INSTALLATION DETAILS MAGIC.SENS MSS 400
Fixing notes
The sounder base is designed for surface mounting and is provided for rear and surface cable entry. The sounder insert has to be removed before fixing the mounting base. To release the sounder insert, fixing clamps have to be pushed in direction of the arrows (Fig.2) . for rear cable entry, conduit box mounting, feed the cable through the openings. For surface cable feed, please break out the prepared cable entries. Install the mounting base with two screws on a flat dry surface. Therefore, only the prepared fixing bores may be used (see Fig. 2)!
Technical Data
Dimensions : see Figure 1 and Figure 2 IP-Rating (as per EN 60529): IP30 Operating temperature: -10_C...+55_C Storage temperature: -25_C...+85_C Housing material: ABS plastics Terminals: In and Out 0,28 - 2,5mm
2
Operating voltage: 9 - 15V DC / 15 - 28V DC Current consumpt. from LSN (standby): 575 - 1025mA Current consumption from LSN (alarm): 20mA
(depending on selected tone) Bosch order number: 4.998.098.974 CPD number: 0786 - CPD - 20186
128
81,5
Sounder insert
Mounting b ase
Detector
Fixing springs
Figure 1: Di m ens i o ns Figure 2: I ns tal l ati o n de tai ls
Figure 3: Mo u nting order
Figure 4: Detector locking spring
Detector with sounder base (complete fitted)
70
60 50
Cable entries for under plaster cable feed
Use only these borings for fixing the mounting base!
Sounder insert fixing clamps
to
release
sounder
insert
Prepared cable entries
Prepared cable entries
Tone table
Page 2
BDL - 4998121822 A3.en/ 28.12.2004 ST-FIR/ PRM1/ deh
The sounder provides 11 different tones with additional second tone option (see table be­low). The sound intensity is selectable in 4 steps via the software WinPara. The tone selection follows also via WinPara.
Both tones can be activated separately, whereby a subsequently activation of the second tone switches off the first tone.
Ton
Tone type, Frequency, 2. Tone
Current
consum
p
-
Sound in-
tensity at
ToneTonetype,
Description
Frequency
,
Modulation
2.Ton
e
(not BZ 500)
consump
tion
[mA] at 24V
24V
[dB(A)] ±2dB
1
Sweeping,
DIN - tone
1200 - 500Hz
1Hz
970 Hz,
Continuous
max. 20 97
2
Sweeping (LF),
BS 5839, Teil 1, 1988
800 / 970Hz
1Hz
970 Hz,
Continuous
max. 20 96
3
Sweeping,
Australian tone, AS 2220
2400-2850Hz
7Hz
970 Hz,
Continuous
max. 20 92
4
Sweeping for 3,5s,
0,5s off, Dutch tone
500-1200Hz
3,5s On / 0,5s Off
970 Hz,
Continuous
max. 20 97
5
Continuous,
BS 5839, Part 1, 1988
970Hz
610 Hz,
Continuous
max. 20 97
6
Alternating tone,
French tone
554Hz / 100ms 440Hz / 400ms
970 Hz,
Continuous
max. 20 94
7
Continuous,
Schwedish tone
660Hz
970 Hz,
Continuous
max. 20 95
8
Alternating tone,
Low power
580Hz / 500ms
1000Hz / 500ms
610 Hz,
Continuous
max. 20 97
9
Pulsed tone,
Low power
580Hz
0,25s On / Off
610 Hz,
Continuous
max. 20 93
10
USA temporal 3 tone,
ISO 8201
610Hz
970 Hz,
Continuous
max. 20 95
11
USA temporal 3 tone,
ISO 8201
2850Hz
970 Hz,
Continuous
max. 20 96
Connection
Clamp Desc rip tion
+
interconne cte d
p
ower
-
interconnectedpower
supply
a1 / a2 LSN -
b1 , b2 LSN + (coming / going)
screen wire (has to be isolated and as short as possible)
b1 LSN+
b1 b2
b2 LSN+
a1 / a2 LSN-