Bosch ZBR42-3A, ZBR28-3A, ZWB42-3A, ZBR16-3A, ZBR35-3A Installation And Service Instructions Manual

...
WARNING:
Improper installation, set-up, modification, operation or maintenance of the heating system can cause personal injury and property damage. Follow these instructions precisely. If you require assistance or further information, contact a trained and certified installer or the gas supply company.
The operating instructions are part of the technical documents that must be handed over to the owner or operator of the heating system. Explain to the owner or operator how to use the heating system using the operating instructions. Make sure that they are familiar with all required information for the safe and proper operation of the heating system.
NOTE:
In Massachusetts, this appliance must be installed by a licensed plumber or gas fitter.
These instructions are available in English and French.
Please keep these instructions for future reference.
6 720 613 303-00.1O
Gas Condensing Boiler
Greenstar
ZBR16-3A... | ZBR28-3A... | ZBR35-3A... | ZBR42-3A... | ZWB28-3A... | ZWB42-3A...
Installation and Service Instructions for Contractors
6 720 643 068 (2011/06) CA/US
2 | Contents
Contents
1 Guideline to symbols and safety instructions . . . . 4
1.1 Guideline to symbols . . . . . . . . . . . . . . . . . 4
1.2 Safety instructions . . . . . . . . . . . . . . . . . . . 4
2 Scope of delivery . . . . . . . . . . . . . . . . . . . . . . . . . . 6
2.1 ZBR - Boiler for space heating and
loading of indirect fired DHW tanks . . . . . .6
2.2 ZWB - Combi boiler for space heating and
DHW generation . . . . . . . . . . . . . . . . . . . . .7
3 Information about the appliance . . . . . . . . . . . . . . 8
3.1 Proper use . . . . . . . . . . . . . . . . . . . . . . . . . 8
3.2 Overview of boiler types . . . . . . . . . . . . . . 8
3.3 Rating plate . . . . . . . . . . . . . . . . . . . . . . . . 9
3.4 Appliance description . . . . . . . . . . . . . . . . 9
3.5 Accessories . . . . . . . . . . . . . . . . . . . . . . . 10
3.6 Product dimensions and minimum
clearances . . . . . . . . . . . . . . . . . . . . . . . . . 11
3.7 Appliance layout heating boiler ZBR..-3A . 12
3.8 Appliance layout combi boiler ZWB..-3A . 14
3.9 Electrical wiring heating boiler ZBR..-3A . 16
3.10 Electrical wiring combi boiler ZWB..-3A . 18
3.11 Technical data heating boiler ZBR16-3A... 20
3.12 Technical data heating boiler ZBR28-3A... 22
3.13 Technical data heating boiler ZBR35-3A... 24
3.14 Technical data heating boiler ZBR42-3A... 26
3.15 Technical data combi boiler ZWB28-3A... 28
3.16 Technical data combi boiler ZWB42-3A... 30
3.17 Condensate composition . . . . . . . . . . . . . 32
4 Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
4.1 Compliance with standards and
regulations . . . . . . . . . . . . . . . . . . . . . . . .33
4.2 Operating limits of the boiler . . . . . . . . . 33
4.3 Additional regulations for installation in
Massachusetts . . . . . . . . . . . . . . . . . . . . .34
5 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
5.1 Notes on installation and operation . . . . 35
5.1.1 Notes on installation and operation . . . . 35
5.1.2 Other important information . . . . . . . . . . 36
5.2 Comparing the size of the integrated
expansion vessel . . . . . . . . . . . . . . . . . . . 37
5.3 ZBR..-3A appliances (heating boilers):
Selecting an expansion vessel . . . . . . . . . 38
5.4 Selecting the installation location . . . . . . 38
5.5 Pre-installing pipes . . . . . . . . . . . . . . . . . 39
5.6 Mounting the appliance . . . . . . . . . . . . . 41
5.7 Installing a low water cut off (LWCO) . . 42
5.8 Connecting flue gas accessories . . . . . . . 43
5.8.1 Installation of the exhaust and air
intake system . . . . . . . . . . . . . . . . . . . . . . 44
5.8.2 Approved examples of horizontal and
vertical venting installation . . . . . . . . . . . 47
5.8.3 Vent and combustion air pipe lengths . . 50
5.9 Testing gas and water connections
for leaks . . . . . . . . . . . . . . . . . . . . . . . . . . 51
6 Making the electrical connections . . . . . . . . . . . 52
6.1 General notes . . . . . . . . . . . . . . . . . . . . . 52
6.2 Low voltage electrical connections in the
Heatronic boiler control . . . . . . . . . . . . . . 52
6.2.1 Open the Heatronic boiler control . . . . . 52
6.2.2 Connecting the outdoor temperature
sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
6.2.3 Connecting the DHW tank temperature sensor (only heating boiler ZBR..-3A) . . . 53
6.2.4 Connecting additional accessories . . . . . 54
6.3 Electrical connections in the junction box
(120 VAC) . . . . . . . . . . . . . . . . . . . . . . . . . 55
6.3.1 Mounting rails for junction box . . . . . . . . 55
6.3.2 Connecting an external heating zone
pump or DHW recirculation pump . . . . . . 55
6.3.3 DHW tank loading pump or 3-way valve with spring return (only heating boiler
ZBR..-3A) . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.3.4 Connecting mains power supply . . . . . . . 56
6.4 Connecting the LWCO device . . . . . . . . . 57
Copyright (optional information)6 720 643 068 (2011/06)
Contents | 3
7 Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7.1 Before operating the appliance . . . . . . . . 59
7.2 Switching the appliance ON/OFF . . . . . . . 59
7.3 Setting up space heating . . . . . . . . . . . . . 60
7.4 Programming the FW 200 heating
control unit . . . . . . . . . . . . . . . . . . . . . . . 60
7.5 After commissioning . . . . . . . . . . . . . . . . . 60
7.6 ZBR..-3A appliances (heating boilers) with DHW tank: Setting the DHW temperature 61
7.7 ZWB..-3A appliances (combi boilers):
Setting the DHW temperature . . . . . . . . . 61
7.8 Setting manual summer mode . . . . . . . . . 62
7.9 Setting frost protection . . . . . . . . . . . . . . 62
7.10 Activating the key pad lock . . . . . . . . . . . 63
8 ZBR..-3A appliances (heating boiler) with
DHW tank: Thermal disinfection . . . . . . . . . . . . . 63
9 Boiler circulator . . . . . . . . . . . . . . . . . . . . . . . . . . 64
9.1 Pump anti-seize protection . . . . . . . . . . . 64
9.2 Changing the pump curve of the
boiler pump . . . . . . . . . . . . . . . . . . . . . . . 64
10 Heatronic boiler control settings . . . . . . . . . . . . . 65
10.1 Guideline to service functions . . . . . . . . . 65
10.2 Overview of the service functions . . . . . . 66
10.2.1 First service level . . . . . . . . . . . . . . . . . . . 66
10.2.2 Second service level . . . . . . . . . . . . . . . . . 66
10.3 Description of the service functions . . . . 67
10.3.1 First service level . . . . . . . . . . . . . . . . . . . 67
10.3.2 Second service level . . . . . . . . . . . . . . . . . 73
11 Gas type conversion . . . . . . . . . . . . . . . . . . . . . . . 75
11.1 Converting to a different gas type . . . . . . 75
11.2 Installation location higher than 2,000 feet
(610 m) above sea level . . . . . . . . . . . . . 76
11.3 Setting the gas-air ratio (CO
or O2) . . . . 76
2
11.4 Dynamic gas pressure test . . . . . . . . . . . 78
14 Inspection and maintenance . . . . . . . . . . . . . . . . 81
14.1 Description of various steps . . . . . . . . . . 82
14.1.1 Calling up the latest fault (service
function 6.A) . . . . . . . . . . . . . . . . . . . . . . . 82
14.1.2 Fresh water filter (only combi boiler
ZWB..-3A) . . . . . . . . . . . . . . . . . . . . . . . . .82
14.1.3 Plate type heat exchanger
(only combi boiler ZWB..-3A) . . . . . . . . . . 82
14.1.4 Checking the electrodes . . . . . . . . . . . . . 83
14.1.5 Burner servicing . . . . . . . . . . . . . . . . . . . . 84
14.1.6 Heat exchanger block inspection and
cleaning . . . . . . . . . . . . . . . . . . . . . . . . . .84
14.1.7 Condensate trap cleaning . . . . . . . . . . . . 86
14.1.8 Checking the mixer diaphragm . . . . . . . . 86
14.1.9 Expansion vessel . . . . . . . . . . . . . . . . . . . 87
14.1.10 Setting the boiler water pressure . . . . . . 87
14.1.11 Testing system water quality . . . . . . . . . . 87
14.1.12 Inspecting electrical wiring . . . . . . . . . . . 87
14.2 Checklist for inspection and maintenance 88
15 Readings on the display . . . . . . . . . . . . . . . . . . . . 89
16 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
16.1 Troubleshooting . . . . . . . . . . . . . . . . . . . . 90
16.2 Faults that are shown on the display . . . . 91
16.3 Faults that are not shown on the display 94
16.4 Check sensor values . . . . . . . . . . . . . . . . 95
16.4.1 Outdoor temperature sensor . . . . . . . . . . 95
16.4.2 Additional supply temperature limiter . . . 95
16.4.3 Supply temperature sensor, External supply temperature sensor, DHW tank temperature sensor, DHW temperature
sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . .95
16.5 Replacement code plug . . . . . . . . . . . . . . 96
17 Commissioning log for the appliance . . . . . . . . . 97
18 Spare parts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 99
12 Flue gas test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
12.1 Emissions test button . . . . . . . . . . . . . . . 79
12.2 Measuring CO content of flue gas . . . . . . 79
13 Environmental responsibility/disposal . . . . . . . . . 80
Index . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 115
6 720 643 068 (2011/06)Copyright (optional information)
4 | Guideline to symbols and safety instructions
1 Guideline to symbols and safety instructions
1.1 Guideline to symbols
Warnings
Warnings are indicated in the text by a warning triangle and a gray background.
In case of danger from electric shock, the exclamation point on the warning triangle is replaced with a flash.
Signal words at the beginning of a warning are used to indicate the type and seriousness of the ensuing risk if measures for minimizing damage are not taken.
NOTE indicates that damage to property may occur.
CAUTION indicates possible minor to medium personal
injury.
WARNING indicates possible severe personal injury.
DANGER indicates a potential for loss of life.
Important Information
Important information neither indicating personal injury nor damage to property are marked with this symbol. They are separated by lines above and below the text.
1.2 Safety instructions
Safety first. Never risk your health or your life. Your own safety must always take the highest priority.
Use approved personal protective devices and common sense safety measures.
If you smell gas
B Turn off the gas cock (Æ page 58).
B Open windows and doors.
B Do not operate any electrical switches.
B Extinguish all open flames.
B From outside the building, call gas utility company and
a trained and certified heating contractor.
If you smell flue gas
B Switch OFF the appliance (Æ page 59).
B Open windows and doors.
B Inform a trained and certified heating contractor.
Danger of electric shock when the control panel is open
B Always disconnect the appliance from the mains power
before performing any work. Disconnect the emergency shutoff switch or disengage the heating system circuit breaker.
B Take measures to prevent accidental reconnection.
Additional symbols
Symbol Explanation
B
Æ
Cross-reference to other points in this
Tab. 1 Additional Symbols
Sequence of steps
document or to other documents
Listing/list entry
Listing/list entry (2nd level)
For appliances operating on room air: Danger of flue gas poisoning if supply of combustion air is insufficient
B Safeguard supply of combustion air.
B The ventilation and exhaust openings must never be
plugged. The cross section of the ventilation and exhaust openings must comply with the design specifications at all times.
B Safeguard sufficient supply of combustion air also for
appliances installed at a later date, e.g. kitchen exhaust fans, clothes dryers, and air conditioning units with vent to the outside.
B Never install a barometric nor a thermally controlled
vent damper with this boiler.
B If the ventilation and exhaust openings do not comply
with the specifications, the heating system must never be operated.
B Notify operator and building owner of the defect in
writing.
Copyright (optional information)6 720 643 068 (2011/06)
Guideline to symbols and safety instructions | 5
Danger of explosion of flammable gases.
B Only employ a trained and certified contractor to carry
out work on the gas train.
Installation and conversion
Only have the appliance installed or modified by a trained and certified heating contractor.
Always follow state of the art construction techniques for installation and maintenance, and observe all applicable codes and regulations.
Never modify any parts that carry flue gas.
Only trained and certified contractors are permitted to carry out electrical work. Follow applicable code.
The DHW tank may only be used for heating domestic hot water.
Never close the outlet of safety valves. Water may be expelled from any safety valve during heat-up.
Inspection and maintenance
The operator is responsible for the safety and environmental compliance of the heating system.
It is recommended to arrange a maintenance and inspection contract with a trained and certified contractor, covering an annual inspection and demand­dependent maintenance. This guarantees high efficiency and environmentally sound combustion.
Do not attempt to repair parts that have built in safety features. Always replace the part. Only use original Bosch spare parts. Bosch does not accept responsibility for damage caused by third party spare parts.
Combustion air/room air
B To prevent corrosion, keep the supply of combustion/
room air free of corrosive substances (e.g. halogenated hydrocarbons that contain chlorine or fluorine compounds).
B Avoid drawing in combustion air from outdoors that is
excessively loaded with dust or airborne particles. Install adequate air filters under the following circumstances:
– Air supply is contaminated with dust from dirt roads
and paths.
– Air supply is contaminated with dust from production
and processing facilities, e.g. quarries, mines, etc.
Airborne seeds from thistles and similar plants.
Halogen-hydrocarbon compounds, e.g. from paint
booths or hair salons.
Risk of system damage due to unsuitable fill water
Risk of system damage due to corrosion or scale formation as the result of using fill and top-up water that does not conform to the system-specific requirements.
Risk of system damage from freezing
The heating system can freeze up and burst in cold weather if it is shut down or locked out.
B Leave the heating system turned on as much as
possible.
B Protect a disabled heating system from freezing by
draining the boiler and water pipes at the lowest point.
Perform maintenance annually. Check the complete heating system for defects and malfunction.
Mitigate defects immediately to avoid larger scale system damage.
To prevent damage to the appliance or the system from descaling agents, remove parts to be descaled during the process.
Explosive and easily combustible materials
Never use or store easily combustible materials (paper, thinners, paints, etc.) near the appliance.
6 720 643 068 (2011/06)Copyright (optional information)
6 | Scope of delivery
2 Scope of delivery
2.1 ZBR - Boiler for space heating and loading of indirect fired DHW tanks
Contents of package 1:
1
2
3
4
1 Gas condensing boiler 2 Set of documents for appliance 3 Mounting bracket with mounting kit 4 Gas conversion kit 5 Adapter for connection of a LWCO
6 720 641 933-22.1O
Fig. 1 Scope of delivery heating boiler ZBR..-3A
10
11
12
5
Contents of package 2: 6 Rail with connection box
6
7
8
7 Flue adapter 8 DHW tank temperature sensor (NTC) 9 Hydraulics connection plate with mounting kit 10 External supply temperature sensor (NTC) 11 Outdoor reset control FW 200 with mounting kit and outdoor
temperature sensor
12 Set of documents for outdoor reset control FW 200
9
Copyright (optional information)6 720 643 068 (2011/06)
2.2 ZWB - Combi boiler for space heating and DHW generation
Contents of package 1:
1
2
1 Gas condensing boiler 2 Set of documents for appliance 3 Mounting bracket with mounting kit 4 Gas conversion kit 5 Adapter for connection of a LWCO
3
4
Scope of delivery | 7
Fig. 2 Scope of delivery combi boiler ZWB..-3A
5
6
7
8
9
10
11
6 720 641 933-04.1O
Contents of package 2: 6 Rail with connection box 7 Flue adapter 8 Hydraulics connection plate with mounting kit 9 External supply temperature sensor (NTC) 10 Outdoor reset control FW 200 with mounting kit and outdoor
temperature sensor
11 Set of documents for outdoor reset control FW 200
6 720 643 068 (2011/06)Copyright (optional information)
8 | Information about the appliance
3 Information about the appliance
ZBR appliances are boilers for central heating and loading
of an indirect fired DHW tank.
ZWB appliances are combi boilers for central heating and on demand DHW heating.
The appliances comply with South Coast Air Quality Management District (SCAQMD) 2012 requirements: (Type-1) 14 Ng/J NOx (and/or 20 ppm at 3% O2).
3.2 Overview of boiler types
Table 2 describes the meaning of the model number:
ZBR16-3
ZBR28-3
ZBR35-3
A 23
A 23
A 23
3.1 Proper use
The appliance may only be installed in closed loop hot water central heating systems.
Any other purpose is considered improper use. Any resulting damage is excluded from the manufacturer's warranty.
The commercial and industrial use of the appliance for generating process heat is not permitted.
ZBR42-3
ZWB28-3
ZWB42-3
A 23
A 23
A 23
Tab. 2 Appliance types
Z Central heating appliance W DHW heating B Condensing technology R Constant temperature control 16 Output up to 54,600 BTU/hr (16 kW) 28 Output and DHW output up to 95,500 BTU/hr (28 kW) 35 Output up to 119,400 BTU/hr (35 kW) 42 Output and DHW output up to 143,300 BTU/hr (42 kW)
-3 Version A Fan-supported appliance 23 Natural gas (NG)
Appliance AHRI Efficiency Rating
ZBR16-3
ZBR28-3
ZBR35-3
ZBR42-3
96.1 %
95.9 %
95.0 %
94.3 %
ZWB28-3
ZWB42-3
Tab. 3 Initial AHRI Rating
95.9 %
94.3 %
Copyright (optional information)6 720 643 068 (2011/06)
Information about the appliance | 9
3.3 Rating plate
The rating plate is located at the right side of the appliance.
6 720 641 933-84.1O
Fig. 3 Position of the rating plate
The rating plate contains the appliance output, model number, approval data and serial number.
3.4 Appliance description
Appliance for wall installation, regardless of chimney and room size
Outdoor reset control FW 200
Intelligent boiler pump control
Heatronic boiler control with 2-wire BUS
Three-speed boiler circulator
Automatic air vent (combi boiler ZWB..-3A only)
Display
Automatic ignition
Continuously-controlled output
Full protection via the Heatronic with flame rod and
solenoid valves
No minimum circulating water flow rate required
Suitable for radiant floor heating
Flue adapter for flue gas and combustion air with test
ports
Variable speed fan
Gas premix burner
Temperature sensor and temperature control for space
heating
Supply temperature sensor
Temperature limiter
Safety relief valve, pressure gauge
Expansion vessel (combi boiler ZWB..-3A only)
Connection possibility for DHW tank temperature
sensor (NTC) (heating boiler ZBR..-3A only)
Flue gas temperature limiter
DHW priority (combi boiler ZWB..-3A only)
Motorized 3-way valve (combi boiler ZWB..-3A only)
Hydraulics connection plate
6 720 643 068 (2011/06)Copyright (optional information)
10 | Information about the appliance
3.5 Accessories
Here you will find a list of typical accessories for this appliance. Refer to the Bosch Product Catalog for a complete overview of all available accessories.
FB 100 room control
Modules for system expansions:
ISM2 for solar systems (DHW heating, space heating
support, pool heating)
– IPM2 for one or two heating zones with pump control
and motorized mixing capability
Copyright (optional information)6 720 643 068 (2011/06)
3.6 Product dimensions and minimum clearances
Information about the appliance | 11
≥ 4" *
(102 mm) *
≥ 4" *
(102 mm) *
17-21/64" (440 mm)
≥ 15"
3-11/32"
(381 mm)
(85 mm)
(850 mm)
33-15/32"
1
≥ 4" **
(102 mm) **
2
(862 mm)
33-15/16"
9-29/64"
(240 mm)
7-7/8"
(200 mm)
3
Fig. 4 Dimensions and minimum clearances (front view, rear view, side view)
1 Appliance jacket 2 Service cover 3 Hydraulics connection plate
33-27/64"
1-3/16"
(30 mm)
≥ 4" *
(102 mm) *
13-57/64"
(849 mm)
(*) Zero clearance from combustibles permitted, but 4" (102 mm)
recommended for serviceability
(**) Distance to door, if mounted inside a closet
(353 mm)
6 720 643 068 (2011/06)Copyright (optional information)
6 720 641 933-01.1O
12 | Information about the appliance
3.7 Appliance layout heating boiler ZBR..-3A
26
25
24 23 22 21 20
19
18
27
28
29
30
31
32
33
17
16
34
35
15
36
14
37 38
13
39 40
1
12
2 3 4
11 10
9
41
5
min
6
Fig. 5 Appliance layout heating boiler ZBR..-3A
8
7
6 720 641 933-02.1O
Copyright (optional information)6 720 643 068 (2011/06)
Key to Fig. 5:
1 Heatronic boiler control 2 ON/OFF switch 3 Burner flame indicator 4 Service button 5 Emissions test button 6 Boiler high limit dial 7 Mounting socket for outdoor reset controls 8 DHW thermostat 9 Key pad lock 10 ECO button 11 Reset button 12 Display 13 Condensate trap 14 Test ports for inlet gas pressure 15 Adjustment screw, minimum gas volume 16 Maximum gas adjuster 17 Flue gas temperature limiter 18 Combustion air intake 19 Exhaust pipe 20 Boiler supply pipe 21 Connection for optional low water cut off (LWCO) 22 Additional supply temperature limiter 23 Manual air bleeder 24 Gas/air premix chamber 25 Fan 26 Bracket 27 Wall hanging bracket 28 Exhaust pipe 29 Sight glass 30 Set of electrodes 31 Supply temperature sensor 32 Boiler block temperature limiter 33 Inspection and cleanout cover 34 Condensate collector 35 Boiler circulator 36 Pump speed switch 37 Condensate drain hose 38 Drain cock 39 Safety relief valve discharge hose 40 Pressure relief valve (heating zone) 41 Boiler water pressure gauge
Information about the appliance | 13
6 720 643 068 (2011/06)Copyright (optional information)
14 | Information about the appliance
3.8 Appliance layout combi boiler ZWB..-3A
28
27
26
29
30
25 24
23
22
21
20 19
18
17
16
15
14
13
31
32
33
34
35
36
37
38
39 40
41 42
43 44
1
2 3 4 5
min
6
Fig. 6 Appliance layout combi boiler ZWB..-3A
8
7
12 11 10
9
45
6 720 641 933-03.1O
Copyright (optional information)6 720 643 068 (2011/06)
Key to Fig. 6:
1 Heatronic boiler control 2 ON/OFF switch 3 Burner flame indicator 4 Service button 5 Emissions test button 6 Boiler high limit dial 7 Mounting socket for outdoor reset controls 8 DHW thermostat 9 Key pad lock 10 ECO button 11 Reset button 12 Display 13 Condensate trap 14 Test ports for inlet gas pressure 15 Adjustment screw, minimum gas volume 16 DHW temperature sensor 17 Plate-type heat exchanger 18 Automatic air vent 19 Maximum gas adjuster 20 Flue gas temperature limiter 21 Combustion air intake 22 Supply pipe 23 Connection for optional low water cut off (LWCO) 24 Additional supply temperature limiter 25 Gas/air premix chamber 26 Expansion vessel 27 Fan 28 Bracket 29 Wall hanging bracket 30 Exhaust pipe 31 Sight glass 32 Set of electrodes 33 Supply temperature sensor 34 Boiler block temperature limiter 35 Inspection and cleanout cover 36 Condensate collector 37 Flow meter 38 3-way valve 39 Drain cock 40 Condensate drain hose 41 Boiler circulator 42 Pump speed switch 43 Pressure relief valve (heating zone) 44 Safety relief valve discharge hose 45 Boiler water pressure gauge
Information about the appliance | 15
6 720 643 068 (2011/06)Copyright (optional information)
16 | Information about the appliance
3.9 Electrical wiring heating boiler ZBR..-3A
20
21
19
17
6
18
22
24
16
23
9
5
4
3
8
7
6
5
4
23
1
7
NP
LP
2
L
N
LS NS
L
1
N
8
B
B
4
2
F
9
A
8
7
9
10
11
4
25
6
9 VAC
120 VAC
25 VAC
14 15
120 VAC
13
Fig. 7 Electrical wiring diagram heating boiler ZBR..-3A
12
26
6 720 641 933-23.1O
Copyright (optional information)6 720 643 068 (2011/06)
Information about the appliance | 17
Key to Fig. 7:
1 Ignition transformer 2 Boiler high limit dial 3 120 VAC connection 4 DHW tank primary pump or 3-way valve 5 External heating pump for unmixed heating circuit (secondary circuit) 2) or DHW recirculation pump 6 Fuse T 6.3 A (120 VAC) 7 DHW thermostat 8 External safety high limit or low water cut off (LWCO) 9 BUS connection, e.g. heating control 10 Room thermostat – dry contact 11 Outdoor temperature sensor 12 Code plug 13 Diagnostic interface 14 ON/OFF switch 15 Transformer 16 Gas valve 17 Fan 18 Flue gas temperature limiter 19 Supply temperature sensor 20 Flame rod electrode 21 Ignition electrode 22 Boiler block temperature limiter 23 DHW tank temperature sensor (NTC) 24 Boiler circulator 25 Additional supply temperature limiter 26 External system supply temperature sensor
1)
2)
1) Set the service function 1.F,Æ page 67
2) Set the service function 5.E, Æ page 71
6 720 643 068 (2011/06)Copyright (optional information)
18 | Information about the appliance
3.10 Electrical wiring combi boiler ZWB..-3A
19
20
18
16
6
17
22
21
23
24
15
25
9
4
3
2
1
8
7
6
5
4
23
1
26
6
NP
LP
LS NS
L
N
7
B
B
4
2
F
9
A
8
7
8
9
10
6
4
5
9 VAC
120 VAC
13
25 VAC
14
120 VAC
12
Fig. 8 Electrical wiring diagram combi boiler ZWB..-3A
11
27
6 720 641 933-24.1O
Copyright (optional information)6 720 643 068 (2011/06)
Key to Fig. 8:
1 Ignition transformer 2 Boiler high limit dial 3 120 VAC connection 4 External heating pump for unmixed heating circuit (secondary circuit) 5 Fuse T 6.3 A (120 VAC) 6 DHW thermostat 7 External safety high limit or low water cut off (LWCO) 8 BUS connection, e.g. heating control 9 Room thermostat – dry contact 10 Outdoor temperature sensor 11 Code plug 12 Diagnostic interface 13 ON/OFF switch 15 Transformer 14 Gas valve 16 Fan 17 Flue gas temperature limiter 18 Supply temperature sensor 19 Flame rod electrode 20 Ignition electrode 21 Boiler block temperature limiter 22 DHW temperature sensor 23 Boiler circulator 24 3-way valve (Space heating/DHW heating) 25 Flow meter (turbine) 26 Additional supply temperature limiter 27 External system supply temperature sensor
Information about the appliance | 19
1)
or DHW recirculation pump
1)
1) Set the service function 5.E, Æ page 71
6 720 643 068 (2011/06)Copyright (optional information)
20 | Information about the appliance
3.11 Technical data heating boiler ZBR16-3A...
Unit NG LPG (propane)
Output
Maximum nominal output (P Maximum nominal output (P Maximum nominal output (P Max. nominal thermal load (Q Max. nominal thermal load (Q Min. nominal output (P Min. nominal output (P Min. nominal output (P
min
min
min
Min. nominal thermal load (Q Min. nominal thermal load (Q Max. nominal thermal load (Q Max. nominal thermal load (Q Min. nominal thermal load (Q Min. nominal thermal load (Q
Gas connection value
Natural Gas – Hs = 1,010 BTU/ft3 (37.3 MJ/m3)ft Liquid Propane Gas – H
Permissible inlet gas pressure
NG in. W.C. (mbar) 3.5-10.5" (8.7-26.1) – LPG (propane) in. W.C. (mbar) – 8-13" (19.9-32.3)
Calculation values for calculating cross-section to EN 13384
Flue gas mass flow at maximum/minimum nominal output gps 6.8/1.7 6.7/2.6 Flue gas temperature 176/140 °F (80/60 °C) at maximum/minimum
nominal heat input Flue gas temperature 104/86 °F (40/30 °C) at maximum/minimum
nominal heat input CO2 at max. nominal output % 9.4 11.0 CO2 at minimum nominal output % 8.6 10.4
Condensate
Max. condensate quantity (tR = 86 °F (30 °C)) gph (l/h) 0.32 (1.2) 0.32 (1.2) pH level, approx. 4.8 4.8
Tab. 4 Technical data heating boiler ZBR16-3A...
) 104/86 °F (40/30 °C) BTU/hr (kW) 54,900 (16.1) 55,300 (16.2)
max
) 122/86 °F (50/30 °C) BTU/hr (kW) 54,300 (15.9) 54,600 (16.0)
max
) 176/140 °F (80/60 °C) BTU/hr (kW) 50,800 (14.9) 51,200 (15.0)
max
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 51,500 (15.1) 51,900 (15.2)
max
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 57,200 (16.8) 56,400 (16.5)
max
) 104/86 °F (40/30 °C) BTU/hr (kW) 12,600 (3.7) 21,500 (6.3) ) 122/86 °F (50/30 °C) BTU/hr (kW) 12,600 (3.7) 21,500 (6.3) ) 176/140 °F (80/60 °C) BTU/hr (kW) 11,300 (3.3) 19,400 (5.7)
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 11,600 (3.4) 19,800 (5.8)
min
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 12,900 (3.8) 21,500 (6.3)
min
) tank (Hi) BTU/hr (kW) 51,500 (15.1) 51,900 (15.2)
max
) tank (Hs)BTU/hr (kW)57,200 (16.8) 56,400 (16.5)
max
) tank (Hi)BTU/hr (kW)11,600 (3.4) 19,800 (5.8)
min
) tank (Hs)BTU/hr (kW)12,900 (3.8) 21,500 (6.3)
min
3
/hr (m3/h) 56 (1.6)
= 2,500 BTU/ft3 (93.1 MJ/m3)ft
D-S
3
/hr (m3/h) – 22 (0.6)
°F ( °C)
°F ( °C)
136/133 (58/56) 136/133 (58/56)
99/88 (37/31) 99/88 (37/31)
Copyright (optional information)6 720 643 068 (2011/06)
Information about the appliance | 21
Unit NG LPG (propane)
General
Voltage VAC 120 120 Frequency Hz 60 60 Max. power consumption (central heating mode) W 205 205 Max. power consumption (Stand-by) W <6 <6 Noise level dB(A) Maximum supply temperature °F ( °C) 194 (90) 194 (90) Max. permissible operating pressure (PMS) heating psi (bar) 30 (2.07) 30 (2.07) Permissible ambient temperature °F ( °C) 32 - 122 (0 - 50) 32 - 122 (0 - 50) Nominal water capacity (heating) Gal (L) 0.925 (3.5) 0.925 (3.5) Weight (without packaging) lbs. (kg) 103.6 (47) 103.6 (47)
Dimensions, W x H x D
inch
(mm)
33
17-21/64" × 33-15/32" × 13-57/64"
(440 × 850 × 353)
33
Tab. 4 Technical data heating boiler ZBR16-3A...
6 720 643 068 (2011/06)Copyright (optional information)
22 | Information about the appliance
3.12 Technical data heating boiler ZBR28-3A...
Unit NG LPG (propane)
Output
Maximum nominal output (P Maximum nominal output (P Maximum nominal output (P Max. nominal thermal load (Q Max. nominal thermal load (Q Min. nominal output (P Min. nominal output (P Min. nominal output (P
min
min
min
Min. nominal thermal load (Q Min. nominal thermal load (Q Max. nominal thermal load (Q Max. nominal thermal load (Q Min. nominal thermal load (Q Min. nominal thermal load (Q
Gas connection value
Natural Gas – Hs = 1,010 BTU/ft3 (37.3MJ/m3)ft Liquid Propane Gas – H
Permissible inlet gas pressure
NG in. W.C. (mbar) 3.5-10.5" (8.7-26.1) ­LPG (propane) in. W.C. (mbar) – 8-13" (19.9-32.3)
Calculation values for calculating cross-section to EN 13384
Flue gas mass flow at maximum/minimum nominal output gps 12.0/3.2 11.6/4.8 Flue gas temperature 176/140 °F (80/60 °C) at maximum/minimum
nominal heat input Flue gas temperature 104/86 °F (40/30 °C) at maximum/minimum
nominal heat input CO2 at max. nominal output % 9.4 11.0 CO2 at minimum nominal output % 8.6 10.4
Condensate
Max. condensate quantity (tR = 86 °F (30 °C)) gph (l/h) 0.6 (2.3) 0.6 (2.3) pH level, approx. 4.8 4.8
Tab. 5 Technical data heating boiler ZBR28-3A...
) 104/86 °F (40/30 °C) BTU/hr (kW) 93,800 (27.5) 93,800 (27.5)
max
) 122/86 °F (50/30 °C) BTU/hr (kW) 93,100 (27.3) 93,100 (27.3)
max
) 176/140 °F (80/60 °C) BTU/hr (kW) 89,400 (26.2) 89,400 (26.2)
max
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 90,800 (26.6) 90,800 (26.6)
max
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 100,800 (29.5) 98,600 (28.9)
max
) 104/86 °F (40/30 °C) BTU/hr (kW) 23,900 (7.0) 39,900 (11.7) ) 122/86 °F (50/30 °C) BTU/hr (kW) 23,900 (7.0) 39,600 (11.6) ) 176/140 °F (80/60 °C) BTU/hr (kW) 21,800 (6.4) 36,200 (10.6)
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 22,200 (6.5) 36,800 (10.8)
min
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 24,600 (7.2) 40,100 (11.7)
min
) tank (Hi) BTU/hr (kW) 90,800 (26.6) 90,800 (26.6)
max
) tank (Hs)BTU/hr (kW)100,800 (29.5) 98,600 (28.9)
max
) tank (Hi)BTU/hr (kW)22,200 (6.5) 36,800 (10.8)
min
) tank (Hs)BTU/hr (kW)24,600 (7.2) 40,100 (11.7)
min
3
/hr (m3/h) 99 (2.8)
= 2,500 BTU/ft3 (93.1MJ/m3)ft
D-S
3
/hr (m3/h) – 39 (1.1)
°F ( °C)
°F ( °C)
147/133 (64/56) 147/133 (64/56)
117/90 (47/32) 117/90 (47/32)
Copyright (optional information)6 720 643 068 (2011/06)
Information about the appliance | 23
Unit NG LPG (propane)
General
Voltage VAC 120 120 Frequency Hz 60 60 Max. power consumption (central heating mode) W 205 205 Max. power consumption (Stand-by) W <6 <6 Noise level dB(A) Maximum supply temperature °F ( °C) 194 (90) 194 (90) Max. permissible operating pressure (PMS) heating psi (bar) 30 (2.07) 30 (2.07) Permissible ambient temperature °F ( °C) 32 - 122 (0 - 50) 32 - 122 (0 - 50) Nominal water capacity (heating) Gal (L) 0.925 (3.5) 0.925 (3.5) Weight (without packaging) lbs. (kg) 103.6 (47) 103.6 (47)
Dimensions, W x H x D
inch
(mm)
39
17-21/64" × 33-15/32" × 13-57/64"
(440 × 850 × 353)
39
Tab. 5 Technical data heating boiler ZBR28-3A...
6 720 643 068 (2011/06)Copyright (optional information)
24 | Information about the appliance
3.13 Technical data heating boiler ZBR35-3A...
Unit NG LPG (propane)
Output
Maximum nominal output (P Maximum nominal output (P Maximum nominal output (P Max. nominal thermal load (Q Max. nominal thermal load (Q Min. nominal output (P Min. nominal output (P Min. nominal output (P
min
min
min
Min. nominal thermal load (Q Min. nominal thermal load (Q Max. nominal thermal load (Q Max. nominal thermal load (Q Min. nominal thermal load (Q Min. nominal thermal load (Q
Gas connection value
Natural Gas – Hs = 1,010 BTU/ft3 (37.3MJ/m3)ft Liquid Propane Gas – H
Permissible inlet gas pressure
NG in. W.C. (mbar) 3.5-10.5" (8.7-26.1) – LPG (propane) in. W.C. (mbar) – 8-13" (19.9-32.3)
Calculation values for calculating cross-section to EN 13384
Flue gas mass flow at maximum/minimum nominal output gps 15.7/4.5 15.2/5.6 Flue gas temperature 176/140 °F (80/60 °C) at maximum/minimum
nominal heat input Flue gas temperature 104/86 °F (40/30 °C) at maximum/minimum
nominal heat input CO2 at max. nominal output % 9.4 11.0 CO2 at minimum nominal output % 8.6 10.4
Condensate
Max. condensate quantity (tR = 86 °F (30 °C)) gph (l/h) 0.8 (3.1) 0.8 (3.1) pH level, approx. 4.8 4.8
Tab. 6 Technical data heating boiler ZBR35-3A...
) 104/86 °F (40/30 °C) BTU/hr (kW) 122,800 (36.0) 122,800 (36.0)
max
) 122/86 °F (50/30 °C) BTU/hr (kW) 121,800 (35.7) 121,800 (35.7)
max
) 176/140 °F (80/60 °C) BTU/hr (kW) 116,700 (34.2) 116,700 (34.2)
max
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 118,700 (34.8) 118,700 (34.8)
max
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 131,900 (38.6) 129,100 (37.8)
max
) 104/86 °F (40/30 °C) BTU/hr (kW) 35,100 (10.3) 46,100 (13.5) ) 122/86 °F (50/30 °C) BTU/hr (kW) 34,800 (10.2) 45,700 (13.4) ) 176/140 °F (80/60 °C) BTU/hr (kW) 31,700 (9.3) 42,000 (12.3)
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 32,400 (9.5) 42,700 (12.5)
min
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 36,000 (10.5) 46,400 (13.6)
min
) tank (Hi) BTU/hr (kW) 118,700 (34.8) 118,700 (34.8)
max
) tank (Hs)BTU/hr (kW)131,900 (38.6) 129,100 (37.8)
max
) tank (Hi)BTU/hr (kW)32,400 (9.5) 42,700 (12.5)
min
) tank (Hs)BTU/hr (kW)36,000 (10.5) 46,400 (13.6)
min
3
/hr (m3/h) 130 (3.7)
= 2,500 BTU/ft3 (93.1MJ/m3)ft
D-S
3
/hr (m3/h) – 52 (1.5)
°F ( °C)
°F ( °C)
162/135 (72/57) 162/135 (72/57)
127/91 (53/33) 127/91 (53/33)
Copyright (optional information)6 720 643 068 (2011/06)
Information about the appliance | 25
Unit NG LPG (propane)
General
Voltage VAC 120 120 Frequency Hz 60 60 Max. power consumption (central heating mode) W 205 205 Max. power consumption (Stand-by) W <6 <6 Noise level dB(A) Maximum supply temperature °F ( °C) 194 (90) 194 (90) Max. permissible operating pressure (PMS) heating psi (bar) 30 (2.07) 30 (2.07) Permissible ambient temperature °F ( °C) 32 - 122 (0 - 50) 32 - 122 (0 - 50) Nominal water capacity (heating) Gal (L) 0.925 (3.5) 0.925 (3.5) Weight (without packaging) lbs. (kg) 103.6 (47) 103.6 (47)
Dimensions, W x H x D
inch
(mm)
44
17-21/64" × 33-15/32" × 13-57/64"
(440 × 850 × 353)
44
Tab. 6 Technical data heating boiler ZBR35-3A...
6 720 643 068 (2011/06)Copyright (optional information)
26 | Information about the appliance
3.14 Technical data heating boiler ZBR42-3A...
Unit NG LPG (propane)
Output at elevation 0 - 2000 feet (0 - 610 m)
Maximum nominal output (P Maximum nominal output (P Maximum nominal output (P Max. nominal thermal load (Q Max. nominal thermal load (Q Min. nominal output (P Min. nominal output (P Min. nominal output (P
min
min
min
Min. nominal thermal load (Q Min. nominal thermal load (Q Max. nominal thermal load (Q Max. nominal thermal load (Q Min. nominal thermal load (Q Min. nominal thermal load (Q
Output at elevation 2000 - 4500 feet (611 - 1372 m) above sea level
Maximum nominal output (P Maximum nominal output (P Maximum nominal output (P Max. nominal thermal load (Q Max. nominal thermal load (Q Max. nominal thermal load (Q Max. nominal thermal load (Q
Output at elevation 4500 - 7000 feet (1373 - 2134 m) above sea level
Maximum nominal output (P Maximum nominal output (P Maximum nominal output (P Max. nominal thermal load (Q Max. nominal thermal load (Q Max. nominal thermal load (Q Max. nominal thermal load (Q
Gas connection value
Natural Gas – Hs = 1,010 BTU/ft3 (37.3MJ/m3)ft Liquid Propane Gas – H
Permissible inlet gas pressure
NG in. W.C. (mbar) 3.5-10.5" (8.7-26.1) – LPG (propane) in. W.C. (mbar) – 8-13" (19.9-32.3)
Tab. 7 Technical data heating boiler ZBR42-3A...
) 104/86 °F (40/30 °C) BTU/hr (kW) 137,500 (40.3) 137,500 (40.3)
max
) 122/86 °F (50/30 °C) BTU/hr (kW) 137,500 (40.3) 137,500 (40.3)
max
) 176/140 °F (80/60 °C) BTU/hr (kW) 134,400 (39.4) 134,400 (39.4)
max
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 136,500 (40.0) 136,500 (40.0)
max
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 151,600 (44.4) 148,300 (43.5)
max
) 104/86 °F (40/30 °C) BTU/hr (kW) 35,500 (10.4) 46,400 (13.6) ) 122/86 °F (50/30 °C) BTU/hr (kW) 35,100 (10.3) 46,100 (13.5) ) 176/140 °F (80/60 °C) BTU/hr (kW) 31,700 (9.3) 42,000 (12.3)
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 32,400 (9.5) 42,700 (12.5)
min
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 36,000 (10.5) 46,400 (13.6)
min
) tank (Hi) BTU/hr (kW) 136,500 (40.0) 136,500 (40.0)
max
) tank (Hs)BTU/hr (kW)151,600 (44.4) 148,300 (43.5)
max
) tank (Hi)BTU/hr (kW)32,400 (9.5) 42,700 (12.5)
min
) tank (Hs)BTU/hr (kW)36,000 (10.5) 46,400 (13.6)
min
) 104/86 °F (40/30 °C) BTU/hr (kW) 123,750 (36.3) 129,250 (37.9)
max
) 122/86 °F (50/30 °C) BTU/hr (kW) 123,750 (36.3) 129,250 (37.9)
max
) 176/140 °F (80/60 °C) BTU/hr (kW) 120,960 (35.5) 126,336 (37.0)
max
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 122,850 (36.0) 128,310 (37.6)
max
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 136,440 (40.0) 139,402 (40.9)
max
) tank (Hi) BTU/hr (kW) 122,850 (36.0) 128,310 (37.6)
max
) tank (Hs)BTU/hr (kW)136,440 (40.0) 139,402 (40.9)
max
) 104/86 °F (40/30 °C) BTU/hr (kW) 114,125 (33.5) 119,625 (35.1)
max
) 122/86 °F (50/30 °C) BTU/hr (kW) 114,125 (33.5) 119,625 (35.1)
max
) 176/140 °F (80/60 °C) BTU/hr (kW) 111,552 (32.7) 116,928 (34.3)
max
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 113,295 (33.2) 118,755 (34.8)
max
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 125,828 (36.9) 129,021 (37.8)
max
) tank (Hi) BTU/hr (kW) 113,295 (33.2) 118,755 (34.8)
max
) tank (Hs)BTU/hr (kW)125,828 (36.9) 129,021 (37.8)
max
3
/hr (m3/h) 149 (4.2)
= 2,500 BTU/ft3 (93.1MJ/m3)ft
D-S
3
/hr (m3/h) – 59 (1.7)
Copyright (optional information)6 720 643 068 (2011/06)
Information about the appliance | 27
Unit NG LPG (propane)
Calculation values for calculating cross-section to EN 13384
Flue gas mass flow at maximum/minimum nominal output gps 18.0/4.5 17.5/5.6 Flue gas temperature 176/140 °F (80/60 °C) at maximum/minimum
nominal heat input Flue gas temperature 104/86 °F (40/30 °C) at maximum/minimum
nominal heat input CO2 at max. nominal output % 9.4 11.0 CO2 at minimum nominal output % 8.6 10.4
Condensate
Max. condensate quantity (tR = 86 °F (30 °C)) gph (l/h) 0.9 (3.5) 0.9 (3.5) pH level, approx. 4.8 4.8
General
Voltage VAC 120 120 Frequency Hz 60 60 Max. power consumption (central heating mode) W 205 205 Max. power consumption (Stand-by) W <6 <6 Noise level dB(A) Maximum supply temperature °F ( °C) 194 (90) 194 (90) Max. permissible operating pressure (PMS) heating psi (bar) 30 (2.07) 30 (2.07) Permissible ambient temperature °F ( °C) 32 - 122 (0 - 50) 32 - 122 (0 - 50) Nominal water capacity (heating) Gal (L) 0.925 (3.5) 0.925 (3.5) Weight (without packaging) lbs. (kg) 103.6 (47) 103.6 (47)
Dimensions, W x H x D
°F ( °C)
°F ( °C)
inch
(mm)
171/135 (77/57) 171/135 (77/57)
133/91 (56/33) 133/91 (56/33)
45
17-21/64" × 33-15/32" × 13-57/64"
(440 × 850 × 353)
45
Tab. 7 Technical data heating boiler ZBR42-3A...
6 720 643 068 (2011/06)Copyright (optional information)
28 | Information about the appliance
3.15 Technical data combi boiler ZWB28-3A...
Unit NG LPG (propane)
Output at elevation 0 - 2000 feet (0 - 610 m)
Maximum nominal output (P Maximum nominal output (P Maximum nominal output (P Max. nominal thermal load (Q Max. nominal thermal load (Q Min. nominal output (P Min. nominal output (P Min. nominal output (P
min
min
min
Min. nominal thermal load (Q Min. nominal thermal load (Q Max. nominal output (P Max. nominal output (P
max
max
Max. nominal thermal load (Q Max. nominal thermal load (Q Min. nominal thermal load (Q Min. nominal thermal load (Q
Gas connection value
Natural Gas – Hs = 1,010 BTU/ft3 (37.3MJ/m3)ft Liquid Propane Gas – H
Permissible inlet gas pressure
NG in. W.C. (mbar) 3.5-10.5" (8.7-26.1) – LPG (propane) in. W.C. (mbar) – 8-13" (19.9-32.3)
Expansion vessel
Pre-charge pressure psi (bar) 10.9 (0.75) 10.9 (0.75) Total contents Gal (L) 3.17 (12) 3.17 (12)
DHW
Max. DHW flow rate gpm (l/min) 2.64 (10) 2.64 (10) Nominal DHW quantity (at 140 °F (60 °C) outlet temperature) gpm (l/min) 2.03 (7.7) 2.03 (7.7) Outlet temperature °F ( °C) 104 - 140 (40 - 60) 104 - 140 (40 - 60) Max. cold water inlet temperature °F ( °C) 140 (60) 140 (60) Max. approved DHW pressure psi (bar) 150 (10.3) 150 (10.3) Minimum water pressure psi (bar) 4.35 (0.3) 4.35 (0.3) Specific flow rate to EN 625 (D) gpm (l/min) 3.75 (14.2) 3.75 (14.2)
Calculation values for calculating cross-section to EN 13384
Flue gas mass flow at maximum/minimum nominal output gps 12.0/3.2 11.7/4.9 Flue gas temperature 176/140 °F (80/60 °C) at maximum/minimum
nominal heat input Flue gas temperature 104/86 °F (40/30 °C) at maximum/minimum
nominal heat input CO2 at max. nominal output % 9.4 11.0 CO2 at minimum nominal output % 8.6 10.4
Condensate
Max. condensate quantity (tR = 86 °F (30 °C)) gph (l/h) 0.6 (2.3) 0.6 (2.3) pH level, approx. 4.8 4.8
Tab. 8 Technical data combi boiler ZWB28-3A...
) 104/86 °F (40/30 °C) BTU/hr (kW) 93,800 (27.5) 93,800 (27.5)
max
) 122/86 °F (50/30 °C) BTU/hr (kW) 93,100 (27.3) 93,100 (27.3)
max
) 176/140 °F (80/60 °C) BTU/hr (kW) 89,400 (26.2) 89,400 (26.2)
max
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 90,800 (26.6) 90,800 (26.6)
max
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 100,800 (29.5) 98,600 (28.9)
max
) 104/86 °F (40/30 °C) BTU/hr (kW) 23,900 (7.0) 39,900 (11.7) ) 122/86 °F (50/30 °C) BTU/hr (kW) 23,900 (7.0) 39,600 (11.6) ) 176/140 °F (80/60 °C) BTU/hr (kW) 21,800 (6.4) 36,200 (10.6)
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 22,200 (6.5) 36,800 (10.8)
min
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 24,600 (7.2) 40,100 (11.7)
min
) DHW (Hi) 113°F (45°C) BTU/hr (kW) 93,600 (27.4) 93,600 (27.4) ) DHW (Hs) 140°F (60°C) BTU/hr (kW) 91,400 (26.8) 91,400 (26.8)
) DHW (Hi) BTU/hr (kW) 90,800 (26.6) 90,800 (26.6)
max
) DHW (Hs)BTU/hr (kW)100,800 (29.5) 98,600 (28.9)
max
) DHW (Hi)BTU/hr (kW)22,200 (6.5) 36,800 (10.8)
min
) DHW (Hs)BTU/hr (kW)24,600 (7.2) 40,100 (11.7)
min
3
/hr (m3/h) 99 (2.8)
= 2,500 BTU/ft3 (93.1MJ/m3)ft
D-S
3
/hr (m3/h) – 39 (1.1)
°F ( °C)
°F ( °C)
147/133 (64/56) 147/133 (64/56)
117/90 (47/32) 117/90 (47/32)
Copyright (optional information)6 720 643 068 (2011/06)
Information about the appliance | 29
Unit NG LPG (propane)
General
Voltage VAC 120 120 Frequency Hz 60 60 Max. power consumption (central heating mode) W 205 205 Max. power consumption (Stand-by) W <6 <6 Noise level dB(A) Maximum supply temperature °F ( °C) 194 (90) 194 (90) Max. permissible operating pressure (PMS) heating psi (bar) 30 (2.07) 30 (2.07) Permissible ambient temperature °F ( °C) 32 - 122 (0 - 50) 32 - 122 (0 - 50) Nominal water capacity (heating) Gal (L) 0.925 (3.5) 0.925 (3.5) Weight (without packaging) lbs. (kg) 110.2 (50) 110.2 (50)
Dimensions, W x H x D
inch
(mm)
39
17-21/64" × 33-15/32" × 13-57/64"
(440 × 850 × 353)
39
Tab. 8 Technical data combi boiler ZWB28-3A...
6 720 643 068 (2011/06)Copyright (optional information)
30 | Information about the appliance
3.16 Technical data combi boiler ZWB42-3A...
Unit NG LPG (propane)
Output at elevation 0 - 2000 feet (0 - 610 m)
Maximum nominal output (P Maximum nominal output (P Maximum nominal output (P Max. nominal thermal load (Q Max. nominal thermal load (Q Min. nominal output (P Min. nominal output (P Min. nominal output (P
min
min
min
Min. nominal thermal load (Q Min. nominal thermal load (Q Max. nominal output (P Max. nominal output (P
max
max
Max. nominal thermal load (Q Max. nominal thermal load (Q Min. nominal thermal load (Q Min. nominal thermal load (Q
Output at elevation 2000 - 4500 feet (611 - 1372 m) above sea level
Maximum nominal output (P Maximum nominal output (P Maximum nominal output (P Max. nominal thermal load (Q Max. nominal thermal load (Q Max. nominal output (P Max. nominal output (P
max
max
Max. nominal thermal load (Q Max. nominal thermal load (Q
Output at elevation 4500 - 7000 feet (1373 - 2134 m) above sea level
Maximum nominal output (P Maximum nominal output (P Maximum nominal output (P Max. nominal thermal load (Q Max. nominal thermal load (Q Max. nominal output (P Max. nominal output (P
max
max
Max. nominal thermal load (Q Max. nominal thermal load (Q
Gas connection value
Natural Gas – Hs = 1,010 BTU/ft3 (37.3MJ/m3)ft Liquid Propane Gas – H
Permissible inlet gas pressure
NG in. W.C. (mbar) 3.5-10.5" (8.7-26.1) – LPG (propane) in. W.C. (mbar) – 8-13" (19.9-32.3)
Expansion vessel
Pre-charge pressure psi (bar) 10.9 (0.75) 10.9 (0.75) Total contents Gal (L) 3.17 (12) 3.17 (12)
DHW
Max. DHW flow rate gpm (l/min) 3.963 (15) 3.963 (15) Nominal DHW quantity (at 140 °F (60 °C) outlet temperature) gpm (l/min) 3.61 (11.4) 3.61 (11.4) Outlet temperature °F ( °C) 104 - 140 (40 - 60) 104 - 140 (40 - 60) Max. cold water inlet temperature °F ( °C) 140 (60) 140 (60) Max. approved DHW pressure psi (bar) 150 (10.3) 150 (10.3) Minimum water pressure psi (bar) 4.35 (0.3) 4.35 (0.3)
Tab. 9 Technical data combi boiler ZWB42-3A...
) 104/86 °F (40/30 °C) BTU/hr (kW) 137,500 (40.3) 137,500 (40.3)
max
) 122/86 °F (50/30 °C) BTU/hr (kW) 137,500 (40.3) 137,500 (40.3)
max
) 176/140 °F (80/60 °C) BTU/hr (kW) 134,400 (39.4) 134,400 (39.4)
max
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 136,500 (40.0) 136,500 (40.0)
max
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 151,600 (44.4) 148,300 (43.5)
max
) 104/86 °F (40/30 °C) BTU/hr (kW) 35,500 (10.4) 46,400 (13.6) ) 122/86 °F (50/30 °C) BTU/hr (kW) 35,100 (10.3) 46,100 (13.5) ) 176/140 °F (80/60 °C) BTU/hr (kW) 31,700 (9.3) 42,000 (12.3)
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 32,400 (9.5) 42,700 (12.5)
min
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 36,000 (10.5) 46,400 (13.6)
min
) DHW (Hi) 113°F (45°C) BTU/hr (kW) 137,500 (40.3) 137,500 (40.3) ) DHW (Hs) 140°F (60°C) BTU/hr (kW) 135,800 (39.8) 135,800 (39.8)
) DHW (Hi) BTU/hr (kW) 136,500 (40.0) 136,500 (40.0)
max
) DHW (Hs)BTU/hr (kW)151,600 (44.4) 148,300 (43.5)
max
) DHW (Hi)BTU/hr (kW)32,400 (9.5) 42,700 (12.5)
min
) DHW (Hs)BTU/hr (kW)36,000 (10.5) 46,400 (13.6)
min
) 104/86 °F (40/30 °C) BTU/hr (kW) 123,750 (36.3) 129,250 (37.9)
max
) 122/86 °F (50/30 °C) BTU/hr (kW) 123,750 (36.3) 129,250 (37.9)
max
) 176/140 °F (80/60 °C) BTU/hr (kW) 120,960 (35.5) 126,336 (37.0)
max
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 122,850 (36.0) 128,310 (37.6)
max
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 136,440 (40.0) 139,402 (40.9)
max
) DHW (Hi) 113°F (45°C) BTU/hr (kW) 123,750 (36.3) 129,250 (37.9) ) DHW (Hs) 140°F (60°C) BTU/hr (kW) 122,220 (35.8) 127,652 (37.4)
) DHW (Hi) BTU/hr (kW) 122,850 (36.0) 128,310 (37.6)
max
) DHW (Hs)BTU/hr (kW)136,440 (40.0) 139,402 (40.9)
max
) 104/86 °F (40/30 °C) BTU/hr (kW) 114,125 (33.5) 119,625 (35.1)
max
) 122/86 °F (50/30 °C) BTU/hr (kW) 114,125 (33.5) 119,625 (35.1)
max
) 176/140 °F (80/60 °C) BTU/hr (kW) 111,552 (32.7) 116,928 (34.3)
max
) heating (Hi) 180/79 °F (82/26 °C) BTU/hr (kW) 113,295 (33.2) 118,755 (34.8)
max
) heating (Hs) 180/79 °F (82/26 °C) BTU/hr (kW) 125,828 (36.9) 129,021 (37.8)
max
) DHW (Hi) 113°F (45°C) BTU/hr (kW) 114,125 (33.5) 119,625 (35.1) ) DHW (Hs) 140°F (60°C) BTU/hr (kW) 112,714 (33.0) 118,146 (34.6)
) DHW (Hi) BTU/hr (kW) 113,295 (33.2) 118,755 (34.8)
max
) DHW (Hs)BTU/hr (kW)125,828 (36.9) 129,021 (37.8)
max
3
/hr (m3/h) 149 (4.2)
= 2,500 BTU/ft3 (93.1MJ/m3)ft
D-S
3
/hr (m3/h) – 59 (1.7)
Copyright (optional information)6 720 643 068 (2011/06)
Loading...
+ 90 hidden pages