Bosch G-SSPK24WLPR, G-SSPK24WLPW, G-SSPK24-15 Installation Manual

4. Carefully pack the defective unit (the manufacturer cannot be responsible for consequential damage due to shipping or mishandling). Include your return address and complete details as to the nature of the difficulties being experienced and date of installation.
5. Return to: Gentex Corporation, 10985 Chicago Drive, Zeeland, MI 49464. Prior to returning, call Gentex at 1-800-436-8391 or e-mail FP_RMA@gentex.com to obtain a RMA Number from our return department.
VII. ELECTRICAL SPECIFICATIONS
Voltage 1/8 Watt 1/4 Watt 1/2 Watt 1 Watt 2 Watt 4 Watt 25 Volts 74.6 dBA @ 10ft. 77.7 dBA @ 10ft. 80.5 dBA @ 10ft. 83.1 dBA @ 10ft. 85.6 dBA @ 10ft. 87.9 dBA @ 10ft.
70.7 Volts 73.7 dBA @ 10ft. 76.7 dBA @ 10ft. 79.6 dBA @ 10ft. 82.5 dBA @ 10ft. 85.4 dBA @ 10ft. 87.9 dBA @ 10ft.
Adjust power taps using needle nose pliers
all Strobe Current Ratings*
W
Regulated 24VDC
Candela
Max. Operating
Current(mA)
15 78mA 113mA 30 96mA 135mA 60 137mA 186mA 75 180mA 245mA
110 224mA 313mA
15/75** 96mA 135mA
Adjust intensity by inserting small flatblade screwdriver to turn dial. Displayed number will indicate selected candela.
NOTE: Field selectable options of 15, 30, 60, 75 and 110 candela.
Note: VDC Voltage Range Limits: 16-33v. VFWR Voltage Range Limits: 16-33v. This product was only tested
to the stated voltage range(s); do not apply 80% and 110% of this range for system operation.
* Speaker Strobes are synchable using the Gentex AVSM Synchronization Module. ** The SSPK24-15/75WLP has a fixed candela rating of 15/75 per UL 1638.
For a period of 36 months from the date of purchase, or a maximum of 42 months from the date of manufacture, Gentex warrants to you, the orig­inal purchaser, that your appliance will be free from defects in workmanship, materials, and construction under normal use and service. If a defect in workmanship, materials, or construction should cause your appliance to become inoperable within the warranty period, Gentex will repair your appli­ance or furnish you with a new or rebuilt replacement appliance without charge to you except for postage required to return the appliance to us. Gentex will not reimburse you for repairs or replacement parts provided by other parties. Your repaired or replacement appliance will be returned to you free of charge and it will be covered under this warranty for the balance of the warranty period.
This warranty is void if our inspection of your appliance shows that the damage or failure was caused by abuse, misuse, abnormal usage, faulty installation, improper maintenance, or repairs other than those performed by us.
ANY WARRANTIES IMPLIED UNDER ANY STATE LAW, INCLUDING IMPLIED WARRANTIES OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR PURPOSE, APPLY ONLY FOR THE WARRANTY PERIOD SPECIFIED ABOVE. PLEASE NOTE THAT SOME STATES DO NOT ALLOW LIMITATIONS ON HOW LONG AN IMPLIED WARRANTY LASTS, SO THE ABOVE EXCLUSION MAY NOT APPLY TO YOU.
Important Notice:
These materials have been prepared by Gentex Corporation ("Gentex") for informational purposes only, are necessarily summary, and are not purported to serve as legal advice and should not be used as such. Gentex makes no representations and warranties, express or implied, that these materials are complete and accurate, up-to-date, or in compliance with all relevant local, state and federal laws, regulations and rules. Thematerials do not address all legal considerations as there is inevitable uncertainty regarding interpretation of laws, regulations and rules and the application of such laws, regulations and rules to particular fact patterns. Each person's activities can differently affect the obligations that exist under applicable laws, regulations or rules. Therefore, these materials should be used only for informational purposes and should not be used as a substitute for seeking professional legal advice. Gentex will not be responsible for any action or failure to act in reliance upon the information contained in this material.
550-0455-C
Field Selectable Power Tap Selection
SSPK24WLP
CANDELA SELECTION
Unregulated 24VFWR
Max. Operating
Current (mA)
LIMITED WARRANTY
GENTEX CORPORATION
10985 CHICAGO DRIVE, ZEELAND, MI 49464
PHONE: 1-800-436-8391
GENTEX WILL NOT BE LIABLE FOR ANY LOSS, DAMAGE, INCIDEN­TAL OR CONSEQUENTIAL DAMAGES OF ANY KIND ARISING IN CONNECTION WITH THE SALE, USE OR REPAIR OF THIS APPLIANCE. THE MAXIMUM LIABILITY OF GENTEX SHALL NOT IN ANY CASE EXCEED THE PURCHASE PRICE PAID BY YOU FOR THE APPLIANCE. PLEASE NOTE THAT SOME STATES DO NOT ALLOW THE EXCLUSION OR LIMITATION OF INCIDENTAL OR CONSEQUENTIAL DAMAGES, SO THE ABOVE EXCLUSION MAY NOT APPLY TO YOU.
If a defect in workmanship, materials, or construction should cause your appliance to become inoperable within the warranty period, you must return the appliance to Gentex postage prepaid. You must also prove to the satisfaction of Gentex the date of purchase of your appliance. Warranty service may only be performed by Gentex personnel at Gentex's facilities in Zeeland, Michigan. You must also pack the appliance to mini­mize the risk of it being damaged in transit. You must also enclose a return address. Appliances returned for warranty service should be sent to: Gentex Corporation, 10985 Chicago Drive, Zeeland, MI 49464. If we receive an appliance in a damaged condition as the result of shipping, we will notify you and you must file a claim with the shipper.
THIS WARRANTY GIVES YOU SPECIFIC LEGAL RIGHTS AND YOU MAY ALSO HAVE OTHER RIGHTS WHICH VARY FROM STATE TO STATE.
www.gentex.com
12-01-06
SSPK24WLP SERIES
UL 1971 COMPLIANT UL 1638 COMPLIANT UL 1480 COMPLIANT
WALL MOUNT LOW PROFILE SPEAKER/STROBE
Installation Instructions- Owner's Information
MODELS
SSPK24WLP*............WALL MOUNT SPEAKER WITH SELECTABLE STROBE
SSPK24-15/75WLP*..WALL MOUNT SPEAKER WITH FIXED 15/75 CANDELA STROBE
* Includes one or more of the following designators: A (alert), P (plain), R (red) or W (white)
The Gentex SSPK24WLP Series is a high quality speaker/strobe. The SSPK24WLP Series is UL Listed for fire protective service. The high intensity strobe utilizes a Xenon flash tube which generates a high-intensity light visible from all sides. The strobe is UL Listed in compliance with UL 1971, Signaling Appliances for the Hearing Impaired.
II. PRODUCT INFORMATION
The SSPK24WLP Series speaker/strobe offer a choice of field selectable power taps, 1/8, 1/4, 1/2, 1, 2 and 4 Watts for use with either 25VRMS or 70.7VRMS audio amplifiers. The speaker/strobe offers high intensity strobe candelas of 15, 30, 60, 75 and 110 which comply with UL 1971 and a high intensity strobe candela of 15/75 which complies with UL 1638. The frequency range of the speakers is 400-4000Hz. All devices are suitable for line supervision. Speaker includes DC blocking capacitor which allows for supervision voltage of either polarity.
III. LOCATION
This appliance is intended for use in Fire Alarm Systems and is to be installed in accordance with this installation manual, the recommendation of the local authorities having jurisdiction, and other NFPA Standards that provide standards on notification appliances for protective signaling systems. The Gentex SSPK24WLP Series speaker/strobe is intended for indoor installations only. These appliances are not approved for outdoor applications.
WARNING! Visual signal must be in the direct viewing area of the occupant in order to be seen. WARNING! Visual signal can not be seen when objects such as doors, furniture or walls block
NOTICE: Visual signals for the hearing impaired are only one method of alerting the hearing
Table A
NA = Not Allowable
WARNING! Visual signal must be installed within 16 feet of the pillow when used
visual signal.
impaired. Visual signals may not be the preferred method for notifying all hearing
impaired individuals.
Room Spacing for Wall-Mounted Visible Appliances per NFPA 72, 2007 Edition
Maximum Room Size Minimum Required Light Output ( Effective Intensity, Cd)
Meters Feet
6.10 x 6.10 20 x 20 15 NA NA
8.53 x 8.53 28 x 28 30 Unknown NA
9.14 x 9.14 30 x 30 34 15 NA
12.2 x 12.2 40 x 40 60 30 15
13.7 x 13.7 45 x 45 75 Unknown 19
15.2 x 15.2 50 x 50 94 60 30
16.5 x 16.5 54 x 54 110 Unknown 30
16.8 x 16.8 55 x 55 115 Unknown 28
18.3 x 18.3 60 x 60 135 95 30
19.2 x 19.2 63 x 63 150 Unknown 37
20.7 x 20.7 68 x 68 177 Unknown 43
21.3 x 21.3 70 x 70 184 95 60
24.4 x 24.4 80 x 80 240 135 60
27.4 x 27.4 90 x 90 304 185 95
30.5 x 30.5 100 x 100 375 240 95
33.5 x 33.5 110 x 110 455 240 135
36.6 x 36.6 120 x 120 540 305 135
39.6 x 39.6 130 x 130 635 375 185
One Light per
Room
Two Lights per Room
(Located on Opposite Walls)
Four Lights per Room (One
Light per Wall)
**Effective Intensity Requirements for Sleeping Area
Visible Notification Appliance
Distance from Ceiling to Top of Lens Intensity
greater than or equal to 24" (610mm) 110 Cd less than 24" (610mm) 177 Cd
in a sleeping area.
WARNING! Visual signal must be installed within 16 feet of the pillow when used in a sleeping area.
WARNING! Visual signal must be in the
direct viewing area of the occupant in order to be seen.
WARNING! Visual signal can not be seen when objects such as doors, furniture or walls block visual signal.
NOTICE: Visual signals for the hearing impaired are only one method of alerting the hearing
impaired. Visual signals may not be the preferred method for notifying all hearing impaired individuals.
NOTICE: The visual signal must be seen by the sleeping person. If the person has head
turned or otherwise unable to be alerted by visual, the visual signal will not be effective.
hearing impaired under these common sense conditions: a. Sleeping face down on the bedding or pillow b. Use of sleep medications of any kind c. Use of alcoholic beverages or recreational drugs d. Use of eye shades e. If there are tendencies of deep sleep conditions f. If a fire cuts power to AC circuits, the visual signal will not operate g. If person is not within line of sight of visual signals
Under these and other similar common situations an alternate fire alert method such as a non-hearing impaired attendant is needed. The visual signal only increases the chance of being alerted to the presence of fire. No system of this type can fully protect the hearing impaired in case of fire.
Visual Signal should NEVER
be relied upon as the primary fire alert for the
IV. MOUNTING ROUGH-IN BOX AND RUN WIRING
MOUNTING - SPEAKER/STROBE
TO GBLP BACK BOX
MOUNTING - SPEAKER/STROBE
To 4” Square x 2 1/8” Deep
METALLIC BACK BOX
SYSTEM CONSIDERATIONS:
1. To select the proper wattage input for the speaker, move the jumper to the appropriate pin.
2. Always maintain electrical isolation between speaker and strobe wiring.
3. Do not exceed 130% of rated speaker voltage. If excessive distortion is heard, check amplifier for signal clipping. If clipping exists, reduce either amplifier input or gain.
4. Product mounts to a standard 4 inch square by 2 1/8 inch deep back box.
5. Four screws are provided, two for securing speaker to the back box and two for aesthetics. The two non-functional screws will be held in place by the pressure fit of the faceplate.
CAUTION
WHEN INSTALLING, ROUTE FIELD WIRING AWAY FROM SHARP
PROJECTIONS, CORNERS AND INTERNAL COMPONENTS.
NOTE: Strobes are not recommended for use on coded or pulsing signaling circuits.
NOTE: DO NOT USE
LOOPED WIRE UNDER
TERMINALS. BREAK WIRE
RUN TO PROVIDE SUPERVISION OF
CONNECTION
*MAX. WIRE DISTANCE (IN FEET) = X WIRE CONDUCTIVITY (STROBE ONLY)
* INCLUDES WIRE TO AND FROM APPLIANCE
ASSUMES ALL APPLIANCES ARE AT THE END OF WIRE RUN (WORST CASE).
CAUTION: APPLIES ONLY TO REGULATED SUPPLIES
PANEL VOLTAGE - DEVICE MINIMUM VOLTAGE
TOTAL CURRENT DRAW
V. CHECKOUT AND TROUBLESHOOTING
1. Supply power to the system control panel. The auxiliary signaling device should not be
activated.
2. If the signal is activated:
a. Check all smoke and fire detectors in the system to make sure they have not been activated. b. Check all wiring connections to make sure the signal detection circuits are not reversed or
shorted together. Check wire color codes and traces.
3. To test the SSPK24WLP Series and other signaling appliances, trip the auxiliary panel,
activate alarm circuit at the main control panel or activate one of the fire detection units in the system. All auxiliary signals should be activated.
4. An operational test on this product should be conducted in accordance with National
Standards or at a minimum annually and more often if dictated by local and state codes or authorities having jurisdiction.
SIGNALING APPLIANCE LIMITATIONS:
Your speaker meets or exceeds current audibility requirements of Underwriters Laboratories. However, if the appliance is located outside a bedroom it may not wake up a sound sleeper, especially if the room door is closed or only partially open.
THIS APPLIANCE WILL NOT OPERATE WITHOUT ELECTRICAL POWER. AS FIRES
FREQUENTLY CAUSE POWER INTERRUPTIONS, GENTEX SUGGESTS YOU DISCUSS
FURTHER SAFEGUARDS WITH YOUR LOCAL FIRE PROTECTION SPECIALIST.
VI. TO RETURN A UNIT
Should you experience problems with your SSPK24WLP unit, proceed as follows:
1. Turn off electrical power to the auxiliary alarm circuit.
2. Unscrew the unit from the mounting box.
3. Disconnect the unit from the field wiring. Reconnect the two positive supply voltage circuits
(red wires) and the two negative supply voltage circuits (black wires) of the auxiliary alarm circuit to maintain power to the other auxiliary alarm appliances in the audio system.
Loading...