Heating Element Removal and Replacement ……………………………..
DipTube and Anode Inspection and Replacement ……………………….
Generic Parts List …………………………………………………………….
2---
2---
3---
6--6--7--8---
9--10- - 11- - -
12- - -
14RE-I
15RE-II
16RE-III
16
16
17
19
21
23
25RE IV
25
27
29
31
33RE-V
34RE-VI
35 RE-VII
36 - - -
This service manual is designed to aid service and maintenance professionals on the function, proper diagnosis
and repair of Bradford White residential electric and light duty commercial electric water heaters.
The text and illustrations in this manual provide step by step instructions to facilitate proper operation and
troubleshooting procedures. Contact the Bradford White Technical Support Group immediately if diagnosis can
not be made using the methods described in this service manual.
- Multi Meter- Phillips Head Screw Driver
- 1-½ Deep Well Socket - Thermometer
- ¼" Nut Driver- Drain Hose
- Various Hand Tools: Pipe Wrench, Channel Locks, Pliers (common & needle nose), Wire cutters, Wire Strippers, Flash Light.
Page 2
2
ABC
Commonly Used Formulas
GENERAL INFORMATION
Amps = (for single phase units) Example: 4500W/240V = 18.75A
Residential Electric Upright RE2 & RE3 Series (Non-Simultaneous Operation)
Residential High Efficiency Upright RE2 Series (Non-Simultaneous Operation)
Residential Electric Lowboy RE2 Series (Non-Simultaneous Operation)
Maximum
Wattage
3,000
6,000
6,000
Element
Upper/Lower
3,000/3,000120
6,000/6,000208, 240
6,000/6,000
Voltage
277, 480
Residential Electric Upright RE2 & RE3 Series (Simultaneous Operation)
Residential High Efficiency Upright RE2 Series (Simultaneous Operation)
Residential Electric Lowboy RE2 Series (Simultaneous Operation)
Light Duty Commercial Electric LE Series (Non-Simultaneous Operation)
Light Duty Commercial Electric LE Series (Simultaneous Operation)
Maximum
Wattage
3,000
10,000
11,000
12,000
Element
Upper/Lower
1,500/1,500120
5,000/5,000208
5,500/5,500240
6,000/6,000
Voltage
277, 480
Residential Electric Utility Series (Single Element Operation)
Light Duty Utility Series (Single Element Operation)
Maximum
Wattage
3,000
6,000
6,000
6,000
Single
Element
3,000120
6,000208, 240
6,000277
6,000480
Page 4
Voltage
4
GENERAL INFORMATION
Surface Mounted Thermostats
Surface mounted thermostats are mounted into a bracket which holds the thermostat against the side of the tank.
Surface mounted thermostats respond to tank surface temperatures to sense a call for heat, set point temperature
settings and high limit (ECO) activation. It is important that the entire back surface of the thermostat is in full contact or
flush with the tank. Improperly mounted thermostat will lead to improper water heater operation.
Manual
ECO (high limit)
Reset button
Surface Mount
Combination Thermostat/
ECO (high limit)
59T/66T Series
Temperature
control Dial
Surface Mount
Combination Thermostat/
ECO (high limit)
59T/66T Series
Temperature
control Dial
Direct Immersion “Screw-in” Type Heating Element
1-½ Hex
Screw-in Flange
Terminal Block
Screw
Terminal Block
Zinc Plated Copper or
Incoloy Sheath
Element Rating Ink Stamped
on side of Terminal Block.
Surface Mount
Thermostat
59T Series
Page 5
5
SEQUENCE OF OPERATION
Residential and light duty commercial electric water heaters are designed to operate using several different operating
modes. The common modes and sequence of operation are as follows:
1. Single Element Operation.
2. Double Element Non-Simultaneous Operation (single phase).
3. Double Element Non-Simultaneous Operation (3 phase).
4. Double Element Simultaneous Operation (single phase).
5. Double Element Simultaneous Operation (3 phase).
Sequence of Operation- Single Element Operation.
Line voltage is applied across terminals
1
L1 & L3 of the thermostat. ECO is
closed, so there is voltage at terminal L4
and to one side of the element.
1
ECO
Closed
Tank is cold therefore thermostat
2
is closed at terminal T2 (calling for heat).
This completes the circuit and allows
current to flow through the element.
3
When the thermostat is satisfied, it opens at
terminal T2 interrupting current flow through the
element. System is now in stand-by mode, waiting
for the next call for heat.
Thermostat closed
at terminal T2
Thermostat opens
at terminal T2
2
3
Page 6
6
SEQUENCE OF OPERATION
Non-Simultaneous and Simultaneous Operation
Double element electric water heaters are designed to operate in either Non-Simultaneous or Simultaneous mode.
Non-Simultaneous Mode: Allows only one heating element to operate at a time. For example, when the tank is cold,
the upper element is energized first, heating the top of the tank. Only when the upper thermostat is satisfied, the upper
element is de-energized and power is directed to the lower thermostat, energizing the lower element and heating the
bottom portion of the tank until the lower thermostat is satisfied. As hot water is drawn off the tank, it is replaced with
cold water delivered through the diptube to the bottom of the tank. When the tank cools at the lower thermostat level, the
lower thermostat will call for heat, energizing the lower element. If enough hot water is drawn from the tank, the top
portion of the tank cools and the upper thermostat will call for heat, de-energizing the lower element and allowing only
the top element to energize until the upper thermostat is satisfied.
Simultaneous mode: allows both heating elements to operate at the same time. That is, if either thermostat (upper or
lower) is calling for heat, the corresponding heating element is energized independent of the other.
Sequence of Operation- Double Element, Non-Simultaneous Operation, Single Phase.
1
Line voltage is applied across terminals
L1 & L3 of the upper thermostat. ECO is
closed, so there is voltage at terminal L4
and to one side of the upper and lower
elements.
2
Tank is cold. Therefore, the thermostats
are closed at terminals T2 & 2 (calling for heat).
The circuit is complete through the upper
thermostat only, allowing current to flow through
upper element.
12
ECO
Thermostat closed
Closed
at terminal T2
3
When the upper thermostat is satisfied, it opens at
terminal T2, interrupting current flow through the
upper element. Terminal T4 closes, allowing voltage
to pass to terminal 1 of the lower thermostat. This
completes the circuit through the lower thermostat
and allows current flow through the lower element.
4
When the lower thermostat is satisfied, it opens at
terminal 2, interrupting current flow through lower
element. The system is now in stand-by mode
waiting for the next call for heat.
5
The lower thermostat/element
combination will generally
cycle on and off more often
than the upper. In some cases,
such as a cold tank or in high
demand periods, the upper
thermostat will call for heat
(opening at terminal
T4 and closing at
Thermostat closed
at terminal T4
terminal T2) prior to the lower
thermostat being satisfied. This
will interrupt current flow
Upper
T’stat
through the lower thermostat
and element and allow current
to flow through the upper
Upper
Element
element only. When the upper
thermostat is satisfied, it
resumes operation as
described in sequence #3
above.
Lower
T’stat
Lower
Element
Upper
T’stat
Upper
Element
Thermostat closed
at terminal 2
Lower
T’stat
Lower
Element
3
Thermostat open
between terminals
1 and 2
Upper
T’stat
Upper
Element
Lower
T’stat
Lower
Element
4
Thermostat closed
at terminal T2
Thermostat closed
between terminals
1 and 2
Upper
T’stat
Upper
Element
Lower
T’stat
Lower
Element
Upper
T’stat
Upper
Element
Lower
T’stat
Lower
Element
5
Page 7
7
SEQUENCE OF OPERATION
A 4 wire, double element heater wired for simultaneous operation is essentially two single element systems operating
independently. The heaters are wired internally with two independent circuits, one circuit for each thermostat/element
combination. When installed using a two wire service, the blue and red (or white) wires will be connected together,
likewise black and yellow wires will be connected together.
Sequence of Operation- Double Element, Simultaneous Operation, Single Phase, 4 wire service
installation.
1
Line voltage from circuit one is applied
across terminals L1 & L3 of the lower
thermostat. Likewise, line voltage from
circuit two is applied across terminals L1 &
L3 of the upper thermostat. ECO in both
upper and lower thermostat is closed, so
there is voltage at terminal L4 of each
thermostat and to one side of the upper and
lower elements.
2
Tank is cold therefore both thermostats
are closed at terminal T2 (calling for heat).
This completes the circuit through the
thermostats and allows current to flow
through the elements.
3
When either thermostat is satisfied, it will
open at terminal T2, interrupting current
flow through the corresponding element. As
both thermostats satisfy, the system will be
in stand-by mode waiting for the next call
for heat. Thermostats will operate
independent of each other.
Circuit one
Circuit one
1
3
Thermostat open
at terminal T2
Circuit two
Circuit two
ECO
Closed
ECO
Closed
Circuit one
Thermostat closed
Thermostat closed
at terminal T2
2
at terminal T2
Circuit two
Thermostat open
at terminal T2
Page 8
8
SEQUENCE OF OPERATION
Sequence of Operation- Double Element, Non-Simultaneous Operation, 3 Phase.
12
1
Line voltage is applied across terminals L1
& L3 of upper thermostat. Likewise, Line
voltage is applied to terminal L3 of lower
thermostat. ECO in both upper & lower
thermostat is closed, so there is voltage at
terminal L4 of both thermostats and to one
side of both upper & lower elements.
2
Tank is cold therefore both thermostats
are closed at terminal T2 (calling for heat).
The circuit is complete through the upper
thermostat only allowing current to flow
through the upper element.
3
When the upper thermostat is satisfied, it
opens at terminal T2 interrupting current
flow through upper element, and closes at
terminal T4 allowing voltage to pass to
terminal L1 of lower thermostat. This
completes the circuit through the lower
thermostat allowing current flow through
lower element.
Thermostat closed
at terminal T4
ECO
Closed
ECO
Closed
Thermostat closed
at terminal T2
Thermostat closed
at terminal T2
3
Thermostat closed
at terminal T4
4
4
When the lower thermostat is satisfied, it
opens at terminal T2 interrupting the
current flow through the lower element. The
system is now in stand-by mode waiting for
the next call for heat.
The lower thermostat/element combination
5
will generally cycle on and off more often
than the upper. In some cases, such as a
cold tank or in high demand periods, the
upper thermostat will call for heat (opening
at terminal T4 and closing at terminal T2)
prior to the lower thermostat being satisfied.
This will interrupt current flow through the
lower thermostat and element and allow
current to flow through the upper element
only. When the upper thermostat is
satisfied, it resumes operation as described
in sequence #3 above.
Thermostat closed
at terminal T2
Thermostat closed
at terminal T2
Thermostat closed
at terminal T2
Thermostat open
at terminal T2
5
Page 9
9
SEQUENCE OF OPERATION
Sequence of Operation- Double Element, Simultaneous Operation, 3 Phase.
1
Line voltage is applied across terminals L1
& L3 of upper thermostat. Line voltage also
extends to terminal L1 of lower thermostat.
Also, line voltage is applied to terminal L3
of lower thermostat. ECO in both upper &
lower thermostat is closed, so there is
voltage at terminal L4 of both thermostats
and to one side of both upper & lower
elements.
2
Tank is cold therefore both thermostats
are closed at terminal T2 (calling for heat).
This completes the circuit through the
thermostats and allows current to flow
through the elements.
3
When either thermostat is satisfied, it will
open at terminal T2, interrupting current
flow through the corresponding element. As
both thermostats satisfy, the system will be
in stand-by mode waiting for the next call
for heat. Thermostats will operate
independent of the other.
Thermostat open
at terminal T2
1
ECO
Closed
ECO
Closed
Thermostat closed
at terminal T2
Thermostat closed
at terminal T2
2
3
10
Thermostat open
Page 10
at terminal T2
SEQUENCE OF OPERATION
Some electric utility companies will offer discounts for using electricity during “Off Peak” Times of the day. The system
allows the use of an “Off Peak” meter, which interrupts power to the lower element during high power demand periods.
Sequence of Operation- Double Element, Non-Simultaneous Operation, Single Phase, Off Peak.
1
Line voltage is applied across terminals
L1 & L3 of the upper thermostat. Line voltage from
off peak meter is supplied to terminal L1 of lower
thermostat. ECO in the upper thermostat is closed,
so there is voltage at terminal L4 of upper
thermostat and to one side of the upper element.
Tank is cold therefore both thermostats
are closed at terminal T2 (calling for heat). The
2
circuit is complete through the upper thermostat
only, allowing current to flow through upper
element.
3
When upper thermostat is satisfied, it opens at
terminal T2 interrupting current flow through upper
element, and closes at terminal T4 allowing voltage
to pass to one side of the lower element. This
completes the circuit through the lower thermostat
and off peak meter allowing current flow through
lower element.
From
Off Peak
Meter
12
ECO
Thermostat closed
Closed
Thermostat closed
at terminal T2
at terminal T2
4
When the lower thermostat is satisfied, it opens at
terminal T2 interrupting current flow through lower
element. The system is now in stand-by mode
waiting for the next call for heat
5
During peak power demand periods as determined
by the local utility, the off peak meter will interrupt
power to terminal L1 of lower thermostat. Only the
top thermostat/element combination is allowed to
operate during this period.
From
Off Peak
Meter
Thermostat closed
at terminal T4
Thermostat closed
at terminal T2
3
Thermostat open
at terminal T2
45
Off Peak
Power interrupted
Thermostat closed
at terminal T2
Page 11
11
TROUBLESHOOTING
Most common cause for improper electric water heater operation can be linked to heating element
failure.
When troubleshooting an electric water heater with the incidence of “No Hot Water” or “Insufficient Amount of Hot
Water,” It’s always a good idea to check the heating elements first by following the procedure on page 15.
Common Heating Element Failures:
1. Dry Firing. Element may be partially submerged in water or most likely, completely exposed with no water in
tank. In some cases, sediment or lime build up around an element can eventually cause an air pocket, and
within seconds, result in a dry fired element. At this point the element becomes inoperative. When element
replacement is required, be sure the tank is full of water prior to energizing the water heater.
2. Grounded Element. An element with a short circuit to ground will in most cases cause the circuit breaker in
the service panel to open or shut off. In some cases, there may not be enough current draw for the circuit
breaker to open. This will allow the heating element to be in continuous operation resulting in over heated
water, limited only by the ECO or Energy Cut Out. Repeated actuation of the ECO is
usually the result of a grounded element.
3. Sediment build up. Slow hot water recovery can usually be traced back to sediment or lime build up around
heating element. Sediment build up can also over time cause a dry fired element.
Figure 1, below shows a common “Screw-In” type heating element identifying certain features commonly referred to
throughout this manual.
1-½ Hex
Screw-in Flange
Terminal Block
Zinc Plated Copper or
Incoloy Sheath
0642
4500W 240V
RC02404524
Terminal Block
Screw
Typical Direct Immersion “Screw-In”
Type Heating Element
Element Rating Ink Stamped
on side of Terminal Block.
Figure 1
12
Page 12
TROUBLESHOOTING
Quick Step Plan to Hot Water
WARNING
1. TURN OFF power to water heater and check all wire
connections to ensure they are tight and corrosion free.
2. Turn power “ON” and determine that service voltage is
present, and the high limit (ECO) has not actuated
(see procedure on page 14).
3. Check for inoperative heating element (see procedure on page 15).
4. Check for proper thermostat operation (see procedures beginning on page 16). NOTE: Thermostat testing procedures
assume items 2 and 3 above are in working order.
SYMPTOMPROBABLE CAUSECORRECTIVE ACTION
1. No Power to heater.
2. Loose wire connections.
No Hot Water
Not Enough Hot
Water
Slow Hot Water
Recovery
Over Heated
Water or
Continued
Operation
3. Inoperative upper heating element.
4. Inoperative upper thermostat.
5. Open ECO.
1. Inoperative lower heating element.
2. Thermostat(s) set to low.
3. Inoperative thermostat(s).
4. Loose wire connection.
5. Sediment or lime build up on element(s).
6. High demand period.
7. Undersized heater.
8. Very cold inlet water to heater.
9. Plumbing connections reversed.
10. Damaged diptube.
1. Sediment or lime build up on element(s).
2. Loose wire connections.
3. Inoperative thermostat(s).
4. Derated heating element installed.
1. Thermostat not in contact with tank.
2. Grounded heating element(s).
3. Thermostat set too high.
4. Inoperative thermostat(s).
5. Inoperative ECO.
6. Undersized water heater.
High voltage exposure. Use caution when
making voltage checks to avoid personal
injury.
SERVICE
PROCEDURE
1. Check fuses or circuit breakers in service
panel.
2. Check all wire connections.
3. Check heating element(s). Replace as
needed.
4. Check thermostat(s) operation. Replace as
needed.
5. Check ECO. Reset or replace
thermostat(s) as needed.
1. Check heating element(s), replace as
needed.
2. Increase thermostat setting.
3. Check thermostat(s), replace as needed.
4. Check all wire connection.
5. Remove heating element(s) and check for
lime build up.
6. Reduce demand.
7. Replace with larger heater.
8. Temper water to heater.
9. Correct plumbing connections.
10. Check dip tube, replace as needed.
1. Remove heating element(s) and check for
lime build up.
2. Check all wire connections.
3. Check thermostat(s), replace as needed.
4. Check terminal block of element for proper
voltage and wattage rating.
1. Position thermostat flush with tank surface.
2. Check heating element(s). Replace as
needed.
3. Adjust thermostat(s) to desired setting.
4. Check thermostat(s), replace as needed.
5. Check ECO, replace thermostat as
needed.
6. Replace with larger heater.
3. See Service Procedure
RE-II, Page 15.
4. See Service Procedure
RE-III, Page 16.
5. See Service Procedure
RE-I, Page 14.
1. See Service Procedure
RE-II, Page 15.
3. See Service Procedure
RE-III, Page 16.
5. See Service Procedure
RE-VI, Page 34.
10. See Service Procedure
RE-VII, Page 35.
1. See Service Procedure
RE-VI, Page 34.
3. See Service Procedure
RE-III, Page 16.
1. See Service Procedure
RE-V, Page 33.
2. See Service Procedure
RE-II, Page 15.
4. See Service Procedure
RE-III, Page 16.
5. See Service Procedure
RE-I, Page 14.
Noisy (singing or
hissing) Elements
1. Lime formation on elements.1. Remove and clean heating elements.
Replace as needed.
Page 13
1. See Service Procedure
RE-VI, Page 34.
13
SERVICE PROCEDURE RE-I
Line Voltage & High Limit (ECO)
Testing
Line Voltage Testing
1. Turn “OFF” power to water heater.
2. Remove access cover(s) from front of water
heater. Remove insulation and plastic cover
from thermostat.
3. Set multi-meter to “Volts AC.”
4. Turn power “ON” to water heater.
5. Check voltage across terminals L1 & L3
of upper thermostat (see Figure 2).
A) Rated voltage IS present, power to the water
heater is okay.
B) Rated voltage NOT present, Check circuit breaker
at service panel.
High Limit (ECO) Testing
WARNING
High voltage exposure. Use caution when
making voltage checks to avoid personal injury.
ECO reset
button
Figure 3
Figure 2
1. Check voltage across terminals L1 & L4 upper thermostat (see Figure 3).
A) Rated Voltage IS present, ECO is okay.
B) Rated voltage NOT present, proceed to step 2.
2. Turn power “OFF” to water heater and firmly press ECO reset button on thermostat(s). Turn power “ON” and recheck
voltage across terminals L1 & L4 of upper thermostat (see Figure 3).
A) Rated voltage IS present, the ECO has previously opened indicating the water in the tank, at
some point did overheat, check the following:
1. Thermostat must be in full contact with tank.
2. Be sure heating element(s) is not shorted to ground (see page 15).
3. Proper thermostat operation (see procedures beginning on page 16).
B) Rated voltage NOT present, water in tank may be over heated.
1. If water is hot, turn “OFF” power to water heater and flow water through tank to cool below set point
of upper thermostat. Recheck voltage per step 1.
2. If water is cool, Replace upper thermostat.
14
Page 14
SERVICE PROCEDURE RE-II
Heating Element Testing
Testing For Open Or Burned Out Element
Step 1. TURN OFF POWER TO WATER HEATER
Step 2. Remove access cover(s) from front of water
heater. Remove insulation and plastic cover
from thermostat.
Step 3. Disconnect wires from heating element(s).
Step 4. Set multi-meter to “ohms” setting.
Step 5. Touch probes of multi-meter to screw
terminals of heating element(s)
(see Figure 4).
Step 6. Reading should be 12.8 ohms (±6%) for a 240
volt, 4500 watt element:
Ohms = Volts
2
Watts
A reading outside the range using the formula
beyond (±6%), indicates a bad element and the
element must be replaced.
WARNING
High voltage exposure. Be sure power is turned
OFF to water heater prior to performing this
procedure.
Meter Probe
Element Screw Terminals
Figure 4
Testing For Heating Element Short Circuit To Ground
Step 1. TURN OFF POWER TO WATER HEATER
Step 2. Remove access cover(s) from front of water
heater. Remove insulation and plastic cover
from thermostat.
Step 3. Disconnect wires from heating element(s).
Step 4. Set multi-meter to “ohms” setting.
Step 5. Touch one probe of multi-meter to either screw
terminal of heating element and the other on
the element flange (see figure 5). There
should be no reading on the ohm meter. Any
reading indicates a grounded element and the
element must be replaced. Repeat this step for
the other screw terminal.
Element Screw Terminal
Meter Probe
Element Flange
Figure 5
Page 15
15
SERVICE PROCEDURE RE-III
Residential Thermostat Testing
Single Element Operation or Double Element,
4 Wire, Simultaneous, Single Phase Operation
Water In Tank Is Cold With Power ON
1. This procedure assumes line voltage, ECO and
elements are in working order.
2. Turn power “ON” to water heater.
3. Set multi-meter to “Volts AC.”
4. Check across terminals L4 and T2 of
thermostat (see Figure 6).
A) Rated voltage NOT present,
Recheck ECO. If ECO is okay,
replace thermostat.
B) Rated voltage IS present,
proceed to next step.
5. Check across element terminals
(see Figure 7).
A) Rated voltage NOT present,
check wire connections from
thermostat to element.
B) Rated voltage IS present,
Repeat element testing
see page 15.
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 6
Figure 7
Water Temperature In Tank Is Above Thermostat Setting
1. This procedure assumes line voltage, ECO and
elements are in working order.
2. Turn power “ON” to water heater.
3. Set multi-meter to “Volts AC.”
4. See Figure 6 above, check across terminals L4 and T2
of thermostat.
A) Rated voltage IS present,
replace thermostat.
B) Rated voltage NOT present,
thermostat is okay.
C) Lower than rated voltage IS present,
recheck for grounded element
(see page 15).
16
Reference 4 Wire, Simultaneous, Single Phase
Wiring diagram.
NOTE: Wiring consists of two single element configurations
operating independently.
Page 16
SERVICE PROCEDURE RE-III
Residential Thermostat Testing
Double Element, Non-Simultaneous, Single Phase
Operation.
Water In Tank Is Cold With Power ON.
1. This procedure assumes line voltage, ECO and
elements are in working order.
2. Turn power “ON” to water heater.
3. Set multi-meter to “Volts AC.”
4. Check across terminals L4 and T2 of
upper thermostat (see Figure 8).
A) Rated voltage NOT present,
Recheck ECO. If ECO is okay,
replace thermostat.
B) Rated voltage IS present,
proceed to next step.
5. Check across element terminals
(see Figure 9).
A) Rated voltage NOT present,
check wire connections from
thermostat to element.
B) Rated voltage IS present,
Repeat element testing
see page 15.
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 8
Figure 9
Tank Does Not Deliver Enough Hot Water.
1. This procedure assumes line voltage, ECO and
elements are in working order.
2. Turn power “ON” to water heater and set multi-meter to “Volts AC.”
3. Adjust temperature setting of upper thermostat to the highest setting.
Water temperature in tank must be below thermostat setting for this test.
4. See Figure 8 above, check voltage across terminals L4 and T2 of upper
thermostat.
A) Rated voltage IS present, okay, upper thermostat is
calling for heat. Go to step 5 below.
B) Rated voltage NOT present, replace upper thermostat.
5. Adjust temperature setting of upper thermostat to the minimum setting.
Water temperature in tank must be above thermostat setting for this test.
6. Check voltage across terminals L4 and T4 of upper thermostat
(see Figure 10).
A) Rated voltage NOT present, replace upper thermostat.
B) Rated voltage IS present, thermostat is okay. Go to step 7 on next page.
Page 17
Figure 10
17
SERVICE PROCEDURE RE-III
Residential Thermostat Testing
Double Element, Non-Simultaneous, Single Phase
Operation (continued).
Not Enough Hot Water (continued).
7. Check voltage across terminal L4 of upper
thermostat and terminal 1 of lower thermostat
(see Figure 11).
A) Rated voltage NOT present,
- check wire connection between thermostats.
B) Rated voltage IS present, okay, go to step 8.
8. Adjust lower thermostat to highest setting. Water temperature in
tank must be below the lower thermostat setting for this test.
9. Check voltage across terminal L4 of upper
thermostat and terminal 2 of lower thermostat (see Figure 12).
A) Rated voltage NOT present, replace lower thermostat.
B) Rated voltage IS present, thermostat is ok.
High voltage exposure. Use caution to avoid
WARNING
Be sure thermostats are reset to their original
temperature settings as found prior to
thermostat testing
WARNING
personal injury during this procedure.
Figure 11
Water Temperature In Tank Is Above Thermostat Setting.
1. This procedure assumes Line voltage, ECO and elements are in working
order.
2. Adjust upper and lower thermostats to the lowest setting.
3. Turn power “ON” to water heater and set multi-meter to “Volts AC.”
4. Check across terminals L4 and T2 of upper thermostat
(see Figure 8 on page 17).
A) Rated voltage IS present, replace upper thermostat.
B) Rated voltage NOT present, upper thermostat is okay. Go to step
5 below.
C) Lower than rated voltage IS present, recheck for grounded upper
element (see page 15).
5. Check across terminals L4 and 2 of lower thermostat (see Figure 12).
A) Rated voltage IS present, replace lower thermostat.
B) Rated voltage NOT present, lower thermostat is okay.
C) Lower than rated voltage IS present, recheck for grounded lower
element (see page 15).
Page 18
Figure 12
18
SERVICE PROCEDURE RE-III
Residential Thermostat Testing
Double Element, Non-Simultaneous, Three Phase
Operation.
Water In Tank Is Cold With Power ON.
1. This procedure assumes line voltage, ECO and
elements are in working order.
2. Turn power “ON” to water heater.
3. Set multi-meter to “Volts AC.”
4. Check across terminals L4 and T2 of
upper thermostat (see Figure 13).
A) Rated voltage NOT present,
recheck ECO. If ECO is okay,
replace thermostat.
B) Rated voltage IS present,
proceed to next step.
5. Check across element terminals
(see Figure 14).
A) Rated voltage NOT present,
check wire connections from
thermostat to element.
B) Rated voltage IS present,
repeat element testing,
see page 15.
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 13Figure 14
Tank Does Not Deliver Enough Hot Water.
1. This procedure assumes line voltage, ECO and
elements are in working order.
2. Turn power “ON” to water heater and set multi-meter to “Volts AC.”
3. Adjust temperature setting of upper thermostat to the highest setting.
Water temperature in tank must be below thermostat setting for this test.
4. See Figure 13 above, check voltage across terminals L4 & T2 of upper
thermostat.
A) Rated voltage IS present, okay, upper thermostat is
calling for heat. Go to step 5 below.
B) Rated voltage NOT present, replace upper thermostat.
5. Adjust temperature setting of upper thermostat to the minimum setting.
Water temperature in tank must be above thermostat setting for this test.
6. Check voltage across terminals T4 of upper thermostat & L3 of lower thermostat
(see Figure 15).
A) Rated voltage NOT present, replace upper thermostat.
B) Rated voltage IS present, upper thermostat is okay. Go to step 7 on next
page.
Page 19
Figure 15
19
SERVICE PROCEDURE RE-III
Residential Thermostat Testing
Double Element, Non-Simultaneous,
Three Phase Operation (continued).
High voltage exposure. Use caution to avoid
WARNING
personal injury during this procedure.
Tank Does Not Deliver Enough Hot Water (continued)
7. Check voltage across terminal L1 & L3 of lower thermostat (see Figure 16).
A) Rated voltage NOT present, check wire connection between thermostats.
B) Rated voltage is present, okay, go to step 8.
8. Adjust lower thermostat to highest setting. Water temperature in tank must be below
the lower thermostat setting for this test.
9. Check voltage across terminal L4 & T2 of lower thermostat (see Figure 17).
A) Rated voltage NOT present, recheck ECO (see page 14). If ECO okay,
replace lower thermostat.
B) Rated voltage IS present, thermostat is ok. Check wire connection to lower
element. If connection okay, recheck lower element (see page 15).
WARNING
Be sure thermostats are reset to their original
temperature settings as found prior to
thermostat testing
Figure 16
Water Temperature In Tank Is Above Thermostat Setting.
1. This procedure assumes line voltage, ECO and elements are in working
order.
2. Adjust upper and lower thermostats to the lowest setting.
3. Turn power “ON” to water heater and set multi-meter to “Volts AC.”
4. Check across terminals L4 and T2 of upper thermostat
(see Figure 13 on page 19).
A) Rated voltage IS present, replace upper thermostat.
B) Rated voltage NOT present, upper thermostat is okay. Go to step
5 below.
C) Lower than rated voltage IS present, recheck for grounded upper
element (see page 15).
5. Check across terminals L4 and T2 of lower thermostat (see Figure 17).
A) Rated voltage IS present, replace lower thermostat.
B) Rated voltage NOT present, lower thermostat is okay.
C) Lower than rated voltage IS present, recheck for grounded lower
element (see page 15).
Figure 17
20
Page 20
SERVICE PROCEDURE RE-III
Residential Thermostat Testing
Double Element, Simultaneous, Three Phase
Operation.
Water In Tank Is Cold Or Not Enough Hot
Water With Power ON.
1. This procedure assumes line voltage,
ECO and elements are in working order.
2. Adjust temperature setting for both
thermostats to the highest setting.
2. Turn power “ON” to water heater.
3. Set multi-meter to “Volts AC.”
4. Check across terminals L4 and T2 of
upper thermostat (see Figure 18).
A) Rated voltage NOT present,
recheck ECO (see page 14).
If ECO is okay, replace
thermostat.
B) Rated voltage IS present,
proceed to next step.
5. Check across upper element terminals
(see Figure 19).
A) Rated voltage NOT present,
check wire connections from
thermostat to element.
B) Rated voltage IS present,
repeat element testing
see page 15.
6. Check across terminals L1 & L3 of
lower thermostat (see Figure 20).
A) Rated voltage NOT present,
check wire connections from
upper to lower thermostats.
B) Rated voltage IS present,
okay, go to step 7.
7. Check across terminals L4 and T2 of
lower thermostat (see Figure 21).
A) Rated voltage NOT present,
recheck ECO (see page 14). If
ECO is okay, replace thermostat.
B) Rated voltage IS present,
proceed to next step.
8. Check across lower element terminals.
A) Rated voltage NOT present,
check wire connections from
thermostat to element.
B) Rated voltage IS present,
Be sure thermostats are reset to their original
repeat element testing
see page 15.
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 18
Figure 20
Figure 19
Figure 21
WARNING
temperature settings as found prior to
thermostat testing
Page 21
21
SERVICE PROCEDURE RE-III
Residential Thermostat Testing
Double Element, Simultaneous, Three Phase
Operation (continued).
Water Temperature In Tank Is Above Thermostat
Setting.
1. This procedure assumes line voltage, ECO and
elements are in working order.
2. Adjust upper and lower thermostat to the lowest setting.
3. Turn power “ON” to water heater.
4. Set multi-meter to “Volts AC.”
5. Check across terminals L4 and T2 of
upper thermostat (see Figure 22).
A) Rated voltage IS present,
replace upper thermostat.
B) Rated voltage NOT present,
upper thermostat is okay. Go to step 6 below.
C) Lower than rated voltage IS present,
recheck for grounded upper element
(see page 15).
6. Check across terminals L4 and T2 of
lower thermostat (see Figure 23).
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 22
A) Rated voltage IS present,
replace lower thermostat.
B) Rated voltage NOT present,
lower thermostat is okay.
C) Lower than rated voltage IS present,
recheck for grounded lower element
(see page 15).
Figure 23
22
Page 22
SERVICE PROCEDURE RE-III
Residential Thermostat Testing
Double Element, Non-Simultaneous, Single Phase,
Off Peak Operation.
Water In Tank Is Cold With Power ON.
1. This procedure assumes line voltage,
ECO and elements are in working order.
2. Turn power “ON” to water heater.
3. Set multi-meter to “Volts AC.”
4. Check across terminals L4 and T2 of
upper thermostat (see Figure 24).
A) Rated voltage NOT present,
recheck ECO (see page 14).
If ECO is okay, replace thermostat.
B) Rated voltage IS present,
proceed to next step.
5. Check across element terminals
(see Figure 25).
A) Rated voltage NOT present,
check wire connections from
thermostat to element.
B) Rated voltage IS present,
Repeat element testing
see page 15.
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 24
Figure 25
Tank Does Not Deliver Enough Hot Water.
1. This procedure assumes line voltage, ECO and elements are in
working order. Be sure OFF PEAK meter has not interrupted
line voltage.
2. Turn power “ON” to water heater and set multi-meter to “Volts AC.”
3. Adjust temperature setting of upper & lower thermostat to the
highest setting. Water temperature in tank must be below thermostat
setting for this test.
4. See Figure 24 above. Check voltage across terminals L4 & T2 of
upper thermostat.
A) Rated voltage IS present, okay, upper thermostat is calling
for heat. Go to step 5 below.
B) Rated voltage NOT present, replace upper thermostat.
5. Adjust temperature setting of upper thermostat to the minimum
setting. Water temperature in tank must be above thermostat setting
for this test.
6. Check voltage across terminals T4 of upper thermostat & L1 of lower
thermostat (see Figure 26).
A) Rated voltage NOT present, replace upper thermostat.
B) Rated voltage IS present, upper thermostat is okay. Go to
step 7 on next page.
Figure 26
Page 23
23
SERVICE PROCEDURE RE-III
Residential Thermostat Testing
Double Element, Non-Simultaneous,
Single Phase, Off Peak Operation.
(continued)
Not Enough Hot Water (continued).
7. Check voltage across terminal T4 of upper
thermostat & T2 of lower thermostat.
(see Figure 27).
A) Rated voltage NOT present,
replace lower thermostat.
B) Rated voltage is present, okay,
go to step 8.
8. Check voltage across lower element
(see Figure 28).
A) Rated voltage NOT present,
check wire connections between
thermostats & element.
B) Rated voltage IS present,
repeat element testing
see page 15.
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 27
Figure 28
WARNING
Be sure thermostats are reset to their original
temperature settings as found prior to
thermostat testing
Water Temperature In Tank Is Above Thermostat Setting.
1. This procedure assumes line voltage, ECO and elements are in working order.
2. Adjust upper and lower thermostats to the lowest setting.
3. Turn power “ON” to water heater and set multi-meter to “Volts AC.”
4. Check across terminals L4 and T2 of upper thermostat (see Figure 24 on page 23).
A) Rated voltage IS present, replace upper thermostat.
B) Rated voltage NOT present, upper thermostat is okay. Go to step 5 below.
C) Lower than rated voltage IS present, recheck for grounded upper element (see page 15).
5. Check across terminals T4 of upper thermostat and T2 of lower thermostat (see Figure 27 above).
A) Rated voltage IS present, replace lower thermostat.
B) Rated voltage NOT present, lower thermostat is okay.
C) Lower than rated voltage IS present, recheck for grounded lower element (see page 15).
24
Page 24
SERVICE PROCEDURE RE-IV
Light Duty Commercial
Thermostat Testing
Double Element, Non-Simultaneous, Single Phase
Operation.
Water In Tank Is Cold With Power ON.
1. This procedure assumes line voltage, ECO and
elements are in working order.
2. Turn power “ON” to water heater.
3. Set multi-meter to “Volts AC.”
4. Check across terminals L4 and T2 of
upper thermostat (see Figure 29).
A) Rated voltage NOT present,
recheck ECO (see page 14). If
ECO is okay, replace thermostat.
B) Rated voltage IS present,
proceed to next step.
5. Check across element terminals
(see Figure 30).
A) Rated voltage NOT present,
check wire connections from
thermostat to element.
B) Rated voltage IS present,
repeat element testing
see page 15.
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 29Figure 30
Tank Does Not Deliver Enough Hot Water.
1. This procedure assumes line voltage, ECO and elements are in
working order.
2. Turn power “ON” to water heater and set multi-meter to “Volts AC.”
3. Adjust temperature setting of upper & lower thermostat to the
highest setting. Water temperature in tank must be below thermostat
setting for this test.
4. See Figure 29 above. Check voltage across terminals L4 & T2 of
upper thermostat.
A) Rated voltage IS present, okay, upper thermostat is calling
for heat. Go to step 5 below.
B) Rated voltage NOT present, replace upper thermostat.
5. Adjust temperature setting of upper thermostat to the minimum
setting. Water temperature in tank must be above thermostat setting
for this test.
6. Check voltage across terminals L3 & T4 of upper
thermostat (see Figure 31).
A) Rated voltage NOT present, replace upper thermostat.
B) Rated voltage IS present, upper thermostat is okay. Go to
step 7 on next page.
Figure 31
Page 25
25
SERVICE PROCEDURE RE-IV
Light Duty Commercial
Thermostat Testing
Double Element, Non-Simultaneous,
Single Phase Operation (continued)
Tank Does Not Deliver Enough Hot
Water (continued).
7. Check voltage across terminal L3 of upper
thermostat & T2 of lower Thermostat.
(see Figure 32).
A) Rated voltage NOT present,
replace lower thermostat.
B) Rated voltage is present, okay,
go to step 8.
8. Check voltage across lower element
(see Figure 33).
A) Rated voltage NOT present,
Check wire connections between
thermostats & element.
B) Rated voltage IS present,
repeat element testing
see page 15.
WARNING
Be sure thermostats are reset to
their original temperature settings
as found prior to thermostat
testing
Figure 32
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 33
Water Temperature In Tank Is Above Thermostat Setting.
1. This procedure assumes line voltage, ECO and elements are in working order.
2, Adjust upper and lower thermostat to the lowest setting.
3. Turn power “ON” to water heater and Set multi-meter to “Volts AC.”
4. See Figure 32 above. Check across terminal L3 of upper thermostat
& T2 of lower thermostat.
A) Rated voltage IS present, replace lower thermostat.
B) Rated voltage NOT present, okay, go to step 5 below.
C) Lower than rated voltage IS present, recheck for grounded lower
element see page 15.
5. Check across terminal L4 & T2 of upper thermostat (see Figure 34).
A) Rated voltage IS present, replace upper thermostat.
B) Rated voltage NOT present, upper thermostat is okay.
C) Lower than rated voltage IS present, recheck for grounded upper
element see page 15.
Page 26
Figure 34
26
SERVICE PROCEDURE RE-IV
Light Duty Commercial
Thermostat Testing
Double Element, Simultaneous, Single Phase
Operation.
Water In Tank Is Cold Or Not Enough Hot
Water With Power ON.
1. This procedure assumes line voltage,
ECO and elements are in working order.
2. Adjust temperature setting for both
thermostats to the highest setting.
3. Turn power “ON” to water heater.
4. Set multi-meter to “Volts AC.”
5. Check across terminals L4 and T2 of
upper thermostat (see Figure 35).
A) Rated voltage NOT present,
recheck upper ECO
(see page 14). If ECO
is okay, replace upper thermostat.
B) Rated voltage IS present,
proceed to next step.
6. Check across upper element terminals
(see Figure 36).
A) Rated voltage NOT present,
check wire connections from
thermostat to upper element.
B) Rated voltage IS present,
repeat element testing
see page 15.
7. Check across terminal L3 of upper thermostat
and T2 of lower thermostat (see Figure 37).
A) Rated voltage NOT present,
check ECO (see page 14) & wire
connections at upper & lower
thermostats. If okay,
replace lower thermostat.
B) Rated voltage IS present,
proceed to next step.
8. Check across lower element terminals
(see Figure 38).
A) Rated voltage NOT present,
check lower element wire
connections to the thermostats.
B) Rated voltage IS present,
repeat lower element testing
see page 15
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 35Figure 36
WARNING
Be sure thermostats are reset to
their original temperature settings
as found prior to thermostat
testing
Figure 37Figure 38
Page 27
27
SERVICE PROCEDURE RE-IV
Light Duty Commercial
Thermostat Testing
Double Element, Simultaneous, Single Phase
Operation (continued)
Water Temperature In Tank Is Above Thermostat
Setting.
1. This procedure assumes line voltage, ECO and
elements are in working order.
2. Adjust upper and lower thermostat to the lowest setting.
3. Turn power “ON” to water heater.
4. Set multi-meter to “Volts AC.”
5. Check across terminals L4 and T2 of
upper thermostat (see Figure 39).
A) Rated voltage IS present,
replace upper thermostat.
B) Rated voltage NOT present,
upper thermostat is okay. Go to step 6 below.
C) Lower than rated voltage IS present,
recheck for grounded upper element
see page 15.
6. Check across terminal L3 of upper thermostat and
T2 of lower thermostat (see Figure 40).
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 39
A) Rated voltage IS present,
replace lower thermostat.
B) Rated voltage NOT present,
lower thermostat is okay.
C) Lower than rated voltage IS present,
recheck for grounded lower element
see page 15.
Figure 40
28
Page 28
SERVICE PROCEDURE RE-IV
Light Duty Commercial
Thermostat Testing
Double Element, Non-Simultaneous, Three Phase
Operation.
Water In Tank Is Cold With Power ON.
1. This procedure assumes line voltage, ECO and
elements are in working order.
2. Turn power “ON” to water heater.
3. Set multi-meter to “Volts AC.”
4. Check across terminals L4 and T2 of
upper thermostat (see Figure 41).
A) Rated voltage NOT present,
recheck upper ECO. If ECO is okay,
replace thermostat.
B) Rated voltage IS present,
proceed to next step.
5. Check across element terminals
(see Figure 42).
A) Rated voltage NOT present,
check wire connections from
thermostat to element.
B) Rated voltage IS present,
repeat element testing
see page 15.
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 41Figure 42
Tank Does Not Deliver Enough Hot Water.
1. This procedure assumes line voltage, ECO and elements are in
working order.
2. Turn power “ON” to water heater and set multi-meter to “Volts AC.”
3. Adjust temperature setting of upper & lower thermostat to the
highest setting. Water temperature in tank must be below thermostat
setting for this test.
4. See Figure 41 above. Check voltage across terminals L4 & T2 of
upper thermostat.
A) Rated voltage IS present, okay, upper thermostat is calling
for heat. Go to step 5 below.
B) Rated voltage NOT present, replace upper thermostat.
5. Adjust temperature setting of upper thermostat to the minimum
setting. Water temperature in tank must be above thermostat setting
for this test.
6. Check voltage across terminals L3 & T4 of upper
thermostat (see Figure 43).
A) Rated voltage NOT present, replace upper thermostat.
B) Rated voltage IS present, upper thermostat is okay. Go to
step 7 on next page.
Figure 43
Page 29
29
SERVICE PROCEDURE RE-IV
Light Duty Commercial
Thermostat Testing
Double Element, Non-Simultaneous,
Three Phase Operation (continued).
Tank Does Not Deliver Enough Hot Water
(continued).
7. Check voltage across terminal L1 of upper
thermostat & T2 of lower thermostat.
(see Figure 44).
A) Rated voltage NOT present,
Replace lower thermostat.
B) Rated voltage is present, okay,
go to step 8.
8. Check voltage across lower element
(see Figure 45).
A) Rated voltage NOT present,
check wire connections between
thermostats & element.
B) Rated voltage IS present,
repeat element testing
see page 15.
WARNING
Be sure thermostats are reset to
their original temperature settings
as found prior to thermostat
testing
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 44
Figure 45
Water Temperature In Tank Is Above Thermostat Setting.
1. This procedure assumes line voltage, ECO and elements are in working order.
2. Adjust upper and lower thermostat to the lowest setting.
3. Turn power “ON” to water heater and Set multi-meter to “Volts AC.”
4. See Figure 44 above. Check across terminal L1 of upper thermostat
& T2 of lower thermostat.
A) Rated voltage IS present, replace lower thermostat.
B) Rated voltage NOT present, okay, go to step 5 below.
C) Lower than rated voltage IS present, recheck for grounded lower
element.
5. Check across terminal L4 & T2 of upper thermostat (see Figure 46).
A) Rated voltage IS present, replace upper thermostat.
B) Rated voltage NOT present, upper thermostat is okay.
C) Lower than rated voltage IS present, recheck for grounded upper
element, see page 15.
Page 30
Figure 46
30
SERVICE PROCEDURE RE-IV
Light Duty Commercial
Thermostat Testing
Double Element, Simultaneous, Three Phase
Operation.
Water In Tank Is Cold Or Not Enough Hot
Water With Power ON.
1. This procedure assumes line voltage,
ECO and elements are in working order.
2. Adjust temperature setting for both
thermostats to the highest setting.
3. Turn power “ON” to water heater.
4. Set multi-meter to “Volts AC.”
5. Check across terminals L4 and T2 of
upper thermostat (see Figure 47).
A) Rated voltage NOT present,
recheck upper ECO
(see page 14). If ECO
is okay, replace upper thermostat.
B) Rated voltage IS present,
proceed to next step.
6. Check across upper element terminals
(see Figure 48).
A) Rated voltage NOT present,
check wire connections from
thermostat to upper element.
B) Rated voltage IS present,
repeat element testing
see page 15
7. Check across terminal L4 of lower thermostat
and T2 of lower thermostat (see Figure 49).
A) Rated voltage NOT present,
check ECO (see page 14) & wire
connections at upper & lower
thermostats. If okay, replace
lower thermostat.
B) Rated voltage IS present,
proceed to next step.
8. Check across lower element terminals
(see Figure 50).
A) Rated voltage NOT present,
check lower element wire
connections to thermostat.
B) Rated voltage IS present,
repeat lower element testing
see page 15.
Figure 47
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 48
WARNING
Be sure thermostats are reset to
their original temperature settings
as found prior to thermostat
testing
Figure 49
Page 31
Figure 50
31
SERVICE PROCEDURE RE-IV
Light Duty Commercial
Thermostat Testing
Double Element, Simultaneous, Three Phase
Operation (continued).
Water Temperature In Tank Is Above Thermostat
Setting.
1. This procedure assumes line voltage, ECO and
elements are in working order.
2. Adjust upper and lower thermostat to the lowest setting.
3. Turn power “ON” to water heater.
4. Set multi-meter to “Volts AC.”
5. Check across terminals L4 and T2 of
upper thermostat (see Figure 51).
A) Rated voltage IS present,
replace upper thermostat.
B) Rated voltage NOT present,
upper thermostat is okay. Go to step 6 below.
C) Lower than rated voltage IS present,
recheck for grounded upper element
see page 15.
6. Check across terminals L4 & T2 of lower thermostat
(see Figure 52).
WARNING
High voltage exposure. Use caution to avoid
personal injury during this procedure.
Figure 51
A) Rated voltage IS present,
replace lower thermostat.
B) Rated voltage NOT present,
lower thermostat is okay.
C) Lower than rated voltage IS present,
recheck for grounded lower element.
Figure 52
32
Page 32
SERVICE PROCEDURE RE-V
Thermostat Removal and
Replacement
Thermostat Removal
1. Turn power “OFF” to water heater.
2. Remove access cover and insulation.
High voltage exposure. Be sure power is
“OFF” when performing this procedure.
WARNING
3. Remove plastic thermostat protector from thermostat.
4. Disconnect wires from thermostat terminals. It may be necessary to label wires for proper re-connection to
new thermostat.
5. Note thermostat temperature setting for proper setting of new thermostat.
6. Slide thermostat upwards and out of mounting bracket.
Thermostat Replacement
1. Use a stiff brush to remove any debris or loose scale from tank surface where new thermostat will be installed.
2. Slide new thermostat down into thermostat bracket until it snaps into place. IMPORTANT! Thermostat must sit
completely flat or flush to tank surface. An improperly installed thermostat will cause improper water heater operation.
3. Refer to the wire diagram located on the inside of the access cover and reconnect wires to the thermostat. Be
sure wire connections are snug and corrosion free. Do not over tighten, doing so may damage thermostat.
4. Set thermostat to the original thermostat setting found on the old thermostat.
5. Re-install plastic thermostat protector.
6. Re-install insulation and access cover.
7. Restore power to water heater and verify proper heater operation.
Front View
Thermostat Mounting
Tank Surface
Thermostat
Thermostat
mounting
bracket
Side View
Proper Thermostat
Mounting
Proper Thermostat mounting
flush with tank surface
Improper Thermostat mounting.
Thermostat not flush with tank surface
Side View
Improper Thermostat
Mounting
Page 33
33
SERVICE PROCEDURE RE-VI
Heating Element Removal
and Replacement
Heating Element Removal
1. Turn power “OFF” To water heater.
WARNING
High voltage exposure. Be sure power is
“OFF” when performing this procedure.
2. Turn off cold water supply to heater. Connect hose to drain
spigot of water heater and route to an open drain. Open
a nearby hot water faucet to vent heater for draining. Open
drain spigot of water heater and allow heater to drain
to a point below the element(s).
3. Close drain spigot and remove hose.
Heater components and stored water may be
HOT when performing the following steps in
this procedure. Take necessary precaution to
prevent personal injury.
WARNING
4. Remove access cover and insulation.
5. Remove plastic thermostat protector from thermostat.
6. Disconnect wires from element terminals.
7. Remove element from tank using 1-½ deep well socket or appropriate wrench. Unscrew element counter-clockwise to
remove from tank.
8. Be sure to remove old element gasket from the tank. It is not recommended to be re-used.
Heating Element Replacement
1. Check element terminal block for proper electrical rating. NOTE: Some elements have dual ratings, be sure to check
all surfaces of the element terminal block (see illustration below).
2. Apply new element gasket to the new element. Be sure gasket is seated flat against element flange without rolls or
gaps (see illustration below).
3. Clean any debris from element fitting on tank. Lubricate element threads as needed with thread lubricant.
4. Thread new element clockwise into tank. Tighten element using 1-½ deep well socket or appropriate wrench. Do not
over tighten, over tightening may damage element gasket.
5. Reconnect wires to element, be sure wires are snug and corrosion free. Do not over tighten, doing so may damage
terminal block.
6. Resume water supply to heater, be sure tank is full of water and check for leaks.
7. Re-install plastic thermostat protector.
8. Re-install insulation and access cover.
9. To resume operation, BE SURE TANK IS FULL OF WATER and restore power to water heater. Verify proper heater
operation.
34
Date Code
Terminal
Block
Element Rating.
Example: (4500 Watt, 240 Volt)
Element Flange
0642
4500W 240V
RC02404524
Manufacturer Identification
Element Gasket Seated Flat Against
Element Flange Without Rolls or Gaps
Page 34
SERVICE PROCEDURE RE-VII
Dip Tube and Anode Inspection and
Replacement
Diptube Inspection and Replacement
WARNING
Heater components and stored water may be HOT when performing the following steps in
this procedure. Take necessary precaution to prevent personal injury.
Step 1.Turn power “OFF” to water heater.
Step 2.Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain.
Step 3. Close drain spigot and remove hose.
Step 4.Disconnect inlet nipple from plumbing system.
Step 5.With an appropriate wrench, remove inlet nipple/dip tube from the water heater. Use caution not to damage
Step 6.Visually inspect inlet nipple/dip tube. Inlet nipple/dip tube should be free of cracks and any blockage.
Step 7.Upon completion of inspection or subsequent replacement, reinstall inlet nipple/dip tube into heater. Ensure pipe dope
Step 8.To resume operation, BE SURE TANK IS FULL OF WATER and turn power “ON” to water heater.
Open a nearby hot water faucet to vent heater for draining. Open drain spigot of water heater and allow
heater to drain to a point below the inlet connection nipple.
nipple threads.
Hydro-jets located near the bottom of the dip tube should be open and free of any blockage.
Anti-siphon hole located approximately 6" from the bottom of nipple, should be free of any blockage.
Any damage such as cracks, restriction due to deformation or unintentional holes are not field repairable
and the inlet nipple/dip tube must be replaced.
is used on the nipple’s threads. Connect nipple to plumbing system, close spigot and remove drain hose, resume
water supply and refill heater with water.
Anode Inspection and Replacement
Step 1.Turn power “OFF” to water heater.
Step 2.Turn off cold water supply to heater. Connect hose to drain spigot of water heater and route to an open drain.
Open a nearby hot water faucet to vent heater for draining. Open drain spigot of water heater and allow
heater to drain to a point below the outlet connection nipple.
Step 3. Close drain spigot and remove hose.
Step 4.Disconnect outlet nipple from plumbing system.
Step 5.With an appropriate wrench, remove outlet nipple/anode from the water heater. Use caution not to damage
nipple threads.
Step 6.Visually inspect outlet nipple/anode. Outlet nipple/anode should show signs of depletion, this is normal.
If depletion is ½ of the original anode diameter (original diameter approximately ¾”), replacement is
recommended. If any of the steel core of the anode is exposed, replacement is recommended.
Step 7.Upon completion of inspection or subsequent replacement, reinstall outlet nipple/anode into heater. Ensure pipe
dope is used on the nipple’s threads. Connect nipple to plumbing system, close spigot and remove drain hose,
resume water supply and refill heater with water.
Step 8.To resume operation, BE SURE HEATER IS FULL OF WATER and turn power “ON” to water heater.
Page 35
35
Generic Parts List
36
1. T&P Relief Valve
2. Heat Trap Insert (Outlet)
3. Hot Water Outlet/Anode
4. Cover Conduit/Ground
5. Junction Box Cover
6. Heat Trap Insert (Inlet)
7. Cold Water Inlet Diptube
8. Upper Thermostat Protector
9. Upper Thermostat
10. Thermostat Mounting Bracket
11. Heating Element
12. Element Gasket
13. Access Cover
14. Lower Thermostat Protector
15. Lower Thermostat (59T)
16. Brass Drain Valve
17. Thermostat w/High Limit (59T/66T)
18. ASSE Approved Mixing Device
19. Kit Heat Trap
Page 36
Loading...
+ hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.