Bryant 355CAV User Manual

PLUS 95S -- MODEL 355CAV DIRECT--VENT 4--W AY MULTIPOISE CONDENSING GAS FURNACE WITH PERFECT SENSET PERFECT HUMIDITYT SERIES A
Installation Instructions
NOTE: Read the entire instruction manual before starting the
installation. This furnace can be vented as a direct vent (2--pipe) or as an optional ventilated combustion air application.
Furnaces installed in Canada must use Vent Systems that are certified to the Standard for Type BH Gas Venting Systems, ULC-- S636. ULC--S636 certified plastic vent system material or the components of ULC --S636 certified vent systems must not be interchanged with other vent systems or unlisted pipe/fittings. Vent components supplied with the furnace and components in factory authorized vent kits may be used with ULC--S636 certified vent systems. The ULC --S636 certified plastic components, and specified primers and glues of the certified system must be from a single--system manufacturer and not mixed with other system manufacturer’s vent system parts. The first 3 ft. (.91 M) of the venting system must be readily accessible for inspection. Some Provinces may require the combustion air system to be ULC--S636 certified.
NOTE: Please retain these instructions with the furnace after installation for future reference.
TABLE OF CONTENTS
PAGE
IMPORTANT INFORMATION 2........................
SAFETY CONSIDERATIONS 3........................
CODES AND STANDARDS 6..........................
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS 7..
INTRODUCTION 7..................................
APPLICATIONS 7...................................
Upflow 7........................................
Downflow 10.....................................
Horizontal Left 11..................................
Horizontal Right 13................................
LOCATION 14......................................
INSTALLATION 16..................................
Air Ducts 19.......................................
Air for Combustion and Ve ntilation 26..................
Combustion Air Pipe 32..............................
Vent Pipe 34......................................
Vent Termination 37................................
Condensate Drain 42................................
START--UP, ADJUSTMENTS, AND SAFETY CHECK 43...
CHECKLIST 59.....................................
As an ENERGY STAR® Partne r, Bryant Heating & Cooling has determined that this product meets the ENERGY STAR® guidelines for energy efficiency.
AIRFLOW
FURNACE RELIABILITY HAZARD
Failure to follow this caution may result in unit damage.
Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure. This furnace can be vented as either a direct vent (2--pipe) furnace or as an optional ventilated combustion air application. A direct vent system shall be installed in accordance with the direct vent (2-- pipe) procedures in the Combustion Air and Vent Pipe Systems section within this instruction. For optional ventilated combustion air applications, refer to the ventilated combustion air option procedures in the same section.
Application of this furnace should be indoors with special attention given to vent sizing and material, gas input rate, air temperature rise, unit leveling, and unit sizing.
ama
AIRFLOW
UPFLOW
HORIZONTAL
LEFT
Fig. 1 -- Furnace Orientation
!
DOWNFLOW
AIRFLOW
CAUTION
ISO 9001:2000
REGISTERED
HORIZONTAL
CERTIFIED
RIGHT
AIRFLOW
A93041
Required Notice for Massachusetts Installations
IMPORTANT
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA --54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements:
(a.)For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in
whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an alarm and battery back--up is installed on the floor level where the gas equipment is to be installed. In addition, the installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard wired
carbon monoxide detector with alarm and battery back-- up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner shall
have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty (30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment. The sign shall read, in print size no less than one--half (1/2) inch in size, ”GAS VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
5. EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
(1.) The equipment listed in Chapter 10 entitled ”Equipment Not Required T oBe Vented” in the most current edition of NFPA
54 as adopted by the Board; and
(2.) Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from the
dwelling, building or structure used in whole or in part for residential purposes.
(c.) MANUFACTURER REQUIREMENTS -- GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design or venting system components with the equipment, the instructions provided by the manufacturer for installation of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
(d.)MANUFACTURER REQUIREMENTS -- GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When the
manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a parts list and detailed installation instructions.
(e.)A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled equipment,
all venting instructions, all parts lists for venting instructions, and/or all venting design instructions shall remain with the appliance or equipment at the completion of the installation.
For questions regarding these requirements, please contact the Commonwealth of Massachusetts Board of State Examiners of Plumbers and
Gas Fitters, 239 Causeway Street, Boston, MA 02114. 617-- 727--9952.
2
SAFETY CONSIDERATIONS
!
CAUTION
FURNACE RELIABILITY HAZARD
Improper installation or misapplication of furnace may require excessive servicing or cause premature component failure.
Application of this furnace should be indoors with special attention given to vent sizing and material combustion air requirements, gas input rate, air temperature rise, unit leveling, and unit sizing.
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury, death, or property damage.
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may cause personal injury or property damage. Consult a qualified installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified installer or agency must use only factory--authorized and listed kits or accessories when modifying this product.
Installing and servicing heating equipment can be hazardous due to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions such as cleaning and replacing air filters. All other operations must be performed by trained service personnel. When working on heating equipment, observe precautions in literature, on tags, and on labels attached to or shipped with unit and other safety precautions that may apply.
These instructions cover the minimum requirements and conform to existing national standards and safety codes. In some instances, these instructions exceed certain local codes and ordinances, especially those that may not have kept up with changing residential construction practices. We require these instructions as a minimum for a safe installation.
Wear safety glasses and work gloves. Have a fire extinguisher available during start--up and adjustment procedures and service calls.
Recognize safety information. This is the safety--alert symbol
. When you see this symbol on the furnace and in instructions or manuals, be alert to the potential for personal injury.
Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety--alert symbol. DANGER identifies the most serious hazards which will result in severe personal injury or death. WARNING signifies a hazard which could result in personal injury or death. CAUTION is used to identify unsafe practices which may result in minor personal injury or product and property damage. NOTE is used to
highlight suggestions which will result in enhanced installation, reliability, or operation.
!
CAUTION
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care and wear appropriate protective clothing and gloves when handling parts.
The 355CAV Condensing Gas--Fired Furnaces are CSA (formerly AGA and CGA) design--certified for natural and propane gases (see furnace rating plate) and for installation in alcoves, attics, basements, closets, utility rooms, crawlspaces, and garages. The furnace is factory--shipped for use with natural gas. A CSA listed gas conversion kit is required to convert furnace for use with propane gas.
See Fig. 3 for required clearances to combustibles.
Maintain a 1--in. (25.4 mm) clearance from combustible materials to supply air ductwork for a distance of 36 inches horizontally from the furnace. See NFPA 90B or local code for further requirements.
These furnaces SHALL NOT be installed directly on carpeting, tile, or any other combustible material other than wood flooring. These furnaces are suitable for installation in a structure built on site or a manufactured building completed at final site. The design of this furnace line is NOT CSA design--certified for installation in recreation vehicles, manufactured (mobile) homes or outdoors.
This furnace is designed for continuous return--air minimum temperature of 60_F db or intermittent operation down to 55_F db such as when used with a night setback thermostat. Return--air temperature must not exceed 80_F db. Failure to follow these return air limits may affect reliability of heat exchangers, motors and controls. (See Fig. 4.)
These furnaces are shipped with the drain and pressure tubes connected for UPFLOW applications. Minor modifications are required when used in DOWNFLOW, HORIZONTAL RIGHT, or HORIZONTAL LEFT (supply--air discharge direction) applications as shown in Fig. 1. See details in Applications section.
Install this furnace only in a location and position as specified in LOCATION and INSTALLATION sections of these instructions.
Combustion products must be discharged outdoors. Connect this furnace to an approved vent system only, as specified in the Combustion Air and Vent piping sections of these instructions.
Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for detection of leaks to check all connections as specified in the GAS PIPING section of these instructions.
Always install the furnace to operate within the furnace’s intended rise range with a duct system which has an external static pressure within the allowable range as specified in the SET TEMPERATURE RISE section of these instructions.
When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by ducts sealed to the furnace casing and terminating outside the space containing the furnace.
355CAV
3
14 1⁄2"
TYP
1
26 15⁄16"
26 1⁄4"
1
24
⁄2"
5
⁄16"
22
2-IN. COMBUSTION­AIR CONN
1
2-IN. DIA
GAS CONN
2-IN. VENT CONN
2-IN. DIA THERMOSTAT
ENTRY
22 11⁄16"
SIDE INLET
CONDENSATE DRAIN TRAP LOCATION (DOWNFLOW & HORIZONTAL LEFT)
7
8-IN. DIA
POWER CONN
7
8-IN. DIA
ACCESSORY POWER ENTRY
CONDENSATE DRAIN TRAP LOCATION (ALTERNATE UPFLOW)
17 5⁄16"
9 7⁄16"
TYP
1
⁄2"
28
AIRFLOW
13
/16"
1
⁄4"
33
TYP
5
⁄8"
32
TYP
13
⁄16"
30
11
⁄16"
29
TYP
5
⁄8"
27
9
⁄16"
27
TYP
1
⁄2"
24
A
D
OUTLET
13
/16"
CONDENSATE DRAIN
TRAP LOCATION
(DOWNFLOW &
HORIZONTAL RIGHT)
OR ALTERNATE
1
⁄2-IN. DIA GAS CONN
30 1⁄2"
18 1⁄4"
TYP
9
⁄16"
26 15⁄16"
26 1⁄4"
5
22
⁄16"
19"
OUTLET
2-IN. COMBUSTION­AIR CONN
1
2-IN. DIA
GAS CONN
7
8-IN. DIA
POWER CONN
1
2-IN. DIA
THERMOSTAT ENTRY
2-IN. VENT CONN
22 11⁄16"
SIDE INLET
13
⁄16"
5
⁄8"
5
⁄16"
7
⁄8"
39
1"
355CAV
11⁄4"
1"
23 1⁄4" TYP
SIDE INLET
26 15⁄16" TYP
CONDENSATE DRAIN LOCATION (UPFLOW)
NOTES: 1. Minimum return-air openings at furnace, based on metal duct. If flex duct is used,
see flex duct manufacturer’s recommendations for equivalent diameters.
2. Minimum return-air opening at furnace: a. For 800 CFM–16-in. round or 14 b. For 1200 CFM–20-in. round or 141/2 c. For 1600 CFM–22-in. round or 141/2 d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data
literature for specific use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
11
/16"
INLET
E
1
/2
x 12-in. rectangle.
x 191/2
-in. rectangle.
x 231/4
-in. rectangle.
11
/16"
CONDENSATE
DRAIN LOCATION
(UPFLOW)
DIMPLE LOCATORS
FOR HORIZONTAL
HANGING
22 1⁄4" TYP
24 3⁄16"
BOTTOM INLET
7
⁄16"
11
⁄16"
A05124
Dimensio ns (In. / mm)
UNIT SIZE A D E
042060 17--- 1/2 / 444.5 15--- 7/8 / 403.2 16 / 406.4
042080 21 / 533.4 19--- 3/8 / 492.1 19--- 1/2 / 495.3
060080 21 / 533.4 19--- 3/8 / 492.1 19--- 1/2 / 495.3
060100 21 / 533.4 19--- 3/8 / 492.1 19--- 1/2 / 495.3
060120 24--- 1/2 / 622.3 22--- 7/8 / 581.0 23 / 584.2
Fig. 2 -- Dimensional Drawing
A gas--fired furnace for installation in a residential garage must be installed as specified in the Hazardous Locations section of these instructions and Fig. 5.
The furnace may be used for construction heat provided that the furnace installation and operation complies with the first CAUTION in the LOCATION section of these instructions.
This gas furnace may be used for construction heat provided that:
S The furnace is permanently installed with all electrical
wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and ter­minated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
S The furnace is controlled by a thermostat. It may not be
“hot wired” to provide heat continuously to the struc­ture without thermostatic control.
S Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the en­trainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
S The temperature of the return air to the furnace is
maintained between 55_F(13_C) and 80_F(27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
S The air temperature rise is within the rated rise range on
the furnace rating plate, and the firing rate has been set to the nameplate value.
S The filters used to clean the circulating air during the
construction process must be either changed or thoroughly cleaned prior to occupancy.
S The furnace, ductwork and filters are cleaned as
necessary to remove drywall dust and construction
4
debris from all HVAC system components after construction is completed.
S After construction is complete, verify furnace operating
conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.
If this furnace is installed with a direct--vent (combustion air and flue) system, a factory accessory termination kit must be installed.
In a direct--vent system, all air for combustion is taken directly from the outside atmosphere and all flue products are discharged to the outside atmosphere. See furnace and factory accessory termination kit instructions for proper installation.
These furnaces are shipped with the following materials to assist in proper furnace installation. These materials are shipped in the main blower compartment.
This forced air furnace is equipped for use with natural gas at altitudes 0 - 10,000 ft (0 - 3,050m), except 140 size furnaces are only approved for altitudes 0 - 7,000 ft.
INSTALLATION
(0 - 2,135m). An accessory kit, supplied by the manufacturer, shall be used to convert to propane gas use or may be required for some natural gas applications. This furnace is for indoor installation in a building constructed on site. This furnace may be installed in a manufactured (mobile) home when stated on rating plate and using factory authorized kit.. This furnace may be installed on combustible flooring in alcove or closet at Minimum Inches Clearance To Combustible Construction as described below. This furnace requires a special venting system. Refer to the installation instructions for parts list and method of installation. This furnace is for use with schedule-40 PVC, PVC-DWV, CPVC, or ABS-DWV pipe, and must not be vented in common with other gas-fired appliances. Construction through which vent/air intake pipes may be installed is maximum 24 inches (600 mm), minimum 3/4 inches (19 mm) thickness (including roofing materials).
Cette fournaise à air pulsé est équipée pour utilisation avec gaz naturel et altitudes comprises entre 0 - 3,050m (0 - 10,000 pi),excepté queles fournaises de 140 taille sont pour altitudes comprises entre 0 - 2,135m (0 - 7,000pi). Utiliser une trousse de conversion, fournie par le fabricant, pour passer au gaz propane ou pour certaines installations au gaz naturel. Cette fournaise à air pulsé est pour installation à l´intérieur dans un bâtiment construit sur place. Cette fournaise à air pulse peut être installée dans une maison préfabriquée (maison mobile) si prescrit par la plaque signalétique et si l' on utilise une trousse specifiée par le fabricant. Cette fournaise peut être installée sur un plancher combustible dans un enfoncement ou un placard en observant les Dégagement Minimum En Pouces Avec
Éléments De Construction Combustibles.
Cette fournaise nécessite un système d´évacuation spécial. La méthode d´installation et la liste des pièces nécessaires figurent dans les instructions d´installation. Cette fournaise doit s´utiliser avec la tuyauterie des nomenclatures 40 PVC, PVC-DWV, CPVC, ou ABS-DWV et elle ne peut pas être ventilée conjointment avec d´autres appareils à gaz. Épaisseur de la construction au travers de laquelle il est possible de faire passer les tuyaux d'aération (admission/évacuation): 24 po (600 mm) maximum, 3/4 po (19mm) minimum (y compris la toiture).
For upflow and downflow applications, furnace must be installed level, or pitched within 1/2" of level. For a horizontal application, the furnace must be pitched minimum 1/4" to maximum of 1/2" forward for proper drainage. See Installation Manual for IMPORTANT unit support details on horizontal applications.
Pour des applications de flux ascendant et descendant, la fournaise doit être installée de niveau ou inclinée à pas plus de 1/2" du niveau. Pour une application horizontale, la fournaise doit être inclinée entre minimum 1/4" et maximum 1/2" du niveau pour le drainage approprié. En cas d´installation en position horizontale, consulter les renseignements IMPORTANTS sur le support dans le manuel d´installation.
MINIMUM INCHES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
ALL POSITIONS:
Minimum front clearance for service 24 inches (610mm).
*
DOWNFLOW POSITIONS:
For installation on combustible floors only when installed on special base No. KGASB0201ALL,
Coil Assembly, Part No. CD5 or CK5, or Coil Casing, Part No. KCAKC.
HORIZONTAL POSITIONS:
Line contact is permissible only between lines formed by intersections of top and two sides of furnace jacket, and building joists, studs, or framing.
§
Clearance shown is for air inlet and air outlet ends.
Ø
120 and 140 size furnaces require 1 inch bottom clearance to combustible materials.
DÉGAGEMENT MINIMUM EN POUCES AVEC ÉLÉMENTS DE
CONSTRUCTION COMBUSTIBLES
POUR TOUS LES POSITIONS:
Dégagement avant minimum de 610mm (24 po) pour l'entretien.
*
POUR LA POSITION COURANT DESCENDANT:
Pour l´installation sur le plancher combustible seulement quand on utilise la base spéciale,
pièce nº KGASB0201ALL, l serpentin, pièce nº KCAKC.
POUR LA POSITION HORIZONTALE:
Le contact n deuxcôtés de la chemise de la fournaise, et des solives, des montants ou de la charpente du bátiment.
§
La distance indiquée concerne l sortie d
Ø
Pour les fournaises de 120 et 140 taille, 1 po (25mm) dégagement des matériaux combusitbles est requis au-dessous.
´
est permis qúentre les lignes formées par les intersections du dessus et des
´
air.
´
ensemble serpentin, pièce nº CD5 ou CK5, ou le carter de
´
extrémité du tuyau d´arrivée d´air et l´extrémité du tuyau de
LEVEL (0")
1/2" MAX
UPFLOW OR DOWNFLOW
TO
FRONT
MIN 1/4" TO 1/2" MAX
FRONT
HORIZONTAL
This furnace is approved for UPFLOW, DOWNFLOW and HORIZONTAL installations.
Cette fournaise est approuvée pour l´installation HORIZONTALE et la circulation d´air VERS LE HAUT et VERS LE BAS.
0" †
1"
Les fléches de dégagement
ne change pas avec
´
orientation de la
l
générateur d´air chaud.
TOP/PLENUM
DESSUS/CHAMBRE D´AI R
C
A
N
R
U
N
F
R
U
FO
R
F
A
F
R
A
V
A
BOTTOM
DESSOUS
Ø
d´évent avec combustibles.
I
S
O
E
C
E
S
I
A
T
N
O
T
N
A
V
S
E
L
È
N
T
O
N
T
N
T
3"
Vent clearance to combustibles 0".
0 (po) Dégagement
D
T
R
EV. B (LIT TOP
E
S
E
R
V
I
E
T
I
Clearance arrows do not change with furnace orientation.
0"
B
A
A
C
R
K
R
I
E
R
E
E
D
I
S
E
T
O
C
0"
§
Clearance in inches Dégagement (po).
328068-201 R
S
355CAV
§
0"
C
E
E
*
N
24
MIN
)
Fig. 3 -- Clearances to Combustibles
5
A04116
Installer Packet Includes:
Installation, Start--- up, and Operating Instructions
Service and Maintenance Instructions
User’s Information Manual
Warranty Certificate
Loose Parts Bag includes: Quantity
Collector Box or Condensate trap extension tube 1
Inducer housing drain tube 1
1/2--- in CPVC street elbow 2
Drain tube coupling 1
Drain tube coupling grommet 1
Gas line grommet 1
Vent pipe grommet 1
Combustion --- air pipe grommet 1
Gas line entry hole filler plug 1
Power entry hole filler plug 2
Condensate trap hole filler plug 3
355CAV
Vent and combustion--- air intake hole filler plug 2
Combustion ---air pipe perforated disk assembly 1
Fig. 4 -- Return-- Air Temperature
18-IN. MINIMUM
TO BURNERS
Fig. 5 -- Installation in a Garage
The furnace shall be installed so that the electrical components are protected from water.
For accessory installation details, refer to applicable installation literature.
80 / 27 C
60
/ 16 C
A06745
A93044
CODES AND STANDARDS
Follow all national and local codes and standards in addition to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating, plumbing, and other codes. In absence of local codes, the installation must comply with the national codes listed below and all authorities having jurisdiction in Canada.
In the United States and Canada, follow all codes and standards for the following:
Safety
S US: National Fuel Gas Code (NFGC) NFPA
54--2006/ANSI Z223.1-- 2006 and the Installation Standards, Warm Air Heating and Air Conditioning Systems ANSI/NFPA 90B
S CANADA: National Standard of Canada, Natural Gas
and Propane Installation Code (CAN/CSA--B149.1--05) CSA B149.1--05
General
Combustion and Ventilation Air
Duct
Acoustical Lining and Fibrous Glass
Gas Piping and Gas Pipe Pressure T
In the state of Massachusetts:
6
Installation
S US: NFGC and the NFPA 90B. For copies, contact the
National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas Association, 400 N. Capitol, N.W., Washington DC 20001.
S A manufactured (Mobile) home installation must
conform with the Manufactured Home Construction and Safety Standard, Title 24 CFR, Part 3280, or when
this standard is not applicable, the Standard for
Manufactured Home Instllation (Manufactured Home Suites, Communities, and Set--Ups), ANSI/NCS A225.1, and/or CAN/CSA--z240, MH Series Mobile Homes.
S CANADA: CAN/CSA --B149.1--05. For a copy,
contact Standard Sales, CSA International, 178 Rexdale Boulevard, Etobicoke (Toronto), Ontario, M9W 1R3, Canada.
S US: Section 9.3 of the NFGC, Air for Combustion and
Ventilation.
S CANADA: Part 8 of the CAN/CSA-- B149.1 --05,
Venting Systems and Air Supply for Appliances.
Systems
S US and CANADA: Air Conditioning Contractors
Association (ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers (ASHRAE) 2005 Fundamentals Handbook Chapter 35.
Duct
S US and CANADA: current edition of SMACNA,
NFPA 90B as tested by UL Standard 181 for Class I Rigid Air Ducts.
esting
S US: NFGC; chapters 5, 6, 7, and 8 and national
plumbing codes.
S CANADA: CAN/CSA --B149.1--05 Parts 4, 5, 6, and 9.
S This product must be installed by a licensed plumber or
gas fitter.
S When flexible connectors are used, the maximum
length shall not exceed 36 inches.
S When lever type gas shutoffs are used they shall be
T--handle type.
S The use of copper tubing for gas piping is not approved
by the state of Massachusetts.
Electrical
Connections
S US: National Electrical Code (NEC) ANSI/NFPA
70--2005.
S CANADA: Canadian Electrical Code CSA C22.1.
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS
!
CAUTION
drain and pressure tubes are connected as shown in Fig. 7. See appropriate application instructions for these procedures.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit components.
Electrostatic discharge can affect electronic components. Take precautions during furnace installation and servicing to protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools which are held during the procedure. These precautions will help to avoid exposing the control to electrostatic discharge by putting the furnace, the control, and the person at the same electrostatic potential.
3. Disconnect all power to the furnace. Multiple disconnects may b e required. DO NOT TOUCH THE CONTROL OR ANY WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE TO GROUND.
4. Firmly touch a clean, unpainted, metal surface of the furnace chassis which is close to the control. Tools held in a person’s hand during grounding will be satisfactorily discharged.
5. After touching the chassis, you may proceed to service the control or connecting wires as long as you do nothing that recharges your body with static electricity (for example; DO NOT move or shuffle your feet, DO NOT touch ungrounded objects, etc.).
6. If you touch ungrounded objects (recharge your body with static electricity), firmly touch furnace again before touching control or wires.
7. Use this procedure for installed and uninstalled (ungrounded) furnaces.
8. Before removing a new control from its container, discharge your body’s electrostatic charge to ground to protect the control from damage. If the control is to be installed in a furnace, follow items 1 through 5 before bringing the control or yourself into contact with the furnace. Put all used AND new controls into containers before touching ungrounded objects.
9. An ESD service kit (available from commercial sources) mayalsobeusedtopreventESDdamage.
INTRODUCTION
The model 355CAV Direct Vent, Upflow, Gas--Fired, Category IV, condensing furnace is available in model sizes ranging in input capacities of 60,000 to 120,000 Btuh.
APPLICATIONS
General
Some assembly and modifications are required for furnaces installed in any of the four applications shown in Fig. 1. All
NOTE: In Canada, installations shall be in accordance with current CAN/CSA--B149.1--05 and/or local codes.
UPFLOW APPLICATION
An upflow furnace application is where furnace blower is located below combustion and controls section of furnace, and conditioned air is discharged upwards.
Condensate Trap (Factory-- Shipped
The condensate trap is factory installed in the blower shelf and factory connected for UPFLOW applications. A factory--supplied tube is used to extend the condensate trap drain connection to the desired furnace side for field drain attachment. See Condensate Trap Tubing section for drain tube extension details. (See Fig. 6.)
Condensate Trap Tubing (Factory--Shipped
NOTE: See Fig. 7 or tube routing label on main furnace door to
confirm location of these tubes.
1. Collector Box Drain, Inducer Housing Drain, Relief Port, and Pressure Switch Tubes. These tubes should be factory attached to condensate trap andpressureswitchreadyforuseinUPFLOW applications. These tubes can be identified by their connection location and also by a color label on each tube. These tubes are identifed as follows: collector box drain tube (blue label), inducer housing drain tube (violet label or molded), relief port tube (green label), and pressure switch tube (pink label).
2. Condensate Trap Drain Tube The condensate trap drain connection must be extended for field attachment by doing the following:
f. Determine location of field drain connection. (See Fig.
2or7.)
NOTE: If internal filter or side filter/media cabinet is used, drain tube should be located to opposite side of casing from return duct attachment to assist in filter removal.
g. Remove and discard casing drain hole plug button from
desired side.
h. Install drain tube coupling grommet (factory--suppliedin
loose parts bag) in selected casing hole.
i. Slide drain tube coupling (factory--supplied in loose parts
bag) through grommet so long end of coupling faces blower.
j. Cement 2 factory--supplied 1/2--in. (12.7mm) street
CPVC elbows to rigid drain tube connection on condensate trap. (See Fig. 7.) These elbows must be cementedtogether and cemented to condensate trapdrain connection.
Orientation)
Orientation)
355CAV
7
BLOWER SHELF
CONDENSATE TRAP (INSIDE)
ALTERNATE DRAIN TUBE LOCATION
CONDENSATE TRAP
DRAIN TUBE LOCATION
UPFLOW APPLICATIONS
FURNACE DOOR
FIELD
DRAIN
CONN
CONDENSATE TRAP
FURNACE
1
26
4
(667mm) (38mm)
SIDE VIEW FRONT VIEW END VIEW FRONT VIEW
DOWNFLOW AND ALTERNATE
EXTERNAL UPFLOW APPLICATIONS
SIDE
1
1
FURNACE DOOR
7
(124mm)
8
4
2
FIELD
DRAIN
CONN
4
3
(146mm) (146mm)
4
5
1
26
4
(667mm) (19mm)
HORIZONTAL
APPLICATIONS
FURNACE SIDE
4
3
3
4
5
4
355CAV
(19mm)
SLOT FOR SCREW
HORIZONTAL
APPLICATION
(OPTIONAL)
1
1
2
3
4
WIRE TIE GUIDES (WHEN USED)
(88mm)
3
1
4
(181mm)
(44mm)
(3mm)
FRONT VIEW SIDE VIEW
NOTE: Failure to use CPVC elbows may allow drain to kink, preventing draining.
k. Connect larger diameter drain tube and clamp
(factory--supplied in loose parts bag) to condensate trap and clamp securely.
l. Route tube to coupling and cut to appropriate length.
m. Attach tube to coupling and clamp securely.
Condensate Trap (Alternate Upflow
Orientation)
An alternate location for the condensate trap is the left--hand side of casing. (See Fig. 2 and 8.)
NOTE: If the alternate left--hand side of casing location is used, the factory--connected drain and relief port tubes must be disconnected and modified for attachment. See Condensate Trap Tubing (Alternate Upflow Orientation) section for tubing attachment.
To relocate condensate trap to the left--hand side, perform the following:
1. Remove three tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotating trap.
3. Install casing hole filler cap (factory--supplied in loose parts bag) into blower shelf hole where trap was removed.
1
8
7
7
8
1
4
2
(57mm)
Fig. 6 -- Condensate Trap
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
4. Install condensate trap into left--hand casing hole by
5. Fill unused condensate trap casing holes with plastic filler
Condensate Trap Tubing (Alternate Upflow
NOTE: See Fig. 8 or tube routing label on main furnace door to
confirm location of these tubes.
1/4 OD COLLECTOR BOX TO TRAP RELIEF PORT
1/2 OD INDUCER HOUSING DRAIN CONNECTION
5/8 OD COLLECTOR BOX DRAIN CONNECTION
SCREW HOLE FOR UPFLOW OR DOWN­FLOW APPLICATIONS (OPTIONAL)
1/2 IN. PVC OR CPVC
!
WARNING
inserting tube connection stubs through casing hole and rotating until tabs snap into locking position.
caps (factory--supplied in loose parts bag).
Orientation)
A07459
8
PLUG
T
COLLECTOR BOX
DRAIN TUBE (BLUE &
WHITE STRIPED)
CAP
COLLECTOR BOX
TUBE (PINK)
INDUCER HOUSING
(MOLDED) DRAIN
UBE (BEHIND
COLLECTOR BOX
DRAIN TUBE)
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (GREEN
ROUTES BEHIND
INDUCER)
CONDENSATE
FIELD-INSTALLED
FACTORY-SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
FIELD-INSTALLED
FACTORY-
SUPPLIED
DRAIN TUBE
FIELD-INSTALLED FACTORY­½ - IN. CPVC STREET
LEFT DRAIN OPTION
SUPPLIED
ELBOWS (2) FOR
FIELD- INSTALLED
FACTORY-
SUPPLIED
DRAIN TUBE
COUPLING (LEFT
DRAIN OPTION)
A07274
Fig. 7 -- Factory--Shipped Trap Location
(Shown with Blower Access Panel Removed)
1. Collector Box Drain Tube Connect collector box drain tube (blue label) to condensate trap.
NOTE: On 17-- 1/2 --in. (444.5mm) wide furnaces ONLY, cut tube between corrugated sections to prevent kinks.
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer housing
draintube which was previously connectedto condensate trap.
b. Use inducer housing drain extension tube (violet label
and factory--supplied in loose parts bag) to connect LOWER inducer housing drain connection to condensate trap.
c. Determineappropriate length, then cut and connect tube.
d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube
a. Connect relief port tube (green label) to condensate trap.
b. Extend this tube (if required) by splicing to small
diameter tube (factory--supplied in loose parts bag).
c. Determineappropriate length, then cut and connect tube.
Condensate Trap Field Drain
Attachment
Refer to Condensate Drain section for recommendations and procedures.
PLUG
COLLECTOR BOX
DRAIN TUBE (BLUE &
WHITE STRIPED)
CAP
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (GREEN)
CONDENSATE
INDUCER HOUSING
(MOLDED) DRAIN
TUBE (VIOLET)
A07281
Fig. 8 -- Alternate Trap Location
Pressure Switch T
ubing
The LOWER collector box pressure tube (pink label) is factory connected to the pressure switch and should not require any modification.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.
Upper Collector Box and Inducer Housing (Unused)
Drain
Connections
Upper Collector Box Drain
Connection
Attached to the UPPER collector box drain connection is a factory--installed corrugated, plugged tube (blue and white striped label). This tube is plugged to prevent condensate leakage in this application. Ensure this tube is plugged.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.
Upper Inducer Housing Drain
Connection
Attached to the UPPER (unused) inducer housing drain connection is a cap and clamp. This cap is used to prevent condensate leakage in this application. Ensure this connection is capped.
NOTE: See Fig. 7 or 8 or tube routing label on main furnace door to check for proper connections.
Condensate Trap Freeze Pr
otection
Refer to Condensate Drain Protection section for recommendations and procedures.
355CAV
9
DRAIN TUBE (BLUE)
COLLECTOR BOX
DRAIN TUBE (BLUE &
WHITE STRIPED)
CONDENSATE
355CAV
INDUCER HOUSING
COLLECTOR BOX
PLUG
CAP
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE EXTENSION
(MOLDED) DRAIN
TUBE (VIOLET)
DRAIN TUBE COUPLING
COLLECTOR BOX TUBE (GREEN)
CAP
COLLECTOR BOX DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (PINK)
PLUG
COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)
COLLECTOR BOX TUBE EXTENSION
INDUCER HOUSING (MOLDED) DRAIN TUBE (VIOLET)
CONDENSATE
COLLECTOR BOX EXTENSION DRAIN TUBE
A07276
Fig. 9 -- Condensate Trap
DOWNFLOW APPLICATIONS
A downflow furnace application is where furnace blower is located above combustion and controls section of furnace, and conditioned air is discharged downwards.
Condensate Trap
The condensate trap must be removed from the factory--installed blower shelf location and relocated in selected application location as shown in Fig. 2, 9, or 10.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove three tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotaing trap.
3. Remove casing hole filler cap from casing hole. (See Fig. 2 and 10.)
4. Install casing hole filler cap (factory--supplied in loose parts bag) into blower shelf hole where trap was removed.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
5. Install condensate trap into left-- hand side casing hole by inserting tube connection stubs through casing hole and rotating until tabls snap into locking position.
6. Fill unused condensate trap casing holes with plastic filler caps (factory--supplied in loose parts bag).
Location
!
WARNING
A07277
Fig. 10 -- Factory--Shipped Trap Location
(Shown with Blower Access Panel Removed)
Condensate Trap T
ubing
NOTE: See Fig. 9 or 10 or tube routing label on main furnace
door to check for proper connections.
1. Collector Box DrainTube
a. Remove factory--installed plug from LOWER collector
box drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was connected to condensate trap.
c. Connect LOWER collector box drain connection to
condensate trap.
(3.) Condensate Trap Located on Left Side of Casing
(a.)Connect LOWER collector box drain tube (blue
and white striped label) to condensate trap. Tube does not need to be cut.
(b.)Clamp tube to prevent any condensate leakage.
(4.) Condensate Trap Located on Right Side of Casing
(a.)Install drain tube coupling (factory-- supplied in
loose parts bag) into collector box drain tube (blue and white striped label) which was previously plugged.
(b.)Connect larger diameter drain tube
(factory--supplied in loose parts bag) to drain tube coupling, extending collecor box drain tube for connection to condensate trap.
(c.)Route extended collector box drain tube
between gas valve and inlet housing as shown in Fig. 10.
(d.)Determine appropriate length and cut.
(e.)Connect to condensate trap.
2. Inducer Housing Drain Tube
a. Remove factory-- installed cap and clamp from LOWER
inducer housing drain connection.
10
b. Remove and discard UPPER (molded) inducer housing
draintube which was previously connectedto condensate trap.
PLUG
AUXILIARY “J” BOX
CONDENSATE
CAP
COLLECTOR BOX
TUBE EXTENSION
COLLECTOR BOX
EXTENSION
DRAIN TUBE
DRAIN TUBE
COUPLING
Fig. 11 -- Horizontal Left Tube Configuration
COLLECTOR BOX DRAIN TUBE (BLUE & WHITE STRIPED)
355CAV
COLLECTOR BOX TUBE (GREEN)
INDUCER HOUSING (MOLDED) DRAIN TUBE (VIOLET)
COLLECTOR BOX DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (PINK)
A07278
c. Install cap and clamp on UPPER inducer housing drain
conection where molded drain tube was removed.
d. Use inducer housing drain tube (violet label and
factory--supplied in loose parts bag) to connect LOWER inducerhousing drain connection to the condensate trap.
e. Connectinducerhousing drain connection to condensate
trap.
(1.) Condensate Trap Located on Left Side of Casing
(a.)Determine appropriate length and cut.
(b.)connect tube to condensate trap.
(c.)Clamp tube to prevent any condensate leakage.
(2.) Condensate Trap Located on Right Side of Casing
(a.)Route inducer yhousing drain tube (violet label)
directly from inducer housing to condensate trap.
(b.)Determine apprpriate length and cut.
(c.)Connect tube to condensate trap.
(d.)Clamp tube to prevent any condensate leakage.
3. Relief Port Tube Refer to Pressure Switch Tubing section for connection procedure.
Condensate Trap Field Drain
Attachment
Refer to Condensate Drain section for recommendations and procedures.
Pressure Switch T
ubing
One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW or HORIZONTAL LEFT applications. The tube MUST be disconnected and used or the condensate trap relief port tube. The other collector box pressure tube (green label)
which was factory connected to the condensate trap relief port connection MUST be connected to the pressure switch in DOWNFLOW o r HORIZONTAL RIGHT applications.
NOTE: See Fig. 9 or 10 or tube routing label on man furnace door to check for proper connections.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to pressure switch.
2. Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connection by splicing to small diameter tube (factory--supplied in loose parts bag).
3. Connect collector box pressure tube (green label) to pressu re switch connection labeled COLLECTOR BOX.
4. Extend collector box pressure tube (pink label) which was previously connected to pressure switch by splicing to remaining small diameter tube (factory--supplied in loose parts bag).
5. Route this extended tube (pink label) to condensate trap relief port connection.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
Condensate Trap Freeze Pr
otection
Refer to Condensate Drain Protection section for recommendations and procedures.
HORIZONTAL LEFT (SUPPLY--AIR DISCHARGE) APPLICATIONS
A horizontal left furnace application is where furnace blower is located to the right of combustion and controls section of furnace, and conditioned air is discharged to the left.
11
COMBUSTION – AIR
 
INTAKE
3
5
⁄4″
VENT
A 12-IN. MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE.
30 MIN WORK AREA
COMBUSTION–AIR
INTAKE
A 3-IN. MINIMUM CLEARANCE TO COMBUSTION-AIR INTAKE IS REQUIRED.
3
5
⁄4″
VENT
A 12-IN. MIN HORIZONTAL PIPE SECTION IS RECOMMENDED WITH SHORT (5 TO 8 FT) VENT SYSTEMS TO REDUCE EXCESSIVE CONDENSATE DROPLETS FROM EXITING THE VENT PIPE.
30-IN. MIN WORK AREA
MANUAL
SHUTOFF
GAS VALVE
SEDIMENT TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
CONDENSATE TRAP
DRAIN
ACCESS OPENING FOR TRAP
Fig. 12 -- Attic Location and Working Platform for Direct
Vent (2--Pipe) Application
355CAV
!
CAUTION
PROPERTY DAMAGE
Failure to follow this caution may result in property damage.
Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.
Condensate Trap
The condensate trap must be removed from the factory--installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 11.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove three tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotaing trap.
3. Remove casing hole filler cap from casing hole. (See Fig. 2or11.)
4. Install casing hole filler cap (factory--supplied in loose parts bag) into blower shelf hole where trap was removed.
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
5. Install condensate trap into left-- hand side casing hole by inserting tube connection stubs through casing hole an rotating until tabls snap into locking position.
6. Fill unused condensate trap casing holes with plastic filler caps (factory--supplied in loose parts bag).
Location
!
WARNING
A93031
MANUAL
SHUTOFF
GAS VALVE
SEDIMENT TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
CONDENSATE TRAP
DRAIN
ACCESS OPENING FOR TRAP
Fig. 13 -- Attic Location and Working Platform for
Ventilated Combustion Air Applications
Condensate Trap T
ubing
NOTE: See Fig. 11 or tube routing label on main furnace door
to check for proper connections.
1. Collector Box DrainTube
a. Install drain tube coupling (factory-- supplied in loose
partsbag) into collector box draintube (bluelabel) which was previously connected to condensate trap.
b. Connect large diameter drain tube and clamp
(factory--supplied in loose parts bag) to drain tube coupling, extending collecor box drain tube.
c. Route extended tube (blue label) to condensate trap and
cut to appropriate length.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
(a.)Remove and discard LOWER (molded) inducer
housing drain tube which was previously connected to condensate trap.
(b.)Use inducer housing drain extension tube (violet
label and factory--supplied in loose parts bag) to connect LOWER inducer housing drain connection to condensate trap.
(c.)Determine appropriate length, cut and connect
tube.
(d.)Clamp tube to prevent any condensate leakage.
3. Relief Port Tube a. Extend collector box tube (green label) which was
previously connected to condensate trap by splicing to small diameter tube (factory--suppled in loose partsbag).
b. Route extended collector box pressur tube to relief port
connectio on condensate trap.
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
Condensate Trap Field Drain
Attachment
Refer to Condensate Drain section for recommendations and procedures.
Pressure Switch T
ubing
The LOWER collector box pressure tube (pink label) is factory connected to the High Pressure Switch for use when furnace is installed in UPFLOW applications. This tube MUST be disconnected, extended rerouted, and then reconnected to the pressure switch in HORIZONTAL LEFT applications for 060 and 080 heating input furnaces.
NOTE: See Fig. 11 or tube routing label on main furnace door to check for proper connections.
Modify tube as described below.
12
A96184
1. Disconnect collector box pressure tube (pink label) attached to High Pressure Switch.
2. Use smaller diameter tube (factory--suppled in loose pars bag) to extend tube disconnected in Item 1.
3. Route extended tube:
a. Behind inducer housing.
b. Between blower shelf and inducer housing.
4. Determine appropriate lenght, cut, and reconnect tube to High Pressure Switch connections labeled COLLECTOR BOX.
Condensate Trap Freeze Pr
otection
Refer to Condensate Drain Protection section for recommendations and procedures.
Construct a Wo rking
Platform
Construct working platform where all required furnace clearances are met. (See Fig. 3 and 12 or 13.)
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation.
The condensate trap MUST be installed below furnace. See Fig. 6 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.
NOTE: A 12 --in. (304.8mm) minimum offset pipe section is recommended with short (5 to 8 ft or 1.5 M to 2.4 M) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 12, 13, or 44.)
HORIZONTAL RIGHT (SUPPLY-- AIR DISCHARGE) APPLICATIONS
A horizontal right furnace application is where furnace blower is located to the left of combustion and controls section of furnace, and conditioned air is discharged to the right.
!
CAUTION
PROPERTY DAMAGE HAZARD
Failure to follow this caution may result in property damage.
Local codes may require a drain pan under entire furnace and condensate trap when a condensing furnace is used in an attic application or over a finished ceiling.
NOTE: In Canada, installations shall be in accordance with current NSCNGPIC and/or local codes.
NOTE: The auxiliary junction box (J--box ) MUST be relocated to opposite side of furnace casing. (See Fig. 14.) See Electrical Connection section for J--box relocation.
Condensate Trap
COLLECTOR BOX
DRAIN TUBE (BLUE)
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE &
WHITE STRIPED)
INDUCER HOUSING
(MOLDED) DRAIN
TUBE (VIOLET)
Location
COLLECTOR BOX
EXTENSION TUBE
PLUG
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX TUBE (PINK)
AUXILIARY “J” BOX RELOCATED HERE
CONDENSATE
A07279
Fig. 14 -- Horizontal Right Tube Configuratio n
The condensate trap must be removed from the factory--installed blower shelf location and relocated in selected application location as shown in Fig. 2 or 14.
To relocate condensate trap from the blower shelf to desired location, perform the following:
1. Remove three tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs inward and rotaing trap.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury or death.
Casing hole filler cap must be installed in blower shelf hole when condensate trap is relocated to prevent combustion products being drawn in from appliances in the equipment room.
3. Install casing hole filler cap (factory--supplied in loose parts bag) into blower shelf hole where trap was removed.
4. Install condensate trap into right-- hand side casing hole by inserting tube connection stubs through casing hole an rotating until tabls snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler caps (factory--supplied in loose parts bag).
355CAV
LEVEL (0)
TO
1
2 MAX
UPFLOW OR DOWNFLOW HORIZONTAL
FRONT
MIN
TO
1
2 MAX
1
4
Fig. 15 -- Proper Condensate Drainage
13
FRONT
A02146
Condensate Trap T
NOTE: See Fig. 14 or tube routing label on main furnace door
to check for proper connections.
1. Collector Box DrainTube
a. Remove factory--installed plug from LOWER collector
box drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was previously connected to condensate trap.
c. Connect LOWER collector box drain tube (blue and
white striped label) to condensate trap. Tube does not need to be cut.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
355CAV
3. Relief Port Tube Refer to Pressure Switch Tubing section for recommendations and procedures.
Condenste Trap Field Drain
Refer to Condensate Drain section for recommendations and procedures.
Pressure Switch T
One collector box pressure tube (pink label) is factory connected to the pressure switch for use when furnace is installed in UPFLOW or HORIZONTAL LEFT applications. This tube MUST be disconnected and used for the condensate trap relief port tube. The other collector box pressure tube (green label) which was factory connected to the condensate trap relief port connection MUST be connect to the pressure switch in DOWNFLOW o r HORIZONTAL RIGHT applications.
NOTE: See Fig. 14 or tube routing label on main furnace door to check for proper connections.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label) attached to pressure switch.
2. Extend collector box pressure tube (green label) which was previously connected to condensate trap relief port connection by splicing to small diameter tube (factory--suppled in loose parts bag.)
3. Connect collector box pressure tube (green label) to pressu re switch connection labeled COLLECTOR BOX.
4. Use remaining small diameter tube (factory--suppled in loose parts bag) to extend collector box pressure tube (pink label) which was previously connected to pressure switch.
5. Route this extende tube (pink label) to condensate trap relief port connection.
6. Determine appropriate lenght, cut, and connect tube.
7. Clamp tube to relief port connection.
ubing
(a.)Remove factory--installed cap and clamp from
LOWER inducer housing drain connection.
(b.)Remove and discard UPPER (molded) inducer
housing drain tube which was previously connected to condensate trap.
(c.)Install cap and clamp on UPPER inducer
housing drain connection where molded drain tube was removed.
(d.)Use inducer housing drain extension tube (violet
label and factory--suppled in loose parts bag) to connect LOWER inducer housing drain connection to condensate trap.
(e.)Determine appropriate length, cut, and connect
tube to condensate trap.
(f.)Clamp tube to prevent any condensate leakage.
Attachment
ubing
Condensate Trap Freeze Pr
Refer to condensate Drain Protection section for recommendations and procedures.
Construct a Wo rking
Construct working platform where all required furnace clearances are met. (See Fig. 3 and 12 or 13.)
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent unit operation.
The condensate trap MUST be installed below furnace. See Fig. 6 for dimensions. The drain connection to condensate trap must also be properly sloped to an open drain.
NOTE: A 12 --in. (304.8mm) minimum offset pipe section is recommended with short (5 to 8 ft or 1.5 m to 2.4 m) vent systems. This recommendation is to reduce excessive condensate droplets from exiting the vent pipe. (See Fig. 12, 13, or 44.)
otection
Platform
CAUTION
LOCATION
General
This furnace must
S be installed so the electrical components are protected
from water.
S not be installed directly on any combustible material
other than wood flooring (refer to SAFETY CONSIDERATIONS).
S be located so combustion-- air and vent pipe maximum
lengths are not exceeded. Refer to Table 7.
S be located where available electric power and gas
supplies meet specifications on the furnace rating plate.
S be attached to an air distribution system and be located
as close to the center of the distribution system as possible. Refer to Air Ducts section.
S be provided with ample space for servicing and
cleaning. Always comply with minimum fire protection clearances shown on the furnace clearance--to--combustibles label. (See Fig. 3.)
This furnace may be located in a confined space without special provisions for dilution or ventilation air.
NOTE: For upflow/downflow applications install furnace so that it is level or pitched and forward within 1/2--in. (12.7mm) for proper furnace operation. For horizontal applications pitch 1/4--in. (6mm) minimum to 1/2--in. (12.7mm) maximum forward to ensure proper condensate drainage from secondary heat exchangers. (See Fig. 15.) When a furnace is installed so that supply ducts carry air circulated by the furnace to areas outside the space containing the furnace, the return air shall also be handled by ducts sealed to furnace casing. The ducts terminate outside the space containing the furnace to ensure there will not be a negative pressure condition within equipment room or space.
14
FRONT
B A C K
BACK
FRONT
A93043
Fig. 16 -- Prohibit Installation on Back
!
CAUTION
UNIT DAMAGE HAZARD
This gas furnace may be used for construction heat provided that:
--The furnace is permanently installed with all electrical wiring, piping, air filters, venting and ducting installed according to these installation instructions. A return air duct is provided, sealed to the furnace casing, and terminated outside the space containing the furnace. This prevents a negative pressure condition as created by the circulating air blower, causing a flame rollout and/or drawing combustion products into the structure.
--The furnace is controlled by a thermostat. It may not be “hot wired” to provide heat continuously to the structure without thermostatic control.
--Clean outside air is provided for combustion. This is to minimize the corrosive effects of adhesives, sealers and other construction materials. It also prevents the entrainment of drywall dust into combustion air, which can cause fouling and plugging of furnace components.
--The temperature of the return air to the furnace is maintained between 55_F(13_C) and 80_F(27_C), with no evening setback or shutdown. The use of the furnace while the structure is under construction is deemed to be intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on the furnace rating plate, and the firing rate has been set to the nameplate value.
--The filters used to clean the circulating air during the construction process must be either changed or thoroughly cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary to remove drywall dust and construction debris from all HVAC system components after construction is completed.
--After construction is complete, verify furnace operating conditions including ignition, input rate, temperature rise and venting, according to the manufacturer’s instructions.
!
WARNING
FIRE OR DEATH HAZARD
Failure to follow this warning could result in property damage, personal injury, or death.
Do not install furnace on its back. (See Fig. 16.) Safety control operation will be adversely affected. Never connect return--air ducts to back of furnace.
The furnace and its return air system shall be designed and installed so that negative pressure created by the air circulating fan cannot affect another appliance’s combustion air supply or act to mix products of combustion with circulating air, and that the air circulating fan of the furnace, if installed in an enclosure communicating with another fuel--burning appliance not of the direct--vent type, shall be operable only when any door or panel covering an opening in the furnace fan compartment or in a return air plenum on ducts is in the closed position.
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in minor property or unit damage.
If these furnaces are installed in an unconditioned space where ambient temperatures may be 32_F(0_C) or lower, freeze protection measures must be taken. See Condensate Drain Protection section and Fig. 17.
32oF MINIMUM INSTALLED AMBIENT OR FREEZE PROTECTION REQUIRED
A93058
Fig. 17 -- Freeze Protection
Furnace Location Relative to Cooling
The cooling coil must be installed parallel with or on downstream side of furnace to avoid condensation in heat exchanger. When installed parallel with a furnace, dampers or other means used to control flow of air shall be adequate to prevent chilled air from entering furnace. If dampers are manually operated, they must be equipped with a means to prevent operation of either unit unless damper is in full--heat or full--cool position.
Equipment
355CAV
15
Hazardous
FIRE, EXPLOSION, INJURY OR DEATH HAZARD
Improper location or inadequate protection could result in fire or explosion.
When furnace is installed in a residential garage, it must be installed so that burners and ignition sources are located a minimum of 18 in. (457.2mm) above floor. The furnace must be located or protected to avoid physical damage by vehicles. When furnace is installed in a public garage, airplane hangar, or other building having a hazardous atmosphere, unit must be installed in accordance with requirements of National Fire Protection Association, Inc. (See Fig. 5.)
355CAV
Locations
!
5
16
1 3⁄4
WARNING
5
16
4. Adjust outside nut to provide desired height, and tighten inside nut to secure arrangement.
NOTE: Bottom closure must be used when leveling legs are used. See Bottom Closure Panel section.
Installation in Upflow or Downflow
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when special base (available from Manufacturer) Part No. KGASB is used. Special base is not required when this furnace is installed on Manufacturer’s Cased Coil Assembly or when Manufacturer’s Coil Box is used.
1. Determine application being installed from Table 1.
2. Construct hole in floor per dimensions specified in Table 1 and Fig. 19.
3. Construct plenum to dimensions specified in Table 2 and Fig. 19.
4. If special b ase (KGASB) is used, install as shown in Fig.
20.
5. If Manuracturer’s Cased Coil Assembly or Manufacturer’s Coil Box is used, install as shown in Fig. 21.
NOTE: Remove furnace perforated discharge duct flanges when they interfere with mating flanges on coil on downflow subbase. To remove furnace perforated discharge duct flange, use hand scanners, wide duct pliers or duct flange tool to bend flange back and forth until it breaks off. Be careful of sharp edges. (See Fig.
22.)
Applications
3
4
1
5
16
5
16
3
4
1
3
1
4
A89014
Fig. 18 -- Leveling Legs
INSTALLATION
Leveling Legs (If Desired)
When furnace is used in upflow position with side inlet(s), leveling legs may be desired. (See Fig. 18.) Install field--supplied, corrosion--resistant 5/16--in.(7.9mm) machine bolts and nuts.
NOTE: The maximum length of bolt should not exceed 1 --1/2 in. (38.1mm).
1. Position furnace on its back. Locate and drill a 5/16--in. (7.9mm) diameter hole in each bottom corner of furnace. (See Fig. 18.) Holes in bottom closure panel may be used as guide locations.
2. For each hole, install nut on bolt and then install bolt and nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat washer if desired.)
!
CAUTION
UNIT MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
Do not bend duct flanges inward as shown in Fig. 22. This will affect airflow across heat exchangers and may cause limit cycling or premature heat exchanger failure. Remove duct flange completely or bend it inward a minimum of 210_F(99_C) as shown in Fig. 22.
Installation in Horizontal Applications
These furnaces can be installed in either horizontal left or right discharge position. In a crawlspace, furnace can either be hung from floor joist or installed on suitable blocks or pad. Furnace can be suspended from each corner by hanger bolts and angle iron supports. (See Fig. 23.) Cut hanger bolts (4 each 3/8-- in. all--thread rod) to desired length. Use 1 X 3/8--in. flat washers, 3/8--in. lock washers, and 3/8--in. nuts on hanger rods as shown in Fig. 23. Dimples are provided for hole locations. (See Fig. 2.)
!
CAUTION
UNIT MAY NOT OPERATE HAZARD
Failure to follow this caution may result in intermittent unit operation or performance satisfaction.
The entire length of furnace MUST be supported when furnace is used in a horizontal position to ensure proper draining. When suspended, bottom brace supports sides and center blower shelf. When unit is supported from the ground, blocks or pad should support sides and center blower shelf area.
16
FURNACE
FACTORY SUPPLIED
CASED COIL OR COIL BOX
A
PLENUM
OPENING
B D
FLOOR
OPENING
C
Fig. 19 -- Floor and Plenum Opening Dimensions
FURNACE
(OR OTHER MANUFACTURERS COIL CASING WHEN USED)
A96283
COMBUSTIBLE
FLOORING
SHEET METAL
PLENUM
FLOOR
OPENING
355CAV
A07586
Fig. 21 -- Furnace, Plenum, and Coil Assembly or Coil Box
Installed on a Combustible Floor
PERFORATED DISCHARGE DUCT FLANGE
NO
COMBUSTIBLE
FLOORING
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
Fig. 20 -- Furnace, Plenum, and Subbase Installed on a
Combustible Floor
A07585
YES
210¡ MIN
YES
A93029
Fig. 22 -- Duct Flanges
17
3
/8-IN. ROD
ANGLE IRON OR EQUIVALENT
355CAV
(B)
(A)
(B)
3
5
DRAIN
/4″
ALTERNATE SUPPORT LOCATION 4-IN. MIN 8-IN. MAX
(A)
(A) ROD LOCATION
USING DIMPLE LOCATORS (SEE DIMENSIONAL DWG FOR LOCATIONS)
(A) PREFERRED ROD LOCATION
(B) ALTERNATE ROD LOCATION
3
/8-IN. HEX NUT
& WASHER (4)
REQD PER ROD
NOTES:
(A)
1. A 1 In. clearance minimum between top of furnace and combustible material.
2. The entire length of furnace must be supported when furnace is used in horizontal position to ensure proper drainage.
(B)
(B)
13
/16-IN. MAX ALTERNATE SUPPORT LOCATION FROM BACK
Fig. 23 -- Crawlspace Horizontal Application for Direct Vent/2--Pipe Installation and for Ventilated Combustion Air Installation
A93304
18
Loading...
+ 42 hidden pages