Bradford White JVS, JVH Installation And Operation Instructions Manual

Installation and Operation Instructions Document 1257B
Installation and
Operation Instructions for
Residential Gas-Fired Hydronic Boilers Models JVH, JVS
JVS
JVH
FOR YOUR SAFETY: This product must be installed and serviced by a professional service technician,
Improper installation and/or operation will void the warranty.
Vent damper is optional in some provinces of Canada..
Sizes 50-225
U.S. Patent No. 1,609,692 Canada Patent No. 383,318
, property damage, or death.
WARNING
If the information in this manual is not followed
property damage, personal injury or loss of life.
vapors and liquids in the vicinity of this or any other appliance.
WHAT TO DO IF YOU SMELL GAS
• Do not try to light any appliance.
• Do not touch any electrical switch; do not use any phone in your building.
• Immediately call your gas supplier from a nearby phone. Follow the gas supplier's instructions.
• If you cannot reach your gas supplier, call the
Installation and service must be performed by
supplier.
AVERTISSEMENT Assurez-vous de bien suivres les instructions données dans cette notice pour réduire au minimum le risque d’incendie ou d’explosion ou pour éviter tout dommage matériel, toute blessure ou la mort.
Ne pas entreposer ni utiliser d’essence ni
le voisinage de cet appareil ou de tout autre appareil.
QUE FAIRE SI VOUS SENTEZ UNE ODEUR DE GAZ:
• Ne pas tenter d’allumer d’appareils.
• Ne touchez à aucun interrupteur. Ne pas vous servir des téléphones dansle bâtiment où vous êtes.
• Appelez immédiatement votre fournisseur de gaz depuis un voisin. Suivez les instructions du fournisseur.
• Si vous ne pouvez rejoindre le fournisseur de gaz, appelez le sservice des incendies.
L’installation et l’entretien doivent être assurés par un installateur ou un service d’entretien
H2359000B
238-49219-00B REV 4/14
Page 2
Bradford White Corp
TABLE OF CONTENTS
SECTION 1. General Information
1A. Introduction ....................................................3
1B. Warranty ........................................................ 3
1C. Heater Identication .......................................4
SECTION 2. Boiler Assembly & Placement
2A. Field Assembly ..............................................4
2B. Boiler Placement ...........................................5
2C. Flooring ..........................................................5
2D. Dimensional Information ................................ 6
2E. Clearance / Closet Installations ..................... 8
SECTION 3.
Air and Venting
3A. Combustion Air Supply .................................. 9
3B. Venting .........................................................10
3C. Vertical Venting - Category I ........................ 11
3D-1 Horizontal Venting - Category III ..................12
3D-2 Venting Connections ....................................12
3D-3 Vent Terminations ........................................ 13
3E. Common Venting System ............................13
SECTION 4. Gas Connections
4A. Gas Supply and Piping ................................ 13
4B. Special Precautions for LP .........................15
SECTION 6.
6A. Electrical Wiring ...........................................20
6B. Outdoor Reset .............................................20
SECTION 7.
7A. Filling the System ........................................25
SECTION 8.
Operating Procedures
8A. System Start-up ...........................................26
8B. Sequence of Operation ................................ 26
8C. Operating Instructions, JVH .........................27
8D. Operating Instructions, JVS ......................... 28
8E. Operating Temperature Control ...................29
SECTION 9.
9A. Maintenance ................................................ 31
9B. Electrical Troubleshooting ...........................32
SECTION 10. Replacement Parts
10A. Glossary of Terms ........................................35
10B. Parts List JVH ..............................................36
10C. Parts List JVS ..............................................38
SECTION 5. Water Connections
5A. Water Piping ................................................ 15
5B. By-pass Piping ............................................. 17
5C. Adjusting the bypass ...................................17
5D. Alternate Auto-Bypass Operation ................17
5E. Flow Requirements ...................................... 18
5F. Chilled Water Systems ................................18
5G. Oxygen Permeable Systems ....................... 18
5H. Anti-Freeze ..................................................18
Brute Mini JV
SECTION 1. General Information
1A. Introduction
This manual provides information necessary for
the installation, operation, and maintenance of the Bradford White Model JV low pressure, copper tube hydronic boilers. These boilers are available in two
congurations; the JVH has a hot surface pilot ignition
system and the JVS has an electronic intermittent
ignition device (I.I.D.). Look for the model designation on the rating plate, which can be found on
top of the boiler. All application and installation procedures should
be reviewed completely before proceeding with the
installation. Consult the Bradford White factory, or local factory representative, with any problems or
questions regarding this equipment. Experience has shown that most operating problems are caused by
improper installation.
WARNING
This hydronic boiler must be installed in
accordance with the procedures detailed in this
manual, or the Bradford White warranty will be
voided. The installation must conform to the
requirements of the local jurisdiction having
authority, and, in the United States, to the latest
edition of the National Fuel Gas Code, ANSI Z223.1. In Canada, the installation must conform with the latest edition of CAN/CGA B149.1 OR .2
installation codes for gas burning appliances, and/
or local codes.
Any modications to the boiler, its gas controls,
gas orices, wiring or draft inducer assembly may void the warranty. If eld conditions require modications, consult the factory representative
before initiating such modications.
Page 3
1B. Warranty
Bradford White appliances are covered by a limited warranty. All warranty claims must be made to an authorized
Bradford White wholesale rep / distributor. To nd
information about the wholesalers in your area,
please go to www.bradfordwhite.com. and click on
'Wholesalers'. Claims must include the serial number and model
(this information can be found on the rating plate), installation date, and name of the installer. Shipping costs are not included in the warranty coverage.
Some accessory items are shipped in separate
packages. Verify receipt of all packages listed on the packing slip. Inspect everything for damage
immediately upon delivery, and advise the carrier of
any shortages or damage. Any such claims should be led with the carrier. The carrier, not the shipper, is responsible for shortages and damage to the shipment
whether visible or concealed.
The warranty does not cover damage caused by improper assembly installation, operation or eld modication.
ATTENTION
L' eau chaude chaudière doit être installé en
conformité avec les procédures détaillées dans
ce manuel, ou le Bradford White garantie sera
annulée. L'installation doit être conforme aux
exigences de la juridiction locale ayant l'autorité,
et, aux ÉTATS-UNIS , à la dernière édition du
National gaz carburant Code, ANSI Z223.1. Au
Canada, l'installation doit être conforme à la plus
récente édition de la norme CAN/CGA B149.1
ou .2 codes d'installation gaz pour appareils de
combustion et/ou codes locaux.
Page 4
1C. Heater Identication
Consult the rating plate on the boiler. The following example simplies the heater identication:
Bradford White Corp
1 2 4 5 6 7 8 9 10 11 12 13
3
VJ U 2B
BRADFORD
WHITE
MODEL
J V
JVH
1st thru 3rd CharaCters (Model designation) BJV = Bradford White Corp. Model JV
Brute Mini 4th CharaCter (ignition systeM) s = spark ignition h = hot surfaCe pilot 5th thru 7th CharaCters (size) input MBtu / h 8th CharaCter (fuel) n = natural gas p = propane gas 9th CharaCter (firing systeM) C = on / off 10th CharaCter (ConstruCtion option) s = standard 11th CharaCter (altitude in feet) s = (0 - 2,000) natural or (0 - 5,000) propane h = (2,001 - 5,000) natural i = (5,001 - 8,000) natural and propane J = (8,001 - 10,000 natural and propane 12th CharaCter (Country) u = usa & Canada 13th CharaCter (reVision) 2 = seCond reVision
IGNIT SYST
S H
Table 1. Boiler Model Identication.
SIZE
0 5 0 0 7 5 1 0 0 1 2 5 1 6 0 2 2 5
FUEL
N P
FIRING
SYST
C D
CONST
OPTION
S P
I
J
ALTITUDE
S H
I
J
COUNTRY
U
JVS
1st thru 3rd CharaCters (Model designation) BJV = Bradford White Corp. Model JV
Brute Mini 4th CharaCter (ignition systeM) s = spark ignition h = hot surfaCe pilot 5th thru 7th CharaCters (size) input MBtu / h 8th CharaCter (fuel) n = natural gas p = propane gas 9th CharaCter (firing systeM) D = on / off 10th CharaCter (ConstruCtion option) i = (standard) J = puMp (050-125 only) 11th CharaCter (altitude in feet) s = (0 - 2,000) natural or (0 - 5,000) propane h = (2,001 - 5,000) natural i = (5,001 - 8,000) natural and propane J = (8,001 - 10,000 natural and propane 12th CharaCter (Country) u = usa & Canada 13th CharaCter (reVision) 2 = seCond reVision
REVISION
2
SECTION 2.
Boiler Assembly and Placement
2A. Field Assembly
These boilers are available in two congurations; the JVH has a hot surface ignition pilot and integral draft fan, and the JVS has an electronic intermittent ignition device (I.I.D.). Look for the model designation on the rating plate, which can be found on top of the boiler in the right rear corner.
The Bradford White automatic vent dampers are standard on all JVS models. The Bradford White side wall power venters can be used on JVS models. Special instructions for their installation are included
in the vent damper and power venter package. Read
them carefully before installation.
Brute Mini JV
Vent Damper (JVS only):
1. Brute Mini JVS boilers have built-in draft diverter for natural draft operation.
2. Find the vent damper box which is located in the boiler package.
3. Install the vent damper directly to the top of the
draft diverter outlet with the damper operator
facing to the front of the boiler, and with the ow direction arrow pointing upward. Use the vent
damper wire harness provided with the boiler to connect the vent damper to the boiler. The
bracket end of the harness should be connected to
the vent damper actuator.
4. For Model JVS only: Install the metal plug
provided with the vent damper onto the damper plate hole.
5. Do not modify the automatic vent damper device. It is very important that no other vents are closed. Provide at least six inches clearance between
the automatic vent damper and combustible construction, and be sure to allow access for
servicing the damper.
Temperature/Pressure Gauge: Install the temp/
pressure gauge provided in the parts box.
Page 5
2C. Flooring
JVS model boilers can only be installed on
noncombustible ooring.
JVH model boilers are designed and certied for installation on a combustible oor.
All boilers must be installed on a level oor and
must NEVER be installed on carpeting. NEVER store objects on or around the boiler.
Noncombustible ooring is dened as ooring material and surface nish not capable of being ignited and burning and with no combustible materials against the underside. Acceptable materials are those consisting entirely of a combination of steel, iron, brick, tile, concrete, slate, glass or plaster.
The JVS model boilers can be installed on a
combustible oor if a noncombustible base
assembly, available from Bradford White, is used.
See the JVS Parts List at the back of this manual for
the appropriate Noncombustible Base Kit part number.
2B. Boiler Placement
1. The boiler must be placed to provide clearances
on all sides for maintenance and inspection. There must also be minimum distances maintained from combustible surfaces. Avoid locations which can
be damaged by water or moisture.
2. A minimum of 15" (381mm) access must be
available in front of the boiler for burner tray removal. Consult local codes for clearances to hot water pipes and accessories.
3. If the boiler is to be installed in a garage, all
burners and burner ignition devices must have a minimum 18" (457mm) clearance
above the oor.
4. Boilers can be installed in a closet as long as
the minimum clearances shown in Table 2 are observed. Special attention should be paid to clearances between the front of the boiler and the closet door when it is closed (see Figure 2).
WARNING
This boiler is intended for indoor installation only.
Do not install this boiler in a location subject to
negative pressure, or improper operation will occur.
Avertissement
Cette chaudière est destiné pour une installation
intérieure uniquement. Ne pas installer cette
chaudière dans un endroit soumis à pression
négative, ou fonctionnement incorrect se produira
Figure 1. Typical Combustible Floor Installation.
As an alternative to the Bradford White
Noncombustible Base Kit, in the United States the
National Fuel Gas Code allows a heater to be placed on a combustible surface when there is a platform under the heater made of hollow masonry no less
than 4 inches (102 millimeters [mm]) thick, covered with sheet metal at least 24 gauge thick and extending
Caution
Do not force motor operation when operator is
fastened to the damper by moving the damper
blade, turning the shaft or by turning the position
indicator.
Attention
Ne pas tourner le registre manuellement avec
ou sans courant électrique ou le moteur sera
endommagé.
Page 6
Size A B C
Wate r
Connection
Gas
Connection
in.
mm
in.
mm
in.
mm
50
75 100 125
160
225
13-3/8 13-3/8 16-7/8 16-7/8 20-3/8 25-5/8
340 340 429
429 518 651
3-1/8 2-1/4 5-3/4 5-1/2 7-1/4
10
79
57 146 140 184
254
2-7/8
2
2-7/8
2 2 2
73 51 73 51 51 51
1-1/4 1-1/4 1-1/4 1-1/4 1-1/4 1-1/4
1/2 1/2 1/2 1/2 1/2
3/4
2D. JVH Dimensional Information
Bradford White Corp
Dimensions in
inches
mm
C B
7
180
6
152
2.4
61
25
635
JVH Dimensions
24
610
6
152
7
180
C B
25
635
2.4
61
24
610
Brute Mini JV
Page 7
2D. JVS Dimensional Information
Dimensions in
inches
mm
7
180
9 -1/4
240
Size A B C D E V
in. mm in. mm in. mm in. mm in. mm in. mm 1-1/4 1/2 50 13-3/8 340 27-3/4 710 23-5/8 600 21-3/4 550 26-1/2 670 4 10 1-1/4 1/2 75 13-3/8 340 27-3/4 710 24-1/8 610 21-3/4 550 27-1/2 700 5 13 1-1/4 1/2
100 16-7/8 430 28-3/4 730 24-1/8 610 22-3/4 580 27-1/2 700 5 13 1-1/4 1/2 125 16-7/8 430 28-3/4 730 23-5/8 600 22-3/4 580 27-1/2 700 6 15 1-1/4 1/2 160 20-3/8 518 28-3/4 730 23-5/8 600 22-3/4 580 27-1/2 700 6 15 1-1/4 1/2 225 25-5/8 651 31-1/2 800 23-1/4 590 23-3/4 630 27-1/2 700 7 18 1-1/4 3/4
JVS Dimensions
Water
Conn
Gas
Conn
Page 8
Bradford White Corp
beyond the full width and depth of the heater by at
least 12 inches (305mm) in all directions. The masonry
must be laid with ends unsealed, and joints matched to
provide free circulation of air from side to side through the masonry (see Figure 1). If the boiler is installed in a carpeted alcove, the entire oor of the alcove must
be covered by a noncombustible platform.
2E. Clearance / Closet Installations
All Brute Mini JV's can be installed in a closet as
long as the minimum clearances are observed. See Table 2JVH and Figure 2JVH for
clearances required for the Brute Mini JVH.
See Table 2JVS and Figure 2JVS for clearances required for the Brute Mini JVS
Special attention should be paid to clearances between the front of the boiler and the closet door when it is closed.
Consult the American National Standard Z21.13 for
more information concerning closet installations. In
Canada, refer to the latest edition of CSA-B149.1.
Boiler Sizes 50 - 225 Clearances in cm Left side 2 5 Right side 5 15 Rear 2 5 Front 4 10 Flue (using B-vent) 6 15 Top 23 58
Boiler Sizes 50 - 125 160 - 225 Clearances in cm in cm
Left side 6 15 6 15
Right side 6 15 6 15 Rear 6 15 6 15 Front 4 10 4 10 Flue 6 15 6 15 Top 23 58 36 91
Table 2JVS Minimum Boiler ClearancesTable 2JVH Minimum Boiler Clearances
Note: Clearances listed are manufacturer’s tested values. These are given as minimum values. Where local and national
codes apply, and values are different than those listed use the greater value to ensure safe operation.
Minimum Boiler Clearances from Combustible Surfaces.
Dégagements Minimaux à Assurer Entre Ics Parois de L’appareil et leo Constructions Combustibles
A
2
(51)
2
(51)
TOP
VIEW
4*
10
5
(127)
6
(152)
6 15
6 15
6 15
6
(152)
MIN
Air
Openings
Figure 2JVH. Closet Installation.
B
SIDE
VIEW
Dimensions in
inches (mm).
Dimensions in inches cm.
*6" for models JV160 to JV225.
Figure 2JVS. Closet Installation
Brute Mini JV
Boiler Size Outside Air Area Inside Air Area
sq. in
sq. cm
sq. in.
sq. cm
50
15
97
100
645
75
20
129
100
645
100
25
161
100
645
125
32
206
125
807
160
40
258
160
1032
225
60
387
225
1452
*Area indicated is for one of two openings: one at floor level and one at the ceiling, so the total net free area would be double the figures shown. For special conditions, refer to
NFPA54 ANSI Z223.1. In Canada, refer to the National
Standard CAN1-B149.1 or .2, which differs from this table. NOTE: Check with louver manufacturers for Net Free Area of Louvers. Correct for screen resistance to the Net Free Area if a
screen is used.
SECTION 3.
Air and Venting
3A. Combustion Air Supply
The boiler location must provide sufcient air
supply for proper combustion, and ventilation of
the surrounding area as outlined in the latest edition of U.S. ANSI standard Z223.1 or in Canada, CAN/
CGA-B149.1 or .2, and any local codes that may be applicable.
In general, these requirements specify that the boiler rooms which represent conned spaces should be provided with two permanent air supply openings; one within 12 inches (305mm) of the ceiling, the other within 12 inches (305mm) of the oor.
Page 9
NOTE: In Canada, follow Canadian Standard,
CAN/CGA-B149 or local codes.
Outside Air Supply: When combustion air is
supplied directly through an outside wall, each opening should have a minimum free area of one square inch per 4,000 BTU/h (6 sq. cm per 1.2 kW) input of the total input rating of all appliances in the
enclosed area.
Inside Air Supply: When combustion is supplied
from inside the building, each opening should have a minimum free area of one square inch per 1,000 BTU/h (6 sq. cm per 0.3 kW) input of the total input rating of all appliances in the enclosed area. These openings should never be less than 100 square inches (645 sq. cm).
CHIMNEY
Table 3. Minimum Recommended
Air Supply to Boiler Room
Exhaust Fans or Vents: Any equipment which exhausts air from the boiler room can deplete the
combustion air supply or reverse the natural draft
action of venting system. This could cause ue
products to accumulate in the boiler room. Additional
air must be supplied to compensate for such exhaust.
The information in Table 3 is not applicable in
installations where exhaust fans or blowers of any type are used. Such installations must be designed by qualied engineers. If a blower or fan is used to supply air to the boiler room, the installer should make sure it does not create drafts which could cause nuisance shutdowns. If a
blower is necessary to provide adequate combustion air to the boiler, a suitable switch or equivalent must
CHIMNEY
LINER
Figure 3. Chimney Venting. Figure 4. Vertical Venting.
THIMBLE
CLEANOUT
(20mm PER M)
1/4"
PER FT.
SLOPE
VENT
SYSTEM
BOILER
LINER
THIMBLE
CLEANOUT
1/4"
PER FT.
(20mm PER M)
SLOPE
VENT
SYSTEM
12" (305mm)
BOILER
Page 10
10 (3.0) OR
LESS
Bradford White Corp
MORE THAN 10
(3.0)
2 (0.6) MIN.
WALL OR PARAPET
CHIMNEY
10 (3.0)
OR LESS
2 (0.6)
RIDGE
Figure 5. Vertical Vent Termination.
MIN.
CHIMNEY
3 (0.9)
MIN.
TERMINATION
10 FT. (3.0m)
OR LESS FROM RIDGE,
WALL OR PARAPET
3 (0.9)
MIN.
Dimensions in feet (m).
be wired into the boiler control circuit to prevent the
boiler from ring unless the blower is operating.
The boiler must be completely isolated and protected from any source of corrosive chemical fumes such as those emitted by trichloroethylene, perchloroethylene, chlorine, etc.
3B. Venting
3 (0.9)
MIN.
WALL OR PARAPET
NOTE: NO HEIGHT ABOVE PARAPET REQUIRED WHEN FROM WALLS OR PARAPET IS MORE THAN 10 FT. (3.0m)
CHIMNEY
RIDGE
MORE THAN 10
(3.0)
2 (0.6)
MIN.
CHIMNEY
10 (3.0)
3 (0.9)
MIN.
The boiler vent collar must be fastened directly to an unobstructed vent pipe with rustproof sheet metal
screws no longer than 1/2” (13mm) and located to
prevent interference with the inducer damper.
Do not weld the vent pipe to the boiler collar. The weight of the stack must not rest on the boiler. The
boiler top must be easily removable for normal boiler service and inspection.
Vent Categories: Brute Mini JVS is a natural draft
appliance for Category I venting only. JVH is a
fan-assisted product that can be vented vertically in a
properly-designed Category I system, or can be vented horizontally as a Category III appliance, per this
installation manual.
WARNING
This boiler must be vented in accordance with
Part 7, Venting of Equipment, of the latest edition
of the National Fuel Gas code, ANSI Z223.1 and
all applicable local building codes. In Canada,
follow CAN/CGA B149 Installation codes.
Improper venting of this appliance can result in
excessive levels of carbon monoxide which can
result in severe personal injury or death!
AVERTISSEMENT
Cette chaudière doit être ventilé, conformément
aux dispositions de la partie 7, de la ventilation de
l'équipement, de la dernière édition du National
gaz carburant code, ANSI Z223.1 et tous les codes du bâtiment locaux. Au Canada, CAN/
CGA B149 codes d'installation. Une mauvaise
ventilation de cet appareil peut entraîner des
niveaux excessifs de monoxyde de carbone qui
peut entraîner de graves blessures ou la mort!
IMPORTANT
Only JVH (induced draft) models may be side-wall
vented per Section 3D without the addition of a
properly sized and installed power venter.
JVS must be connected only using Category Type
I methods and materials per Section 3C. JVH may be connected per Category I or III (See Section 3D) methods and materials. See fuel gas code for more
information regarding your venting application.
IMPORTANT
Seulement JVH (induits projet) modèles peut être
paroi ventilé par chapitre 3D sans l'addition de la
bonne taille et de puissance installée venter. JVS
doivent être connectés uniquement en utilisant Type de catégorie I méthodes et matériaux par
Section 3C. JVH peut être connecté par catégorie
I ou III (voir section 3D) Les méthodes et les
matériaux. Voir gaz combustible code pour plus
d'informations concernant votre application
d'aération.
Avoid terminating boiler vents near air conditioning or air supply fans. The fans can pick up exhaust ue products from the boiler and return them to the building, creating a possible health hazard. Avoid oversized vent pipe or extremely long runs
Brute Mini JV
Page 11
of the pipe, which may cause excessive cooling and
condensation.
3C. Vertical Venting - Category I
(JVS and JVH)
All venting must comply with fuel gas code and be installed by a licensed professional.
The Brute Mini JVS or JVH series boiler can
be vented into a masonry chimney, (see Figure 2) provided several conditions are met:
1. The chimney must have an appropriate tile lining
that is clean, properly constructed and properly sized.
2. The chimney passage way shall be examined to
ascertain that it is clear and free of obstructions.
WARNING
Do not store any chemical, cleaners, or other
corrosive material near combustion air openings
or in the room. Avoid locating dryer vents in the
vicinity of combustion air openings. Failure to
prevent corrosive materials from mixing with
combustion air can result in reduced boiler life
and unsafe boiler operation.
AVERTISSEMENT
N’entrepposer aucun produit chimique, produit
nettoyant ou produit corrosif à proximité des
bouches d’air de combustion ou dans la pièce.
Éviter de placer des tuyaux de ventilation pour
sécheuse à proximité des bouches d’air de
combustion. Le fait de laisser des maitières corrosives se mélanger à l’air de combustion risque de réduire le cycle de vie de l’appareil
de chauffage et de compromettre son
fonctionnement.
3. If a chimney rebuild is required, it shall conform to nationally recognized standards (see National Building Code or ANSI/NFPA 211).
4. The boiler must not be connected to a replace, wood stove or other solid fuel burning
equipment.
5. When the boiler and a hot water heater are to be connected to the same chimney, they must have their own vent connector and enter the chimney
at least 6” (152mm) apart.
IMPORTANT NOTE: Always provide a minimum clearance of 6” (152mm) between Type C (single wall)
vent pipe and any combustible materials.
WARNING
Single wall vent pipe must NEVER pass through
interior walls or through oors or ceilings! Failure
to comply with this warning could result in a re
causing property damage, personal injury, or death!
AVERTISSEMENT
Paroi simple tuyau d'évent doit jamais passer par
l'intérieur les murs ou par planchers ou plafonds
! Le non-respect de cet avertissement peut
provoquer un incendie causant des dommages
matériels ou corporels, ou de mort!
When installing the vent system, all applicable
national and local codes must be followed! The use
of thimbles, restops and other protective devices, when penetrating combustible or noncombustible
construction, must be in accordance with all applicable national and local codes.
4 (1.2)
MIN.
VENT
TERMINAL
Dimensions in
feet (m).
Figure 6. Horizontal Vent Termination.
4 (1.2)
MIN.
12 (3.7)
MIN.
VENT TERMINAL
3 (0.9)
MIN.
VENT TERMINAL
LESS THAN
(3.0)
FORCED
AIR INLET
10
6 (1.8) MIN.
GRADE
CAULK JOINTS
ANCHORED
FASTENER
THIMBLE
SHEET METAL
SCREWS
SEAL ENTIRE
CIRCUMFERENCE
OF JOINT
CAULK JOINTS
ANCHORED
FASTENER
EXHAUST
HOOD
VENT TERMINAL DETAIL
Page 12
Si ze
Diameter
No. of
Elbows
Horizontal Run Length
in.
mm
ft.
m
50 - 160
4
102
4
35
10.7
225
4
102
2
10
3.0
225
6
152
4
35
10.7
Bradford White Corp
Vertical vents of the induced draft JVH boilers must
be installed in accordance with the code requirement
for Category 1, Fan Assisted Appliances. Follow the requirements as indicated in the latest edition of ANSI Z223.1/NFPA 54, sizing of Category I Venting System and Appendix G, or in Canada, follow the instruction
of CAN/CGA-B149 installation code. An unused lined chimney can be used as a raceway
for single wall vent pipe, (see Figure 3). Never run vent pipe through a ue that has another appliance
attached to it.
3D-1. Horizontal Venting - Category III
(JVH only)
When venting is horizontal, or cannot meet the requirements of Category I, it can develop positive
pressure and must be installed in accordance with
this section and the specic vent manufacturer’s instructions. Common venting is not allowed in Category III systems.
BOILER VENTING
DETAIL
OUTSIDE WALL
VENT
SYSTEM
THIMBLE
BOILER
VENT TERMINAL
HOOD
Figure 7. Horizontal Venting.
SHEET METAL
SCREWS
12" (305mm)
*
MIN.
CAULK ENTIRE
JOINT, INCLUDING
THE SCREWS
*WHEN HORIZONTAL RUN
EXCEEDS 5 FT. (1.5m)
For best results, horizontal vent systems should
be as short and straight as possible. Material of vent connectors shall be as follows:
Description Manufacturer Product
High Temperature
RTV
2" (51mm) wide
Aluminum foil tape
- adhesively backed
Dow Corning Trade Mate
Venture
Product
#3243
2" (51mm) wide
Aluminum foil tape
3M Product #433
- adhesively backed
Vent Sealing Materials.
Materials Vent Length
In U.S.A.: UL type 304, 316 or 294-C
stainless steel or equal 26 gauge minimum. In Canada: Use "BH-Type" vent material certied to ULD-S636 Class I (more than 135°C, but not more than 245°C
ue gas temperature), made of AL29-4C stainless steel or equal.
Do not use plastic venting of any kind.
Up to a maximum
of 55' (17m) of
equivalent pipe run (including required
elbows).
The boiler vent collar must be fastened to the vent
pipe with rustproof metal screws no longer than 1/2” (13mm) and sealed with high temperature (500ºF / 260ºC) silicone sealant. For larger diameter vent pipes,
use a sealed reducer fastened directly to the boiler collar and seal all joints as indicated in Figure 7.
Allow the sealant to cure for 24 hours before operating
the boiler. The entire vent system must not exceed the size
specied in Table 4. The following criteria must be observed:
1. Attach a vertical pipe at least 12” (305mm) high
to the boiler outlet before the horizontal run if
run exceeds 5 feet (see Figure 5).
2. Support the vent run at 3’ (.9m) intervals with overhead hangers.
3D-2. Vent Connections (JVH only)
The vent system must be gas tight. All seams and joints must be sealed with silicone sealant or adhesive
tape having a minimum temperature rating of 400°F (204ºC). Use at least three corrosion resistant screws at
each slip joint, when required.
For each elbow eliminated, add 5’ (1.5m) of allowable vent.
Table 4. Horizontal Venting Conguration.
3. Pitch down the vent run, toward the vent terminal
(hood), 1/4” per foot (20mm per meter).
4. Do not locate any joint screws at the bottom of
the vent run.
3D-3. Vent Termination (JVH only)
The side wall vent terminal (hood), Bradford White
Brute Mini JV
Page 13
Part Number D2004300 (4”) or D2000401 (6”), must be used when the boiler is vented through a side wall. It provides a means of installing vent pipe through the building wall, and must be located in accordance with ANSI Z223.1/NFPA 54, or in Canada CAN/
CGA-B149 and local applicable codes, (see Figure 6 ).
Locate the vent terminal so that it cannot be
blocked by snow. Most codes requires termination of at least 12” (305mm) above grade, but the installer
must follow local codes.
3E. Common Venting System
WARNING
Operation of appliances with a blocked common
vent may lead to serious injury or death. Safety
devices must be implemented to prevent blocked
common vent operation. If safe operation of all
appliances connected to a common vent cannot
be assured, including prevention of spillage of ue
gasses into living spaces, common venting should
not be applied, and appliances should each be
vented separately.
AVERTISSEMENT
Le fonctionnement des appareils avec un
système d’évacuation bloqué peut provoquer des
blessures graves, voire la mort. Des dispositifs
de sécurité doivent être installés pour éviter le blocage des systèmes d’évacuation. Si le
fonctionnement de tous les appareils connectés
à un système d’évacuation commun ne peut
pas être assuré, y compris la prévention de la
dispersion des gaz toxiques dans les espaces
habités, on ne devrait pas installer un système
d’évacuation commun et chaque appareil devrait
être ventilé séparément.
3. Insofar as it is practical, close all building doors
and windows and all doors between the space in
which the appliances remaining connected to the common venting system are located and other spaces of the building. Turn on clothes dryers and any gas burning appliance not connected to the common venting system. Turn bathroom exhausts, so they will operate at maximum speed. Do not operate a summer exhaust fan. Close replace dampers.
4. Place in operation the appliance being inspected. Follow the lighting instructions.
Adjust thermostat so appliance will operate continuously.
5. Test for spillage at the burner opening after ve
minutes of main burner operation.
6. After it has been determined that each appliance remaining connected to the common venting
system properly vents when tested as outlined
above, return doors, windows, exhaust fans, replace dampers and any other gas burning
appliance to their previous conditions of use.
7. Any improper operation of the common venting
system should be corrected so the installation conforms with the National Fuel Gas Code,
ANSI Z223.1. When re-sizing any portion of the common venting system, the common venting system should be re-sized to approach the minimum size as determined using the appropriate tables in Appendix G in the National Fuel Gas Code, ANSI Z223.1.
SECTION 4. Gas Connections
4A Gas Supply and Piping
When an existing boiler is removed from a common
venting system, the common venting system is likely to be too large for proper venting of the appliances remaining connected to it. At the time of removal of an existing boiler, the following steps shall be followed with each appliance remaining connected to the common venting system
placed in operation, while the other appliances
remaining connected to the common venting system
are not in operation.
1. Seal any unused openings in the common venting
system.
2. Visually inspect the venting system for proper
size and horizontal pitch and determine there is
no blockage or restriction, leakage, corrosion or other deciencies which could cause an unsafe
condition.
WARNING
The Brute Mini JVS and JVH boilers are
designed for use with either natural gas or LP
gas. Check the rating plate to be sure that the
boiler is designed to use the type of gas being
supplied. DO NOT ATTEMPT TO CONVERT
THIS HEATER FOR USE WITH ANY OTHER
TYPE OF FUEL.
AVERTISSEMENT
Les appareils de chauffage à faibles sont conçus
pour être utillsés avec du gaz naturel ou du gaz
de pétrole liquéé (GPL). Vériez l’information
inscrite sur la plaque signalétique du pour vous
assurer que l’appareil est conçu pour le type de
gaz fourni. NE PAS ESSAYER DE CONVERTIR
CET APPAREIL À UN AUTRE TYPE DE GAZ.\
Page 14
Bradford White Corp
1. Gas piping installation must be in accordance with the latest edition of ANSI Z223.1 and all local codes. In Canada, the installation must be in
accordance with CSA-B149.1 and all local codes that apply.
2. Check the gas supply to be sure that it is the same as the gas indicated on the boiler’s plate. Brute Mini JVS and JVH boilers, as shipped from the factory, are certied to operate within the altitude range indicated on the rating plate. If a eld conversion to a different altitude range or different gas should be necessary, conversion
parts are available. Contact a Bradford White representative or the factory for the correct part numbers to order for conversions
Caution
Permanent damage to the gas valve will occur if the following procedures are not followed.
Attention
Vous endommagerez la soupape de gaz
si vous ne respectez pas les procédures suivantes.
3. Use the gures in Table 6 to size the gas inlet piping from the gas meter to the heater. Check all local codes for compliance before installing the
heater.
Supply Pressure Minimum Maximum
Natural Gas 5.5 Inches WC 10.5 Inches WC (1.3 kPa) (2.5 kPa) LP Gas 10.0 Inches WC 13.0 Inches WC
(2.4 kPa) (3.1 kPa)
Table 5. Gas Supply Pressure Requirements.
50-100' 15-30m
100-200'
30-60m
*Note: These gures are for Natural Gas (.65 Sp. Gr.), and are based on 1/2" water column pressure drop. Check supply pressure with a manometer, and local code requirements for variations. For LPG, reduce pipe diameter one size, but main­tain a 1/2" minimum diameter. A 'normal' number of Tees and elbows have been taken into allowance.
Table 6. Natural Gas Pipe Size Requirements*
Gas Supply Inlet
Tee Fitting
3/4 3/4 3/4 1 1 1-1/4
3/4 1 1 1 1-1/4 1-1/4
To Equipment Inlet
Boiler Size
Distance
From Gas
50 75 100 125 160 225
Meter
Pipe Size
0-50
0-15m
3" (76mm)
Figure 8. Gas Supply Piping.
1/2 3/4 3/4 3/4 1 1
DROP
HORIZONTAL
MIN.
TO BOILER
SEDIMENT TRAP OR DRIP LEG
3 in. (76mm) Min.
Nipple
Cap
Figure 9. Typical design for a sediment trap/drip leg.
TO BOILER
RISER
3" (76mm)
MIN.
SEDIMENT TRAP OR DRIP LEG
Brute Mini JV
4. A sediment trap (drip leg) must be installed ahead of the gas controls (see Figure 8). Fit the
trap with a threaded cap which can be removed
for cleaning.
5. Install a manual gas shutoff valve for service and safety. Do not use a restrictive gas cock. Flexible gas connectors, if used, must be CSA rated for the total input rating of the boiler.
6. Disconnect the boiler and its individual shutoff valve from the gas supply system during pressure testing of the system at pressures higher than 1/2 pounds per square inch (psi) (3.45 kilopascals [kPa]). If the test pressure is equal to or less than 1/2 psi (3.45 kPa), close the manual shutoff valve on the heater during the piping pressure test.
7. If the gas supply pressure is less than required, check for undersized pipe between the meter and the boiler, a restrictive tting, or an undersized gas meter. Gas supply pressures to the heater are
listed in Table 5.
NOTE: The maximum inlet gas pressure must not
exceed the specied value. The minimum value listed is for the purpose of input adjustment. Refer to Table 5.
NOTE: The boiler and all other gas appliances sharing the boiler gas supply line must be ring
at maximum capacity to properly measure the
inlet supply pressure. Low gas pressure could be an indication of an undersize gas meter and/or obstructed gas supply line.
8. The correct high re burner manifold gas pressure is stamped on the rating plate. The regulator is pre-set at the factory, and normally requires no further adjustment. For two-stage units (JVS 100-225) be sure unit is able to re at both high and low re.
9. Before operating the boiler, the complete gas
supply system and all connections must be tested
for leaks using a leak detector solution. Do not use an open ame.
Caution
Some leak test solutions (including soap and water) may cause corrosion or stress cracking. Rinse the piping with water after testing.
Attention
Certaines solultions d’essai d’étanchéité (y
compris l’eau et le savon) peuvent causer de
la corrosion ou de la ssuration. Rincez les tuyaux à l’eau apprès l’essai d’étanchéité.
Page 15
4B Special Precautions for LP Gas
LP Gas is heavier than air and can therefore more readily collect or “pool” in enclosed areas if provision
for proper ventilation is not made. Be sure to pay
special attention to proper ventilation for LP gas. Locate boilers a safe distance from LP gas cylinders and lling equipment. In the United States, consult the “National Fuel Gas Code” (NFPA 54 / ANSI Z223.1, latest edition) or in Canada, the Propane Installation Code (CSA-B149.1), any local codes and re protection authorities about specic installation
restrictions in your area.
SECTION 5. Water Connections
5A. Water Piping
Figure 10. shows ‘typical’ plumbing installations. Be sure to provide unions and isolation valves at the boiler inlet and outlet so it can be isolated for service.
Check local codes for specic plumbing requirements before beginning the installation. An ASME pressure relief valve is supplied on all JV boilers, and is pre-set at 30 PSI. The valve outlet piping must discharge to a drain. Under no circumstances should the relief valve piping be a
closed circuit.
A pressure reducing valve (automatic feed) must be
used to maintain the system at constant proper pressure
(see Figure 10). Supply properly installed purge
valves to eliminate air from each circuit. A drain valve is supplied with the boiler, and can be
found in the plastic bag shipped with each boiler. This valve is to be installed on the lower right side of the boiler and is used for draining the unit. To drain the
boiler completely, open the drain valve and remove the two drain plugs located on the lower left side of the boiler.
Be sure to include air vent devices located at the
highest point in the system to eliminate trapped air,
and an air elimination device near the outlet side of the JV boiler. Manual vent valves are recommended.
Hot water piping should be supported by suitable hangers or oor stands, NOT by the boiler. Due to expansion and contraction of copper pipe, consideration should be given to the type of hangers used. Rigid hangers could transmit noise through the system caused by the piping sliding in the hangers. It is recommended that padding be used when rigid hangers are installed. Gas piping should also be supported by suitable hangers or oor stands, not the boiler. A properly sized expansion tank must be included in
the system.
Page 16
Bradford White Corp
Multi-Zone Pump System
JV
JV
Single Circuit System
Multi-Zone Valve System
Primary Secondary Multi-Zone Pump System
JV
JV
JV
Primary/Secondary Multi-Zone Valve System Low Temperature Installation
KEY: PUMP CHECK VALVE VALVE ZONE VALVE UNION AUTO AIR BLEEDER
Figure 10. Typical Plumbing Installations.
JV
Primary/Secondary Multi-Zone Valve System
Brute Mini JV
15°F 8°C 20°F 11°C 25°F 14°C
Size Flow Rate Headloss Flow Rate Headloss Flow Rate Headloss
gpm l/s ft m gpm l/s ft m gpm l/s ft m
50 5.3 0.3 0.3 0.1 4 0.3 0.2 0.1 3.2 0.2 0.1 0 75 8 0.5 0.6 0.2 6 0.4 0.3 0.1 4.8 0.3 0.2 0.1 100 10.7 0.7 1.3 0.4 8 0.5 0.7 0.2 6.4 0.4 0.5 0.2 125 13.3 0.8 2.2 0.7 10 0.6 1.3 0.4 8 0.5 0.8 0.2 160 17 1.1 2.5 0.8 12.8 0.8 1.8 0.5 10.2 0.6 1.2 0.4 225 24 1.5 5 1.5 18 1.1 3.1 0.9 14.4 0.9 1.9 0.6
gpm = Water Flow in gallons per minute. l/s = Water ow in liters per second.
ft = Pressure drop (headloss) through the boiler in feet of water. m = Pressure drop (headloss) through the boiler in meters of water.
Notes: 1. Shaded area is the recommended ow and temperature rise.
2. Temperature rise and associated ow rates are based on high re operation at the Normal Input Rate from the rating plate.
Table 7. Temperature Rise °F °C.
Page 17
5B By-pass Piping
The following information and suggestions are made on by-pass piping as it affects the temperature rise at the boiler. A boiler temperature rise must be taken on all JV boiler installations. If the temperature rise exceeds 30°F (17°C) at full rate, it is an indication that the boiler is not receiving adequate water ow. Check
the pump for any obstruction, replace the pump with a
larger size where necessary, or install a system by-pass
as indicated in Figures 10 and 11.
A full sized, 1¼" bypass with balancing valves is strongly recommended for all systems, and required when: 1) the boiler is installed without primary­secondary piping in a multiple zone system; 2) when the return water temperature can be expected to be lower than 120°F (44°C); or 3) whenever the system piping on the outlet side of the boiler may allow reduced ow through the heat exchanger, causing excessive temperature rise (see Section 5.2).
Note: Bradford White strongly recommends a primary/
secondary piping system for all installations, especially
sizes 125, 160 and 225. In this system, a circulator is dedicated to pumping the boiler only. This circulator should be sized for the boiler head loss and ow rate.
5C Adjusting the bypass:
Refer to Figure 11. Provide a means of measuring
temperature on the inlet pipe to the boiler such as
using a strap on or infrared thermometer. Starting with both balancing valves fully open, start the boiler. Adjust the balancing valve on the return to the system slowly to provide 120°F (44°C) water at the inlet to the boiler, leaving the bypass balancing valve fully
open. As the system warms up, this valve may need
to be adjusted open. In rare cases, this valve will have to be kept fully open, and the bypass balancing valve
adjusted toward closed to prevent heated bypass water
from satisfying the call for heat when the system is up
to temperature.
5D Alternate Auto-Bypass Operation
Use of the Bradford White thermostatic union, p/n 2400-030, can provide automatic bypass operation in primary - secondary piped systems (but cannot be used when primary - secondary piping is not used). The thermostatic union is installed on the outlet piping, after the bypass assembly. It can be used in place of a balancing valve. It opens fully at 140°F
(see Figure 11). Contact the factory for more information.
All precautions must be taken by the installer to insure that a maximum temperature rise through the boiler does not exceed 30°F (17°C). The temperature rise on boilers installed in multi-zone systems using zone valves must be taken when the zone of the longest length and/or the zone of the highest head loss is open.
A full size, 1¼" diameter by-pass with
balancing valve must be installed if a return water temperature below 120°F (44°C) is expected under operating conditions regardless of boiler size. This may be expected in many systems, including in­oor radiant and snow melt systems.
Page 18
Bradford White Corp
System
From
System
A full size by-pass must be installed.
Figure 11. By-pass Piping.
Balancing
Valve
In (Return)
Left Side View
Balancing Valve
or optional thermo-
static union, Bradford
White P/N 2400-030.
(Primary/Secondary
Out
(Supply)
To
single zone systems. Consult the factory or a qualied system designer if you have more ttings or different
size or type of pipe.
1/2" Pipe 3/4" Pipe 1" Pipe 1-1/4" Pipe
Size Pump Pump Pump Pump H.P. H.P. H.P. H.P.
piping, one zone valve and up to eight elbows for
only)
Drip
Leg
1/25 1/12 1/25 1/12 1/6 1/25 1/12 1/6 1/25 1/12 1/6 50 50 99 390 680
75
* 35 160 300 460 640 * * * * *
100 * * 77 150 260 330 620 * * * * 125 * * 27 80 140 170 360 600 * * *
160 * * * 25 72 57 160 330 190 480 *
* * * * * * * 110 * 69 330
225
*A circulator and/or primary/secondary piping are required. Consult factory.
1. Chart is based on 30°F (17°C) maximum temperature rise.
2. Calculations are based on Type L copper tubing with one zone valve and eight elbows.
3. Typical circulating pumps: SLC-25, Grundfos UP15-42F, or equivalent. 12, Grundfos UP26-42F, or equivalent. Grundfos UP43-75, or equivalent.
Table 8. Maximum Suggested Circuit Length in Feet.
* * * * * * *
1
/25 HP=Taco 007, B&G LR-20 or
1
/
HP=B&G LR-
12
1
/
HP=B&G series HV,
6
5E Flow Requirements
All high recovery, low volume water boilers must have adequate ow for efcient operation. Pump selection is critical to this goal, and pumps should be selected to provide for system design water temperature rise. Table 7 details temperature rise and water ow (GPM)
for the Brute Mini boilers.
Damage from improper ow is not warranteed.
Failure to insure proper water ow through the heat exchanger of the boiler will void the Bradford White warranty. Flow can be veried by measuring
the difference in water temperatures between the
boiler inlet and outlet. For example: For a JV-100 installation, the inlet water temperature is 160°F (71°C), and the outlet temperature is 180°F (82°C) at Normal Input Rate from the rating plate. That means there is a 20° (11°C) temperature rise through the boiler. According to Table 7, that would indicate a ow rate of 8 GPM (0.5L/S). Temperature rise must be measured with the longest (highest head) zone calling for heat alone. Other factors to be considered before selecting a pump are pipe size, the number of ttings throughout
the system, smoothness of the interior surface of the
pipe, the quantity of water owing through the pipe, whether a glycol solution is being used, and the total length of piping in the system. Table 8 provides example pump selection criteria using Type L copper
5F Chilled Water Systems
If the boiler is installed in conjunction with refrigeration systems, it shall be installed so that the chilled medium is piped in parallel with the heating
boiler with appropriate valves to prevent the chilled
medium from entering the heating boiler. When boiler piping is connected to heating coils, which are in close proximity to refrigerated air circulation, there must be ow control valves or other automatic methods to prevent gravity circulation of the boiler water during the cooling cycle.
5G Oxygen Permeable Systems
The JV boiler must not be direct connected to a
heating system utilizing oxygen permeable tubing. Provide a water-to-water heat exchanger between
systems to prevent corrosion of ferrous metals such
as the boiler’s piping wet walls, etc. Air elimination devices are not sufcient protection, and corrosion damage is not covered under the limited warranty.
5H Anti-Freeze
Non-toxic HVAC anti-freeze may be added to the
hydronic system provided the concentration does
not exceed 50%, and the anti-freeze contains an anti
foamant and rust inhibitor. Follow the anti-freeze
manufacturer’s recommendations for yearly or
biannual replacement of system anti-freeze. Never use automotive anti-freeze in a boiler system.
Brute Mini JV
Page 19
The preferred piping configuration for JV boilers is always using primary/secondary piping.
There are some applications that are acceptable without primary/secondary piping, see below.
LOW TEMP SYSTEMS
Pump
To
System
From
System
System Loop with Tempering Valve and Pump with Boiler Loop
To
System
From
System
To
System
with Tempering Valve and Pump
Pump
Balancing
Valve
Primary/Secondary Piping with Field Balancing
(for Fixed Low Return Temperatures)
Pump
Tempering
Valve
Tempering
Valve
Primary/Secondary
Balancing
Valve
Variable Speed
Control
Isolation Valve
Pump
Isolation Valve
Pump
Isolation
Isolation Valve
JV
Isolation
Valve
JV
Valve
Isolation
To
System
From
System
Primary/Secondary Piping with Automatic By-Pass
System
System
System
To
From
To
Pump
Auto
By-Pass
Valve
Balancing
Valve
Pump
Balancing
Pump
Primary/Secondary Piping with By-Pass
(for Fixed Low Return Temperatures)
Laars
Thermostatic
Union
PN 2400-030
Pump
Valve
Pump Isolation
Valve
Isolation
Valve
Valve
Isolation
Valve
Isolation
Valve
JV
JV
120°+
From
System
Primary/Secondary Piping with Variable Speed Injection
Pump
Isolation
Valve
JV
From
System
Primary/Secondary Piping with Laars
Thermostatic Union as an Automatic Bypass
Balancing
Valve
Isolation
Pump
Valve
NON-LOW TEMPERATURE SYSTEMS
(120°F+ Return Temps)
Pump
Isolation
Valve
Isolation
Valve
To
System
From
System
Tempering
Valve
Pump
Tempering Valve with System Loop
and Boiler Loop Pump
Isolation Valve
Pump
Isolation
Valve
JV
To
System
From
System
Simple Primary/Secondary Piping-Hydronic-Not Low Temp
Pump
Figure 12. Typical Plumbing Diagrams.
NOTE: All closed loop systems should include air elimination, expansion tank and feed water inlet. Place at point of lowest
pressure (typically at the inlet of pump).
NOTE: Ball valves should not be used as balancing valves. Only use for shutoff apps.
JV
JV
Page 20
Bradford White Corp
SECTION 6.
6A. Electrical Wiring
Follow these instructions to make the necessary
initial electrical connections.
1. Remove the two screws attaching the front cover of the control box.
2. There are wires coiled in the area on the right side of the control box, supplied with wire nuts: black wires and white wires.
3. Follow the schematic in Figures 14A. and 14B.
Remove the wire nut from the two sets of wires,
and connect the hot lead from the 115V power supply, and the neutral lead to the white wires.
4. Attach the leads from the wall thermostat to the terminal strip, located on the left side of the
control box.
5. Check the boiler wiring and pump for correct voltage, frequency and phase. If the pump circuit
is other than 115V, be sure there is an appropriate transformer or relay installed. The pump relay is
suitable for pumps of 1/3 HP or less (max 5A).
6. For systems with multiple zone pumps or valves
(see Figure 17).
WARNING
The boiler must be electrically grounded in
accordance with the requirements of the authority
having jurisdiction or, in the absence of such
requirements, with the latest edition of the national
Electrical Code, ANSI/NFPA 70, in the U.S. and with
the latest edition of CSA C22.1 Canadian Electrical
Code, Part 1, in Canada. Do not rely on the gas or
water piping to ground the metal parts of the boiler.
Plastic pipe or dielectric unions may isolate the boiler
electrically. Service and maintenance personnel who
work on or around the boiler may be standing on wet
oors and could be electrocuted by an ungrounded
boiler.
AVERTISSEMENT
La chaudière doit être mis à la terre conformément
aux prescriptions de l'autorité ayant juridiction ou,
en l'absence de telles exigences, avec la dernière
édition du national Electrical Code, ANSI/NFPA
70, aux ÉTATS-UNIS et à la dernière édition de la
norme CSA C22.1 Code électrique canadien, partie
1, au Canada. Ne pas compter sur le gaz ou l'eau
tuyauterie à la masse des pièces métalliques de la
chaudière. Tuyau en plastique ou diélectrique les
syndicats peuvent isoler la chaudière électrique.
A means of disconnecting the electrical supply must be provided within sight of the boiler. The pump and
boiler must be wired as shown to insure that the pump
is running whenever the boiler is ring.
Flow Switch: If the system includes a ow switch, it should be wired in series with the high-limit switch. The boiler will not re unless the pump is running and the ow switch is closed. Field installed safety devices and operating
controllers, such as valve end switches, relays, timers,
can be connected to the boiler through the wall thermostat circuit. Do not exceed a draw of 40VA on
the transformer secondary. A 2-Amp fuse is here to protect the transformer.
Terminals
Figure 13A
Figure 13B
6B. Outdoor Reset.
To comply with Federal Law, the Brute Mini JV
automatically sets water temperature based on outdoor
temperature. A sensor (E2347400) supplied must be located outdoors yet out of direct sunlight. If not
connected, the boiler may not be fully functional.
Connect the sensor to the terminals labeled "COM" and "OUTDOOR" located on the left side of the control box, using outdoor rated min 24 gauge wire.
(See Figures 13A and 13B)
(220V OPT)
TRANSFORMER
24V 115V
R
CURVE
WWSD
DHW CALL
HEAT CALL
POWER
12
34
BOILER
SENSOR
120 VAC L
SWITCHED 120 VAC TO PUMP
0.4
2.0
3.6
OFF ON
FIELD
WIRING
INDUCER FAN
BK
BL
BOX
R
R
PILOT
HSI
BOILER
SENSOR
HI
LIMIT
FAN
PROVING
FLAME
ROLL
OUT
DIVIDER
W
BK
(Fourni Lors De
Boiler
Pump 5A Max
(Field Supplied)
Pompe À Chaleur
L'Installation)
R
W
FUSE
O BK
24
3 1
BR
BL
INDUCED DRAFT
MODEL JVH
Y
GAS VALVE/
CONTROLLER
SV9501, SV9601
FAN
Y
R
HOT CHAUD
115/60HZ (220V50Hz OPTIONAL)
POWER SUPPLY
NEUTRAL
NEUTRE
GROUNDING
CONDUCTOR
CABLE DE MISE
A LA TERRE
W
Y
P
G-VERT
G-GREEN
P-MAUVE
P-PURPLE
BK-BLACK
BK-NOIR
W-WHITE
W-BLANC
R-RED
R-ROUGE
Y-YELLOW
Y-JAUNE
BL-BLUE
BL-BLEU
BR-BROWN
BR-BRUN
O-ORANGE
O-ORANGE
THE BOILER WILL NOT OPERATE
WITHOUT THE AUTOMATIC VENT
DAMPER. THE VENT DAMPER WIRE
HARNESS MUST BE INSERTED INTO
THE VENT DAMPER RECEPTACLE.
IN CANADA:
SOME UNITS ARE
SUPPLIED WITH VENT DAMPER
JUMPER PLUG. DO NOT REMOVE
JUMPER UNLESS VENT DAMPER
IS TO BE INSTALLED.
LA CHAUDIÈRE NE FONCTIONNERA
PAS SANS LE VOLET MOTORISÉ
AUTOMATIQUE. LE F AISCEAU DE
CÂBLES DU VOLET MOTORISÉ DOIT
ÊTRE INSÉRÉ DANS LA PRISE DU
VOLET MOTORISÉ
AU CANADA: CERTAINS APPAREILS
SONT MUNIS D’UN CAVAL IER DE
VOLET MOTORISÉ. NE PAS RETIR ER
LE CAVALLIER À MOINS Q UE LE
VOLET MOTORISÉ NE SOIT INST ALLÉ
NOTE:
1. 4-PIN MOLEX AS VIEWED FROM REAR OF BOARD.
INTENDED SIZE:
C
B
1
2
3
4
SOFTWARE
DWG. NO:
B
SHEET 1 OF 1
REV.
AE23446
HOT SURFACE IGN. NAT/LP
WIRE DIAGRAM JVH
1/8"
TITLE:
FRACTIONS
1
.010 DECIMALS .XXX
.03DECIMALS .XX
.1
S
PM 9-20-11
N/A
N/A
FINISH
MATERIAL:
TOLERANCES ARE:
DECIMALS .X
DIMENSIONS ARE IN INCHES.
UNLESS OTHERWISE SPECIFIED:
APPR
ENGR
DRAFT
APPROVALS
ANGLES
DO NOT SCALE DRAWING.
THIRD ANGLE PROJECTION.
SCALE: NONE
SYS
COM
OUT
HEAT CALL
COM CALL
DHW CALL
Brute Mini JV
Page 21
Figure 14A. Wiring Diagram, JVH
Page 22
4
BOILER
SENSOR
SYS
COM
OUT
HEAT CALL
COM CALL
DHW CALL
120 VAC L
SWITCHED 120 VAC TO PUMP
0.4
2.0
3.6
1 2 3 4
OFF ON
FIELD
WIRING
INDUCER FAN
BK
R
CURVE
WWSD
DHW CALL
HEAT CALL
POWER
12
3
BL
C
MV
H
PV
24V 115V
TRANSFORMER
(220V OPT)
SPARK
2 MV/PV
IGNITION
CONTROL
9 SPARK
8 MV
7 TH-W
6 24V
5 24 V (GR)
4 GND
3 PV
1 MV
TEMPERATURE
SENSOR
BOX
DIVIDER
1. 4-PIN MOLEX AS VIEWED RNOTE:
FROM REAR OF BOARD.
Pompe À Chaleur
THE BOILER WILL NOT OPERATE
WITHOUT THE AUTOMATIC VENT
DAMPER. THE VENT DAMPER WIRE
HARNESS MUST BE INSERTED INTO
THE VENT DAMPER RECEPTACLE.
IN CANADA:
SOME UNITS ARE
SUPPLIED WITH VENT DAMPER
JUMPER PLUG. DO NOT REMOVE
JUMPER UNLESS VENT DAMPER
IS TO BE INSTALLED.
LA CHAUDIÈRE NE FONCTIONNERA
PAS SANS LE VOLET MOTORISÉ
AUTOMATIQUE. LE F AISCEAU DE
CÂBLES DU VOLET MOTORISÉ DOIT
ÊTRE INSÉRÉ DANS LA PRISE DU
VOLET MOTORISÉ
AU CANADA: CERTAINS APPAREILS
SONT MUNIS D’UN CAVAL IER DE
VOLET MOTORISÉ. NE PAS RET
IR ER
LE CAVALLIER À MOINS Q UE LE
VOLET MOTORISÉ NE SOIT INST ALLÉ
BK-BLACK
BK-NOIR
W-WHITE
W-BLANC
R-RED
R-ROUGE
Y-YELLOW
Y-JAUNE
BL-BLUE
BL-BLEU
BR-BROWN
BR-BRUN
O-ORANGE
O-ORANGE
P-PURPLE
P-MAUVE
G-GREEN
G-VERT
Pilot Burner
with Spark
Electrode Sensor
Veilleuse À
Capteur
D'Électrode À Étincelles
High Limit
Limite
Supérieure
Power Venter Receptacle
See Doc. 1077
Prise De Ventilation
À Air Pulsé (Voir Manuel)
Gas Valve
HW VR8304
Soupape De Gaz
HW VR8304
Roll-Out
Switch
Limiteur
De Retour
De Falmme
Blocked
Ven
t
Safety
Switch
Vent Damper Receptacle
Prise Du Faisceau De
Câbles De Volet Motorisé
Boiler Pump 5A Max
(Field Supplied)
(Fourni Lors De L'Installation)
Y
O
321
6
54
1 2
43
(2-STAGE ONLY)
BK
BL
FUSE
BK (2-STAGE ONLY)
Y
R
R
R
R
HOT CHAUD
115/60Hz (220V/50Hz OPTIONAL)
POWER SUPPLY
NEUTRAL
NEUTRE
GROUNDING
CONDUCTOR
CABLE DE MISE
A LA TERRE
JUMPER
CAVALIER
W
W
BK
Y
R
BKBK
BK
REMOTE FLAME SENSOR
Y
O
Y
BR
BR
Y
Y
P
JVS H2355500D
Disconnect
for 2 stage
operation
Bradford White Corp
Figure 14B. Wiring Diagram, JVS
Brute Mini JV
Y
O
BR
IGNITION CONTROL
2nd STAGE ONLY
GAS VALVE
MV
MV/PV
PV
H
BK
TEMP CONTROL
3
5
PV
C
6
MV
BLOCKED
VENT
ROLLOUT
SW
BKBKBK
POWER VENTER
HI LIMIT
BL
1
DAMPER
R
24
GND
R
R
BK
N
JVS
BK
TEMP CONTROL
PUMP
5A MAX
TRANSFORMER
110 VAC
FUSE
2A
P
TEMP
CONTROL
TEMP
CONTROL
FAN
PROVING
ROLLOUT
SW
GAS VALVE
R
24
GND
R
BL
R
N
JVH
BK
TEMP CONTROL
BOILER
PUMP
TRANSFORMER
110V
110 VAC
FUSE
1
BR
INDUCER
FAN
TEMP CONTROL
CONTROL
RLY
CONTROL
RLY
24V
31
TEMP
CONTROL
HI LIMIT
GAS
VALVE
4
Page 23
JVH PILOT
1.25
(32)
Figure 15A. JVH Ladder Diagram
0.16
(4)
MAIN BURNER
FLAME PATTERN
Figure 15B. JVS Ladder Diagram
1.25
(32)
JVS PILOT
0.10 TO 0.35 (3 to 9)
MINIMUM FLAME
Figure 16. Main Burner/Pilot Flame Pattern.
LENGTH
0.50 (13)
Dimensions in
inches (mm).
MINIMUM FLAME
LENGTH
0.50 (13)
Page 24
COM
HEAT
Bradford White Corp
Wiring with Taco
Zone Valves
COM
HEAT
COM
HEAT
Wiring with Honeywell
Zone Valves
Wiring with Multiple Zone Pumps
Figure 17. Multiple Zone Wiring.
Brute Mini JV
SECTION 7.
7A Filling the System
Page 25
It is crucial to the efcient operation of the system
that all air be removed from the circuit. For this reason, an air scoop and vent should be located close to the boiler outlet, and there should be a minimum
distance between cold water feed and system purge
valve.
1. When the system has been completely installed,
close all air vents and open the makeup water valve. Allow the circuit to ll slowly.
2. If a make-up water pump is employed, adjust the pressure to provide a minimum of 12 psi (83kPa) at the highest point in the circuit. If a pressure regulator is also installed in the line, adjust it to
the same pressure.
3. Close all valves. Purge one circuit at a time as follows:
a. Open one circuit drain valve and let water
drain out for at least 5 minutes. Be certain there are no air bubbles visible in the water
stream before closing the drain valve.
b. Repeat this procedure for each circuit.
4. Open all valves after all circuits have been purged.
5. Run the system circulating pump for a minimum of 30 minutes with the boiler shut off.
6. Open all strainers in the system, and check for
debris.
7. Recheck all air vents as described in Step 3.
8. Inspect the liquid level in the expansion tank,
with the system full of water, and under normal
operating pressure, to ensure proper water level in the expansion tank.
9. Start up boiler according to the procedures
described in Section 2 and operate the system,
including the pump, boiler, and radiation units,
for one hour.
10. Recheck the water level in the expansion tank. If it exceeds 1/2 of the volume of the tank, open the tank drain and reduce the water level.
11. Shut down the entire system, and vent all
radiation units and high points in the system.
12. Close the water makeup valve and check the strainer in the pressure reducing valve for sediment or debris. Reopen the water makeup
valve.
13. Verify system pressure with the boiler pressure
gauge before beginning regular operation.
14. Within 3 days of start-up, recheck and bleed all air vents and the expansion tank using these
instructions.
Page 26
SECTION 8.
Operating Procedures
Before placing the boiler in operation, check and reset the safety shutoff devices. Once the boiler is connected to the gas and water piping and after all the requirements in previous pages have been met, follow these procedures:
Bradford White Corp
8A. System Start-up
1. Verify that the pump system is operating properly:
a. Shut off the manual gas valve located
outside the boiler.
b. Raise the wall thermostat high enough to
call for heat.
c. The pump should come on immediately. If
it does not, test the electrical circuits.
2. Pilot and Main Burner Lighting:
a. The JV boiler does not require manual
lighting. The pilot is controlled by the automatic ignition system.
b. Different models of the JV boiler utilize
various gas valves. Although the gas valves may have different control knobs, they are
all similar in operation.
c. Understand and follow the operating
instructions that are applicable to the type
of ignition system installed on the boiler.
3. The pilot and main burners will automatically
ignite when there is a call for heat.
8B. Sequence of Operation
1. Wall thermostat will call for heat.
2. Pump relay will turn on the circulating pump.
3. If water temperature is below the limit setting,
the inducer motor relay will turn on the draft
inducer (JVH).
4. Pressure switch will sense the fan (JVH only) operation and send 24 volts to the ame rollout
switch.
5. In normal conditions, the ame rollout switch
will be in a closed position. 24 volts will be sent
to the gas valve/controller, the igniter will glow/spark and the pilot valve will open, lighting
the pilot.
6. After pilot is proven to be lit, the main gas valve will open, the main burners will ignite and
continue until either the primary control, hi-limit or wall thermostat opens.
7. When the wall thermostat is satised, the burners
will shut off. The relays will turn off the draft
inducer (JVH only) and the circulating pump.
When the room temperature falls below the wall
thermostat setting, the cycle will repeat.
Brute Mini JV
Page 27
8C. Operating Instructions
Brute Mini JVH
Page 28
Bradford White Corp
8D. Operating Instructions
Brute Mini JVS
Page 29
1.
Control Access
2.
Panel
Figure 18A.
8.E Operating Temperature Controls
Note: The Temperature Controllers, the Dip switch panel, and the LED panel can be found under the Control Access Panel after removing the bolts.
Two temperature controls are now standard on all
JVS and JVH boilers.
1. The primary temperature controller maintains all normal heating operations.
2. A secondary, mechanical high-limit aquastat provides safe shutdown, should the primary controller fail.
Important: If the secondary controller (See Figure 18A and Figure 18B) dial is set below 220F, it may
inhibit proper operation of the primary controller.
Prior to calling for technical support, please ensure high limit control is set for at least 220F).
Figure 18B. Secondary, mechanical high-limit
aquastat
Pump Operation. When a call for HEAT and/ or DHW is present the boiler pump will turn on. Post purge can be selected via dip switch #5, Pump Post Purge Inactive (Off) /Active 3 min. (On). In the On
position the pump will continue to run for 3 min after
the last call has been satised. When the dip switch is
Off there is no post purge of the pump, the pump turns
off immediately after the last call is removed. Bradford
White strongly recommends using a pump post purge. During WWSD and a call for HEAT is present the
pump will remain off. Pump Exercising The control exercises the boiler pump every 3 days of inactivity. While the
control is exercising the pump all LEDs will turn off and the power LED will ash for 10 seconds. Staging (where applicable – factory setting): Dip #1 is used to select the number of stages: 2-Stage (Off) / Single Stage (On). Note: Use of 2-Stage operation may reduce efciency. For 2-stage operation, the rst stage is cycled on Proportional error and the second stage is cycled based on PI according to a xed algorithm. No user
adjustment is necessary. Note: All stages are turned off when the water
outlet temperature reaches the Maximum setting that is elected via dip switch #4, Boiler Maximum 210°F (Off) / 190°F (On).
Auto Boiler Target Setpoint: Space Heating:
The boiler target temperature is automatically determined from Space Heating and DHW requirements. Space heating is based on outdoor reset. When both a Heat Call and a DHW Call are present
at the same time, the control operates to provide the
higher boiler target temperature.
Heating Curve (Outdoor Temperature Reset)
The control uses a linear heating curve to calculate a target setpoint. The following data are used to calculate the target setpoint from the outdoor
temperature.
1. The heating curve or reset ratio (RR) is set by the potentiometer with a range of 0.4 to 3.6.
2. The room temperature is xed at 70 deg F.
Outdoor Heating Curve=Reset Ratio (RR)=
Temp F 1.0 2.0 3.0
Boiler Target F
-30 170
-20 160
-10 150 0 140
210
210
10 130 190 20
170
30 150 190 40 50 60
130
130
160
130
70 WWSD OFF
Reset Ratio Calculation:
Boiler Target = 70 + RR *(70 - Actual Outdoor)
Table 9
Page 30
JVH050 50 83
JVH075 75 83
JVH100 100 82
JVH125 125 82
JVH160 160 82
JVH225 225 82
JVS050 50 85
JVS075 75 85
JVS100 100 85
JVS125 125 85
JVS160 160 85
JVS225 225 85
136
118
191
166
64
56
8574102
89
131
114
184
160
41
36
62
54
82
71
MiniTherm Series Boiler Natural Gas
Model
Input, MBH
Heating Capacity,
Net AHRI Rating
Bradford White Corp
DHW Operation The boiler target for DHW calls is xed at 180 deg F. Note: There is no control of a DHW pump, so the boiler pump runs with the call for DHW. Limiting The boiler target is limited to a minimum and a maximum target to ensure that the water temperature does not exceed the limits.
1. Target Min - The boiler target minimum is the point at which the stages will start to turn on to
maintain a minimum water temperature. The Boiler
Minimum water temperature is 130 deg F, regardless of other calculated targets. To ensure that the water temperature is greater than the Boiler Minimum water temperature the target is increased to allow the stages
to cycle on by the Boiler Minimum water temperature,
Boiler Minimum target is set to Boiler Minimum +
differential/2.
2. Target Max - The boiler target maximum is the point at which the stages will start to turn off to maintain a maximum water temperature. The Boiler Maximum water temperature is set by setting dip switch #4: Boiler Maximum 210°F (Off) / 190°F (On).
To ensure that the water temperature is less than the
Boiler Maximum water temperature the target is decreased to allow the stages to cycle off by the Boiler Maximum water temperature, Boiler Maximum target is set to Boiler Maximum - differential/2.
Auto Differential The control automatically
adjusts differential to prevent short cycling and maximize the lifetime of components.
WWSD Operation Warm Weather Shutdown -
WWSD feature is selected via dip switch #3, WWSD Inactive (Off) / Active 70°F (On). WWSD point is xed at 70 deg F. Control exits WWSD when the outdoor temp falls to 65 F. When there is a call for HEAT and the control is in WWSD the HEAT call will be ignored. When there is a call for DHW and the control is in WWSD the DHW call will be satised. WWSD LED turns on when control detects WWSD.
Summary of Dip Switch Settings:
#1 Two Stage (Off) / Single Stage (On) (Note: Efciency may be reduced with 2-stage
operation.)
#2 (Off) / Outdoor Reset (On) (Note: Outdoor Reset
is required for residential operation) #3 WWSD Inactive (Off) / Active 70°F (On) #4 Boiler Maximum 210°F (Off) / 190°F (On) #5 Pump Post Purge Inactive (Off) / Active 3 min.
(On)
LEDs State Description
1. Power
2. Heat – On = call for heat; Flashes for Boiler
sensor error
3. DHW – On = call for DHW; Flashes for
outdoor sensor error
4. WWSD – On = Outdoor Reset AND WWSD
Active AND control in WWSD; Flashes for
outdoor sensor error, operation continues with xed boiler target of 140°F.
Summary of Input Sensors:
1. Outdoor sensor - monitors the outside air
temperature for outdoor reset mode
2. Boiler outlet sensor -monitors the water temperature of the boiler outlet supply
3. System Supply sensor - monitors the water temperature of the system supply
The boiler outlet sensor is required at all times. If
the boiler outlet sensor has any fault then the control
will ash an error and turns all stages off. The
system supply sensor is optional and utilizes primary
/ secondary piping. If the system supply sensor has a fault then the control ashes an error message and operates using the boiler outlet sensor (system supply = boiler outlet).
Table 10. Efciencies
Number
MBH
43 37
106 92
Water, MBH AFUE, %
Brute Mini JV
Page 31
SECTION 9.
9A. Maintenance
1. Lubricate the water circulating pump per the instructions on the pump.
2. If a strainer is employed in a pressure reducing valve or the piping, clean it every six months.
3. At start-up, and periodically thereafter, the burner
and pilot ames should be observed. If the ame has the appearance of “sooting” tips, check for debris near the orices and call the service
technician.
4. Ensure proper operation of the mechanical damper, mounted in the ue collar, by observing the damper handle. Be sure the handle swings when the draft inducer starts (depending on the boiler size, swing may be as little as 30°). Remove any obstructions and clean around the pivot rod (handle) holes.
5. Inspect the venting system for obstruction, leakage or corrosion at least once a year.
6. Keep the boiler area clear and free from combustible materials, gasoline, and other ammable vapors and liquids.
7. Be sure that all combustion air and ventilation
openings are unobstructed.
8. Upon completion of the installation, inspect the external surfaces of the heat exchanger for fouling based on the following schedule:
24 hours - 7 days - 30 days - 90 days
Once every six months thereafter.
9. If the boiler is not going to be used for long periods of time in locations where freezing
occurs, it should be completely drained of all water. To accomplish this, there is a drain
valve on the right side of the boiler which can be opened. This will drain the right side of the boiler. There are two plugs located on the left
side of the heater which must be removed to drain that side. Both sides must be drained.
10. The gas and electric controls on the boiler are engineered for long life and dependable
operation, but the safety of the equipment
depends on their proper functioning. It is strongly
recommended that the basic items listed below be
inspected by a qualied service technician every
year.
a. Water temperature controls. b. Pilot safety system.
c. Automatic gas valves. d. Fan proving switch. e. Inducer/Blower assembly. f. Mechanical ue damper operation.
WARNING
The Warranty does not cover damage caused by
lack of required maintenance, lack of water ow,
or improper operating practices.
AVERTISSEMENT
La garantie ne couvre pas les dommages causés
par l'absence d'entretien, absence de débit d'eau,
ou pratiques de fonctionnement irrégulières
Fouling on the external surfaces of the heat exchanger is caused by incomplete combustion, and is a sign of venting and/or combustion air problems. The heat exchanger can be inspected by using a ashlight and placing a mirror under the burners. An alternate method is to remove the venting and top panel to inspect the exchanger from above. The vent system should be inspected at the same time. If cleaning is required:
a. Shut off all power to the boiler.
b. Remove the venting top, ue collector,
draft inducer assembly, and heat exchanger
bafes. c. Remove the burner tray. d. Use a hand-operated spray bottle lled with
water, and a wire brush to clean soot and
loose scale from the underside of the heat
exchanger. DO NOT USE COMPRESSED
AIR, HIGH PRESSURE WATER, OR A
GARDEN HOSE.
e. Clean any fallen debris from the bottom of
the unit.
f. Check to make sure the burner ports and
pilot assembly are free of debris before
returning the burner tray to its original
position.
g. Reassemble the boiler in reverse order,
making sure to replace the heat exchanger
bafes.
Page 32
Bradford White Corp
9B. Electrical Troubleshooting
1. Remove the control box cover on the front of the
boiler.
2. Verify that 115 volts is reaching the boiler by testing across the black wire and the white wire
on the transformer.
3. Verify 24 volts transformer output by placing the meter leads on the yellow and red wires. If
24 volts is not evident, replace the transformer.
Perform the following series of tests with one
meter lead attached to the yellow wire on the transformer.
4. Place the second lead on the “HEAT” connection
on the terminal board. Turn the wall thermostat
high enough to call for heat. If the meter fails to register 24 volts, the thermostat or its circuit may
be defective.
5. Place the second lead on the purple wire terminal
on the hi-limit switch. If no voltage across the switch, check for defective hi-limit, open circuit due to excessive water temperature, or a low temperature setting.
6. For JVH only, place the second lead on the blue wire terminal on the fan proving switch. If voltage is present, skip to step 8. If voltage isn’t
present, connections or the draft inducer/motor could be defective.
Caution
Label all wires prior to disconnection when servicing controls. Wiring errors can cause
improper and dangerous operation. Verify proper
operation after servicing.
Étiquette
de mise en garde tous les ls avant le
débranchement lors de l'entretien. Les erreurs de
câblage peut causer le mauvais et dangereux.
Vérier le fonctionnement correct après l'entretien
WARNING
Follow local regulations with respect to installation
of carbon monoxide (CO) detectors and
manufacturer’s maintenance schedule of the
boiler.
AVERTISSEMENT
Conformez-vous aux réglementations locales
pour ce qui est de l'installation de détecteur de
monoxyde de carbone (CO) et du programme de
maintenance du fabricant de la chaudière.
7. Verify the voltage across the roll-out safety
switch.
8. If it is determined that there is voltage to the gas valve, the pilot is lit and the pilot sensor is
properly positioned, and the thermostat is set
high enough to call for heat, the gas valve or the
pilot assembly may be defective.
9. See Section 8E for LED fault codes on
temperature controller.
Brute Mini JV
Page 33
#
1 Pump not operating No power . . . . .
2 Pilot outage Inlet gas pressure too low . . . . .
3 Flame roll-out on start-up Blocked outlet Check ue damper operation.
4 Flame has lazy yellow tip Low primary air . . . . Correct manifold pressure according to rating plate. Correct
5 Not enough heat Inadequate gas supply . . . . . Gas meter too small. Gas line from meter to boiler too small.
6 Pump noisy Air in volute . . . . . Bleed air from volute. Check pump alignment.
7 Boiler pounding or knocking Too low water ow through boiler
8 Boiler condensing Low water temperature . . . . . Flue product moisture will condense at the start-up until
9 Pump cavities or low water
10 Pressure relief valve opens Waterlogged expansion tank . . . . Drain 2/3 of the water from the expansion
11 Pilot is lit but main burners
12 Boiler short cycles Heat anticipator in room
Symptom Cause Remedy
Check circuit breakers and power source. Replace. Recheck wiring diagrams.
Consult gas utility company. Inlet gas pressure to boiler should be 5.5" (1.4 kPa) to 9.0" (2.2 kPa) water column on natural gas. 10.0" (2.5k Pa) to 14.0" (3.4 kPa) on propane gas.
Pressure should be regulated within limits shown above.
Correct pilot position.
Clean and correct as necessary.
orice size if necessary (see parts list). Clean burner ports if dirty.
open. Should be adjusted to 4.0" (1.0 kPa) W.C. natural gas
9.0" (2.2 kPa) W.C. propane.,
Check temperature rise between inlet and outlet boiler piping. 15°F (8°C) to 25°F (14°C) temperature rise is recommended. If temperature rise is over 25°F (14°C), increase pipe size or pump capacity or locate obstruction. Check for stuck closed zone valves. Check for zone pumps not operating. Check for closed valve in system.
the boiler water temperature reaches the normal operating conditions.
Replace.
Re-pipe expansion tank to suction size of pump at high temperature.
tank.
thermostat should be wired to T-T terminals. For multiple zone systems with ozone pumps, thermostats for extra zones should be wired to R&A terminals.
Check continuity through thermostat circuit with
Increase setting (1.0 is usually satisfactory)
Increase setting to at least 20°F (11°C) over outlet water temperature.
pressure at boiler gauge or bubbles in system at high temperature
will not come on
Pump defective . . . . .
Incorrectly wired . . . . .
Inlet gas pressure to high
causing an unstable blowing
pilot. . . . .
Damaged pilot. . . . Replace.
Dirty pilot. . . . Blow dust or lint out of pilot.
Plugged or undersized pilot. . . . Replace pilot orice.
Pilot out of position (delayed
ignition) . . . .
Blocked heat exchanger or ue
. . . . .
Refractory tile out of place . . . . . Correct or replace tile as necessary.
Low manifold gas pressure . . . . . Gas pressure on boiler manifold, with Modusnap valve wide
Boiler size inadequate . . . . . Replace with boiler of higher input.
Worn coupling or bearings . . . . . Replace worn parts.
. . . . .
Defective ll valves or pressure regulator .
Oversized expansion tank . . . . . Replace.
Expansion tank piped incorrectly
. . . . .
Boiler off on hi-limit control . . . . . Check for low water ow or hi-limit setting.
Boiler incorrectly wired . . . . . On single or multiple zone systems with zone valves, room
Broken wire in thermostat circuit or defective thermostat . . .
thermostat set too low . . . . .
Low water ow through boiler . . Increase size of pump or increase piping size. Hi-limit switch may be set too
low . . . .
Page 34
START
• TURN GAS SUPPLY OFF
• SET THERMOSTAT TO
CALL FOR HEAT
SV9501/SV9601 IS POWERED (24 VAC NOMINAL)
YES
IGNITER WARMS UP AND GLOWS RED
Bradford White Corp
Troubleshooting Honeywell SV9501/SV9601
Hot Surface Pilot System (JVH only)
CHECK:
• LINE VOLTAGE POWER
• LOW VOLTAGE TRANSFORMER
• LIMIT CONTROLLER
NO
NO
• THERMOSTAT
• WIRING
• FAN PROVING SWITCH ON COMBUSTION AIR BLOWER
UNPLUG IGNITER MEASURE VOLTAGE AT TWO BOTTOM TERMINAL OF SV9501/SV9601 (24 VAC NOMINAL)
YES
NO
REPLACE
SV9501/
SV9601
PILOT VALVE OPENS
YES
TURN GAS ON. PILOT BURNER LIGHTS?
YES
MAIN VALVE OPENS?
YES
NO
NO
NO
REPLACE IGNITER
REPLACE SV9501/SV9601
MEASURE VOLTAGE TO SV9501/SV9601. VOLTAGE MUST BE AT LEAST
19.5 VAC.
YES
REPLACE IGNITER
REPLACE IGNITER SENSOR AND RETAIN: RESTART TROUBLE-SHOOTING SEQUENCE. DOES MAIN VALVE OPEN?
YES
NO
NO
CHECK TRANS-FOR­MER, LINE VOLT SUP­PLY
REPLACE SV9501/ SV9601. SAVE OLD IGNIT­ER-SENSOR
FOR
SERVICE.
SYSTEM OK
NO
DISCARD OLD IGNITER SENSOR
Brute Mini JV
SECTION 10. Replacement Parts
10A Glossary of Terms
Air Vent
A device used to purge air from the Circuit. Should be located at the highest point in the Circuit.
Branch
The section(s) of supply and return piping, including
the heat distribution units connected directly to the
trunk. Also referred to as a “zone”.
By-Pass
A section of pipe (including an adjustable valve) that diverts part of the water ow from undersized piping to the boiler. Adjusted to maintain minimum ow requirement (GPM) through the boiler.
Circuit
Entire water circulation piping, beginning and ending at the boiler (Series Loop System).
Expansion Tank (Compression Tank)
Installed in the circuit to accommodate excess water produced by heat expansion.
Heat Distribution Units
Transfers heat from the water supplied by the boiler
to the area to be heated through the use of baseboard, convector, radiator, nned tube. Also known as “radiation”.
Page 35
Reverse-Return Piping
Balanced, equal ow (rst in, last out) piping. Utilized
with multiple boilers and/or radiation. Applied with
single system pumps, or primary-secondary pump.
System Purge Valve
A device used to purge air from the circuit. Should be
located as close as possible to the cold water feed, but not immediately after the cold water feed.
Temperature Controllers The primary temperature controller maintains all
normal heating operations.
A secondary, mechanical high-limit aquastat provides safe shutdown, should the primary controller fail.
Trunk
The section of piping which connects the boiler return and supply with the branch(es). Also known as a “main” or “header”. Should be same size as boiler
inlet/outlet connections.
Zone Pump
Circulators installed in branch piping that divert hot water coming from the boiler into various areas (zones) of a building.
Isolation Valve
Used to isolate the boiler from the circuit. It minimizes
the amount of water drained from the system.
Primary-Secondary Piping
Two or more interconnecting circulating loops, each with its own pump. Primary =System Circuit; Secondary=Boiler Circuit.
Zone Valve
Diverts hot water from the boiler into various areas (zones) of a building.
Page 36
Mini-Therm JVH Size
Description JVH-50 JVH-75 JVH-100 JVH-125 JVH-160 JVH-225
Bradford White Corp
10B Parts List JVH
Gas System
1 Pilots
Pilot Assembly (Nat.), Hot Surface RW2001800 RW2001800 RW2001800 RW2001800 RW2001800 RW2001800
Pilot Assembly (LP), Hot Surface RW2001900 RW2001900 RW2001900 RW2001900 RW2001900 RW2001900 2 Burner with Pilot Bracket L0056500 L0056500 L0056500 L0056500 L0056500 L0056500 3 Main Burner L0052500 L0052500 L0052500 L0052500 L0052500 L0052500
4 Main Gas Valves
Gas Valve, Hot Surface, (Nat.) SV9600H R0384700 R0384700 R0384700 R0384700 R0384700 RV2001900
Gas Valve, Hot Surface, (LP) SV9500H R0384800 R0384800 R0384800 R0384800 R0384800 R0384800
5 Gas Orifices
(0-2000 FT.) Nat., Orifices L0032200 L0032200 L0032200 L0032200 L0050700 L0050700
(2001-5000 FT.) Nat., Orifices L0050700 L0050700 L0050700 L0050700 L0032600 L0032600
(5001-8000 FT.) Nat., Orifices L0032600 L0032600 L0032600 L0032600 L0050300 L0050300
(8001-10,000 FT.) Nat., Orifices L0050300 L0050300 L0050300 L0050300 L0050300 L0050300
(0-5000 FT.) LP, Orifices L0032900 L0032900 L0032900 L0032900 L0032900 L0032900
(5001-8000 FT.) LP, Orifices L0032800 L0032800 L0032800 L0032800 L0032800 L0032800
(8001-10,000 FT.) LP, Orifices L0032700 L0032700 L0032700 L0032700 L0032800 L0032800 6 Gas Manifold L0052601 L0052602 L0052603 L0052604 L0052605 L0052606
Electrical System
7 Controller, Tekra RE2344300 RE2344300 RE2344300 RE2344300 RE2344300 RE2344300 8 Transformerll5/24V(50VA) E2074400 E2074400 E2074400 E2074400 E2074400 E2074400 9 Switch, Air Pressure (0-5000 FT.) E2074501 E2074501 E2074501 E2074502 E2074502 E2074503
Switch, Air Pressure (5001-10000 FT.) E2074504 E2074504 E2074504 E2074505 E2074505 E2074506
10 Blower/Motor, Induced Draft R2069600 R2069600 R2069600 R2069600 R2069600 R2069600 11 Switch, Roll-out Safety E2103200 E2103200 E2103200 E2103200 E2103200 E2103200 12 Switch, Limit R0061300 R0061300 R0061300 R0061300 R0061300 R0061300 13 Ignition Control E2102800 E2102800 E2102800 E2102800 E2102800 E2102800
Wire Harness (not shown) E2347500 E2347500 E2347500 E2347500 E2347500 E2347500
Fuse, 5-Pack, 4-Amp (not shown) RE0084401 RE0084401 RE0084401 RE0084401 RE0084401 RE0084401
Temp Sensor (not shown) E2347600 E2347600 E2347600 E2347600 E2347600 E2347600
Outdoor Sensor (not shown) E2347400 E2347400 E2347400 E2347400 E2347400 E2347400
Water System
14 Heat Exchanger R0402007 R0402008 R0402009 R0402010 R0402011 R0402012 15 Gauge, Temperature/Pressure A2000400 A2000400 A2000400 A2000400 A2000400 A2000400 16 Gauge, Temperature 2400-392 2400-392 2400-392 2400-392 2400-392 2400-392
17 Valve, Pressure Relief 30 PSI R0061400 R0061400 R0061400 R0061400 R0061400 R0061400 18A Well, Immersion, 1/2" NPT E0025902 E0025902 E0025902 E0025902 E0025902 E0025902 18B Well, Immersion, 3/4" NPT E2345700 E2345700 E2345700 E2345700 E2345700 E2345700
19 Valve, Drain 1/2' NPT 70-270 70-270 70-270 70-270 70-270 70-270
Jacket and Fire Box Components
20 Base Weldment 20400701 20400702 20400703 20400704 20400705 20400706
21 Front Panel 11028301 11028301 11028303 11028303 11028306 11028306
22 Jacket 11027901 11027901 11027903 11027903 11027905 11027906
23 Cover, top rear 11028501 11028502 11028503 11028504 11028505 11028506
24 Cover, top front 11028401 11028402 11028403 11028404 11028405 11028406
25 Access Panel, heat exchanger plug 10535900 10535901 10535900 10535901 10535901 10535901
26 Cover, piping jacket top 11047601 11047602 11047601 11047602 11047602 11047602
27 Flue Collector Weldment 20403901 20403902 20403903 20403904 20403905 20403906
28 Burner Tray Weldment 20403001 20403002 20403003 20403004 20403005 20403006
29 Control Box Weldment 20608500 20608500 20608500 20608500 20608500 20608500
30 Control Box Cover 11045901 11045901 11045901 11045901 11045901 11045901
31 Burner Cover 20403304 20403305 20403306 20403304 20403305 20403306
32 Tile Cover 10469504 10469505 10469506 10469504 10469505 10469506
33 Heat Exchanger Baffle 10485307 10485305 10485306 10485307 10485305 10485306
34 Front Refractory T2007704 T2007705 T2007706 T2007704 T2007705 T2007706
35 Rear Refractory T2007804 T2007805 T2007806 T2007804 T2007805 T2007806
36 Orifice Plates
Orifice Plate, Nat. (0-5000 FT.) 20404605 20404607 20404609 20404605 20404607 20404609 Orifice Plate, Nat. (5001-10,000 FT.) 20404605 20404606 20404608 20404605 20404606 20404608 Orifice Plate, LP (0-5000 FT.) 20404606 20404608 20404610 20404606 20404608 20404610
Orifice Plate, LP (5001-10,000 FT.) 20404604 20404606 20404612 20404604 20404606 20404612 37 Flue Outlet D2004201 D2004201 D2004201 D2004201 D2004201 D2004201 38 Bracket, pressure switch 11028200 11028200 11028200 11028200 11028200 11028200
Page 31
25
21
Page 37
26
23
24
22
30
12
13
8
25
7
16
29
15
27
9
37
36
32
10
35
31
18B
(left side)
38
33
18A
4
(right side)
11
5
6
32
34
3
28
2
1
Figure 19A. JVH Parts Identication.
17
14
19
20
Page 38
Mini-Therm JVS Size
Description JVS-50 JVS-75 JVS-100 JVS-125 JVS-160 JVS-225
Gas System
1 Pilots
Pilot Assembly (Nat.) R0061600 R0061600 R0061600 R0061600 R0061600 R0061600
Pilot Assembly (LP) W0039600 W0039600 W0039600 W0039600 W0039600 W0039600
2 Main Gas Valves
Gas Valve, Natural R0385100 R0385100 R0407700 R0407700 R0407700 R0407700
Gas Valve, LP V0077500 V0077500 V0079100 V0079100 V0079100 V0079100
3 Gas Manifold L0052601 L0052602 L0052603 L0052604 L0052603 L0052604
3 Burner, Main L0052500 L0052500 L0052500 L0052500 L0052500 L0052500
4 Burner W/Pilot Bracket L0056500 L0056500 L0056500 L0056500 L0056500 L0056500
Burner/Air Shutter (LP) (not shown) L0055900 L0055900 L0055900 L0055900 L0055900 L0055900
Gas Orifices (not shown)
Gas Orifice (Nat.) L0032200 L0032200 L0032200 L0032200 L0032200 L0032200
Gas Orifice (LP) L0032900 L0032900 L0032900 L0032900 L0032900 L0032900
Electrical System
5 Controller RE2344300 RE2344300 RE2344300 RE2344300 RE2344300 RE2344300
6 Transformer 115/24V (40VA) R0021300 R0021300 R0021300 R0021300 R0021300 R0021300
7 Ignition Control E2102800 E2102800 E2102800 E2102800 E2102800 E2102800
8 Limit Switch R0061300 R0061300 R0061300 R0061300 R0061300 R0061300
9 Blocked Vent SafetySwitch R2061100 R2061100 R2061100 R2061100 R2061100 R2061100
10 Roll-out Safety Switch E2103200 E2103200 E2103200 E2103200 E2103200 E2103200
Wiring Harness (not shown) E2347700 E2347700 E2347700 E2347700 E2347700 E2347700
Hi-Tension Lead (not shown) 10449514 10449514 10449514 10449514 10449515 10449516
Fuse, 5-Pack, 4-Amp (not shown) RE0084401 RE0084401 RE0084401 RE0084401 RE0084401 RE0084401
Temp Sensor (not shown) E2347600 E2347600 E2347600 E2347600 E2347600 E2347600
Outdoor Sensor (not shown) E2347400 E2347400 E2347400 E2347400 E2347400 E2347400
Water System
11 Heat Exchanger R0402001 R0402002 R0402003 R0402004 R0402005 R0402006
12 Pressure Relief Valve, 30PSI R0061400 R0061400 R0061400 R0061400 R0061400 R0061400
13A Well, Immersion, 1/2" NPT E0025902 E0025902 E0025902 E0025902 E0025902 E0025902
13B Well, Immersion, 3/4" NPT E2345700 E2345700 E2345700 E2345700 E2345700 E2345700
14 Drain Valve 1/2" NPT (not shown) 70-216 70-216 70-216 70-216 70-216 70-216
Temp/Pressure Gauge (not shown) R0060600 R0060600 R0060600 R0060600 R0060600 R0060600
Jacket and Fire Box Components
15 Draft Diverter 11020101 11020102 11020103 11020104 11020105 11020106
16 Rear Panel 11020201 11020201 11020203 11020203 11020205 11020206
17 Jacket 11020301 11020301 11020303 11020303 11020305 11020306
18 Top 11020401 11020401 11020403 11020404 11020405 11020406
19 Cover, Piping, Top 11047603 11047604 11047603 11047604 11047604 11047606
20 Flue Collector 20034901 20034902 20034903 20034904 20034905 20034906
21 Access Panel HX, (L&R) 10535900 10535900 10535900 10535900 10535900 10535900
22 Base, Control Box 20608500 20608500 11045700 11045700 11045700 11045700
23 Cover, Control Box 11045901 11045901 11045800 11045800 11045800 11045800
24 Burner Cover 10500601 10500601 10500602 10500602 10494105 10494106
25 Heat Exchanger Baffle 10485301 10485308 10485309 10485311 10485310 10485306
26 Tile Cover 10469501 10469502 10469503 10469504 10469505 10469506
27 Refractory, Front T0022001 T0022002 T0022003 T0022004 T0022605 T0022606
28 Refractory, Rear T0021701 T0021702 T0021703 T0021704 T0021705 T0021706
29 Base Assembly 10467101 10467102 10467103 10467104 10467105 10467106
Non-Combustible Base Kit (optional) 10466701 10466701 10466702 10466702 10466703 10466704
Vent Damper Components
Vent Damper Assembly (not shown)
E2071501 E2071502 E2071502 E2071503 E2071503 E2071504
Vent Damper Harness (not shown) E0099100 E0099100 E0099100 E0099101 E0099101 E0099101
10C Parts List JVS
Bradford White Corp
Brute Mini JVS
Page 39
19
18
9
15
20
17
7
8
5
16
23
6
13B
(on left side)
26
24
22
2
13A
27
21
26
28
12
25
11
14
29
4
1
3
Figure 19B. JVS Parts Identication.
Page 40
Bradford White Corp
H2359000B
Ambler, PA 19002 Tech. Service (800) 334-3393 Service Parts (800) 538-2020 www.BradfordWhite.com Warranty Service (800) 531-2111 Litho in U.S.A. © Bradford White 1401 Document 1257B
Loading...