Improper installation, set-up, modification, operation
or maintenance of the heating system can cause
personal injury and property damage.
Follow these instructions precisely.
If you require assistance or further information, contact
a trained and certified installer or the gas supply
company.
WARNING:
The operating instructions are part of the technical
documents that must be handed over to the owner or
operator of the heating system.
Explain to the owner or operator how to use the heating
system using the operating instructions. Make sure that
they are familiar with all required information for the
safe and proper operation of the heating system.
NOTE:
In Massachusetts, this appliance must be installed by
a licensed plumber or gas fitter.
These instructions are available in English and French.
Please keep these instructions for future reference.
Warnings are indicated in the text by a
warning triangle and a gray background.
In case of danger from electric shock, the
exclamation point on the warning triangle is
replaced with a flash.
Signal words at the beginning of a warning are used to
indicate the type and seriousness of the ensuing risk if
measures for minimizing damage are not taken.
• NOTE indicates that damage to property may occur.
• CAUTION indicates possible minor to medium personal
injury.
• WARNING indicates possible severe personal injury.
• DANGER indicates a potential for loss of life.
Important Information
Important information neither indicating
personal injury nor damage to property are
marked with this symbol. They are separated
by lines above and below the text.
1.2Safety instructions
Safety first. Never risk your health or your life. Your own
safety must always take the highest priority.
Use approved personal protective devices and common
sense safety measures.
If you smell gas
B Turn off the gas cock (Æ page 58).
B Open windows and doors.
B Do not operate any electrical switches.
B Extinguish all open flames.
B From outside the building, call gas utility company and
a trained and certified heating contractor.
If you smell flue gas
B Switch OFF the appliance (Æ page 59).
B Open windows and doors.
B Inform a trained and certified heating contractor.
Danger of electric shock when the control panel is open
B Always disconnect the appliance from the mains power
before performing any work. Disconnect the emergency
shutoff switch or disengage the heating system circuit
breaker.
B Take measures to prevent accidental reconnection.
Additional symbols
SymbolExplanation
B
Æ
Cross-reference to other points in this
•
–
Tab. 1 Additional Symbols
Sequence of steps
document or to other documents
Listing/list entry
Listing/list entry (2nd level)
For appliances operating on room air: Danger of flue gas
poisoning if supply of combustion air is insufficient
B Safeguard supply of combustion air.
B The ventilation and exhaust openings must never be
plugged. The cross section of the ventilation and
exhaust openings must comply with the design
specifications at all times.
B Safeguard sufficient supply of combustion air also for
appliances installed at a later date, e.g. kitchen exhaust
fans, clothes dryers, and air conditioning units with vent
to the outside.
B Never install a barometric nor a thermally controlled
vent damper with this boiler.
B If the ventilation and exhaust openings do not comply
with the specifications, the heating system must never
be operated.
B Notify operator and building owner of the defect in
B Only employ a trained and certified contractor to carry
out work on the gas train.
Installation and conversion
Only have the appliance installed or modified by a trained
and certified heating contractor.
Always follow state of the art construction techniques for
installation and maintenance, and observe all applicable
codes and regulations.
Never modify any parts that carry flue gas.
Only trained and certified contractors are permitted to
carry out electrical work. Follow applicable code.
The DHW tank may only be used for heating domestic hot
water.
Never close the outlet of safety valves. Water may be
expelled from any safety valve during heat-up.
Inspection and maintenance
The operator is responsible for the safety and
environmental compliance of the heating system.
It is recommended to arrange a maintenance and
inspection contract with a trained and certified
contractor, covering an annual inspection and demanddependent maintenance. This guarantees high efficiency
and environmentally sound combustion.
Do not attempt to repair parts that have built in safety
features. Always replace the part.
Only use original Bosch spare parts. Bosch does not
accept responsibility for damage caused by third party
spare parts.
Combustion air/room air
B To prevent corrosion, keep the supply of combustion/
room air free of corrosive substances (e.g. halogenated
hydrocarbons that contain chlorine or fluorine
compounds).
B Avoid drawing in combustion air from outdoors that is
excessively loaded with dust or airborne particles.
Install adequate air filters under the following
circumstances:
– Air supply is contaminated with dust from dirt roads
and paths.
– Air supply is contaminated with dust from production
and processing facilities, e.g. quarries, mines, etc.
– Airborne seeds from thistles and similar plants.
– Halogen-hydrocarbon compounds, e.g. from paint
booths or hair salons.
Risk of system damage due to unsuitable fill water
Risk of system damage due to corrosion or scale formation
as the result of using fill and top-up water that does not
conform to the system-specific requirements.
Risk of system damage from freezing
The heating system can freeze up and burst in cold
weather if it is shut down or locked out.
B Leave the heating system turned on as much as
possible.
B Protect a disabled heating system from freezing by
draining the boiler and water pipes at the lowest point.
Perform maintenance annually. Check the complete
heating system for defects and malfunction.
Mitigate defects immediately to avoid larger scale system
damage.
To prevent damage to the appliance or the system from
descaling agents, remove parts to be descaled during the
process.
Explosive and easily combustible materials
Never use or store easily combustible materials (paper,
thinners, paints, etc.) near the appliance.
2.1ZBR - Boiler for space heating and loading of indirect fired DHW tanks
Contents of package 1:
1
2
3
4
1Gas condensing boiler
2Set of documents for appliance
3Mounting bracket with mounting kit
4Gas conversion kit
5Adapter for connection of a LWCO
6 720 641 933-22.1O
Fig. 1Scope of delivery heating boiler ZBR..-3A
10
11
12
5
Contents of package 2:
6Rail with connection box
6
7
8
7Flue adapter
8DHW tank temperature sensor (NTC)
9Hydraulics connection plate with mounting kit
10External supply temperature sensor (NTC)
11Outdoor reset control FW 200 with mounting kit and outdoor
temperature sensor
12Set of documents for outdoor reset control FW 200
2.2ZWB - Combi boiler for space heating and DHW generation
Contents of package 1:
1
2
1Gas condensing boiler
2Set of documents for appliance
3Mounting bracket with mounting kit
4Gas conversion kit
5Adapter for connection of a LWCO
3
4
Scope of delivery | 7
Fig. 2Scope of delivery combi boiler ZWB..-3A
5
6
7
8
9
10
11
6 720 641 933-04.1O
Contents of package 2:
6Rail with connection box
7Flue adapter
8Hydraulics connection plate with mounting kit
9External supply temperature sensor (NTC)
10Outdoor reset control FW 200 with mounting kit and outdoor
temperature sensor
11Set of documents for outdoor reset control FW 200
ZBR appliances are boilers for central heating and loading
of an indirect fired DHW tank.
ZWB appliances are combi boilers for central heating and
on demand DHW heating.
The appliances comply with South Coast Air Quality
Management District (SCAQMD) 2012 requirements:
(Type-1) 14 Ng/J NOx (and/or 20 ppm at 3% O2).
3.2Overview of boiler types
Table 2 describes the meaning of the model number:
ZBR16-3
ZBR28-3
ZBR35-3
A23
A23
A23
3.1Proper use
The appliance may only be installed in closed loop hot
water central heating systems.
Any other purpose is considered improper use. Any
resulting damage is excluded from the manufacturer's
warranty.
The commercial and industrial use of the appliance for
generating process heat is not permitted.
ZBR42-3
ZWB28-3
ZWB42-3
A23
A23
A23
Tab. 2 Appliance types
ZCentral heating appliance
WDHW heating
BCondensing technology
RConstant temperature control
16Output up to 54,600 BTU/hr (16 kW)
28Output and DHW output up to 95,500 BTU/hr (28 kW)
35Output up to 119,400 BTU/hr (35 kW)
42Output and DHW output up to 143,300 BTU/hr (42 kW)
-3Version
AFan-supported appliance
23Natural gas (NG)
Here you will find a list of typical accessories
for this appliance. Refer to the Bosch Product
Catalog for a complete overview of all
available accessories.
• FB 100 room control
• Modules for system expansions:
– ISM2 for solar systems (DHW heating, space heating
support, pool heating)
– IPM2 for one or two heating zones with pump control
1Ignition transformer
2Boiler high limit dial
3120 VAC connection
4DHW tank primary pump or 3-way valve
5External heating pump for unmixed heating circuit (secondary circuit) 2) or DHW recirculation pump
6Fuse T 6.3 A (120 VAC)
7DHW thermostat
8External safety high limit or low water cut off (LWCO)
9BUS connection, e.g. heating control
10Room thermostat – dry contact
11Outdoor temperature sensor
12Code plug
13Diagnostic interface
14ON/OFF switch
15Transformer
16Gas valve
17Fan
18Flue gas temperature limiter
19Supply temperature sensor
20Flame rod electrode
21Ignition electrode
22Boiler block temperature limiter
23DHW tank temperature sensor (NTC)
24Boiler circulator
25Additional supply temperature limiter
26External system supply temperature sensor
1Ignition transformer
2Boiler high limit dial
3120 VAC connection
4External heating pump for unmixed heating circuit (secondary circuit)
5Fuse T 6.3 A (120 VAC)
6DHW thermostat
7External safety high limit or low water cut off (LWCO)
8BUS connection, e.g. heating control
9Room thermostat – dry contact
10Outdoor temperature sensor
11Code plug
12Diagnostic interface
13ON/OFF switch
15Transformer
14Gas valve
16Fan
17Flue gas temperature limiter
18Supply temperature sensor
19Flame rod electrode
20Ignition electrode
21Boiler block temperature limiter
22DHW temperature sensor
23Boiler circulator
243-way valve (Space heating/DHW heating)
25Flow meter (turbine)
26Additional supply temperature limiter
27External system supply temperature sensor
The condensate volume and ingredients may change with
regionally and seasonally varying gas quality and air
quality. Typically the following ingredients and
concentrations can be expected:
Observe all rules, regulations, standards and
guidelines applicable to the installation and
operation of this appliance in your country.
In the Commonwealth of Massachusetts,
this appliance must be installed by a
licensed plumber and gas fitter. Valves
external to the boiler must be fitted with
T-handles and condensate piping must be
installed in accordance with the State
Plumbing Code.
4.1Compliance with standards and
regulations
The installation must conform to the requirements of the
authority having jurisdiction or, in the absence of such
requirements, to the latest edition of the National Fuel Gas
Code, ANSI Z223.1./NFPA 54. In Canada, installation must
be in accordance with the requirements of CAN/CSA
B149.1, Natural Gas and Propane Installation Code.
This wall mounted condensing gas boiler complies in its
design and mode of operation with the American National
Standard ANSI Z21.13/CSA4.9, latest edition for Gas Fired
Low Pressure Steam and Hot Water Boilers.
4.2Operating limits of the boiler
The heat exchanger has been designed and certified in
accordance with the ASME Boiler and Pressure Vessel
Code, Section IV.
Maximum boiler temperature194 °F (90 °C)
Maximum operating pressure30 psi (2.07 bar)
Tab. 11 Operating limits
The hot water distribution system must comply with all
applicable codes and regulations. When replacing an
existing boiler, it is important to check the condition of the
entire hot water distribution system to ensure safe
operation. Common practice calls for inspecting an
existing system in its entirety and bringing it up to code.
All pipework should be properly cleaned and flushed.
Other confirmed approvals and certifications are indicated
by labels on the boiler.
Where required by the authority having jurisdiction, the
installation must conform to the Standard for Controls and
Safety Devices for Automatically Fired Boilers, ANSI/ASME
CSD-1.
Install CO detectors per local regulations. Boiler requires
yearly maintenance (Æ chapter 14, page 81).
4.3Additional regulations for installation in
Massachusetts
(a) For all side wall horizontally vented gas fueled
equipment installed in every dwelling, building or
structure used in whole or in part for residential purposes,
including those owned or operated by the Commonwealth
and where the side wall exhaust vent termination is less
than seven (7) feet [2150 mm] above finished grade in the
area of the venting, including but not limited to decks and
porches, the following requirements shall be satisfied:
1. INSTALLATION OF CARBON MONOXIDE DETECTORS.
At the time of installation of the side wall horizontal vented gas fueled equipment, the installing plumber or gasfitter shall observe that a hard wired carbon monoxide
detector with an alarm and battery back-up is installed
on the floor level where the gas equipment is to be
installed. In addition, the installing plumber or gasfitter
shall observe that a battery operated or hard wired carbon monoxide detector with an alarm is installed on
each additional level of the dwelling, building or structure served by the side wall horizontal vented gas fueled
equipment. It shall be the responsibility of the property
owner to secure the services of qualified licensed professionals for the installation of hard wired carbon monoxide detectors.
– In the event that the side wall horizontally vented gas
fueled equipment is installed in a crawl space or an
attic, the hard wired carbon monoxide detector with
alarm and battery back-up may be installed on the
next adjacent floor level.
– In the event that the requirements of this subdivision
can not be met at the time of completion of
installation, the owner shall have a period of thirty
(30) days to comply with the above requirements;
provided, however, that during said thirty (30) day
period, a battery operated carbon monoxide detector
with an alarm shall be installed.
2. APPROVED CARBON MONOXIDE DETECTORS. Each
carbon monoxide detector as required in accordance
with the above provisions shall comply with NPA 720
and be ANSI/UL 2034 listed and IAS certified.
3. SIGNAGE. A metal or plastic identification plate shall be
permanently mounted to the exterior of the building at
a minimum height of eight (8) feet above grade directly
in line with the exhaust vent terminal for the horizontally vented gas fueled heating appliance or equipment.
The sign shall read, in print size no less than one-half
(½) inch in size, “GAS VENT DIRECTLY BELOW. KEEP
CLEAR OF ALL OBSTRUCTIONS”.
4. INSPECTION. The state or local gas inspector of the side
wall horizontally vented gas fueled equipment shall not
approve the installation unless, upon inspections, the
inspector observes carbon monoxide detectors and signage installed in accordance with the provisions of
248 CRM 5.08(2)(a) 1 through 4.
(b) EXEMPTIONS: The following equipment is exempt from
248 CRM 5.08(2)(a) 1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment
Not Required To Be Vented” in the most current edition
of NFPA 54 as adopted by the board; and
• Product Approved side wall horizontally vented gas
fueled equipment installed in a room or structure
separate from the dwelling, building or structure used
in whole or in part for residential purposes.
(c) MANUFACTURERS REQUIREMENTS - GAS EQUIPMENT
VENTING SYSTEM REQUIRED. When the manufacturer of
Product Approved side wall horizontally mounted gas
equipment provides a venting system design or venting
system components with the equipment, the instructions
provided by the manufacturer for the installation of the
equipment and venting shall include:
• Detailed instructions for the installation of the venting
system or the venting system components; and
• A complete parts list for the venting system design or
venting system.
ANUFACTURERS REQUIREMENTS - GAS EQUIPMENT
(d) M
VENTING SYSTEM
manufacturer of Product Approved side wall horizontally
vented gas fueled equipment does not provide the parts
for the venting of flue gases, but identifies special venting
systems, the following requirements shall be satisfied by
the manufacturer:
1. The referenced special venting systems shall be
included with the appliance or equipment installation
instructions; and
2. The special venting systems shall be Product Approved
by the Board, and the instructions for that system shall
include a parts list and detailed installation
instructions.
(e) A copy of all i nstructions for all Product Approved side
wall horizontally vented gas fueled equipment, all venting
instructions, all parts lists for venting instructions, and/or
venting design instructions shall remain with the appliance
or equipment at the completion of the installation.
Installation, power connection, connection on
the gas and flue gas side and commissioning
must only be carried out by a contractor
certified for such work by the state or local
jurisdiction or the local gas or power utility.
5.1Notes on installation and operation
When installing and operating the heating system observe
the following:
• The elevation of the installation location above sea level
must be taken into account (Æ Chapter 11.2).
• Follow all local building regulations regarding the
installation conditions on site.
• The local building regulations regarding air supply and
venting systems and the chimney flue connection.
• Electrical code requirements for connection to the
electrical power supply.
• The technical regulations of the gas company regarding
the connection of the gas burner to the local gas main.
• The regulations and standards relating to the DHW
heating system.
5.1.1Notes on installation and operation
Fill and make-up water for the heating system
Unsuitable fill and make-up water can result in the heating
system scaling up or failing prematurely.
Water hardness in grains
per gallon (Ca(HCO
concentration in ppm)
soft: ≤9 grains
(
≤
150 ppm)
medium: 9 - 14.6 grains
(150 - 250 ppm)
hard: ≥14.6 (≥250 ppm)Required
Tab. 12 Water preparation for filling and maintaining the
heating system (water hardness)
pH-valueWater preparation
7-8.5Not needed
<7 or >8.5Required
Tab. 13 Water preparation for filling and maintaining the
heating system (pH-value)
Recirculation pump/DHW recirculation lines
Total length DHW/
recirculation line
≤
33 ft (10 m)0.66 gpm (2.5 l/min)
33 - 66 ft (10 - 20 m)0.92 gpm (3.5 l/min)
3)2
Water preparation
Not needed
Recommended
Flow rate
66 - 98 ft (20 - 30 m)1.32 gpm (5 l/min)
Tab. 14 Recommended flow rates
Use service function 6.d, to determine the
current flow rate (Æ page 71).
Electrical connection of the DHW recirculation pump
(Æ page 55).
Connect the DHW recirculation line with the cold water
inlet as close as possible to the Hydraulics connection
plate.
5.2Comparing the size of the integrated
expansion vessel
The following diagrams allow verifying that the integrated
expansion vessel has sufficient capacity for the intended
application, or if an additional expansion vessel is needed
(not for radiant floor heating).
The following standard conditions were used:
• Precharge volume 20% of the rated volume in the
expansion vessel
• Differential to the safety valve of 7.25 psi (0.5 bar)
• Precharge pressure of the expansion vessel equal to the
static system height above the boiler
• Maximum operating pressure: 30 psi (2.07 bar)
200
180
I
160
/°F
140
V
t
120
100
80
0204080100
A
III
II
60
VA/gal
B
120
6720641933-13.1O
90
80
I
B
70
/°C
60
V
t
50
40
30
Fig. 10 Operating capacity of the expansion vessel in °C
5.3ZBR..-3A appliances (heating boilers):
Selecting an expansion vessel
External expansion vessel
B Determine size of the expansion vessel.
5.4Selecting the installation location
Installation location requirements
Observe the current national and local codes and
regulations.
B Observe country-specific requirements.
B Observe installation instructions of the venting system
accessories and their clearances.
Combustion air
To avoid corrosion, keep the supply of combustion air free
of corrosive substances; contained in solvents, paints,
adhesives, propellants and domestic cleaning agents.
Industrial sources
Chemical cleaningTrichloroethylene, tetrachloroethyl-
The max. surface temperature of this appliance is below
185 °F (85 °C). According to ANSI/Z223.1/NFPA43
(National fuel gas code) and CAN/DAS B 149.1 (Natural
Gas and Propane installation code), the appliance is
approved for zero clearance to combustibles. For servicing
a clearance of 4" (102 mm) is recommended.
B Secure the installation template (supplied with the
technical documentation) to the wall; observe the
minimum side clearances of 4 inches (102 mm)
(Æ page 11).
B Drill holes for the appliance and for the hydraulics
connection plate in accordance with the mounting
template.
250
200
60/100
150
111
100
87
80/125
3°
3°
Installation | 39
B Secure the hydraulics connection plate and the
mounting bracket with the mounting kits supplied.
Fig. 12 Mounting template
NOTICE: For walls with insufficient load
capacity, the appliance and the hydraulics
connection plate must be mounted on a sheet
of plywood or similar reinforcement.
6 720 641 933-30.1O
Fig. 13 Mounting of the hydraulics connection plate and the
The boiler is equipped with several sensors that prevent
firing or running the boiler in case of low water pressure or
low water levels. Nevertheless code may require the
installation of a separate low water cut off (LWCO).
The boiler is equipped with a dedicated port for
installation of a LWCO on the supply pipe inside the boiler
cabinet. This location represents the minimum water level
for safe operation of the boiler.
The LWCO device must be specified for an ambient
temperature of 176 °F (80 °C) and a water temperature of
250 °F (121 °C). It needs a dry contact.
The following LWCO is approved with the boiler:
• Hydrolevel Safgard 1100
The device is available at most Bosch wholesalers.
It requires an external 24VAC 20VA transformer provided
on site.
B Screw the LWCO as far as possible into LWCO adapter
located in the boiler accessory kit. Follow the
Hydrolevel Safgard 1100 instructions.
6 720 641 933-64.1O
Fig. 20 Installing a LWCO device - LWCO adapter
B Push the adapter with the LWCO onto the pipe (step 1)
and secure with the clip (step 2).
If other LWCO devices are to be used, they
must be installed external to the boiler.
The Hydrolevel Safgard 1100 is installed in the supply pipe
to the left of the heat exchanger.
B Disconnect the boiler from power by shutting off the
emergency shutoff switch or disengaging the heating
system circuit breaker.
B Drain the boiler.
B Remove the safety clip from the dummy plug in the
supply pipe (step 1).
B Pull off the dummy plug (step 2) and place with the
boiler documentation.
B Ensure the O-ring remains in place on the pipe.
B Lubricate the O-ring.
2
1
1
2
6 720 641 933-65.1O
Fig. 21 Installing a LWCO device – securing with a clip
B Connect the wires of the LWCO (Æ chapter 6.4,
page 57).
The LWCO is positioned upright for technical
reasons. Tests have shown that all air will
bleed from the pipe during commissioning
and full functionality is established.
Fig. 19 Installing a LWCO device - removing dummy plug
6 720 641 933-64.1O
If fault d3 is displayed when commissioning
the boiler, purge the boiler properly and check
the boiler water pressure.
5.8.1Installation of the exhaust and air intake system
NOTICE:
B Vent connectors serving appliances vented
by natural draft shall not be connected to
any portion of mechanical draft systems
operating under positive pressure.
NOTICE: Burner damage!
B Avoid drawing in combustion air
excessively loaded with dust or airborne
particles.
DANGER:
B Ensure that the flue pipes and seals are not
damaged.
B Use only sealing compounds (primer and
glue) approved with the vent material.
B Never install a barometric nor a thermally
controlled vent damper with this boiler.
B Connect only one boiler to each flue system
or chimney flue.
B Do not route the flue system piping through
or inside another duct that is used for
exhausting air or other flue gases.
B The condensate trap must be primed at all
times. Failure to do so may allow
combustion gases to escape into boiler
room.
Consult local and state codes pertaining to
special building code and fire department
requirements. Adhere to national code
requirements.
Observe the listed maximum lengths of vent
system, which are boiler model dependent
(Æ chapter 5.8.3).
Optional vent kits are:
• Concentric termination for horizontal/vertical
(Part-#196006)
• Stainless steel parallel wall terminal
(Part-#46546901)
Direct vent installations (sealed combustion)
For direct vent applications all applicable items below
must be met.
X
2
1
X
XX
6 720 641 933-19.1O
Fig. 25 Vent and combustion air pipe position of a sealed
combustion system
1Intake
2Exhaust
XAt least 1 foot (305 mm)
The termination shall terminate at least 1 foot (305 mm)
below, 1 foot (305 mm) horizontally from or 1 foot
(305 mm) above any door, window or gravity air inlet into
any building (Æ fig. 26 [2], [X
If multiple boilers are installed in a row, allow at least
1 foot (305 mm) clearance between the vent termination
of one and the combustion air intake of the other.
Vent termination must be at least 1 foot (305 mm) above
grade, anticipated snow line or roof surface (Canada
1-1/2 feet (457 mm) minimum) (Æ fig. 26 [Y
Vent termination must be at least 7 feet (2135 mm) above
a public walkway (Æ fig. 26 [X
condensate spilling from the termination does not create
a hazard or a nuisance.
Vent termination must be 3 feet (915 mm) above any
forced air intake within 10 feet (3050 mm) (Æ fig. 26 [1],
], page 46).
[Y
B
Do not extend exposed vent pipe outside the building
beyond recommended distance. Condensate could freeze
and block vent pipe.
Vent should terminate at least 3 feet (915 mm) away from
adjacent walls, inside corners and 5 feet (1 525 mm) below
roof overhang (Æ fig. 26 [X
], [X4], page 46).
2
It is not recommended to terminate vent above any door
The exhaust pipe must be properly
supported and pitched a minimum of ¼ inch
(6.35 mm) per foot back to the boiler. This
allows the condensate to properly drain.
or window, condensate can freeze causing ice formations.
Do not use chimney as a raceway if another boiler or
fireplace is vented into or through chimney.
All non-steel vent pipes must be glued, except for the flue
gas adapter-pipe connection.
All non-steel combustion air and vent pipe materials and
NOTICE: Damage of 2 inch PVC pipes.
B For ZBR42-3A and ZWB42-3A use 2 inch
CPVC-pipes or 3 inch pipes.
fittings must comply with the following and must be UL
approved venting material:
ZBR16-3A
ZBR28-3A
ZBR35-3A
MaterialItemUnited statesCanada
PVC schedule 40, 80
PVC-DWVANSI/ASTM D2665XXXX
CPVC schedule 40, 80ANSI/ASTM F441XXXXXX
PVC schedule 40, 80
PVC-DWVANSI/ASTM D2665XXXXXX
CPVC schedule 40, 80ANSI/ASTM F441XXXXXX
2" (50 mm) Vent
or air pipe and
fitting
3" (76 mm) Vent
or air pipe and
fitting
ANSI/ASTM D1785
ANSI/ASTM D1785XXXXXX
BH Gas venting
systems,
ULC S636
1)
XXXX
ZBR42-3A
ZWB28-3A
ZWB42-3A
PVC
CPVCANSI/ASTM F493XXXXXX
Pipe cement/
primer
ANSI/ASTM D2564XXXXXX
Tab. 18 Materials for pipe
1) Components of the certified vent systems must not be interchanged with other vent systems or unlisted pipe fittings. Plastic
components, and specified primers and glues of the certified vent system must be from a single system manufacturer and not
intermixed with other system manufacturer's vent system parts.
Roof terminalsMaterialSupplierPart number
Ø 3" / Ø 6" (Ø 76/150 mm)concentric PVCIPEX196016
Tab. 19 Roof terminals
Wall terminalsFlue System / MaterialsSupplierPart number
the primary circuit of the boiler. Use CPVC
or stainless steel only!
3
4
X
1
X
X
NOTICE:
B Vent terminations must keep the following
minimum clearances from electric meters,
gas meters, regulators and relief
equipment: 4 feet (1220 mm) [Canada
6 feet (1830 mm)] horizontally and in no
case above and below, unless a horizontal
distance of 4 feet (1220 mm) [Canada
6 feet (1830 mm)] is maintained.
3
1
X
2
3
X
5
X
3
3
X
3
Fig. 26 Vent and combustion air pipe position
Direct vent (sealed combustion):
1Forced Air Inlet
2Gravity Air Inlet
3Exhaust terminal
1 foot (305 mm)
X
1
3 feet (915 mm)
X
2
X
1 foot (305 mm)
3
5 feet (1525 mm)
X
4
X
7 feet (2135 mm) above public walkway
5
At least 1 feet (305 mm) above grade and snow line
Y
A
Exhaust terminal must be at least 3 feet (915 mm) above
Y
B
forced air inlet within 10 feet (3050 mm)
Y
X
X
B
3
Y
2
1
X
1
2
A
Fan assisted appliance (non-sealed combustion):
1Forced Air Inlet
2Gravity Air Inlet
3Exhaust terminal
X
1 foot (305 mm)
1
3 feet (915 mm)
X
2
X
4 feet (1220 mm)
3
5 feet (1525 mm)
X
4
X
7 feet (2135 mm) above public walkway
5
At least 1 foot (305 mm) above grade and snow line
Y
A
Exhaust terminal must be at least 3 feet (915 mm) above
Fig. 31 Vertical venting system (sealed combustion)
X
Y
2
1
6 720 641 933-07.1O
X
Y
1
2
6 720 641 933-10.1O
Fig. 32 Vertical venting system (room air only)Fig. 33 Vertical venting system (sealed combustion)
Key to Fig. 31, Fig. 32 and Fig. 33:
1Intake
2Exhaust
3Concentric termination
XGreater than 12 inches (305 mm)
Y12 inches (305 mm) above maximum snow level or at least 24 inches (610 mm) whichever is greater
For all installation situations and for all appliances the
maximum vent and combustion air pipe length is 100 feet
each, with no more than 8 elbows each.
2" (50 mm) Vent and combustion air pipe
The maximum combined vent and
combustion air pipe
length (Æ tab. 21, 22 and 23) depend on the installation
situation, the appliance type and the number of elbows
used.
Installations Æ Fig. 27, 28, 29, 31, 32 and 34
Separate terminations
(120 VAC), disconnect the boiler from the
grid by shutting off the emergency shutoff
switch or disengaging the heating system
circuit breaker. Take measures to prevent
accidental reconnection.
B It is not sufficient to simply shut off the
controls.
B Observe all applicable electrical codes and
regulations.
Electrical components must be installed by a trained and
certified electrician and the installation must meet the
National Electric Code as well as all applicable local codes
and regulations.
The boiler must be properly electrically grounded in
accordance with the requirements of the authority having
jurisdiction or, in the absence of such requirements with
the National Electrical Code, ANSI/NFPA 70 and/or the
Canadian Electrical Code Part I, CSA C221.1, Electrical
Code.
Provide a dedicated circuit breaker for the
boiler and heating system rated at least 15A.
All line voltage wiring must use at least
AWG14 size cables.
6.2Low voltage electrical connections in
the Heatronic boiler control
6.2.1Open the Heatronic boiler control
NOTICE: Small pieces of wire can cause
shorts and damage the electronics.
B Always strip cables away from electronics.
B Unhook the clip (step 1) and fold the Heatronic down
(step 2).
1
2
Fig. 35 Fold the Heatronic down
B Remove screws (step 1), unhook cable and remove
cover (step 2).
6 720 641 933-72.1O
All appliance modulation, control and safety components
are tested and pre-wired for use.
Observe safety precautions and all rules and regulations
required by local code and the National Electric Code.
Fuses
The appliance is protected with a fuse. It is located on the
circuit board (Æ Fig. 8, page 18).
Replacement fuses can be found on the back
of the cover (Æ Fig. 36).
Controls and modules
For installation and electrical connection of controls and
modules, see the installation instructions of the accessory.
Connecting Third party room thermostats or zone
controls
A voltage free (dry contact) third party room thermostat or
heat demand from a relay panel can be used to send an
ON/OFF signal to the appliance.
B
B
4
2
1
F
9
A
8
7
1
2
6 720 641 933-70.1O
ϑ
LS NS
NP
LP
Fig. 43 Electrical wiring third party room thermostat or
zone control
To communicate a heat demand the third party room
thermostat or zone control must connect pins 2 and 4.
6.3.2Connecting an external heating zone pump or
DHW recirculation pump
Without accessories the appliance offers the connection
of one heating zone pump, one circulator of an unmixed
heating circuit, or one DHW recirculation pump.
The pump used must have the following connection
values: 120 VAC, max. 2 A.
B Route cable from pump to appliance.
B Insert cable into the junction box as shown in Fig. 46.
B Connect cable to the black plug according to Fig. 45.
1
2
3
4
Fig. 45 Attach plug (external pump)
1L (120 VAC, 60 Hz)
2PE (GND, Ground)
3N (Neutral)
4Black plug (in the junction box upon delivery)
6 720 641 933-41.1O
6.3Electrical connections in the junction
box (120 VAC)
6.3.1Mounting rails for junction box
B Hold the rail against the appliance from below (step 1)
and fasten with the screws from the outside or inside
(step 2).
B Loosen junction box from the rail (step 3).
2
1
2
3
Fig. 44 Mounting rails for junction box
6 720 641 933-42.1O
B Connect black plugs and insert grommet until stop.
L PE N
blackCH pump
I III III III
8 737 701 503
redStorage
tank pump
for mixed heating
6 720 641 933-40.1O
L PE N
white
Mains
120V/60Hz
L PE N
Fig. 46 Cable connected (external pump)
B Use service function 5.E, to set connection to 01 (DHW
recirculation pump) (Æ page 71)
-or-
B Use service function 5.E to set connection to 02
(external heating zone pump in an unmixed heating
circuit) (Æ page 71).
-or-
B Use service function 5.E to set connection to 03
(external heating pump) (Æ page 71).
The DHW recirculation pump is controlled by
the Bosch FW 200.
properly filled and purged will damage the
appliance.
B Only operate this appliance after ensuring
there is sufficient water in the boiler and
the system.
B Adjust the expansion vessel pre-charge pressure to the
static head of the heating system (Æ page 37).
B Open radiator and zone valves (as applicable).
B Open heating supply and return valves, fill heating
system to 14.5 to 21.75 psi (1 - 1.5 bar) and close fill
valve.
B Bleed all air from the system.
B If the boiler water pressure has dropped, fill the heating
system again to 14.5 to 21.75 psi (1 to 1.5 bar).
B On ZBR..-3A appliances (heating boilers) with a DHW
tank, open the cold water supply and open a DHW tap
until water runs out.
B Verify that the gas type specified on the rating plate is
the same as the gas type used.
B Open the gas cock.
7.2Switching the appliance ON/OFF
Startup
B Switch the appliance ON using the ON/OFF switch.
The display indicates the supply temperature of the hot
water in °F. If necessary, convert to °C (Æ Service
function 0.E: Metric or US customary units, page 73)
4
3
5
2
1
6
max
Fig. 54 Switching the appliance ON/OFF
When the appliance is switched ON for the
first time, it performs a once-only purging
sequence. This involves the heating zone
pump switching on and off at intervals (for
approx. 4 minutes).
The display shows in alternation with the
supply temperature.
B Open the automatic vent [9] (only combi boiler
ZWB..-3A) and close it again when the purging sequence
has finished (Æ page 58).
6 720 613 896-05.1O
If the display shows in alternation with the
supply temperature, the trap filling function is
active (Æ page 70).
Shutdown
B Switch appliance OFF using the ON/OFF switch.
The display goes out.
B If the appliance is taken out of service for a longer
Set the maximum supply temperature based on the
structure's heat loss on design day.
Boiler high
limit dial
1approx. 95°F
2approx. 109°F
3approx. 122°F
4approx. 140°F
5approx. 153°F
6approx. 167°F
maxapprox. 194 °F
Typical supply
temperatures
(35 °C)
(43 °C)
(50 °C)
(60 °C)
(67 °C)
(75 °C)
(90 °C)
Sample application
Frost protection
Radiant floor heating
system
Panel radiator system
Cast iron radiator
system
Baseboard and
convector system
7.4Programming the FW 200 heating
control unit
Observe the operating instructions for the
heating control included in the scope of
delivery. There you can read:
B How to set the operating mode and the
heating curve for outdoor reset controls
B How to adjust the room temperature
B How to heat economically and comfortably
B How the control can be mounted in the
boiler or in the living space
9
12
15
h
6
24
3
Fig. 56 FW 200 heating control
h
18
21
6 720 612 660-07.2O
Tab. 24 Typical supply temperatures
With radiant floor heating, limit the maximum
permissible supply temperature as
recommended by the manufacturer.
B In order to set the maximum supply temperature, turn
the boiler high limit dial .
reset
eco
4
3
2
5
1
6
max
4
3
e
2
1
6
max
min
6 720 641 933-53.1O
Fig. 55 Switch on heat
If the burner is operating, the burner operation
indicator lamp is illuminated.
7.5After commissioning
B Check flue path for tightness.
B Check gas supply dynamic pressure (Æ page 78).
B Check that condensate is being discharged from the
condensate hose. If that is not the case, switch the
appliance first OFF and then ON again using the ON/
OFF switch. That activates the trap filling sequence
(Æ page 70). Repeat the procedure several times until
condensate starts running out.
7.6ZBR..-3A appliances (heating boilers)
with DHW tank: Setting the DHW
temperature
B Set the DHW temperature on the DHW thermostat .
The set DHW temperature flashes on the display for
30 seconds.
reset
eco
34
2
5
1
6
max
Fig. 57 Set the DHW temperature (heating boiler ZBR..-3A)
4
3
2
e
1
6
max
6 720 641 933-54.1O
Commissioning | 61
ECO button
The default setting is DHW priority; the ECO button is not
lit.
In order to switch between DHW tank priority and
alternating operation, press the ECO button.
• DHW priority
First, the DHW tank is heated up to the set temperature.
The appliance then goes into heating mode. Therefore,
it can happen that space heating is interrupted for a
while and the room temperature may drop.
DHW tank priority guarantees highest DHW comfort.
• Alternating operation
The appliance switches between space heating mode
and DHW mode. This prevents the room from cooling off
too much.
Alternating operation guarantees an even room
temperature with somewhat less DHW convenience.
DHW thermostat Typical DHW temperatures
minapprox. 59 °F (15 °C)
eapprox. 131°F (55°C)
maxapprox. 158°F (70°C)
Tab. 25 Typical DHW temperatures for heating boiler
ZBR..-3A
WARNING: Danger of scalding!
B In normal operation, it is recommended to
limit the DHW temperature to 122 °F
(50 °C) to limit the risk of scalding.
B Install a tempering valve if running DHW
temperatures above 104 °F (40 °C).
B Only use temperatures up to 158 °F (70 °C)
for thermal disinfection (Æ page 63).
If there is reason for concern for contamination
from bacteria such as legionella, consider
setting the DHW thermostat to at least “e”
(131 °F (55 °C)).
This setting ensures an economical and
comfortable DHW generation. Consult your
local water department or municipality for
further information.
7.7ZWB..-3A appliances (combi boilers):
Setting the DHW temperature
B Set the DHW temperature on the DHW thermostat .
The set DHW temperature flashes on the display for
30 seconds.
reset
eco
34
2
5
1
6
max
Fig. 58 Set the DHW temperature (combi boiler ZWB..-3A)
DHW thermostat Typical DHW temperatures
minapprox. 104 °F (40 °C)
eapprox. 122 °F (50 °C)
maxapprox. 140 °F (60 °C)
Tab. 26 Typical DHW temperatures for combi boiler
ZWB..-3A
ECO button
Pressing and holding the ECO button until it lights up
switches between Comfort mode and Economy mode.
4
3
2
e
1
6
max
6 720 641 933-55.1O
• Comfort mode (default setting)
The appliance is continually maintained at the set
temperature. Consequently, DHW draws are immediate,
however the appliance may run even if no DHW is being
drawn.
• Economy mode, ECO button lights up
– DHW is only generated when DHW is drawn.
– On demand: Quickly open and close a DHW tap to
signal the appliance to heat to the selected
temperature. After a short wait DHW will be
available.
The DHW on demand signal allows maximum
gas and water savings.
7.9Setting frost protection
Frost protection of the heating system:
B Leave the appliance switched ON; set the boiler high
limit to at least
95°F (35°C)
page 60).
3
2
1
Fig. 60 Frost protection of the heating system
(position 1, Æ Tab. 24,
reset
eco
4
5
6
max
3
e
2
6
1
max
min
6 720 641 933-68.1O
7.8Setting manual summer mode
In summer mode or warm weather shut down (WWSD),
the heating zone pump and consequently central heating
are switched off. DHW generation remains active following
the DHW program.
See also the warm weather shutdown
(WWSD) feature in the operating instructions
for the heating control included in the scope
of delivery.
NOTICE: Heating system at risk of freezing. In
manual summer mode, only the appliance is
protected from freezing.
B Observe frost protection measures where
there is a risk of frost (Æ Chapter 7.9).
B Make a note of the setting of the boiler high limit
dial.
B Turn the boiler high limit dial counterclockwise
to.
reset
eco
-or- If you want to leave the appliance switched OFF:
B Mix Bosch-approved anti-freeze into the heating water
(Æ Tab. 15, page 36) and drain the DHW circuit.
For further information, see the operating
instructions for the heating control included in
the scope of delivery.
Frost protection of the DHW tank:
B Leave the appliance switched ON; set the boiler high
limit to at least
95°F (35°C)
(position 1, Æ Tab. 24,
page 60).
B Turn the DHW thermostat counterclockwise to min
(59 °F (15 °C)).
reset
eco
2
1
34
5
6
max
3
e
2
1
min
6
max
6 720 641 933-69.1O
Fig. 61 Frost protection for the DHW tank
4
3
5
2
1
6
max
3
2
1
min
6 720 615 065-13.1O
Fig. 59 Summer mode
For further information, see the operating instructions for
the heating control included in the scope of delivery.
The key pad lock affects the boiler high limit dial, the DHW
thermostat, and all buttons except the ON/OFF switch,
emissions test button, and reset button. It can be used to
limit unauthorized access to the boiler.
Activating the key pad lock:
B Press the key pad lock button until and the heating
supply temperature are alternating on the display.
reset
eco
34
2
5
1
6
max
Fig. 62 Key pad lock
Unlocking the key pad:
B Press the key pad lock button until the display shows
only the supply temperature.
3
2
1
min
6 720 615 065-17.1O
4
e
6
max
8ZBR..-3A appliances (heating
boiler) with DHW tank:
Thermal disinfection
Thermal disinfection covers the DHW system including the
taps. For solar DHW tanks, the solar portion of the tank is
not covered.
WARNING: Risk of scalding!
Hot water can result in severe scalding.
B Carry out thermal disinfection only outside
the normal hours of use, or install a
tempering valve.
B Close all DHW taps.
B Advise occupants of the risk of scalding if no tempering
valve is installed.
B Set the time and DHW temperature accordingly on the
heating control with DHW program.
B Set any DHW recirculation pump to continuous
operation.
B Turn DHW thermostat clockwise to max (approx. 158 °F
(70 °C)).
reset
eco
2
1
34
5
6
max
4
3
2
1
6 720 615 065-10.1O
e
6
max
Fig. 63 Thermal disinfection
B Wait until the maximum temperature has been reached.
B Open all DHW taps, from the nearest to the one furthest
away, and draw off hot water until it reaches a minimum
of 158 °F (70 °C) at all taps for at least 3 minutes.
B Reset the DHW thermostat, DHW recirculation pump,
and heating control to standard operation.
Thermal disinfection can also be carried out
automatically and on a regular basis; see
operating instructions for the heating control
included in the scope of delivery.
This function prevents the heating zone pump
from seizing up following longer idle periods.
The appliance will briefly run the pump at least every 24
hours after its last activation.
9.2Changing the pump curve of the boiler
pump
The speed of the boiler pump can be changed using the
dial on the pump.
25
20
15
H / ft
10
1
2
4
3
5
0
025781436
.
V / gpm
7
6
5
4
4
3
H / m
2
2
1
3
25
20
15
H / ft
10
5
2
1
4
3
0
0213546 87
.
V / gpm
7
6
5
4
4
3
H / m
2
1
0
0
40080012001600
1
3
2
.
V / l/h
Fig. 65 Pump curve of the boiler pump combi boiler
ZWB..-3A
Key to Fig. 64 and Fig. 65:
1Residual head pressure at speed 1
2Residual head pressure at speed 2
3Residual head pressure at speed 3 (default setting)
4Head pressure of the boiler pump by itself (at speed 3)
HHead pressure in feet of head (m)
Circulating water volume in gallons per minute (l/h)
V
6 720 641 933-61.1O
1
0
0
4008001200160020060010001400
.
V / l/h
Fig. 64 Pump curve of the boiler pump heating boiler
ZBR..-3A
In order to save as much energy as possible
and keep any water circulation noises to a
minimum, select the lowest possible pump
speed.
The Heatronic allows easy setting and testing of many
appliance functions.
For an overview of service functions, see Chapter 10.2 on
page 66.
3
reset
4
3
eco
4
5
e
6
max
6 720 641 933-52.1O
2
1
4
3
2
1
5
6
max
Fig. 66 Overview of the controls
1Emissions test button
2Service button
3Display
4ECO button, service functions “up”
5Key pad lock, service functions “down”
Selecting a service function
The service functions are subdivided into two levels: The
1st level includes service functions up to 0.E, the 2nd
level includes service functions starting with 8.A.
B Press and hold the service button until it illuminates.
The display shows a code such as 1.A (first service
level).
B Repeatedly press the key pad lock button or ECO
button to scroll to the desired service function.
B Press and release the emissions test button .
The emissions test button will light up and the
display shows the setting for the selected service
function.
2
1
min
Heatronic boiler control settings | 65
Adjust Value
B Repeatedly press the key pad lock button or ECO
button to adjust the value up or down.
B Record the value in the commissioning log (Æ page 97).
Saving the value
B Press and hold the emissions test button until the
display shows (value saved).
The unit automatically exits the service level if
no button is pressed for 15 minutes.
Exiting the service function without saving values
B Briefly press the emissions test button .
The light of the emissions test button will go out.
Restoring factory settings
In order to reset all values for the service levels 1 and 2 to
the factory setting:
B Press and hold the service button until it illuminates.
The display shows a code such as 1.A (first service
level). Press the ECO button and key pad lock button
simultaneously until e.g. 8.A appears (second service
level).
B On the second service level, select the service function
8.E and value 00. The appliance restarts with the default
settings.
10.2.1 First service level (press and hold the service
button until it lights up)
Service function
DisplayPage
1.A
1.b
1.E
1.F
2.A
2.b
2.C
2.d
2.F
3.A
3.b
3.C
3.d
3.E
3.F
4.b
4.d
4.E
4.F
5.A
5.b
5.E
5.F
6.A
6.b
6.C
6.d
7.A
7.b
7.d
7.E
0.A
0.d
0.E
Tab. 27 Service functions, 1st level
Maximum space heating output67
Maximum DHW output67
Pump mode for space heating operation67
Pump mode67
Heating circuit pump lockout time68
Maximum supply temperature68
Purging function68
Thermal disinfection68
Operating mode68
Automatic anti-cycle function69
Set anti-cycle time69
Switching differential (hysteresis)69
Minimum output (heating and DHW)69
Cycle time, keeping DHW hot69
Constant DHW period70
Maximum heat exchanger temperature70
Audible fault warning tone 70
Appliance type70
Condensate trap filling sequence70
Reset inspection interval70
Fan post purge time71
Functionality of black plug in boiler
junction box
Set inspection interval71
Display the latest fault code71
Room temperature control, current volt-
age, terminal 2
Supply temperature required by outdoor
reset control
Current DHW turbine flow rate71
Indicator lamp for burner operation /
faults
3-way valve in center position72
Connecting an external supply or low-
loss header temperature sensor
Building drying function72
Do not use this setting!72
Altitude adjustment72
Metric or US customary units73
71
71
71
71
72
10.2.2 Second service level (at first service level,
service button lights up, press ECO button and
key pad lock button simultaneously until e.g. 8.A
appears)
Service function
DisplayPage
8.A
8.b
8.C
8.d
8.E
8.F
9.A
9.b
9.C
9.d
9.E
9.F
A.b
A.C
b.F
C.d
Software version73
Code plug number 73
GFA Gas burner control status73
GFA Gas burner control fault73
Restore boiler to factory settings73
Permanent ignition73
Constant mode73
Current fan speed 73
Current boiler output 73
Set fan start speed74
Turbine signal delay 74
Heating zone pump post purge74
Display DHW temperature74
Display DHW tank temperature74
Solar DHW backup heating delay74
Display current heat demand74
Service function 1.E: Pump mode for space heating
operation
10.3.1 First service level
Service function 1.A: Maximum space heating output
Some gas supply companies offer a performancedependent basic price.
The output can be limited in percent between the
minimum and maximum nominal output to suit the specific
heat demand.
Even if the heating output has been limited,
the maximum nominal output is still available
for DHW generation.
B Select service function 1.A.
B Select heat output in MBH (kW) and determine
associated setting in percent (%).
B Enter the setting (Æ 10.1).
B Save the setting (Æ 10.1).
B Record the set heat output in the commissioning log
(Æ page 97).
B Exit the service functions.
The display returns to the supply temperature.
Default setting is the maximum nominal output: U0
(100 %).
Service function 1.b: Maximum DHW output
The hot water output can be adjusted between the
minimum and maximum DHW outputs to suit the heat
transfer capacity of the DHW tank coil.
B Select service function 1.b.
B Select the DHW output in MBH (kW) and determine the
associated setting in percent (%).
B Enter the setting (Æ 10.1).
B Save the setting (Æ 10.1).
B Record the set DHW output in the commissioning log
(Æ page 97).
B Exit the service functions.
The display returns to the supply temperature.
Default setting is the maximum nominal output: U0
(100 %).
If an outdoor temperature sensor for an
outdoor reset control is connected, pump
control mode 04 is automatically set.
• Pump control mode 00 (automatic mode): The BUS
control controls the central heating pump.
• Pump control mode 01: For heating systems without
control.
The supply temperature controls the central heating
pump. When there is a demand for heat, the central
heating pump and the burner start up.
• Pump control mode 02: Do not use.
• Pump control mode 03: The central heating pump runs
continuously (exceptions: See heating control
operating instructions).
• Pump control mode 04: Intelligent control of central
heating pump in heating systems with outdoor reset
control. The heating zone pump is only switched on
when needed.
Default setting is 00.
Service function 1. F: Pump mode (only heating boiler
ZBR..-3A)
NOTICE: System damage or boiler
malfunction!
B Never change the setting of this service
function on combi boiler ZWB..-3A
appliances.
Based on this setting, the pump connected to the
Heatronic or 3-way valve are controlled according to the
configuration of the heating system.
The following settings are possible:
• Pump mode 00: T
heating boiler.
• Pump mode 01: A 3-way valve for DHW tank loading is
connected in boiler circuit before low loss header (see
also service function 2.A).
• Pump mode 02: Do not use this setting!
• Pump mode 03: A DHW tank pump is connected on the
system side after the low loss header.
In DHW mode, DHW tank
Service function 2.A: Heating circuit pump lockout time
(only heating boiler ZBR..-3A)
NOTICE: System damage or boiler
malfunction!
B Never change the setting of this service
function on combi boiler ZWB..-3A
appliances.
This setting is only active if Service function
1. F: Pump mode is set to 01 (3-way valve).
During the runtime of an external 3-way valve actuator, the
space heating pump is blocked. Select the run time of the
3-way valve actuator between 01 - 24 (10 - 240) seconds
according to the manufacturer's documentation
.
Default setting is 24 (240 seconds).
Service function 2.b: Maximum supply temperature
The values of this service function displayed depend on
the setting of the service function 0.E:
Service function 0.E is set to 00 (metric units):
• The maximum supply temperature can be adjusted
between 35 and 88 (35 - 88 °C).
Service function 0.E is set to 01 (US customary units):
• The maximum supply temperature can be adjusted
between 96 and 190 (96 - 190 °F).
The following settings are possible:
• 00: Purging function off
• 01: Purging function is switched on and after
completion automatically reset to 00
• 02: Purging function is permanently on and is not reset
to 00
Default setting is 00 for heating boilers ZBR..-3A
appliances, otherwise 01.
Service function 2.d: Thermal disinfection (legionella
protection)
WARNING: Risk of scalding!
Hot water can result in severe scalding.
B Carry out thermal disinfection only outside
the normal hours of use.
B Install a tempering valve if this function is
enabled permanently.
When this service function is enabled, the DHW is
permanently heated to approx. 158 °F (70 °C) if the DHW
temperature dial has been turned clockwise to max.
The following settings are possible:
• 00: Thermal disinfection not enabled
• 01: Thermal disinfection enabled
Default setting is 00 (disabled).
Default setting is 190 (190 °F (88 °C)).
Service function 2.C: Purging function
When the appliance is switched ON for the
first time, it performs a once-only purging
sequence. This involves the heating zone
pump switching on and off at intervals (for
approx. 4 minutes).
The display shows in alternation with the
supply temperature.
This service function allows activating the
purging function manually, e.g. after servicing.
Service function 2.F: Operating mode
With this service function, you can temporarily change the
appliance's operating mode.
The following settings are possible:
• 00: Default mode; the appliance runs according to
control settings.
• 01: The appliance runs for 15 minutes at minimum
output. The display shows 2.F. When this service
function is aborted or has been active for 15 minutes,
the appliance reverts to default mode.
• 02: The appliance runs for 15 minutes at maximum
output. The display shows 2.F. When this service
function is aborted or has been active for 15 minutes,
the appliance reverts to default mode.
Service function 3.A: Automatic anti-cycle function
If an outdoor reset control is connected, there
is no need to adjust this setting on the
appliance.
The control automatically optimizes the anticycle time.
Use service function 3.A to set the automatic adaptation of
the anti-cycle time. This can be required in case of
unfavorably-dimensioned heating systems. Short cycling
may increase boiler and system wear and tear, increase
emissions, reduce comfort, and should be avoided.
With auto-adaptation of the anti-cycle time disabled, the
anti-cycle time must be set using service function 3.b
(Æ page 69).
The following settings are available:
• 00: Automatic adaptation of the anti-cycle time is
disabled
• 01: Automatic adaptation of the anti-cycle time is
enabled
Default setting is 00 (switched off).
Service function 3.C: Switching differential
Only if the automatic anti-cycle time is disabled (service
function 3.A) will this function be active.
If an outdoor reset control is connected, there
is no need to adjust this setting on the
appliance.
The control automatically optimizes this
setting.
The switching differential is the permitted boiler
differential from the target supply temperature. It can be
set in increments of 1 °F (0.5 °C). The minimum supply
temperature is 95 °F (35 °C).
Service function 0.E is set to 00 (metric units):
• You can set the switching differential between 00 and
30 (0 - 30 °C).
Service function 0.E is set to 01 (US-customary units):
• You can set the switching differential between 00 and
54 (0 - 54 °F).
Default setting is 18 (18 °F (10 °C)).
Service function 3.b: Set anti-cycle time
Only if the automatic anti-cycle time is disabled (service
function 3.A) will this function be active.
If an outdoor reset control is connected, there
is no need to adjust this setting on the
appliance.
The control automatically optimizes the anticycle time.
The anti-cycle time can be set from 00 to 15
(0 to 15 minutes).
With 00, the anti-cycle lock is switched off.
The shortest possible switching interval is 1 minute
(recommended for single zone or forced air heating
systems).
Default setting is 03.
Service function 3.d: Minimum output
(heating and DHW)
The output for heating and DHW can be set to any level in
percent between the minimum and maximum nominal
output.
The default setting is the minimum nominal output
(heating and DHW) and varies according to appliance.
Service function 3.E: Cycle time, keeping DHW hot
(only combi boiler ZWB..-3A)
NOTICE: System damage or boiler
malfunction!
B Never change the setting of this service
function on heating boiler ZBR..-3A
appliances.
This service function is only active in comfort mode.
It specifies the time from completion of preheating or
DHW demand until the next time the plate-type heat
exchanger is heated up. This prevents the plate-type heat
exchanger from overheating.
Service function 3.F: Constant DHW period
(only combi boiler ZWB..-3A)
NOTICE: System damage or boiler
malfunction!
B Never change the setting of this service
function on heating boiler ZBR..-3A
appliances.
The constant DHW period specifies how long the space
heating mode remains disabled after DHW is drawn.
The duration for keeping DHW hot can be set from 00 to
30 (0 to 30 minutes).
Default setting is 01 (1 minute).
Service function 4.b: Maximum heat exchanger
temperature (only combi boiler ZWB..-3A)
NOTICE: System damage or boiler
malfunction!
B Never change the setting of this service
function on heating boiler ZBR..-3A
appliances.
This function can be used to reduce limestone built-up in
the heat exchanger, which increases with temperature.
The maximum heat exchanger temperature can be set in
steps of 1 °F (0.5 °C).
Service function 0.E is set to 00 (metric units):
• The maximum temperature for keeping the heat
exchanger hot can be set from 40 to 65 (40 to 65 °C).
Service function 0.E is set to 01 (US-customary units):
• The maximum temperature for keeping the heat
exchanger hot can be set from 104 to 150
(104 to 150 °F).
Default setting is 140 (140 °F (60 °C)).
Service function 4.d: Audible fault warning tone
The appliance can be set to sound an audible alarm to alert
the operator of a fault present. The audible warning tone
can be deactivated with the service function 4.d.
• 00: Warning tone off
• 01: Warning tone on
Default setting is 01 (ON).
Service function 4.E: Appliance type
This service function displays the appliance type detected.
Possible displays are:
• 00: Central heating only
• 01: Combi appliance
• 02: DHW tank temperature sensor (NTC) connected to
Heatronic.
• 03: DHW tank thermostat connected to Heatronic.
• 04: Stratified DHW tank
• 05: Tank with NTC return
Service function 4.F: Condensate trap filling sequence
DANGER: Risk of flue gas poisoning!
If the condensate trap is not filled, flue gas
may escape from the dry trap.
B Only deactivate the trap filling sequence
for servicing purposes.
B When servicing is complete, reactivate the
trap filling function.
The trap filling sequence ensures that the condensate trap
is filled after initial installation or after a longer downtime
of the appliance.
The trap filling sequence is activated if:
• The appliance is switched OFF using the ON/OFF switch
• The burner has not been in use for at least 28 days
• You are switching between summer and winter mode
The next time there is a demand for heat in central heating
or hot water mode, the appliance is held at low output for
15 minutes. The trap filling sequence remains active until
completed 15 minutes of operation at
the appliance h
as
low output. The display shows in alternation with the
supply temperature.
The following settings are available:
• 00: Condensate trap filling sequence is off.
• 01: Trap filling program at the lowest output.
• 02: Trap filling sequence at set minimum output.
Default setting is 01.
Service function 5.A: Reset inspection interval
This function enables resetting the indication on the
display after completing inspection/servicing of the
appliance.
Service function 7.b: 3-way valve in center position
After the value 01 has been saved, the 3-way valve moves
to the center position. This allows draining the system
completely and removing the motor easily.
When you exit this service function, the appliance returns
to setting 00.
Service function 7.d: Connecting an external supply or
low-loss header temperature sensor
Presence of an external supply or low loss header
temperature sensor is automatically detected by default;
you do not need to change any settings.
If a sensor is disconnected, change the setting
back to the default setting 00.
The following settings are available:
• 00: Once-only automatic detection of a sensor
• 01: External supply temperature sensor connected to
Heatronic.
• 02: External supply temperature sensor connected to
IPM2.
Default setting is 00.
Service function 0.A: Do not use this setting!
Default setting is 00 (disabled).
Service function 0.d: Altitude adjustment
Input and output rates are reduced at higher altitudes due
to thin air with reduced oxygen levels.
ZBR42-3A... and ZWB42-3A... appliances are derated at
3 % per 1000 feet (305 m).
ZBR16-3A..., ZBR28-3A..., ZBR35-3A... and ZWB28-3A...
appliances offer altitude adjustment which compensates
for the effects of thin air, and are therefore NOT derated
up to 6000 feet (1829 m). Above 6000 feet (1829 m) a
rate of 3 % per 1000 feet (305 m) applies.
This service function is used to adjust the fan speed for
high altitude operation.
The following settings are available:
• 00: Normal
• 01: Medium
• 02: High
Setting Elevation above sea level
000 ft – 2,000 ft (0 m – 610 m)
012,001 ft – 4,500 ft (611 m – 1 372 m)
Service function 7.E: Building drying function
This service function allows you to start and stop the
building drying function.
Never confuse the appliance building drying
function with the slab drying function of the
outdoor reset control FW200.
When the building drying function is on, you
cannot adjust the appliance gas settings.
The following settings are available:
• 00: Off
• 01: Heating operation only in accordance with the
appliance or control setting, i.e. all other heat demands
are blocked.
Default setting is 00.
02above 4,500 ft (1 372 m)
Tab. 29 Altitude adjustment (service function 0.d)
Service function 0.E: Metric or US customary units
With this service function you can set if Metric or US
customary units are displayed on the boiler.
The following settings are available:
• 00: °C, l/min (metric units)
• 01: °F, gpm (US-customary units)
Default setting is 01.
10.3.2 Second service level
Service function 8.A: Software version
The current software version is displayed.
Service function 8.b: Code plug number
The last four digits of the code plug number
are shown.
The code plug determines the appliance
functions. If the appliance has been converted
from natural gas to LPG (or vice versa), the
code plug must be replaced.
Service function 8.C: GFA Gas burner control unit status
Internal parameter. If you are on the line with Bosch
Technical Support you may be asked for this number.
Service function 8.d: GFA Gas burner control unit fault
Internal parameter.
Service function 8.E: Restore boiler to factory settings
This function allows resetting all parameters of the boiler
including all service functions to their factory settings.
B Press and hold the emissions test button until the
display shows .
All settings are reset and the appliance restarts with the
default settings.
B Reset altered service functions to the settings recorded
in the commissioning log (Æ page 97).
Service function 8.F: Permanent ignition
NOTICE: Ignition transformer damage.
B Never leave this function on for longer than
2 minutes at a time.
This function enables permanent ignition without gas
supply to test the performance of all ignition related
components.
The following settings are available:
• 00: Off
• 01: On
Default setting is 00.
Service function 9.A: Constant mode
This function sets one operating mode permanently
(Æ Service function 2.F: Operating mode, page 68).
The following settings are available:
• 00: Default mode: the appliance runs according to
control settings.
• 01: The appliance runs permanently at minimum output.
The display shows 9.A.
• 02: The appliance runs permanently at maximum
output. The display shows 9.A.
Default setting is 00.
B Press and hold the service button until it illuminates.
The display shows a code such as 1.A (first service
level).
B Press and hold ECO button and key pad lock button
simultaneously until a service function, e.g. 8.A, is
displayed (second service level).
B Repeatedly press the key pad lock button or ECO
button until service function 8.E is displayed.
B Press and release the emissions test button .
The emissions test button lights up and the display
shows 00.
Service function 9.b: Current fan speed
This service function allows you to display the current fan
speed in revolutions per second (1/s).
At higher elevations the boiler fan may need to spin faster
upon startup to ensure reliable ignition every time. The
start speed of the boiler fan can be set from 45 to
77 revolutions per second (1/s).
Default setting is 50.
Service function 9.E: Turbine signal delay
(only combi boiler ZWB..-3A)
NOTICE: System damage or boiler
malfunction!
B Never change the setting of this service
function on heating boiler ZBR..-3A
appliances.
This service function allows setting a time delay to prevent
the appliance starting up as a result of transient pressure
spikes in the water supply.
Through spontaneous pressure change in the water
supply, the flow meter (turbine) can signal that DHW is
being drawn and cause the burner to come on
unnecessarily.
Service function b.F: Solar DHW backup heating delay
(only combi boiler ZWB..-3A)
For systems with a solar thermal DHW ta nk in series b ef or e
the DHW line of the combi boiler. DHW heating by the
boiler will be suppressed expecting that solar thermal
DHW will reach the hot water temperature sensor prior
eliminating the need to run the boiler. Set the heating
delay in accordance with system conditions.
If this setting is enabled, the DHW demand
signal is no longer available Æ page 61.
The start delay can be set between 00 to 50 (0 to 50
seconds) in increments of 1 second.
Default setting is 00.
Service function C.d: Display current heat demand
Available displays are:
• 00: No heat demand
• 01: Space heating demand present
• 02: DHW heat demand present
The turbine signal delay can be set from 02 to 08 (0.5
seconds to 2 seconds) in increments of 0.25 seconds.
Default setting is 04 (1 second).
Service function 9.F: Heating zone pump post purge
This service function allows setting a pump post purge
time after the end of the heat demand from the external
control.
The pump post purge time can be set from 01 to 10
(1 to 10 minutes).
Default setting is 03.
Service function A.b: Display DHW temperature
This service function allows displaying the current DHW
temperature.
Service function A.C: Display DHW tank temperature
This service function allows displaying the temperature of
the DHW tank temperature sensor.
a trained and certified installer in
accordance with the manufacturer‘s
instructions and all applicable codes and
requirements of the authority having
jurisdiction.
B If the information in these instructions is
not followed exactly, or the installation,
adjustment, modification, operation or
maintenance is carried out by an
unqualified person, a fire, explosion or
generation of large amounts of carbon
monoxide may result causing property
damage, personal injury or loss of life.
B Before carrying out electrical work:
Disconnect the installation from the power
supply at the emergency shutoff switch or
by disengaging the heating system circuit
breaker. Take measures to prevent
accidental reconnection.
B The installer is responsible for the proper
conversion of this appliance.
B The conversion is not complete until the
operation of the converted appliance is
checked as specified in these instructions.
The gas-air ratio must always be set on the basis of a CO2
reading taken at maximum nominal output and
or O
2
minimum nominal output using an electronic flue gas
analyzer.
11.1Converting to a different gas type
DANGER: Explosion!
B Close the gas cock prior to working on the
gas train.
B Check for gas leaks after carrying out work
on the gas train.
A gas conversion kit is included in the scope of delivery.
B Fold the Heatronic down.
B Check the number on the code plug from the gas
conversion kit (Code plug number Æ table 42, page 96).
B Replace the code plug in the Heatronic with the code
plug from the gas conversion kit.
6 720 641 933-57.1O
Fig. 67 Replacing the code plug
B Affix the gas type label from the gas conversion kit to
the appliance.
Adjustment to different flue systems using throttle discs or
baffles is not necessary.
NG
• Appliances are set at the factory to Wobbe index
3
1,333 BTU/ft
(1016 hPa)
(49.6 MJ/m3) at 60 °F (15 °C), 30" Hg
and 7.0" W.C. (17.4 mbar) gas supply
pressure and sealed.
6 720 641 933-58.1O
Fig. 68 Affixing the gas type label
B Always adjust the gas-air ratio (CO
or O2,
2
Æ Section 11.3) after converting to a different gas type
and measure the CO content of the flue gas
(Æ Section 12).
11.2Installation location higher than
2,000 feet (610 m) above sea level
Input and output rates are reduced at higher altitudes due
to thin air with reduced oxygen levels.
ZBR42-3A... and ZWB42-3A... appliances are derated at
3 % per 1000 feet (305 m).
ZBR16-3A..., ZBR28-3A..., ZBR35-3A... and ZWB28-3A...
appliances offer altitude adjustment which compensates
for the effects of thin air, and are therefore NOT derated
up to 6000 feet (1829 m). Above 6000 feet (1829 m) a
rate of 3 % per 1000 feet (305 m) applies.
The Bosch Greenstar boiler is factory set for
installation below 2000 feet (610 m) above
sea level.
B Correction of the fan speed curve of the burner:
Use service function 0.d to adjust the elevation setting
(Æ page 72).
11.3Setting the gas-air ratio (CO2 or O2)
B Switch the appliance OFF using the ON/OFF switch.
B Remove the cover (Æ page 41).
B Switch the appliance ON using the ON/OFF switch.
B Open one of the flue gas test ports.
6 720 641 933-79.1O
Fig. 69 Open one of the flue gas test ports
B Insert the probe approx. 2-3/4 inches (70 mm) into the
test port and seal around it.
B Press and hold the emissions test button until it
lights up.
The display shows the supply temperature alternating
with = maximum set output in heating mode.
B Briefly press the emissions test button .
The display shows the supply temperature in
alternation with = maximum nominal output.
B Switch the appliance OFF and close the gas shut-off
valve.
B Loosen the screw in the test port for gas inlet pressure
(Æ Fig. 72, [1]) and connect a pressure gauge
(Æ Fig. 74).
6 720 614 090-34.1O
Fig. 74 Dynamic gas pressure test port
B Turn on the gas cock and switch the appliance ON.
B Press and hold the emissions test button until it
lights up.
The display shows the supply temperature alternating
with = maximum set output in heating mode.
B Briefly press the emissions test button .
The display shows the supply temperature in
alternation with = maximum nominal output.
B Check the required inlet gas pressure according to
table 31.
Gas type
Nominal
pressure
" W.C.
(mbar)
Permissible pressure
range for maximum
nominal output
" W.C. (mbar)
NG7 (17.4)3.5-10.5 (8.7-26.1)
LPG (propane)11 (27.4)8-13 (19.9-32.3)
Tab. 31 Inlet gas pressure
Do not operate the appliance if the measured
value is below or above these values.
Determine the cause and eliminate the fault. If
this is not possible, block the appliance on the
gas side and notify the gas supplier.
B Repeatedly press the emissions test button until the
light goes out.
The display returns to the supply temperature.
B Switch the appliance OFF, turn off the gas cock, remove
the pressure gauge and tighten the screw in the test
port for gas inlet pressure.
Environmental responsibility is one of the fundamental
company policies of the Bosch Group.
We regard quality of performance, economy and
environmental responsibility as equal objectives.
Environmental protection laws and regulations are strictly
adhered to.
To protect the environment, we use the best possible
technology and materials taking into account economic
points of view.
Packaging
All packaging materials used are environmentally-friendly
and recyclable.
Old appliances
Old appliances contain resources that must be submitted
for recycling.
The components are easy to separate and the plastics are
marked. This allows the various components to be sorted
for appropriate recycling or disposal.
Regular service and maintenance are recommended for a
long service life of the appliance, for efficient and
economical operation, and to keep the environmental
impact as low as possible. Owners/operators are
encouraged to sign a service and maintenance contract
with a trained and certified installer for annual servicing
and maintenance of the boiler.
DANGER: Explosion!
B Close the gas cock prior to working on the
gas train.
B Check for gas leaks after carrying out work
on the gas train.
DANGER: Risk of flue gas poisoning.
B Check for leaks after carrying out work on
the venting system.
DANGER: Risk of electric shock!
B Always disconnect the appliance from the
mains power before performing any work.
Disconnect the emergency shutoff switch
or disengage the heating system circuit
breaker. Take measures to prevent
accidental reconnection.
NOTICE: Insufficient antifreeze can
accelerate corrosion.
B Frost protection level has to be checked
annually during the regular scheduled
maintenance of the condensing boiler.
Heat exchanger
NOTICE: Damage to the coating of the heat
exchanger.
B Cleaning of the heat exchanger should not
be necessary until five years after the initial
commissioning.
B Only use a Bosch cleaning blade or Bosch
cleaning brush (Æ page 114).
B Only clean heat exchanger if soiling is
clearly visible.
Heatronic boiler control
In case of a component defect, a fault is shown on the
display.
The Heatronic boiler control monitors all safety and
control components.
NOTICE: The Heatronic boiler control can be
damaged by leaking water.
B Cover the Heatronic prior to working on
water filled components.
Notes on installation and operation
An overview of the faults can be found on
page 91.
• The following analytical tools are needed for service and
maintenance:
– Electronic flue gas analyzer for CO
gas temperature
– Pressure gauge 0 to 12 inches W.C. (0 to 30 mbar)
– pH Test strips
– Glycol tester of antifreeze is being used
• Special tools are not required.
• Approved lubricants are:
– For parts touched by water: Unisilkon L 641
(part-# 8 709 918 413 0)
– or fittings: HFt 1 v 5 (part-# 8 709 918 010 0).
B Use part-# 8 719 918 658 0 as heat conducting paste.
B Use only genuine Bosch spare parts.
B Request spare parts (Æ Section 18, page 99).
B Replace removed gaskets and O-rings with new ones.
14.1.6 Heat exchanger block inspection and cleaning
NOTICE: Damage to the coating of the heat
exchanger.
B Cleaning of the heat exchanger should not
be necessary until five years after the initial
commissioning.
B Only use a Bosch cleaning blade and Bosch
cleaning brush (Æ page 114).
B Only clean heat exchanger in case if soiling
is clearly visible.
B Remove the inspection cover (Æ page 12) and any
sheet metal insert below, if installed.
B Determine degree of soiling of the heat exchanger
through visual inspection.
If mechanical cleaning is required:
For cleaning the heat exchanger, Bosch offers the service
accessory kit which includes main heat exchanger gaskets,
the heat exchanger brush and heat exchanger cleaning
blade (part-# 7719001998).
B Remove the condensate trap (steps 1 and 2) and place
a suitable container underneath.
7 181 465 330-08.2R
Fig. 85 Burner
B Reinstall burner in reverse order, including a new gasket
mains power before performing any work.
Disconnect the emergency shutoff switch
or disengage the heating system circuit
breaker. Take measures to prevent
accidental reconnection.
WARNING: Danger of scalding!
Hot water can scald.
B Drain the appliance before working on
components that are water filled.
NOTICE: The Heatronic boiler control can be
damaged by leaking water.
B Cover the Heatronic prior to work on water
filled components.
The Heatronic boiler control monitors all safety and
control components.
If a fault arises during operation, an audible warning tone
sounds.
Press a button to mute the warning sound.
The display indicates a fault code (e.g. ) and the reset
button flashes.
If the reset button is flashing:
B Press the reset button and hold it until appears on
the display.
The appliance starts up again and the current supply
temperature is displayed.
If the reset button is not flashing:
B Switch the appliance OFF and ON again.
The appliance starts up again and the current supply
temperature is displayed.
An overview of the faults can be found on
page 91.
An overview of the status codes can be found
on page 89.
If the fault persists:
B Check the PCB and replace if required. Adjust the
service functions in accordance with the commissioning
report (Æ page 97).
The DHW tank temperature sensor was
recognized before the connection was
lost.
Code plug not detected.
Internal data error.
Fault in the burner controls.
Fan not running.
Outdoor temperature sensor not recognized.
B
Check temperature sensor and leads for interruptions or
shorts, and replace if defective.
B
Insert code plug correctly; replace if defective.
B
Check BUS communications wiring, replace if defective.
B
Check control, replace if defective.
B
Check DHW tank temperature sensor and connecting lead,
replace if defective.
B
Reset the boiler to the factory default settings (Æservice
function 8.E), reset the IPM 2
default settings and carry out the automatic system configuration.
B
Insert code plug correctly; replace if defective.
B
Reset boiler to factory default setting (Æservice function
8.E).
B
Reset boiler to factory to default setting (Æservice function
8.E).
B
Check fan leads and fan, replace if defective.
B
Check outdoor temperature sensor and leads for interruptions, replace if defective.
B
Verify the outdoor temperature sensor is connected to terminals A and F.
(if installed)
to the factory
d3
d5
Tab. 37 Faults shown on the display
Temperature high limit defective.
External guard has tripped.
Temperature limiter locked out.
External supply temperature sensor defective (low-loss header).
The external supply temperature sensor
was recognized on the BUS and then
reconnected to the appropriate terminal.
B
Check temperature sensor and leads for interruptions or
shorts, and replace if defective.
B
Temperature guard TB1 has tripped. Check if jumper across
8-9 or PR-P0 is missing.
B
Reset external temperature limiter (if installed).
B
Reset LWCO (if installed).
B
Check temperature sensor and leads for interruptions or
shorts, and replace if defective.
B
Check whether only one temperature sensor is connected;
otherwise remove second temperature sensor.
B
Reset the boiler to the factory default settings (Æservice
function 8.E), reset the IPM 2 (if installed) to the factory
default settings and carry out the automatic system configuration.
B Order spare parts by name and part number using the
spare parts list.
Spare parts | 99
Designation
Group 1 - Sheet metal
Group 2 - Burner/Heat exchanger
Group 3 - Gas valve
Group 4 - Pipes combi boiler ZWB..-3A
Group 5 - Pipes heating boiler ZBR..-3A
Group 6 - Control box
Group 7 - Hydraulic block combi boiler ZWB..-3A
Group 8 - Accessories for service/installation