Bradford White RG140T*N, RG240T*N, RG230S*N, RG230T*N, RG240S*N Service Manual

...
Flammable Vapor Ignition Resistant
Water Heaters
SERVICE
MANUAL
Troubleshooting Guide
and Instructions for Service
(To be performed ONLY by
qualified service providers)
Manual 238-51542-00B REV 10/18
by This Manual:
RG130T*(N,X) RG140T*(N,X) RG150T(N,X) LG250H65*(N,X) RG230S*(N,X) RG230T*(N,X) RG240S*(N,X) RG240T*(N,X) RG250H*(N,X) RG250L*(N,X) RG250S*(N,X) RG250T*(N,X) (*) Denotes Warranty Years
Save this manual for future reference
Introduction 3 - - -
Troubleshooting Chart 4 - - -
Inner Door Gasket Removal, Inspection, and Replacement 9 RG-I
Thermocouple/Thermopile Testing and Replacement 12 RG-II
The Bradford White
®
Page Service Procedure
Pilot Assembly Inspection Cleaning and Replacement 15 RG-III
Piezo Igniter, Electrode Testing and Replacement 16 RG-IV
White Rodgers Gas Valve Testing and Replacement 17 RG-V
Honeywell Gas Control Testing, Disassembly, and Replacement 22 RG-VI
Burner Operation Inspection, Adjustment, Cleaning and Replacement 28 RG-VII
Resettable Thermal Switch Testing and Replacement 31 RG-VIII
ScreenLok
®
Flame Arrestor Cleaning
33 RG-IX
DipTube and Anode Inspection and Replacement 34 RG-X
Generic Parts List 36 - - -
2
2
INTRODUCTION
The Bradford White DEFENDER Safety System
®
The Bradford White DEFENDER Safety System®was designed to resist the ignition of flammable vapors that can occur outside of the water heater. Use and installation are nearly identical to previous versions of atmospherically fired and vented water heaters. A number of exclusive design features are incorporated in the system that will require additional knowledge on the part of the qualified service provider. The following information will instruct service professionals on the function, proper diagnosis and repair of water heaters employing the Bradford White DEFENDER Safety System.
How the Safety System Works
During normal operation, air for combustion is drawn into the water heater through the opening in the jacket. This air travels down and around the combustion chamber and enters through holes in the very bottom of the corrosion-resistant combustion chamber. The air then travels up through the oriented flame arrestor plate louvers, where the velocity of the air is increased and its direction altered. The air then mixes in a normal manner with the supplied gas and is efficiently combusted, producing very low NOx emissions.
In the case where trace amounts of flammable vapors are present in the air flowing into the combustion chamber, the vapors are harmlessly ignited by the burner / pilot flame. If flammable vapors are in sufficient quantity to prevent normal combustion, the burner/pilot flame is shut down.
Should the flammable vapors continue to the burner, the flame arrestor plate prevents the flames from traveling backwards and igniting vapors outside of the combustion chamber. The calibrated, multipurpose thermal switch recognizes this and shuts down the pilot and main burner. This switch also deactivates the burner and pilot in the unlikely event of restricted airflow caused by severe lint, dust or oil accumulation on the arrestor plate.
3
3
White Rodgers Gas Control Troubleshooting Chart
Flammable Vapor Ignition Resistant Water Heaters
Symptom Probable Cause Corrective action
1.
Pilot will not light.
Pilot will not stay lit when button is released.
No incoming gas or too low gas pressure.
2.
Gas control knob set to wrong position.
3.
Pilot light button not being fully depressed when attempting to light pilot.
4.
Pilot orifice or pilot tube is obstructed or kinked.
5.
Pilot electrode not sparking to pilot.
6.
Piezo igniter not functioning.
1.
Poor thermocouple connection at combination thermostat/gas valve.
2.
Thermocouple not fully engaged in pilot assembly bracket.
3.
Pilot flame is not fully enveloping the thermocouple “hot” junction.
4.
Weak or defective thermocouple.
5.
Open ECO on combination thermostat/ gas valve.
6.
Defective magnet in combination thermostat/gas valve.
7.
Resettable thermal switch has opened.
1.
Turn on gas supply and/or check line pressure.
2.
Review lighting instruction. Set combination/thermostat gas valve to correct position.
3.
Review lighting instruction. Fully depress pilot lighting button.
4.
Clean, repair or replace.
5.
Verify correct electrode position. Replace pilot assembly.
6.
Replace piezo igniter.
1.
Check connection at combination thermostat/gas valve. Proper tightness should be finger tight plus ¼ turn.
2.
Inspect thermocouple to ensure that it is fully engaged into pilot bracket.
3.
Adjust tip of thermocouple to be fully engulfed by pilot flame.
4.
Check thermocouple and replace if necessary.
5.
Check ECO continuity and replace combination thermostat/gas valve if necessary.
6.
Check magnet operation and replace combination thermostat/gas valve if necessary.
7.
Determine cause of switch activation. To reset, depress button on resettable thermal
Service
Procedure
1.
See Service Procedure RG-V, Page 12.
2.
See Service Procedure RG-III, Page 10.
3.
See Service Procedure RG-III, Page 10.
4.
See Service Procedure RG-IV, Page 11.
1.
See Service Procedure RG-II, Page 8.
2.
See Service Procedure RG-V, Page 14.
3.
See Service Procedure RG-V, Page 13.
switch located on inner door.
1.
Adjust temperature dial on combination thermostat/gas valve.
2.
Check temperature dial setting on combination thermostat/gas valve.
3.
Check gas supply and line pressure.
4.
Check combination thermostat/gas valve for proper operation, replace if necessary.
1.
See installation and operation manual.
2.
See Service Procedure RG-V, Page 12.
3.
See Service Procedure RG-V, Page 12.
Pilot will light but the main burner will not come on.
1.
Combination thermostat/gas valve set too low for desired water temperature.
2.
Combination thermostat/gas valve temperature is satisfied.
3.
Insufficient gas supply or low gas pressure.
4.
Combination thermostat/gas valve has wide differential or is out of calibration.
4
4
White Rodgers Gas Control Troubleshooting Chart
Flammable Vapor Ignition Resistant Water Heaters
Symptom Probable Cause Corrective action
Pilot goes out periodically (after heating cycles, once a day, once a week etc.)
Not enough hot water.
1.
Insufficient combustion air supply.
2.
Incorrect, clogged vent system/vent terminal or location.
3.
Inconsistent gas supply or gas pressure.
4.
Combination thermostat/gas valve set too low for desired water temperature.
5.
Cold inlet water temperature is very cold.
6.
High demand periods.
7.
Incorrectly sized water heater for application.
8.
Combination thermostat/gas valve is out of calibration/not functioning.
9.
Out of spec dip tube is diluting hot water with cold water.
1.
Verify adequate combustion air is available to the unit. Check and clear Jacket slot openings of any dirt, dust, restrictions or other obstructions. Inspect flame arrestor plate and clean with stiff bristled brush and/or vacuum to remove any debris accumulation.
2.
Check venting for proper sizing and proper operation
3.
Check gas supply and line pressure.
1.
Check dial on combination thermostat/gas valve.
2.
Extremely cold water going into the heater will decrease the amount of hot water produced. It may be necessary to temper incoming water supply.
3.
Adjust high demand usage.
4.
Contact Plumbing professional.
5.
Check combination thermostat/gas valve for proper operation, replace if necessary.
6.
Inspect dip tube and replace if necessary.
Service
Procedure
1.
See Service Procedure RG­VIII, Page 22.
2.
See Service Procedure RG-V, Page 14.
1.
See Service Procedure RG-V, Page 12.
2.
See Service Procedure RG-IX, Page 23.
5
5
g
g
V
Observe green LED indicator on Gas Control. Status flash codes are displayed with a three second pause before repeating. Check and repair the system as noted in the troubleshooting table below.
Honeywell V1 Gas Control Troubleshooting Chart
Flammable Vapor Ignition Resistant Water Heaters
LED Status Control Status Probable Cause Service Procedure
If the pilot will not stay lit None (LED not on or flashing)
Pilot assembly is not lit
Gas control is not powered. Light Pilot.
replace pilot assembly. If
problem persists replace
as control.
1.
One flash and three second pause
LED on continuously (solid)
If setpoint knob is in “PILOT” position then pilot flame is detected. Turn setpoint knob to desired setting.
2.
If the setpoint knob is already at the desired setting, the water heater is
satisfied. Setpoint knob has been recently turned to the “OFF” position. Wait until LED goes out before attemptin
to relight.
1.
Gas control is powered and waiting for setpoint knob to be turned to a water temperature setting.
2.
Water heater is satisfied and operating normally.
Setpoint knob was turned to “OFF” position.
Normal operation.
LED will not go out and the control will function normally the is lit.
Two flashes and three second pause
Three flashes and three second pause
6
Weak pilot signal detected. System will reset when pilot flame is sufficient.
Insufficient water heating. System will reset.
1.
Thermopile failure.
2.
Unstable pilot.
3.
Pilot tube block or restricted.
1.
Thermal sensor out of calibration.
2.
Faulty gas control.
1.
See service procedure IV
2.
See service procedure II
3.
See service procedure II
Replace gas control.
6
g
y
Observe green LED indicator on Gas Control. Status flash codes are displayed with a three second pause before repeating. Check and repair
Honeywell V1 Gas Control Troubleshooting Chart
Flammable Vapor Ignition Resistant Water Heaters
the system as noted in the troubleshooting table below.
LED Status Control Status Probable Cause Service Procedure
Four flashes three second pause
Five flashes and three second pause
Six flashes and three second pause
Seven flashes and three second pause
Eight flashes and three second pause
Excessive tank temperature. System must be reset.
Temperature sensor fault.
Water leak detected by accessory module
Gas control electronic fault detected.
Standing pilot remains on while setpoint knob is in “OFF” position.
1.
Temperature sensor out of calibration.
2.
Faulty gas control.
1.
Damage to the
temperature sensor.
2.
Temperature sensor resistance out of ran
e.
Excessive amount of water in drain pan/water dam.
1.
Control needs to be reset.
2.
Control is wet or ph
sically damaged.
Pilot valve stuck in open position.
Replace gas control
Replace gas control
1. Check T&P valve.
2. Check all water fittings.
3. Pressurize and leak test tank.
1. Reset gas control
2. Replace gas control.
Replace gas control
7
7
Honeywell V2 Gas Control Troubleshooting Chart
Flammable Vapor Ignition Resistant Water Heaters
Observe colored LED indicator on Gas Control. Status flash codes are displayed with a three second pause before repeating. Check and repair the system as noted in the troubleshooting table below.
LED Status Control Status Probable Cause Service Procedure
If the pilot will not stay lit replace pilot assembly. If problem persists, replace gas control.
Normal operation.
Normal operation.
1. See service procedure IV.
2. See service procedure II.
3. See service procedure II.
None (LED not on or flashing)
One flash every four seconds (LED green)
One flash every second (LED green)
Two flashes (LED yellow)
Millivolt power is not present. Light pilot.
Not an error. Indicates pilot is lit and main burner is off.
Not an error. Indicates main valve is open and main burner is lit.
Low thermopile voltage; main valve not turned ON.
Gas valve is functioning normally. Gas valve is not powered. Light pilot.
You can now turn the know to a desired setpoint temperature
None. Control will automatically shut main burner off when water temperature reaches the setpoint temperature.
Check thermopile and its connections. Check pilot flame.
Check the valves and the water temperature sensor. Reduce the
Four flashes (LED red)
Temperature cut-out limit reached.
water temperature setpoint. Thoroughly check out main valve operation and water
Replace gas control
temperature control before walking away. Check water temperature sensor
Five flashes (LED red)
Water temperature sensor failure.
and its connection for open circuits, shorts, or differences in resistance between the two sensor
Replace gas control
elements.
1. Check T&P valve.
Six flashes (LED red)
Solid ON (LED red)
8
Tank leakage detected by accessory module.
Not an error-indicates that the control is in OFF mode.
Control recovers after receiving message from accessory module.
None; wait until LED turns off if you want to restart system.
2. Check all water fittings.
3. Pressurize and leak test tank.
LED will go out and the control will function normally the pilot is lit.
8
Inner Door Removal Procedure
)
SERVICE PROCEDURE RG-I
Inner Door/Gasket Removal,
Inspection, and Replacement
Step 1.
Rotate knob of the combination thermostat/gas valve to the “OFF” position.
Step 2.
Step 3.
Remove outer jacket burner access door.
Inner Door Removal.
a) Disconnect resettable thermal switch wire leads
(leading from gas control/gas valve). b) Remove (2) hex drive screws from right side inner door. c) Remove (2) hex drive screws from flange section of inner door. d) Remove (2) hex drive screws from left side inner door.
e
Remove inner door and inspect per step 4.
Step 4. Fully inspect inner door gaskets for the following:
>Tears >Missing material >Cracks
>Other imperfections that will inhibit proper seal >Gasket adhesion to inner door >Material left on combustion chamber (around opening)
>Dirt or debris
If the gasket is not affected by any of the above, gasket replacement is not required. If replacement is required, proceed to Inner Door Gasket Replacement Procedure.
Inner Door Gasket Replacement Procedure
RECOMMENDED
PATTERN FOR RTV
SEALANT
PLACE FLANGE
SECTIONS FIRST
EXPANDED
VIEW
GASKET OVERLAP MUST BE AS SHOWN ±1/32"
VIEW WITH
GASKETS IN
PLACE
ENLARGED VIEW OF FLANGE AREA
9
9
SERVICE PROCEDURE RG-I
Inner Door/Gasket Removal,
Inspection, and Replacement
Installation of Inner Door with Gasket
Step 5.
Step 6.
Step 7.
Clean any residual gasket residue or other debris from combustion chamber surface before installing the inner door/gasket assembly. Place the left side inner door into position first. Firmly position the radiused channel of the inner door around the feedline. Using the (2) hex drive screws from step 3d, secure left side inner door in place
DO NOT OVER TIGHTEN SCREWS.
Position thermocouple, pilot tube and Piezo wire against left side inner door flange gasket.
DO NOT ROUTE THROUGH RADIUSED CHANNEL WITH FEEDLINE.
WARNING
Stripped fastener connections may allow
for seal breach of inner door. A seal
breach may result in a fire or explosion
causing property damage, personal injury
or death. Do not over tighten screws in
steps 8, 10 and 11.
If a fastener connection is stripped,
contact the manufacturer listed on the
water heater rating plate.
10
10
SERVICE PROCEDURE RG-I
Inner Door/Gasket Removal, Inspection
Replacement and Reinstallation
Step 8.
Step 9.
Firmly place right side inner door flange against the left side inner door flange and secure with (2) hex drive screws from step 3c. DO NOT OVER TIGHTEN SCREWS.
Align right side inner door to combustion chamber and verify the fastener holes of the combustion chamber are aligned with the right side inner door slotted opening. Verify seal integrity around combustion opening. Secure right side inner door using (2) hex drive screws from step 3b. DO NOT OVER TIGHTEN SCREWS. Verify both left and right sides of the inner door are properly positioned and sealed against the combustion chamber.
Step 10.
Step 11.
Step 12.
Reconnect lead wires from combination thermostat/gas valve to resettable thermal switch (See photo in step 3). Note, wire terminations are interchangeable with either resettable thermal switch connections.
Replace outer jacket burner access door.
To resume operation, follow the instructions located on th e lighting instruction label or the lighting instructions located in the installation and operation manual.
11
11
SERVICE PROCEDURE RG-II
Thermocouple/Thermopile Testing and
Replacement
CLOSED CIRCUIT THERMOCOUPLE TESTING (White Rodgers Control)
Step 1.
Closed circuit testing is the preferred method for testing thermocouple. Following the lighting instruction label on the heater, proceed to light the pilot and allow to operate for three minutes. If the pilot will not stay lit, hold the pilot button (located on the combination thermostat/gas valve) down during this test.
Step 2.
Using a multimeter capable of measuring millivolts, connect one lead using an alligator clip to the copper sheath of the thermocouple, use the second lead of the multimeter to probe the top terminal located at the back of the combination thermostat/gas valve.
Step 3.
If meter reads 10 mv or higher, the thermocouple is OK. If reading is below 10 mv, replace the thermocouple.
12
12
Loading...
+ 28 hidden pages