Thank you for purchasing this quality-built Briggs & Stratton home generator. We’re pleased that you’ve placed your
confidence in the Briggs & Stratton brand. When operated and maintained according to the instructions in this manual, your
Briggs & Stratton home generator will provide many years of dependable service.
This manual contains safety information to make you aware of the hazards and risks associated with home generator systems
and how to avoid them. This home generator system is designed and intended only for use as an optional home standby
system that provides an alternate source of electric power and to serve loads such as heating, refrigeration systems, and
communication systems that, when stopped during any power outage, could cause discomfort or inconvenience. This product
is not intended for any other purpose and does not qualify for emergency standby as defined by NFPA 70 (NEC).
This home generator requires professional installation before use. Refer to the separate Installation Manual for full
information. Follow the instructions completely. Save these instructions for future reference.
Where to Find Us
You never have to look far to find Briggs & Stratton support and service for your generator. Consult your Yellow Pages.
There are thousands of Briggs & Stratton authorized service dealers worldwide who provide quality service. You can
also contact Briggs & Stratton Customer Service by phone at (800) 743-4115, or use the Service Center Locator at
BRIGGSandSTRATTON.COM, which provides a list of Briggs & Stratton Authorized Dealers.
See Installation Manual for system purchase date and component identification numbers
Briggs & Stratton Power Products Group, LLC
900 North Parkway
Jefferson, WI 53549
The safety alert symbol () is used with a signal word
(DANGER, CAUTION, WARNING), a pictorial and/or a safety
message to alert you to hazards. DANGER indicates a hazard
which, if not avoided, will result in death or serious injury.
WARNING indicates a hazard which, if not avoided, could
result in death or serious injury. CAUTION indicates a hazard
which, if not avoided, might result in minor or moderate
injury. NOTICE indicates a situation that could result in
equipment damage. Follow safety messages to avoid or
reduce the risk of injury or death.
The manufacturer cannot possibly anticipate every possible
circumstance that might involve a hazard. The warnings in
this manual, and the tags and decals affixed to the unit are,
therefore, not all-inclusive. If you use a procedure, work
method or operating technique that the manufacturer does
not specifically recommend, you must satisfy yourself that
it is safe for you and others. You must also make sure that
the procedure, work method or operating technique that you
choose does not render the generator system unsafe.
Hazard Symbols and Meanings
WARNING
Storage batteries give off explosive hydrogen
gas during recharging.
Slightest spark will ignite hydrogen and cause
explosion.
Battery electrolyte fluid contains acid and is
extremely caustic.
Contact with battery contents will cause severe
chemical burns.
A battery presents a risk of electrical shock and
high short circuit current.
DO NOT dispose of battery in a fire.
•
DO NOT allow any open flame, spark, heat, or lit cigarette
•
during and for several minutes after charging a battery.
DO NOT open or mutilate the battery.
•
Wear protective goggles, rubber apron, and rubber
•
gloves.
Remove watches, rings, or other metal objects.
•
Use tools with insulated handles.
•
WARNING
Explosion
Toxic Fumes
Fire
Rotating Parts
Electrical Shock
Hot Surface
Chemical BurnExplosive PressureAuto Start
Running engine gives off carbon monoxide, an
odorless, colorless, poison gas.
Breathing carbon monoxide can cause
headache, fatigue, dizziness, vomiting,
confusion, seizures, nausea, fainting or death.
Operate generator ONLY outdoors.
•
Install a battery operated carbon monoxide alarm near the
•
bedrooms.
Keep exhaust gas from entering a confined area through
•
windows, doors, ventilation intakes, or other openings.
WARNING
The engine exhaust from this product contains chemicals
known to the State of California to cause cancer, birth
defects, or other reproductive harm.
4 BRIGGSandSTRATTON.COM
WARNING
WARNING
Generator produces hazardous voltage.
Failure to properly ground generator can result
in electrocution.
Failure to isolate generator from power utility
can result in death or injury to electric utility
workers due to backfeed of electrical energy.
When using generator for backup power, notify utility
•
company.
DO NOT touch bare wires or receptacles.
•
DO NOT handle generator or electrical cords while
•
standing in water, while barefoot, or while hands or feet
are wet.
If you must work around a unit while it is operating,
•
stand on an insulated dry surface to reduce shock hazard.
DO NOT allow unqualified persons or children to operate
•
or service generator.
In case of an accident caused by electrical shock,
•
immediately shut down the source of electrical power and
contact the local authorities. Avoid direct contact with
the victim.
Despite the safe design of the home generator, operating
•
this equipment imprudently, neglecting its maintenance
or being careless can cause possible injury or death.
Remain alert at all times while working on this
•
equipment. Never work on the equipment when you are
physically or mentally fatigued.
Before performing any maintenance on the generator,
•
disconnect the battery cable indicated by a NEGATIVE,
NEG or (-) first. When finished, reconnect that cable last.
After your home generator is installed, the generator
•
may crank and start without warning any time there is
a power failure. To prevent possible injury, always set
the generator’s system switch to OFFAND remove the
15 Amp fuse BEFORE working on the equipment.
Propane and Natural Gas are extremely
flammable and explosive.
Fire or explosion can cause severe burns or
death.
Install the fuel supply system according to N.F.P.A 37
•
and other applicable fuel-gas codes.
Before placing the home generator into service, the fuel
•
system lines must be properly purged and leak tested.
After the generator is installed, you should inspect the
•
fuel system periodically.
NO leakage is permitted.
•
DO NOT operate engine if smell of fuel is present or other
•
explosive conditions exist.
DO NOT smoke around the generator. Wipe up any oil
•
spills immediately. Ensure that no combustible materials
are left in the generator compartment. Keep the area near
the generator clean and free of debris.
WARNING
Contact with muffler area can result in serious
burns.
Exhaust heat/gases can ignite combustibles or
structures causing a fire.
DO NOT touch hot parts and AVOID hot exhaust gases.
•
Allow equipment to cool before touching.
•
DO NOT install the generator closer than 5 feet (1.5m)
•
from any combustibles or structures with combustible
walls having a fire resistance rating of less than 1 hour.
5
WARNING
Starter and other rotating parts can entangle
hands, hair, clothing, or accessories.
NEVER operate generator without protective housing or
•
covers.
DO NOT wear loose clothing, jewelry or anything that
•
may be caught in the starter or other rotating parts.
Tie up long hair and remove jewelry.
•
CAUTION
Installing the control panel’s 15A fuse could
cause the engine to start.
DO NOT install this fuse until all plumbing and wiring has
•
been completed and inspected.
CAUTION
Excessively high operating speeds increase risk of injury
and damage to generator.
Excessive load will cause engine shutdown..
DO NOT tamper with governed speed. Generator supplies
•
correct rated frequency and voltage when running at
governed speed.
DO NOT modify generator in any way.
•
NOTICE
Improper treatment of generator can damage it and
shorten its life.
Use generator only for intended uses.
•
If you have questions about intended use, ask dealer or
•
contact Briggs and Stratton.
Operate generator only on level surfaces.
•
Adequate, unobstructed flow of cooling and ventilating air
•
is critical to correct generator operation.
The Coolant Fill, Battery and Control Panel doors must be
•
installed whenever the unit is running.
DO NOT expose generator to excessive moisture, dust,
•
dirt, or corrosive vapors.
Despite the safe design of the home generator, operating
•
this equipment imprudently, neglecting its maintenance or
being careless can cause possible injury or death.
DO NOT start engine with air cleaner base removed.
•
DO NOT insert any objects through cooling slots.
•
DO NOT use the generator or any of its parts as a step.
•
Stepping on the unit can cause stress and break parts.
This may result in dangerous operating conditions from
leaking exhaust gases, fuel leakage, oil leakage, etc.
If connected devices overheat, turn them off and
•
disconnect them from generator.
Shut off generator if:
•
-electrical output is lost;
-equipment sparks, smokes, or emits flames;
-unit vibrates excessively.
CAUTION
Avoid prolonged or repeated skin contact with used motor
oil.
Used motor oil has been shown to cause skin cancer in
•
certain laboratory animals.
Thoroughly wash exposed areas with soap and water.
•
NOTICE
Exceeding generators wattage/amperage capacity can
damage generator and/or electrical devices connected to it.
See Essential Circuits.
•
Start generator and let engine stabilize before connecting
•
electrical loads.
6 BRIGGSandSTRATTON.COM
Installation
We sincerely appreciate your patronage. For this reason,
Briggs & Stratton has made every effort to provide for a safe,
streamlined and cost-effective installation. Because each
installation is unique, it is impossible to know of and advise
the trade of all conceivable procedures and methods by
which installation might be achieved. Neither could we know
of possible hazards and/or the results of each method or
procedure. For these reasons,
Only current licensed electrical and plumbing contractors
should attempt home generator system installations.
Installations must strictly comply with all applicable
codes, industry standards and regulations.
Your Briggs & Stratton home generator is supplied with this
“Operator’s Manual” and a separate “Installation Manual”.
These are important documents and should be retained by
the owner after the installation has been completed.
For the Home Owner
To help you make informed choices and communicate
effectively with your installation contractor(s),
Read and understand Owner Orientation in this manual
before contracting or starting your home generator
installation.
To arrange for proper installation, contact the store at which
you purchased your Briggs & Stratton home generator, your
dealer, a licensed electrician or your utility power provider.
The home generator warranty is VOID unless the
system is installed by licensed electrical and plumbing
professionals.
The Emission Control System for this generator is warranted
for standards set by the U.S. Environmental Protection
Agency and by the California Air Resources Board (CARB).
Federal and local codes, appearance, noise levels, fuel types,
and distances are the factors that must be considered when
negotiating with an installation professional. Remember
that as the distance from the existing electrical service and
gaseous fuel supply increases, and the number of 90 degree
bends in the fuel supply increases; equal compensations
in piping and wiring materials must be allowed for. This is
necessary to comply with local codes and overcome electrical
voltage drops and gaseous fuel pressure drops.
The factors mentioned above will have a direct affect on
the overall price of your home generator installation.
NOTE: In some areas you may need to acquire electrical
permits for installing the home generator, building permits
for installing gas lines, and permits for noise allowances.
Your installer should check your local codes AND obtain the
permits before installing the system.
Fuel Factors
This home generator system was factory tested and adjusted
using natural gas. It can also operate on liquid propane (LP
vapor). For proper engine function, factors that are inherent
to each of these fuels, your location and the duration of
possible utility interruptions are important considerations in
the following fuel guidelines:
• Use clean, dry fuel, free of moisture or any
particulate material. Using fuels outside the following
recommended values may cause performance
problems.
• For engines set up to run on propane vapor (LP),
commercial grade HD5 propane with a minimum fuel
energy of 2500 BTUs/ft3 with maximum propylene
content of 5% and butane and heavier gas content of
2.5% and minimum propane content of 90%.
WARNING
For the Installing Dealer/Contractor
For most applications, the Installation manual contains all
the information required to properly install and start the
home generator. This Operator’s Manual describes essential
circuit selection, routine operation and owner maintenance
procedures.
If you need more information, call (800) 743-4115, between
8:00 AM and 5:00 PM CT.
Owner Orientation
This section provides home generator owners with the
information necessary to achieve the most satisfactory and
cost effective installation possible.
The illustrations are for typical circumstances and are meant
to familiarize you with the installation options available with
your home generator. A thorough understanding of these
options will provide fundamental control over the cost of
your installation, as well as ensure your final satisfaction and
security.
Propane and Natural Gas are extremely
flammable and explosive.
Fire or explosion can cause severe burns or
death.
The home generator is equipped with an automatic safety
•
gas “fuel shut-off” valve.
DO NOT operate the equipment if the “fuel shut-off” valve
•
is missing or inoperative.
Power Decrease at High Altitude or High Temperature
Air density is less at high altitudes, resulting in less available
engine power. Specifically, engine power will decrease 3.5%
for each 1,000 feet (300 meters) above sea level and 1% for
each 10° F (5.6°C) above 77°F (25°C). Make sure you and
your installer consider these factors when determining total
generator load.
7
Generator Location
The actual physical location of your home generator has a
direct affect on:
1. The amount of plumbing required to fuel your
generator.
2. The amount of wiring required to control and connect
your generator.
NOTE: Specific location guidelines are discussed in the
Installation Manual. Acquaint yourself with that information
and confer with your installer. Be sure to ask how your site
might affect installation costs and compliance with local
codes and standards.
Generator Clearances
The generator must be installed outdoors. DO NOT install
generator where exhaust gas could accumulate and enter
inside or be drawn into a potentially occupied building.
Ensure exhaust gas is kept away from any windows, doors,
ventilation intakes or other openings that can allow exhaust
gas to collect in a confined area. Prevailing winds and air
currents should be taken into consideration when positioning
generator. See the Installation Manual for full details on safe
generator location.
WARNING
Exhaust heat/gases can ignite combustibles or
structures causing a fire.
DO NOT install the generator closer than 5 feet (1.5m)
•
from any combustibles or structures with combustible
walls having a fire resistance rating of less than 1 hour.
Essential Circuits
As a home generator owner, it is important that you clearly
identify the circuits in your building that are “essential” to
you.
It is also important that your installer understand which
circuits you want to include as “Essential Circuits”.
Depending on the power consumed by these circuits, most
or all of them can be switched to the home generator for the
duration of normal power interruption.
The wattage reference table that follows will assist you with
your decision-making process. It provides the wattage used
by many ordinary household devices. Use it as a guide when
selecting your essential circuits. Review this information with
your installer and ask about any technical considerations that
might affect your installation. This chart serves as a guide
only. For exact wattage use an appropriate wattage meter.
Device
q
Air Conditioner (12,000 Btu)*1700
q
Air Conditioner (24,000 Btu)*3800
q
Air Conditioner (40,000 Btu)*6000
q
Battery Charger (20 Amp)500
q
Circular Saw (6-1/2”)800 to 1000
q
Clothes Dryer (Electric)*5750
q
Clothes Dryer (Gas)*700
q
Clothes Washer*1150
q
Coffee Maker1750
q
Compressor (1 HP)*2000
q
Compressor (1/2 HP)*1400
q
Compressor (3/4 HP)*1800
q
Curling Iron700
q
Dehumidifier*650
q
Electric Blanket400
q
Electric Range (per element)1500
q
Electric Skillet1250
q
Freezer*700
q
Furnace Fan (1/2 HP)*800
q
Garage Door Opener*500 to 750
q
Hair Dryer1200
q
Hand Drill250 to 1100
q
Iron1200
q
Jet Pump*800
q
Light Bulb100
q
Microwave Oven700 to 1000
q
Milk Cooler*1100
q
Oil Burner on Furnace300
q
Oil Fired Space Heater (140,000 Btu)400
q
Oil Fired Space Heater (30,000 Btu)150
q
Oil Fired Space Heater (85,000 Btu)225
q
Radio50 to 200
q
Refrigerator700
q
Slow Cooker200
q
Submersible Pump (1 HP)*2000
q
Submersible Pump (1/2 HP)*1500
q
Submersible Pump (1-1/2 HP)*2800
q
Sump Pump*800 to 1050
q
Table Saw (10”)*1750 to 2000
q
Television200 to 500
q
Toaster1000 to 1650
Running Watts
*Allow three (3) times listed watts for starting device
8 BRIGGSandSTRATTON.COM
Essential Circuit Selection
When selecting the essential circuits that will be switched
to “Standby Power,” it is important that the sum of the
combined circuit loads does not exceed the wattage/
amperage capacity of the generator. To help you with your
selection of essential circuits, please consider the following:
• Add up the total wattage of all electrical devices to be
connected at one time. This total should NOT be greater
than the generator’s wattage capacity.
The rated wattage of lights can be taken from light
bulbs. The rated wattage of tools, appliances and
motors can usually be found on a data plate or decal
affixed to the device.
• If the appliance, tool or motor nameplate does not
list wattage, multiply volts times the ampere rating to
determine watts (Volts x Amps = Watts).
Some electric motors (induction types) require about
three times more watts of power for starting than for
running. This surge lasts for only a few seconds. Be
sure you allow for this high starting wattage when
selecting electrical devices that will be energized by the
home generator:
• Figure the watts required to start the largest motor.
• Add that to the total running watts of all other
connected loads.
This Briggs & Stratton home generator complies with the
following “stationary standby power rating”:
The standby power rating is applicable for supplying
power for the duration of normal power interruption.
No sustained overload capability is available for this
rating.
This rating is applicable to installations served by
a reliable normal utility source. This rating is only
applicable to variable loads with an average load factor
of 80% of the standby rating. The standby rating is
only applicable for optional standby power where the
generator set serves as the backup to the normal utility
source.
Use the wattage reference table provided and mark those
circuits you consider “critical” or “essential”. Make sure you
and your installer consider the system’s altitude above sea
level and the ambient temperature range when determining
total generator load.
In a utility outage, you need to ‘manage’ power distribution
by turning off non-essential loads. Some examples of non
essential loads are as follows:
• Pool pump
• Hot tub
• Electric hot tub and/or pool heaters
• Central air conditioners
• Electric hot water heaters
• Electric range and/or oven
• Arc welder
• Non essential electric heaters
Delivery Inspection
Carefully inspect the home generator for any damage that
may have occurred during shipment.
IMPORTANT: If loss or damage is noted at time of delivery,
have the person(s) making delivery note all damage on the
freight bill and affix his signature under the consignor’s
memo of loss or damage. If loss or damage is noted after
delivery, separate the damaged materials and contact the
carrier and your installer for claim procedures. Missing or
damaged parts are not warranted.
The home generator system is supplied with:
• Home generator
• Fully-serviced coolant system
• Fully-serviced oil/lubricating system
• UL569/CSA8.3-listed flexible fuel hook-up
• Installation and start-up manual
• Operator’s manual
• Engine operator’s manual
• Installation checklist
• Two access door keys
• One spare 15A fuse
• 10 Pole control panel connector
• Remote LED indicator kit (red LED/plate/screws)
To be supplied by Installer:
• 650 CCA 55 amp-hour starting battery
• Connecting wire and conduit
• Fuel supply valves/plumbing
• Various specialty tools/equipment
9
Features and Controls
Home Generator
Read this Operator’s Manual and Safety Rules before operating your generator.
Compare the illustrations with your generator to familiarize yourself with the locations of various controls and
adjustments. Save this manual for future reference.
A
B
R
P
C
DEF
G
J
Generator is pictured with access doors removed for clarity
A - Exhaust Port — High-performance muffler lowers engine
noise to comply with most residential codes.
B - Coolant Fill Door — Provides access for servicing engine
with oil and coolant.
C - Air Cleaner — Protects engine by filtering dust and
debris out of intake air.
D - Battery Door opening — Provides access to starting
battery and air cleaner.
E - Oil Dip Stick — Used to check the engine oil level.
F - Oil Fill Cap — Remove to service the engine with
recommended oil.
G - Engine Label — Identifies engine model and type.
H - Coolant Recovery Bottle — Provides visual indicator of
N
MH
L
K
J - Oil Filter — Filters engine oil to prolong system life.
K - Oil Drain Plug — Provided to facilitate oil changing.
L - Fuel Inlet — Fuel supply is connected here.
M - Unit Data Decal (located on base) — Identifies unit by
serial number.
N - Circuit Breaker Enclosure - Equipped with removable
bottom to assist with conduit connection.
P - Control Panel — Used for various test, operation and
maintenance functions. See System Control Panel on
the next page.
R - Control Panel Door opening — Provides access to
control panel.
NOTE: Circuit Breaker enclosure equipped with removable
bottom panel to assist with conduit connection.
engine coolant level.
10 BRIGGSandSTRATTON.COM
System Control Panel
Compare this Control Panel illustration with your generator to familiarize yourself with the location of these important controls:
FE
D
C
B
A
A - Circuit Breaker — Protects the system from shorts and
other over-current conditions. Must be ON to supply
power to the Automatic Transfer Switch.
B - Set Exercise Button — Used to set the exercise cycle
start time and day-of-the-week. Exercise cycle only
occurs in AUTO mode.
C - Manual Over-Ride Button — With system switch in
AUTO position, push the manual over-ride switch to
start the generator. To turn off the generator, push and
hold the manual over-ride switch again until engine
stops.
D - 15 Amp Fuse — Protects the home generator DC control
circuits. If the fuse has ‘blown’ (melted open) or was
removed, the engine cannot crank or start. Replace the
fuse using only an identical ATO 15A fuse.
E - System Switch — This two-position switch is the most
important control on the system and is used as follows:
• “AUTO” position is the normal operating position. If a
utility power outage is sensed, the system will start the
generator. When utility power is restored, AUTO lets
the engine stabilize internal temperatures, shuts off the
generator, and waits for the next utility power outage.
• “OFF” position turns off running generator, prevents
unit from starting and resets any detected faults.
F - Digital Display — Displays the total number of hours
the generator has been running and fault codes. Used
to schedule maintenance tasks and for troubleshooting
operational problems with the home generator. All fault
conditions are described in Fault Detection System.
11
D
C
B
A
E
Access Doors
The home generator is equipped with an enclosure that has
three access doors, as shown above. The doors are named
for a significant component located behind them, as follows:
A Fuel Inlet port (shown for reference)
B Control Panel door
C Exhaust opening (shown for reference)
D Coolant Fill door
E Battery door
WARNING
Contact with muffler area can result in serious
burns.
DO NOT touch hot parts and AVOID hot exhaust gases.
•
Allow equipment to cool before touching.
•
The enclosure also includes muffler and radiator access
panels, used for cleaning those components. Those panels
should remain closed at all other times.
Each home generator is equipped with two identical keys.
These keys fit the locks that secure the access doors.
To Open an Access Door:
1. Insert key into lock of access door handle you wish
to open and turn one quarter turn counterclockwise.
Remove key. Handle will remain unlocked until you relock it.
2. Grasp door’s handle and turn one quarter turn
counterclockwise to open.
3. Coolant Fill door is unlocked in the same manner. It can
be used for adding coolant or engine oil.
To Close an Access Door:
1. Close door and turn handle one quarter turn clockwise.
2. Insert key into lock in handle and turn one quarter turn
clockwise. Remove key.
NOTE: The Coolant Fill, Battery and Control Panel doors must
be installed whenever the unit is running.
12 BRIGGSandSTRATTON.COM
Operation
Important Owner’s Considerations
Engine Oil
NOTICE
Any attempt to crank or start the engine before it has been
properly serviced with the recommended coolant or oil will
result in equipment failure.
Refer to Maintenance in the Operator’s Manual and
•
engine manual for coolant and oil fill information.
Damage to equipment resulting from failure to follow this
•
instruction will void engine and generator warranty.
This engine is shipped from the factory pre-run and filled
with non-synthetic oil (API SL 10W-30W). This allows for
system operation in a wide range of temperature and climate
conditions. Before starting the engine, check oil level and
ensure that engine is serviced as described in the engine
operator’s manual.
NOTE: The use of multi-grade oil does not alter the required
oil change intervals described in the engine operator’s
manual.
Coolant System
This engine is shipped from the factory filled with a
50-50 mix of automotive (Dex-Cool™ orange) anti-freeze
and water. This will provide optimum year round protection
against freezing, boiling and corrosion. The coolant system
incorporates a water heater that operates when ambient
temperature is below 80ºF AND utility power is present at
the transfer switch. Before starting the engine, check coolant
level as described in the engine operator’s manual.
Battery
The installer must supply a sealed, rechargeable 12 Volt DC,
650 Cold Cranking Amps (CCA) 55 amp hour starting battery.
The battery may not be at full charge when installed. If
battery voltage is below 12 Volts, charge the battery. See
Battery in the Maintenance section for details.
15 Amp Fuse
The generator’s 15 Amp fuse is critical to correct system
operation. Your installer will ensure the fuse is properly
installed upon completion of the installation.
Automatic Operation
To select automatic operation, do the following:
1. Confirm 15 Amp fuse is installed in control panel.
2. Set the main distribution panel circuit breaker that
sends utility voltage to the transfer switch to ON.
3. Set the generator’s main circuit breaker to its ON
position.
4. Set the control panel System switch to AUTO.
CAUTION
With the system switch set to AUTO, the engine
may crank and start at any time without warning.
Such automatic starting normally occurs when
utility source voltage drops below a preset level
or during the normal exercise cycle.
To prevent possible injury that may be caused by such
•
sudden starts, always set the system switch to OFF if
performing maintenance on the system.
Remove the 15 Amp fuse before working on or around
•
the generator or transfer switch.
Checking Automatic Operation
To check the system for proper automatic operation, proceed
as follows:
1. Turn OFF main distribution panel circuit breaker
sending power to automatic transfer switch.
The engine will crank and start when utility voltage is lost
and the sensor has timed out. Let the system go through its
entire automatic operation sequence.
2. With generator output supplying its loads, turn ON main
distribution panel circuit breaker that supplies utility
power to Automatic Transfer Switch.
3. The automatic transfer switch will transfer loads back
to utility power after 5 minute minimum run time and
utility is restored.
4. The generator will run for an additional one minute for
engine cool down, then shut down.
NOTE: If utility is restored and generator does not shut down
after 10 minutes, set system switch to OFF and contact your
installer or local service center.
This completes the test procedures for automatic operation.
The home generator will now start automatically and will
supply power to the transfer switch when utility power is
lost.
13
Setting Exercise Timer
The home generator is equipped with an exercise timer that
will start and exercise the system once every seven days.
During this exercise period, the unit runs for approximately
20 minutes and then shuts down. Electrical load transfer
DOES NOT occur during the exercise cycle (unless an utility
power outage occurs).
A button on the control panel is labeled “Set Exercise” (see
System Control Panel). The specific day and the specific
time of day this button is pressed is programmed into the
control board memory. This date and time is then used to
automatically initiate the system exercise cycle. The “SET
EXERCISE” legend on the control panel will flash until the set
exercise cycle is set.
To perform the Set Exercise procedure:
1. Choose the day and time you want your home generator
to exercise.
2. On that day and time, press and hold down the “Set
Exercise” button for three seconds.
NOTE: “SET EXERCISE” will flash until the button is pressed
for three seconds, then “SET EXERCISE” will illuminate for
5 seconds, and finally turn off.
3. The unit will then start and run it’s 20 minute exercise
cycle.
For example, if you press the “Set Exercise” button on
Sunday morning at 10:00 AM, the unit will run an immediate
exercise cycle and an exercise cycle every following Sunday
at 10:00 AM (+/- 1/2 hour).
NOTE: “Set Exercise” will only work if the unit is in the
Automatic mode and this exact procedure is followed. The
exerciser will need to be re-set if the 15 Amp fuse is removed
or changed, or if the 12 Volt DC battery is disconnected.
If you want to change the day and time the unit exercises,
simply perform the “Set Exercise” procedure at the exact
weekday and time you want it to take place.
Maintenance
Servicing the System
To service the home generator system:
1. Remove 15 Amp fuse from control panel.
2, Set control panel System switch to OFF.
3. Set the generator’s main circuit breaker to its OFF
position.
4. Utility voltage is present. Disconnect power before
servicing by removing the two 10 Amp fuses from the
transfer switch.
Fault Detection System
The generator may have to run for long periods of time with
no operator present. For that reason, the system is equipped
with sensors that automatically shut down the generator
in the event of potentially damaging conditions, such as
low oil pressure, high temperature, over speed, and other
conditions.
The generator’s control panel has a digital display that shows
fault codes, like “FC_1”. The table below lists the detected
fault, the fault code as displayed on the control panel, and
the number of blinks seen on the remote LED indicator.
Fault DescriptionFault CodesLED Flashes
Low battery voltageFC_11
Low oil pressureFC_22
Low voltageFC_33
Engine fails to startFC_44
Low frequencyFC_55
Engine overspeedFC_66
High temperatureFC_77
Transfer switch faultFC_88
The remote LED indicator is installed at a convenient inside
location. The LED will remain lit when the generator is in
AUTO. Should a system fault be detected, the LED will turn
on and off in a series of blinks that identify the problem. The
blink pattern is repeated with a brief pause between each
series of blinks.
Reset Fault Detection System
The operator must reset the fault detection system each time
it activates. To do so, place the control panel System switch
in the OFF position for 5 seconds or more. Remedy the fault
condition, then return the home generator to service by
placing the system switch in the AUTO position.
14 BRIGGSandSTRATTON.COM
A description of each fault and suggested remedies are as
follows:
No LED - Discharged Battery
If there is a detected fault condition but the LED is not
blinking, this is because the battery is completely discharged.
To remedy the problem, remove the 15 Amp fuse and
disconnect the battery from the generator. Take the battery
to a local battery store for analysis. Replace the battery after
it has been fully recharged, connecting the NEGATIVE cable
last. Then install the 15 Amp fuse in the control panel.
NOTE: With the battery installed, all wiring to transfer switch
and home generator completed, utility power supplied to
the Automatic Transfer Switch, and the unit in AUTO mode,
the battery receives a trickle charge while the engine is not
running. The trickle charge is not able to recharge a battery
that is completely discharged. See Battery in Maintenance.
Low Battery Voltage (FC_1)
This fault is indicated by fault code FC_1 and one blink on the
LED indicator. This condition occurs if the generator cannot
start because the starting battery output power is below that
needed to crank the engine. Causes for this problem may be
a faulty battery or battery charge circuit.
To remedy the problem, contact your local service center to
check the battery charge output. Remove the 15 Amp fuse
and disconnect the battery from the generator. Take the
battery to a local battery store for analysis.
Replace the battery after it has been fully recharged,
connecting the NEGATIVE cable last. Then install the 15 Amp
fuse.
Low Oil Pressure (FC_2)
This fault is indicated by fault code FC_2 and two blinks on
the remote LED indicator. The unit is equipped with an oil
pressure switch which uses normally closed contacts held
open by engine oil pressure during operation. Should oil
pressure drop below the 8 psi range, switch contacts close
and the engine is shut down.
To remedy the low oil pressure condition, add the
recommended oil to the FULL mark on the dipstick.
If the low oil pressure condition still exists, the engine will
start, then shut down again. The fault code will appear and
the LED will flash. In this case, contact a Briggs & Stratton
Authorized Dealer.
Low Voltage (Generator, FC_3)
This fault is indicated by fault code FC_3 and three blinks on
the LED indicator. This condition is caused by a restriction in
the fuel flow, a broken or disconnected signal lead, a failed
alternator winding, the control panel circuit breaker is open,
or the generator is overloaded.
To remedy the problem, contact your installer or a Briggs &
Stratton Authorized Dealer.
Engine Fail To Start (FC_4)
This fault is indicated by fault code FC_4 and four blinks on
the LED indicator. This feature prevents the generator from
damaging itself if it continually attempts to start in spite
of another problem, such as no fuel supply. Each time the
system is directed to start, the unit will crank for 10 seconds,
pause for 10 seconds, and repeat. If the system does not
begin producing electricity after approximately 2 minutes, the
unit will stop cranking and the LED will blink.
Check to make sure the generator’s main circuit breaker is in
the ON position in order for the sensing leads to verify that
the unit is running.
The most likely cause of this problem is no fuel supply.
Check the internal and external fuel shut off valves to
ensure they are fully open. Other causes could be failed
spark plug(s), failed engine ignition, or the engine air filter
is clogged. You may need to contact your installer for
assistance if you can’t remedy these problems.
Low Frequency (FC_5)
This fault is indicated by fault code FC_5 and five blinks on
the LED indicator. This feature protects devices connected
to the transfer switch by shutting the generator down if
the engine runs slower than 55 Hz for three seconds. This
condition is caused by a failed engine component or by
excessive loads on the generator. To remedy the problem,
contact your installer or a Briggs & Stratton Authorized
Dealer.
Engine Overspeed (FC_6)
This fault is indicated by fault code FC_6 and six blinks on
the LED indicator. This feature protects devices connected
to the transfer switch by shutting the generator down if
the engine happens to run faster than the preset limit. The
overspeed fault is detected as follows:
• If the generator output frequency is 65-70 Hz, after
three seconds, the generator will shut down.
• If the generator output frequency is greater than 70 Hz,
the generator will shut down immediately.
This condition is caused by a failed engine component. To
remedy the problem, contact your installer or a Briggs &
Stratton Authorized Dealer.
15
High Temperature (FC_7)
This fault is indicated by fault code FC_7 and seven blinks on
the LED indicator. The contacts of the coolant temperature
switch are normally open. If the engine coolant temperature
exceeds approximately 115.5°C (240°F), the fault is detected
and the engine shuts down.
Common causes for this condition include running the
unit with all access doors removed, obstructed air inlet or
exhaust port, low oil or coolant level, or debris in the engine
compartment or radiator.
To resolve the problem, let the engine cool down and remove
any accumulated debris and obstructions. Ensure that the
access doors are installed whenever the unit is running.
Transfer Switch Fault (FC_8)
This fault is indicated by fault code FC_8 and eight blinks on
the LED indicator (if transfer switch is equipped with fault
detection). The most likely cause of this fault is a blown fuse
in the transfer switch.
To remedy the problem, contact your installer or a Briggs &
Stratton Authorized Dealer.
Generator Maintenance
The generator warranty does not cover items that have been
subjected to operator abuse or neglect. To receive full value
from the warranty, the operator must maintain the system as
instructed in the engine operator’s manual.
All adjustments should be made at least once each season.
Follow the requirements in the engine operator’s manual.
Generator maintenance consists of keeping the unit clean.
Operate the unit in an environment where it will not be
exposed to excessive dust, dirt, moisture or any corrosive
vapors. Cooling air louvers on the enclosure must not
become clogged with snow, leaves, or any other foreign
material.
Check the cleanliness of the unit frequently and clean when
dust, dirt, oil, moisture or other foreign substances are
visible on its exterior/interior surface.
NOTE: DO NOT use direct spray from a garden hose to clean
generator. Water can enter the engine and generator and
cause problems.
Engine Maintenance
An engine manual was packaged with this system. Please
refer there for all engine-related maintenance topics.
However, proper engine cooling and lubrication are so
important we give them special mention here.
Engine Oil
The system is filled with the recommended non-synthetic oil
(API SL 10W-30W). This allows for system operation in a
wide range of temperature and climate conditions.
NOTE: Refer to the engine operator’s manual for
recommended oil change intervals.
Shown here is the oil drain location (B) and the oil filter (A).
A
B
Changing Engine Oil
CAUTION
Avoid prolonged or repeated skin contact with used
motor oil.
Used motor oil has been shown to cause skin cancer in
•
certain laboratory animals.
Thoroughly wash exposed areas with soap and water.
•
KEEP OUT OF REACH OF CHILDREN. DON’T
POLLUTE. CONSERVE RESOURCES. RETURN
USED OIL TO COLLECTION CENTERS.
1. Disconnect the negative battery terminal from battery.
2. Change oil while the engine is still warm from running,
as described in the engine operator’s manual.
NOTICE
Any attempt to crank or start the engine before it has been
properly serviced with the recommended oil will result in
equipment failure.
Refer to Maintenance and engine manual for oil fill
•
information.
Damage to equipment resulting from failure to follow this
•
instruction will void engine and generator warranty.
To fill your engine with oil:
Follow the oil grade recommendation and oil fill instructions
given in the engine operator’s manual.
To make the task of adding oil more convenient, we
recommend use of a funnel attached to a length of tubing
long enough to reach from the Coolant Fill door to the oil fill
opening on the engine valve cover.
16 BRIGGSandSTRATTON.COM
Engine Coolant System
With the engine cold, check the coolant level in the coolant
reservoir, seen inside the Control Panel door. Maintenance
instructions for engine coolant are found in the engine
operator’s manual.
5. Connect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-)).
6. Ensure hardware on both positive and negative battery
terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
Battery
Charging the Battery
If it is necessary to charge the battery, proceed as follows:
1. Set generator’s system switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Disconnect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-).
NOTICE
Failure to disconnect negative battery cable will result in
equipment failure.
DO NOT attempt to jump start the battery.
•
Damage to equipment resulting from failure to follow this
•
instruction will void warranty.
4. Charge battery with battery charger at 2 Amps until
battery holds 12 Volts.
WARNING
Storage batteries give off explosive hydrogen
gas during recharging.
Slightest spark will ignite hydrogen and cause
explosion.
Battery electrolyte fluid contains acid and is
extremely caustic.
Contact with battery contents will cause severe
chemical burns.
A battery presents a risk of electrical shock and
high short circuit current.
DO NOT dispose of battery in a fire.
•
DO NOT allow any open flame, spark, heat, or lit cigarette
•
during and for several minutes after charging a battery.
DO NOT open or mutilate the battery.
•
Wear protective goggles, rubber apron, and rubber
•
gloves.
Remove watches, rings, or other metal objects.
•
Use tools with insulated handles.
•
NOTE: With the battery installed and utility power available
to the transfer switch, the battery receives a trickle charge
whenever the engine is not running. It may take up to
72 hours to fully charge a discharged battery with the trickle
charge. The trickle charge is not able to recharge a battery
that is completely discharged.
CAUTION
Installing the control panel’s 15A fuse could
cause the engine to start.
DO NOT install this fuse until all plumbing and wiring has
•
been completed and inspected.
8. Set generator’s system switch to AUTO.
9. Reset exercise timer. See Setting Exercise Timer.
Servicing the Battery
If it is necessary to service the battery, proceed as follows:
1. Set control board System switch to OFF.
2. Remove 15 Amp fuse from control panel.
3. Service or replace battery as required.
4. Connect red battery cable to battery positive terminal
(indicated by POSITIVE, POS, or (+)).
5. Connect negative battery cable to negative battery
terminal (indicated by NEGATIVE, NEG, or (-).
6. Ensure hardware on both positive and negative battery
terminals is secure.
7. Reinstall 15 Amp fuse in control panel.
8. Set generator’s system switch to AUTO.
9. Reset exercise timer. See Setting Exercise Timer.
To Clean the Generator
NOTICE
Improper treatment of generator can damage it and
shorten its life.
DO NOT expose generator to excessive moisture, dust,
•
dirt, or corrosive vapors.
DO NOT insert any objects through cooling slots.
•
• Use a damp cloth to wipe exterior surfaces clean.
• Use a soft, bristle brush to loosen caked on dirt, oil,
etc.
• Use a vacuum cleaner to pick up loose dirt and debris.
• Use low pressure air (not to exceed 25 psi) to blow
away dirt. Inspect cooling air slots and openings on
the generator. These openings must be kept clean and
unobstructed.
17
When Calling the Factory
You must have the following information at hand if it is
necessary to contact a local service center regarding service
or repair of this unit:
1. Obtain the unit Model Number and Serial Number from
the unit data label. See Controls for location of the label
or refer to the information recorded on the inside front
cover of the Installation Manual.
2. Obtain the engine identification numbers from the
engine label. See the engine operator’s manual for
location of this information. Please note that several
different home generator systems are described in this
manual, so your unit’s appearance may vary from that
presented herein.
Storage
The Briggs & Stratton home generator is designed for
long term service as a backup generator. As such, there
is no need to take any storage precautions. However, if it
becomes necessary to take the system out of service for an
extended period, call Briggs and Stratton Technical Services
at (800) 743-4115, between 8:00 AM and 5:00 PM CT for
specific recommendations. Refer to the engine operator’s
manual for additional information
18 BRIGGSandSTRATTON.COM
Troubleshooting
ProblemCauseCorrection
Engine is running, but no AC output is
available.
Engine runs good at no-load but “bogs
down” when loads are connected.
Engine will not start; or starts and runs
rough.
Engine shuts down during operation.
Loss of power on essential circuits.
1. Circuit breaker open or defective.
2. Fault in generator control panel.
3. Poor wiring connections or
defective transfer switch.
1. Short circuit in a connected load.
2. Generator is overloaded.
3. Shorted generator circuit.
4. Fuel pressure or mixture is
incorrect.
5. Kinked fuel line.
1. 15 Amp fuse missing or blown.
2. Fuel supply turned off or depleted.
3. Failed battery.
4. Fuel pressure is incorrect
1. Fuel supply turned off or depleted.
2. Fault indicator blinking.
1. Generator circuit breaker is open.
2. Transfer switch problems.
1. Reset or replace circuit breaker.
2. Contact local service facility.
3. Check and repair.
1. Disconnect shorted electrical load.
2. See Essential Circuits.
3. Contact local service facility.
4. See Gaseous Fuel System in the
Installation Manual.
5. Remove kink. Replace if necessary.
1. Install (new) 15 Amp fuse. See
System Control Panel.
2. Open fuel valve(s); check propane
tank.
3. Replace battery.
4. See Gaseous Fuel System in the
Installation Manual.
1. Check fuel valves, fill propane tank.
2. Count blinks and refer to Fault Detection System.
1. Reset circuit breaker.
2. See the transfer switch manual.
19
BRIGGS & STRATTON HOME POWER PRODUCTS GROUP, LLC
STANDBY GENERATOR OWNER WARRANTY POLICY
Effective January 1, 2008 replaces all undated Warranties and all Warranties dated before January 1, 2008
LIMITED WARRANTY
Briggs & Stratton Power Products Group, LLC will repair or replace, free of charge, any part(s) of the equipment that is defective in material or
workmanship or both. Travel expenses will be reimbursed as specified under the Briggs and Stratton Warranty Guidelines document to authorized
Briggs & Stratton dealers for performing warranty repair work. This warranty is effective for the time periods and subject to the conditions stated below.
For all warranty service, find the nearest Authorized Service Dealer in our dealer locator map at BRIGGSandSTRATTON.COM.
THERE IS NO OTHER EXPRESS WARRANTY. IMPLIED WARRANTIES, INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE, ARE LIMITED TO ONE YEAR FROM PURCHASE, OR TO THE EXTENT PERMITTED BY LAW. ANY AND ALL IMPLIED WARRANTIES ARE
EXCLUDED. LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMAGES ARE EXCLUDED TO THE EXTENT EXCLUSION IS PERMITTED BY LAW. Some
states or countries do not allow limitations on how long an implied warranty lasts, and some states or countries do not allow the exclusion or limitation
of incidental or consequential damages, so the above limitation and exclusion may not apply to you. This warranty gives you specific legal rights and
you may also have other rights which vary from state to state or country to country.
WARRANTY PERIOD
Consumer Use
Commercial Use
4 years or 2000 hours, whichever comes first
2 years or 1000 hours, whichever comes first. First year 100% full
coverage; second year alternator and engine only
Rental Use
The warranty period begins on the date of purchase by the first retail consumer or commercial end user, and continues for the period of time stated above.
“Consumer use” means personal residential household use by a retail consumer. “Commercial use” means all other uses, including use for commercial
or other income producing purposes. “Rental use” means any use of this product in a temporary or semi-permanently installed rental application. Once
equipment has experienced commercial or rental use, it shall thereafter be considered as commercial or rental use for purposes of this warranty.
NO WARRANTY REGISTRATION IS NECESSARY TO OBTAIN WARRANTY ON BRIGGS & STRATTON PRODUCTS. SAVE YOUR PROOF OF PURCHASE
RECEIPT. IF YOU DO NOT PROVIDE PROOF OF THE INITIAL PURCHASE DATE AT THE TIME WARRANTY SERVICE IS REQUESTED, THE MANUFACTURING
DATE OF THE PRODUCT WILL BE USED TO DETERMINE THE WARRANTY PERIOD.
None
ABOUT YOUR WARRANTY
We welcome warranty repair and apologize to you for being inconvenienced. Any Authorized Service Dealer may perform warranty repairs. Most warranty
repairs are handled routinely, but sometimes requests for warranty service may not be appropriate. For example, warranty service would not apply if
equipment damage occurred because of misuse, lack of routine maintenance, and shipping, handling, warehousing or improper installation. Similarly, the
warranty is void if the manufacturing date or serial number(s) on the equipment has been removed or the equipment has been altered or modified. During the
warranty period, the Authorized Service Dealer, at its option, will repair or replace any part that, upon examination, is found to be defective under normal use
and service. This warranty will not cover the following repairs and equipment:
• Normal Wear: Outdoor Power Equipment and engines, like all mechanical devices, needs periodic parts and service to perform well. This warranty
does not cover repair when normal use has exhausted the life of a part or the equipment.
• Installation and Maintenance: This warranty does not apply to equipment or parts that have been subjected to improper or unauthorized installation or
alteration and modification, misuse, negligence, accident, overloading, overspeeding, improper maintenance, repair or storage so as, in our judgment,
to adversely affect its performance and reliability.
• Exclusions: For further clarification of engine warranty policies and procedures, contact Power Solutions Incorporated at 1-630-350-9400 or visit www.
PSIengines.com. IMPCO Technologies is the holder of the Manufacturer of Record of all Environmental Protection Agency (EPA) compliance issues
related to the use and performance of the engine.
This warranty excludes wear items such as engine oil, oil gauges, o-rings, filters, fuses, spark plugs, or anti-freeze, starting batteries, etc., or damage
or malfunctions resulting from accidents, abuse, modifications, alterations, or improper servicing or freezing or chemical deterioration. Accessory parts
are excluded from the product warranty. This warranty excludes failures due to acts of God and other force majeure events beyond the manufacturers
control. Also excluded is used, reconditioned, and demonstration equipment; equipment used for prime power in place of utility power and equipment
used in life support applications.
Warranty terms continue on next page.
20 BRIGGSandSTRATTON.COM
Other Exclusions:
1. Any costs for adjustments, loose or leaking connections or clamps, installation or start-up operations fuel system cleaning and obstruction (due to
chemical, dirt, carbon, lime, and so forth) and any failures caused by contaminated fuels, anti-freeze or oil, etc.
2. Units sold for primary power applications as defined by the U.S. & Canadian National Electric Codes whether utility power exists or where utility power
does not normally exist
3. Any rental unit applications
4. Any loss of revenue that is a direct or indirect result of the failure of this unit
5. Failures caused by any external forces or Act of God such as, but not limited to freezing, theft, fire, collision, wars or riots, vandalism, lightning, earth
quake wind storm, hail, volcanic eruption, water or flood damage, tornados, hurricanes, terrorist acts or nuclear holocaust
6. Any incidental, consequential or indirect damages caused by defects in materials or workmanship or any delay in repair of replacement of the defective
part(s)
7. Failure due to misapplication or misrepresentation
8. Telephone, satellite, facsimile, cell phone, internet or any other communication expenses
9. Overtime, holiday or emergency labor expenses
10. Any mode of transportation deemed as abnormal in our judgment such as planes, ferries, railroad, buses, helicopters, snowmobiles, snow-cats, offroad vehicles, etc.
11. Any and all expenses incurred investigating performance complaints unless defective BSHPP materials and/or workmanship were the direct cause of the
problem
12. Overnight freight costs for replacement parts
13. Other rental equipment used while warranty repairs are being performed (i.e., generators, material handling equipment, etc.)
14. Bodily injuries including death which results from the product’s failure 204949E, Rev. B, 1/17/2008
BRIGGS & STRATTON POWER PRODUCTS GROUP, LLC
JEFFERSON, WI, USA
21
Loading...
+ 47 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.