Bryan Boilers CLM-300-W-GI, CLM-90, CLM-120, CLM-150, CLM-180 Brochure & Specs

...
Bryan “Flexible Water Tube”
CLM Series
Steam & Water Boilers
900,000 to 3,000,000 BTUH
Atmospheric gas fi red
Form No. 1920
(Rev. 02/08)
BRYAN® BOILERS
Steam Boiler
Water Boiler
CLM-300-W-GI
Originators of the “Flexible Water Tube” design
High effi ciency hot water and steam boilers for commercial and industrial applications
Bryan fl exible tube boilers are ideally suited for both hot water and steam space heating systems as well as either high or low pressure process steam. In a range of sizes from 900,000 to 3,000,000 BTUH in­put, Bryan CLM series fl exible tube boilers are ideal for many commercial, institutional and industrial applications. These include healthcare facilities; schools; apartments; churches; offi ce buildings; correctional facilities; airports; sewage treatment plants; golf, tennis and fi tness clubs. Hospitals, dairies, restaurants, laundries, dry cleaners, food processing, tire recapping and metal plating are just a few of the many applications. All Bryan boilers are built in accor­dance with the requirements of the ASME Boiler and Pressure Vessel Code.
Effi cient “Flexible Water Tube” design
The Bryan bent water tube provides rapid internal circulation — for maximum heat transfer and operating effi ciency.
Easily replaceable tubes
Tubes are easily removable and replaceable without welding or rolling. Little service space is required.
No “Thermal Shock”
The fl exibility of the bent water tube design elimi­nates all possible damage from "Thermal Shock" and from stresses caused by poor or unequal internal circulation. This is particularly important with forced hot water heating systems designed for higher tem­peratures and greater temperature drops.
Steam Boilers: Section IV or I
Steam release area
Large, full-size steam drum provides for dry steam and stable water level.
High or low pressure construction
Boiler is constructed as standard for 15 psi or 150 psi maximum working pressure. Also available for higher pressures to 300 psi.
Water Boilers: Section IV
High or low pressure construction
Boiler is constructed as standard for 160 psi maximum working pressure at 230°F operating temperature and 250°F design temperature. Also available for higher pressures to 250 psi, at 285°F operating temperature and 300°F design temperature.
Natural internal circulation
The water tube design and the large downcomer legs provide adequate internal circula­tion without concern over exterior pumping condi­tions. Low pressure drop through boiler.
Compact — minimum fl oor space
Requires less floor space than most boilers, minimum boiler room size. Since the tubes can be removed from one side, the boilers are available with right or left hand construction for common tube removal, further minimizing space needs. Shipped completely assembled and wired. Units can also be shipped "Knocked Down" for on-site assembly.
Bryan CLM Series Boiler Specifi cations
NOMINAL OUTPUT STEAM HEATING APPROX.
BOILER INPUT MODEL MBH (KW)
CLM-90 900 (264) 720 (211) 21 (206) 742 (337) 110 (10.2) 1,450 (658) CLM-120 1,200 (352) 960 (281) 29 (284) 990 (449) 145 (13.5) 1,750 (794) CLM-150 1,500 (440) 1,200 (352) 36 (353) 1,237 (561) 180 (16.7) 2,050 (930) CLM-180 1,800 (527) 1,440 (422) 43 (421) 1,485 (674) 215 (20.0) 2,350 (1,066) CLM-210 2,100 (615) 1,680 (492) 50 (490) 1,732 (786) 251 (23.3) 2,650 (1,202) CLM-240 2,400 (703) 1,920 (563) 57 (559) 1,979 (898) 287 (26.7) 2,950 (1,338) CLM-270 2,700 (791) 2,160 (633) 64 (627) 2,227 (1,010) 322 (29.9) 3,500 (1,588) CLM-300 3,000 (879) 2,400 (703) 72 (706) 2,474 (1,122) 360 (33.5) 3,950 (1,792)
NOTES: * Lbs. steam per hour from and at 212°F.
MBH (KW) BHP LBS/HR* SQ. FT. (M²) LBS. (KG)
OUTPUT SURFACE SHIP WT.
Low initial cost, high operating effi ciency deliver substantial return on investment
True “fl exible water tube” design guaranteed
shock free
Longer service life with superior performance
Full fi ve sq ft of heating
surface per BHP
Quality Construction Features
A. Heavy steel boiler frame, built and stamped
in accordance with the appropriate ASME boiler code.
B. Large volume water leg downcomers pro-
mote rapid internal circulation, temperature equalization and effi cient heat transfer.
C. Bryan bent water tubes are fl exible, individu-
ally replaceable without welding or rolling. Never more than two tube confi gurations.
D. Boiler tube and furnace area access panel:
heavy gauge steel casing with 2" high tem­perature ceramic fi ber and insulation, bolted and tightly sealed to boiler frame.
E. Jacket access panels make the interior of the boiler
easily accessible for service and inspection.
F. Heavy gauge steel boiler jacket with rust-resistant
zinc coating and attractive enamel fi nish, insulated with 1½" fi berglass to insure exceptionally cool outer surface.
G. Minimum sized fl ue vent.
B
D
E
G
L
I
J
C
F
A
K
H
J. Control panel: all controls installed and connected
to terminal strip.
K. Water side or steam side interior accessible for clean-
out and inspection, front and rear openings, upper and lower drums.
I. All controls, gauges, relief valve(s) are factory installed
and wired and easily accessible for servicing.
Bryan CLM Series Boilers Standard and Optional Equipment
STANDARD EQUIPMENT FURNISHED
Water Boiler
Combination thermometer and pres­sure gauge, ASME-rated boiler relief valve, water temperature control (240°F max. std.), high limit control, probe LWCO.
Steam Boiler
Steam pressure gauge, steam pres­sure control, combination low water cutoff and pump control, auxiliary low water cutoff with manual reset, high limit pressure control, ASME-rated boiler relief valve, water glass set.
Atmospheric equipment
Electronic combustion safety control, automatic operating gas valve, safety gas valve, pilot solenoid valve, electric
ignition assembly, main manual gas shut-off valve, pilot shut-off valve, pilot and main gas pressure regula­tors, barometric draft controller, all controls installed and wired standard voltage 120/1/60.
OPTIONAL EQUIPMENT:
1. Manual reset high limit control
2. Manual reset low water cutoff
3. Auxiliary low water cutoff (water)
4. Combination low water cutoff and feeder
5. Alarm bells or horns
6. UL, CUL, CSD-1, FM, IRI or other insurance approved
control systems
7. Low fi re start, Hi-Lo or
modulation fi re control
8. Indicating lights, as desired
L. Steam boilers with extra large drum with high steam
release area ensure stable water level and dry steam.
9. Lead-lag systems for two or more boilers with or without outdoor reset control
10. Heat exchanger coils for
domestic water
11. Special construction: left hand, Knocked Down
OPTIONAL CONSTRUCTION:
Steam boiler
Optional construction to ASME Power Boiler Code requirements for pressure exceeding 150 psi to maximum of 300 psi design pressure.
Hot water boiler
Optional construction to ASME Power Boiler Code requirements for temperatures exceeding 240°F and/or pressure exceeding 160 psi to maxi­mum of 285°F operating and 300°F design temperature and 250 psi.
When ordering, please
specify:
1. Boiler size
2. Supply and return temperatures required
3. Boiler relief valve setting
4. Type of fuel: natural or LP, BTU content, specifi c gravity and pressure available
5. Optional extra equip­ment or construction
6. Special approvals re­quired (UL, CUL, CSD-1, FM or IRI)
7. Altitude
G
D
K
I
B
H
LEFT END VIEW FRONT VIEW
PLAN VIEW
RIGHT END VIEW
Barometric
Draft Control
E
L
C
J
F
A
E
G
A
D
E
K
I
B
H
LEFT END VIEW FRONT VIEW
PLAN VIEW
RIGHT END VIEW
Barometric
Draft Control
E
L
C
J
F
Bryan CLM Series Steam & Hot Water Boilers
STEAM BOILER DIMENSIONS in inches (cm)
Boiler Length Gas Train Model of Number Jacket
CLM-90-S
CLM-120-S
CLM-150-S
CLM-180-S
CLM-210-S
CLM-240-S
CLM-270-S
CLM-300-S
A B C D E F G H I J K L
Supply
Feed
Nozzle
Width Min. Tube Height Height Floor to
Outside Removal Over Over Flow
Conn.
Jacket Clearance Barometric Jacket Nozzle
1
/2 NPT 383/8 30 8113/16 685/16 711/
Flue Flue Overall
Location Size Length
1
/2 203/4 14 551/2 11/4 NPT 4 FLG 2 NPT 11/2 NPT 383/8 30 785/16 685/16 711/
41
(105.40) (52.70) (35.60) (141.0) (3.18) (10.20) (5.10) (3.81) (97.47) (76.2) (198.90) (173.51) (181.61)
11
/16 2511/32 16 6411/16 11/4 NPT 6 FLG 3 NPT 11/2 NPT 383/8 30 7913/16 685/16 711/
50
(128.74) (64.37) (40.64) (164.30) (3.18) (15.24) (7.62) (3.81) (97.47) (76.2) (202.72) (173.51) (181.61)
11
/16 2927/32 18 7311/16 11/2 NPT 6 FLG 3 NPT 11/2 NPT 383/8 30 805/16 685/16 711/
59
(151.60) (75.80) (45.72) (187.16) (3.81) (15.24) (7.62) (3.81) (97.47) (76.2) (203.99) (173.51) (181.61)
1
/8 349/16 20 831/8 2 NPT 6 FLG 3 NPT 11/2 NPT 383/8 30 8013/16 685/16 711/
69
(175.57) (87.78) (50.80) (211.13) (5.08) (15.24) (7.62) (3.81) (97.47) (76.2) (205.26) (173.51) (181.61)
3
/8 393/16 20 923/8 2 NPT 6 FLG 3 NPT 11/2 NPT 383/8 30 815/16 685/16 711/
78
Connection (Approx.) 15 psi 150 psi
(199.07) (99.53) (50.80) (234.63) (5.08) (15.24) (7.62) (3.81) (97.47) (76.2) (206.53) (173.51) (181.61)
88 44 20 102 2 NPT 6 FLG 3 NPT 1
(223.52) (111.76) (50.80) (259.08) (5.08) (15.24) (7.62) (3.81) (97.47) (76.2) (207.80) (173.51) (181.61)
97 48
(246.38) (123.19) (50.80) (281.94) (5.08) (15.24) (7.62) (3.81) (97.47) (76.2) (209.07) (173.51) (181.61)
106
1
/2 20 111 2 NPT 6 FLG 3 NPT 11/2 NPT 383/8 30 825/16 685/16 711/
5
/8 533/16 20 1205/8 21/2 NPT 6 FLG 3 NPT 11/2 NPT 383/8 30 8213/16 685/16 711/
(270.82) (135.09) (50.80) (306.38) (6.35) (15.24) (7.62) (3.81) (97.47) (76.2) (210.34) (173.51) (181.61)
2
2
2
2
2
2
2
2
Boiler Length Gas Width Min. Tube Height Height Floor to Model of Number Jacket
CLM-90-W
CLM-120-W
CLM-150-W
CLM-180-W
CLM-210-W
CLM-240-W
CLM-270-W
CLM-300-W
Specifi cations subject to change without notice. Consult factory to consult on other boiler options.
Form No. 1920 ©2008 Bryan Steam LLC Printed in USA 28-6833
A B C D E F G H I J K L
Flue Flue Overall
Location Size Length
1
41
/2 203/4 14 551/2 11/
(105.40) (52.70) (35.60) (141.0) (3.18) (7.62) (7.62) (87.31) (76.2) (180.20) (154.78) (165.25)
11
50
/16 255/16 16 6411/16 11/
(128.74) (64.29) (40.64) (164.30) (3.18) (7.62) (7.62) (87.31) (76.2) (183.48) (154.78) (165.25)
11
/16 2913/16 18 7311/16 11/
59
(151.60) (75.72) (45.72) (187.16) (3.81) (7.62) (7.62) (87.31) (76.2) (185.25) (154.78) (165.25)
1
/8 349/16 20 831/8 2
69
(175.57) (87.78) (50.80) (211.13) (5.08) (7.62) (7.62) (87.31) (76.2) (186.52) (154.78) (165.25)
3
/8 393/16 20 923/8 2
78
(199.07) (99.53) (50.80) (234.63) (5.08) (7.62) (7.62) (87.31) (76.2) (187.79) (154.78) (165.25)
88 44 22 102 2
(232.52) (111.76) (55.88) (259.08) (5.08) (7.62) (7.62) (87.31) (76.2) (189.06) (154.78) (165.25)
1
97 48
/2 22 111 2 NPT 3 NPT 3 NPT 345/8 30 7415/16 6015/16 651/
(246.38) (123.19) (55.88) (281.94) (5.08) (7.62) (7.62) (87.31) (76.2) (190.33) (154.78) (165.25)
5
/8 533/16 22 1205/8 21/
106
(270.82) (135.41) (55.88) (306.38) (6.35) (7.62) (7.62) (87.31) (76.2) (191.60) (154.78) (165.25)
WATER BOILER DIMENSIONS in inches (cm)
Train Connection
NPT 3 NPT 3 NPT 345/8 30 7015/16 6015/16 651/
4
NPT 3 NPT 3 NPT 345/8 30 727/16 60
4
NPT 3 NPT 3 NPT 345/8 30 7215/16 6015/16 651/
2
NPT 3 NPT 3 NPT 345/8 30 737/16 60
NPT 3 NPT 3 NPT 345/8 30 7315/16 6015/16 651/
NPT 3 NPT 3 NPT 345/8 30 747/16 6015/16 651/
NPT 3 NPT 3 NPT 345/8 30 757/16 6015/16 651/
2
Supply Return Nozzle Nozzle
Outside Removal Over Over Flow Jacket Clearance Barometric Jacket Nozzle