Bryan Boilers CLM User Manual

0 (0)
Bryan “Flexible Water Tube”
CLM Series
Steam & Water Boilers
1,200,000 to 3,000,000 BTUH
Forced draft gas, oil or dual fuel fired
Form No. 1930
(04/05)
Water Boiler
CLM-300-W-FDG
BRYAN® BOILERS
Originators of the “Flexible Water Tube” design
Steam Boiler
High efficiency hot water and steam boilers for commercial and industrial applications
Bryan flexible tube boilers are ideally suited for both hot water and steam space heating systems as well as either high or low pressure process steam. In a range of sizes from 1,200,000 to 3,000,000 BTUH input, Bryan CLM series flexible tube boilers are ideal for many commercial, institu­tional and industrial applications. These include healthcare facilities; schools; apartments; churches; office buildings; correctional facilities; airports; sewage treatment plants; golf, tennis and fitness clubs. Hospitals, dairies, restaurants, laundries, dry cleaners, food processing, tire recapping and metal plating are just a few of the many applications.
All Bryan boilers are built in accordance with the require­ments of the ASME Boiler and Pressure Vessel Code.
Efficient “Flexible Water Tube” design
The Bryan bent water tube provides rapid internal circulation — for maximum heat trans­fer and operating efficiency.
Easily replaceable tubes
Tubes are easily removable and replaceable without welding or rolling. Little service space is required.
No “Thermal Shock”
The flexibility of the bent water tube design eliminates all possible damage from "Thermal Shock" and from stresses caused by poor or unequal internal circulation. This is particularly important with forced hot water heating systems designed for higher temperatures and greater temperature drops.
Steam Boilers: Section IV or I
Steam release area
Large, full-size steam drum provides for dry steam and stable water level.
High or low pressure construction
Boiler is constructed as standard for 15 psi or 150 psi maximum working pressure. Also available for higher pres­sures to 300 psi.
Water Boilers: Section IV
High or low pressure construction
Boiler is constructed as standard for 160 psi maximum working pressure at 230°F operating temperature and 250°F design temperature. Also available for higher pressures to 250 psi, at 285°F operating temperature and 300°F de­sign temperature.
Natural internal circulation
The water tube design and the large downcomer legs provide adequate internal circulation with­out concern over exterior pumping conditions. Low pressure drop through boiler.
Compact — minimum floor space
Requires less floor space than most boilers, minimum boiler room size. Since the tubes can be removed from one side, the boilers are available with right or left hand construction for common tube removal, further minimizing space needs.
Shipped completely assembled and wired. Units can also
be shipped "Knocked Down" for on-site assembly.
Bryan CLM Series Boiler Specifications
BOILER INPUT STEAM OUTPUT
MODEL
CLM120-W 1,200 (352) 960 (281) 29 (281) 978 (287) 29 (287) 145 (13.5) 2,250 (1,021)
CLM120-S 1,200 (352) 960 (281) 29 (281) 990 (449) 145 (13.5) 2,450 (1,111)
CLM150-W 1,500 (440) 1,200 (352) 36 (352) 1,223 (358) 37 (358) 180 (16.7) 2,675 (1,213)
CLM150-S 1,500 (440) 1,200 (352) 36 (352) 1,237 (561) 180 (16.7) 2,850 (1,293)
CLM180-W 1,800 (527) 1,440 (422) 43 (422) 1,467 (430) 44 (430) 215 (20.0) 2,975 (1,350)
CLM180-S 1,800 (527) 1,440 (422) 43 (422) 1,485 (674) 215 (20.0) 3,250 (1,474)
CLM210-W 2,100 (615) 1,680 (492) 50 (492) 1,712 (502) 51 (502) 251 (23.3) 3,475 (1,576)
CLM210-S 2,100 (615) 1,680 (492) 50 (492) 1,732 (786) 251 (23.3) 3,650 (1,656)
CLM240-W 2,400 (703) 1,920 (563) 57 (563) 1,956 (573) 58 (573) 287 (26.7) 3,900 (1,769)
CLM240-S 2,400 (703) 1,920 (563) 57 (563) 1,979 (898) 287 (26.7) 4,050 (1,837)
CLM270-W 2,700 (791) 2,160 (633) 64 (633) 2,201 (645) 66 (645) 322 (29.9) 4,400 (1,996)
CLM270-S 2,700 (791) 2,160 (633) 64 (633) 2,227 (1,010) 322 (29.9) 4,900 (2,223)
CLM300-W 3,000 (879) 2,400 (703) 72 (703) 2,445 (716) 73 (716) 360 (33.5) 4,800 (2,177)
CLM300-S 3,000 (879) 2,400 (703) 72 (703) 2,474 (1,122) 360 (33.5) 4,925 (2,234)
NOTES: (1) W = Water / S = Steam
(1)
MBH (KW) MBH (KW) HP (KW) MBH (KW) HP (KW) LBS/HR (KG/HR) SQ. FT. (M²) LBS. (KG)
(2) Output and horsepower based on boiler industry standard of 80% of input.
(3) Output and horsepower based on an average natural gas combustion efficiency of 81.5% for hot water boiler. Actual combustion efficiencies for oil will be higher. (4 )Lbs. steam per hour from and at 212°F.
OUTPUT @ 80% EFFICIENCY
(2)
OUTPUT @ 81.5% EFFICIENCY
(3)
(4)
HTG. SURFACE APPROX. SHIP