Praesideo 3.5 | Installation and User Instructionsen | 2
Intentionally left blank.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructionsen | 3
Disclaimer
Although every effort has been made to ensure the
information and data contained in these Installation and
User Instructions is correct, no rights can be derived
from the contents.
Bosch Security Systems disclaim all warranties with
regard to the information provided in these instructions.
In no event shall Bosch Security Systems be liable for
any special, indirect or consequential damages
whatsoever resulting from loss of use, data or profits,
whether in action of contract, negligence or other
tortious action, arising out of or in connection with the
use of the information provided in these Installation and
User Instructions.
Important Safeguards
Prior to installing or operating this product, always read
the Important Safety Instructions which are available as
a separate document and are packed with all units that
can be connected to the mains.
FCC Requirements Class A
All Praesideo devices are verified to comply according
47 CFR subpart 15 B, Unintentional Radiators. Class A
Digital device, peripherals and external switching power
supplies.
NOTE:
This equipment has been tested and found to comply with
the limits for a Class A digital device, pursuant to Part 15
of the FCC Rules. These limits are designed to provide
reasonable protection against harmful interference when
the equipment is operated in a commercial environment.
This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in
accordance with the instruction manual, may cause
harmful interference to radio communications. Operation
of this equipment in a residential area is likely to cause
harmful interference in which case the user will be
required to correct the interference at his own expense.
FCC Notice
This device complies with Part 15 of the FCC Rules.
Operation is subject to the following two conditions:
1. This device may not cause harmful interference, and
2. This device must accept any interference received,
including interference that may cause undesired
operation.
Modifications
Any modifications made to this device that are not
approved by the manufacturer may void the authority
granted to the user by the FCC to operate this
equipment.
Canada
This Class A digital apparatus complies with Canadian
ICES-003.
Cet appareil numérique de la classe A est conforme à la
norme NMB-003 du Canada.
(Pb)
(Hg)(Cd)
(Cr6+)
(PBB's) (PBDE's)
X O O O O O
X O X X X X
X O X X O O
O O O O X X
X O X X O O
X O X X O O
O:SJ/T11363-2006.
X:SJ/T11363-2006.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructionsen | 4
Intentionally left blank.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | 0 | Table of Contentsen | 5
Important Safeguards..........................................................................................................................................................3
FCC Requirements Class A ..............................................................................................................................................3
Table of Contents..................................................................................................................................................................5
Praesideo on board of ships........................................................................................................................................... 71
Part 2 - Introduction .......................................................................................................................................................... 73
1 About this manual .......................................................................................................................................................................... 75
1.1Purpose of this manual ....................................................................................................................................................... 75
2 System overview ............................................................................................................................................................................ 76
2.2User-friendly software control ........................................................................................................................................... 76
2.4Distributed control ............................................................................................................................................................... 76
2.5Combination of functions ................................................................................................................................................... 76
2.9High system flexibility .......................................................................................................................................................... 77
Part 3 - Control Equipment.............................................................................................................................................. 81
5.5Using the configuration menu ........................................................................................................................................... 92
5.6Configuration and operation .............................................................................................................................................. 96
5.7Technical Data ....................................................................................................................................................................102
6.5Using the configuration menu .........................................................................................................................................111
6.6Configuration and operation ............................................................................................................................................114
6.7Technical data .....................................................................................................................................................................116
7.2Controls and connectors ..................................................................................................................................................120
7.7Using the configuration menu .........................................................................................................................................124
7.8Configuration and operation ............................................................................................................................................127
7.9Technical data .....................................................................................................................................................................129
Part 4 - Amplifiers ............................................................................................................................................................ 131
8 Power Amplifiers ..........................................................................................................................................................................133
8.2Controls, connectors and indicators .............................................................................................................................134
8.4Fan control ...........................................................................................................................................................................144
8.6Using the configuration menu .........................................................................................................................................146
8.7Configuration and operation ............................................................................................................................................149
8.8Technical data .....................................................................................................................................................................151
9 PRS-16MCI Multi Channel Interface ......................................................................................................................................157
9.2Controls, connections and indicators ............................................................................................................................158
9.5Configuration and operation ............................................................................................................................................162
9.6Technical data .....................................................................................................................................................................164
10.4 Fan control ...........................................................................................................................................................................175
10.7 Technical data .....................................................................................................................................................................178
11 Single loudspeaker line supervision ........................................................................................................................................182
11.4 Technical data supervision-master .................................................................................................................................187
11.5 Technical data supervision-slave ....................................................................................................................................188
12 Multiple loudspeaker line supervision .....................................................................................................................................189
12.5 Technical data supervision control board .....................................................................................................................195
12.6 Technical data loudspeaker supervision board ...........................................................................................................196
12.7 Technical data EOL supervision board .........................................................................................................................197
14.3 Technical data .....................................................................................................................................................................199
Part 5 - Call Stations .......................................................................................................................................................201
15 LBB4430/00 Call Station Basic ..............................................................................................................................................203
15.6 Technical data .....................................................................................................................................................................207
16 LBB4432/00 Call Station Keypad ..........................................................................................................................................208
16.6 Technical data .....................................................................................................................................................................211
17.7 Technical data .....................................................................................................................................................................215
18 LBB4433/00 Call Station Kit ...................................................................................................................................................216
18.4 Technical Data ....................................................................................................................................................................225
19 LBB4434/00 Call Station Keypad Kit ....................................................................................................................................226
19.4 Technical data .....................................................................................................................................................................232
20 PRS-CSR Remote Call Station ................................................................................................................................................233
20.6 Technical data .....................................................................................................................................................................238
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | 0 | Table of Contentsen | 8
21 PRS-CSRK Remote Call Station Kit .......................................................................................................................................240
21.4 Technical Data ....................................................................................................................................................................249
22 PRS-CSI Call Station Interface ................................................................................................................................................250
22.6 Technical data .....................................................................................................................................................................255
23.2 Controls and indicators ....................................................................................................................................................258
23.6 Technical data .....................................................................................................................................................................259
25.2 Controls and connectors ..................................................................................................................................................263
25.6 Technical data .....................................................................................................................................................................268
26.5 Technical data .....................................................................................................................................................................275
27.5 Technical data .....................................................................................................................................................................277
Part 7 - System Hardware Installation .......................................................................................................................293
31.2 System bus ..........................................................................................................................................................................295
31.4 Maximum distance .............................................................................................................................................................296
31.5 Maximum cable length ......................................................................................................................................................297
31.6 Bending and coiling ...........................................................................................................................................................298
32.2 Basic system .......................................................................................................................................................................299
32.8 IP Addresses .......................................................................................................................................................................302
32.9 Connecting an alarm buzzer ............................................................................................................................................302
33 Power Consumption ...................................................................................................................................................................304
33.2 Power consumption ...........................................................................................................................................................304
33.4 Power sources ....................................................................................................................................................................305
34.1 Clean air inlets ....................................................................................................................................................................307
35.2 Starting the DVD ................................................................................................................................................................311
36.2 Installation on PC ...............................................................................................................................................................311
36.4 Upgrade system software ................................................................................................................................................313
Part 9 - System Configuration ......................................................................................................................................321
40.2 Starting and logging on ....................................................................................................................................................323
41 User management .......................................................................................................................................................................328
41.3 Add a user ...........................................................................................................................................................................329
41.4 Delete a user .......................................................................................................................................................................330
42 System definition .........................................................................................................................................................................331
42.2 Serial numbers ....................................................................................................................................................................331
42.4 Power amplifier ...................................................................................................................................................................333
42.5 Call station ...........................................................................................................................................................................335
42.10 Multi Channel Interface ....................................................................................................................................................338
43.3 Power amplifier ...................................................................................................................................................................346
43.4 Call station ...........................................................................................................................................................................352
43.8 Multi Channel Interface .....................................................................................................................................................363
44 System wide settings .................................................................................................................................................................368
44.2 Recorded messages .........................................................................................................................................................368
44.4 System settings ..................................................................................................................................................................371
45 Zone & amplifier ...........................................................................................................................................................................373
45.2 Zone configuration .............................................................................................................................................................373
45.3 Zone Grouping ...................................................................................................................................................................377
49 Automatic volume control ..........................................................................................................................................................404
50.3 Number of nodes ................................................................................................................................................................407
50.6 Device information .............................................................................................................................................................408
Part 10 - Events................................................................................................................................................................. 411
51.2 General events ....................................................................................................................................................................413
52 General events list .......................................................................................................................................................................415
53 Call events list ..............................................................................................................................................................................418
54 Fault events list ............................................................................................................................................................................419
Part 11 - Optional Software ..........................................................................................................................................433
55.10 CobraNet Control and Configuration ............................................................................................................................441
56 Logging Server .............................................................................................................................................................................446
56.5 Main window .......................................................................................................................................................................448
58 PC Call Server .............................................................................................................................................................................459
59 PC Call Server Configuration Client .......................................................................................................................................461
60 PC Call Station Client ................................................................................................................................................................474
60.6 User Interface ......................................................................................................................................................................475
61 PC Telephone Interface Client .................................................................................................................................................480
61.7 Voice response menu ........................................................................................................................................................481
62 Open Interface .............................................................................................................................................................................486
Part 12 - Appendices ....................................................................................................................................................... 487
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | Emergency Sound Systemsen | 13
Emergency Sound Systems
Bosch Security Systems has made a great effort for the design and manufacturing of the components and also
supplies all documentation that enables the assembly of a safe and high quality emergency unit in accordance with
EN60849:1998, EN54-16:2008 and ISO7240-16:2007. Bosch Security Systems has made up this list of requirements,
based on the standard, which needs to be filled in and subsequently signed off by both parties. The signed paper has
the nature of a certificate and can have significant meaning in the case of a legal investigation of the liability issue for
personal injuries.
•The safety of the system in accordance with EN60849:1998, EN54-16:2008 and
ISO7240-16:2007 in an alarm and emergency application does not only depend on component safety, but also
highly on the installation engineer and the operator. For example, the sound pressure level of the system depends
on the installation. Moreover, the system should only be installed and operated by qualified personnel.
•Modifications of the system should only be executed by authorized persons in accordance with the safety
concept and need to be registered in the system documentation.
•If third party components (not delivered by Bosch Security Systems) are added to the minimal configuration of
Praesideo, then the EN60849:1998, EN54-16:2008 and ISO7240-16:2007 certification becomes expired.
•Only use Power Supply Equipment that is compliant to the current standards and legislation in combination with
the Praesideo system. Within Europe the Power Supply Equipment shall be EN54-4 compliant.
•The end-user must maintain a journal for the system.
•In case continuous event logging (beyond the possibilities and capacity provided by the Network Controller) is
required, the end-user/installer must use the Praesideo system in combination with a logging PC. In that case the
logging PC is considered as a basic element of the system.
•The installer is responsible for security measures to prevent improper use of the system via the Internet and local
wired or wireless networks.
•Bosch Security Systems refuses any liability for damage that might result from non-observance of these
instructions.
Herewith the undersigned states that he/she has processed for him/her applicable requirements, as specified in this
document, in an adequate way and has confirmed this fact by signing the rightmost column of each applicable
requirement.
Installer
Name:
Signature:
Date:
Place:
End-user
Name:
Signature:
Date:
Place:
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | Emergency Sound Systemsen | 14
List of authorized end-users
NameName
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998en | 15
EN60849: 1998 compliancy checklist
EN60849 - 4. General system requirements
EN60849 - 4.1 Principal features
RequirementComplianceSignature
A sound system for emergency purposes shall permit
the broadcasting of intelligible information of measures
to be taken for the protection of lives within one or more
specified areas.
The following criteria shall be fulfilled:
a When any alarm is detected, the system shall
immediately disable any functions not connected
with its emergency role (such as paging, music or
general pre-recorded announcements being
broadcast to the loudspeaker zones requiring
emergency broadcasts).
b Unless damaged as a result of the emergency, the
system shall be available for operation at all times
(or as required by the system specification).
c The system shall be capable of broadcasting within
10 s after primary or secondary power is applied.
d Except during the condition described in 4.1c), the
system shall be capable of broadcasting a first
attention-drawing signal within 3 s of being placed
in an emergency mode by the operator, or
automatically on receipt of a signal from a fire or
other detection system. In the latter case, the
period of 3 s includes the reaction time of the
detection system from the time the emergency is
first detected, to commanding the alarm broadcast.
e The system shall be able to broadcast attention-
drawing signals and speech messages to one or
more areas simultaneously. There shall be at least
one appropriate attention-drawing signal
alternating with one or more speech messages for
this purpose.
fAt any time the system operator shall be able to
receive, by means of a monitoring system,
indications of the correct functioning or otherwise
of the relevant parts of the emergency system (see
also 5.2 and 5.3).
g Failure of a single amplifier or loudspeaker circuit
shall not result in total loss of coverage in the
loudspeaker zone served.
NOTE 1 - The monitoring system specified
in 4.1f) should indicate the failure of an amplifier or of a
loudspeaker circuit.
NOTE 2 - Particularly in small buildings, it may not be
necessary to install two separate loudspeaker circuits
in one loudspeaker zone. A decision on this matter
may be subject to local regulations.
h An attention-drawing signal shall precede the first
message for 4 s to 10 s. Successive signals and
messages shall then continue until either changed
in accordance with the evacuation procedure, or
manually silenced. The interval between successive
messages shall not exceed 30 s and attentiondrawing signals shall be broadcast whenever
periods of silence might otherwise exceed 10 s.
Where more than one attention-drawing signal is
used, such as those used for different types of
emergency, each signal shall be clearly
distinguishable in character.
Compliant, if properly installed. Responsibility of the
installer.
Compliant.
Compliant, if installed with:
• Redundant ring network.
• Spare Power Amplifiers.
• Multiple loudspeaker circuits per zone and one
loudspeaker circuit per amplifier channel.
• Battery back-up / UPS back-up.
• Emergency Call Station in failsafe layout or
Emergency Call Station Kit in the failsafe layout.
Responsibility of the installer.
Compliant, if installed with failsafe layout. Responsibility
of the installer.
Compliant.
Compliant, if attention-drawing signal is part of the prerecorded message. Responsibility of the installer.
Compliant, indicated by call stations and/or by a control
output of the Network Controller (if properly installed).
Fault is also displayed by the Network Controller and
the Logging Viewer (optional).
Compliant if installed with:
•Spare Power Amplifiers.
•Multiple loudspeaker circuits per zone and one
loudspeaker circuit per amplifier channel.
•Line Supervision set.
Responsibility of the installer.
Compliant, if attention-drawing signal is part of the prerecorded message and call macro has been configured
properly. Responsibility of the installer.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998en | 16
RequirementComplianceSignature
iAll messages shall be clear, short, unambiguous
and as far as practicable, pre-planned.
Where pre-recorded messages are used they shall
be held in a non-volatile form, preferably in a solidstate store, and be continuously monitored for
availability.
The system design shall make it inherently
impossible for an external source to corrupt or
derange the store or its contents.
NOTE - On grounds of reliability, it is preferable not
to use storage media depending on mechanical
devices.
jThe language(s) used shall be specified by the
purchaser.
k The system shall be capable of being divided into
emergency loudspeaker zones if required by the
evacuation procedure. Such zones need not be the
same as other zones, for example emergency
detection zones or non-emergency loudspeaker
zones.
lIn determining loudspeaker zones, the following
criteria shall apply:
1 the intelligibility of messages broadcast in one
zone shall not be reduced below the
requirement of 5.1 by the broadcasting of
messages in other zones or from more than one
source.
2 no emergency detection zone shall contain
more than one emergency loudspeaker zone.
For non-emergency use, a loudspeaker zone
may be subdivided.
m A secondary power source shall be available
(see 5.6).
Responsibility of the installer.
First 128 MB of compact flash card is continuously
monitored, which is equivalent to the first 25 minutes of
audio.
Compliant.
Storage medium is a compact flash card. Proper
installation of the compact flash card is the
responsibility of the installer.
Responsibility of the installer.
Compliant, if properly installed. Responsibility of the
installer.
Compliant, if properly installed. Responsibility of the
installer.
Compliant, if properly installed. Responsibility of the
installer.
Compliant, if properly installed. Responsibility of the
installer.
EN60849 - 4.2 Responsible person
RequirementComplianceSignature
The person or body, having control of the premises
shall nominate a "responsible person", identified by
name or job title, who shall be responsible for ensuring
that the system is properly maintained and repaired so
as to continue to operate as specified.
Responsibility of the person or body having control of
the premises. Action to be taken care of by the installer.
EN60849 - 4.3 Priorities
EN60849 - 4.3.1 Classification of priorities
RequirementComplianceSignature
It is necessary to decide upon an order of priority for
the message distribution based upon:
a Any automatic programmed response.Compliant, if properly installed. Responsibility of the
b The perceived risk to occupants, which may require
manual override of the programmed response.
Events shall be given a level of priority according to
their urgency. The following primary levels are
recommended but there may be advantages in adding
further subgroups, depending on the operational
strategies of the site:
a Evacuate - potentially life-threatening situation
needing immediate evacuation.
b Alert - dangerous situation nearby requiring
warning of pending evacuation.
c Non-emergency - operational messages, e.g.
system test, etc.
installer.
Compliant, if properly installed. Responsibility of the
installer.
Compliant, if properly installed. Responsibility of the
installer.
Compliant, if properly installed. Responsibility of the
installer.
Compliant, if properly installed. Responsibility of the
installer.
Compliant, if properly installed. Responsibility of the
installer.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998en | 17
RequirementComplianceSignature
The use of these levels in descending order of priority
will ensure that appropriate alarm signals and
messages are provided first to the zones immediately at
risk.
Compliant, if properly installed. Responsibility of the
installer.
EN60849 - 4.3.2 Operational priorities
RequirementComplianceSignature
If the voice alarm system is capable of operation in fully
automatic mode, a facility shall always be available to
control:
a The type of pre-recorded message being
broadcast.
b The distribution of messages to different zones.Compliant.
c Real-time instructions or information to occupants
via the emergency microphone (if any).
Means shall be provided for manual intervention to
override any automatically programmed functions. This
shall apply both to the nature of the message being
broadcast and to the distribution paths of the message.
Thus, manual controls shall be provided at the central
control point (and also at specified remote control
points) to allow:
a Starting or stopping of pre-recorded alarm
messages.
b Selection of appropriate pre-recorded alarm
messages.
c Switching on or off, of selected loudspeaker zones.Compliant, if properly installed. Manual selection of
d Broadcasting of live messages via the emergency
microphone (if any).
NOTE - The above controls may form part of an
emergency detection control panel.
The emergency control microphone shall have the
highest level of priority for access to the voice alarm
system, with provision to allow it to override all other
broadcasts.
Compliant, if properly installed:
•Input contact configured to start a call with a prerecorded message.
•Running message can be overridden by higher
priority manually started messages.
The numeric keypad PRS-CSNKP should not be used
for zone selection for emergency purposes in a system
that has to comply to EN60849:1998, because the
LCD does not have a self-test function to check for
correct operation.
Compliant, if properly installed. Manual selection of
loudspeaker zones is supported. Adding or removing
zones from a running call is supported.
Compliant, if properly installed. Running message can
be overridden by higher priority manually started
messages.
Compliant, if properly installed. Manual selection of prerecorded alarm messages is supported.
loudspeaker zones is supported. Adding or removing
zones from a running call is supported.
Compliant, if properly installed. Live calls from an
emergency call station are supported.
Compliant, if properly installed.
The PC call station (PRS-CSC) should not be used to
make emergency announcements in a system that has
to comply to EN60849:1998, because a PC does not
comply to this standard for such use.
EN60849 - 4.4 Safety requirements
RequirementComplianceSignature
The safety requirements applying to emergency sound
systems are given in IEC60065 or other appropriate
IEC safety standards.
The mechanical construction of the system shall be
such that under the influence of internally generated
heat, explosion or implosion, however caused, no part
shall cause injury to any person.
Where any part of the system is installed in areas with
hazardous or explosive atmospheres, the relevant
safety requirements of IEC60079 shall be met.
Compliant. Praesideo complies to IEC60065.
Compliant.
Responsibility of the installer. The Praesideo equipment
itself does not comply to IEC60079.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998en | 18
Unless otherwise specified, the following requirement
shall be satisfied:
The speech intelligibility over all of an area of coverage
(see 3.1) shall be greater than or equal to 0,7 on the
common intelligibility scale (CIS). See annexes A and B
for the conversion between CIS and other scales of
intelligibility. The noise level (see B.5) at the time of
measurement (but in the absence of the test signal)
and the test signal level shall be stated with the test
result.
NOTE - If the persons who are required to understand
the messages are, or will be, reasonably familiar with
them through regular system tests, the effective
intelligibility tends to increase by approximately 0,05 on
the CIS if the intelligibility is in the range 0,6 to 0,7. This
may apply, for example, in an office building. However,
in a sports ground, for example, most of the messages
are likely to be relatively unfamiliar to the majority of
persons present, and no relaxation of the above
requirement should be considered.
The system specification may exclude from the area of
coverage, defined areas rarely or never occupied by
people.
Responsibility of the installer.
Responsibility of the installer.
EN60849 - 5.2 Automatic status indication
RequirementComplianceSignature
A clear indication shall automatically be given at the
designated control locations of:
a System availability.Compliant. Indication on call stations if properly
b Power supply availability.Compliant. Indication on call stations if properly
c Any fault condition.Any fault is indicated by a control output of the Network
d (For systems having numerous loudspeaker zones),
which loudspeaker zones are selected and the
mode of operation of each zone, i.e. "evacuate" or
"alert" and pre-selection of emergency microphone.
Where different alarm messages are provided,
which are dependent on the evacuation
requirements, indication of which message is being
broadcast and into which zone, shall be displayed
by a suitable method. This information shall be
continuously displayed and kept up to date.
installed.
installed.
Controller, if properly installed.
Compliant.
EN60849 - 5.3 Automatic fault monitoring
RequirementComplianceSignature
A clear indication shall automatically be given, at
specified locations, e.g. at main equipment locations,
of:
a Short-circuit or disconnection or failure of the
primary power source.
b Short-circuit or disconnection or failure of the
standby power source.
c Short-circuit or disconnection or failure of any
battery charging equipment associated with the
primary or standby power sources.
d Rupture of any fuse or operation of circuit breaker,
isolator or protective device that may prevent an
emergency broadcast.
Compliant, if properly installed. Responsibility of the
installer. (UPS should be monitored via control input.)
Compliant, if properly installed. Responsibility of the
installer. (UPS should be monitored via control input.)
Responsibility of the installer. Supervision of third party
charging equipment is via control inputs.
Compliant. Fault is indicated by a control output of the
Network Controller, if properly installed. Fault is also
displayed by the Network Controller and the Logging
Viewer (optional).
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998en | 19
RequirementComplianceSignature
e Failure of microphone, including capsule voice coil,
pre-amplifier and essential wiring to the rest of the
system.
fFailure of critical signal paths through the
amplification chain, with individual amplifiers
separately identified.
g Amplifiers or critical modules missing.Compliant. Fault is indicated by a control output of the
h Failure of any standby amplifier.Compliant. Fault is indicated by a control output of the
iFailure of emergency signal generators, including
emergency pre-recorded message stores.
jFailure of any loudspeaker circuit (open- and short-
circuit faults).
k Short-circuit or disconnection of visual alarm
devices.
lFailure of a processor to correctly execute its
software program.
m Detection of any error during memory checking.Compliant. Program memory is checked on correctness
n Cessation of any scanning or interrogation
process.
o Failure of the interconnecting data or voice
communication links between parts of a distributed
system.
In addition to individual fault identification at these
locations, a common sounder shall sound for a
minimum of 0,5 s every 5 s. A fault shall cause the
sounder to operate in a latched mode and a visual
indicator to light, either steadily, or in a flashing mode.
Manual acceptance and reset switching shall be
included. When accepted, the sounder shall be
silenced and the indicator shall change to (or remain in)
steady illumination. The occurrence of a further fault
condition shall reactivate the sounder and the visual
indicator. When all the faults have been cleared, the
indicator shall be switched off, either automatically or
by operating a reset switch.
The fault indication should be given within
100 s of the occurrence of the fault, regardless of
whether the voice alarm system is being used for nonemergency purposes, such as the transmission of
background music.
Compliant. Fault is indicated by a control output of the
Network Controller, if properly installed. Fault is also
displayed by the Network Controller and the Logging
Viewer (optional).
Compliant. Fault is indicated by a control output of the
Network Controller, if properly installed. Fault is also
displayed by the Network Controller and the Logging
Viewer (optional).
Network Controller, if properly installed. Fault is also
displayed by the Network Controller and the Logging
Viewer (optional).
Network Controller, if properly installed. Fault is also
displayed by the Network Controller and the Logging
Viewer (optional).
Compliant. Fault is indicated by a control output of the
Network Controller, if properly installed. Fault is also
displayed by the Network Controller and the Logging
Viewer (optional). The chime generator is supervised by
a watchdog circuit. First 128 MB of compact flash card
(message store) is checked (first 25 minutes).
Compliant, if properly installed using single or multiple
line supervision. Responsibility of the installer. Fault is
indicated by a control output of the Network Controller,
if properly installed. Fault is also displayed by the
Network Controller and the Logging Viewer (optional).
Compliant, if properly installed. Responsibility of the
installer. Visual alarm device must provide feedback to
control input.
Compliant, using the control outputs of the Network
Controller.
via checksum during system start-up. Fault is indicated
by a control output of the Network Controller, if properly
installed. Fault is also displayed by the Network
Controller and the Logging Viewer (optional).
Compliant. Fault is indicated by a control output of the
Network Controller, if properly installed. Fault is also
displayed by the Network Controller and the Logging
Viewer (optional).
Compliant. Fault is indicated by a control output of the
Network Controller, if properly installed. Fault is also
displayed by the Network Controller and the Logging
Viewer (optional).
Compliant. Responsibility of the installer to install a
buzzer and a lamp using the control outputs of the
Network Controller. Acknowledge/Reset with Call
Station Keypad, if properly installed or in the Logging
Viewer.
Compliant.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998en | 20
EN60849 - 5.4 Monitoring of software controlled equipment
RequirementComplianceSignature
The correct execution of the system software by any
microprocessor shall be monitored by internal selfchecking procedures and by an appropriate monitoring
circuit (e.g. "watch dog" circuit) complying with the
following:
a The monitoring circuit and its associated indication
and signalling circuits shall not be prevented from
determining and signalling a fault condition by the
failure of any microprocessor or associated clock
circuits.
b The monitoring circuit shall monitor the execution of
routines associated with the main program
elements (i.e. it shall not be solely associated with
"waiting" or other "housekeeping" routines).
c In the event of a failure by a microprocessor to
execute its software correctly, the monitoring circuit
shall (in addition to initiating an audible and visual
fault warning) perform as follows:
1 re-initialize the processor and attempt to restart
the program at a suitable point within 10 s of
the occurrence of the failure. The reinitialisation procedure shall verify that the
contents of memory, both program and data,
are not corrupted, and
2either
irecord that a failure has occurred (using a
system capable of recording a minimum of
99 failures and re-settable only by an
operation restricted to authorized servicing
personnel) or
iiautomatically reset the equipment and give
an audible and visual warning that an
automatic reset has occurred.
Compliant.
Compliant. Indication on Call Station Basic and Call
Station Kit if properly installed.
Compliant. Fault are indicated by a control output of the
Network Controller, if properly installed. Responsibility
of the installer.
Compliant, both data and program are checked for the
Network Controller and the firmware in the units.
Compliant.
EN60849 - 5.5 Interface with emergency detection system
RequirementComplianceSignature
The communication link between the emergency
detection system and the sound system shall be
continuously monitored for faults. This is normally
performed by the control equipment for the emergency
detection system, which gives an audible and visual
indication of a fault in the link between the two systems.
The emergency detection system shall also be capable
of receiving information regarding faults in the sound
system and shall include a provision, usually at its
control and indicating equipment, for appropriate
audible and visual indication of such faults. As a
minimum, the sound system shall be capable of
transmitting to the emergency detection system one
general "Sound system fault" for any of the fault
conditions listed in 5.3 that may occur within the sound
system.
The link between a fire detection and alarm system and
the voice alarm system is of crucial importance in
maintaining the integrity of overall operation. It may be
desirable on larger systems, where distributed control
equipment is used, to provide a link at each control
equipment location rather than to rely on a central
location. Each link shall be monitored. The voice alarm
system shall be capable of continuing to broadcast
alarm messages, which have been initiated by the fire
detection and alarm system, even in the event of a
subsequent fault in the interconnecting link between
the two systems (i.e. the voice alarm system shall
"latch" on receipt of a signal from the fire detection and
alarm system). Interruption by higher priority broadcasts
shall still be possible.
Compliant, if properly installed using supervised control
inputs. Responsibility of the installer.
Compliant, if properly installed using control outputs.
Responsibility of the installer.
Compliant, if properly installed. Responsibility of the
installer. Control input should be in toggle mode.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998en | 21
RequirementComplianceSignature
In complex buildings in which actions, such as initiation
of evacuation signals, silencing of alarm signals, etc.,
can be implemented at remote voice alarm equipment,
consideration shall be given to whether there is a need
for such actions to be indicated at any central fire
detection and alarm control and indicating equipment.
Responsibility of the installer.
EN60849 - 5.6 Secondary power supply
RequirementComplianceSignature
If the building is to be evacuated following primary
power failure, a secondary power supply shall be
provided. This shall be capable of operating the system
in the emergency mode for a period equal to twice the
evacuation time determined by the appropriate
authority for the building. In any event, the secondary
power supply shall be capable of powering the system
for a minimum of 30 min.
If the building is not to be evacuated following failure of
the principal power supply, the secondary power
supply shall be capable of operating the system for at
least 24 h, or 6 h if an emergency generator is
available, and then powering the system in emergency
mode for a minimum of 30 min. If a building remains
unoccupied for several days, provision should be made
to ensure that the voice alarm system is capable of
operation in emergency mode for 30 min. when the
building is re-occupied.
Non-emergency functions within the system, such as
background music, shall not operate from the
secondary power supply if this will reduce the capacity
for emergency operation.
If batteries are used as a secondary power supply they
shall be of the secondary type, complete with automatic
charging facilities. Where lead-acid batteries are used
they shall be of the valve-regulated type unless
otherwise specified, and the charging system shall
incorporate charging current compensation for
changes in the ambient temperature, where this is
necessary to achieve the specified battery life.
Batteries shall be used in accordance with the
manufacturer's recommendations in order to achieve
their specified life, which shall be not less than four
years. The end of life shall be taken as the time when
deterioration to less than 80% of the rated amperehour capacity (at the one-hour rate) has occurred.
Automatic charging shall ensure that the batteries are
fully recharged to 80% of their maximum rated capacity
from the fully discharged state in a period of not more
than 24 h.
Adequate ventilation and protection against corrosion
and dangers resulting from gases emitted by the
batteries shall be provided.
Responsibility of the installer.
Responsibility of the installer.
Compliant if properly installed. Responsibility of the
installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998en | 22
EN60849 - 5.7 Climate and environmental conditions
RequirementComplianceSignature
As all or part of the system may be installed inside or
outside buildings, under various climatic and
environmental conditions, and exposed to possible
mechanical damage, full information on the conditions
under which the system is required to operate shall be
included in the system specification. For tests, refer to
IEC60068-1 (environmental testing).
When not otherwise specified, equipment shall operate
in accordance with the system specification under the
following conditions:
a Control and amplification equipment and
associated battery power supplies:
•Ambient temperature -5 °C to + 40 °C.
•Relative humidity 25% to 90%.
•Air pressure 86 kPa to 106 kPa.
b All other equipment:
•Ambient temperature -20 °C to +55 °C.
•Relative humidity 25% to 99%.
•Air pressure 86 kPa to 106 kPa.
Praesideo specifications exceed the environmental
requirements given by EN60849:1998.
EN60849 - 5.8 Marking and symbols for marking
RequirementComplianceSignature
Equipment shall be permanently marked with
information regarding its function.
Terminals and controls shall be permanently marked
with information regarding their function, characteristics
and polarity.
The marking shall be such that it shall be possible to
adjust the user controls and to confirm their positions
accurately in conformity with the information given in
the user instructions.
Marking shall preferably include letter symbols, signs,
numbers and colors that are internationally
comprehensible. Reference is required to IEC60027
and IEC60417. Marking not included in these standards
shall be clearly explained in the user instructions.
Compliant.
Compliant.
Compliant.
Compliant.
EN60849 - 5.9 Electrical matching values
RequirementComplianceSignature
For the electrical matching values, reference is required
to IEC61938 unless otherwise specified.
Compliant (specified in Technical data sections).
EN60849 - 5.10 Connectors
RequirementComplianceSignature
Connectors shall comply with IEC60268-11 or
IEC60268-12. Requirements for fire resistance of
connectors may also be stipulated by the relevant
authorities.
Connectors comply to IEC60268-11 or IEC60268-12.
Additional requirements are the responsibility of the
installer.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998en | 23
EN60849 - 6. Installation requirements
RequirementComplianceSignature
The system shall be installed in accordance with
IEC60364 or with mandatory national or local
standards.
If the emergency sound system forms part of an
emergency detection and/or alarm system, the cabling
shall meet the requirements of mandatory national or
local, emergency and/or alarm system standards.
Where the application specifically excludes detection
and/or alarm, the cabling shall be of a standard suitable
for the application.
Precautions shall be taken to prevent the spread of
hazardous effects via the wiring routes.
When a sound system for emergency purposes is
installed in combination with an emergency detection
system, the installation standards for the sound system
shall comply as far as is applicable with the standards
required for that detection system.
When additions and/or modifications are made to a
non-compliant system the existing system may require
to be upgraded to meet this standard. In all cases the
additions and/or modifications shall meet this standard.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998en | 24
EN60849 - 7. Instructions for use
EN60849 - 7.1 Instructions for operation
RequirementComplianceSignature
Instructions for the operation of the system, including
actions to be taken in accordance with established and
well-rehearsed procedures, shall be available for rapid
reference, preferably prominently and permanently
displayed, at each control station.
As far as possible, graphic illustrations should be used:
where text is necessary this should be clearly legible
and in the preferred language(s).
Updating of the instructions for operation shall be
carried out after additions to or modifications of the
system, or on the basis of practical experience, or
revised procedures.
Instructions shall include:
•The functional operation of the system.Responsibility of the installer.
•Action to be taken in the event of a system failure.Responsibility of the installer.
A bound copy of the operational instructions shall be
provided.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
EN60849 - 7.2 Records to be kept
RequirementComplianceSignature
Installation, logbook and maintenance records shall be
kept by the end-user and/or maintenance company
contracted by the end-user in accordance with relevant
international and national standards. These shall
comprise as a minimum:
a InstallationResponsibility of the installer.
1 details of the locations of all items of the
equipment.
2 “as installed” performance measurements of
the system including:
•measured loudspeaker loading per circuit in
emergency mode.
•settings of any adjustable items within the
system, including the output level of power
amplifiers.
•sound pressure levels.Responsibility of the installer.
•intelligibility measurements.Responsibility of the installer.
b Log book
A stiff covered log book shall be kept, in which all
usage of the system and all fault occurrences
should be recorded, together with all available
automatically produced records, to include:
1 dates and times of usage of the system.
2 details of tests and routine checks carried out.
3 time and date of each fault occurrence.
4 details of the fault found and the circumstances
of it being found (for example during routine
maintenance).
5 action taken to rectify or remedy.
6 date, time and name of person in charge of the
system.
7 countersignature of the responsible person, if
any faults occurred or have been rectified.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the installer.
Responsibility of the person nominated by the person or
body, having control of the premises (see 4.2). Action
to be taken care of by the installer.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998en | 25
EN60849 - 7.3 Maintenance
EN60849 - 7.3.1 General
RequirementComplianceSignature
There shall be an established and documented
procedure for the scheduled maintenance and retesting
of the sound system and equipment as recommended
by the system designer in conjunction with the
equipment manufacturer and in accordance with
relevant international and national standards. It is
recommended that a minimum of two scheduled
maintenance inspections, by a competent person, be
made each year. A responsible person (see 4.2) shall
be nominated to ensure that the procedure continues
to be carried out correctly.
Responsibility of the installer to establish the
maintenance procedures using the manufacturer
documentation.
EN60849 - 7.3.2 Maintenance instructions
RequirementComplianceSignature
A stiff-covered maintenance manual should be available
giving details of all work required to maintain the
installation and equipment in proper working order,
consistent with specified performance criteria and any
other requirements of this standard and other relevant
international or national standards. This should state
clearly:
a The method of maintenance.
b Any sequence related to maintenance.
c Identification of parts requiring maintenance, giving
reference to the location of items on drawings,
together with manufacturer’s reference numbers,
and the addresses, telephone and facsimile
numbers, of suppliers of materials and parts.
d Original versions of equipment and materials
catalogues.
e List and location of spare parts.
fList and location of special tools.
The maintenance instructions should also include:
g Test certificates as required to be examined by the
relevant authority.
h A set of "as fitted" drawings.
Responsibility of the installer to establish the
maintenance procedures using the manufacturer
documentation.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN60849: 1998en | 26
Intentionally left blank.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN54-16: 2008en | 27
EN54-16: 2008 compliancy checklist
Clause / RequirementComplianceSignature
4 General requirements
4.1 GeneralPraesideo is compliant.
4.1.1 If an optional function with requirements is
included in the VACIE, then all the corresponding
requirements shall be met (see Annex B).
4.1.2 If functions other than those specified in this
European Standard are provided, they shall not
jeopardize compliance with any requirements of this
European Standard
4.2 Combined VACIE and CIE
When the VACIE and CIE are combined they may
share common indications, manual controls and
outputs (see Annex F). In this case, the following shall
apply:
a single fault in the CIE shall not adversely affect
the mandatory functions of the VACIE;
b indication(s) and manual control(s) of the voice
alarm condition shall be clearly identifiable, with
the exception of the optional audible warning.
4.3 Power supplyPraesideo is compliant.
Power supply equipment, external or included in the
VACIE, shall comply with the requirements of EN 54-4.
NOTE - The power supply may be shared with that of
the fire detection and fire alarm system.
The following optional functions, with requirements, are included
in Praesideo from version 3.3 upwards:
• Audible warning (7.3)
• Phased evacuation (7.5)
• Manual silencing of the voice alarm condition (7.6.2)
• Manual reset of the voice alarm condition (7.7.2)
• Output to fire alarm devices (7.8)
• Voice alarm condition output (7.9)
• Indication of faults related to the transmission path to the
CIE (8.3)
• Indication of fault related to voice alarm zones (8.4)
• Voice alarm manual control (10)
• Interface to external control device(s) (11)
• Emergency microphone(s) (12)
• Redundant power amplifiers (13.14)
The following optional functions with requirements are not
included in Praesideo:
• Delay(s) to entering the voice alarm condition (7.4)
• Disabled condition (9)
Praesideo power amplifiers and basic amplifiers shall not be
configured to enter the power save mode when mains power
fails. Although this would save battery power, the amplifier
supervision and line/loudspeaker supervision is not active in this
mode, which is a necessity for systems operating in accordance
with EN54-16.
The Praesideo PC call station shall not be used as an emergency
call station in systems operating in accordance to EN54-16. A
PC does not comply with the requirements as set forward by this
standard.
This requirement is not applicable. In Praesideo, the Voice Alarm
Control and Indicating Equipment (VACIE) is not combined with
a fire alarm Control and Indicating Equipment (CIE).
The installer must use power supplies and battery charging
equipment in accordance with EN54-4, e.g. the Bosch
PRS-48CH12, with separate wiring for mains (230Vac) and
battery backup (48Vdc) from the power supply to the Praesideo
system.
The power supply equipment must be installed in a separate
cabinet, not shared with the Praesideo system, unless the
combination of the actual power supply equipment and
Praesideo system elements in the same cabinet has been
certified.
The content of the EN54-16 certification is subject to change.
The most recent version of this certificate can be found on
www.boschsecurity.com.
The network controller and all amplifiers are supplied with a
mains supply and DC backup supply (48V) input. Switch over
between the both takes place automatically, without any
interruption or status change other than the power supply related
indications.
The installer must ensure that the output voltages of the power
supply equipment do not exceed the specifications of the mains
and battery inputs of the connected Praesideo equipment.
The power supply may be shared with that of a fire detection
system, but when operated with a battery a new capacity
calculation is required.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN54-16: 2008en | 28
Clause / RequirementComplianceSignature
5 General requirements for indications
5.1 Display and functional conditionsPraesideo is compliant.
5.1.1 The VACIE shall be capable of unambiguously
indicating the following functional conditions, as described
in Clauses 6 to 9:
• quiescent condition;
• voice alarm condition;
• fault warning condition;
• disablement condition (option with requirements)
5.1.2 The VACIE shall be capable of being simultaneously
in any combination of the following functional conditions on
different voice alarm zones:
•voice alarm condition;The voice alarm condition is indicated per system on each
•fault warning condition;The fault warning condition is indicated per system on each
•disablement condition (option with requirements).The optional disablement condition is not implemented in
5.2 Indication displayPraesideo is compliant.
All mandatory indications shall be clearly identifiable, except
where otherwise specified in this European Standard.
See Clauses 6 to 9.
The Praesideo system is capable of being simultaneously in
the voice alarm condition and in the fault warning condition.
call station (system status LED) and on the display of the
network controller (emergency menu). This system wide
indication can be combined with the indication of the fault
warning condition: each call station uses a different LED
(power/fault LED) for indication of the fault warning
condition; therefore both conditions can be indicated
simultaneously. The display of the network controller can
indicate both the voice alarm condition and the fault
warning condition (note that it will only show one condition
automatically, the voice alarm condition has precedence;
the user is able to see the fault warning condition by
navigating through the menu if both conditions apply to the
system simultaneously).
To indicate the voice alarm condition per zone, the installer
shall use a call station keypad kit with correctly connected
red LEDs (see clause 13.9.1) with configuration of the
‘Zone status’.
call station (power/fault LED) and on the display of the
network controller (faults menu). This system wide
indication can be combined with the indication of the voice
alarm condition: each call station uses a different LED
(system status LED) for indication of the voice alarm
condition; therefore both conditions can be indicated
simultaneously. The display of the network controller can
indicate both the voice alarm condition and the fault
warning condition (note that it will only show one condition
automatically, the voice alarm condition has precedence;
the user is able to see the fault warning condition by
navigating through the menu if the system is in both
conditions simultaneously).
The installer must configure zone names in a way that the
zone name is visible in the fault logging and network
controller display (see clause 8.2.7 for details). In this way
faults are indicated per zone.
Praesideo.
The Praesideo system uses the following color coding for
indications throughout the system:
• Green: system ok
• Red: system/zone in voice alarm condition
• Yellow: system in fault warning condition
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN54-16: 2008en | 29
Clause / RequirementComplianceSignature
5.3 Indication on alphanumeric displaysPraesideo is compliant.
Where an alphanumeric display is used to display
indications relating to different functional conditions these
may be displayed at the same time. However, for each
functional condition there shall be only one window, in
which all of the information relating to that functional
condition is grouped.
5.4 Indication of the supply of powerPraesideo is compliant.
5.4.1 A visible indication shall be given by means of a
separate discrete light-emitting indicator while the VACIE is
supplied with power.
5.4.2 Where the VACIE is distributed in more than one
cabinet, an indication of supply of power to each distributed
cabinet shall be given at that point.
5.5 Additional indicationsPraesideo is compliant.
Where additional indications are provided, they shall be
clearly identifiable and shall not override the primary
indication of the VACIE.
The alphanumeric display of the network controller
indicates the voice alarm condition by means of the
emergency menu. The display indicates the fault warning
condition by means of the faults menu.
If a fault occurs in the system, the faults menu is displayed
automatically. If the system enters the voice alarm
condition, the emergency menu is displayed automatically.
The emergency menu has precedence over the faults
menu.
The faults menu has a submenu for each individual fault.
The user can scroll through the individual faults.
The logging application delivered with the Praesideo
system offers a graphical user interface for viewing events
(Logging Viewer). The Logging Viewer has three separate
tab pages: Fault Events (shows events related to the fault
warning condition), Call Events and General Events (shows
events related to the voice alarm condition).
Each Praesideo system component either has a dedicated
power LED or a display with a backlight. For components
with a power LED, the LED is on when the component is
supplied with power. For components with a display, the
backlight of the display is on when the component is
supplied with power.
The Praesideo system can be distributed in more than one
cabinet, depending on the installation of the system. Many
system components can be mounted in a 19’’ rack. Each
cabinet will indicate supply of power independently if the
system is distributed in more than one cabinet.
For LEDs with multiple indication functions , all of the
additional indications are clearly identified (in the
Installation and User Instructions of the Praesideo system);
since the fault warning indication and the voice alarm
indication always have precedence over the additional
indications, the primary indications are not overridden.
The LED indicator belonging to a key of the call station
keypad is used for status indications. The status indications
depend on the function which has been assigned to the
programmable key. The Installation and User Instructions of
the Praesideo system clearly identifies the possible status
indications. These status indications do not override the
primary indication of the Praesideo system, since they are
separate LEDs.
The display of the network controller offers a menu that is
also used for other indications than indication of the voice
alarm and/or fault warning condition. The Installation and
User Instructions of the Praesideo system clearly identifies
the other indications of the menu. The other menus do not
override the emergency and faults menu; indication of the
faults menu and emergency menu has precedence (higher
priority) over indication of the other menus.
Bosch Security Systems | 2011-02
Praesideo 3.5 | Installation and User Instructions | EN54-16: 2008en | 30
Clause / RequirementComplianceSignature
6 The quiescent condition
Any kind of system information may be displayed during the
quiescent condition. However, no indications shall be given
which could be confused with indications used in the
•voice alarm condition,If the Praesideo system enters the voice alarm condition
•fault warning condition,If the Praesideo system enters the fault warning condition
•disablement condition (option with requirements).The disablement condition is not implemented in
Praesideo is compliant.
each call station will show a red system status LED and the
emergency menu will pop up on the display of the network
controller. In the quiescent condition no red indicators are
used at all and the display of the network controller will
never automatically switch to the emergency menu.
each call station will show a yellow (blinking or on) power/
fault LED and the faults menu will pop up on the display of
the network controller. In the quiescent condition the
power/fault LED of each call station will be green and the
display of the network controller will never automatically
switch to the faults menu.
Praesideo.
Bosch Security Systems | 2011-02
Loading...
+ 468 hidden pages
You need points to download manuals.
1 point = 1 manual.
You can buy points or you can get point for every manual you upload.