Bradford White RG1D30T*(N, X), RG1D40S*(N, RG1D40T*(N, RG1D50T*(N Service Manual

...
Residential D Series
Gas Water Heaters
SERVICE
MANUAL
Troubleshooting Guide
and Instructions for Service
(To be performed ONLY by
qualified service providers)
by This Manual:
RG1D30T*(N,X) RG1D40S*(N,X) RG1D40T*(N,X) RG1D50T*(N,X) RG2D40S*(N,X) RG2D50S*(N,X) (*) Denotes Warranty Years
Manual 2385163700A 10/15
Save this manual for future reference
The Bradford White
2
Residential D Series
Gas Water Heaters
Table of Contents
Page D Service Procedure
Introduction ................................................................................................................................ 4 ---
How to Use This Manual .......................................................................................................... 5 ---
Tools Required for Service ....................................................................................................... 5 ---
Specifications ............................................................................................................................. 6 ---
Control Timings ......................................................................................................................... 7 ---
Sequence of Operation .............................................................................................................. 8 ---
Troubleshooting ......................................................................................................................... 11 ---
Burner Inspection, Cleaning & Replacement ......................................................................... 13 D-I
Pilot Testing, Cleaning & Replacement .................................................................................. 15 D-II
Damper Removal & Installation .............................................................................................. 16 D-III
Gas Control Testing & Replacement ....................................................................................... 17 D-IV
Flammable Vapor Device Testing and Replacement ............................................................. 20 D-V
Diptube Inspection & Replacement ......................................................................................... 21 D-VI
Anode Inspection & Replacement ........................................................................................... 22 D-VII
Flue Baffle Inspection & Replacement .................................................................................... 23 D-VIII
Inner Door Removal, Inspection & Replacement .................................................................. 25 D-IX
115 VAC Circuit Trace ............................................................................................................. 28 D-X
Damper Relay Installation ........................................................................................................ 29 D-XI
Resettable Thermal Switch, Inspection & Replacement ........................................................ 32 D-XII
ScreenLok
®
Flame Arrestor Cleaning ..................................................................................... 34 ---
Glossary of Terms ..................................................................................................................... 35 ---
Parts List ..................................................................................................................................... 36 ---
2
Res. D Series
3
WARNING:
If the information in these instructions is not followed exactly, a fire or explosion may result causing property damage, personal injury, or death.
IMPORTANT
Before proceeding, please inspect the
water heater and its components for
possible damage. DONOT install any
water heater with damaged
components. If damage is evident then please contact the supplier where the water heater was purchased or the
manufacturer listed on the rating plate
for replacement parts.
WHATTODOIFYOUSMELLGAS!
x
Donottrytolightanyappliance.
x
Donottouchanyelectricalswitch;donotuseany
phoneinyourbuilding.
x
Immediatelycallyourgassupplierfromaneighbor'sphone. Followthegassupplier'sinstructions.
x
Ifyoucannotreachyourgassupplier,callthefire
department.
Installationandservicemustbeperformedbyaqualified installer,serviceagencyorthegassupplier.
DANGER
Do not store or use gasoline or other flammable, combustible, or corrosive vapors and liquids in the vicinity of this or any other appliance.
WARNING
DO NOT ATTEMPT TO LIGHT ANY GAS APPLIANCE IF YOU ARE NOT CERTAIN OF THE FOLLOWING:
x Liquefied petroleum gases/propane gas and natural gas
have an odorant added by the gas supplier that aids in the detection of the gas.
x Most people recognize this odor as a “sulfur” or “rotten egg”
smell.
x Other conditions, such as “odorant fade” can cause the
odorant to diminish in intensity, or “fade”, and not be as readily detectable.
x If you have a diminished sense of smell, or are in any way
unsure of the presence of gas, immediately contact your gas supplier from a neighbor’s telephone.
Gas detectors are available. Contact your gas supplier, or plumbing professional, for more information.
WARNING
FAILURE TO INSTALL AND MAINTAIN A NEW, LISTED ¾” X ¾”
TEMPERATURE AND PRESSURE RELIEF VALVE WILL RELEASE
THE MANUFACTURER FROM ANY CLAIM THAT MIGHT RESULT
FROM EXCESSIVE TEMPERATURE AND PRESSURES.
CAUTION
Turn off or disconnect the electrical power supply to the water heater before servicing. Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Verify proper operation after servicing.
WARNING
Water heaters are heat producing appliances. To avoid damage or injury, do not store materials against the water heater or vent-
air intake system. Use proper care to avoid unnecessary contact
(especially by children) with the water heater and vent-air intake
components. UNDER NO CIRCUMSTANCES MUST
FLAMMABLE MATERIALS, SUCH AS GASOLINE OR PAINT
THINNER BE USED OR STORED IN THE VICINITY OF THIS
WATER HEATER, VENT-AIR INTAKE SYSTEM OR IN ANY
LOCATION FROM WHICH FUMES COULD REACH THE
WATER HEATER OR VENT-AIR INTAKE SYSTEM
WARNING
Hydrogen gas can be produced in an operating water heater that
has not had water drawn from the tank for a long period of time
(generally two weeks or more). Hydrogen gas is extremely
flammable. To prevent the possibility of injury under these
conditions, we recommend the hot water faucet to be open for
several minutes at the kitchen sink before you use any electrical
appliance which is connected to the hot water system. If hydrogen is present, there will be an unusual sound such as air escaping through the pipes as hot water begins to flow. Do not
smoke or have open flame near the faucet at the time it is open.
CAUTION
If sweat fittings are to be used DO NOT apply heat to the nipples
on top of the water heater. Sweat the tubing to the adapter
before fitting the adapter to the water connections. It is
imperative that heat is not applied to the nipples containing a
plastic liner.
3
Res. D Series
4
Introduction
The new Bradford White Residential Flue Damper water heaters are designed to provide reliable performance with enhanced standard features. New design features include reliable spark-to-pilot ignition system, enhanced diagnostics, simplified servicing, significantly quiet operation, and the Bradford White Defender Safety System.
Spark-to-Pilot Ignition System – employing the spark-to-pilot ignition system promotes reliable and consistent pilot and main burner ignitions to provide hot water on demand.
Integrated Immersion Thermal Well/Gas Control with LED – was developed for ease of troubleshooting by providing simple diagnostic codes to pinpoint an installation or component performance issue.
Rugged Wiring Connections – receptacle type connections promote error free wiring.
The gas control maintains water temperature, ignition sequence, and regulates gas flow. If a situation outside of the normal operating parameters exists, the gas control diagnostic LED will flash a code to positively identify an operational issue.
Please read the service manual completely before attempting service on this new series of damper models.
How the Safety System Works
During normal operation, air for combustion is drawn into the water heater through the openings in the jacket. This air travels down and around the combustion chamber and enters through holes in the very bottom of the corrosion resistant combustion chamber. The air then travels up through the flame arrestor louvers, where the velocity of the air is increased and its direction altered. The air then mixes in a normal manner with supplied gas and is efficiently combusted, producing low NO
x
emissions.
In the unlikely event trace amounts of flammable vapors are present in the air flowing into the combustion chamber, the vapors are harmlessly ignited by the burner. If flammable vapors are sufficient quantity to prevent normal combustion, the flammable vapor sensor recognizes this and shuts down the pilot and main burner. Should the flammable vapors continue to burn, the flame arrestor prevents the flames from traveling backwards and igniting the vapors outside of the combustion chamber. And, the resettable thermal switch also will open and shut down the pilot and main burner.
4
Res. D Series
5
It is intended for this manual to be used by qualified service personnel for the primary purpose of troubleshooting and repair of the Bradford White D Series water heaters. Understanding the sequence of operation section of this manual will contribute greatly to troubleshooting the water heater.
The Honeywell WV4462 electronic gas control will display status codes in the event of abnormal operation. Status codes are listed in the troubleshooting chart beginning on page 11 of this service manual. The troubleshooting chart will also indicate the probable cause for the status code and direct the service professional to a service procedure to properly diagnose the abnormal operation.
Contact the Bradford White technical support group immediately if diagnosis cannot be made using the methods described in this service manual.
Tools Required for Service
Manometer:
Multi-Meter:
Electronic Probes:
Thermometer:
Water Pressure Gage:
Various Hand Tools:
A liquid “U” tube type or a digital (magnahelic) type can be used. This device is used to measure gas and/or air pressure and vacuum.
A digital type is strongly recommended. This device is used to measure electrical values. The meter you select must have the capability to measure volts AC, volts DC, Amps, micro-amps and ohms.
In some cases, standard multi-meter probes will damage or simply not be effective to obtain certain voltage and ohm readings. It will be necessary to have special electronic “pin” type multi-meter probes. These probes are available at most electronic wholesale outlets.
Used to measure water temperature. An accurate thermometer is recommended.
Used to measure water supply pressure. Also used to determine tank pressure by adapting to the drain valve of the heater.
Pipe wrench, channel locks, open end wrenches (3/8”, 7/16”, 1/2”), 12” crescent wrench, allen wrench set, screw drivers (common & Phillip’s), 1/4” nut driver, pliers (common & needle nose), socket set, side cutters, wire cutters, wire strippers, wire crimpers, torpedo level, small shop vac, step ladder, flashlight and 5 gallon pail.
5
Res. D Series
6
Power supply Dedicated 115 VAC, 60 Hz, 15A Gas Supply Pipe Minimum 1/2” NPT (schedule 40 black iron pipe recommended) Approved Gas Type
Natural Gas or Propane, unit must match gas type supplied
Gas Pressure
5.0” w.c. min. for Natural Gas, 11.0” w.c. min. for Propane, 14.0” w.c. maximum
(Natural Gas & Propane) Venting System Single or Double Wall Metal Vent Pipe Minimum Clearance for Servicing
18” from top, 24” from front, 4” sides and rear
Water Supply Pressure
150 PSI maximum allowable working pressure. Check local codes for supply
pressure Gas Control ECO Limit
Residential 188°F (87°C)
Temperature Setpoint Range
60°F (16°C) to 160°F (71°C) (approximate temperatures)
6
Res. D Series
7
Control Timings
Ignition State Timing
Adjust Damper Position and Verify (Open Position)
15 Seconds
Trial for Ignition 90 Seconds Flame Stabilization Period
3 Seconds
Re-adjust Damper Position and Verify
15 Seconds
Flame Failure Response Time 1.5 Seconds (2 second maximum; 1 second minimum.) Adjust Damper Position and Verify (Closed Position)
15 Seconds
Damper Blade Position Fault (failed open/close) Retry after 2 minutes Soft Lockout Retry after 5 minutes ECO Limit Lockout Indefinite (see page 27) Verify Resistive Delay Retry after 2 minutes (repeats 5 times) Simulated Resistive Load Lockout Indefinite (cycle power to restart)
Hardware Status Lockout
Indefinite (self clears if fault clears for at least 15 seconds)
Wiring Diagram
7
Res. D Series
8
Power Up Sequence
1. Start Up. Upon power up, the control runs a safe-start check with a typical start-up delay of 5 seconds.
2. Flammable Vapor. The gas control verifies that the Flammable Vapor Sensor is in the proper operating range prior to energizing any components. If the sensor is within the proper range, the gas control resumes normal operation. If the Flammable Vapor Sensor is out of range, the gas control LED immediately flashes 7 times with a 3 second pause.
Normal Heating Sequence
When the phrase “Damper Open” is used, this means that the damper blade is in the vertical position (open). Alternatively, “Damper Closed” means that the damper blade is in the horizontal position (closed). This must not be confused with the phrase “Damper Circuit Open,” as this means that the damper blade is in the horizontal position. “Damper Circuit Closed” means that the damper blade is in the vertical position, and the water heater can proceed to an ignition trial.
1. Thermostat calls for heat. Prior to energizing damper, gas control verifies the damper safety circuit to ensure it is in the correct state. If the safety circuit is closed, the gas control LED flashes 2 times with a 3 second pause. The gas control waits 2 minutes. Then, the damper is powered closed. This cycle repeats until the safety circuit opens.
2. Damper Powered Open.
3. Damper Safety Circuit Check: If the damper safety circuit does not close within 30 seconds, the gas control LED flashes 3 times with 3 second pause. The damper is powered open for a maximum of 30 seconds every 2 minutes trying to close the damper safety circuit. This cycle repeats as long as there is a call for heat.
4. Damper hold period (15 seconds).
5. Trial for pilot ignition (90 seconds): The gas control lights the pilot by activating the spark igniter and gas flow to the pilot burner. If flame is not sensed within 90 seconds, the spark igniter and gas flow are deactivated. The damper will remain open, and the gas control LED flashes 6 times with a 3 second pause.
6. Main burner ignition: After the pilot flame is sensed, the gas control activates the main valve for main burner ignition. The gas control will ignore flame signals for 3 seconds to allow for the main burner to stabilize
8
Res. D Series
9
Normal Heating Sequence (cont.)
7. Steady state operation.
During steady state operation, the control monitors:
Thermostat temperature sensor-when set point temperature is satisfied, gas valve is shut down and damper is powered closed. The gas control LED flashes a short flash once every 4 seconds (idle) status code.
Damper Position-if the damper position is altered during a call for heat, the pilot and main valves are shutdown. The damper is powered open attempting to close the damper safety circuit. The gas control LED flashes 3 times with a 3 second pause.
Flame sensor-if flame is lost, pilot & main valves are shut down. The damper is powered open. The gas control attempts to re-light the pilot 4 times. If unsuccessful, the damper is closed, and the gas control proceeds to a 5 minute lockout. The gas control re-attempts to light the pilot starting at normal heating sequence #2.
8. Thermostat satisfies. (Gas Control LED flashing once every 4 seconds).
9. Burner off.
10. Damper Powered Closed (15 seconds).
Abnormal Operation
1. Flammable Vapor Sensor Fault:
a. If the resistance is greater than 70,000 Ohms-the gas control immediately
turns off all outputs. The gas control waits and monitors resistance for 30 seconds. If the resistance is greater than 65,000 ohms after 30 seconds, the gas control proceeds to verify resistive delay for 2 minutes and flashes 7 times, then 1 time with a three second pause. This process is repeated 5 times until the control either returns to normal operation or proceeds to flammable vapor lockout.
b. If the resistance is below 3000 Ohms-The gas control immediately turns
off all outputs and proceeds to flash 8 times, then 1 time with a three second pause. The status self clears if the resistance returns to normal range for at least 15 seconds.
2. Temperature Sensor Fault:
a. Temperature sensor open circuit–The gas control immediately turns off all
outputs and proceeds to flash 8 times then, 3 times with 3 second pause. The status self clears if the fault clears for at least 15 seconds.
b. Thermal well sensor not reading the same temperature within ±5.5°F
The gas control immediately turns off all outputs and proceeds to flash 8
9
Res. D Series
10
Abnormal Operation (cont.)
times, then 3 times twice with 3 second pauses. The status self clears if the fault clears for at least 15 seconds.
c. Water temperature in excess of ECO (energy cut off) limit -The gas
control immediately turns off pilot & main valves and proceeds to flash 4 times with a 3 second pause. To reset the gas control, rotate the setpoint knob to the minimum setting for at least 6 seconds before returning to desired temperature setting.
3. Damper Safety Circuit Fault:
a. Damper Failed to Open-The gas control proceeds to flash 3 times with a 3
second pause. The gas control waits 5 minutes, and then tries to open the damper again.
b. Damper failed to close-the gas control proceeds to flash 2 times with a 3
second pause. The gas control waits 5 minutes, and then tries to open the damper again.
4. Trial for Ignition Fault:
a. Damper Jostled During Trial-The gas control stops the trial for ignition.
The gas control proceeds to flash 3 times with a 3 second pause. The gas control waits 5 minutes, and then tries to open the damper again.
b. Flame not sensed-The gas control energizes the spark igniter attempting to
light the pilot and prove flame. If flame is not sensed within 90 seconds, the spark igniter turns off, the pilot valve is closed. The gas control LED flashes 6 times, then 1 time with a 3 second pause. The gas control waits 5 minutes before repeating the ignition sequence.
5. Flame sensing fault:
a. Flame lost during run-The gas control turns off pilot and main valves. The
gas control increments the recycle count, if the recycle count has not reached its limit (4), another trial for ignition begins. If the recycle count has been reached, the gas control LED flashes 6 times, then 3 times with a 3 second pause. The gas control waits 5 minutes before repeating the ignition sequence.
b. Flame sensed out of sequence-the gas control only looks for pilot flame
when the damper is in the open position. If flame is present when the pilot valve is not open, the gas control proceeds to wait for flame loss and flashes 5 times with 3 second pause. This continues until flame is lost. Once the flame signal is lost, the control flashes 6 times then, 4 times with 3 second pause. The control waits 5 minutes before repeating the ignition sequence.
10
Res. D Series
11
Observe green LED indicator on electronic gas control. Status flash codes are displayed with a three second pause before repeating. Check and repair the system as noted in the troubleshooting table below.
LEDStatus
ControlStatus ProbableCause
Service Procedure
None, control LED not on or flashing
No electrical power
Control power switch in “OFF” position. Supply voltage interrupted.
Turn power on.
One short flash, once every four seconds
Stand-by mode, Waiting for call
for heat (no fault).
Temperature demand is satisfied.
Normal operation. Adjust thermostat to
temp level.
“Heartbeat” alternates bright/dim
Thermostat calling for heat (no fault).
Tank temperature below set point of thermostat.
Normal operation. Adjust thermostat to
temp level.
Short flash once per second
Weak pilot signal on last call for heat.
1. Unstable pilot.
2. Pilot tube blocked or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad connection at gas valve.
1. See burner inspection on Page
13.
2-4. See Pilot
Inspection, Testing and Replacement on page 15.
Two flash, three second pause
Damper test circuit not working
1. Damper not in proper position or malfunctioning-stuck in open position.
2. Obstructed venting.
3. Faulty damper.
1. Verify cord sets are fully plugged in
2. Verify switch on damper is in “Automatic” position.
3. Replace damper, see page 16.
Three flash, three second pause
Damper test circuit not working.
1. Damper not in proper position or malfunctioning-not reaching full open position.
2. Obstructed venting.
3. Faulty damper.
1. Verify cord sets are fully plugged in
2. Verify switch on damper is in “Automatic” position.
3. Replace damper, see page 16.
Four flash, three second pause
Excessive tank temperature. System must be
reset.
1. Temperature sensor out of calibration.
2. Faulty gas control.
Replace gas control, page 19.
Five flash, three second pause
Undesired-false pilot flame present.
1. Pilot valve stuck in open position.
Replace gas control, page 19.
11
Res. D Series
12
LEDStatus ControlStatus ProbableCause
Service Procedure
Six-one flash, three second pause
Failed to light pilot. System auto
resets.
1. Unstable pilot.
2. Pilot tube blocked or restricted.
3. Oxidation build up on pilot electrode.
4. Wire damage to pilot assembly or bad connection at gas valve.
1. See Burner Inspection on page
13.
2. See Pilot Inspection, Testing and Replacement on page 15.
Six-two flash, three second pause
Damper test circuit not working properly during burner operation, system auto resets after (5) minutes.
1. Damper not in proper position or malfunctioning-damper moved from full open position during run cycle.
2. Obstructed venting.
3. Faulty damper.
4. Damper jostled during run cycle.
Page 16.
Six-three flash, three second pause
Pilot flame extinguished. System auto
resets.
1. Unstable pilot.
2. Pilot tubing kinked or blocked.
3. Oxidation build-up on pilot electrode.
4. Wire damage to pilot assembly or bad connection at gas control.
5. Insufficient combustion air.
6. Insufficient gas pressure.
1-4. Page 15.
5-6. Refer to Installation & Operation Manual.
Six-four flash, three second pause
Undesired-false pilot flame sensed. System auto
resets.
Pilot valve stuck in open position.
Replace gas control, Page 19.
Seven flash, three second pause
Flammable vapor sensor or resettable thermal switch fault detected.
1. Flammable vapor present
2. Flammable vapor sensor exposed to excessive moisture
3. Flammable vapor sensor exposed to extreme ambient temperature
4. Resettable thermal switch open
1-3. Flammable sensor
testing, Page 21.
4. Resettable thermal switch testing, Page 32
Eight-one flash, three second pause
Flammable vapor sensor out of specification.
Flammable vapor sensor out of specification. Page 20.
Eight-two flash, three second pause
Temperature Sensor fault.
1. Damage to temperature sensor wire.
2. Temperature sensor resistance out of range.
Replace gas control, Page 19.
Eight-three flash, three second pause
Gas Control electronics fault detected.
1. Control needs to be reset.
2. Control is wet or physically damaged.
1. Interrupt power supply
2. Replace gas control,
page 19.
Eight-four flash, three second pause
Gas valve fault detected.
1. Control needs to be reset.
2. Control is wet or physically damaged.
1. Interrupt power supply
2. Replace gas control,
page 19.
12
Loading...
+ 28 hidden pages