Bosch WR400-1K, WR400-1 K P Installation Operation & Maintenance

Instantaneous gas water heater
Models WR400-1K…
· Installation
· Operation
· Maintenance
The Bosch instantaneous water heater is a high efficiency, space saving answer to your water heating needs. All Bosch instantaneous water heaters heat water only as required; no energy is lost maintaining a large volume of water at elevated temperatures as in tank-type storage wa­ter heaters.
Suitable for heating potable water only. Not approved for space heating purposes.
READ INSTRUCTIONS CAREFULLY BEFORE INSTALLING
NOTICE TO INSTALLER: Please leave this manual with
the owner or affix adjacent to appliance.
ASTRAVAN DISTRIBUTORS, LTD.
6 720 603 100 (03.05) AL
123 Charles Street North Vancouver, BC. V7H 1S1
Phone Canada: (604) 929-5488 Phone USA: (206) 860-8448 Web Site: www.astravan.com
WARNING: If the information in this manual is not followed exactly, a fire or explosion may result causing property damage, personal injury or death.
- Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance.
- WHAT TO DO IF YOU SMELL GAS
- Do not try to light any appliance
- Do not touch any electrical switch; do not use any phone in your building.
- Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions.
- If you cannot reach your gas supplier, call the fire department.
- Installation and service must be performed by a qualified installer, service agency or the gas supplier.
Note: In case of problems please contact your salesman or installer.
DIMENSIONS
Figure 1
Maximum hydrostatic water pressure – 1.03 Mpa (150 p.s.i.) Maximum recommend working pressure – 0.69 Mpa (100 p.s.i.) Minimum working pressure – 0.0138 Mpa (2 p.s.i.) at 2 Litres/min. (0.5 U.S. Gallons/min) free discharge
Minimum recommended inlet water pressure for use with showers 40 p.s.i.g.
Dimensions in Milimetres (inches)
Model dimensions A B D E F
WR400 - 1
Model Type of gas Altitude Input
WR400
WR400
milimetres
inches
Natural
Propane/LP 0.79 diam. 18
Natural
Propane/LP 0.79 diam. 18
460 755 130 diam. 740 542
18 1/8 29 3/4 5 1/8 diam. 29 1/8 21 11/32
Main Burner Orifices
Size, mm Qt.
standard 34.28 kW 1.20 diam. 18
(0 - 2,000 Pieds) (117,000Btu/hr)
high* 30.85 kW 1.20 diam. 18
(2,000 - 4,500 Pieds) ( 105,000Btu/hr)
* The high altitude ratings listed are Canadian Gas Association high altitude ratings and are only valid in Canada. In the
U.S., the National Fuel Gas Code, ANSI Z223.1/NFPA 54, recommends for high altitude installations above 2,000 feet, that the input rate be reduced 4% for each 1,000 feet above sea level. – See page 8.
2
FOREWORD
This design complies with CAN1-4.3-77 and ANS1Z21.10.3b 1994 as an instantaneous gas water heater. In addition the unit complies with CAN1-2.17- M80 use at high altitude,
2.000- 4.500 feet above sea level.
Installation, operation and maintenance information is provided in this manual . Installation and operation instructions should be thoroughly reviewed before proceeding with installation of the BOSCH instantaneous gas water heater.
The BOSCH instantaneous gas water heater is designed to operate on natural or propane gas; however make sure that gas on which heter is to operate is the same as specified on the heater’s model/rating plate.
In addition of these instructions, the water heater shall be installed in accordance with CAN1-B149 Installation Code (in Canada) or ANSI Z223-1/NFFA 54 National Fuel Gas Code (in U.S.) and/or local installation codes. These shall be carefully followed in all cases.
INSTALLATION INSTRUCTIONS
Note: Proper plumbing, venting, gas connections and an
adequate supply of combustion air are required for safe and reliable operation. Ability equivalent to that of a licensed tradesman in the field involved is required for installation and/or service of these water heaters.
LOCATION
Before installing the BOSCH instantaneous water heater consideration must be given to proper location. The location should be as close to a chimney or gas vent as practicable, in an area with an adequate air supply and as centralized with the piping system as possible. The heater should not be located in an area where it will be subject to freezing. The heater should be located in an area where leakage of the heater or its connections will not result in damage to the area adjacent to the heater or to lower floors of the structure.
Note: When such locations cannot be avoided, it is
recommended that a suitable drain pan, adequately drained, be installed under the water heater. The pan must no restrict combustion air flow.
AIR REQUIREMENTS
For safe operation, sufficient air combustion, ventilation and dilution of the flue gas must be available. An insufficient supply of air will result in a yellow luminous burner flame, causing carboning or sooting of the heat exchanger.
In order to prevent corrosion, make sure that the combustion air is kept free of aggressive substances. Substances that especially contribute to corrosion are halogenated hydrocarbons (e.g., chlorine and fluorine) which are contained in solvents, paint, adhesives, propellant gases, various household cleaners, etc. Take precautionary measures as necessary.
In unconfined spaces, in buildings of normal construction, infiltration normally is adequate to provide air for combustion, ventilation and dilution of the flue gases. However, a confined space must be provided with two permanent openings to provide combustion and ventilation air to the appliance. Each opening shall have a free area on one square inch per 1,000 BTU/Hr* of total input rating of all the appliances in the enclosure. One opening shall be within 12 inches of the top and one within 12 inches of the bottom of the enclosure.
*Special Note
When the WR400-1 is installed in a confined space of minimum size the openings described above must be increased in to a size of 1 ½ square inches per 1,000 BTU/ Hr. In order words, when the WR400-1 is installed in a minimum sized confined space the two openings that are to be made in the enclosure within 12 inches of the top and 12 inches of the bottom must each have a minimum free
area of (1 ½ “) x (117) = 175.5 square inches.
3
For either a confined or unconfined space in a building of tight construction with inadequate infiltration, air must be drawn from the outdoors or from spaces that freely communicate with the outdoors. Two permanent openings located as indicated above are to be provided as follows:
1. When communicating with outdoors directly or by
means of vertical ducts, each opening shall have a
free area of not less than one square inch per 4,000 BTU/Hr of total input of all appliances in the space.
2. When communicating with outdoors by means of
horizontal ducts, each opening shall have a free area
of not less than one square inch per 2,000 BTU/Hr of total input of all appliances in the space.
MOUNTING
The WR400-1 is design certified for mounting to a wall. The heater must not be installed on a carpeted wall. The heater must be mounted to the wall using appropriate anchoring materials.
Note: If wall is a stud wall sheathed with plasterboard it is recommended that support board(s), either 1 x 4’s or ½ “ (minimum) plywood first be attached across a pair of studs and then the heaters should be attached to the support boards. See Figure 2.
For detailed requirements see:
In Canada, CAN/CGA- B149 Installation Codes
In U.S.A., ANSI Z223.1/NFPA 54, National Fuel Gas
Code.
WARNING!
1. Flammable materials gasoline, pressurized containers, or any other items or articles that are potentially fire hazards must never be placed on or adjacent to the heater. The appliance area must be kept free of all combustible materials, gasoline and other flammable vapors and liquids.
2. Do not obstruct the flow of combustion and ventilation air to the appliance.
CLEARANCE
The WR400-1 is design certified for installation on a combustible wall and for installation in an alcove or closet with minimum clearances to combustible construction of 0mm from back, 102mm (4 inches) from sides, 305mm (12 inches) from top and bottom, and 102mm (4 inches) from front. A minimum of 305mm (12 inches) shall be allowed for maintenance of serviceable parts. Clearance from vent is dependent upon the clearance rating of the venting material used; type B-1 vent is approved for 1 inch clearance, B-2 vent for 2 inch, etc.
WALL STUDS
1”X4” SUPPORT BOARDS
Figure 2
Expansion and contraction of piping due to changing water temperature in the pipes imparts movement to the heater which, if mounted directly to a brittle, friable board, such as plasterboard, can cause failure of mounting.
THIS APPLIANCE MUST BE INSTALLED IN ACCORDANCE WITH THE NATIONAL FUEL GAS CODE ANSI Z223.1/ NFPA 54 IN U.S.A OR CAN/CGA- B149 INSTALLATION CODES IN CANADA. LOCAL CODES AND/OR REQUIREMENTS OF THE AUTHORITY HAVING JURISDICTION MUST BE FOLLOWED.
4
DRIP TRAY
If the water heater is being mounted above a floor of combustible construction the drip tray ( shipped loose in the carton with the water heater) must be attached to the bottom of the front cover of the water heater at the time of installation. The drip tray should be attached to the front cover, using screws provided, as shown in Figure 3.
Failure to use drip tray when installing unit above a floor of combustible construction will cause an unsafe condition and possible fire and will be in violation of A.G.A. and C.G.A
certification of the unit.
For high altitude use the adaptor must be installed as shown in Figure 4, without alteration, before connecting the six inch flue to the unit. The adaptor must be secured to the draft diverter outlet with a minimum of two screws.
Also, in Canada, the gas pressure regulator supplied with the water heater is factory preset to deliver gas to the water heater at the proper pressure setting for high altitude operation, see PRESSURE REGULATION section of this manual.
WARNING!
Failure to increase the vent size of the WR400-1 to six inches and/or to assure that manifold pressure is set to proper value listed on rating plate for applications at altitudes in range of 2,000 to 4,500 ft. above sea level will cause unsafe venting, asphyxiation, and voids C.G.A. Certification.
WATER CONNECTIONS
DRIP TRAY
Figure 3
VENTING
The BOSCH instantaneous water heaters have built-in draft diverters and are designed for indoor installation only. The draft diverter outlet must be connected to a clear, unobstracted vent of the same size, or larger, refer to:
In Canada, CAN/CGA- B149 Installation Codes for detailed requirements.
In U.S.A., ANSI Z223.1/NFPA 54, National Fuel Gas Code for detailed requirements.
The flue connection for the WR400-1 is 130 mm (5 inches); however, in Canada for installations at high altitude (2,000­4,500 ft. above sea level) a six inch (6”) flue is required.
5” x 6” adaptor used on high altitude model WR 400 only
The BOSCH instantaneous water heaters are provided with two S- bend water connectors/adaptors that must be connected to inlet and outlet connections on water valve assembly, see Figure 1 and Figure 5, below.
Water valve and S-bends, top view
Figure 5
The purpose of the S- bend water connectors/ adaptors is to provide threaded water connections that meet standards used in North America, ANSI Standard Taper Pipe Thread (1/2 “ NPT). The cold water supply should be connected to S- bend attached to inlet of water valve and the hot water connection should be made to S- bend attached to the outlet of water valve.
Figure 4
If plastic piping is to be used, a 1.5 meter (approx. 5 feet) length of metal piping must be attached to both the cold water inlet and hot water outleet of the water heater.
Note: A shut-off valve should be placed in the cold water
supply line to the heater to facilitate servicing the heater.
5
RELIEF VALVE
The listed pressure relief valve supplied must be installed near the hot water outlet at time of installation of the heater. No valve is to be placed between the relief valve and the heater. A drain line must be connected to the relief valve to direct discharge to a safe location. Do not install reducing coupling or any other restriction in the discharge line. The discharge line must be installed so as to allow complete drainage of both the valve and the line. See figure 6.
Figure 6
Check to make sure that the gas listed on the rating plate is the same as the gas listed on the pressure regulator. See PRESSURE REGULATION section of this manual for information regarding gas pressure settings.
Note: Before attaching the gas supply line, be sure that all
gas pipe is clean on the inside. To trap any dirt or foreign material in the gas supply line, a drip leg must be readily accessible and not subject to freezing conditions. Install in accordance with the recommendations of the serving gas supplier.
Joint compounds (pipe dope) shall be applied sparingly and only to the male threads of pipe joints. Do not apply compound to the first two threads. The joint compound used must be resistant to the action of liquified petroleum gases.
Before placing water heater in operation check for gas leakage. Soap and water solution, or other material acceptable for this purpose, shall be used in locating gas leaks. Matches, candles, lighters, or other ignition sources shall not be used for this purpose.
GAS CONNECTIONS
Before connecting the gas supply to the heater, check heater’s model/rating plate to make sure that the gas on which heater is to operate is the same as specified on the model/rating plate.
The WR400-1 instantaneous water heaters are supplied with a gas pressure regulator that must be installed on the heater before attaching the gas supply line. See figure 7. Failure to install the gas pressure regulator as shown in figure 7 will be a violation of A.G.A. and C.G.A. certification of the unit.
BOSCH water heaters are shipped from the factory with the gas pressure regulators preset for the gas shown on the rating plate to the correct pressure:
In Canada, for high altitude operation;
In U.S.A., for standard altitude operation unless
specifically marked as a high altitude unit.
WARNING!
The heater and its individual shutoff valve must be disconnected from the gas supply piping system during any pressure testing of that system at test pressures in excess of 3.45 kPa (1/2 psig).
The water heater must be isolated from the gas supply piping system by closing its individual manual shutoff valve during any pressure testing of the gas supply piping system at test pressures equal to or less than 3.45 kPa (1/2 psig).
The water heater, including the pressure regulator provided with in, must not be operated at gas supply pressures in excess of 3.45 kPa (1/2 psig). If overpressure has occurred such as through improper testing of the gas lines or emergency malfunction of the supply system, the gas valve and regulator must be checked for safe operation. Make sure that the outside vent valves are protected against blockage. These are part of the gas supply system, not the water heater. Vent blockage may occur during ice storms.
Figure 7
6
GAS INLET PIPE
PRESSURE TAP
PRESSURE REGULATOR
OPERATING INSTRUCTIONS
WARNING!
If the water heater has been damaged or exposed to fire or sooting, or if any part has been underwater, do not use. Immediately call a qualified service technician to inspect the appliance and to replace any part of the control system and any gas control which has been underwater and to clean the heat exchanger assembly and water valve.
FILLING
Before proceeding with operation of the water heater make sure that the system is filled with water:
Make sure drain is closed. See figure 8, below.
Open a nearby hot water faucet to permit the water to
fill the heater and piping.
Close the hot water faucet after the water flows freely and all air has escaped from the system.
The water heater is now ready to be lit.
LIGHTING INSTRUCTIONS
1. STOP! Read the safety information above on this plate.
2. The gas valve should be turned off by sliding the gas valve button to the far left, under the “OFF” mark, .
3. Wait five (5) minutes to clear out any gas. If you then smell gas, STOP! Follow “B” in the safety information above on this plate. If you don’t smell gas, go to next step.
4. The pilot burner is located behind the peephole located in the front center of the jacket directly below this instruction plate.
5. Slide the gas valve button to the right, under “PILOT” MARK, .
6. Fully depress the gas valve button and light the pilot by pressing the “PILOT IGNITER” button, . This may have to be repeated.
7. Observe the pilot flame through the peephole. The gas valve button should be held down at least 10 seconds with pilot burning. When the gas valve button is released the pilot should continue to burn:
If the gas valve button does not pop up when released stop and immediately call your service technician or gas supplier.
If the pilot does not stay lit, repeat steps 1 through 7.
If the pilot will not stay lit after several tries, slide the
gas valve button to the left under the “OFF” mark and call your service technician or gas supplier.
Figure 8
SERVICE HINT
The strainer (screen) in the water valve, located in the inlet of the water valve, may require occasional cleaning due to foreign material in the water supply. This will restrict the flow of water and may effect heater operation and prolong filling time. To inspect the strainer, close the cold water supply valve ahead of the heater, disconnect the S- bend from the inlet of the water valve and remove strainer from inlet. Clean if required, replace strainer in inlet to the water valve, reconnect S- bend and turn on water supply.
Light the water heater in accordance with the instructions on the Lighting and Operating Plate on the water heater.
For your convenience, the instructions are repeated below:
8. Slide gas valve button to the far right, under the “ON” mark . The heater will now fire when water is drawn at a rate greater than the threshold flow rate (see manual*).
Note: If main burner should fail to ignite, make sure pilot is burning. If not, repeat lighting procedure steps 1 through 8.
TO TURN OFF GAS TO APPLIANCE
1. Slide the gas valve button to the far left, off position, under the “OFF” mark, and close the heater’s
individual shutoff valve.
* = see TEMPERATURE REGULATION section.
7
PRESSURE REGULATION
The pressure regulator supplied with the water heater is adjusted to operate on the gas specified on the rating plate, and:
· In Canada, is factory preset to deliver gas at the high altitude pressure setting listed on the rating plate and as shown below;
· In the U.S.A., is factory preset to deliver gas at the standard altitude setting listed on the rating plate and as shown below.
The pressure setting of the gas pressure regulator should be checked at installation to assure that the setting is correct for the gas being used and the altitude at which the appliance is installed. See rating plate of the unit, or Table 1, below, for proper setting.
In Canada, for a heater being installed at standard altitude (0- 2,000 ft. above sea level), the manifold pressure should be reset at installation to value shown on the rating plate, or Table 1, below, for standard altitude.
Your appliance dealer and/or your local gas supplier should be consulted in regard to any high altitude installation. If filed adjustment is required it should be performed by a quali­fied serviceman experienced in such work.
TEMPERATURE REGULATION
The BOSCH WR400-1 is equipped with a modulating gas valve which adjusts the flow of gas to the main burner in proportion to the water flow rate. Within its heating capac­ity the WR400-1 attempts to maintain burner in proportion to the water flow rate. Within its heating capacity the WR400-1 attempts to maintain the set temperature rise across the heater. This temperature rise can be set in range of 25ºC –to- 50ºC (45º F – to – 90ºF), by means of the water flow selector. See figure 10. With the gas control button slid all the way to the right under the “ON” position mark @ when the water flow selector is turned to the right hand stop the water flow selector is turned to the right hand stop the water heater is set for 50ºC (90ºF) temperature rise; when the water flow selector is set to the left hand
stop it is set for 25ºC (45ºF) temperature rise.
PRESSURE TAP
PRESSURE REGULATOR
Figure 9
The gas pressure specified below refer to flow pressure taken at the pressure tap in the gas inlet pipe (just above the pressure regulator), see figure 9 while the heater is operating at full input.
Type Pressure tap Altitude
of gas kPa inches W.C.
Natural 1.41 5.7 standard
Propane 2.61 10.5 (0 - 2,000 ft)
Natural 1.14 4.6 high*
Propane 2.09 8.4 (2,000 - 4,500 ft)
* Note: The high altitude ratings listed are Canadien Gas
Association high altitude ratings for the appliances and are only valid in Canada. In the U.S.A. the National Fuel Gas Code, ANSI Z223.1/NFPA 54, recommends for high altitude installations, above 2,000 feet, that the input rate be reduced 4% for each 1,000 feet above sea level.
GAS CONTROL SLIDE
WATER FLOW SELECTOR
Figure 10
With the water flow selector turned to its right hand stop position (50ºC rise setting) and with an inlet water temperature of 10ºC (50ºF) the outlet water temperature will be maintained at approximately 60ºC (140ºF) in the water flow rate range of approximately 2 litres/min. (0.5 U.S.gals/ min) to 8 litres /min. (2.1 U.S. gals/min.).
The minimum flow rate for operation, the “Threshold Flow Rate” referred to in the lighting instructions is 2 litres/min (0.5 U.S. gals./min). If the water flow rate is below this level the main burner will not fire. If the flow rate excess 8 litres/ min (2.1 U.S. gals/min.) the temperature rise across the heater will decrease in proportion to the rate above this temperature.
HIGH TEMPERATURE LIMIT SWITCH
The BOSCH WR series instantaneous gas water heaters are equipped with a high temperature limit switch with a set point of approximately 90ºC (194ºF). If the water temperature at the sensing points exceeds the set point the switch will open, interrupting the safety circuit and stopping gas flow to the pilot and main burner.
Outage as the result of high limit operation indicates that the heater is not functioning properly. The heater should be checked by a qualified serviceman and the reason for the malfunction is corrected. To relight the pilot, follow instructions provided on the unit.
8
Loading...
+ 16 hidden pages