Bosch NOM 100 LSN, NOM K 100 LSN Product Information

PRODUCT INFORMATION PI−34.62c
Page 1
BDLF.01U.002.709
A5.en / 29.12.2004
STFIR/ PRM1 / deh
Optical smoke detector
NOM 100 LSN/NOM K 100 LSN
PI 34.62cProduct Information Optical Smoke Detector NOM/NOM K 100 LSN
Seite 2 von 30
BDLF.01U.002.709
A5.en / 29.12.2004
STFIR/ PRM1 / deh
Table of Contents
1. Product Description 4. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
1.1. Block Diagram 5. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
2. Features 6. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3. Planning Notes 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
3.1. Recommended Use 7. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4. Scope of Order 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.1. Detector Models 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.2. Detector Base 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
4.3. Accessories 8. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5. Device Design 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5.1. Dimensions – Detector Module 9. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6. Functional Description 10. . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.1. Smoke Measurement 11. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.2. Contamination Measurement 12. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.3. Monitoring Stages 13. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4. Alarm Triggering 15. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.4.1. Alarm Triggering with Slightly Contaminated Detectors 16. . . . . . . . . . . . . . . . . . .
6.5. Detector Fault 17. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.5.1. Detector Exchange Required/Detectors Highly Contaminated 17. . . . . . . . . . . . .
6.5.2. Detector Not Sensitive Enough 18. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6. Planning Monitoring/Change in Functionality 19. . . . . . . . . . . . . . . . . . . .
6.6.1. Planning Monitoring 19. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.6.2. Change in Functionality 20. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
6.7. Sectional View of Upper Section of Detector 21. . . . . . . . . . . . . . . . . . . .
7. Technical Data 21. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PI 34.62cProduct Information Optical Smoke Detector NOM/NOM K 100 LSN
Seite 3 von 30
BDLF.01U.002.709
A5.en / 29.12.2004
STFIR/ PRM1 / deh
8. Assembly Drawings for Detector Bases 22. . . . . . . . . . . . .
8.1. Standard Detector Bases NMS 100, NMS 100 V 22. . . . . . . . . . . . . . . .
8.2. Damp Room Detector Bases NMS F 100, NMS F 100 V 22. . . . . . . . . .
8.3. Cavity Detector Bases NMS H 100, NMS H 100V 23. . . . . . . . . . . . . . .
8.4. Ventilation Duct Detector Base NMS K 100 24. . . . . . . . . . . . . . . . . . . . .
8.5. Mounting Tips for Detector Bases 24. . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.6. Connection Diagram 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
8.6.1. Detector Base NMS 100 25. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9. Tips on Maintenance and Service 26. . . . . . . . . . . . . . . . . .
9.1. Repair 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.2. Disposal 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.3. Additional Documentation 26. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
9.4. Service Accessories 27. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10. Table of Abbreviations 28. . . . . . . . . . . . . . . . . . . . . . . . . . . .
11. Notes 29. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
PI 34.62cProduct Information Optical Smoke Detector NOM/NOM K 100 LSN
Seite 4 von 30
BDLF.01U.002.709
A5.en / 29.12.2004
STFIR/ PRM1 / deh
1. Product Description
Optical smoke detectors NOM 100/NOM K 100 work using a scattered light proce­dure and are suitable for use in all cases where smoke is likely to form in the event of a fire.
The detectors are particularly sensitive to white, visible smoke (e.g. smoldering fires). With other types of smoke (e.g. open fires with smoke that is hardly visible and with
thick, black smoke), detection sensitivity is, as a result of the design, somewhat lesser, but does always comply with the values required in line with EN 54.
The optical detector is available in two designs:
Standard smoke detector NOM 100 LSN and
Smoke detector NOM K 100 LSN for use in a ventilation duct.
The smoke detectors are designed for connection in a local security network (LSN). Depending on the application, connection takes place with other network elements
in loops or stub lines. The power supply is provided by the two wires of the data line.
NOM 100 LSN NOM K100 LSN
PI 34.62cProduct Information Optical Smoke Detector NOM/NOM K 100 LSN
Seite 5 von 30
BDLF.01U.002.709
A5.en / 29.12.2004
STFIR/ PRM1 / deh
1.1. Block Diagram
Power supply
Send
data
Receive
data
A/D converter
Receiver
NOM 100/NOM K 100
Contamination measurement
Smoke measurement
Measuring chamber
Microprocessor for
data transfer
Sensor evaluation
FET switch
b LSN 1
a LSN 1
LSN LSN
Tableau point
Open collector
rd
ye
b LSN 2
a LSN 2
PI 34.62cProduct Information Optical Smoke Detector NOM/NOM K 100 LSN
Seite 6 von 30
BDLF.01U.002.709
A5.en / 29.12.2004
STFIR/ PRM1 / deh
2. Features
D Detector polling routines and evaluation with transmission of events in the case of:
Deviation from basic value
Detector fault due to the risk of false alarms caused by excessive contamination
Detector exchange requirement (maintenance)
Prealarm (change in functionality)
Alarm
D Automatic adjustment of thresholds
D Measurement of detector contamination using a separate smoke recording method
D Individual detector identification
D Active sensor technology selfmonitoring with relevant evaluation electronics
D Wide sensor check (remote diagnosis)
D Different detector display via a twocolor LED
(red = alarm, yellow = fault)
D Activation of a remote external detector alarm display
D Several base versions are available for the detector.
(See PI34.95b detector base NMS 100).
D Can be connected to the following fire panels:
BZ 500 LSN
UEZ 1000 (LSN)
UEZ 2000LSN
UGM 2020 (LSN)
Control units with receiver modules with identical connection properties
D VdS approval number: G 293004
PI 34.62cProduct Information Optical Smoke Detector NOM/NOM K 100 LSN
Seite 7 von 30
BDLF.01U.002.709
A5.en / 29.12.2004
STFIR/ PRM1 / deh
3. Planning Notes
3.1. Recommended use
Offices, hotels, hospitals, nursing homes, stores, theaters, museums, churches, assembly rooms/exhibition rooms etc.
Clean, maintained rooms
Easily contaminated rooms
Depots/machine shops, production/manufacturing workshops with low dust accumulation etc.
Very contaminated rooms 1
Rooms with dust and lint accumulation (wood/textile industry)
Very contaminated rooms 2
Rooms used for raw/semifinished production for mechanical engi­neering etc. with the exception of strong, oily deposits
Electrical risks 1
Cable ducts, cable funnels, raceways, rooms with electrotechni­cal/IT/switching stations with a wind speed of < 10m/s
Electrical risks 2
Object surveillance in switch cabinets/switchboards etc.
Rooms with corrosive ambient air
Chemicals industry, plastics processing etc.
Rooms susceptible to smoke and flash formation 1
Manufacturing workshops, smoking offices, conference rooms, laun­dromats
Rooms susceptible to smoke and flash formation 2
Halls with vehicle operation (combustion engines)
Recommended Not recommended
NOM K 100 NOM 100 Use
Wind tunnels with a wind speed of < 20m/s
Wind tunnel electrical risks 1
Antitheft protection
If required, detector modules can be secured with a lock to prevent theft or accidental movement.
Maximum number of detectors in an LSN ring
Owing to the different current consumption from the LSN data line, the maximum number of network elements (interfaces and detectors) that can be connected must always be observed.
The limiting values can be determined by reading the product information for the danger detection system in question.
Installation cable
The installation cable for the NLT line must be a JY(St)Y n x 2 x 0.6 or JY(St)Y n x 2 x 0.8 cable.
Norms, guidelines and planning recommendations
Additional norms, guidelines, and planning recommendations with respect to installation location, monitoring area etc. must be taken into account (see fire detector manual).
PI 34.62cProduct Information Optical Smoke Detector NOM/NOM K 100 LSN
Seite 8 von 30
BDLF.01U.002.709
A5.en / 29.12.2004
STFIR/ PRM1 / deh
4. Scope of Order
4.1. Detector Models
Product ID DU* Designation
2.799.330.824 PC NOM 100 LSN optical smoke detector
2.799.330.865 PC NOM K 100 optical smoke detector
for use in a ventilation duct
*DU = Delivery unit, PC = Pieces, PAK = Pack
4.2. Detector base
Product ID DU* Designation
2.799.330.859 PC NMSKV 100 ventilation duct base
4.3. Accessories
Product ID DU* Designation
2.799.330.669 PC External detector alarm display
MPA external detector alarm display according to DIN 14 623
2.799.330.870 PA C Replacement filter (packaging unit = 10 pieces)
PI 34.62cProduct Information Optical Smoke Detector NOM/NOM K 100 LSN
Seite 9 von 30
BDLF.01U.002.709
A5.en / 29.12.2004
STFIR/ PRM1 / deh
5. Device Design
The NOM 100/NOM K 100 comprises a detector module and a detector base. The housing is made from impactresistant ABS plastic.
The NOM K 100 is supplied with a dust filter and the appropriate mounting clamp. The detector module contains the photoelectronic part with the light source and
the light receiver, a electronic evaluation switching, a wire mesh for insect protec­tion in the smoke entry opening, shielding against electrical interference fields and a silent individual display (twocolor LED).
The detector base contains the contact and locking pins and the terminal clamps for the detector line and also offers the option of connecting an external detector alarm display.
The detector module is engaged in the detector base by slotting it in and turning it.
Several detector base versions are available for NOM 100.
There is a special ventilation duct base for the NOM K 100.
5.1. Dimensions – Detector Module
66
64