353BAV
DELUXE 4--WAY MULTIPOISE 2--STAGE
CONDENSING GAS FURNACE
SIZES 060--120
Installation, Start--up and
Operating Instructions
NOTE:Read the entire instruction manual before starting
the installation.
NOTE: This furnace can be installed as a
or (1-pipe) non-direct vent
Special Venting Requirements for Installations in Canada
Installation in Canada must conform to the requirements of CSA
B149 code. Vent systems must be composed of pipe, fittings,
cements, and primers listed to ULC S636. The special vent
fittings and accessory concentric vent termination kits and
accessory external drain trap have been certified to ULC S636 for
use with those IPEX PVC vent components which have been
certified to this standard. In Canada, the primer and cement must
be of the same manufacturer as the vent system -- IPEX System
636, PVC/CPVC Primer, Purple Violet for Flue Gas Venting and
IPEX System 636, PVC Cement for Flue Gas Venting, rated
Class IIA, 65 deg C. must be used with this venting system -- do
not mix primers and cements from one manufacturer with a vent
system from a different manufacturer. Follow the manufacturer’s
instructions in the use of primer and cement and never use primer
or cement beyond its expiration date.
The safe operation, as defined by ULC S636, of the vent system
is based on following these installation instructions, the vent
system manufacturer’s installation instructions, and proper use of
primer and cement. All fire stop and roof flashing used with this
system must be UL listed material. Acceptability under Canadian
standard CSA B149 is dependent upon full compliance with all
installation instructions. Under this standard, it is recommended
that the vent system be checked once a year by qualified service
personnel.
The authority having jurisdiction (gas inspection authority,
municipal building department, fire department, etc) should be
consulted before installation to determine the need to obtain a
permit.
condensing gas furnace.
(2-pipe) direct vent
Consignes spéciales pour l’installation de ventillation au Canada
L’installation faite au Canada doit se conformer aux exigences du
code CSA B149. Ce systême de ventillation doit se composer de
tuyaux, raccords, ciments et apprêts conformes au ULC S636. La
tuyauterie de ventillation des gaz, ses accessoires, le terminal
concentrique mural ainsi que l’ensemble du drain de condensat
extérieur ont été certifiés ULCS 636 pour l’application des
composantes IPEX PVC qui sont certifiées à ce standard. Au
Canada l’apprêt et le ciment doivent être du même manufacturier
que le systême de ventillation -- IPEX Système 636, Apprêt
PVC/CPVC. Mauve Violette pour conduit en évacuation des gaz
et IPEX Système 636, ciment pour PVC pour conduit en
évacuation des gaz, évalué CLASSEIIA,65deg.C.doitëtre
utilisé avec ce systèeme d’évacuation -- ne pas mélanger l’apprêt
et le ciment d’un manufacturier avec le systême de ventillation
d’un autre manufacturier. Bien suivre les indications du
manufacturier lors de l’utilisation de l’apprêt et du ciment et ne
pas utiliser ceux--ci si la date d’expiration est atteinte.
L’opération sécuritaire, tel que définit par ULC S636, du système
de ventilation est basé sur les instructions d’installation suivantes,
ainsi que l’usage approprié de l’apprêt et ciment. Tout arrët feu et
solin de toit utilisés avec ce système doivent être des matériaux
listés UL. L’acceptation du standard Canadien CSA B419 est
directement relié à l’installation conforme aux instructions ci-haut mentionnées. Le standard Canadien recommande l’
inspection par un personel qualifié et ce, une fois par année.
Some Provinces may require the combustion air system to be
ULC--S636 certified.
1
Required Notice for Massachusetts Installations
IMPORTANT
The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows:
5.08: Modifications to NFPA--54, Chapter 10
2) Revise 10.8.3 by adding the following additional requirements:
a. For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used
in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where
the side wall exhaust vent termination is less than seven (7) feet (2.1 M) above finished grade in the area of the
venting, including but not limited to decks and porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS. At the time of installation of the side wall horizontal vented
gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide detector with an
alarm and battery back--up is installed on the floor level where the gas equipment is to be installed. In addition, the
installing plumber or gasfitter shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is
installed on each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled
equipment. It shall be the responsibility of the property owner to secure the services of qualified licensed professionals for
the installation of hard wired carbon monoxide detectors
a. In the event that the side wall horizontally vented gas fueled equipment is installed in a crawl space or an attic, the hard
353BAV
wired carbon monoxide detector with alarm and battery back--up may be installed on the next adjacent floor level.
b. In the event that the requirements of this subdivision can not be met at the time of completion of installation, the owner
shall have a period of thirty (30) days to comply with the above requirements; provided, however, that during said thirty
(30) day period, a battery operated carbon monoxide detector with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each carbon monoxide detector as required in accordance with the
above provisions shall comply with NFPA 720 and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be permanently mounted to the exterior of the building at a
minimum height of eight (8) feet above grade directly in line with the exhaust vent terminal for the horizontally vented gas
fueled heating appliance or equipment. The sign shall read, in print size no less than one--half (1/2) inch in size, ”GAS
VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side wall horizontally vented gas fueled equipment shall not approve
the installation unless, upon inspection, the inspector observes carbon monoxide detectors and signage installed in
accordance with the provisions of 248 CMR 5.08(2)(a)1 through 4.
5. EXEMPTIONS: The following equipment is exempt from 248 CMR 5.08(2)(a)1 through 4:
(1.) The equipment listed in Chapter 10 entitled ”Equipment Not Required To Be Vented” in the most current edition of
NFPA 54 as adopted by the Board; and
(2.) Product Approved side wall horizontally vented gas fueled equipment installed in a room or structure separate from
the dwelling, building or structure used in whole or in part for residential purposes.
c. MANUFACTURER REQUIREMENTS -- GAS EQUIPMENT VENTING SYSTEM PROVIDED. When the
manufacturer of Product Approved side wall horizontally vented gas equipment provides a venting system design
or venting system components with the equipment, the instructions provided by the manufacturer for installation
of the equipment and the venting system shall include:
1. Detailed instructions for the installation of the venting system design or the venting system components; and
2. A complete parts list for the venting system design or venting system.
d. MANUFACTURER REQUIREMENTS -- GAS EQUIPMENT VENTING SYSTEM NOT PROVIDED. When
the manufacturer of a Product Approved side wall horizontally vented gas fueled equipment does not provide the
parts for venting the flue gases, but identifies “special venting systems”, the following requirements shall be
satisfied by the manufacturer:
1. The referenced “special venting system” instructions shall be included with the appliance or equipment installation
instructions; and
2. The “special venting systems” shall be Product Approved by the Board, and the instructions for that system shall include a
parts list and detailed installation instructions.
e. A copy of all installation instructions for all Product Approved side wall horizontally vented gas fueled
equipment, all venting instructions, all parts lists for venting instructions, and/or all venting design instructions
shall remain with the appliance or equipment at the completion of the installation.
For questions regarding these requirements, please contact the Commonwealth of Massachusetts Board of State Examiners of Plumbers
and Gas Fitters, 239 Causeway Street, Boston, MA 02114. 617--727--9952.
Failure to follow this caution may result in unit component
damage.
Application of this furnace should be indoors with special
attention given to vent sizing and material, gas input rate, air
temperature rise, unit leveling, and unit sizing.
!
WARNING
FIRE, EXPLOSION, ELECTRICAL SHOCK AND
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury,
death or property damage.
Improperinstallation,adjustment,alteration,service,
maintenance, or use can cause carbon monoxide poisoning,
explosion, fire, electrical shock, or other conditions which may
cause personal injury or property damage. Consult a qualified
installer, service agency, local gas supplier, or your distributor
or branch for information or assistance. The qualified installer
or agency must use only factory-authorized and listed kits or
accessories when modifying this product.
Installing and servicing heating equipment can be hazardous due
to gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations
must be performed by trained service personnel. When working
on heating equipment, observe precautions in literature, on tags,
and on labels attached to or shipped with unit and other safety
precautions that may apply.
These instructions cover the minimum requirements and conform
to existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing
residential construction practices. We require these instructions as
a minimum for a safe installation.
Wear safety glasses and work gloves.
!
CUT HAZARD
Failure to follow this caution may result in personal injury.
Sheet metal parts may have sharp edges or burrs. Use care
and wear appropriate protective clothing and gloves when
handling parts.
Follow all safety codes. Wear safety glasses, protective clothing
and work gloves. Have a fire extinguisher available. Read these
instructions thoroughly and follow all warnings or cautions
included in literature and attached to the unit. Consult local
building codes, the current editions of the National Fuel Gas
Code (NFGC) NFPA 54/ANSI Z223.1 and the National Electrical
Code (NEC) NFPA 70.
In Canada, refer to the current editions of the National Standards
of Canada CAN/CSA--B149.1 and .2 Natural Gas and Propane
Installation Codes, and Canadian Electrical Code CSA C22.1.
Recognize safety information. This is the safety-alert symbol
When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury.
Understand these signal words: DANGER, WARNING, and
CAUTION. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies hazards
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which may result in minor personal
injury or product and property damage. NOTE is used to
CAUTION
353BAV
.
3
highlight suggestions which will result in enhanced installation,
reliability, or operation.
AIRFLOW
UPFLOW
HORIZONTAL
LEFT
AIRFLOW
353BAV
Fig. 1 -- Multipoise Orientations
DOWNFLOW
AIRFLOW
HORIZONTAL
RIGHT
The model 353BAV, 2-Stage, 4-way Multipoise, Gas-Fired,
Category IV, condensing furnace is available in model sizes
ranging in high-stage gas input rates of 60,000 to 120,000 Btuh.
This furnace is CSA (formerly AGA and CGA) design-certified
for natural and propane gases (see furnace rating plate) and for
installation in alcoves, attics, basements, closets, utility rooms,
crawlspaces, and garages. This furnace is factory-shipped for use
with natural gas. A CSA listed gas conversion kit is required to
convert furnace for use with propane gas.
See Fig. 3 for required clearances to combustibles.
This furnace SHALL NOT be installed directly on carpeting, tile,
or any other combustible material other than wood flooring. For
downflow installations, a factory accessory floor base must be
used when installed on combustible materials and wood flooring.
Special base is not required when this furnace is installed on the
manufacturer’s coil assembly or when the manufacturer’s coil
box is used. The design of the 353BAV furnace is not CSA
certified for installation in mobile homes, recreational vehicles, or
outdoors. This furnace is suitable for installation in a structure
built on site or a manufactured building completed at final site.
This furnace is designed for continuous return-air minimum
temperature of 60°F(15°C) db or intermittent operation down to
55°F(13°C) db such as when used with a night setback
thermostat. Return-air temperature must not exceed 80°F(27°C)
db. Failure to follow these return air limits may affect reliability
of heat exchangers, motors and controls. (See Fig. 4.)
This furnace is shipped with the drain and pressure tubes
connected for UPFLOW applications. Minor modifications are
requiredwhenusedinDOWNFLOW, HORIZONTAL RIGHT,
or HORIZONTAL LEFT (supply-air discharge direction)
applications as shown in Fig. 1. See details in Applications
section.
Install this furnace only in a location and position as specified in
LOCATION and INSTALLATION sections of these instructions.
Always provide adequate combustion and ventilation air as
specified in section Combustion Air and Vent Pipe Systems of
these instructions to furnace.
AIRFLOW
A93041
Combustion products must be discharged outdoors. Connect this
furnace to an approved vent system only, as specified in the
Combustion Air and Vent Piping sections of these instructions.
Never test for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of
leaks to check all connections, as specified in the GAS PIPING
section of these instructions.
Always install furnace to operate within the furnace’s intended
rise range with a duct system which has an external static
pressure within the allowable range, as specified in the SET
TEMPERATURE RISE section of these instructions and furnace
rating plate.
When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing the
furnace, the return air shall also be handled by duct(s) sealed to
the furnace casing and terminating outside the space containing
the furnace.
A gas-fired furnace for installation in a residential garage must be
installed as specified in the Hazardous Locations section of these
instructions.
The furnace may be used for construction heat provided that the
furnace installation and operation complies with:
S The furnace is permanently installed with all electrical wiring,
piping, air filters, venting and ducting installed according to
these installation instructions. A return air duct is provided,
sealed to the furnace casing, and terminated outside the space
containing the furnace. This prevents a negative pressure
condition as created by the circulating air blower, causing a
flame rollout and/or drawing combustion products into the
structure.
S The furnace is controlled by a thermostat. It may not be “hot
wired” to provide heat continuously to the structure without
thermostatic control.
S Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and other
construction materials. It also prevents the entrainment of
drywall dust into combustion air, which can cause fouling and
plugging of furnace components.
S
The temperature of the return air to the furnace is maintained
between 55°F(13°C) and 80°F(27°C), with no evening
setback or shutdown. The use of the furnace while the structure
is under construction is deemed to be intermittent operation per
our installation instructions.
S The air temperature rise is within the rated rise range on the
furnace rating plate, and the firing rate has been set to the
nameplate value.
S The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
S The furnace, ductwork and filters are cleaned as necessary to
remove drywall dust and construction debris from all HVAC
system components after construction is completed.
This furnace is shipped with the following materials to assist in
proper furnace installation. These materials are shipped in the
main blower compartment.
The furnace shall be installed so that the electrical components
are protected from water.
For accessory installation detail, refer to the accessory installation
instruction.
4
NOTE: Remove all shipping materials before operating furnace.
Installer Packet includes:
Installation, Startup, and Operating Instructions
Service and Maintenance Instructions
User’s Information Manual
Warranty Certificate
Loose Parts Bag includes:Quantity
Pressure tube extension1
Collector Box or condensate trap extension tube1
Inducer housing drain tube1
1/2--in CPVC street elbow2
Drain tube coupling1
Drain tube coupling grommet1
Condensate trap hole filler plug3
Vent and combustion-air intake hole filler plug2
Combustion--air intake pipe perforated disk assembly1
Gas line grommet1
Vent pipe grommet1
Combustion--air pipe grommet1
Power entry hole filler plug2
Vent Pipe Extension1*
*100,000 Btuh and larger.
CODES AND STANDARDS
Follow all national and local codes and standards in addition
to these instructions. The installation must comply with
regulations of the serving gas supplier, local building, heating,
plumbing, and other codes. In absence of local codes, the
installation must comply with the national codes listed below and
all authorities having jurisdiction.
In the United States and Canada, follow all codes and standards
for the following:
Step 1 -- Safety
S US: National Fuel Gas Code (NFGC) NFPA 54--2009/ANSI
Z223.1--2009 and the Installation Standards, Warm Air Heating
and Air Conditioning Systems ANSI/NFPA 90B
S CANADA: National Standard of Canada, Natural Gas and
S US: NFGC and the NFPA 90B. For copies, contact the
National Fire Protection Association Inc., Batterymarch Park,
Quincy, MA 02269; or for only the NFGC contact the
American Gas Association, 400 N. Capitol, N.W., Washington
DC 20001
S CANADA: NSCNGPIC. For a copy, contact Standard Sales,
S CANADA: Part 8 of the NSCNGPIC, Venting Systems and Air
Supply for Appliances
Step 4 -- Duct Systems
S US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning
Contractors National Association (SMACNA), or American
Society of Heating, Refrigeration, and Air Conditioning Engineers
(ASHRAE) 2005 Fundamentals Handbook Chapter 35.
Step 5 -- Acoustical Lining and Fibrous Glass Duct
S US and CANADA: current edition of SMACNA, NFPA 90B as
tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6 -- Gas Piping and Gas Pipe Pressure Testing
S US: Section 9.3 NFPA 54/ANSI Z223.1--2009 NFGC; Chapters 5,
6, 7, and 8 and national plumbing codes.
CANADA: CAN/CSA----B149.1----05, Parts 4, 5, 6, and 9.
In the state of Massachusetts:
S This product must be installed by a licensed plumber or gas fitter.
S When flexible connectors are used, the maximum length shall
not exceed 36 in. (914 mm).
S When lever type gas shutoffs are used they shall be T--handle type.
S The use of copper tubing for gas piping is not approved by the
state of Massachusetts.
Step 7 -- Electrical Connections
S US: National Electrical Code (NEC) ANSI/NFPA 70--2008
S CANADA: Canadian Electrical Code CSA C22.1
(27º C)
0
60
(16º C)
A05004
Fig. 2 -- Return--Air Temperature
353BAV
5
(694mm)
"
(724mm)
16
⁄
"
2
⁄
15
1
26
28
(667mm)
"
4
⁄
1
26
(567mm)
"
16
⁄
5
22
(21mm)
(16mm)
"
"
16
⁄
8
⁄
5
13
(483mm)
19"
OUTLET
"
16
⁄
5
AIR CONN
2-IN. COMBUSTION-
(8mm)
-IN. DIA
2
⁄
GAS CONN
1
DIA
-IN.
8
⁄
POWER CONN
7
1
. DIA
-IN
2
⁄
"
8
⁄
7
39
(1013mm)
T ENTRY
A
THERMOST
. VENT CONN
2-IN
"
16
⁄
1
1
22
1"
(25mm)
SIDE INLET
(11mm)
"
16
⁄
7
TYP
"
4
⁄
1
22
1
1
3
(565mm)
(17mm)
"
16
⁄
"
16
⁄
24
BOTTOM INLET
(614mm)
"
16
⁄
9
TYP
(14mm)
"
2
⁄
1
30
TYP
(845mm)
"
16
⁄
13
30
"
(783mm)
16
⁄
1
1
TYP
29
(775mm)
"
8
⁄
5
TYP
32
(754mm)
"
8
⁄
5
27
(702mm)
353BAV
(DOWNFLOW &
TRAP LOCATION
HORIZONTAL RIGHT)
CONDENSATE DRAIN
OR ALTERNATE
-IN. DIA GAS CONN
2
⁄
1
"
4
⁄
1
33
"
16
/
13
A
D
"
16
/
13
OUTLET
AIRFLOW
(22mm)
Y
(22mm)
-IN. DIA
CCESSOR
8
⁄
A
7
CONDENSAT E
POWER ENTRY
HORIZONTAL LEFT)
(DOWNFLOW &
TRAP LOCATION
CONDENSATE DRAIN
-IN. DIA
8
⁄
POWER CONN
7
(829mm)
"
16
⁄
9
TYP
27
(700mm)
ALTERNATE
(
LOCATION
DRAIN TRAP
1
UPFLOW)
"
2
⁄
24
"
4
⁄
1
18
(464mm)
"
(622mm)
16
⁄
5
17
7
.
P
ate
. ES
, a
.C
5“ W
0.
CFM at
00
ve 18
. The use of both side inlets
s
CFM, see Air Delivery table in Product Data
ove 1800
ab
return air openings for airflow requirements abo
combination of 1 side and the bottom, or the bottom only will ensure adequ
literature for specific use of single side inlet
d. For airflow requirements
DIMENSIONS --- IN. (MM)
ADE
21 (533)19---3/8 (492)19---1/2 (495)
7---1/2 (445)15---7/8 (403)16 (406)
17---1/2 (445)15---7/8 (403)16 (406)
1
17---1/2 (445)15---7/8 (403)16 (406)
24---1/2 (622)22---7/8 (581)23 (584)
CONDENSAT E
DRAIN LOCATION
INLET
ORS
(UPFLOW)
DIMPLE LOCAT
"
16
/
11
HANGING
FOR HORIZONTA L
ed,
-in. (495mm) rectangle.
-in.(591mm) rectangle.
2
4
/
/
1
1
x 23
valent diameters.
(368mm) x 19
(368mm)
2
(368mm) x 12-in. (305mm) rectangle.
2
/
2
/
1
/
1
E
1
, based on metal duct. If flex duct is us
round or 14
round or 14
)
round or 14
"
16
/
11
at furnace
s recommendations for equi
ufacturerÕ
n
a
see flex duct m
)
08mm
n .(559mm)
n . (5
n . (406mm
0-i
6-i
00 CFM 2
600 CFM 22-i
c. For 1
b. For 12
a. For 800 CFM 1
2. Minimum return-air opening at furnace:
(440mm)
036060
036080
048080
060100
"
16
⁄
TYP
9
(240mm)
(UPFLOW)
DRAIN LOCATION
CONDENSAT E
NOTES: 1. Minimum return-air openings
UNIT SIZE
060120
(684mm)
"
16
⁄
(667mm)
15
"
4
⁄
1
26
26
(51mm)
(666mm)
"
(567mm)
2
⁄
1
"
16
⁄
24
5
22
-IN. COMBUSTION2
AIR CONN
(13mm)
-IN. DIA
2
⁄
1
GAS CONN
-IN. VENT CONN
(51mm)
2
T
TA
ENTRY
"
16
⁄
1
1
22
THERMOS
(13mm)
-IN. DIA
2
⁄
1
(576mm)
(32mm)
"
4
⁄
1
1
T
E
(591mm)
P
TY
"
SIDE INL
4
⁄
1
23
1"
(25mm)
(684mm)
P
TY
"
16
⁄
15
26
T
SIDE INLE
"
2
⁄
P
1
TY
14
(368mm)
Fig. 3 -- Dimensional Drawing
6
A08323
335122-201 REV. B LIT TOP
Fig. 4 -- Clearances to Combustibles
353BAV
A08435
ELECTROSTATIC DISCHARGE (ESD)
PRECAUTIONS PROCEDURE
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in damage to unit
components.
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing to
protect the furnace electronic control. Precautions will
prevent electrostatic discharges from personnel and hand
tools which are held during the procedure. These precautions
will help to avoid exposing the control to electrostatic
discharge by putting the furnace, the control, and the person
at the same electrostatic potential.
3. Disconnect all power to the furnace. Multiple disconnects
may be required. DO NOT TOUCH THE CONTROL OR
ANY WIRE CONNECTED TO THE CONTROL PRIOR
TO DISCHARGING YOUR BODY’S ELECTROSTATIC
CHARGE TO GROUND.
4. Firmly touch the clean, unpainted, metal surface of the
furnace chassis which is close to the control. Tools held in
hand during grounding will be discharged.
5. After touching the chassis, you may proceed to service the
control or connecting wires as long as you do nothing to
recharge your body (moving or shuffling feet, touching
ungrounded objects, etc.).
6. If you touch ungrounded objects, firmly touch a clean,
unpainted metal surface of the furnace again before
touching control or wires.
7. Use this procedure for installed and uninstalled
(ungrounded) furnaces.
8. Before removing a new control from its container,
discharge your body’s electrostatic charge to ground to
protect the control from damage. If the control is to be
installed in a furnace, follow items 1 through 4 before
bringing the control or yourself in contact with the
furnace. Put all used and new controls into containers
before touching ungrounded objects.
9. An ESD service kit (available from commercial sources)
mayalsobeusedtopreventESDdamage.
7
INTRODUCTION
The model 353BAV 4-way multipoise, Gas-Fired, Category IV,
condensing furnace is available in model sizes ranging from input
capacity of 60,000 to 120,000 Btuh as a direct vent (2-pipe)
application as well as a non-direct vent (1-pipe) application.
APPLICATIONS
!
CAUTION
PROPERTY DAMAGE
Failure to follow this caution may result in property damage.
Local codes may require a drain pan under entire furnace and
condensate trap when a condensing furnace is used in an attic
application or over a finished ceiling.
Step 1 -- General
Some assembly and modifications are required for furnaces
installed in any of the 4 applications shown in Fig. 1. All drain
353BAV
and pressure tubes are connected as shown in Fig. 6. See
appropriate application instructions for these procedures.
Step 2 -- Upflow Applications
In an upflow application, the blower is located below the burner
section, and conditioned air is discharged upwards.
CONDENSATE TRAP LOCATION
(FACTORY-SHIPPED ORIENTA
The condensate trap is factory installed in the blower shelf and
factory connected for UPFLOW applications. A factory-supplied
tube is used to extend the condensate trap drain connection to the
desired furnace side for field drain attachment. See Condensate
Trap Tubing (Factory-Shipped Orientation) section for drain tube
extension details. (See Fig. 5.)
TION)
CONDENSATE TRAP TUBING
(FACTORY-SHIPPED ORIENTA
NOTE: See Fig. 6 or tube routing label on main furnace door to
confirm location of these tubes.
1. Collector Box Drain, Inducer Housing Drain, Relief Port,
and Pressure Switch Tubes
These tubes should be factory attached to condensate trap
and pressure switch ready for use in upflow applications.
These tubes can be identified by their connection location
and also by a color label on each tube. These tubes are
identified as follows: collector box drain tube (blue label),
inducer housing drain tube (violet label or molded), relief
port tube (green label), and pressure switch tube (pink
label).
2. Condensate Trap Drain Tube
The condensate trap drain connection must be extended
for field attachment by doing the following:
f. Determine location of field drain connection. (See Fig.
2or6)
NOTE: If internal filter or side Filter/Media Cabinet is used,
drain tube should be located to opposite side of casing from
return duct attachment to assist in filter removal.
g. Remove and discard casing drain hole plug button
from desired side.
h. Install drain tube coupling grommet (factory-supplied
in loose parts bag) in selected casing hole.
i. Slide drain tube coupling (factory-supplied in loose
parts bag) through grommet ensuring long end of
coupling faces blower.
j. Cement 2 factory-supplied 1/2-in. street CPVC elbows to
the rigid drain tube connection on the condensate trap.
(See Fig. 6.) These elbows must be cemented together
and cemented to condensate trap drain connection.
TION)
8
Fig. 5 -- Condensate Trap
NOTE: Failure to use CPVC elbows may allow drain to kink
and prevent draining.
k. Connect larger diameter drain tube and clamp (factory
supplied in loose parts bag) to condensate trap and
clamp securely.
l. Route tube to coupling and cut to appropriate length.
m. Attach tube to coupling and clamp securely.
CONDENSATE TRAP LOCATION (ALTERNATE
UPFLOW ORIENTA
An alternate location for the condensate trap is the left-hand side
of casing. (See Fig. 2 and 7.)
NOTE: If the alternate left-hand side of casing location is used,
the factory-connected drain and relief port tubes must be
disconnected and modified for attachment. See Condensate Trap
Tubing (Alternate Upflow Orientation) section for tubing
attachment. To relocate condensate trap to the left hand side,
perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose
parts bag) into blower shelf hole where trap was removed.
TION)
A93026
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
Casing hole filler cap must be installed in blower shelf hole
when condensate trap is relocated to prevent combustion
productsbeingdrawninfromappliancesinthe
equipment room.
4. Install condensate trap into left-hand side casing hole by
inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler
caps (factory-supplied in loose parts bag).
CONDENSATE TRAP TUBING (ALTERNATE
UPFLOW ORIENTA
NOTE: See Fig. 7 or tube routing label on main furnace door to
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer
housing drain tube which was previously connected to
condensate trap.
b. Use inducer housing drain extension tube (violet label
and factory-supplied in loose parts bag) to connect
LOWER inducer housing drain connection to the
condensate trap.
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube
a. Connect relief port tube (green label) to
condensate trap.
b. Extend this tube (if required) by splicing to small
diameter tube (factory-supplied in loose parts bag).
c. Determine appropriate length, cut, and connect tube.
CONDENSATE TRAP FIELD DRAIN
ATT
ACHMENT
Refer to Condensate Drain section for recommendations
and procedures.
PRESSURE SWITCH TUBING
The LOWER collector box pressure tube (pink label) is factory
connected to the High Pressure Switch and should not require
any modification.
A01030
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
DRAIN TUBE (BLUE)
CONDENSATE
TRAP
INDUCER
HOUSING
DRAIN TUBE
(VIOLET)
A01031
Fig. 7 -- Alternate Upflow Configuration and Trap Location
NOTE: See Fig. 6 or 7 or tube routing label on main furnace
door to check for proper connections.
UPPER COLLECTOR BOX AND INDUCER
HOUSING (UNUSED) DRAIN
Upper Collector Box Drain Connection
Attached to the UPPER collector box drain connection is a
factory-installed corrugated, plugged tube (blue and white striped
label). This tube is plugged to prevent condensate leakage in this
application. Ensure this tube is plugged.
NOTE: See Fig. 6 or 7 or tube routing label on main furnace
door to check for proper connections.
Upper Inducer Housing Drain Connection
Attached to the UPPER (unused) inducer housing drain
connection is a cap and clamp. This cap is used to prevent
condensate leakage in this application. Ensure this connection
is capped.
NOTE: See Fig. 6 or 7 or tube routing label on main furnace
door to check for proper connections.
CONNECTIONS
CONDENSATE TRAP FREEZE PROTECTION
RefertoCondensateDrainProtectionsectionfor
recommendations and procedures.
Step 3 -- Downflow Applications
In a downflow furnace application, the blower is located above
the burner section, and conditioned air is discharged downwards.
CONDENSATE TRAP LOCATION
The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application
location as shown in Fig. 2, 8 or 9.
10
COLLECTOR BOX
DRAIN TUBE (BLUE)
CAP
PLUG
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
CONDENSATE
TRAP
INDUCER HOUSING
DRAIN TUBE (VIOLET)
DRAIN TUBE
COUPLING
PLUG
CAP
COLLECTOR BOX
DRAIN TUBE (BLUE)
COLLECTOR BOX
TUBE (PINK)
COLLECTOR BOX
TUBE (GREEN)
COLLECTOR BOX
EXTENSION TUBE
COLLECTOR BOX
DRAIN TUBE (BLUE
& WHITE STRIPED)
COLLECTOR BOX
EXTENSION TUBE
INDUCER HOUSING
DRAIN TUBE
(VIOLET)
CONDENSATE
TRAP
COLLECTOR BOX
EXTENSION
DRAIN TUBE
353BAV
A01023
Fig. 8 -- Downflow Tube Configuration
(Left-Hand Trap Installation)
To relocate condensate trap from the blower shelf to desired
location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
3. Remove casing hole filler cap from casing hole.
(See Fig.2, 8 or 9.)
4. Install casing hole filler cap into blower shelf hole where
trap was removed.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
Casing hole filler cap must be installed in blower shelf hole
when condensate trap is relocated to prevent combustion
productsbeingdrawninfromappliancesinthe
equipment room.
5. Install condensate trap into desired casing hole by
inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
CONDENSATE TRAP TUBING
NOTE: See Fig. 8 or 9 or tube routing label on main furnace
door to check for proper connections.
Relocate tubes as described below.
1. Collector Box Drain Tube
a. Remove factory-installed plug from LOWER collector
box drain tube (blue and white striped label).
A01024
Fig. 9 -- Downflow Tube Configuration
(Right-Hand Trap Installation)
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was connected to
condensate trap.
c. Connect LOWER collector box drain connection to
condensate trap.
(3.) Condensate Trap Located on Left Side of Casing
a. Connect LOWER collector box drain tube (blue
and white striped label) to condensate trap.
Tube does not need to be cut.
b. Clamp tube to prevent any condensate leakage.
(4.) Condensate Trap Located on Right Side of Casing
a. Install drain tube coupling (factory-supplied in
loose parts bag) into collector box drain tube
(blue and white striped label) which was
previously plugged.
b. Connectlargerdiameterdraintube
(factory-supplied in loose parts bag) to drain
tube coupling, extending collector box drain
tube for connection to condensate trap.
c. Route extended collector box drain tube
directly from collector box drain to condensate
trap as shown in Fig. 9.
d. Determine appropriate length and cut.
e. Connect to condensate trap.
f. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove factory-installed cap and clamp from LOWER
inducer housing drain connection.
11
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to
condensate trap.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
d. Use inducer housing drain tube (violet label and
factory-supplied in loose parts bag) to connect
LOWER inducer housing drain connection to the
condensate trap.
e. Connect inducer housing drain connection to
condensate trap.
(1.) Condensate Trap Located on Left Side of Casing
a. Determine appropriate length and cut.
b. Connect tube to condensate trap.
c. Clamp tube to prevent any condensate leakage.
(2.) Condensate Trap Located on Right Side of Casing
a. Route inducer housing drain tube (violet label)
directly from inducer housing to condensate
353BAV
3. Relief Port Tube Refer to Pressure Switch Tubing section
for connection procedure.
trap as shown in Fig. 9.
b. Determine appropriate length and cut.
c. Connect tube to condensate trap.
d. Clamp tube to prevent any condensate leakage.
CONDENSATE TRAP FIELD DRAIN
ATT
ACHMENT
Refer to Condensate Drain section for recommendations
and procedures.
PRESSURE SWITCH TUBING
One collector box pressure tube (pink label) is factory connected
to the High Pressure Switch for use when furnace is installed in
upflow applications. This tube MUST be disconnected and used
for the condensate trap relief port tube. The other collector box
pressure tube (green label) which was factory connected to the
condensate trap relief port connection MUST be connected to the
High Pressure Switch in DOWNFLOW or HORIZONTAL
RIGHT applications
NOTE: See Fig. 8 or 9 or tube routing label on main furnace
door to check for proper connections.
1. Disconnect collector box pressure tube (pink label)
attached to High Pressure Switch.
2. Extend collector box pressure tube (green label) which
was previously connected to condensate trap relief port
connectionbysplicingtosmalldiametertube
(factory-supplied in loose parts bag).
3. Connect collector box pressure tube (green label) to High
Pressure Switch connection labeled COLLECTOR BOX.
4. Extend collector box pressure tube (pink label) which was
previously connected to High Pressure Switch by splicing
to remaining small diameter tube (factory-supplied in
loose parts bag).
5. Route this extended tube (pink label) to condensate trap
relief port connection.
6. Determine appropriate length, cut, and connect tube.
7. Clamp tube to relief port connection.
CONDENSATE TRAP FREEZE PROTECTION
RefertoCondensateDrainProtectionsectionfor
recommendations and procedures.
Step 4 -- Horizontal Left (Supply-Air Discharge)
Applications
In a horizontal left furnace application, the blower is located to
the right of the burner section, and conditioned air is discharged
to the left.
CONDENSATE TRAP LOCATION
The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application
location as shown in Fig. 2 or 10.
To relocate condensate trap from the blower shelf to desired
location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose
parts bag) into blower shelf hole where trap was removed.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
Casing hole filler cap must be installed in blower shelf hole
when condensate trap is relocated to prevent combustion
productsbeingdrawninfromappliancesinthe
equipment room.
4. Install condensate trap into left-hand side casing hole by
inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler
caps (factory-supplied in loose parts bag).
CONDENSATE TRAP TUBING
NOTE: See Fig. 10 or tube routing label on main furnace door to
check for proper connections.
1. Collector Box Drain Tube
a. Install drain tube coupling (factory-supplied in loose
parts bag) into collector box drain tube (blue label)
which was previously connected to condensate trap.
b. Connect large diameter drain tube and clamp
(factory-supplied in loose parts bag) to drain tube
coupling, extending collector box drain tube.
c. Route extended tube (blue label) to condensate trap
and cut to appropriate length.
d. Clamp tube to prevent any condensate leakage.
2. Inducer Housing Drain Tube
a. Remove and discard LOWER (molded) inducer
housing drain tube which was previously connected to
condensate trap.
b. Use inducer housing drain extension tube (violet label
and factory-supplied in loose parts bag) to connect
LOWER inducer housing drain connection to the
condensate trap.
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
12
AUXILIARY "J" BOX
PLUG
CAP
COLLECTOR BOX
DRAIN TUBE
(BLUE AND WHITE STRIPED)
CONDENSATE
RELOCATE TUBE BETWEEN BLOWER SHELF AND INDUCER HOUSING FOR
TRAP
COLLECTOR
BOX EXTENSION
DRAIN TUBE
COLLECTOR BOX
EXTENSION TUBE
040, 060, AND 080 HEATING INPUT FURNACES
Fig. 10 -- Horizontal Left Tube Configuration
3. Relief Port Tube
a. Extend collector box tube (green label) which was
previously connected to the condensate trap by splicing
to small diameter tube (factory-supplied in loose parts
bag).
b. Route extended collector box pressure tube to relief
port connection on the condensate trap.
c. Determine appropriate length, cut, and connect tube.
d. Clamp tube to prevent any condensate leakage.
CONDENSATE TRAP FIELD DRAIN
ATT
ACHMENTS
Refer to Condensate Drain section for recommendations and
procedures.
PRESSURE SWITCH TUBING
The LOWER collector box pressure tube (pink label) is factory
connected to the High Pressure Switch for use when furnace is
installed in UPFLOW applications. This tube MUST be
disconnected, extended, rerouted, and then reconnected to the
pressure switch in HORIZONTAL LEFT applications for 060 and
080 heating input furnaces.
NOTE: See Fig. 10 or tube routing label on main furnace door to
check for proper connections.
Modify tube as described below:
1. Disconnect collector box pressure tube (pink label)
attached to High Pressure Switch.
2. Use smaller diameter tube (factory-supplied in loose parts
bag) to extend tube disconnected in item 1.
3. Route extended tube:
a. Behind inducer housing.
b. Between blower shelf and inducer housing.
DRAIN TUBE COUPLING
COLLECTOR BOX TUBE (PINK)
4. Determine appropriate length, cut, and reconnect tube to
HighPressureSwitchconnectionlabeled
COLLECTOR BOX.
CONDENSATE TRAP FREEZE PROTECTION
RefertoCondensateDrainProtectionsectionfor
recommendations and procedures.
CONSTRUCT A WORKING PLATFORM
Construct working platform where all required furnace clearances
are met. (See Fig. 3 and 11 or 12.)
!
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent
unit operation.
The condensate trap MUST be installed below furnace. See
Fig. 5 for dimensions. The drain connection to condensate trap
must also be properly sloped to an open drain.
NOTE:Combustion-air and vent pipes are restricted to a
minimum length of 5 ft. (1.5 M). (See Table 14.)
NOTE: A 12-in. (305 mm) minimum offset pipe section is
recommended with short (5 to 8 ft (1.5 to 2.4 M)) vent systems.
This recommendation is to reduce excessive condensate droplets
from exiting the vent pipe. (See Fig. 11, 12 or 43.)
Step 5 -- Horizontal Right (Supply-Air Discharge)
Applications
In a horizontal right furnace application, the blower is located to
the left of the burner section, and conditioned air is discharged to
the right.
COLLECTOR BOX
TUBE (GREEN)
INDUCER HOUSING
DRAIN TUBE (VIOLET)
COLLECTOR BOX
DRAIN TUBE (BLUE)
CAUTION
353BAV
A01029
13
COMBUSTION - AIR
5
3
/4″
INTAKE
(146 mm)
VENT
A 12-IN. (305 mm) MIN HORIZONTAL PIPE
SECTION IS RECOMMENDED WITH
SHORT (5 TO 8 FT / 1.5 TO 2.4 M) VENT
SYSTEMS TO REDUCE EXCESSIVE
CONDENSATE DROPLETS FROM
EXITING THE VENT PIPE.
30″ (762 mm)MIN
WORK AREA
353BAV
MANUAL
SHUTOFF
GAS VALVE
SEDIMENT
TRAP
CONDENSATE
TRAP
DRAIN
ACCESS OPENING
FOR TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING
FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
Fig. 11 -- Attic Location and Working Platform for Direct Vent (2-Pipe) Applications
!
CAUTION
PROPERTY DAMAGE
Failure to follow this caution may result in property damage.
Local codes may require a drain pan under entire furnace and
condensate trap when a condensing furnace is used in an attic
application or over a finished ceiling.
NOTE: The auxiliary junction box (J-Box) MUST be relocated
to opposite side of furnace casing. (See Fig. 13.) See Electrical
Connection section for J-Box relocation.
CONDENSATE TRAP LOCATION
The condensate trap must be removed from the factory-installed
blower shelf location and relocated in selected application
location as shown in Fig. 2 or 13.
To relocate condensate trap from the blower shelf to desired
location, perform the following:
1. Remove 3 tubes connected to condensate trap.
2. Remove trap from blower shelf by gently pushing tabs
inward and rotating trap.
3. Install casing hole filler cap (factory-supplied in loose
parts bag) into blower shelf hole where trap was removed.
A93031
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
Casing hole filler cap must be installed in blower shelf hole
when condensate trap is relocated to prevent combustion
productsbeingdrawninfromappliancesinthe
equipment room.
4. Install condensate trap into right-hand side casing hole by
inserting tube connection stubs through casing hole and
rotating until tabs snap into locking position.
5. Fill unused condensate trap casing holes with plastic filler
caps (factory-supplied in loose parts bag).
CONDENSATE TRAP TUBING
NOTE: See Fig. 13 or tube routing label on main furnace door to
check for proper connections.
1. Collector Box Drain Tube:
a. Remove factory-installed plug from LOWER collector
box drain tube (blue and white striped label).
b. Install removed clamp and plug into UPPER collector
box drain tube (blue label) which was previously
connected to condensate trap.
c. Connect LOWER collector box drain tube (blue and
white striped label) to condensate trap. Tube does not
need to be cut.
d. Clamp tube to prevent any condensate leakage.
14
A 3-IN.(76mm) MINIMUM CLEARANCE
TO COMBUSTION-AIR INTAKE
IS REQUIRED.
VENT
COMBUSTION AIR
GAS VALVE
INTAKE
MANUAL
SHUTOFF
30-IN. (762mm) MIN
3
5
/4 IN. (146mm)
SEDIMENT
TRAP
NOTE: LOCAL CODES MAY REQUIRE A DRAIN PAN UNDER THE
FURNACE AND CONDENSATE TRAP WHEN A CONDENSING
FURNACE IS INSTALLED ABOVE FINISHED CEILINGS.
CONDENSATE
TRAP
WORK AREA
DRAIN
A 12-IN. (305mm) MIN HORIZONTAL PIPE
SECTION IS RECOMMENDED WITH
SHORT (5 TO 8 FT / 1.5 TO 2.4M) VENT
SYSTEMS TO REDUCE EXCESSIVE
CONDENSATE DROPLETS FROM
EXITING THE VENT PIPE.
ACCESS OPENING
FOR TRAP
Fig. 12 -- Attic Location and Working Platform for Non-Direct Vent (1-pipe) Applications
353BAV
A96184
2. Inducer Housing Drain Tube:
a. Remove factory-installed cap and clamp from LOWER
inducer housing drain connection.
b. Remove and discard UPPER (molded) inducer housing
drain tube which was previously connected to
condensate trap.
c. Install cap and clamp on UPPER inducer housing drain
connection where molded drain tube was removed.
d. Use inducer housing drain extension tube (violet label
and factory-supplied in loose parts bag) to connect
LOWER inducer housing drain connection to
condensate trap.
e. Determine appropriate length, cut, and connect tube to
condensate trap.
f. Clamp tube to prevent any condensate leakage.
3. Relief Port Tube:
Refer to Pressure Switch Tubing section for connection
procedure.
CONDENSATE TRAP FIELD DRAIN ATTACHMENT
Refer to Condensate Drain section for recommendations
and procedures.
PRESSURE SWITCH TUBING
One collector box pressure tube (pink label) is factory connected
to the High Pressure Switch for use when furnace is installed in
UPFLOW applications. This tube MUST be disconnected and
used for the condensate trap relief port tube. The other collector
box pressure tube (green label) which was factory connected to
the condensate trap relief port connection MUST be connected to
the High Pressure Switch in DOWNFLOW or HORIZONTAL
RIGHT applications.
NOTE: See Fig. 12 or tube routing label on main furnace door
to check for proper connections.
Relocate tubes as described below.
1. Disconnect collector box pressure tube (pink label)
attached to High Pressure Switch.
2. Extend collector box pressure tube (green label) which
was previously connected to condensate trap relief port
connectionbysplicingtosmalldiametertube
(factory-supplied in loose parts bag).
3. Connect collector box pressure tube (green label) to High
Pressure Switch connection labeled COLLECTOR BOX.
4. Use remaining smaller diameter tube (factory-supplied in
loose parts bag) to extend collector box pressure tube
(pink label) which was previously connected to High
Pressure Switch. Route this extended tube (pink label) to
condensate trap relief port connection.
5. Determine appropriate length, cut, and connect tube.
6. Clamp tube to relief port connection.
CONDENSATE TRAP FREEZE PROTECTION
RefertoCondensateDrainProtectionsectionfor
recommendations and procedures.
CONSTRUCT A WORKING PLATFORM
Construct working platform where all required furnace clearances
are met. (See Fig. 3 and 11 or 12.)
15
PLUG
CAP
COLLECTOR BOX DRAIN TUBE (BLUE)
COLLECTOR BOX TUBE (GREEN)
COLLECTOR BOX EXTENSION TUBE
COLLECTOR BOX TUBE (PINK)
AUXILARY “J” BOX RELOCATED HERE
353BAV
COLLECTOR BOX DRAIN TUBE
(BLUE AND WHITE STRIPED)
INDUCER HOUSING
DRAIN TUBE (VIOLET)
COLLECTOR BOX
EXTENSION TUBE
Fig. 13 -- Horizontal Right Tube Configuration
!
CAUTION
UNIT OPERATION HAZARD
Failure to follow this caution may result in intermittent
unit operation.
The condensate trap MUST be installed below furnace. See
Fig. 5 for dimensions. The drain connection to condensate
trap must also be properly sloped to an open drain.
NOTE: Combustion-air pipe (when applicable) and vent pipe(s)
are restricted to a minimum length of 5 ft (1.5 M). (See Table 11.)
NOTE: A 12-in. (305 mm) minimum offset pipe section is
recommended with short (5 to 8 ft (1.5 to 2.4 M)) vent systems.
This recommendation is to reduce excessive condensate droplets
from exiting the vent pipe. (See Fig. 11, 12 or 43.)
LOCATION
Step 1 -- General
This furnace must
S be installed so the electrical components are protected from water.
S not be installed directly on any combustible material other than
wood flooring (refer to SAFETY CONSIDERATIONS).
S be located so combustion-air and vent pipe maximum lengths
are not exceeded. Refer to Table 11.
S be located where available electric power and gas supplies
meet specifications on the furnace rating plate.
S be attached to an air distribution system and be located as close
to the center of the distribution system as possible. Refer to Air
Ducts section.
S be provided with ample space for servicing and cleaning.
Always comply with minimum fire protection clearances
CONDENSATE
TRAP
A01028
shown on the furnace clearance to combustibles label.
NOTE: For upflow/downflow applications install furnace so that
it is level or pitched forward within 1/2-in. (13 mm) for proper
furnace operation. For horizontal applications pitch 1/4-in. (6
mm) minimum to 1/2-in. (13 mm) maximum forward to ensure
proper condensate drainage from secondary heat exchangers.
(See Fig. 14.)
When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing the
furnace, return air must also be handled by ducts sealed to
furnace casing. The ducts terminate outside the space containing
the furnace to ensure a negative pressure condition will not occur
within equipment room or space.
!
WARNING
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in property damage,
personal injury, or death.
Do not install furnace on its back. (See Fig. 15.) Safety control
operation will be adversely affected. Never connect return-air
ducts to back of furnace.
LEVEL (0”)
TO 1/2” (13mm)
MAX
UPFLOW OR DOWNFLOW
FRONTFRONT
MIN 1/4” (7mm)
TO 1/2” (13mm)
MAX
Fig. 14 -- Proper Condensate Drainage
HORIZONTAL
A02146
16
!
CAUTION
UNIT DAMAGE HAZARD
Failure to follow this caution may result in property or unit
damage.
This gas furnace may be used for construction heat provided that:
--The furnace is permanently installed with all electrical
wiring, piping, air filters, venting and ducting installed
according to these installation instructions. A return air duct
is provided, sealed to the furnace casing, and terminated
outside the space containing the furnace. This prevents a
negative pressure condition as created by the circulating air
blower, causing a flame rollout and/ or drawing combustion
products into the structure.
--The furnace is controlled by a thermostat. It may not be “hot
wired” to provide heat continuously to the structure without
thermostatic control.
--Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and other
construction materials. It also prevents the entrainment of
drywall dust into combustion air, which can cause fouling
and plugging of furnace components.
--The temperature of the return air to the furnace is
maintained between 55°F(13°C) and 80°F(27°C), with no
evening setback or shutdown. The use of the furnace while
the structure is under construction is deemed to be
intermittent operation per our installation instructions.
--The air temperature rise is within the rated rise range on the
furnace rating plate, and the firing rate has been set to the
nameplate value.
--The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
--The furnace, ductwork and filters are cleaned as necessary
to remove drywall dust and construction debris from all
HVAC system components after construction is completed.
-- After construction is complete, verify furnace operating
conditions including ignition, input rate, temperature rise and
venting, according to the manufacturer’s instructions.
!
CAUTION
FRONT
B
A
C
K
BACK
FRONT
A93043
Fig. 15 -- Prohibit Installation on Back
Step 3 -- Hazardous Locations
!
WARNING
FIRE, EXPLOSION, INJURY OR DEATH HAZARD
Failure to follow this warning could result in personal injury,
or death or property damage.
When the furnace is installed in a residential garage, the
burners and ignition sources must be located at least 18 in.
(457 mm) above the floor. The furnace must be located or
protected to avoid physical damage by vehicles. When the
furnace is installed in a public garage, airplane hangar, or other
building having a hazardous atmosphere, the furnace must be
installed in accordance with the NFGC or NSCNGPIC. (See
Fig. 17.)
Step 4—Furnace Location and Application
DIRECT VENT (2-PIPE) APPLICATION
Furnace may be located in a confined space without special
provisions for dilution or ventilation air.
353BAV
UNIT DAMAGE HAZARD
Failure to follow this caution may result in property or unit
damage.
If this furnace is installed in an unconditioned space where
the ambient temperatures may be 32°F(0°C) or lower, freeze
protection measures must be taken. (See Fig. 16.)
Step 2 -- Furnace Location Relative to Cooling
Equipment
The cooling coil must be installed parallel with or on downstream
side of furnace to avoid condensation in heat exchanger. When
installed parallel with a furnace, dampers or other means used to
control flow of air shall be adequate to prevent chilled air from
entering furnace. If dampers are manually operated, they must be
equipped with a means to prevent operation of either unit unless
the damper is in full-heat or full-cool position.
A07911
Fig. 16 -- Freeze Protection
17
18-IN. (457.2 mm)
MINIMUM TO BURNERS
Fig. 17 -- Installation in a Garage
NON-DIRECT VENT (1-PIPE) APPLICATION
!
CAUTION
353BAV
UNIT DAMAGE HAZARD
Failure to follow this caution may result in intermittent
unit operation.
Do not install furnace in a corrosive or contaminated
atmosphere. Make sure all combustion and circulating air
requirements are met.
Refer to the AIR FOR COMBUSTION AND VENTILATION
section for details.
AIR FOR COMBUSTION AND
VENTILATION
Provisions for adequate combustion, ventilation, and dilution air
must be provided in accordance with:
S U.S. Installations: Section 9.3 NFPA 54/ANSI Z223.1--2009,
Air for Combustion and Ventilation and applicable provisions
of the local building codes.
S Canadian Installations: Part 8 of CAN/CS----B149.1--05.
Venting Systems and Air Supply for Appliances and all
authorities having jurisdiction.
!
WARNING
FURNACE CORROSION HAZARD
Failure to follow this warning could result in reduced furnace
component life.
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements could corrode heat exchangers and
shorten furnace life. Air contaminants are found in aerosol
sprays, detergents, bleaches, cleaning solvents, salts, air
fresheners, and other household products.
The following types of furnace installations may require
OUTDOOR AIR for combustion due to chemical exposures:
S Commercial buildings
S Buildings with indoor pools
S Laundry rooms
S Hobby or craft rooms, and
S Chemical storage areas
If air is exposed to the following substances, it should not be
used for combustion air, and outdoor air may be required
for combustion:
S Permanent wave solutions
S Chlorinated waxes and cleaners
A93044
S Chlorine based swimming pool chemicals
S Water softening chemicals
S De-icing salts or chemicals
S Carbon tetrachloride
S Halogen type refrigerants
S Cleaning solvents (such as perchloroethylene)
S Printing inks, paint removers, varnishes, etc.
S Hydrochloric acid
S Cements and glues
S Antistatic fabric softeners for clothes dryers
S Masonry acid washing materials
All fuel-burning equipment must be supplied with air for fuel
combustion. Sufficient air must be provided to avoid negative
pressure in the equipment room or space. A positive seal must be
made between the furnace cabinet and the return-air duct to
prevent pulling air from the burner area and from draft
safeguard opening.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in personal injury
or death.
The operation of exhaust fans, kitchen ventilation fans, clothes
dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make-up air MUST be provided for the ventilation devices, in
addition to that required by the furnace. Refer to the Carbon
Monoxide Poisoning Hazard warning in the venting section of
these instructions to determine if an adequate amount of
make-up air is available.
The requirements for combustion and ventilation air depend upon
whether or not the furnace is located in a space having a volume
of at least 50 cubic feet per 1,000 Btuh input rating for all gas
appliances installed in the space.
S Spaces having less than 50 cubic feet per 1,000 Btuh require
the OUTDOOR COMBUSTION AIR METHOD.
S Spaces having at least 50 cubic feet per 1,000 Btuh may use
the INDOOR COMBUSTION AIR, STANDARD or
KNOWN AIR INFILTRATION METHOD.
Outdoor Combustion Air Method
1. Provide the space with sufficient air for proper
combustion, ventilation, and dilution of flue gases using
permanent horizontal or vertical duct(s) or opening(s)
directly communicating with the outdoors or spaces that
freely communicate with the outdoors.
2. Fig. 18 illustrates how to provide TWO OUTDOOR
OPENINGS, one inlet and one outlet combustion and
ventilation air openings to the outdoors.
a. One opening MUST commence within 12 in. (305
mm) of the ceiling and the second opening MUST
commence within 12 in. (305 mm) of the floor.
b. Size openings and ducts per Fig. 18 and Table 1.
c. TWO HORIZONTAL DUCTS require 1 square inch of
free area per 2,000 Btuh (1,100 mm
input for all gas appliances in the space per Fig. 18 and
Tab le 1 .
d. TWO OPENINGS OR VERTICAL DUCTS require 1
square inch of free area per 4,000 Btuh (550 mm
for combined input of all gas appliances in the space
per Fig. 18 and Table 1.
3. ONE OUTDOOR OPENING requires:
a. 1 square inch of free area per 3,000 Btuh (734 mm
for combined input of all gas appliances in the space
per Table 1 and 11.
2
/kW) of combined
2
/kW)
2
/kW)
18
Ta bl e 1 – Minimum Free Area Required for Each Combustion Air Opening or Duct to Outdoors
100,000+40,000= (140,000 divided by 4,000)= 35.0 Sq. In. for each two Vertical Ducts or Openings
60,000+40,000= (100,000 divided by 3,000)= 33.4 Sq. In. for a Single Duct or Opening
80,000+30,000= (110,000 divided by 2,000)= 55.0 Sq. In. for each of two Horizontal Ducts
Ta bl e 2 – Minimum Space Volumes for 100% Combustion, Ventilation and Dilution Air from Outdoors
In. (mm) Dia
353BAV
OTHER THAN FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
ACH
0.60
0.50
0.40
0.30
0.20
0.10
0.00NPNPNPNPNPNPNPNPNP
b. Not less than the sum of the areas of all vent
connectors in the space.
304050446688110132154
SpaceVolumeFt3(M3)
1,050
(29.7)
1,260
(35.6)
1,575
(44.5)
2,100
(59.4)
3,150
(89.1)
6,300
(178.3)
1,400
(39.6)
1,680
(47.5)
2,100
(59.4)
2,800
(79.2)
4,200
(118.9)
8,400
(237.8)
1,750
(49.5)
2,100
(59.4)
2,625
(74.3)
3,500
(99.1)
5,250
(148.6)
10,500
(297.3)
1,100
(31.1)
1,320
(37.3)
1,650
(46.7)
2,200
(62.2)
3,300
(93.4)
6,600
(186.8)
1,650
(46.7)
1,980
(56.0)
2,475
(70.0)
3,300
(93.4)
4,950
(140.1)
9,900
(280.3)
The Standard Method:
1. The space has no less volume than 50
The opening shall commence within 12 in. (305 mm)
of the ceiling. Appliances in the space shall have
clearances of at least 1 in. (25 mm) from the sides and
back and 6 in. (153 mm) from the front. The opening
shall directly communicate with the outdoors or shall
communicate through a vertical or horizontal duct to
the outdoors or spaces (crawl or attic) that freely
communicate with the outdoors.
Indoor Combustion AirE NFPA & AGA
Standard and Known-Air-Infiltration Rate Methods
Indoor combustion air is permitted for combustion, ventilation,
and dilution, if the Standard or Known-Air-Infiltration Rate
Method is used.
!
WARNING
CARBON MONOXIDE POISONING HAZARD
Failure to follow this warning could result in death and/or
2. The air infiltration rate is not known to be less than 0.40
The Known Air Infiltration Rate Method shall be used, if the
infiltration rate is known to be:
1. Less than 0.40 ACH and
2. Equal to or greater than 0.10 ACH
Infiltration rates greater than 0.60 ACH shall not be used. The
minimum required volume of the space varies with the number of
ACH and shall be determined per Table 2 or Equations 1 and 2.
Determine the minimum required volume for each appliance in
the space and add the volumes together to get the total minimum
required volume for the space.
Table 2 -- Minimum Space Volumes were determined by using the
following equations from the National Fuel Gas Code ANSI
Z223.1--2009/NFPA 54--2009,9.3.2.2:
FAN-ASSISTED TOTAL
(1,000’S BTUH GAS INPUT RATE)
2,200
(62.2)
2,640
(74.7)
3,300
(93.4)
4,400
(124.5)
6,600
(186.8)
13,200
(373.7)
2,750
(77.8)
3,300
(93.4)
4,125
(116.8)
5,500
(155.7)
8,250
(233.6)
16,500
(467.2)
3,300
(93.4)
3,960
(112.1)
4,950
(140.1)
6,600
(186.8)
9,900
(280.3)
19,800
(560.6)
3
ft. (1.43M) (per
1,000 Btuh of the maximum input ratings for all gas
appliances installed in the space and
air changes per hour (ACH).
personal injury.
Many homes require air to be supplied from outdoors for
furnace combustion, ventilation, and dilution of flue gases.
The furnace combustion air supply must be provided in
accordance with this instruction manual.
3,850
(109.0)
4,620
(130.8)
5,775
(163.5)
7,700
(218.0)
11,550
(327.0)
23,100
(654.1)
19
Loading...
+ 43 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.