Bosch FPP-RNAC-8A-4C Specsheet

Fire Alarm Systems | FPP‑RNAC‑8A‑4C Remote Notification Appliance Circuit (RNAC) Power Supply
FPP‑RNAC‑8A‑4C Remote Notification Appliance Circuit (RNAC) Power Supply
www.boschsecurity.com
u 8 A of power
u Fully supervised outputs
Use the FPP‑RNAC‑8A‑4C power supply to add four additional notification appliance circuits to a fire alarm control panel (when connected via the option bus), or as a NAC power supply for fire-protective signaling systems (when connected directly to the NAC output). The additional notification appliance circuits can be NFPA 72, Class B (Style Y) or Class A (Style Z). This regulated power supply provides up to 8 A of power that is used to operate both continuous and intermittent loads. This 8 A of power can be distributed through the four output circuits and auxiliary power circuit. The FPP‑RNAC‑8A‑4C power supply is UL Listed for use in commercial fire alarm applications.
Functions
Compatible Control Panel Connections
The FPP‑RNAC‑8A‑4C power supply is compatible with any UL Listed control panel that uses reverse polarity supervised notification outputs with 12 VDC or 24 VDC regulated outputs. It is also compatible with the following Bosch Control Panels:
• D7022 Two‑zone Conventional FACP
• D8024 and D10024A Analog FACPs
power
u Regulated 24 VDC output (nominal) with
over‑current protection
u Built‑in NAC patterns
– For the D7022 conventional panel and the D8024
and D10024A analog panels, the FPP‑RNAC‑8A‑4C connects through a NAC circuit. No option bus connection is necessary.
• D7024 Four‑zone Addressable FACP
• DS9400i Four‑zone FACP
• DS9400M AddressiFire FACP – Connect up to two FPP‑RNAC‑8A‑4C power
supplies to a D7024, DS9400i, or DS9400M Control Panel. The control panel can individually control each of the four NAC outputs for each power supply. Only the four NAC outputs of a single power supply will be synchronized.
• FPD‑7024 or FPA‑1000 Analog Addressable Fire
Panels
– Connect up to four FPP‑RNAC‑8A‑4C power
supplies to an FPD‑7024 or an FPA‑1000 control panel. Each RNAC’s four NAC outputs will be synchronized and can be individually controlled for a total of 16 synchronized circuits.
NAC Output Patterns
The NAC circuits can be set to produce the following output patterns:
• Steady
• Temporal Code 3
2 | FPP‑RNAC‑8A‑4C Remote Notification Appliance Circuit (RNAC) Power Supply
• Pulsed
• California March
• Wheelock Synch
• Gentex Synch
• System Sensor Synch
Status Displays
There are eight local status display LEDs on the power supply's printed circuit board that show the following conditions:
• AC OK
• System Trouble
• Ground Fault
• Input Active
• Trouble Output 1, 2, 3, and 4
DIP Switch Settings
If connected to the fire alarm control panel’s option bus, the power supply needs its own option bus address. Set this address through the DIP switches. Set the DIP switches to choose:
• NAC or power supply output
• NAC Input Variable option
• AC Delay Time
Certifications and approvals
Region Certification
USA UL UOXX: Control Unit Accessories, System
(ANSI/UL 864, 9th edition) and UTRZ: Power-supply Units (UL 1481)
FM FPP-RNAC-8A-4C
CSFM see our website
FDNY-
#6101
CoA
FDNY-
#6173
CoA
Installation/configuration notes
Compatible Products
The following products are compatible with the FPP‑RNAC‑8A‑4C RNAC Power Supply:
Category Product ID Product Description
Batteries D126 12 V, 7 Ah battery
D1218
D1224
D1238
*
**
**
*
Up to two 18 Ah batteries fit in the enclosure
**
Requires BATB-40 Battery Box
12 V, 18 Ah battery
12 V, 24 Ah battery
12 V, 38 Ah battery
Magnetic Door Holders D370B Brass‑Plated
Wall‑Mount
D370C Chrome‑Plated
Wall‑Mount
D371B Brass‑Plated
Floor‑Mount
D371C Chrome‑Plated
Floor‑Mount
Four-wire Smoke
Refer to Technogram (P/N: F01U010790)
Detectors
NAC Devices Refer to Technogram (P/N: F01U010791)
Wiring
All wiring is connected to the power supply board by lift‑gate terminals that can accept up to 12 AWG (ISO 4 mm2) wire.
Parts included
Quant. Component
1 FPP‑RNAC‑8A‑4C board
1 AE4 Large Enclosure (red), vented
1 Lock set with two #1358 (D102) keys (P/N: F01U083084)
4 2.21 kΩ end‑of‑line (EOL) resistors (P/N: F01U034504)
For retrofitting applications, allowable EOL values are in the range of 1 kΩ to 20 kΩ
1 Hardware pack
Technical specifications
Environmental Considerations
Temperature (operating): +32°F to +120°F (0°C to +49°C)
Inputs (NAC)
Response Time (input to output): 10 ms maximum
Mechanical Properties
Color: Red
Dimensions (HxWxD) without door:
20.4 in. x 14.8 in. x 4.1 in. (52 cm x 38 cm x 10.4 cm)
Material: cold-rolled steel
Base: 18 gauge (1.2 mm) Cover: 19 gauge (1.1 mm)
Outputs (auxiliary)
Current (output): 850 mA maximum
Voltage (output): 24 VDC (regulated)
Outputs (NAC)
Output per circuit: 2.5 A maximum
Output (total): 8 A (all NAC and auxiliary outputs)
Voltage (output): 24 VDC (regulated)
Voltage (standby): -24 VDC (regulated)
Outputs (NAC when configured as power supply)
Compatibility range: 19.6 VDC to 27.5 VDC
Current (output): 1.3 A maximum
Loading...