Bradford White LE16U3-1, LE110U3-1, LE112T3-1, LE115U3-1, LE120U3-1 User Manual

ElectriFLEX LD™ (Light Duty)
Commercial Utility Electric Water Heater
Bradford White ElectriFLEX LD™ Utility Electric Models Feature:
Fully Automatic Thermostat Controls—Fast acting surface-mount
thermostat with high limit energy cut-off (manual reset) for safety.
Direct Heat Transfer With a Single Immersed Element—Transfers heat
directly and efficiently to the water. Screw-in style element.
Vitraglas
superior tank protection from the highly corrosive effects of hot water. This formula (Vitraglas over 1600°F (871°C).
Insulation System—1" (25mm) Non-CFC foam insulation covers the
sides and top of the tank, reducing heat loss. This results in less energy consumption, improved efficiencies, and jacket rigidity.
Water Connections—3⁄4" (19mm) NPT factory-installed true dielectric fittings
extend water heater life and simplify water line connections. Located on the side for easier installation (Fittings packaged separately inside carton).
Protective Magnesium Anode Rod—Provides added protection against
corrosion for long trouble-free service.
Steel Tank—Heavy gauge steel automatically formed, rolled, and welded.
Voltages Available—120V, 208V, 240V, 277V, 380V, 415V, 480V.
Single Phase Operation Only.
Field Conversion Kits—Change voltage, and kW in the field (see options on
following page).
T&P Relief Valve—Installed.
®
Lining—An exclusively engineered enamel formula that provides
®
) is fused to the steel surface by firing at a temperature of
Photo is of
LE112T3-1
Copper Screw Type Immersion Element
(INCOLOY® type immersion element available upon request)
3 or 5-Year Limited Tank Warranties / 1-Year Limited Warranty on Component Parts.
For more information on warranty, please visit www.bradfordwhite.com
For products installed in USA, Canada, and Puerto Rico. Some states do not allow limitations on warranties. See complete copy of the warranty included with the heater.
MANUFACTURED UNDER ONE OR MORE OF THE FOLLOWING U.S. PATENTS: 5,682,666; 7,634,976; 5,660,165; 5,954,492; 6,056,542; 6,935,280; 5,372,185; 5,485,879; 5,574,822; 7,971,560; 7,992,526; 6,684,821; 7,334,419; 7,866,168; 7,270,087; 7,007,748; 5,596,952; 6,142,216; 7,699,026; 5,341,770; 7,337,517; 7,665,211; 7,665,210; 7,063,132; 7,063,133; 7,559,293; 7,900,589; 5,943,984; 8,082,888; 5,988,117; 7,621,238; 7,650,859; 5,761,379; 7,409,925; 5,277,171; 8,146,772; 7,458,341; 2,262,174. OTHER U.S. AND FOREIGN PATENT APPLICATIONS PENDING. CURRENT CANADIAN PATENTS: 2,314,845; 2,504,824; 2,108,186; 2,143,031; 2,409,271; 2,548,958; 2,112,515; 2,476,685; 2,239,007; 2,092,105; 2,107,012. Vitraglas
®
is a registered trademark of Bradford White® Corporation.
1412-A-0918
59
1
59
3
50
59
5
60
3
Liters
ElectriFLEX LD™ (Light Duty) Commercial Utility Electric Water Heater
Recovery
GPH Temperature Rise °F
Wattage
1500W 2000W 2500W 3000W 3500W 4000W 4500W 5000W 5500W 6000W
60
10 14 17 21 24 28 31 34 38 41
80
8 10 13 15 18 21 23 26 29 31
90
7
9 11 14 16 18 21 23 25 28
100
6
8 10 12 14 16 19 21 23 25
120
5 7
9 10 12 14 15 17 19 21
Recovery
LPH Temperature Rise °C
Wattage
1500W 2000W 2500W 3000W 3500W 4000W 4500W 5000W 5500W 6000W
34
38 53 64 79
91 106 117 129 144 155
45
30 38 49 57 68 79 87
98 110 117
50
26 34 42 53 61 68 79 87 95
106
56
23 30 38 45 53 61 72 79 87 95
67
19 26 34 38 45 53 57 64 72 79
Voltage
Wattage
Limitations
1500W 2000W 2500W 3000W 3500W 4000W 4500W 5000W 5500W 6000W
yes yes yes yes
no no no no no no
120V
yes yes yes yes yes yes yes yes yes yes
208V
yes yes yes yes yes yes yes yes yes yes
240V
yes yes yes yes
no yes yes yes
no yes
277V
yes yes yes yes yes yes yes yes yes yes
380V
yes yes yes yes yes yes yes yes yes yes
415V
yes yes yes yes
no yes yes yes yes yes
480V
B
Voltage
Single Element
Wattage
Voltage and Wattage Conversion Kits
1500W 2000W 2500W 3000W 3500W 4000W 4500W 5000W 5500W 6000W
265-46409-01
265-46409-02*
265-46409-03* 265-46409-04*
N/A N/A N/A N/A N/A N/A
120V
265-46409-05 265-46409-06 265-46409-07 265-46409-08 265-46409-09 265-46409-10 265-46409-11
265-46409-12 265-46409-46* 265-46409-47*
208V
265-46409-13 265-46409-05 265-46409-06 265-46409-14 265-46409-07 265-46409-08 265-46409-09 265-46409-15 265-46409-10
265-46409-48*
240V
265-46409-16 265-46409-17 265-46409-18 265-46409-19
N/A 265-46409-20 265-46409-21 265-46409-22
265-46409-40**
265-46409-23
277V
265-46409-24 265-46409-43 265-46409-25 265-46409-26 265-46409-27 265-46409-29 265-46409-30 265-46409-31 265-46409-44 265-46409-45
380V
265-46409-41 265-46409-24 265-46409-43 265-46409-25 265-46409-26 265-46409-27 265-46409-28 265-46409-29 265-46409-30 265-46409-31
415V
265-46409-32 265-46409-33 265-46409-34 265-46409-35
N/A 265-46409-36 265-46409-37 265-46409-38
265-46409-42**
265-46409-39
480V
ElectriFLEX LD™ Utility Electric Models
Model
Number
LE16U3-1† LE110U3-1 LE112T3-1† LE115U3-1 LE120U3-1
Model
Number
LE16U3-1† LE110U3-1 LE112T3-1† LE115U3-1 LE120U3-1
Nominal
Gal.
Capacity
U.S. Gal.
6 10 12 15 19
Nominal
Liter
Capacity
Recovery at 100°F Rise*
Imp. Gal.
5
8 10 13 16
23 38 45 57 72
U.S. GPH
6 6 6 6 6
Recovery
56°C Rise*
Liters/
Hour
23 23 23 23 23
Imp. GPH
5 5 5 5 5
A
Floor to
Top of
Heater
in.
1
16
/2 171/2 273/4 201/4 243/4
A
Floor to
Top of
Heater
mm.
419 445 705 514 629
B
Jacket
Dia.
in.
14 16 14 18 18
B
Jacket
Dia.
mm.
356 406 356 457 457
D
Floor to
C/L of
Hot Water
Conn.
in.
1
/8
10
15
1
21
/8 173/4 181/2
D
Floor to
C/L of
Hot Water
Conn.
mm.
257 381 537 451 470
E
Floor to
C/L of
Cold Water
Conn.
in.
31/8
511/16
3
1
6
/8
3
E
Floor to
C/L of
Cold Water
mm.
79
144
76
156
76
Specify wattage and voltage when ordering. Use chart below for maximum wattages at certain voltages. † Maximum wattage at any voltage is 3000W. For 5 year models, change suffix “3” to “5”. Single element only. *Based on 1500W operation. NSF Kits available when ordering.
B
G
F
Floor to
T&P
Conn.
in.
1
/8
10
14
1
21
/8 163/4 181/2
F
Floor to
T&P
Conn.
mm.
257 355 537 425 470
G
Floor to
Anode
Rod
in.
1
16
/2 911/16 273/4 101/8 181/2
G
Floor to
Anode
Rod
mm.
419 246 705 257 470
Water Conn.
NPT
in.
3
/4
3
/4
3
/4
3
/4
3
/4
Water Conn.
NPT
mm.
19 19 19 19 19
C.E.C. Listed
Approx.
Shipping
Weight
lbs.
33 48 48 55 59
Approx.
Shipping
Weight
kg.
15 22 22 25 27
D
F
G
E
Note: Above chart can be used to determine maximum wattage at certain voltages. **INCOLOY contain only one element. These kits cannot be wired as simultaneous. These are non-simultaneous kits only. Except where noted above, each kit will include two replacement elements, two gaskets, a rating plate overlay and one set of instructions. For water heaters with only one element, please retain the extra element and gasket as a service part.
General:
All models are exempt from NAECA requirements and ASHRAE Standard 90.1b. All models ETL listed. These heaters are wired Single Phase, 120V with one 1500W element, unless otherwise specified. All water and electrical connections are 3/4" (19mm) NPT. All models certified at 300 PSI test pressure (2068 kPa) and 150 PSI working pressure (1034 kPa). Applicable models CSA verified for energy performance in accordance with C191.1-M90.
Dimensions and specifications subject to change without notice in accordance with our policy of continuous product improvement.
10 & 15 Gallon Models
Ambler, PA
A
G
D
A
F
E
6, 12, & 20 Gallon Models
®
element only. * 265-46409-02, -03, -04, -46, -47, & -48
For field service, contact your professional installer or local Bradford White sales representative.