Fire Alarm Systems | G-SSPK24CLPW Multi-candela Ceiling-mount Speaker Strobe (white, FIRE)
G-SSPK24CLPW Multi-candela Ceilingmount Speaker Strobe (white, FIRE)
www.boschsecurity.com
u High quality dB output
u Frequency range of 400 Hz to 4000 Hz
The G‑SSPKCLPW Low‑profile Ceiling‑mount Speaker
Strobe is designed to meet code requirements for
audio, visual, and voice communications. This
speaker‑strobe offers dependable evacuation signaling
and visual alarms, or a combination of both. It
provides a 25 VRMS or 70.7 VRMS speaker with
field‑selectable power taps of 1/8 W, 1/4 W, 1/2 W, 1
W, 2 W, or 4 W.
The multi-candela strobe can be set for 15 cd, 30 cd,
75 cd, 95 cd, or 115 cd and maintains a constant flash
rate of 1 Hz regardless of input voltage. The strobe can
be synchronized by using the AVSM Synchronization
Module, or by Fire Alarm Control Panels (FACPs) or
power supplies that include the Gentex sync protocol.
Certifications and approvals
Gentex Corporation holds the Listings and Approvals.
u Screw terminals; separate In and Out wiring 18 AWG
to 12 AWG (ISO 0.75 mm2 and 4 mm2)
u Field‑selectable power taps: 1/8 W, 1/4 W, 1/2 W,
1 W, 2 W, 4 W
u Speaker voltage 25 VRMS or 70.7 VRMS standard;
field‑selectable
Region
USA UL UUKC: Signaling Appliances and Equip-
Certification
ment for the Hearing Impaired (ANSI/UL
1971), UUMW: Speakers and Amplifiers
for Fire Protective Signaling Systems
(UL1480, UL2043)
CSFM see our website
NYCMEA
580-06-E, Vol. 3
Installation/configuration notes
Mounting Considerations
The G‑SSPKCLP Speaker Strobes are for indoor
installation only. Mount them on interior ceilings or
other hard surfaces where they are protected from
weather elements such as rain or snow. The units
flush‑mount on a standard 4‑inch square by 2.125‑inch
deep back box.

2 | G-SSPK24CLPW Multi-candela Ceiling-mount Speaker Strobe (white, FIRE)
Wiring Considerations
Notice
Do not use these strobe units in coded or pulsed
signaling circuits.
Wire Diameter:
The input terminals accept solid wires with diameters
between 18 AWG and 12 AWG (ISO 0.75 mm2 and
4 mm2) or stranded wires with diameters between
18 AWG (1.2 mm) and 12 AWG (2.3 mm).
Notice
Do not use looped wire under terminals. Break the
wire run to provide supervision of connection.
Synchronization
The strobes can be synchronized by using the Gentex
AVSM Control Module, FACP’s or power supplies that
include the Gentex Synchronization Protocol.
Parts included
Quant. Component
1 Speaker Strobe
1 Hardware pack
1 Literature pack
Environmental
Temperature (operating): +32°F to +120°F (0°C to +49°C)
Mechanical
Dimensions (HxWxD): 6.1 in. x 6.1 in. x 1.88 in.
(154.9 mm x 154.9 mm x 47.8 mm)
Trademarks
All hardware and software product names used in this
document are likely to be registered trademarks and
must be treated accordingly.
Ordering information
G-SSPK24CLPW Multi-candela Ceiling-mount Speaker
Strobe (white, FIRE)
This white speaker strobe is designed to meet code
requirements for audio, visual, and voice
communications. It offers dependable evacuation
signaling and visual alarms, or a combination of both.
Order number G-SSPK24CLPW
Technical specifications
Electrical
Current , Maximum Operating (strobe)
• 15 cd: 24 VDC: 120 mA; 24 VFWR: 183 mA
• 30 cd: 24 VDC: 130 mA; 24 VFWR: 190 mA
• 75 cd: 24 VDC: 272 mA; 24 VFWR: 374 mA
• 95 cd: 24 VDC: 318 mA; 24 VFWR: 439 mA
• 115 cd: 24 VDC: 360 mA; 24 VFWR: 494 mA
Voltage
• Nominal: 24 V (DC or FWR)
• Range: 16 V to 33 V (DC or FWR)
Speaker dBA [UL typical dB at 10 ft (3 m)]
• 1/8 W: 25 V: 74.6 dBA; 70.7 V: 73.7 dBA
• 1/4 W: 25 V: 77.7 dBA; 70.7 V: 76.7 dBA
• 1/2 W: 25 V: 80.5 dBA; 70.7 V: 79.6 dBA
• 1 W: 25 V: 83.1 dBA; 70.7 V: 82.5 dBA
• 2 W: 25 V: 85.6 dBA; 70.7 V: 85.4 dBA
• 4 W: 25 V: 87.9 dBA; 70.7 V: 87.9 dBA

3 | G-SSPK24CLPW Multi-candela Ceiling-mount Speaker Strobe (white, FIRE)
Represented by:
Americas: Europe, Middle East, Africa: Asia-Pacific: China: America Latina:
Bosch Security Systems, Inc.
130 Perinton Parkway
Fairport, New York, 14450, USA
Phone: +1 800 289 0096
Fax: +1 585 223 9180
security.sales@us.bosch.com
www.boschsecurity.us
Bosch Security Systems B.V.
P.O. Box 80002
5617 BA Eindhoven, The Netherlands
Phone: + 31 40 2577 284
Fax: +31 40 2577 330
emea.securitysystems@bosch.com
www.boschsecurity.com
Robert Bosch (SEA) Pte Ltd, Security
Systems
11 Bishan Street 21
Singapore 573943
Phone: +65 6571 2808
Fax: +65 6571 2699
apr.securitysystems@bosch.com
www.boschsecurity.asia
Bosch (Shanghai) Security Systems Ltd.
201 Building, No. 333 Fuquan Road
North IBP
Changning District, Shanghai
200335 China
Phone +86 21 22181111
Fax: +86 21 22182398
www.boschsecurity.com.cn
Robert Bosch Ltda Security Systems Division
Via Anhanguera, Km 98
CEP 13065-900
Campinas, Sao Paulo, Brazil
Phone: +55 19 2103 2860
Fax: +55 19 2103 2862
latam.boschsecurity@bosch.com
www.boschsecurity.com
© Bosch Security Systems 2014 | Data subject to change without notice
2736217867 | en, V2, 15. Sep 2014