outdoor unit. It is recommended that AWG No. 18 color-coded copper thermostat wire be used for lengths up to 100 ft. For wire lengths over 100 ft, use AWG No. 16 wire.
24. Is Status Code 41 flashing? 25 26
25. Go to the page number indicated in the Index for Status Code 41. INDEX
26. - Check outdoor unit for correct suction pressure and verify charge.
- Check furnace coil.
27. Is a User Interface connected to the ABCD connector? 28 2
28. The wrong size outdoor unit may have been selected in the User Interface. You will need to set the proper size of the outdoor unit in the User Interface. If set properly then the User Interface may be reducing the airflow for dehumidification.
27
3
6
10 9
7
12 13
14
INDEX
6
6
7
7
- 12 -
Table 2 – Cooling Tonnage vs. Airflow (CFM)
AIR CONDITIONING TONS
(12,000 BTU/HR)
1-1/2
2
2-1/2
3
3-1/2
4 5 6
AIR CONDITIONING (A/C) OR CONTINUOUS-FAN (CF)
BASED ON 350 CFM/TON (SETUP SWITCH SW1-5 OFF)
MODEL
SIZE
060, 3T-080
5T-080, 100
120
DEF.
DEF.
DEF.
AIRFLOW
(CFM)
060, & 3T-080
MODEL
5T-080 & 100
MODEL
120 MODEL
525 X 700 X X X
875 X X X 1050 X X X 1225 X X X 1400 X X 1750 X X 2100 X
AIRFLOW SELECTION CHART
SETUP SWITCH SW3 POSITIONS
525
700
875
1050
1225
1225
1750
1750
1
1
1225
1750
2100
2
700
875 1050
2
700 8752 1050
1225
1225
1
1400
1400
BASED ON 400 CFM/TON (SETUP SWITCH SW1-5 ON)
MODEL
SIZE
060, 3T-080
5T-080, 100
120
1. DEFAULT A/C AIRFLOW WHEN A/C SWITCHES ARE IN OFF POSITION
2. DEFAULT CONT. FAN AIRFLOW WHEN CF SWITCHES ARE IN OFF POSITION
3. SWITCH POSITIONS ARE ALSO SHOWN ON FURNACE WIRING DIAGRAM
DEF.
DEF.
DEF.
SETUP SWITCH SW3 POSITIONS
600
800
2
800
2
800 10002 1200
1000
1000 1200
1200
1400
1400
1
1400
1600
1600
1400
2000
2000
1
1
1400
2000
2100
MEDIUM AND/OR HIGH HEAT TEMPERATURE RISE TOO LOW - Generally, this indicates the HI solenoid in gas valve GV has failed, the throttling valve TV has failed, the furnace is extremely underfired, or the gas valve GV is miswired.
STEP ACTION YES NO GO TO
1. Remove the blower access panel. Disconnect User Interface ABCD connector (if used) or the R thermostat lead (if used) from the furnace control board. If setup switches SW1-2 or SW4-2 are ON then set them to OFF.
2. Depress the door switch. Use piece of tape to hold it closed. 19
3. Jumper R and W/W1 thermostat terminals. 4
4. When the furnace is running in medium heat, clock the medium heat gas rate. On propane installations check the manifold pressure.
5. Jumper R and W2 thermostat terminals. When the furnace is running in high heat, clock the high heat gas rate. On propane installations check the manifold pressure.
6. Is the high heat rate approximately the same as the medium heat rate? 7 13
7. Do you have 24-vac across terminals HI and C on gas valve GV during high heat? 12 8
8. Are the BLUE and GREEN/YELLOW wires on the gas valve GV reversed? The BLUE wire should be connected to the M terminal and the GREEN/YELLOW wire should be connected to the C terminal.
9. Is 24-vac across BROWN wire on the high heat pressure switch HPS and COM-24V on variable speed furnace control?
10. You have an open wire or bad terminal on the BROWN wire from the high heat pressure switch HPS to the gas valve GV. Repair it or replace the harness.
2
5
6
18 9
10 35
11
- 13 -
STEP ACTION YES NO GO TO
11. Go to the page number indicated in Index for the CLEANUP AND STARTUP INSTRUCTIONS.
12. Replace the gas valve GV. 11
13. Is the high heat rate within 2% of that specified on the rating plate? 15 14
14. Ensure the gas inlet pressure and burner orifice are correct. Then adjust the gas valve to the proper rate. If it cannot be adjusted to the proper rate, replace the gas valve GV.
15. Is outdoor condensing unit operating during heating cycle? 18 16
16. Check temperature rise and external static pressure with blower access panel in place. Temperature rise should be mid range or higher than midpoint of range stated on furnace rating plate. External static pressure must not exceed .7 in.w.c. If return temperature is below 60 deg. F condensation may form on heat exchangers. If left uncorrected failure will result.
17. Check return air ducts in unheated spaces for leaks. 11
18. Fix problem. 11
19. Is the temperature rise problem in high heat only?
If the temperature rise problem occurs in medium and high heat go to step 20.
20. Put setup switch SW4-2 into the ON position. 3
21. Jumper R and W/W1 thermostat terminals. 22
22. Once the blower motor turns ON and the furnace is running in low heat, clock the low heat gas rate. You have 15 minutes on this first call for heat before the units switches to high heat. On propane installations check the manifold pressure.
23. Remove jumper across R and W/W1 thermostat terminals and wait for blower motor to turn OFF.
24. Put setup switch SW4-2 into the ON position. 25
25. Jumper R and W/W1 thermostat terminals. 26
26. When the furnace is running in medium heat, clock the medium heat gas rate. On propane installations check the manifold pressure.
27. Is the medium heat rate approximately the same as the low heat rate? 28 31
28. Do you have 24-vac across both terminals on throttling valve TV during medium heat? 30 29
29. You have an open wire or bad terminal on the VIOLET wire from the medium heat pressure switch MPS to the throttling valve TV or the GREEN/YELLOW from gas valve GV to throttling valve TV. Repair it or replace the harness.
30. Replace the valve train assembly. The valve train assembly includes the gas valve GV and the throttling valve TV. The throttling valve TV is not a serviceable part by itself.
31. Is the medium heat rate within 2% of that specified on the rating plate? 33 32
32. Ensure the gas inlet pressure and burner orifice are correct. Then adjust medium heat on the gas valve to the proper rate. If medium heat cannot be adjusted to the proper rate, replace the gas valve GV.
33. Is outdoor condensing unit operating during heating cycle? 18 34
34. Check medium heat temperature rise and external static pressure with blower access panel in place. Temperature rise should be mid range or higher than midpoint of range stated on furnace rating plate. External static pressure in medium heat should be less then .25 in.w.c. If return temperature is below 60 deg. F condensation may form on heat exchangers. If left uncorrected failure will result.
35. Replace the pressure switch assembly. 11
INDEX
11
17
20 21
23
24
27
11
11
11
- 14 -
Status Code 11
NO PREVIOUS CODE - Stored status codes are erased after 72 hours or can be cleared by jumpering R, W/W1, and Y/Y2 thermostat leads while setup switch SW1-1 is ON. Run system through a heating or cooling cycle to check system.
This usually indicates one of the following:
- The status history has been cleared and setup switch SW1-1 is in the ON position.
- Component test was successfully completed and setup switch SW1-6 is in the ON position.
STEP ACTION YES NO GO TO
1. Remove the blower access panel, depress the door switch. Use piece of tape to hold it closed. 2
2. Is setup switch SW1-1 in the ON position. 3 5
3. Put setup switch SW1-1 in the OFF position. 4
4. Go to the page number indicated in Index for the CLEANUP AND STARTUP INSTRUCTIONS.
5. Is setup switch SW1-6 in the ON position. 6 7
6. Put setup switch SW1-6 in the OFF position. 4
7. Jiggle setup switches SW1-1 and SW1-6 back and forth. If status code 11 continues to flash replace the variable speed furnace control
INDEX
4
Status Code 12
BLOWER ON AFTER POWER UP - Blower will run for 90 seconds when furnace power is interrupted and later restored during a call for heat (R-W/W1 closed) or if the call for heat is interrupted (R-W/W1 opens) during the blower on-delay period. If this status code repeats every couple of minutes it is probably caused by a direct short in the pressure switch circuits, gas valve GV, throttling valve TV, wiring to gas valve GV, wiring to throttling valve TV, or humidifier coil.
STEP ACTION YES NO GO TO
1. Remove the blower access panel and disconnect User Interface ABCD connector (if used) or the R thermostat lead (if used) from the furnace control board.
2. Depress the door switch. Use piece of tape to hold it closed. 3
3. Jumper R and W/W1 thermostat terminals. 4
4. Does the furnace keep repeating the following cycle?
Induced draft motor IDM runs, induced draft motor IDM stops, blower motor BLWM runs for 90 seconds while AMBER LED status light flashes status code 12.
5. Do you have less than 17-vac across R and COM-24V on the variable speed furnace control? 6 14
6. Do you have less than 90-vac across L1 and L2 on the variable speed furnace control? 7 10
7. Make sure wire gage between main fuse box and furnace complies with wire size specification in Installation, Start-Up, and Operating Instructions.
8. Fix problem. 9
9. Go to the page number indicated in Index for the CLEANUP AND STARTUP INSTRUCTIONS.
10. Disconnect the R thermostat lead. 11
11. Do you have less than 19-vac across R and COM-24V on the variable speed furnace control? 12 13
12. Replace transformer. 9
13. The thermostat and/or thermostat wires are loading down the transformer. Replace the thermostat or repair thermostat wires.
14. Does the hot surface igniter HSI come on during the cycle? 15 27
15. Disconnect the humidifier lead from HUM terminal on variable speed furnace control. 16
16. Does the furnace still alternately cycle induced draft motor IDM and blower motor BLWM as described in Step 4.
17. The humidifier may not be wired into the system properly or there is a direct short in wiring to humidifier solenoid coil, diode bridge(if used), or humidifier solenoid coil.
18. There is a short in the gas valve GV or wiring to gas valve GV. Refer to Appendix E to check gas valve GV.
19. There is a direct short in the ORANGE wire from the low heat pressure switch LPS. 8
20. While the unit is operating in low heat jumper R and W2 thermostat terminals. 21
2
5 20
8
INDEX
9
18 17
8
8
- 15 -
Loading...
+ 33 hidden pages