Communication Systems | LBB 1990/00 Plena Voice Alarm Controller
LBB 1990/00 Plena Voice Alarm Controller
Heart of the Plena Voice Alarm System
Compliant with standards for emergency sound
systems (IEC60849) 6-zone system controller
Built-in 240 W booster amplifier
12 Business and emergency control inputs and
outputs
The Plena Voice Alarm Controller is the heart of the voice alarm system. It is the basis of the Plena Voice Alarm System, and has all the essential functionality for compliance with the IEC 60849 standard, including full system supervision, loudspeaker line impedance supervision, a supervised emergency microphone on the front panel and a supervised message manager. The messages can be merged to allow even more flexible use of pre-recorded announcements and evacuation messages. The controller can be used as a stand-alone system with up to 6 zones, or expanded to up to 60 zones using additional 6-zone routers. Up to 8 call stations can be connected. Interconnections are made using standard RJ45 connectors and shielded CAT-5 cable. A built-in 240 W amplifier provides the power for the emergency call channel and BGM. Additional Plena Amplifiers can be added to provide two-channel operation, or for additional power if the total power requirement exceeds 240 W (maximum 480 W per 6 zones). All amplifiers are supervised. The audio output uses standard analog audio 100 V line switching for full compatibility with the Plena family of public address equipment and Bosch EVAC-compliant loudspeakers. The system is configured using DIP switches for basic functionality and a PC for more advanced functions.

Functions

www.boschsecurity.com
2 | LBB 1990/00 Plena Voice Alarm Controller
Each message can have any length within the total available capacity. Messages and configurations are uploaded from a PC via USB into the memory, after which the unit operates without PC connection. The standard WAV-format is used for the messages and sample rates of 8 kHz up to 24 kHz with 16-bit word length (linear PCM) are supported. This gives up to 17 minutes of recording time with CD-quality signal-to­noise ratio. The unit has 12 contact trigger inputs for business and emergency (EMG) calls. Each can be configured for a message consisting of a sequence of up to 8 wave files. In this way some wave files may be used in different combinations with other messages, optimizing flexibility and used storage space. Multiple messages can be merged to form one integrated message. Together with this sequence, for each trigger input, a zone selection can be configured.

Certifications and Approvals

EMC emission acc. to EN 55103-1 EVAC compliance acc. to IEC 60849 EMC immunity acc. to EN 55103-2 Safety acc. to EN 60065

Installation/Configuration Notes

Rear view

Parts Included

Quantity Component 1 LBB 1990/00 Plena Voice Alarm Controller 2 19”Mounting brackets 1 Mains cable 1 Plena CD

Technical Specifications

Electrical
Mains Voltage 230 / 115 VAC, ±10%, 50 / 60 Hz Main Power Consumption 60 VA Max/Rated Output Power 360 W / 240 W Battery Current 24VDC, +20% / -10% Max Mains Inrush Current 8A @ 230 VAC / 16A @ 115 VAC Mains Current System Idle 0.26 A = 60 VA System Idle with Pilot Tone 0.6 A = 136 VA Maximum Load* 24 V Current System Idle 0.9 A Maximum Load* 14 A Performance Frequency Response 60 Hz – 18 kHz (+1/-3 dB, @ -10 dB ref. rated
Distortion <1% @ rated output, 1 kHz Bass Control -8/+8 dB @ 100 Hz Treble Control -8/+8 dB @ 10 kHz Inputs Mic / Line Input Type XLR, 6.3 mm jack Sensitivity 1 mV / 1V S/N 63 dB (flat at max volume) S/N 75 dB (flat at min volume/muted) Headroom 25 dB Speech Filter -3 dB@ 315 Hz, high-pass, 6 dB/oct Phantom Power Supply 12 V VOX Trigger Level –20 dB (100 V mic / 100 mV line)
Limiter Automatic BGM and PC Call Station Input Type Cinch stereo (converted to mono) Input Level 200 mV – 2 V Impedance 22 kOhm S/N 70 dB (flat at max volume) S/N 75 dB (flat at min volume/muted) Headroom 25 dB Trigger Inputs Type MC1,5/14-ST-3,5 Activation Programmable Supervision On EMG inputs, programmable Supervision Method Series / parallel resistor 100 V Input MSTB 2,5 /16-ST Power Handling Capacity 480 Watts
*) Maximum load means; maximum power out, maximum load 24V out, maximum number of
call stations
)
3.6 A = 830 VA
output)
or via input contact
6 EMG, 6 business