The 310AAV/JAV 4-Way Multipoise Gas Furnace was designed by Bryant
dealers for Bryant dealers. Applications are easy with 4-way multipoise
design, through-the-furnace downflow venting, 13 different venting options,
and a door designed for easy service access. An inner blower door is
provided for tighter sealing in sensitive applications. The 310AAV/JAV
furnace is approved for use with natural or propane gas, and the 310JAV is
also approved for use in Low NOx Air Quality Management Districts.
STANDARD FEATURES
• Noise elimination combustion system
• Microprocessor based control center
Adjustable heating air temperature rise
LED diagnostics and self test feature
• Patented blocked vent safeguard to ensure proper furnace venting
• All models are Chimney Friendly when used with accessory vent kit
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 4
Tab 6a 8a
PC 101Catalog No. See CoverPrinted in U.S.A.Form 58ST-11SIPg 112-02Replaces: 58ST-2SI
33-5/16"
28-7/8"
25-1/4"
22-9/16"
JUNCTION BOX
LOCATION
7/8" DIA
ACCESSORY
1/2" DIA THERMOSTAT
WIRE ENTRY
3-15/16"
LEFT HAND GAS
ENTRY
7/8" DIA. ACCESSORY
24-7/8"
4-13/16"
8-7/16"
1-7/16"
ALTERNATE
VENT OUTLET
3-3/4"
1-9/16"
2-9/16"
A
D
13/16"
F
JUNCTION BOX
LOCATION (TYP)
5 PLACES (TYP)
AIRFLOW
19"
OUTLET
1-1/2" DIA.
RIGHT HAND
GAS ENTRY
1/2" DIA. THERMOSTAT
WIRE ENTRY
7/8" DIA. ACCESSORY
13/16"
11/16"
14-7/8"
11/16"
NOTES:
1. Two additional 7/8-in. diameter holes are located in the top plate.
2. Minimum return-air openings ar furnace, based on metal duct. If flex duct is used, see flex duct manufacturer’s recommendations for equivalent diameters.
a. For 800 CFM-16-in. round or 14 1/2 x 12-in. rectangle.
b. For 1200 CFM-20-in. round or 14 1/2 x 19 1/2-in. rectangle.
c. For 1600 CFM-22-in. round or 14 1/2 x 22-in. rectangle.
d. For airflow requirements above 1800 CFM, see Air Delivery table in Product Data literature for specific
use of single side inlets. The use of both side inlets, a combination of 1 side and the bottom, or the
bottom only will ensure adequate return air openings for airflow requirements above 1800 CFM.
21-5/8"
BOTTOM INLET
1-11/16"
5-1/2"
E
11/16"
22-1/16"
SIDE INLET
1-1/4"
1"
→ Fig. 1—Dimensional Drawing
SAFETY CONSIDERATIONS
Sheet metalparts may have sharp edgesor burrs. Use care and
Improper installation, adjustment, alteration, service, maintenance, or use can cause carbon monoxide poisoning, explosion, fire, electrical shock, or other conditions which may
cause personal injury or property damage. Consult a qualified
installer, service agency, local gas supplier, or your distributor or branch for information or assistance. The qualified
installer or agency must use only factory-authorized and
listed kitsor accessories whenmodifying this product. Failure
to follow this warning could result in electrical shock, fire,
personal injury, or death.
Application of this furnace should be indoors with special
→
attention given to vent sizing and material, gas input rate, air
temperature rise, unit leveling, and unit sizing. Improper
installation or misapplication of furnace can require excessive
servicing or cause premature component failure.
Installing andservicing heating equipment can be hazardous due to
→
gas and electrical components. Only trained and qualified
personnel should install, repair, or service heating equipment.
Untrained personnel can perform basic maintenance functions
such as cleaning and replacing air filters. All other operations must
be performed by trained service personnel. When working on
heating equipment, observe precautions in literature, on tags, and
on labels attached to or shipped with unit and other safety
precautions that may apply.
These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residential construction practices. We require these instructions as a
minimum for a safe installation.
wear appropriate protective clothing and gloves when handling parts. Failure to follow this caution could result in
personal injury.
Wear safety glasses and work gloves. Have fire extinguisher
available during start-up and adjustment procedures and service
calls.
This is the safety-alert symbol
. When you see this symbol on
the furnace and in instructions or manuals, be alert to the potential
for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which will result in
severe personal injury or death. WARNING signifies a hazard
which could result in personal injury or death. CAUTION is used
to identify unsafe practices which would result in minor personal
injury or product and property damage. NOTE is used to highlight
suggestions which will result in enhanced installation, reliability,
or operation.
1. Use only with type of gas approved for this furnace. Refer to
the furnace rating plate.
2. Install this furnace only in a location and position as specified
in the “Location” section of these instructions.
3. Provide adequate combustionand ventilation airto the furnace
space as specified in “Air for Combustion and Ventilation”
section.
4. Combustion products must be discharged outdoors. Connect
this furnace to an approved vent system only, as specified in
the “Venting” section of these instructions.
5. Never test for gas leaks with an open flame. Use a commercially available soap solution made specifically for the detection of leaks to check all connections, as specified in the “Gas
Piping” section.
A02304
2
INSTALLATION
MINIMUM INC HES CLEARANCE TO COMBUSTIBLE CONSTRUCTION
DISTANCE MINIMALE EN POUCES AUX CONSTRUCTIONS COMBUSTIBLES
This forced air furnace is equipped for use with
natural gas at altitudes 0-10,000 ft (0-3,050m).
An accessory kit, supplied by the
manufacturer,shall be used to convert to propane
gas use or may be required for some natural gas
applications.
This furnace is for indoor installation in a
building constructed on site.
This furnace is appro ved for UPFLOW, DOWNFLOW, and
HORIZONTAL installations.
Cette fournaise est approuvée pour l´inst alla tio n H O R IZ ONTAL E
et la circulation d´air VER S LE HA U T et VERS LE BAS.
Les fléches de dégagement
Clearance arrows
do not change with
furnace orientation.
1"
ne changent pas avec
l´orientation de la fournaise.
This furnace may be installed on com bustible
floori ng i n alcove or closet at mini mum clearance
as indicated by the diagram from combustible
mate rial .
This furnace may be used w ith a Type B-1 Ven t
and may be vented i n commo n wit h other gasfired appliances .
Cette fournaise à air pulsé est équipée
pour utilisation avec gaz naturel et altitudes
comprises entre 0-3,050m (0-10,000 pi).
Utili ser une trousse de conversion, fournie par
le fabri cant, pour passer au gaz propane ou pour
certaines installations au gaz naturel.
0"
0"
*
B
A
A
C
R
K
R
I
È
R
E
E
D
I
S
É
T
Ô
C
TOP / PLENUM
U
F
F
DESSUS / CHAMBRED’AIR
E
C
E
A
S
N
I
A
R
N
R
U
O
T
N
O
T
R
N
F
A
V
A
F
A
E
R
O
N
V
T
A
N
T
3"
MIN
Ø
Cette fournaise est prévue pour être
installée dans un bâtiment construit sur place.
Cette fournaise peut être installée sur
un plancher combustible dans une alcôve ou
dans un garde-robe en respectant le minimum
d'espace libre des matériaux combustibles, tel
qu'indiqué sur le dia gramm e ..
Cette fournaise peut être utilisée avec un
conduit d´évacuation de Type B-1 ou conn ectée
au conduit commu n d´autres appareils à gaz..
BOTTOM
DESSOUS
"
0
†
Vent C learance to combustibles:
For Single Wall vents 6 inches (6 po).
For Type B-1 vent type 1 inch (1 po).
Dégagement de l´évent avec combu stibles:
Pour conduit d´évacuation à paroi simple 6 po (6 in c h e s ).
Pour conduit d´évacuation de Type B-1 1 po (1 inch).
Clearance in inches
Dégagem ent (po).
MINIMUM INCHES CLEARA NCE TO COM BUSTIBLE CONSTRUCTION
DOWNFLOW POSITIONS:
Installation on non-com bus tible floors only.
†
For Installation on combustible flooring only when installed on special base, Part No . KGASB0201ALL,
Co il Assem b ly , Part No. CD5 o r CK5, or Coil Cas in g , Part No . KCA KC.
18 inches front clearance required for alcove.
Ø
Indicates supply or return sides when furnace is in the horizontal position. Line contact only permissible
*
between lines formed by intersections of the T op and two Sides of the furnace jacket, and building joists,
studs or framing.
DÉGAGE MENT MINIMUM EN POUCES AVEC ÉLÉMENTS
DE CONSTRUCTION COM BUSTIB LES
POUR LA POSITION COURANT DESCENDANT:
Pour l´installation sur plancher non com b ustible seulement.
†
Pour l´installation sur un plancher combustible seulement quand on utilise la base sp éciale, pièce
o
n KGASB 02 0 1 AL L , l ´ensemble serpentin, pièce n CD5 ou CK5, ou le carter de serpentin, pièce
o
n KCAKC .
Dans une alcôve, on doit maintenir un dégagem ent à l´avant de 18 po (450 mm).
Ø
La position indiquée concerne le côté d´entrée ou de retour quand la fournaise est dans la
*
position horizo ntale.
Le contact n´est permis qu´entre les lignes formées par les intersections du dessus et des
deux côtés de la chem ise de la fournaise et les solives, montant sous cadre de charpente.
→ Fig. 2—Clearances to Combustibles
o
327590-101 REV. B
0"
E
D
*
I
È
S
T
Ô
C
S
E
R
N
V
I
T
R
C
E
E
T
I
E
N
30"
MIN
A02330
6. Always install furnace to operate within the furnace’s intended
temperature-rise range with a duct system which has an
external static pressure within the allowable range, as specified in the “Start-Up, Adjustments, and Safety Check” section.
See furnace rating plate.
7. When a furnace is installed so that supply ducts carry air
circulated by the furnace to areas outside the space containing
the furnace, the return air shall also be handled by duct(s)
sealed to the furnace casing and terminating outside the space
containing the furnace. See “Air Ducts” section.
8. A gas-fired furnacefor installation ina residential garage must
be installed as specified in the warning box in the “Location”
section.
9. The furnace is not to be used for temporary heating of
buildings or structures under construction.
10. These Multipoise Gas-Fired Furnaces are CSA (A.G.A. and
→
C.G.A.) design-certified for natural and propane gases (see
furnace rating plate) and for installation in alcoves, attics,
basements, closets, utility rooms, crawlspaces, and garages.
The furnace is factory-shipped for use with natural gas. A
*5” or 6” vent connector may be required in some cases.
CSA (A.G.A. and C.G.A.) listed gas conversion kit is required
to convert furnace for use with propane gas.
→
11. See Fig. 2 for required clearances to combustibles.
→
12. Maintain a 1-in. clearance from combustible materials to
supply air ductwork for a distance of 36 inches horizontally
from the furnace. See NFPA 90B or local code for further
requirements.
13. These furnaces SHALL NOT be installed directly on carpet-
→
ing, tile, or any other combustible material other than wood
flooring. In downflow installations, factory accessory floor
base MUST be used when installed on combustible materials
and wood flooring. Special base is not required when this
furnace is installed on manufacturer’s Coil Assembly Part No.
CD5 or CK5, or when Coil Box Part No. KCAKC is used.
INTRODUCTION
This 4–way multipoise Category I fan-assisted furnace is CSA
→
(A.G.A. and C.G.A.) design-certified for natural and propane gas
and for installation in alcoves, attics, basements, closets, utility
rooms, crawlspaces, and garages. A fan-assisted furnace is an
appliance equipped with an integral mechanical means to either
draw or force products of combustion through the combustion
chamber and/or heat exchanger. The furnace is factory-shipped for
use with natural gas. A CSA (A.G.A. and C.G.A.) listed gas
conversion kit is required to convert furnace for use with propane
gas. This furnace is not approved for installation in mobile homes,
recreational vehicles, or outdoors.
This furnace is designed for minimum continuous return-air
temperature of 60°F db or intermittent operation down to 55°Fdb
such as when used with a night setback thermostat. Return-air
temperature must not exceed 85°F db. Failure to follow these
return-air limits may affect reliability of heat exchangers, motors,
and controls. (See Fig. 3.)
For accessoryinstallation details, referto the applicable instruction
literature.
NOTE: Remove all shipping brackets and materials before operating the furnace.
other codes. In absence of local codes, the installation must
comply with the national codes listed below and all authorities
having jurisdiction.
In the United States and Canada, follow all codes and standards for
the following:
Step 1—Safety
• US: National Fuel Gas Code (NFGC) NFPA 54–2002/ANSI
Z223.1–2002 and the Installation Standards,Warm Air Heating
and Air Conditioning Systems ANSI/NFPA 90B
• CANADA: CAN/CGA-B149.1–and .2–M00 National Standard
of Canada. Natural Gas and Propane Installation Codes (NSCNGPIC)
Step 2—General Installation
• US: Current edition of the NFGC and the NFPA 90B. For
copies, contact the National Fire Protection Association Inc.,
Batterymarch Park, Quincy, MA 02269; or for only the NFGC,
contact the American Gas Association, 400 N. Capitol, N.W.,
Washington DC 20001 or www.NFPA.org.
• CANADA: NSCNGPIC. For a copy, contact Standard Sales,
Follow allnational and local codes andstandards in addition to
these instructions. The installation must comply with regulations
of the serving gas supplier, local building, heating, plumbing, and
onto), Ontario, M9W 1R3 Canada
Step 3—Combustion and Ventilation Air
• US: Section 5.3 of the NFGC, Air for Combustion and
Ventilation
VENT
CONN*
4
SHIP WT. (LB)
60
A02055
THE BLOWER IS LOCATED
TO THE RIGHT OF THE
BURNER SECTION, AND
AIR CONDITIONED AIR IS
DISCHARGED TO THE LEFT .
THE BLOWER IS
LOCATED BELOW THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED UPWARD.
THE BLOWER IS
LOCATED ABOVE THE
BURNER SECTION, AND
CONDITIONED AIR IS
DISCHARGED DOWNWARD
Fig. 4—Multipoise Orientations
• CANADA: Part 7 of NSCNGPIC, Venting Systems and Air
Supply for Appliances
Step 4—Duct Systems
• US and CANADA: Air Conditioning Contractors Association
(ACCA) Manual D, Sheet Metal and Air Conditioning Contractors National Association (SMACNA), or American Society of Heating, Refrigeration, and Air Conditioning Engineers
(ASHRAE) 2001 Fundamentals Handbook Chapter 34.
Step 5—Acoustical Lining and Fibrous Glass Duct
• US and CANADA: current edition of SMACNA and NFPA
90B as tested by UL Standard 181 for Class I Rigid Air Ducts
Step 6—Gas Piping and Gas Pipe Pressure Testing
• US: NFGC; chapters 5, 6, 7, and 12 and National Plumbing
Codes
→
• CANADA: NSCNGPIC Parts 3, 4, 5, A, B, E and H.
Step 7—Electrical Connections
• US: National Electrical Code (NEC) ANSI/NFPA 70–2002
• CANADA: Canadian Electrical Code CSA C22.1
→
ELECTROSTATIC DISCHARGE (ESD) PRECAUTIONS
Electrostatic discharge can affect electronic components.
Take precautions during furnace installation and servicing to
protect the furnace electronic control. Precautions will prevent electrostatic discharges from personnel and hand tools
which are held during the procedure. These precautions will
help to avoid exposing the control to electrostatic discharge
by putting the furnace, the control, and the person at the same
electrostatic potential.
PROCEDURE
THE BLOWER IS
LOCA TED T O THE LEFT
OF THE BURNER SECTION,
AND CONDITIONED AIR IS
DISCHARGED TO THE RIGHT .
A02097
NOT move or shuffle your feet, do not touch ungrounded
objects, etc.).
4. If you touch ungrounded objects (and recharge your body with
static electricity), firmly touch a clean, unpainted metal
surface of the furnace again before touching control or wires.
5. Use this procedure for installed and uninstalled (ungrounded)
furnaces.
6. Before removing a new control from its container, discharge
your body’s electrostatic charge to ground to protect the
control from damage. If the control is to be installed in a
furnace, follow items 1 through 4 before bringing the control
or yourself in contact with the furnace. Put all used and new
controls into containers before touching ungrounded objects.
7. An ESD service kit (available from commercial sources) may
also be used to prevent ESD damage.
LOCATION
Step 1—General
Some assembly and modifications are required when used in any
of the four applications shown in Figure 4.
This furnace must:
• be installed so the electrical components are protected from
water.
• not be installed directly on any combustible material other than
wood flooring. Refer to Introduction section.
• be located close to the chimney/vent and attached to an air
distribution system. Refer to Air Ducts section.
• be provided ample space for servicing and cleaning. Always
comply with minimum fire protection clearances shown on the
furnace clearance to combustible label.
1. Disconnect all power to the furnace. Multiple disconnects may
be required. DO NOT TOUCH THE CONTROL OR ANY
WIRE CONNECTED TO THE CONTROL PRIOR TO DISCHARGING YOUR BODY’S ELECTROSTATIC CHARGE
TO GROUND.
2. Firmly touch theclean, unpainted, metalsurface of the furnace
chassis which is close to the control. Tools held in a person’s
hand during grounding will be satisfactorily discharged.
3. After touching the chassis, you may proceed to service the
control or connecting wires as long as you do nothing to
recharge your body with static electricity (for example; DO
Do not install furnace in a corrosive or contaminated atmosphere. Make sure all combustion and circulating air requirements are met, in addition to all local codes and ordinances.
5
This gas furnace may be used for construction heat provided
that:
-The furnace is permanently installed with all electrical
wiring, piping, venting and ducting installed according to
these installation instructions. A return air duct is provided,
sealed to the furnace casing, and terminated outside the space
containing the furnace. This prevents a negative pressure
condition as created by the circulating air blower, causing a
flame rollout and/or drawing combustion products into the
structure.
-The furnace is controlled by a thermostat. It may not be ″hot
wired″ to provide heat continuously to the structure without
thermostatic control.
-Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and other
construction materials. It also prevents the entrainment of
drywall dustinto combustion air, which can cause fouling and
plugging of furnace components.
-The temperature of the return air to the furnace is no less
than 55 degrees F, with no evening setback or shutdown. The
use of the furnace while the structure is under construction is
deemed to be intermittent operation per our installation
instructions.
-The air temperature rise is within the rated rise range on the
furnace rating plate, and the firing rate has been set to the
nameplate value.
-The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
-The furnace, ductwork and filters are cleaned as necessary to
remove drywall dust and construction debris from all HVAC
system components after construction is completed.
DO NOT install the furnace on its back or facing down.
→
Safety control operation will be adversely affected. Never
connect return-air ducts to back of furnace. Failure to follow
this warning could result in fire, personal injury, or death.
(See Fig. 5.)
furnace. If the dampers are manually operated, they must be
equipped with means to prevent operation of either unit unless the
damper is in the full-heat or full-cool position.
AIR FOR COMBUSTION AND VENTILATION
Provisions for adequate combustion and ventilation air must be
provided in accordance with Section 5.3 of the NFGC, Air for
Combustion and Ventilation, or applicable provisions of the local
building codes.
Canadian installations must be installed in accordance with NSCNGPIC Part 7 and all authorities having jurisdiction.
18-IN. MINIMUM
TO BURNERS
A93044
Fig. 6—Installation in a Garage
When the furnace is installed in a residential garage, the
burners andignition sources must be located at least 18 inches
above the floor. The furnace must be located or protected to
avoid damage by vehicles. When the furnace is installed in a
public garage, airplane hangar, or other building having a
hazardous atmosphere, the furnace must be installed in
accordance with the NFGC or NSCNGPIC. (See Fig. 6.)
Air for combustion must not be contaminated by halogen
compounds, which include fluoride, chloride, bromide, and
iodide. These elements are found in aerosol sprays, detergents, bleaches, cleaning solvents, salts, air fresheners, and
other household products.
A02054
Fig. 5—Prohibit Installation on Back
Step 2—Location Relative to Cooling Equipment
The cooling coil must be installed parallel with, or on the
downstream side of the unit to avoid condensation in the heat
exchangers. When installed parallel with the furnace, dampers or
other flow control must prevent chilled air from entering the
All fuel-burning equipment must be supplied with air for fuel
combustion. Sufficient air must be provided to avoid negative
pressure in the equipment room or space. A positive seal must be
made between the furnace cabinet and the return-air duct to
prevent pulling air from the burner area and from blocked vent
safeguard opening.
The operation of exhaust fans, kitchen ventilation fans,
→
clothes dryers, attic exhaust fans or fireplaces could create a
NEGATIVE PRESSURE CONDITION at the furnace.
Make-up airMUST be provided for the ventilation devices, in
addition to that required by the furnace. Refer to Carbon
Monoxide Hazard warning in venting section of these instructions to determine amount of make-up air required.
The requirements for combustion and ventilation air depend upon
whether the furnace is located in an unconfined or confined space.
6
Table 2–Minimum Free Area of Combustion Air Opening*
* Free area shall be equal to or greater than the sum of the areas of all vent connectors in the confined space. Opening area must be increased ifother gas appliances
in the space require combustion air.
UNCONFINED SPACE
Free Area
of Opening
(Sq In.)
OUTDOOR AIR THROUGH
VERTICAL DUCTS
Free Area of
Opening and Duct
(Sq. In.)
Round Pipe
(in. Dia)
OUTDOOR AIR THROUGH
HORIZONTAL DUCTS
Free Area of
Opening and Duct
(sq In.)
Round Pipe
(in. Dia)
OUTDOOR AIR THROUGH
SINGLE DUCT
Free Area of
Opening and Duct
(Sq In.)
Round Pipe
(In. Dia)
Step 1—Unconfined Space
An unconfined space has a volume of at least 50 cu ft for each
1000 Btuh total input for all appliances (furnaces, clothes dryers,
water heaters, etc.) in the space.
For example:
FURNACE
INPUT (BTUH)
44,000294
66,000441
88,000587
110,000734
132,000881
154,0001028
MINIMUM WITH
7–1/2 FT CEILING (SQ. FT.)
If the unconfined space is constructed unusually tight, air for
combustion and ventilation must come from either the outdoors or
spaces freely communicating with the outdoors. Combustion and
ventilation openings must be equivalent to those used for a
confined space (defined below). Return air must not be taken from
the room unless an equal or greater amount of air is supplied to the
room.
Step 2—Confined Space
A confined space has a volume less than 50 cu ft per 1000 Btuh
of total input ratings of all appliances installed in that space. A
confined space must have provisions for supplying air for combustion, ventilation, and dilution of flue gases using one of the
following methods in Table 2 and Fig. 7 and 8.
NOTE: When determining the free area of an opening, the
blocking effect of louvers, grilles, and screens must be considered.
If the free area of the louver or grille design is unknown, assume
wood louvers have a 20 percent free area and metal louvers or
grilles have a 60 percent free area. Screens must not be smaller
than 1/4-in. mesh. Louvers and grilles must be constructed so they
cannot be closed.
The opening size depends upon whether air comes from outside of
the structure or an unconfined space inside the structure.
1. Air from inside the structure requires 2 openings (for structures not of unusually tight construction):
a. Each opening must have a minimum free area of not less
than 1 sq in per 1000 Btuh of total input rating for all gas
utilization equipment in the confined space, but not less
than 100 sq in. The minimum dimension of air openings
should be no smaller than 3 in. (See Table 2 and Fig. 7 ).
b. If building construction is unusually tight, a permanent
opening directly communicating with the outdoors shall be
provided. (See next section).
AIR
DUCTS
INTERIOR
HEATED
SPACE
AIR DUCTS
* Minimum opening size is 100 sq in. with
minimum dimensions of 3 in.
†
Minimum of 3 in. when type-B1 vent is used.
VENT THROUGH ROOF
12″ MAX
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
UNCONFINED
SPACE
CONFINED
SPACE
6″ MIN
(FRONT)
1 SQ IN.
PER 1000
BTUH* IN DOOR
OR WALL
†
12″ MAX
A02038
Fig. 7—Confined Space: Air for Combustion and
Ventilation from an Unconfined Indoor Space
c. If the furnace is installed on a raised platform to provide a
return-air plenum, and return air is taken directly from the
hallway or space adjacent to furnace, all air for combustion
must come from outdoors.
2. Air from outside the structure requires 1 of the following:
a. If combustion air is taken from outdoors through 2 vertical
ducts, the openings and ducts must have at least 1 sq in. of
free area per 4000 Btuh of total input for all equipment
within the confined space. (See Fig. 8 and Table 2.)
b. If combustion air is taken from outdoors through 2 hori-
zontal ducts, the openings and ducts must have at least 1 sq
in. of free area per 2000 Btuh of total input for all
equipment within the confined space. (See Fig. 8 and Table
2.)
7
DUCTS
TO
OUTDOORS
1 SQ IN.
PER 4000
*
BTUH
12″ MAX
1 SQ IN.
PER 2000
*
BTUH
DUCTS
TO
OUTDOORS
1 SQ IN.
PER 2000
*
BTUH
12
*Minimum dimensions of 3 in.
NOTE:
A
AIR
DUCTS
B
″ MAX
AIR DUCTS
Use any of the following
combinations of openings:
A & B C & D D & E F & G
D
VENT
THROUGH
ROOF
C
DUCT
TO
OUTDOORS
CONFINED
SP A CE
E
12″ MAX
F
1 SQ IN.
BTUH*
1 SQ IN.
BTUH*
G
1 SQ IN.
PER 4000
*
BTUH
12″
MAX
PER
4000
OUTDOORS
PER
4000
12″
MAX
A02165
Fig. 8—Confined Space: Air for Combustion and
Ventilation from Outdoors
c. If combustion air is taken from the outdoors through a
single opening or duct (horizontal or vertical) commencing
within 12 in. of the top of the confined space, the opening
and duct must have at least 1 sq in. of free area per 3000
Btuh ofthe total input for allequipment within the confined
space and not less than the sum of the areas of all vent
connectors in the confined space. Equipment clearances to
the structure shall be at least 1 in. from the sides and back
and 6 in. from the front of the appliances. See Table 2 and
Fig. 8.
When ducts are used, they must be of the same cross sectional area
as the free area of the openings to which they connect. The
minimum dimension of ducts must not be less than 3 in.
INSTALLATION
Step 1—Upflow Installation
BOTTOM RETURN AIR INLET
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
1. Tilt or raisefurnace and remove 2 screws holding bottom filler
panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Fig. 9—Removing Bottom Closure Panel
SIDE RETURN AIR INLET
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. This panel MUST be in place when
only side return air is used.
NOTE: Side return-air openings can be used in UPFLOW and
→
most HORIZONTAL configurations. Do not use side return-air
openings in DOWNFLOW configuration.
LEVELING LEGS (IF DESIRED)
In upflow position with side return inlet(s), leveling legs may be
used. (See Fig. 10.) Install field-supplied, 5/16 X 1 1/2 in. (max)
corrosion-resistant machine bolts, washers and nuts.
NOTE: Bottom closure mustbe used when leveling legs are used.
It may be necessary to remove and reinstall bottom closure panel
to install leveling legs. To remove bottom closure panel, see Fig.
9.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each
bottom corner of furnace. (See Fig. 10.)
2. For each leg, install nut on bolt and then install bolt and nut in
hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat
washer if desired.)
4. Adjust outside nutto provide desired height, andtighten inside
nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
Step 2—Downflow Installation
NOTE: For downflow applications, this furnace is approved for
use on combustible flooring when any one of the 3 accessories are
used:
• Special Base, KGASB
• Cased Coil Assembly Part No. CD5 or CK5
• Coil Box Part No. KCAKC
1. Determine application being installed from Table 3.
2. Construct hole in floor per Table 3 and Fig. 11.
3. Construct plenum to dimensions specified in Table 3 and Fig.
11.
4. If downflow subbase, KGASBis used, install as shown in Fig.
12. If Coil Assembly Part No. CD5 or CK5 or Coil Box Part
No. KCAKC is used, install as shown in Fig. 13.
8
A02098
5
⁄16″
1 3⁄4″
5
⁄16″
PLATFORM UNIT SUPPORT
Construct working platform at location where all required furnace
clearances are met. (See Fig. 2 and 17.) For furnaces with 1-in.
clearance requirement on side, set unit on non-combustible blocks,
bricks or angle iron. For crawlspace installations, if the unit is not
suspended from the floor joists, the ground underneath unit must
be level and the unit set on blocks or bricks.
3
⁄4″
1
5
⁄16″
5
⁄16″
3
1
⁄4″
3
⁄4″
1
Fig. 10—Leveling Legs
NOTE: It is recommended that the perforated supply-air duct
flanges be completely folded over or removed from furnace when
installing the furnace on a factory-supplied cased coil or coil box.
To remove the supply-air duct flange, use wide duct pliers or hand
seamers tobend flange back and forthuntil it breaks off. Becareful
of sharp edges. (See Fig. 14.)
BOTTOM RETURN AIR INLET
→
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
1. Tilt or raisefurnace and remove 2 screws holding bottom filler
panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
Step 3—Horizontal Installation
A02071
ROLL-OUT PROTECTION
Provide a minimum 17 3/4″ X22″ piece of sheet metal for roll-out
protection in front of burner area for units closer than 12 inches
above the combustible deck or suspended units closer than 12-in.
to joists. The sheet metal MUST extend underneath the furnace
casing by 1 in. with the door removed.
The bottom closure pan on furnaces of widths 17 1/2 in. and larger
may be used for roll-out protection when bottom of furnaceis used
for return air connection. See Fig. 17 for proper orientation of
roll-out shield.
BOTTOM RETURN AIR INLET
→
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel,
perform the following:
1. Tilt or raisefurnace and remove 2 screws holding bottom filler
panel. (See Fig. 9.)
2. Rotate bottom filler panel downward to release holding tabs.
3. Remove bottom closure panel.
4. Reinstall bottom filler panel and screws.
SIDE RETURN AIR INLET
→
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. This panel MUST be in place when
only one side return air is used.
Not all horizontal furnaces are approved for side return air
→
connections (See Fig. 20.)
Step 4—Filter Arrangement
Never operate a furnace without a filter or with filter access
door removed. Failure to follow this warning could result in
fire, personal injury, or death.
Do not install the furnace on its back or hang furnace with
control compartment facing downward. Safety control operation will be adversely affected. Never connect return-air ducts
to the back of the furnace. Failure to follow this warning
could result in fire, personal injury, or death.
The furnace can be installed horizontally in an attic or crawl space
on either the left-hand (LH) or right-hand (RH) side. The furnace
can be hung from floor joists, rafters or trusses or installed on a
platform, non-combustible blocks, bricks or pad.
SUSPENDED UNIT SUPPORT
The furnace may be supported under each end with threaded rod,
angle iron or metal plumber’s strap as shown. (See Fig. 15 and 16.)
Secure angle iron to bottom of furnace as shown. Heavy-gauge
sheet metal straps (plumber’s straps) may be used to suspend the
unit from each bottom corner. To prevent screws from pulling out,
use2#8x¾-in. screw into the side and2#8x¾-in. screw in the
bottom of the furnace casing for each strap. (See Fig. 15 and 16.)
There are no provisions for an internal filter rack in these furnaces.
A field-supplied accessory external filter rack is required.
This furnace requires KGAFR0301ALL 1″ external filter rack or a
suitable field-supplied substitute, such as the Media Cabinet.
Refer to the instructions supplied with external filter rack for
assembly and installation options.
Step 5—Air Ducts
GENERAL REQUIREMENTS
The duct system should be designed and sized according to
accepted national standards such as those published by: Air
Conditioning Contractors Association (ACCA), Sheet Metal and
Air Conditioning Contractors National Association (SMACNA) or
American Society of Heating, Refrigerating and Air Conditioning
Engineers (ASHRAE) or consult The Air Systems Design Guide-lines reference tables available from your local distributor. The
duct system should be sized to handle the required system design
CFM at the design external static pressure.
9
A
PLENUM
OPENING
B
FURNACE
(OR COIL CASING
WHEN USED)
COMBUSTIBLE
D
FLOORING
FLOOR
OPENING
C
A96283
Fig. 11—Floor and Plenum Opening Dimensions
COIL ASSEMBLY
DOWNFLOW
SUBBASE
SHEET METAL
PLENUM
FLOOR
OPENING
A96285
Fig. 12—Furnace, Plenum, and Subbase Installed on
a Combustible Floor
FURNACE
CD5 OR CK5
OR KCAKC
COIL BOX
COMBUSTIBLE
FLOORING
SHEET METAL
OPENING
Fig. 13—Furnace, Plenum, and Coil Assembly or Coil Box Installed on a Combustible Floor
When a furnace is installed so that the supply ducts carry air to
areas outside the space containing the furnace, the return air must
also be handled by a duct(s) sealed to the furnace casing and
terminating outside the space containing the furnace.
Secure ductwork with proper fasteners for type of ductwork used.
Seal supply- and return-duct connections to furnace with code
approved tape or duct sealer.
PLENUM
FLOOR
A96284
Flexible connections should be used between ductwork and
furnace to prevent transmission of vibration. Ductwork passing
through unconditioned space should be insulated and sealed to
enhance system performance. When air conditioning is used, a
vapor barrier is recommended.
Maintain a1-in. clearance from combustible materialsto supply air
ductwork fora distance of 36 in. horizontally from thefurnace. See
NFPA 90B or local code for further requirements.
10
FURNACE
CASING
WIDTH
14–3/16
17–1/2
21
24-1/2
Table 3—Opening Dimensions (In.)
APPLICATION
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring (KGASB
subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box (KGASB subbase
not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring (KGASB
subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box (KGASB subbase
not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on combustible flooring (KGASB
subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box (KGASB subbase
not required)
Upflow Applications on Combustible or Noncombustible
Flooring (KGASB subbase not required)
Downflow Applications on Noncombustible Flooring
(KGASB subbase not required)
Downflow applications on Combustible flooring (KGASB
subbase required)
Downflow Applications on Combustible Flooring with CD5 or
CK5 Coil Assembly or KCAKC coil box (KGASB subbase
not required)
PLENUM OPENINGFLOOR OPENING
ABCD
12-11/1621-5/813-5/1622-1/4
12-9/161913-3/1619-5/8
11-13/161913-7/1620-5/8
12-5/161913-5/1620
1621-5/816-5/822-1/4
15-7/81916-1/219-5/8
15-1/81916-3/420-5/8
15-1/21916-1/220
19-1/221-5/820-1/822-1/4
19-3/8192019-5/8
18-5/81920-1/420-5/8
19192020
2321-1/823-5/822-1/4
22-7/81923-1/219-5/8
22-1/81923-3/420-5/8
22-1/21923-1/220
UPFLO
90˚
120˚
MIN
WOWNFLOW
PREFERRED
PREFERRED
PERMITTED
D
120˚
MIN
→ Fig. 14—Duct Flanges
DUCTWORK ACOUSTICAL TREATMENT
Metal duct systems that do not have a 90 degree elbow and 10 ft
of main duct to the first branch take-off may require internal
acoustical lining. As an alternative, fibrous ductwork may be used
if constructed and installed in accordance with the latest edition of
HORIZONTAL
90˚
PREFERRED
PREFERRED
PERMITTEDPERMITTED
120˚
MIN
SMACNA construction standard on fibrous glass ducts. Both
acoustical lining and fibrous ductwork shall comply with NFPA
90B as tested by UL Standard 181 for Class 1 Rigid air ducts.
PREFERRED
PREFERRED
A02329
11
OUTER DOOR
ASSEMBLY
8" MIN FOR DOOR
REMOVAL
(2) HEX NUTS, (2) WASHERS & (2) LOCK WASHERS
REQ. PER ROD
→ Fig. 15—Horizontal Unit Suspension
1
/4" THREADED ROD
4 REQ.
SECURE ANGLE
IRON TO BOTTOM
OF FURNACE WITH
3 #8 x
TYPICAL FOR 2 SUPPORTS
1" SQUARE, 1
OR UNI-STRUT MAY BE USED
1
/4" x 11/4" x 1/4" ANGLE IRON
3
/4" SCREWS
A02345
Fig. 16—Horizontal Suspension with Straps
SUPPLY AIR CONNECTIONS
→
For a furnace not equipped with a cooling coil, the outlet duct shall
be provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for possible openings using
light assistance or a probe can be inserted for sampling the air
stream. The cover attachment shall prevent leaks.
A02014
Upflow and Horizontal Furnaces
Connect supply-air duct to flange on furnace supply-air outlet.
Bend flange upward to 90° with wide duct pliers. The supply-air
duct attachment must ONLY be connected to furnace supplyoutlet-air duct flanges or air conditioning coil casing (when used).
DO NOT cut main furnace casing to attach supply side air duct,
humidifier, or other accessories. All accessories MUST be connected external to furnace main casing.
12
LINE CONTACT ONLY PERMISSIBLE BETWEEN
LINES FORMED BY INTERSECTIONS OF
THE TOP AND TWO SIDES OF THE FURNACE
JACKET AND BUILDING JOISTS,
STUDS, OR FRAMING.
MANUAL SHUTOFF
GAS VALVE
SEDIMENT
TRAP
Fig. 17—Typical Attic Installation
SHEET
METAL
GAS
ENTRY
22
17 3/4
″
17 3/4
″ OVER ALL
4 3/4
″ UNDER DOOR
1″ UNDER FURNACE
TYPE-B
VENT
MIN*
″
6
″
30-IN. MIN
WORK AREA
EXTEND OUT 12″ OUT
FROM FACE OF DOOR
* WHEN USED WITH
SINGLE WALL VENT
CONNECTIONS
A02164
Downflow Furnaces
Connect supply-air duct to supply-air opening on furnace. The
supply-air duct attachment must ONLY be connected to furnace
supply/outlet or air conditioning coil casing (when used). When
installed on combustible material, supply-air duct attachment must
ONLY be connected to the accessory subbase, KGASB0201ALL,
or factory approved air conditioning coil casing. DO NOT cut
main furnace casing to attach supply side air duct, humidifier, or
other accessories. All accessories MUST be connected external to
furnace casing.
RETURN AIR CONNECTIONS
Never connect return-air ducts to the back of the furnace. A
failure tofollow this warning can cause a fire, personalinjury,
or death.
Downflow Furnaces
The return-air duct must be connected to return-air opening
(bottom inlet) as shown in Fig. 1. DO NOT cut into casing sides
(left or right). Side opening is permitted for only upflow and most
horizontal furnaces. Bypass humidifier connections should be
made at ductwork or coil casing sides exterior to furnace.
Upflow and Horizontal Furnaces
The return-air duct must be connected to bottom, sides (left or
right), or a combination of bottom and side(s) of main furnace
casing as shown in Fig. 1. Bypass humidifier may be attached to
unused side return air portion of the furnace casing. (See Fig. 18,
19, and 20.)
Not all horizontal furnaces are approved for side return air
connections. (See Fig. 20.)
Step 6—Gas Piping
Never purge a gas line into a combustion chamber. Never test
→
for gas leaks with an open flame. Use a commercially
available soap solution made specifically for the detection of
leaks to check all connections. A failure to follow this
warning could result in fire, explosion, personal injury, or
death.
Gas piping must be installed in accordance with national and local
codes. Refer to current edition of NFGC in the U.S., the NSCNGPIC in Canada.
Installations must be made in accordance with all authorities
having jurisdiction. If possible, the gas supply line should be a
separate line running directly from meter to furnace.
Refer to Table 4 for recommended gas pipe sizing. Risers must be
used to connect to furnace and to meter. Support all gas piping
with appropriate straps, hangers, etc. Use a minimum of 1 hanger
every 6 ft. Joint compound (pipe dope) should be applied sparingly
and only to male threads of joints. Pipe dope must be resistant to
the action of propane gas.
→
If local codes allow the use of a flexible gas appliance
connector, always use a new listed connector. Do not use a
connector which has previously serviced another gas appliance. Black iron pipe shall be installed at the gas valve and
extend a minimum of 2-in. outside the furnace.
13
Loading...
+ 31 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.